66kV变电站部分电气一次设计浅析
66kV变电站一次部分设计
60kV变电站一次部分设计摘要随着工业时代的不断发展,人们对电力供应的要求越来越高,特别是供电的稳固性、可靠性和持续性。
然而电网的稳固性、可靠性和持续性往往取决于变电站的设计和配置。
由于变电所的设计内容多、范围广、逻辑性强,因此要求要有较高的专业水平,并熟悉各种设计规程和设计原理,设计过程中要针对变电所的规模和形式,具体问题具体分析。
本文是60kv/10kv降压变电所的一次变电的设计方案。
本设计包括对导线的选择,主变压器的选择,无功补偿静电电容器的选择,电气主接线的确定,短路计算,各种电气设备的选择与校验,高压配电装置的规划设计。
在设计和选择设备中都充分考虑到了可靠性,灵活性和经济性。
另外,各种断路器、隔离开关、电流互感器型号的选择要与高压配电装置的布置联系在一起考虑。
本设计是有文字说明和图表解释的比较完整的变电所的设计方案。
关键词:电力系统;电气设备;变压器;变电站The design of 60kv satellite substationAbstractWith the development of the industrial time , people have higher demand of the power supply, especially the power supply stability, reliability and consistency. However, power grid stability, reliability and durative often depends on the design and configuration of substation. As a result of substation design, a wide range of content, logic is strong, it is required to have higher professional level, and are familiar with a variety of design procedures and design principle, design process for substation the size and form, concrete analysis of concrete problems. This is the 60kv/10kv substation of a substation designThis design including the selection of conductors, the selection of main transformer, reactive power compensation capacitors, the main electrical wiring, short-circuit calculation, all kinds of electrical equipment choice and verification, the planning and design of high voltage distribution device. In the design and selection of equipment are fully taken into account the reliability, flexibility and economy. In addition, a variety of circuit breaker, isolating switch, current transformer model should be selected with the high voltage distribution device arrangement linked to consider.This design is a written instructions and diagrams explain the relatively complete substation design.Keywords power system;electrical equipment,;transformer;Transformer substation目录摘要 (I)Abstract (II)第1章绪论 ............................................................................................................ . (1)1.1 课题背景 ............................................................................................................... .1 1.2 合理设计变电站的意义.................................................................................... .1 1.3 变电站设计相关的原则和规范.. (2)第2章10kv线路导线的选择..................................................................................... ..4 2.1选择机械制造厂出线架空型号 ....................................................................... .4 第3章选择主变压器的台数、容量、型号. (9)3.1 线路损耗的总功率 (9)3.2线路所有负荷的总功率 (9)3.3计算变压器二次侧总功 (10)3.4选择变压器型号 (11)第4章补偿电容器的选择 (13)4.1计算变压器功率损耗 (13)4.2计算变压器高压侧功率 (13)4.3计算无功补偿前系统的功率因数 (13)4.4计算需要补偿的无功容量 (13)4.5选择电容器 (14)第5章电气主接线方案设计 (16)5.1主机线设计的基本要求 (16)5.2主接线方案 (17)第6章短路电流的计算 (18)6.1发生短路的原因和短路的定义 (18)6.2短路的分类 (18)6.4短路电流的计算 (18)第7章电气设备的选择 (20)7.1断路器的选择 (20)7.2隔离开关的选择 (23)7.3互感器的选择 (24)7.4避雷器的选择 (27)7.5高压开关柜的选择 (28)7.6母线的选择 (28)结论 (33)致谢 (34)参考文献 (35)附录A (36)附录B (37)第1章绪论1.1课题背景电力工业是关系国计民生的基础产业,在我国电力工业发展中,国家电网承担着优化能源资源配置,保障国家能源安全和促进国民经济发展的重要作用。
66kV变电站10kV配电线路及主变跳闸分析及整改措施
