JN6-40.5接地开关使用说明书

合集下载

KYN61-40.5中说明书Microsoft Office Word 文档

KYN61-40.5中说明书Microsoft Office Word 文档

KYN61-40.5型铠装移开式交流金属封闭开关设备KYN61-40.5 type indoor a.c metal-clad enclosed switchgear配移开式ZN95-40.5(3AV3)型和SF型和FP系列六氟化硫断路器With moved ZN95-40.5(3AV3) 、SF and FP series SF6 breaker一.概述GeneralKYN61-40.5 type indoor a. c metal-clad enclosed switchgear ( abbr.Switchgear hereinafter) is a complete set of the latest indoor electric distribution equipment produced by Shenyang Haocen Electric Co., Ltd. It is applied to three-phase a.c distribution single busbar sectionalizing system with rated voltage of 40.5KV,50HZ,indoor electric distribution equipment. Becoming recognized more and more widely, it has been used in many industries such as power plant, metallurgy, and chemical industry. KYN61-40.5 comply with the standards GB/T11022-1999.GB3906-1991 and DL404-1997 .型铠装移开式交流金属封闭开关柜(以下简称开关柜)系三相交流50Hz,额定电压40.5kV的户内成套配电装置.作为发电厂.变电站及工矿企业接受和分配电能之用,对电路起到控制.保护和检测等功能,还可用于频繁操作的场所.本开关柜符合GB/T11022-1999.GB3906-1991及DL404-1997等标准.二.使用环境条件normal service condition1. Ambient temperature:Maximum +40℃~-15℃the average temperature within 24 hours ambient temperature shall not be greater than +35℃, the lowest ambient temperature shall not be smaller than -15℃环境温度: 上限+40C,且24小时内测得的平均值不超过35C,下限-15C.2. Height above sea level shall not exceed 1000m海拔高度: 海拔不超过1000m3. humidity : the average relative humidity should not exceed 90% withina day.The average relative humidity should not exceed 95% within a month.相对湿度: 日平均值不超过95%, 月平均值不超过90%.4. earthquake intensity should not be greater than 8 degrees.地震烈度: 不超过8度5.the vapor pressure should not exceed 2.2kPa within a day.The vapor pressure should not exceed 90% within a month.水蒸气压力: 日平均值不超过2.2kPa,月平均值不超过90%.三.Structure features结构特点1.The thermal shrinkage insulating material and epoxy-coatedinsulating process is used. The electrode shape is optimized. The structure of cabinet body is compact and the floor area is reduced.采用热缩绝缘材料及环氧涂覆绝缘工艺,优化电极形状,柜体结构紧凑,缩小占地面积;2. For the switch cabinet body, the high-grade cold rolled steel plate is formed by the NCsheet metal processing and then it is connected by the high –strength bolt and nut as well as riveting nut. For the surface of structural member, the plastic spraying or galvanizing process is adopted. 开关柜体选用冷轧钢板经数控钣金加工成形后通过高强度螺栓螺母和铆螺母连接而成,构件表面采用喷塑或镀锌工艺.3. it can be equipped with the homemade ZN85-40.5(3AV3) vacuum circuit breaker and French Schneider SF1 and SF2 model as well as Alston FP series of sulfur hexafluoride circuit breaker to meet the demands of different clients系列六氟化硫断路器,以满足不同用户的要求.;4. The metal partition is used to separate among every funcking 开关柜各功能小室均采用金属隔板封隔,并设有独立的压力释放通道;5. the circuit breaker and earthing switch are operated at the high voltage compartment door of closed .断路器.接地开关等操作均可在柜门关闭情况下进行,即可实现关门操作.7. all the interlocking between the main circuit breaker, the hand cart and the cubicle door are of mandatory mechanical locking means and can satisfy the requirements of five prevention.手车.断路器.接地开关和后柜门之间设有防止误操作的机械联锁装置,”五防”功能齐全,安全可靠.四. T echnical parameter技术参数1. 开关柜技术参数序号项目单位参数1 额定电压Rated voltage kV 40.52 额定频率all the interlocking between Hz 503 主母线额定电流Main busbar rated current A 1250,1600,20004 分支母线额定电流Branchal busbar rated current A 630, 1250, 1600额定1min 工频耐受电压(有效值)Rated power-frequency withstand voltage (1min)kV 相间.相对地一次间隔断口绝缘95 1155. 水平雷电冲击耐受电压(峰值)Rated lightening impulse withstand voltagekV 185 215辅助控制回路1min 工频耐受电压V 2000Rated voltage of aux. control circuit6. 额定短路开断电流kA 25 , 31.5Rated short time breaking current7 额定短路关合电流(峰值) kA 63.80Rated short time msking current8. 额定短时耐受电流(4S) kA 25, 31.5Rated short time withstand current9 额定峰值耐受电流kA 63.8Rated peak withstand current10 辅助控制回路额定电压V -110 ~220 -220Rated voltage of aux. control circuit11 防护等级IP4X for enclose 外壳Protective class隔室间.断路器门打开时IP2XIP2x for each compartment12. 外形尺寸(宽x深x高) mm 1400x2800(3000)x2800( *包括内数字为SF6手车方案) 13 重量kg 约2300weight2. ZN95-40.5(3AV3)真空断路器技术参数technical parameter ofZN95-40.5(3AV3)vacuum circuit braker序号no. 单位unit sepcification 参数1.额定电压Rated voltage kV 40.52.额定频率Rated frequency3.额定绝工频耐受电压(有效值) power withstand (rms)954.Rated insulated loevel缘水平雷电冲击耐受电压(峰值) kV 185 Rated switching (Lighting) impul s e wi t hstand voltage((peak)5.额定电流rated current A630,1250,1600,20006.额定短路开断电流kA 25, 31.5Rated short-circuit breaking current7.额定短路关合电流kA 63.80Rated short-circuit making current8.额定短时耐受电流(4S) kA 25,9.Rated short time withstand current10.额定峰值耐受电流kA 63.80Rated peak wi t hstand current11.额定电容器组开断电流 A 630Rated capacitor bank breaking current12.额定短路开断电流开断次数次20Rated short circuit breaking times13.额定操作顺序Rated operating sequence0-0.3-CO-180S-CO14.分闸时间ms 35~60Opening time15.合闸时间ms 45~100Closing time16.机械寿命次10000Mechanical life17.触头开距mm 20±2Clearance between contacts18.超行程mm 6±2Distance over travel19.触头允许磨损累积厚度mm 3Wearing for contract permitted20.平均合闸速度m/S 0.5~0.8Average closed speed21.平均分闸速度m/S 1.6~2.0 Average trip speed22.触头合闸弹跳时间ms ≤2Time of contract closed23.三相触头分闸不同期ms ≤2Non synchronous of 3-phase contacts trip24.三相触头合闸不同期ms ≤2Non synchronous of 3-phase contacts closed25.每相回路直流电阻μΩ≤50DC resistance for each circuit26.合闸状态额定触头弹簧压力N 3100±Rated contacts spring pressure at closed20027.相间中心距mm 300Center distance between phase3. FP40系列六氟化硫断路器技术参数technical parameter ofFP40series of SF6 circuit breaker绝缘水平最高工开断作电压冲击工频耐压电流耐压50Hz kAkV KVP kV1min 400 630 800 1250 1600 2000 2500 315040.5 185 95 12.5 FP4012A FP4012B FP4012C FP4012D16 FP4016B FP4016C FP4016D FP4016E20 FP4020C FP4020D FP4020E FP4020F FP4020G FP4020H25 FP4025C FP4025D FP4025E FP4025F FP4025G FP4025H31.54. 施耐德SF型六氟化硫断路器技术参数序号项目单位参数1.额定电压kV 40.52.额定绝(工频耐受电压) kV 95缘水平雷电冲击耐压(峰值) kV 1853.额定电流 A 630,1250,1600,20004.额定短路开断电流kA 25, 31.55.额定短路关合电流kA 63.806.额定短时耐受电流(3S) kA 25, 31.57.额定峰值耐受电流kA 63.808.额定电容器组开断电流 A 440, 875, 17509.额定短路开断电流开断次数次2010.额定操作顺序0-0.3-CO-180S-CO11.分闸时间ms 45±412.合闸时间ms 68±413.机械寿命次100005. LZZQJ9-35C型电流互感器技术参数额定一次电流准确级相应准确级下的额定输出额定短时耐受电流额定峰值耐受电流Rated primary current a ccuracy class rated output rated short time withstand current rated peak withstand current( A) 组合combine 0.2 0.5 10p10 10p15 10p20 (1S有效值rms)(KA) (有效值rms)(KA)30~100 0.2/10P10 15 30 50 30 20 150 lin 375lin150 0.2/10P15 15 30 50 30 20 31.5 80200 0.2/10P20 15 30 50 30 20 44.5 80300~500 0.5/10P10 15 30 50 30 20 54.5 80600~800 0.5/10P15 30 50 50 40 30 63 801000~2000 0.5/10P20 40 50 50 50 30 80 1006. LDBJ8-40.5型环氧树脂浇注全封闭触头盒式电流互感器技术参数epoxy resin casting whole sealed contacts box type CT主要技术参数;额定绝缘水平: 95/185kV表面爬距: 830 mm额定二次电流: 5A(或2A,1A)局部放电量: ≤20PC准确级次: 0.2S. 0.2. 0.5. 10P10. 10P15. 