66kV变电站10kV配电线路及主变跳闸分析及整改措施发布时间:2022-01-04T07:28:35.892Z 来源:《新型城镇化》2021年23期作者:郭红[导读] 2020年1月24日9时36分,永安变10kV焦化线过流保护动作,开关跳闸,重合闸动作后,焦化线过流保护再次动作,开关跳闸不重合;焦化线过流保护第二次动作的同时,微波线过流保护动作,重合闸出口,10kV微波线重合成功;在故障时,10kV市街线出口有弧光放电现象,放电后10kV市街线A相断线,故障后,10kV母线三相电压为A相4.6kV,B:5.1kV,C:6.7kV,3U0:33V。
本文针对 66kV变电站10kV配电线路及主变跳闸进行分析。
国网鸡西供电公司黑龙江鸡西 158100摘要:2020年1月24日9时36分,永安变10kV焦化线过流保护动作,开关跳闸,重合闸动作后,焦化线过流保护再次动作,开关跳闸不重合;焦化线过流保护第二次动作的同时,微波线过流保护动作,重合闸出口,10kV微波线重合成功;在故障时,10kV市街线出口有弧光放电现象,放电后10kV市街线A相断线,故障后,10kV母线三相电压为A相4.6kV,B:5.1kV,C:6.7kV,3U0:33V。
本文针对 66kV变电站10kV配电线路及主变跳闸进行分析。
关键词:配电线路;主变跳闸;措施引言11时34分,10kV焦化线过流Ⅲ段保护动作,开关跳闸不重合(因送电合开关前,将该线路的重合闸已停用)。
11时36分,10kV微波线开关跳闸,过流Ⅲ段保护动作,重合闸动作,开关重合后过流Ⅲ段保护再次动作,开关跳闸不重合;随后依次出现1#主变66kV后备过流保护Ⅳ段动作跳开10kV分段开关,过流Ⅲ段保护动作跳开1#主变高低压侧开关;变电站10kV母线失压,1#主变停电。
一、故障原因分析1、变电站事故前运方式10kVⅠ、Ⅱ段母线并列运行,1号主变带全所负荷,2号主变在热备用状态。
试析66kV变电站电气一次设计手段的合理选择
试析66kV变电站电气一次设计手段的合理选择摘要:随着社会现代化进程的推进和发展,人们对物质生活质量的需求也不断地提高。
电气设备作为人类生活不可或缺的重要组成部分,其发展更新速度也日臻完善。
变电站占据了社会生活环境的关键地位,人们越来越重视电力设备的安全设计和经济效益。
关键词:电气一次;设计手段;合理选择一、电气主接线的设计标准1.1确保安全供电,维护电能质量电力系统运行的根本就是要安全、稳定,减少停电次数与规模,从而减少发电厂自身以及其他用电行业客户的损失,而且故障性断电还可能造成供电设备损坏、报废,社会安定受到影响等等。
这其中所带来的损失是巨大的。
所以,电气主接线的设计必须本着供电安全稳定的原则,其中要确保电压合理、频率合理、供电线路连接正确等等,只有具备这几点基本要求,才能确保电能质量,主接线必须在不同工作状态中达到这些基本标准。
1.2富于灵活性、便捷性电气主线在供电运行过程中安全、稳定的同时,也要具有一定的自由度和灵活度,例如:当电力系统出现故障时,电气设备需检修时,电气主线能够方便、灵活地被调度,能够及时转变运行方式来维持供电系统持续供电,尽量控制停电范围与时间。
1.3成本合理、经济廉价在确保供电安全、稳定、高质的前提下,主接线设计也要本着经济实惠的原则,要确保对设备的成本投入最少,所占空间最小、转移费用最低,为了控制设计成本,尽量一次性设计成功,并实施分期投资战略,这样才能有效控制成本投入量,创造良好的经济效益。
二、66kV变电站的接线设计2.166kV变电站的设计分析主接线设计是66kV变电站电气一次设计的重中之重。
鉴于变电系统的复杂性和多变性背景,因此变电站电气的一次设计必须秉承灵活性和可靠性的根本原则。
通过依据变电站终端建设规模、电力系统负荷、电气设备备用容量来进行科学化、专业化、技术化的系统设计。
整个电气系统中的各个配电装置、继电保护设备、拟定电气设备和自动控制装置的合理配置都是主接线设计中主要考虑的关键因素。
66kV变电所电气部分的设计
立题题目66kV变电所电气部分的设计题目来源□来源于生产实际□来源于科研项目☑其他题目性质□基础研究□应用研究☑应用基础研究□其他题目完成形式□毕业论文☑毕业设计申请立题教师白皓然职称副教授从事专业电力电子与电气传动立题说明:电能是一种清洁的二次能源。
由于电能不仅便于输送和分配,易于转换为其它的能源,而且便于控制、管理和调度,易于实现自动化。
电能已广泛应用于国民经济、社会生产和人民生活的各个方面。
我国的电力系统从50年代开始迅速发展。
到2010年初,电力系统装机容量,年发电量,均居世界前位。
而各种形式的发电厂是电力系统的重要组成部分,它直接影响整个电力系统的安全与经济,在我国电源结构中火电设备容量占总装机容量的75%。
由发电、变电、输电、配电和用电等环节组成的电能生产与消费系统。
它的功能是将自然界的一次能源通过发电动力装置(主要包括锅炉、汽轮机、发电机及电厂辅助生产系统等)转化成电能,再经输、变电系统及配电系统将电能供应到各负荷中心。
因此掌握和研究变电站电气部分的设计具有重要的现实意义,同时可以使学生巩固和加强对发电厂和电力系统电气设计方面的知识。
教研室意见教研室主任签名:年月日毕业论文(设计)领导工作小组意见:教学院长签名:年月日论文(设计)题目66kV变电所电气部分的设计要求完成时间2012.06.08论文(设计)内容(需明确列出研究的问题):本设计主要内容是(1)确定主接线:根据设计任务书,确定主接线(2)选择主变压器:选择变压器的容量、台数、型号等。
(3)短路电流计算:根据电气设备选择的需要,选择短路计算点,绘制等值网络图,计算短路电流。
(4)电气设备的选择:选择并校验断路器、隔离开关、电抗器、电流互感器、电压互感器、母线、电缆、避雷器等,选用设备的型号、数量汇总成设备一览表。
(5)绘制电气主接线图、平面布置图、进线间隔和出线间隔断面图,防雷保护规划示意图。
(6)应用matlab软件,通过simulink对短路电流进行仿真,输出变化波形图。
220-66kV变电站电气一次部分设计开题报告
220-66kV变电站电气一次部分设计开题报告毕业设计(论文)开题报告
学生姓名: 学号: 专业: 发电厂及电力系统设计(论文)题目:220/66kV变电站电气一次部分设计
指导教师: 赵妍
2011 年03 月18日
开题报告填写要求
1(开题报告(含“文献综述”)作为毕业设计(论文)答辩委员会对学生答辩资格审查的依据材料之一。
此报告应在指导教师指导下,由学生在毕业设计(论文)工作前期内完成,经指导教师签署意见及所在系审查后生效;
2(开题报告内容必须用黑墨水笔工整书写或按教务处统一设计的电子文档标准格式打印,禁止打印在其它纸上后剪贴,完成后应及时交给指导教师签署意见;
3(“文献综述”应按论文的格式成文,并直接书写(或打印)在本开题报告第一栏目内,学生写文献综述的参考文献应不少于10篇(不包括辞典、手册);
4(有关年月日等日期的填写,应当按照国标GB/T 7408—94《数据元和交换格式、信息交换、日期和时间表示法》规定的要求,一律用阿拉伯数字书写。
如“2002年4月26日”或“2002-04-26”。
毕业设计(论文)开题报告
毕业设计(论文)开题报告
毕业设计(论文)开题报告。
220,66变电站的设计
摘要电力工业在我国经济中占有十分重要的地位和作用,社会发展电力先行。
电力系统是将自然界的一次能源通过发电动力装置转化成电能,再经输、变电系统及配电系统将电能供应到各负荷中心。
电气设计工作是工程建设的关键工作环节,做好设计工作,对工程建设的工期、质量、投资、费用和建成投产后的运行安全,可靠性和生产的综合经济效益都起着决定性作用。
本文主要是变电站一次部分设计。
首先根据任务书上所给系统、线路及所有负荷情况,通过对负荷的分析计算及供电范围确定了主变压器的台数、容量及型号,同时也确定了站用变压器的容量及型号;其次,根据原始资料,通过对电力系统的安全、可靠、灵活、经济运行等方面的考虑,确定了220kV和66kV侧的电气主接线;最后,根据最大持续工作电流及短路电流的计算结果,对断路器、隔离开关、电压互感器、电流互感器、避雷器、导体等电气设备进行了选型,从而完成了220kV变电站电气一次部分的设计。
关键字:220kV变电站;电气一次部分设计;变压器;主接线;电气设备选择目录摘要 (1)220/66kV变电所电气部分设计说明书 (4)第1章原始资料的分析 (4)1.1 设计变电站的类型及其在电网中的地位和作用 (4)1.2 本站进线情况 (4)1.3 设计变电站负荷情况 (4)1.4 设计变电站站址的自然及环境条件 (5)第2章主变压器的选择 (6)2.1 主变台数的确定 (6)2.2 主变容量的确定 (6)2.3 主变型式选择 (7)第3章主接线方案拟定 (8)3.1设计原则(对主接线基本要求) (8)3.2各级电压等级主接线形式 (8)3.3“典设”中各级电压出线回路数的推荐值 (8)3.4设计步骤 (8)第4章短路电流计算 (11)4.1短路计算的主要目的 (11)4.2短路计算的一般规定 (11)4.3计算短路电流的计算步骤 (11)4.4短路电流水平 (12)4.5应用运算曲线计算短路电流的计算步骤 (12)第5章站用变压器及站用电接线 (14)5.1站用变压器的台数、型式及容量确定 (14)5.2站用变电源引接方式 (14)5.3站用变压器低压侧接线 (14)第6章无功补偿配置 (15)6.1概述 (15)6.2无功补偿装置类型 (15)6.3无功补偿容量的确定 (15)6.4并联电容器装置 (15)6.5并联电容器分组容量和分组数 (15)第7章电气设备选择 (16)7.1电器和导体选择的一般条件 (16)7.2电器选择的依据 (16)7.3断路器(QF) (16)7.4 隔离开关(QS) (17)7.5 电流互感器(TA) (18)7.6 电压互感器(TV) (20)7.7 避雷器(F) (20)7.8 导体选择 (21)第八章电气布置及配电布置 (23)8.1 电气设备布置 (23)8.2 配电装置布置 (23)220/66kV变电所电气部分设计计算书 (24)第9章主变压器的选择 (24)9.1 主变容量的确定: (24)第10章短路电流计算 (266)10.1 基准的选择 (266)10.2 计算各元件电抗值 (266)10.3简化等值网络 (27)10.4短路电流结果表 (31)第11章电气设备的选择 (322)11.1 断路器的选择和校验 (322)11.2 隔离开关的选择和校验 (334)第12章电压互感器的选择 (355)12.1 型式 (355)12.2 选择结果表如下 (355)第13章电流互感器的选择 (366)13.1 220kV电流互感器的选择 (366)13.2 66kV互感器的选择: (366)第14章避雷器的选择 (377)14.1 选取型号 (377)14.2 220kV侧校验 (377)14.3 66kV侧校验 (378)第15章导线的选择和校验 (399)15.1 220kV侧 (399)15.2 66kV侧 (409)参考文献 (422)致谢 (433)220/66kV变电所电气部分设计说明书第1章原始资料的分析1.1 设计变电站的类型及其在电网中的地位和作用本站为系统枢纽变电站,与水火两大电力系统联系,并为地区重要负荷供电。
内蒙兴安盟66kV降压变电所电气部分设计
内蒙兴安盟66kV降压变电所电气部分设计一、本文概述Overview of this article本文旨在详细阐述《内蒙兴安盟66kV降压变电所电气部分设计》的核心内容。
文章将简要介绍项目背景,包括内蒙兴安盟地区的电力需求、电网架构以及降压变电所建设的必要性。
随后,文章将概述设计的主要目标,包括确保变电所的安全稳定运行、提高供电效率、优化能源结构等。
This article aims to elaborate on the core content of the electrical design of the 66kV step-down substation in Xing'an League, Inner Mongolia. The article will briefly introduce the project background, including the electricity demand in the Xing'an League region of Inner Mongolia, the power grid architecture, and the necessity of constructing step-down substations. Subsequently, the article will outline the main objectives of the design, including ensuring the safe and stable operation of the substation, improving power supply efficiency, optimizing energy structure, etc.在电气部分设计方面,本文将详细分析变电所的主要电气设备选型、配置及运行方式。
具体包括变压器、断路器、隔离开关、互感器、避雷器等关键设备的选型原则、参数计算及布置方案。
66kV变电站部分电气一次设计探究
66kV变电站部分电气一次设计探究作者:孟璐璐赵婉辰李琦来源:《环球市场》2018年第04期摘要:在整个电力系统建设的过程中,变电站作为主要的设施之一,对其进行科学合理的设计是很有必要的,不过由于变电站中的电气设备设计十分的复杂,而且在对其进行设计时,来要考虑到变电站电气设计的合理性、经济性等方面的因素,为此我们在对部分电气进行设计时,就采用一次设计的方法来对其进行处理。
下面我们就对66kV变电站部分电气一次设计的相关内容进行分析。
关键词:66kV变电站;电气一次设计;作用;要点就当前对电力需求量日趋变大的情况下,相关的供电设备也需要不断的进行改良更新,从而满足各行各业在生产作业当中对电力的一个大量需求,满足人们日益上涨物质文化需求。
一、变电站一次设计的作用变电站电气一次设计的主要包括变压器、发电机、隔离开关、断路器、输电线路以及电力电缆等电气设备的设计。
变电站是在电网之间以纽带的形式以便让各个电网之间相互联系,并且利用变压器把各个等级电压的相关电网有机的联系在一起,从而能使电能进行相应的变换与分配。
发电、输电以及配电过程都是依靠变电站电气一次设备之间的相互连接而进行的。
变电站能否安全以及可靠的运行,直接关系到了整个电网是否能够安全运行。
根据相应的调查分析,变电站的主要作用是使电能在高低压之间进行科学、安全的转换。
在此过程中,有一些变电站把发电厂中的发电机出口电压进行有机的升压,这样以来,就有利于电能在进行远距离传输之时,可以降低电能在线路上的一些损耗。