10P20额定一次电流准确级组合与相应的额定输出(VA) 额定短时耐受电流额定峰值耐受电流(A)0.2/10P10 0.5/10P10 0.2/0.5 10P10/10P10 (Is有效值)(kA) (有效值)(kA)5~300 1`0/30 20/30 10/20 20/20 150lin 375lin400~500 10/40 15/40 10/15 25/25 63 130600~800 20/50 30/50 20/30 30/30 63 1301000~1600 30/50 50/50 30/50 40/40 80 1802000~3150 40/50 50/50 40/50 50/50 100 1807. JN□-40.5/31.5型接地开关技术参数earthing switch序号名称单位参数1 额定电压kV 40.52 额定绝雷电冲击耐压(峰值) kV 95缘水平1min工频耐受电压kV 853 额定短时耐受电流(4S) kA 31.54 额定峰值耐受电流(峰值) kA 805 额定短路关合电流(峰值) kA 80五. 开关柜结构KYN61-40.5 structure1. 结构structureKYN61-40.5型金属封闭开关设备主要由柜体和断路器手车两大部分组成.柜体分为断路器室(也称手车室),母线室,电缆室和继电器仪表室等四个单独隔室.外壳防护等级为IP4X,断路器门打开时防护等级为IP2X,断路器手车由断路器和底盘车两部分构成.并具有电缆进出线.架空进出线.联络.计量.隔离及其他功能方案.The switchgear consists of a fixed body and the withdrawable parts(the handcarts), the body is of assembly type structure and is assembled by the bolts. the fixed body is divided into a busbar compartment, a CB compartment, a cable compartmentand an instrument compartment by the baffle plates. The protection grade of the enclosure is IP3X, and that of the compartment is IP2X, further more, all the metal parts reliably connect ground, and each compartment of the main circuit system has a pressure releasing passage with independent exhaust. 2. 柜体柜体是选用优质冷轧钢板或敷铝锌板经过数控钣金设备加工折弯形成,通过高强度螺栓.螺母(8.8级)或拉铆螺母组装而成.柜体各构件采用喷塑或表面镀锌工艺,这样使柜体不仅具有很高的精度,而且与同类设备相比具有重量轻,机械强度高,外形美观的特点.同时由地采用了组装式结构使零.部件通用性强.加工周期短,生产占地面积小.可以根据订货情况便捷地组织生产.Cabinet bodyThe cabinet body is made from the high-grade cold-cooled steel plate or aluminized zinc plate. It is assembled through the high-strength bolt and nut (grade 8.8) or riveted nut after the plate is machined and bent as well as formed by the NC sheet metal equipment. For every structural member of cabinet body, the plastic-spraying or surface galvanizing process is used. Therefore, the cabinet body not only has the very high height but also it can have such features as lightweight and high mechanical strength as well as beautiful appearance comparing with the similar equipment. At same time, there are such features as strong versatility, short machining period, small floor area for production of component because the assembly-type structure is adopted. The production can be organized conveniently depending on the ordering condition.1.手车室T ruck compartment2.二次插头Secondary plug3.断路器手车(ZN95或SF6) breaker truck4.二次仪表室low voltage compartment5.活门shutter6.小母线室small busbar compartment7.压力释放装置pressure release device8.架空进出线穿墙套管wall bushing9.母线室busbar compartment10.母线套管busbar bushing11.触头盒case of plug-in contracts12.带电流互感器触头盒contact box with CT13.接地开关earthing switch14.绝缘隔板insulated clapboard15.电缆接线cable connect16.电缆室cable compartment17.电流互感器CT18.接地母线earthing busbar图1. KYN61-40.5 开关柜内部结构示意图product structure1.手动储能孔2.机械计数器3.手动合闸按钮4.储能指示牌5.摇进机构孔.活门6.拉手7.断路器铭牌8.观察窗9.手车面板10.紧急跳闸钮11.横梁栓舌12.接地开关联锁杆13.活门开启装置14.分/合位置指示牌15.手动分闸按钮16.接地触头图2 ZN95-40.5真空断路器与手车面板布置图3手车手车骨架由优质钢板折弯焊接而成,根据用途手车可分为断路器手车,隔离手车,电压互感器手车和避雷器手车等,同规格手车可以互换,本开关柜为落地手车柜.手车制底盘车有丝杠螺母推进机构,超越离合器和联锁机构等.丝杠螺母推进机构可轻便地操作使手车在试验位置和工作位置之间移动,借助丝杠螺母自锁性可使手车可靠地锁定在工作位置,而防止因电动力作用引起手车窜动引发事故,超越离合器在手车移动退至试验位置和进至工作位置到位时起作用,使操作轴与丝杠自动脱离而空转,可防止超限操作损坏推进机构.T rolley1.The framework of trolley is bent and welded by the high-grade sheet steel.The trolley can be divided into the trolley of circuit breaker, separation trolley, trolley of voltage transformer and trolley of lightning arrester and so on according to the purpose. Trolley of same specification can be interchangeable. .The pushing device of trolley consists of leading screw nut pushing mechanism, overrunning clutch and interlocking mechanism and so on. The leading screw nut pushing mechanism can operate easily to make the trolley move between the testing position and working position. The elf-locking property of leading screw nut can be utilized to lock the trolley at the working position reliably and prevent the accident from play of trolley due to action of electrical force. The overrunning clutch will enable the operating shaft to separate from the lead screw automatically and the operating shaft runs idly when the trolley moves back to the testing position and advances to the working position, and thus avoid damage to the construction.4 隔室CompartmentKYN61-40.5型金属封闭开关设备设有独立的隔室,即为断路器隔室.母线室.电缆室和继电器仪表室,而且断路器室.母线室和电缆室都设有泄压通道.The individual compartment, namely, compartment of circuit breaker, bus compartment, cable compartment and compartment of relay instrument, is installed in the KYN61-40.5 metal enclosed switchgear. The pressure-relief channel is installed in the compartment of circuit breaker and bus compartmentas well as cable compartment.(1 ) 断路器室compartment of circuit breaker断路器室底部装有导轨,对手车在试验位置和工作位置间平稳运动起正确导向作用.触头盒前装有活门,上下活门在手车从实验位置移动到工作位置过程中自动打开,当手车反方向移动时自动关闭形成有效的隔离,上下活门联动检修时可锁定,可保证检修人员不会触及带电体,柜门关闭时手车可以操作;门面开有紧急分闸操作孔,在故障特别情况下可手动分闸,通过门上的观察窗可以观察到手车所处位置,断路器分合位置指示器及合闸弹簧储能状态.The guide rail is installed at the bottom of circuit breaker compartment to function as the correct guidance for the smooth operation of trolley between the testing position and working position. The valve is installed in front of the contact box. The upper and lower valve opens automatically during the process that the trolley moves to the working position from the testing position. When the trolley moves oppositely, the valve closes automatically to form the effective separation. The upper and lower valve can be locked while overhauling so that it can ensure that the maintainer will not contact the charged body. The trolley can be operated when the cabinet door is closed. The emergency switching-off operating hole is installed at the door face for manual switching off. The position where the trolley is located at and on/off position indicator of circuit breaker as well as energy-storage state ofswitching-on spring can be observed through the observation window on the door.(2) 母线室Busbar compartment主母线.分段母线.通过分支母线和触头盒固定,不需要其他绝缘子支撑,主母线为紫铜圆母线,联络母线和分支母线均为短形截面铜排,相邻柜间用母线套管隔开,能有效防止事故蔓延,同时对主母线起到辅助支撑作用,母线均采用硫化涂覆绝缘.The main bus and staged bus is fixed through the branch bus and contact box and the support from the other insulator is not necessary. The main bus and connecting bus as well as branch bus is the red copper bus. The wall sleeve is separated between adjacent cabinets so that it can prevent the accident form spreading effectively. At same time, it functions as the auxiliary support for main bus. The compound insulation technique is used for main insulation in the bus compartment to ensure the insulation reliability.(3) 电缆室Cable compartment每相可并接1~3根电缆,最多并接6根单芯电缆,将手车和可抽出式水平隔板移开后,安装检修人员就可以从正面进入柜内,可对其电流互感器.电压互感器.接地开关.避雷器等元件进行检修安装,柜底配置开缝的可拆卸式封板,方便电缆的施工.1-3 cables can be connected in parallel in every phase. Maximum 6 ingle-core cables can be connected in parallel. After the trolley is moved away, the installer and maintainer can enter into the cabinet from the front side to repairand install such elements as current transformer, voltage transformer, grounding switch and lightning arrester and so on. It is equipped with the slotted dismountable sealing plate for easy cable construction.(4) 继电器仪表室Compartment of relay instrument继电器仪表室内可安装继电保护控制元件,仪表以及特殊要求的二次设备,二次线路的辅设在线槽内并有金属盖板可使二次线与高压部分隔离.The relay protection and control element and instrument as well as secondary equipment with special requirement can be installed in the compartment of relay instrument. The small bus is located at the top of compartment of relay instrument for laying and control of small bus.六防止误操作联锁装置Interlocking device preventing false operation KYN61-40.5型金属封闭开关设备装有可靠的防误联锁装置,可满足”五防要求”KYN61-40.5 metal enclosed switchgear is equipped with reliable interlocking device preventing false operation so that it can meet the“5-pretection requirement”.1 继电器仪表室门上有明显提示标志的操作按钮或KK转换开关以及与用户之模拟图板上提示标志(如红绿翻牌) 相配合以防误合.误分断路器..There are operating button with obvious prompting sign or KK changeover switch and prompting sign on the analog drawing board from the client (e.g. red/green drawing) on the door of relay instrument compartment. They arecooperated to prevent the circuit breaker from wrong switching on and off.2. 断路器手车只有处在试验或工作位置时断路器才能进行分合闸操作,而且断路器只有处在分闸位置时手车才能从实验位置推向工作位置,或者从工作位置退到实验位置,从而可靠的防止带负荷分合隔离插头.The switching-on/off operation of circuit breaker can be done only when the trolley of circuit breaker is located at the testing position or working position. Moreover, the trolley can be pushed to the working position from the testingposition or returned back to the testing position from the working position only when the circuit breaker is located at the switching-off position. Thus, it prevents switching on and off isolating contact with charge.手车只有在实验位置接地开关才能进行合闸操作,防止带电合隔离开关.3.The switching-on operation of grounding switch can be done only when the trolley is located at the testing position to prevent switching on the grounding switch with charge.接地开关处于合闸状态,手车不能推到工作位置,防止带接地开关合闸.4.When the grounding switch is located at the switching-on state, the trolley cannot be entered into the working position to prevent switching on the grounding switch.接地开关不合则开关柜后门开不了;反之,后门不关则接地开关不能分闸,从而防止误入带电间隔.5.The rear door of switch cabinet cannot be opened if the grounding switch does not switch on. On the other hand, the grounding switch cannot switch off if the rear door is not closed. Thus, it can be prevented that the charged compartment is entered wrongly.不装接地开关的断路器柜,母线分段柜和母线设备柜等还需要相应的电磁锁(或程序锁)配合完成全部防误功能.6.For the circuit breaker cabinet and subsection cabinet of bus as well as bus contact cabinet and so on without installation of grounding switch, the corresponding electromagnetic lock (or program lock) is needed to cooperate and finish allmistake-prevention functions.手车只有在试验位置二次插件才能插入或拔出,手车在工作位置二次插件被锁定拔不出.7.The secondary plug-in unit can be inserted in or plugged out only when the trolley is located at the testing position. The secondary plug-in unit is locked at the working position and it cannot be plugged out if the trolley is located at the working position.七接地装置Earthing device1.手车与柜体间有可靠的接地装置;There is a reliable earthing devicebetween the trolley and cabinet body.2.电缆室内单独设有5X40(mm2)接地铜排,此铜排能贯穿整个排列与柜体接触良好,供直接接地元件使用,从而使整个柜都处于良好的接地状态之中..The 5×40(mm2) copper grounding bar is installed in the cable compartmentindividually. This copper bar can be through the whole arrangement and contacts with the cabinet body well. It is provided to the direct grounding element for its use. Thus, the whole cabinet is located at the good grounding state.八泄压装置pressure relief device在断路器式,母线道和电缆室设有泄压通道,各泄压盖板的一端用金属螺栓固定,另一端用塑料螺栓固定,当故障时,内部高压气体能容易地将泄压盖板冲开释放压力,以确保操作人员和开关设备安全.The pressure relief devices are equipped on the top of the circuit breaker compartment, busbar compartment and cable compartment. Incase fault arcing is occurred inside these three compartments, the special sealing ring seals the front door completely, and along with the increase of the gas pressure inside the compartment , the top mounted pressure relief metal cover plate will open automatically to release pressure and the high temperature gas to ensure operator and switchgear in safe condition.九电压显示装置charge indicator开关柜装设有监视一次回路带电状态的带电显示装置,该装置不但可以显示高压回路带电状态,而且可以与电磁锁配合实现强制闭锁手柄,从而提高产品的防护性能.The charge indicator is in talled in the switchgear to monitor the operation of the primary circuit. it consists of high sensor and indicator which are connected together by external wiring. This device is used to monitor whether the high-voltage circuit is in live. And it also can be equipped with electrical magnetic lock to ensure the front and back door not be opened when there are power on. So that operators don’t make such mistakes as close earthing switchgear in live or access the compartments in live.十防凝露措施condensation and corrosion prevention为了防止在高温度或温度变化较大的气候环境中产生凝露而带来的危害,可在断路器室和电缆室分别装设加热器,To prevent switchgear form undesirable condensation due to highhumidity or big change in climate condition, heaters could be added inside switchgear which can be controlled by humiture probe.十一操作程序operation procedures制作KYN61-40.5型金属封闭开关设备设计有保证开关柜各部分操作程序正确性的联锁,但操作人员对该型开关柜各部分的操作仍应严格按照有关操作规程和本《说明书》中的要求进行,不应在操作受阻时不加分析地进行操作,可能容易造成设备损坏甚至引起事故.Operator must operate the switchgear in accordance with the related operating procedures and this technical document. Any optional operating must be avoided and in case of trouble, any rough and forced operation without careful analysis must be avoided and otherwise damage and person injury might result.十二. 无接地开关的断路器柜的操作operation of circuit breaker panel without earthing switch1.断路器手车进入柜内;断路器手车准备由柜外推入柜内前应认真检查断路器状态是否完好,断路器是否处于分闸状态,否则应进行分闸,有无工具等杂物遗漏在手车上,确认良好后,将手车推入柜内并锁定在试验位置上,Mount with drawable circuit breaker into the panel:Before moving the withdrawable circuit breaker into the compartment, it isnecessary to check the withdrawable circuit breker wheather in good condition, wheather any part or sundries are left inside the mechanism box and compartment. Put the withdrawable circuit breaker on the transfer truck and lock it well. Push the transfer truck up to the fornt of the switchgear and lift it to a proper height. Insert the front positioning lock plate of the transfer truck into the slot of the compartment partition and lock the transfer truck and the compartment body together. Open the locking hook of the withdrawable circuit breaker and push it into the compartment smoothly and steadily and lock it well. After the locking of withdrawable circuit breaker and compartment body is confirmed, unlock and disconnect the transfer truck from the compartment body and move it away.2.