另外,一些变电站把高压转变成低压,然后再传送到用户端。
66KV变电站是一种直接面对客户端的变电站,其数量较多,分布相对较为宽所以,在对该种变电站进行一次设计时,应充分考虑其经济性、可靠性以及灵活性。
因为只有通过这种方式综合比较选择,才能减少变电站在某个区域内的投资成本,灵活地应对该地区所发生的各种停电现象以及相应的电网故障,从而提高这一区域中供电的可靠性。
浅谈66KV地下变电所的设计要点
浅谈66KV地下变电所的设计要点【摘要】以市场变为例,介绍了地下变电所在设计中注意的几个问题。
【关键词】地下变电所;设计要点一、概述城市用地寸土寸金,尤其是繁华地带,用电密度日益增大,需要建立地下变电所。
66KV市场变电所为哈市中心地带建造的一座全地下无人值守变电站所。
本期设三台SF6气体绝缘有载调压变电器,每台容量为50MV A。
根据电气工艺的要求,总体为五层结构,地下一层、三层为电气设备层,层高为5.1m;地下二层、四层、五层为夹层,层高为3m。
变电所进出风口为出地面建筑。
变电所占地面积1295平方米,建筑面积6475平方米。
二、主要电气设备选择选择地下变电所的电气设备,特别要注意防燃、防爆和低噪声等。
2.1一次设备变电所三台变压器为SF6气体绝缘有载调压变压器,电压为66/11KV,容量为50MV A。
66KV高压设备为SF6绝缘的GIS组合电器。
SF6是一种惰性气体绝缘介质,是一种稳定的、五色的、不燃、无污染的绝缘气体,其密度是空气的三倍,介质强度是空气的2-3倍。
变压器及GIS组合电器均带有SF6漏气显示器,并提通过压力信号继电器把压力信号送到集控站,以便集中监视SF6的压力。
2.2直流操作电源直流操作电源采用220v密封阀控铅酸蓄电池,能保证不间断供电。
该产品具有对环境污染小,维护工作量小,运行中不需要补充电解液(即免维护)等优点。
作为直流操作、控制、信号和事故照明等不停电的直流电源之用。
2.3二次部分本变电所按无人值守设计,全所采用变电站综合自动化系统,采用系统保护一体化方式,10KV控保单元采用分散式布置。
装置面板上的液晶显示器随时都在轮流显示它所测量的所有模拟量值。
并通过站内通信网向变电站层有关设备报告,供站内监控及运动用。
采用分层分布的系统结构方式,纵向分为变电站层和间隔(或功能)层两层。
间隔层在横向按站内一次设备或特殊功能单元分布。
三、平面布置3.1由于地下工程每平方米的造价较大,在符合使用的前提下,尽量做到平面布置要紧凑,而且层高也要降低,地上部分的空间要充分利用,这样可以减少地下的开挖深度,也有利于防水的处理。
66kV变电所供电设计探讨 郭彦生
66kV变电所供电设计探讨郭彦生摘要:伴随着社会经济的飞速发展,人们在日常生活与工作中对于电力资源有着极高的需求量,需要电力企业结合本地区的实际用电情况,修建现代化的智能变电所,以此进行有效供电,确保人们用电的安全性、可靠性。
基于此本文选取某地区修建的66KV变电所为研究对象,从多方面进行了供电设计,以期为更多地区变电所供电设计工作的有效开展提供参考经验。
关键词:66KV;变电所;供电设计电力系统的稳定健康运行可以确保人们获得优质的供电服务,其中供电系统在电力系统中发挥着关键性作用,要求电力企业在进行变电站的改造设计时,重视供电系统的设计工作,选择质量性能良好的供电设备,对于供电参数进行准确计算,以此保证最终设计完成的变电站供电改造设计方案可以满足该区域人们用电的要求,可以保质保量的开展供电工作。
本文研究选择的某区域变电所主要由高压配电室、低压配电室、值班室、室内微机操控部分、变压器、电容器等组成。
某区域变电所为一级负荷,采用两回路进线,两台有载调压电力变压器同时为用户供电,可以在带负载运行条件下,自动或电动改变变压器一、二次绕组的匝数比,以保证稳定的输出电压,从而提高用电设备的工作效能和可靠性。
本变电所将66kV电压变换为10kV电压为各个用电单位供电。
1区域型变电所设备选型与建设施工1.1变电所设备选型介绍设备的选择配置应力求小型化,要保证技术先进、工作性能稳定可靠,质量有保证,且售后服务跟得上。
所内主变压器要求节能且有载调压型,一般采用S10或SZ10型变压器,S11型也在发展之列。
变压器容量要根据电力负荷情况而定,但两台主变容量比不应超过1:3,阻抗电压、变比、接线组别应相同,误差不超过±5,为以后变压器并列运行提供条件。
所用变压器采用1~2台S11—50kVA/66/0.4kV直配变,装在66kV进线外侧或66kV母线上,采用跌落熔断器控制。
高压断路器应采用SF6断路器,66kV断路器采用LW9—66型,10kV断路器采用VS1—12型。
66kV变电站部分电气一次设计浅析
66kV变电站部分电气一次设计浅析摘要:在当前人类社会发展的过程中,电能已经成为了人们生活、工作和学习中不可缺少的能源之一,因此大量发展电力行业有着十分重要的意义,这不仅可以有效的满足人们对物质生活的基本要求,还有利于整个社会经济的发展。
而在整个电力系统建设的过程中,变电站作为主要的设施之一,对其进行科学合理的设计是很有必要的,不过由于变电站中的电气设备设计十分的复杂,而且在对其进行设计时,来要考虑到变电站电气设计的合理性、经济性等方面的因素,为此我们在对部分电气进行设计时,就采用一次设计的方法来对其进行处理。
下面我们就对66kV变电站部分电气一次设计的相关内容进行分析。
关键词:66kV变电站;电气一次设计1 66kV变电站电气一次部分总体设计概述在这一个过程中,我们可以了解到对于变电站中的电气一次部分主接线而言,它主要是通过由高压电器设备通过连接线进行组成的线路,这一种线路它能够在工作中直观的反映出设备的作用、连接方式等等关系。
且电气主接线是一项能够保障供电和电能质量的重点内容,因此,我们需要让它能够满足具有可靠性、灵活性的特点。
2 66kV变电站一次设计的作用变电站电气一次设计的主要包括变压器、发电机、隔离开关、断路器、输电线路以及电力电缆等电气设备的设计。
变电站是在电网之间以纽带的形式以便让各个电网之间相互联系,并且利用变压器把各个等级电压的相关电网有机的联系在一起,从而能使电能进行相应的变换与分配。
发电、输电以及配电过程都是依靠变电站电气一次设备之间的相互连接而进行的。
变电站能否安全以及可靠的运行,直接关系到了整个电网是否能够安全运行。
根据相应的调查分析,变电站的主要作用是使电能在高低压之间进行科学、安全的转换。
在此过程中,有一些变电站把发电厂中的发电机出口电压进行有机的升压,这样以来,就有利于电能在进行远距离传输之时,可以降低电能在线路上的一些损耗。
另外,一些变电站把高压转变成低压,然后再传送到用户端。
66kv10kV变电所电气部分设计
摘要电在人们的日常生活中扮演着十分重要的角色,所以变电所的设计也就显得尤为重要。
本设计是对于德州66kV/10kV变电所的设计。
运用所学的知识,对变电所进行具体的设计。
首先根据任务书的已知数据对所给的负荷进行分析,之后确定负荷计算方案并进行负荷计算。
为了使系统中的无功功率达到要求,需要设计无功补偿方案,并对变压器进行选择。
根据实际情况确定电气主接线方式,并选择短路点进行短路计算。
通过短路计算得出的短路电流的有效值与峰值,进行电气设备的选择与校验。
在将这些工作系统设计完之后,进行电力系统继电保护的设计,根据之前求出的短路电流跟长时工作电流对变压器保护、补偿电容器保护进行设计,最后再对变电所的防雷与接地系统进行设计。