手车在柜内的操作;Operation of the withdrawable circuit breaker inside the compartment:当手车在试验位置后即将二次插件插好,此时对断路器进行操作试验,若还要继续操作,首先必须将所有的柜门关闭并确认断路器处于分闸状态,然后打开推进机构操作孔挡析插入操作摇把,并以顺进针方向转动,使手车向前移动,直至超越离合器,起作用使操作轴空转,此时主回路已接通,手车已处于工作位置(热备用状态),可通过控制回路对其进行和分闸操作.若将手车从工作位置退出时,则以逆时针方向转动摇把,手车向后移动,直至超越离合器起作用使操作轴空转,手车便退至试验位置,此时主回路已断开,活门已关闭(处于冷备用状态).After the withdrawable circuit breaker is moved inside the compartment by transfer truck and the withdrawable circuit breaker is in sconnected/testing position, first insert the secondary plug of the auxiliary circuit to put withdrawable circuit breaker into ready operating status. With power connected, the testing position indicator on the low voltage compartment will light, and at that time, an electrical operating test could be made withoutconnection of the main circuit. For further operation, it must close all compartment doors, insert the keys to lock the doors and confirm the circuit breaker at its opening condition . Then insert the hand crank into the operating hole of the middle panel to turn it clockwise till the crank is obstructed obviously and hear a clear switchover sound of the auxiliary switch. In the meantime, the service position indicator on the low voltage compartment will light and then remove the hand crank. At this time, the main circuit is connected with power and the withdrawable circuit breaker is at its service position, operator can open or close the withdrawable circuit breaker via control circuit. To withdraw the withdrawable circuit breaker from its service position, it should first confirm the withdrawable circuit breaker at its opening state , insert withdrawable the circuit breaker hand crank and turn the hand crank anticlockwise till the crank is obstructed obviously and hear a clear switchover sound of the auxiliary switch. At that time, the withdrawable circuit breaker returns back its testing position, the main circuit is open completely and the shutters are closed.3. 手车退出柜外;Take the withdrawable circuit breaker out of thecompartment:首先应确认手车已处于试验位置,然后拔出二次插件并将扣锁在手车上,解除手车与柜体间的锁定,拉动手车退至柜外.In order to take the withdrawable circuit breaker out of the compartment, first it should confirm the withdrawable circuit breaker in testing position, then unplug the secondary plug of the auxiliary circuit, and lock the moving plug onto the withdrawable circuit breaker frame. Push the transfer truck up to the front of the panel.4.断路器在柜内分合闸状态的确认;Confirmation of open or close state of the circuit breaker inside the compartment:可由断路器手车面板分合闸指示牌及继电器仪表们上的合分闸指示灯两方面来判定.judgment be made according to the open and close indication plate on the withdrawable circuit breaker and open and close indicative lamps on the lowvoltage compartment.5.紧急手动分闸操作;在控制回路发生故障.断路器失去了控制电源的情况下,而且由于特殊原因必须断路器分闸,可由操作人员在柜前对断路器进行紧急分闸,严禁在正常运行情况下用手动分闸操作杆使断路器分闸.十三. 有接地开关的断路器柜的操作;Operation of Withdrawable Circuit Breaker Panel With Earthing Switch1.手车推入柜内或手车从柜内退出的操作程序与无接地开关之断路器的操作是完全相同的,固不再繁述.The operation procedures to move the withdrawable circuit breaker in and out of the compartment are as same as that for withdrawable circuitbreaker without earthing switch.2.手车在柜内操作Operation of the withdrawable circuit breaker inside the compartment欲将手车推入工作位置时,除了要遵守无接地开关之断路器柜操作11.12中的各项要求外,还应确认接地开关处于分闸状态,否则下一步操作无法完成.To move the withdrawable circuit breaker into its service position, in addition to the operation requirements as described in 11,12, it must confirm the earthing switch in its opening condition otherwise no further operation can be done.3.合分接地开关操作; Operation of earthing switch ON and OFFa)接地开关合闸操作; operation of earthing switch on首先确认手车已处于实验位置,而且电压显示装置之表示灯已完全熄灭,然后解除手车与接地开关操作轴的锁定,插入接地开关操作手柄,以顺时针方向转动270°接地开关合闸;To turn on the earthing switch, first confirm the withdrawable circuit breaker has been moved to its testing and take out the forward moving hand crank. Then insert the eathing switch operating handle to turn it 270°to turn on the earthing switch.b)接地开关分闸操作; operation of earthing switch off首先确认手车处于实验位置,而且前后门都已关闭,然后插入接地开关操作手柄,以逆时针方向转动270°接地开关分闸.To turn off the earthing switch, first confirm the withdrawable circuit breaker has been moved to its testing position and closed the doors. Then insert the searthing switch operating handle to turn it anticlockwise 270°,it will turn the earthing switch.十四. 隔离柜的操作operation of isolation truck隔离车不具备接通和开断负荷电流的能力,因此在进行隔离手车柜内操作时必须保证先将与之配合的断路器分闸后,而且通过辅助接点转换解除与之配合的隔离手车上的电气连锁,只有这时才能操作隔离手车,具体操作程序与断路器手车相同.The isolation truck is unable to connect or disconnect load current, therefore, to push or pull the truck with load is not allowed. In operation of isolation truckinside the compartment, first it must ensure related circuit breaker truck open and after the circuit breaker truck is open, it should unlock the electrical interlock between the auxiliary contact changeover and isolation truck. Only at that time, it is possible to operate the isolation truck with the specific operation procedures as same as that for withdrawable circuit breaker.The isolation truck is unabl十五. 安装installation1.安装前工作preparation for installation1.首先检查合同与开关柜型号.规格是否相同符合,无问题后方可开箱;At first, check the model and size and quantity of switch cabinet is conformed to the contract. It can be unpacked if there no problem.2.开箱后起吊时挂钩在挂在吊孔中以及搬运中,不得较大冲击力.Note that the proper force is applied and the product is lifted up and down slightly during the process of unpacking and handling as well as transportation to protect the product against the undesirable loss for damage.3.检查柜体及断路器元件等有无损坏,如发现损坏应速与厂家联络Check the cabinet body and element of the circuit breaker and so on for damage. The manufacturer shall be contracted quickly incase of any damage.4.清除脏污,尤其绝缘表面,应清扫干净.Remove the dirt especially insulating surface shall be cleaned up.5.手动使断路器分闸,同时手动储能进行合分闸,良好后进行开关柜安装.Manual switch off the circuit breaker and manual store the energy to switch on and off at same time. The switch cabinet installed after it is in good condition.安装Installation1.首先检查基础是否符合设计要求,以及本产品之基础(见图P15)要求,合格后方可安装;.At first, check if the foundation meets the design requirement and foundation requirement of this product (see the figure P15).The installation can be proceeded after it is acceptable.2.开关柜安装应将中间先搬运到基础上,而后将两侧开关柜排列好并找齐,再紧固柜间螺栓,然后固定好柜体与基础间螺栓.For the installation of switch cabinet, the intermediate cabinet shall be conveyed on the foundation at first. Afterwards, the both sides of switch cabinet are well arranged and aligned. The bolt among cabinets is tightened. Afterwards, the bolt between the cabinet body and foundation is fixed.3.当柜体排列排列整齐和坚固好,再将主母排联接端面涂上导电膏,而后安装好主母排,并紧固联接螺栓,而且母线套管应紧固,母线。