在对变电所进行设计的过程中,首先需要考虑变电所供电的可靠性,需要保证变电所遇到突发事故的时候不至于造成重大的损失。
并且要注意的是,在保证可靠性的同时,还要保证经济性,要考虑建设变电所所需投资的费用,使投资尽可能少。
关键词:电力系统;变电所;电气主接线;继电保护AbstractElectricity in People's Daily life plays a very important role, so the design of the substation is particularly important. This design for the 66 kv / 10 kv Dezhou ing the learned knowledge, for the design of specific substation.First of all, according to the specification of the known data to analyze the load, according to the known load after load calculation. In order to make the system reactive power requirements, reactive power compensation scheme needs to be designed, and choose the transformer. Choose the main electrical wiring according to actual situation,And short-circuit point selection for short circuit calculation.According to the short circuit calculation of short-circuit current RMS and peak, after choosing electric equipment and check.Will these work after the system design.For the design of power system relay protection,According to calculate short circuit current and long before the working current of the transformer protection, compensation capacitor protection design.At last, the design of lightning protection and grounding protection.In the process of design of the substation,first of all, need to consider the reliability of the substation power supply,and Need to make sure that substation meet the accident not cause significant losses.And note,In the guarantee of reliability at the same time, and to ensure the economy.then to consider the cost of the investment needed for construction of substation, make investment in as little as possible.Key words:Power system; Substation; The main electrical wiring; Relay protection目录第1章绪论 01.1 变电所的意义与分类 01.2 德州变电所的地理位置与气候 0第2章负荷计算 (2)2.1 负荷的意义 (2)2.2 负荷计算的方法 (3)2.3 负荷计算 (4)第3章无功补偿方案 (6)3.1 无功补偿的意义 (6)3.2 无功补偿器的选择 (6)3.3 系统无功功率的平衡 (8)第4章变压器台数及容量 (10)4.1 变压器的种类与特点 (10)4.2 变压器容量及数量 (11)4.3 变压器的形式与结构 (12)第5章电气主接线设计 (14)5.1 电气主接线的意义 (14)5.2 电气主接线设计的基本要求 (14)5.3 电气主接线的基本形式与特点 (15)5.4 主接线形式的选择 (18)第6章导线的选择及校验 (21)6.1 选择导线的条件 (21)6.2 导线的选择与校验 (21)第7章短路计算 (24)7.1 短路的种类与危害 (24)7.2 短路计算的意义与步骤 (25)7.3 短路计算 (26)第8章电气设备选择与校验 (29)8.1 电气设备的选择与检验条件 (29)8.2 电气设备的选择与校验 (30)第9章变压器保护与电容器保护的设计 (40)9.1 变压器的故障与不正常运行状态 (40)9.2 变压器保护的种类与意义 (40)9.3 变压器保护的设计 (41)9.4 电容器故障类型及保护方式 (46)9.5 电容器保护设计 (47)第10章防雷与接地设计 (48)10.1 雷电的危害与防雷保护的意义 (48)10.2 变电所防雷保护设计 (48)10.3 变电所接地的概念及分类 (50)10.4 接地设计的步骤 (50)10.5 变电所接地设计 (51)第11章结论 (53)参考文献 (54)致谢 (55)附录 (56)第1章绪论1.1变电所的意义与分类作为电网正常工作运行必不可少的重要组成部分,变电所的地位不可替代。
66KV变电站部分电气一次设计浅析
进行相应 的变换 与分 配。变 电站能否安 全以及可靠的运行 ,直 接关 系到 该装 置的成 本投 资较高 ,故一般不会被采 用。由于 当今城 市的用地 较为
了整个 电网是 否能 够安全 运行。
紧张 ,在 市中心或用 地较 为紧张 的地 方,一般 采用66kV断路 器布置 形
1.2变 电站 的作用
机出 口电压 进行有机 的升压 ,这 样以来 ,就 有利于 电能 在进行 远距 离传
在66KV变电站 电气一次设 计 中,首先要考虑 的是 中间变电站及 终
输 之时 ,可 以降低 电能在 线路上 的一些 损耗 。另外 ,一些变 电站把 高压 端 变 电站 。中间变 电站接 近66kV变电站 的负荷中心,且在66kV变 电站
提 供 的电力,运 行方式 比较 灵活且可靠性较 高 ,但其依 旧有一定 的不足
2.66kV变电 站 中主接 线 设计
之处 。
2.1灵活性
4.2内桥 接线方式
主接线 在设 计时应该满 足调度 、检 修以及扩建 中的灵活性 。
该 方式一般 是用在66kV变电站 中的高压主 接线 ,这种方 式的线路
66KV变电站的电气一次部分相关的设计技术进行 了分析、比较 ,并就66KV变 设备 或轻 型 电器;在 系统安 全运 行以 及继 电保护 满足相 应的要 求时 ,
电站的一次部分设计提站便可 以采 用一些简易电器。