KYN -40.5(Z)技术描述

KYN  -40.5(Z)技术描述

KYN□-40.5 (Z)开关柜技术描述1、用途KYN□-40.5Z铠装式户内交流金属封闭开关设备(高压手车柜)系三相交流50HZ户内装置的金属铠装式手车柜。

可用于发电厂、变电站及工矿企业等额定电压35KV(最高运行电压40.5KV)的单母线及单母线分段电力系统中作为接受、控制和分配电能之用。

其技术性能达到IEC298《交流金属封闭开关设备和控制设备》和GB3906-1991《3-35KV交流金属封闭开关设备》标准。

具有体积小、外型美观、尺寸精度高、开断短路电流大、安装方便、检修周期长、操作维护方便、使用安全等众多优点。

2、使用条件a、安装地点:户内b、海拔高度:≤1000mc、环境温度:上限+40℃,下限-10℃d、相对湿度:日平均值不大于95%(25℃),月平均值不大于90%(25℃)e、周围空气应不受腐蚀性或可燃性气体、水蒸气等明显污染f、地震烈度:不超过8度g、无经常性的剧烈震动3、引用标准所有设备的制造、测试和安装均采用中国国家标准,同时满足相应的IEC标准,主要标准号如下:GB3906-91《3-35KV交流金属封闭开关设备》GB11022-89《高压开关设备通用技术要求》GB11032《交流无间隙金属氧化锌避雷器》GB1984-89《交流高压断路器》GB1985-89《交流高压隔离开关和接地开关》GB311.1-83和GB311.2~6~83《高电压试验技术》GB1P1《包装贮运标志》GB50171-92《电器装置安装工程盘,柜及二次回路接线施工及验收规范》GB2706《交流高压电器在长期工作时的发热》GB1207《电压互感器》GB1208《电流互感器》DL/T403-91《10~35KV户内高压真空断路器订货条件》DL/T404-97《户内交流高压开关柜订货条件》DL/T402-91《交流高压断路器订货技术条件》DL/T593-96《高压开关设备的共用订货技术条件》IEC298《交流金属封闭开关设备和控制设备》4、电气参数真空断路器基本参数5、产品结构和特点5.1 结构概述5.1.1 KYN□-40.5Z铠装式户内交流金属封闭开关柜属封闭式结构,整个结构分为柜体和手车两部分。

KYN61-40[1].5KV开关柜说明书样本

KYN61-40[1].5KV开关柜说明书样本

KYN61-40.5交流铠装移开式开关柜安装使用维护手册江苏东能电力科技有限公司目录1 概述................................................................................... 错误!未定义书签。

1.1 概要.......................................................................... 错误!未定义书签。

1.2 标准和规范.............................................................. 错误!未定义书签。

1.3 使用环境条件.......................................................... 错误!未定义书签。

2 技术参数........................................................................... 错误!未定义书签。

2.1 电气参数.................................................................. 错误!未定义书签。