【关 键词 】一次设计;66KV变电站 ;设计技 术
转变成低压 ,然后再传送 到用户端。
的负荷 中心 中,被分成 两路进 线 ,进而把 电能运输 给 低压客户端 ,这一
66KV变 电站 是一 种直接面 对客户端 的变 电站,其 数 量较多 ,分布 过程需要 两台主变压 器来 完成。
66KV变电站的设计
66KV变电站的设计66KV变电站的设计是电力系统中非常重要的一个环节。
变电站作为电力系统中的一个重要组成部分,承担着将高压输电线路的电能转换为低压供电线路所需的任务。
在变电站设计中,需要考虑到各种因素,包括供应可靠性、设备安全性、节能环保等等。
本文将从以下几个方面对66KV变电站的设计进行深入研究。
第一章:引言在现代社会中,电力能源的重要性不言而喻。
作为电力传输系统的重要组成部分,66KV变电站承担着电能转换、分配和传输的重要任务。
本章将阐述66KV变电站的社会价值,并介绍本文的研究目的、研究方法和研究意义。
第二章:基本原理和技术本章将深入探讨66KV变电站设计所需遵循的基本原理和技术要求。
首先,我们将介绍高压输电线路与低压供应线路之间的能量转换原理,分析其对变电站设计的影响。
能量转换原理的理解对于设计出高效、稳定的变电站至关重要。
接下来,我们将阐述设备选型原则,包括设备的性能、可靠性、经济性等方面。
正确的设备选型是保证变电站运行稳定的基础。
最后,我们将讨论各种保护措施,如过电压保护、短路保护等,以确保变电站的安全稳定运行。
这些保护措施是防止事故发生,保障电力系统正常运行的关键。
第三章:供应可靠性供应可靠性是衡量电力系统运行质量的关键指标。
本章将围绕如何提高66KV变电站供应可靠性展开讨论。
首先,我们会介绍备用设备的配置,这是保证电力系统稳定运行的重要手段。
其次,我们将探讨智能化监控系统的应用,通过实时监控系统,我们可以及时发现并处理问题,从而提高供电可靠性。
此外,本章还将讨论故障处理策略,如故障诊断、故障处理流程等。
最后,我们会探讨供电可靠性评估方法及其在66KV变电站设计中的应用,这有助于我们更好地理解和提高供电可靠性。
第四章:设备安全性设备安全性是保障66KV变电站正常运行的基础。
本章重点介绍各种设备的安全要求,如隔离开关、变压器、断路器等。
对于这些设备的选型和安装要求,本章将给出详细的规定和说明。
01-66kV变电所设计任务书
《发电厂电气部分》课程设计任务书66kV 变电所电气部分设计1、原始资料分析(1)设计变电所类型为:终端变电所,建成后向10kV 地区负荷供电。
(2)变电所的地理位置如图1-1所示:图1-1 变电所地理位置图(3)电力系统与本地连接情况①该变电所在电力系统中的地位和作用:一般性终端变电所 ②该变电所连入系统的电压等级为66kV ,进线回数为2回。
火电厂:发电机两台,MW 30=e P ,8.0cos =φ,18.0"=d X ,经线路长度km 501=L 输入变电所。
(4)电力负荷水平①变电所最大负荷作用小时数T max =4000h ,同时率∑K 取0.9; ②10kV 用户负荷资料如表1-1所示:该变电所地处半丘陵区,海拔高度为50m,无污染影响,年最高温度为40℃,年最低温度为-10℃,最热月平均温度为34℃,最热地下0.8m处土壤温度为30.4℃。
2、设计任务(1)电气主接线设计及主变压器选择(2)短路电流计算。
(3)电气设备选择及校验(4)线路及变压器的保护设计3、设计成果⑴设计说明书及计算书各一份。
⑵变电所电气主接线图一张。
(手画)4、参考文献[1] 刘介才主编 . 工厂供电设计指导 . 北京:机械工业出版社, 1998[2] 刘介才主编 . 实用供配电技术手册 .. 北京:中国水利水电出版社, 2002[3] 杨宛辉等 . 发电厂、变电所电气一次部分设计参考图册 .[4] 刘介才主编 . 工厂供用电实用手册 . 北京:机械工业出版社, 2001[5] 导体和电器选择设计技术规定 SDGJ14-86. 中国电力出版社 .[6] 水利电力部西北电力设计院编 . 电力工程电气设计手册(电气一次部分上、下) . 北京:中国电力出版社 ,1998[7] 工厂常用电气设备手册(第 2 版) . 北京:中国电力出版社, 1997[8] 熊信银主编. 发电厂电气部撰写人:王越明教研室主任:郭明良。
66kv-10kV变电所电气部分设计
摘要电在人们的日常生活中扮演着十分重要的角色,所以变电所的设计也就显得尤为重要。
本设计是对于德州66kV/10kV变电所的设计。
运用所学的知识,对变电所进行具体的设计。
首先根据任务书的已知数据对所给的负荷进行分析,之后确定负荷计算方案并进行负荷计算。
为了使系统中的无功功率达到要求,需要设计无功补偿方案,并对变压器进行选择。
根据实际情况确定电气主接线方式,并选择短路点进行短路计算。
通过短路计算得出的短路电流的有效值与峰值,进行电气设备的选择与校验。
在将这些工作系统设计完之后,进行电力系统继电保护的设计,根据之前求出的短路电流跟长时工作电流对变压器保护、补偿电容器保护进行设计,最后再对变电所的防雷与接地系统进行设计。
在对变电所进行设计的过程中,首先需要考虑变电所供电的可靠性,需要保证变电所遇到突发事故的时候不至于造成重大的损失。
并且要注意的是,在保证可靠性的同时,还要保证经济性,要考虑建设变电所所需投资的费用,使投资尽可能少。
关键词:电力系统;变电所;电气主接线;继电保护AbstractElectricity in People's Daily life plays a very important role, so the design of the substation is particularly important. This design for the 66 kv / 10 kv Dezhou ing the learned knowledge, for the design of specific substation.First of all, according to the specification of the known data to analyze the load, according to the known load after load calculation. In order to make the system reactive power requirements, reactive power compensation scheme needs to be designed, and choose the transformer. Choose the main electrical wiring according to actual situation,And short-circuit point selection for short circuit calculation.According to the short circuit calculation of short-circuit current RMS and peak, after choosing electric equipment and check.Will these work after the system design.For