2.2 外型尺寸和重量...................................................... 错误!未定义书签。

2.2.1 配VD4/VG1-40.5真空断路器...................... 错误!未定义书签。

3 KYN61-40.5的结构 ......................................................... 错误!未定义书签。

3.1 基本结构(图1) ........................................................ 错误!未定义书签。

快速接地开关操作方法

快速接地开关操作方法

快速接地开关操作方法快速接地开关是一种用于电力系统中的保护设备,其作用是在电气设备发生故障时能够迅速将故障电流导入地面,从而保护设备和人身安全。

下面我将详细介绍快速接地开关的操作方法。

首先,操作人员在进行快速接地开关操作前,应先确保自己已具备相关的知识和技能,并穿戴好必要的个人防护装备。

操作前还需要进行安全措施的检查,确保操作环境安全可靠。

操作方法如下:1. 根据电气设备的故障情况,判断是否需要进行快速接地开关操作。

通常情况下,当设备发生电气故障时,如断路器无法正常切断故障电流,就需要调用快速接地开关进行操作。

2. 先将电气设备的电源切断,并将设备排空。

然后,使用测试仪器对故障电流的大小和方向进行测量,以确保快速接地开关的正确操作。

3. 根据快速接地开关的型号和规格,选择合适的接地导线进行连接。

接地导线应具有足够的导电能力和耐高温、耐腐蚀的特性,以确保电流畅通和长期可靠使用。

4. 将接地导线的一端连接到快速接地开关的接地端子上,并将另一端连接到接地装置或地下的接地点。

需要注意的是,在连接过程中要保持接地导线的良好接触,并确保接地点与地面之间有良好的接触。

5. 当所有接地导线连接完成后,检查连接是否牢固可靠,确保没有松动或断裂的情况。

同时,还需要检查接地导线的可靠性和绝缘性能,以确保在故障发生时能够正确工作。

6. 打开快速接地开关的控制开关,使其处于接通状态。

在接通过程中,要观察开关运行是否正常,是否有异常情况发生,及时处理问题。

7. 当故障得到修复后,需要切断接地导线与快速接地开关的连接。

先关闭快速接地开关的控制开关,然后将接地导线逐一拆除。

8. 在操作完成后,要对快速接地开关进行检查和维护。

清理开关和接地导线的污垢,查看电器连接是否正常,确保设备处于良好工作状态。

以上就是快速接地开关的操作方法。

在操作过程中,要时刻注意安全,严格按照电力系统的操作规程进行操作,并与其他维护人员保持良好的沟通和协作。

KYN61-40.5(Z)型铠装移开式交流金属封闭开关柜 说明书

KYN61-40.5(Z)型铠装移开式交流金属封闭开关柜 说明书

KYN61-40.5(Z)型铠装移开式交流金属封闭开关柜使用说明书襄樊金恒电气有限公司二0一0年目 录一. 概述 (3)二. 使用环境条件 (3)三. 结构特点 (3)四. 技术参数 (4)4.1 开关柜技术参数 (4)4.2 ZN85-40.5(3AV3)真空断路器技术参数 (5)4.3 JN□-40.5/31.5型接地开关技术参数 (6)五. 开关柜结构 (6)六. 防止误操作联锁装置 (10)七. 接地装置 (11)八. 泄压装置 (11)九. 电压显示装置 (11)十. 防凝露措施 (12)十一. 无接地开关的断路器柜的操作 (12)十二. 有接地开关的断路器柜的操作 (13)十三. 隔离柜的操作 (14)十四. 设备的安装 (14)十五. 设备加电前检测 (15)十六. 操作试验 (17)十七. 日常维护 (18)十八. 包装运输与储藏 (19)十九. 随机文件及清单 (19)KYN61-40.5型铠装移开式交流金属封闭开关设备KYN61-40.5 type indoor a.c metal-clad enclosed switchgear 一. 概述型铠装移开式交流金属封闭开关柜(以下简称开关柜)系三相交流50Hz,额定电压40.5kV的户内成套配电装置。

作为发电厂.变电站及工矿企业接受和分配电能之用,对电路起到控制。

保护和检测等功能,还可用于频繁操作的场所。

本开关柜符合GB/T11022-1999.GB 3906-1991及DL404-1997等标准。

二. 使用环境条件1. 环境温度: 上限+40℃,且24小时内测得的平均值不超过35℃,下限-15℃。

2. 海拔高度: 海拔不超过1000m。

3. 相对湿度: 日平均值不超过95%, 月平均值不超过90%。

4. 地震烈度: 不超过8度。

5. 水蒸气压力: 日平均值不超过2.2kPa,月平均值不超过90%。

三. 结构特点1. 采用热缩绝缘材料及环氧涂覆绝缘工艺,优化电极形状,柜体结构紧凑,缩小占地面积;2. 开关柜体选用敷铝锌板经数控钣金加工成形后通过高强度螺栓螺母和铆螺母连接而成,构件表面采用喷塑或镀锌工艺。

KYN61型高压开关柜

KYN61型高压开关柜

使用条件
• 1.海拔高度:不超过2000米; 2.环境温度:上限为+40℃,下限为-15℃; 3.相对湿度:日平均值不大于95%;月平均 值不大于90%; 4.地震烈度:不超过8度; 5.没有火灾爆炸危险,没有剧烈震动及化学 腐蚀等严惩污秽的场所。
Байду номын сангаас
产品特点
• 1.采用热缩绝缘材料及环氧涂覆绝缘工艺,优化电极形 状,柜体结构紧凑,缩小占地面积; 2.开关柜柜体选用优质冷轧钢板经数控钣金加工成形后, 通过高强度螺栓螺母和铆螺母连接而成,构件表面采用 喷塑或镀锌工艺; 3.可配用国产ZN85-40.5(3AV3)真空断路器和法国施耐 德 SF1、SF6型及阿尔斯通FP系列六氟化硫断路器, 以满足不同用户的需求; 4.开关柜各功能小室均采用金属隔板封隔,并设有独立 的压力释放通道; 5.断路器、接地开关等操作均可在开关柜门关闭情况下 进行,即可实现关门操作; 6.开关柜的结构适应性强,主结线方案可以达到198种 以上,能满足不同用户的需要; 7.手车、断路器,接地开关和后柜门之间设有防止误操 作的机械锁装置,“五防”功能齐全,安全可靠。
符合标准
• KYN61-40.5型高压开关柜符合: • GB3906《3~35KV交流金属封闭开关设备》 • GB/TII022高压开关设备和控制设备标的共用技 术要》 • DL/404交流高压开关柜订货技术条件》 • IEC60298《额定电压1kV以上52kV及以下交流金 属封闭开关设备和控制设备》等标准。
KYN61-40.5型高压开关柜
产品概述
• KYN61-40.5型铠装移开式交流金属封闭开关设 备(以下简称KYN61-40.5型高压开关柜)其主要 特点是柜内配用ZN85-40.5型新型全绝缘真空断 路器及弹簧操动机构,柜体采用镀锌钢板组装而 成,提高了手车与柜体的配合精度,手车推进拉 出十分轻便,互换性强。 • KYN61-40.5型高压开关柜用于35kV三相交流 50Hz JN电力系统中,作为发电厂、变电气及工 矿企业的配电室接受与分配电能之用,具有控制、 保护和监测功能。

KYN□-40.5产品简介

KYN□-40.5产品简介

1 产品概述KYN□—40.5(Z)型铠装移开式金属封闭开关设备(以下简称开关柜)系40.5kV三相交流50Hz户内成套配电装置,主要用于中小型发电厂,大、中型工矿企业配电,实行电能的控制保护、监测之用。

本开关柜满足GB3906等标准要求,具有防止带负荷推拉断路器手车,防止误分、合断路器,防止接地开关处在闭合位置时关合断路器,防止误入带电隔室,防止在带电时误合接地开关的联锁功能,是一种性能优越的配电装置。

1.1 产品型号及名称KYN□—40.5(Z)型铠装移开式金属封闭开关设备1.2引用标准GB/T 11022─1999高压开关设备和控制设备标准的共用技术要求GB 1207─1997电压互感器GB 1208─1997电流互感器GB/T 16927.1─1997高压试验技术第一部分:一般试验要求GB 191─2000包装储运图示标志GB 1984─1989交流高压断路器GB 1985─1989交流高压隔离开关和接地开关GB /T 2681─1981电工成套装置中的导线颜色GB 311.1─1997 高压输变电设备的绝缘配合GB 3309─1989 高压开关设备常温下的机械试验GB 3906─1991 3~35kV交流金属封闭开关设备1.3 使用范围1.3.1 周围空气温度:-15℃~ +40℃。

1.3.2 海拔:不超过1000m。

1.3.3 湿度相对湿度:日平均值不大于95%,月平均不大于90%。

水蒸气压力:日平均值不大于2.2×10-3MPa,月平均不大于1.8×10-3MPa。

1.3.4 地震烈度不超过8度。

1.3.5周围空气没有明显地受到尘埃、烟、受腐蚀性和/或可燃性气体、蒸气或盐雾的污染。

1.3.6 无经常性的剧烈震动。

1.3.7对于特殊运行环境如:高湿度、温度变化较大的气候环境,具有II级以上污秽等,设计中应作一些特殊处理。

1.4 产品外形和重量1.4.1 产品外形( 宽×深×高):1200×2600×2500。

KYN61-40.5 铠装移开式交流金属封闭开关设备配移开式 说明书

KYN61-40.5 铠装移开式交流金属封闭开关设备配移开式 说明书

KYN61-40.5型铠装移开式交流金属封闭开关设备配移开式ZN85-40.5(3AV3)型真空断路器SF型和FP系列六氟化硫断路器KYN61-40.5铠装移开式交流金属封闭开关设备(以下简称开关柜)适用于三相交流50Hz、40.5kV单母线及单母线分段电力系统,主要应用与发电厂、变电站及工矿企业、高层建筑的变配电中作为接受和分配电能之用,并对电路起到控制、保护和检测,满足IE20698、GB3906、DL404等标准的要求。