the design of power system relay protection,According to calculate short circuit current and long before the working current of the transformer protection, compensation capacitor protection design.At last, the design of lightning protection and grounding protection.In the process of design of the substation,first of all, need to consider the reliability of the substation power supply,and Need to make sure that substation meet the accident not cause significant losses.And note,In the guarantee of reliability at the same time, and to ensure the economy.then to consider the cost of the investment needed for construction of substation, make investment in as little as possible.Key words:Power system; Substation; The main electrical wiring; Relay protection目录第1章绪论 (1)1.1 变电所的意义与分类 (1)1.2 德州变电所的地理位置与气候 (1)第2章负荷计算 (3)2.1 负荷的意义 (3)2.2 负荷计算的方法 (4)2.3 负荷计算 (5)第3章无功补偿方案 (7)3.1 无功补偿的意义 (7)3.2 无功补偿器的选择 (7)3.3 系统无功功率的平衡 (9)第4章变压器台数及容量 (11)4.1 变压器的种类与特点 (11)4.2 变压器容量及数量 (12)4.3 变压器的形式与结构 (13)第5章电气主接线设计 (15)5.1 电气主接线的意义 (15)5.2 电气主接线设计的基本要求 (15)5.3 电气主接线的基本形式与特点 (16)5.4 主接线形式的选择 (19)第6章导线的选择及校验 (22)6.1 选择导线的条件 (22)6.2 导线的选择与校验 (22)第7章短路计算 (25)7.1 短路的种类与危害 (25)7.2 短路计算的意义与步骤 (26)7.3 短路计算 (27)第8章电气设备选择与校验 (30)8.1 电气设备的选择与检验条件 (30)8.2 电气设备的选择与校验 (31)第9章变压器保护与电容器保护的设计 (41)9.1 变压器的故障与不正常运行状态 (41)9.2 变压器保护的种类与意义 (41)9.3 变压器保护的设计 (42)9.4 电容器故障类型及保护方式 (47)9.5 电容器保护设计 (48)第10章防雷与接地设计 (49)10.1 雷电的危害与防雷保护的意义 (49)10.2 变电所防雷保护设计 (49)10.3 变电所接地的概念及分类 (51)10.4 接地设计的步骤 (51)10.5 变电所接地设计 (52)第11章结论 (55)参考文献 (56)致谢 (57)附录 (58)第1章绪论1.1变电所的意义与分类作为电网正常工作运行必不可少的重要组成部分,变电所的地位不可替代。
66KV变电站电气一次设计要点分析
66KV变电站电气一次设计要点分析作者:王勐来源:《科学导报·科学工程与电力》2019年第26期【摘要】电力行业的快速发展带动我国各行业发展迅速,同时为我国整体经济建设作出杰出贡献。
66KV变电站电气一次设备是保障电力系统正常运行的关键性设备,一次设备的安装也一直是变电站设备运行维护的重点与难点,如何提升一次设备安装施工中的安全管理水平,已经成为近年来电力生产中亟待解决的难题。
【关键词】66KV变电站;电气一次设计要点引言随着我国经济建设的快速发展,人们生活水平和生活质量的不断提高,对于电能的需求也是与日俱增。
变电站是供电环节中最为重要的部分,它主要是将电力资源的电压进行调节,然后按照不同的需求输送给用户。
变电站电压的转换以及输电等环节,都离不开变电站的电气一次设备等设施,所以这些设备的工作情况将会对变电站的正常工作产生极大的影响。
166KV变电站电气一次设备安装施工中的安全问题分析66KV变电站电气一次设备主要包括母线、断路器、变压器、隔离开关、电缆等,这些设备是保证变电站正常运行的核心部件,因此,要保证变电站的安全、稳定、高效运行,首先应提升电气一次设备的安装水平,重视设备安全管理。
对电气一次设备的安装水平的评价主要包括电气设备安装后运行的安全性、可靠性、稳定性以及规范性。
必须重视变电站电气一次设备安装施工的安全管理,才能够保证电力系统的稳定运转。
66KV变电站在日常运行过程中需要承载高电压、高电流电能的中转任务,这样特殊的工作条件也对电气一次设备的安装施工过程中的安全管理提出了极高的要求。
变电站运行的安全性与稳定性受电气设备安装水平的影响较为显著,往往安装调试水平较高的变电站,其故障率与事故率也极低。
但是变电站电气一次设备的安装是一项影响因素众多的工作,安装施工人员的行为规范、设备制造质量、安装材料质量、设备安装管理水平、设备适配与参数调整等都会影响设备安装,因此,电气一次设备的质量控制是一项复杂而又繁复的工作。
66kV变电站设计
摘要
电力系统是国民经济的重要能源部门,而变电所的设计是电力工业建设中必不可少的一个项目。由于变电所的设计内容多、范围广、逻辑性强,因此要求要有较高的专业水平,并熟悉各种设计规程和设计原理,设计过程中要针对变电所的规模和形式,具体问题具体分析。本文是对大北60kv/10kv二次降压变电所提供的设计方案,设计分为两部分。
high pressure in transformer substain,In allofthe design the equipments choice in consideration ofreliability,flexibilityand economy. Moreover,all of the circuit breaker,disconnectingswitch, electric current the choice of feeling machine model number want to go together with the decoration of giving or getting an electric shock the device with high pressure to contact to together consider with each other.
The design is a text description and a chart to explain the relatively complete secondary step-down substation design.