并具备完善的“五防”功能。

1 使用条件1.1海拔高度:海拔不超过2000米;1.2环境温度:上限为+40℃,且24h下限为-15℃;1.3相对湿度:日平均值不大于95%,月平均值不大于90%;1.4地震烈度:不超过8度;1.5没有火灾爆炸危险:没有剧烈振动及化学腐蚀等严重污秽的场所。

2 特点2.1采用热缩绝缘材料及环氧涂覆的绝缘手段,优化电极形状,归体结构紧凑,缩小占地面积;2.2 开关柜柜体选用优质冷轧钢板或进口敷铝锌板经数控板金加工成型后,通过高强度螺栓螺母和铆螺母连接而成,一般构件表面采用喷塑和镀锌工艺; 2.3可配用国产ZN85-40.5(3AV3)真空断路器和法国施耐德SF1、SF2型及阿尔斯通FP系列六氟化硫断路器,以满足不同用户的要求;2.4开关柜各功能小室均采用金属板封隔,并设有独立的压力释放通道;2.5断路器、接地开关等操作均可在开关柜门关闭的情况下进行,即可实现关门操作;2.6开关柜的结构适应性强,主接线方案可以达到160种以上,能满足不同用户的需要;2.7手车、断路器,接地开关和后柜门之间设有防止误操作的机械连锁装置,“五防”功能齐全,安全可靠。

3 技术参数3.1开关柜技术参数 序 号 项 目单 位参 数 1 额定电压kV 40.5 2 额定频率Hz 50 3 主母线额定电流A 1250,1600,2000,2500 4 分支母线额定电流A 630,1250,1600,2000 相间、相对地一次隔离断口1min 工频耐受电压(有效值)95 115 雷电冲击耐受电压(峰值)kV 185 215 5 额定绝缘水平 辅助控制回路1min 工频耐受电压V 2000 6 额定短路开断电流kA 25,31.5 7 额定短路关合电流(峰值) kA63,80 8 额定短时耐受电流(4s) kA25,31.5 9 额定峰值耐受电压 kA63。

KYN61-40.5型开关柜技术规范书

KYN61-40.5型开关柜技术规范书

KYN61-40.5型开关柜技术规范书***⼯程35kV⾼压开关柜技术规范书招标⽅:******有限公司投标⽅:***有限公司设计院:**⼯程公司2012年5⽉⽬录⽬录 (1)1总则 (1)2适⽤的技术标准和规范 (1)3使⽤环境 (1)4开关柜技术参数 (2)5真空断路器技术参数 (3)6技术要求: (4)7开关柜供货设备及配置表 (7)8技术⽂件、资料和图纸 (7)9出⼚试验和验收 (8)10标志、包装、装卸、运输与储存 (10)11质量保证及售后服务 (11)1总则1.1本设备技术规范书适⽤于****************⼯程35kV⾦属铠装移开式开关柜成套设备的功能设计、结构、性能、安装和试验等⽅⾯的技术要求1.2本设备技术规范书提出的是最低限度的技术要求,并未对⼀切技术细节作出规定,也未充分引述有关标准和规范条⽂,投标⽅提供的产品应符合招标书要求和本技术规范及相关⼯业标准的优质产品。

1.3本设备技术规范书所使⽤的标准如遇与投标⽅所执⾏的标准不⼀致时,按较⾼标准执⾏。

1.4投标书中应列出与本技术规范或采⽤材料不⼀致的差异表。

2适⽤的技术标准和规范现⾏国家标准应优先执⾏,仅⽆相关国标时才采⽤相应IEC标准。

GB 1208 电流互感器GB 1207 电压互感器GB 3906 3.6kV~40.5kV交流⾦属封闭开关设备和控制设备GB 1984 交流⾼压断路器DLT 403 12kV~40.5kV⾼压真空断路器订货技术条件DLT 404 户内交流⾼压开关柜订货技术条件GB/T 8349 ⾦属封闭母线GB/T 15166.2 ⾼压交流熔断器第2部分:限流熔断器GB 4208 外壳防护等级(IP代码)以及其它相关标准以上标准按最新版本执⾏,优先采⽤国家标准及较⾼要求标准。

开关柜内所有的元器件应符合相应的国家标准。

3使⽤环境3.1外部环境条件(1)安装地点户内(2)海拔⾼度⼚房零⽶海拔⾼度为 2.5~3.4⽶左右(吴淞⾼程系)。

智通GW4-40.5(110)型说明书

智通GW4-40.5(110)型说明书
1510 1510 1560 1650
1.接线夹
2.左接线主装配 3.绝缘柱
4.左导电杆装配
5.防雨罩
6.右接线主装配 7.右导电杆装配 8.接地触指
9.接地刀闸杆 10.接地连杆
11.底座装配
12.支座装配
图 4 GW4-40.5(126)D2 单极装配
注: 1.该图为双接地型开关的单极装配; 2. 单接地型只有右侧的项 8、9、10 且右接线座带接地静触指; 3. 不接地型没有项 8、9、10 。
图 3 CS11 型手动操动机构 4﹑安装与调试
4.1 运行前的检查 4.1.1 导电部位接触面 (见图 7) 4.1.2 紧固件有无松动,保证各联结部位牢固可靠,验收项目见表 2(见下页) 4.1.3 各运动部位是否卡滞,保证各相对运动部位灵活;
4.1.4 检查操动机构,辅助开关动作是否正确,信号可靠; 4.2 操作与运行 4.2.1 对上述项目进行检查,确定各项均达到要求后方可进行操作; 4.2.2 接通电源,按合闸或分闸按钮,可实现开关的分合闸,在操作过程中, 如果遇到意外情况, 按停止按 钮,待事故处理完毕才能继续操作; 4.2.3 在无电源时,可用摇柄手动操作。
GW4-40.5 型 GW4-126 型
户外高压隔离开关 安装使用说明书
长沙智通电力设备有限公司
1﹑产品概述
1.1 概述 GW4 型系列户外交流高压隔离开关是在电力系统中无载的情况下,分合电力线路的电器设备,广
泛用于电力系统和工矿企业; 产品的各项指标符合 GB1985-1989《交流高压隔离开关和接地开关》、 DL/T593-1996 《高压开关设备的共用订货技术导则》、 DL486-1992《交流高压隔离开关订货技术 条件》的要求。 1.2 工作环境 1.2.1 海拔不超过 1000m,高原型产品不超过 3000m; 1.2.2 环境温度不低于-40℃,不高于+40℃,日温差≤32k; 1.2.3 风压不超过 700Pa(相当于风速 34m/s); 1.2.4 地震强度不超过 8 度; 1.2.5 覆冰层厚度 ≤10mm 1.2.6 污秽等级

JN22-40.5接地开关使用说明书

JN22-40.5接地开关使用说明书

JN22-40.5型户内高压接地开关概述JN22-40.5/31.5型户内高压接地开关(以下简称接地开关)系户内高压电器设备,适用于额定电压35KV,三相交流50Hz的电力系统中。