Key wordselectriபைடு நூலகம்al power system,electrical equipment,transformer,relay protection
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
66kV变电站部分电气一次设计浅析
【摘要】在整个电力系统运行的过程中,变电站在其中有着十分重要的意义,它不仅可以对整个电力系统的运行情况进行相应的监督管理,还有利于电力资源的输送,因此我们在对其进行设计建设的过程中,就要对整个电网系统的安全性、可靠性以及稳定性等方面因素进行考虑。
而且在66kV变电站进行设计减少的过程中,由于工作人员考虑到整个电网系统的可靠性和经济性,就采用一次设计的方法来对变电站部分电气进行科学合理的处理,以确保整个电力系统的正常运行。
本文首先通过对变电站的定义和作用进行简要的介绍,其次讨论了66kV 变电站部分电气一次设计的相关内容,以供同行参考。
【关键词】变电站;一次设计;应用分析
在当前人类社会发展的过程中,电能已经成为了人们生活、工作和学习中不可缺少的能源之一,因此大量发展电力行业有着十分重要的意义,这不仅可以有效的满足人们对物质生活的基本要求,还有利于整个社会经济的发展。
而在整个电力系统建设的过程中,变电站作为主要的设施之一,对其进行科学合理的设计是很有必要的,不过由于变电站中的电气设备设计十分的复杂,而且在对其进行设计时,来要考虑到变电站电气设计的合理性、经济性等方面的因素,为此我们在对部分电气进行设计时,就采用一次设计的方法来对其进行处理。
下面我们就对66kV变电站部分电气一次设计的相关内容进行分析。
1 变电站的概念及其作用
1.1 变电站的概念
在电力工程建设施工的过程中,所谓的变电站也就是指在整个电力系统用于电压转换和接收电能的电力设施,而且它在实际应用的过程中,人们也可以根据实际情况和相关要求,来对电能和电流进行适当的分配和控制。
因此,可以看出变电站整个电网系统主要是起到一个纽带的作用,因此我们在对其进行设计的过程中,就要对变电站的安全性和可靠性进行严格的要求,从而有效的保障整个电网系统安全稳定的运行。
这不仅有效的促进了社会经济的发展,还有效的满足了人们日常生活的基本需求。
1.2 变电站的作用
通过相关的数据统计,我们发现变电站它在实际应用的过程中,可以按照相关的规范要求,来对电流、电压进行安全有效的转化,进而满足人们的生活和生产的相关要求。
而且在电流、电压转化的过程中,变电站的应用也可以有效的降低电能的损耗,从而保障电能在远距离输送的过程中,不会出现较大的损耗问题,从而给人们的带来了一定的损失。
而所谓的66kV变电站其实就是一种用于直接对客户端供电的变电站,这种
变电站在实际应用的过程中,有着数量较多,分布较广特点,所以我们在对其进行设计的过程中,就采用一次设计的方法,这样不仅使得66kV变电站设计的可靠性和灵活性得到进一步的提高,还充分体现了变电设计的经济性特点,使得整个供电区域的电网故障问题得到了很好的经济。
从而保障了人们日常生活供电的安全性和可靠性。
而且对66kV变电站的分布点进行科学的设计,还有利于电力资源的节约,减少电力系统的运行荷载。
2 66kV变电站中主接线设计
2.1 灵活性
主接线在设计时应该满足调度、检修以及扩建中的灵活性。
2.1.1 调度
应该灵活地投入或切除变压器以及线路调配电源中的负荷满足系统,从而可以满足在一定事故中运行检修方式下的调度要求。
2.1.2 检修
能够方便地停运母线、断路器以及其他继电保护等设备,在进行相应的安全检修时,不会影响电网的运行以及用户用电。
2.1.3 扩建
能够比较方便的将接线从初期过渡到末期。
这样在连续供电或最短的停电时间内(不会产生一定影响的情况下),对其进行相应的扩建。
2.2 可靠性
电力生产的第一任务是安全可靠,所以在对66kV变电站进行主接线时,一定要保障其可靠性:在对断路器进行检修时,不会对系统以及负荷的供电产生影响;在线路或母线发生故障时,应尽量减少停电时间及停运线路的次数,同时要保证一级二级中大部分负荷供电;尽可能的不出现全站停运或停电现象。
2.3 经济性
主接线在满足灵活性以及可靠性之后,应该尽可能的做到经济性。
2.3.1 投资省
主接线应该尽可能的清晰简单,进而节省断路器以及隔离开关等一次设备;继电保护同二次回路不要过于复杂,尽可能的节省二次设备以及控制电缆;有效地限制短路的电流,有利于选择一些价廉的电气设备或轻型电器;在系统安全运
行以及继电保护满足相应的要求时,66kV及其以下的终端或分支中的变电站便可以采用一些简易电器。
2.3.2 损失电能较少
通过科学地选择主变压器的数量、种类以及容量等,这样可以降低两次变压给电能带来的损失。
2.3.3 占地面积较小
主接线在进行设计时,要尽可能的降低占地面积等。
3 选择66kV变电站电气一次设计中的高压配电装置
66kV变电站电气一次设计中的高压配电装置一般有两种布置方式,屋外布置以及屋内布置。
在这两种布置中,屋内布置有三类,分别是断路器布置、SF6全封闭的组合电器(GIS)布置以及安装普通电器的屋内装置。
这其中SF6全封闭的组合电器(GIS)布置与安装普通电器的屋内装置不管是在投资成本上还是在占地面积上特点较为相似。
虽然,SF6全封闭的组合电器(G1s)布置占地面积较小,有利于对其进行维护,但是该装置的成本投资较高,故一般不会被采用。
由于当今城市的用地较为紧张,在市中心或用地较为紧张的地方,一般采用66kV 断路器布置形式。
与此同时,屋外的布置主要有高型布置、半高型布置以及中型布置等。
4 66kV变电站电气一次设计中的接线方式
在66kV变电站电气一次设计中,首先要考虑的是中间变电站及终端变电站。
中间变电站接近66kV变电站的负荷中心,且在66kV变电站的负荷中心中,被分成两路进线,进而把电能运输给低压客户端,这一过程需要两台主变压器来完成。
终端变电站的主接线有三种:线路变压器组的接线、内桥接线以及单母线接线。
4.1 单母线接线的方式
该方式一般用于66kV变电站中的高压主接线,同时,单母线的分段接线方式一般用于66kV变电站中的低压主接线。
这种接线方式所提供的电力,运行方式比较灵活且可靠性较高,但其依旧有一定的不足之处。
4.2 内桥接线方式
该方式一般是用在66kV变电站中的高压主接线,这种方式的线路进出比较方便,但其运行方式不够灵活,供电也不可靠。
综上所述,对于66kV变电站应该进行科学、合理的设计,从而促进我国电力事业的飞速发展,满足人们日益增长的物质生活的需求。
5 结束语
由此可见,在当前我国电力行业发展的过程中,对66kV变电站部分电气进行一次设计有着十分重要的意义,这不仅满足了人们对电力资源的基本要求,还使得电网系统的经济性、灵活性以及可靠性等方面的问题得到进一步的提高。
不过,从当前我国66kV变电站一次设计的实际情况来看,其中还存在着一定的问题,因此我们还要在不断的实践过程中,对其设计方法进行改进和完善,进而推动我国电力行业的发展。
【参考文献】
[1]莫广宁.降压变电站的电气主接线选择[J].科技资讯,2011(21).
[2]杨晓青,宋传山.66KV变电站的设计浅议[J].科技风,2010(14).。