产品性能不仅符合GB1985-1989《交流高压隔离开关和接地开关》的要求,而且也符合IEC129的要求。

具有设计先进、技术性能可靠、结构简单,安装调试方便等优点。

可用于40.5kV的铠装型移开式交流金属封闭开关设备,亦可作为高压电器设备检修接地使用。

接地开关具有较高的关合能力。

接地开关与主开关、手车及柜门之间采用机械闭锁,机械能满足“五防”功能。

1、JN22-35型户内高压接地开关的使用环境1.1海拔高度不超过2000m;1.2环境温度:最高40℃,平均值不超过35℃,最低 -25℃;1.3相对湿度日平均不大于95%,月平均值不大于90%;水蒸气压力日平均值不大于2.2×103Mpa,月平均值不大于1.8×103Mpa;1.4地震烈度不超过8度;1.5周围空气没有明显的尘埃、烟雾,腐蚀性或可燃性气体,水蒸气或盐雾污染。

2、JN22-40.5型户内高压接地开关的技术参数2.1 额定电压:40.5kV2.2 最高工作电压:40.5kV2.3 4s额定短时耐受电流:31.5kA2.4 额定峰值耐受电流: 80kA2.5 关合电流: 80kA2.6 额定绝缘水平:1min工频耐压: 95kV雷电冲击耐受电压: 185kV二次回路1min工频耐压:2kV3、型号规格含义如下:4、安装尺寸外形图5、订货须知1、订货时必须注明产品型号、规格、相距、齿轮式还是拐臂式。

2、用户如对JN22-40.5型户内高压接地开关,有特殊需要时,亦可与我公司技术部门协商解决。

说明书ZCW40.5G

说明书ZCW40.5G

1 概述1.1ZCW10-40.5G/T1600-31.5敞开式组合电器是采用空气作为外绝缘SF6气体作为灭弧介质的成套组合电器。

用于三相交流的40.5kV输配电系统的控制与保护,亦可用于联络断路器及开合电容器组的场合。

适合于用地紧张的城市变电站、企业变电站、山区变电站。

该产品具有以下特点1)将断路器、隔离开关、接地开关、电流互感器、SF6电压互感器、避雷器、母线等元件有机的组合在接地的钢结构支架上,结构紧凑。

2)其所占空间只有分体式的30%-50%,具有节约用地,减少工程造价等显著特点。

3)整个间隔工厂预制,在出厂前完成装配及所有的调试并整体运输到安装现场,极大的缩短安装周期。

4)采用新一代高性能的灭弧室、SF6电压互感器、复合绝缘子避雷器,基本无维护、可靠性高5)间隔间工厂预制的自支撑母线,无须钢架和绝缘子。

6)布置灵活,可用于各种接线方式。

1.2ZCW10配用优化的自能式灭弧室,CT10-A弹簧操动机构。

1.3ZCW10执行国家标准GB1984-2003、GB11032-89、GB1985-2004,并满足国际电工委员会标准IEC62271-100:2001、IEC99-4和IEC62271-102:2002及IEC60694:2002的要求。

其内所配各其他元件均满足其各自的国标要求。

2使用环境条件2.1 本产品为户外产品,亦可用在户内。

使用环境条件见下a.海拔高度:不超过2000米。

b.环境温度:-30℃-- +40℃(特殊要求-40℃-- +40℃)。

c.相对湿度:日平均不大于95%,月平均不大于90%(25℃)。

d.风速:不大于35米/秒。

e.污秽等级Ⅳ级,瓷套爬距大于1450mm(公称爬电距离大于31mm/kV)。

f.无易燃、易爆、化学腐蚀及剧烈震动场合。

g.地震烈度:不超过8度。

h.履冰厚度不大于10mm。

3ZCW10-40.5G主要技术参数见表1:表 23.2 隔离开关参数表 33.3.1电站型表 43.3.2 电容器型表 53.4电流互感器3.4.1常规电流互感器3.4.2高精度电流互感器技术参数准确限值系数,LR型准确级为0.5级,LRD型为10P级。

KYN61-40.5安装使用说明书

KYN61-40.5安装使用说明书

1.概述XXX电气股份有限公司开发设计的KYN61-40.5型铠装移开式户内交流金属封闭开关设备(以下简称开关设备)系三相交流50Hz、35kV单母线及单母线分段系统中的户内成套配电装置。

主要用于发电厂、中小型发电机送电、工矿企事业配电及电力系统的二次变电所的受电、送电及大型高压电动机起动等,对电路具有控制、保护和监测等功能。

除广泛用于一般电力系统外,还可用于频繁操作的场所。

本开关设备满足IEC62271-200、GB3906等标准要求,具有“五防”功能要求,外壳防护等级达到IP4X,各小室间和手车室门打开时防护等级为1P2X。

开关设备可从正面进行安装调试和维护,因此它可以背靠背组成双重排列的双母线回路安装,提高了开关设备的安全性和灵活性,减少了占地面积。

开关设备配采用新型全绝缘真空断路器或六氟化硫断路器,柜体采用敷铝锌板组装结构,产品不仅外形美观,还提高了手车与柜体的配合精度,采用绝缘母线和带屏蔽的穿墙套管,优化了电极形状。

该产品是技术先进、性能稳定、使用方便、安全可靠的输配电设备。

2.产品型号含义K_YJI61-40.5/口-口额定短路开断电流(kA)额定电流(A)额定电压(kV)设计序号户内型移开式(手车式)铠装柜3.使用环境条件3.1正常使用条件:a.环境温度:上限+40℃,下限-10℃;b.海拔:不超过2000m;c.空气相对湿度:日平均值不大于95%,月平均值不大于90%;d.地震烈度:不超过8度;e.安装场所:没有火灾、爆炸危险、严重污秽、化学腐蚀及剧烈振动的户内场所。

3.2特殊工作条件:超过规定的%常使用环境条件时,由用户和制造厂协商。

为防止凝露现象,开关设备设有加热器。

当开关设备处于备用状态时,即应投入使用,即使在正常运行中,也应注意投用。

开关设备的散热可通过附加的通风设施来解决。

4.技术参数4.1开关设备的技术数据(见表1)。

4.3VYK2-40.5固封式真空断路器机械特性参数(见表3)KYK61-40.5开关设备的内部结构及外形见图Io图1开关设备结构按其组成可分为柜体、手车两大部分。

KYN61-40.5KV开关柜说明书

KYN61-40.5KV开关柜说明书

KYN61-40.5交流铠装移开式开关柜安装使用维护手册KYN61-40.5 metal-clad withdrawable switchgearinstruction manual江苏长江电器股份有限公司JIANGSU CHANGJIANG ELECTRIC CO., LTD.目录1 1.1 1.2 1.32 2.1 2.23 3.1 3.2 3.3 3.44 4.1 4.2 4.3 4.4 概述概要标准和规范使用环境条件技术参数电气参数外型尺寸和重量结构和柜体固定点基本结构外壳和分隔手车室联锁/防止误操作运输及存放运输条件包装运输交货和中途存储页码4444445677771919202020目录77.17.27.37.3.17.3.27.3.37.47.4.17.4.2维护目的一般要求检查与维护检查维护检修测试测试断路器抽出式单元测试联锁功能页码282828292929303030305 5.1 5.2 5.2.1 5.3 5.4 5.56 6.1 6.1.1 6.1.2 6.2 6.2.1 6.2.2 6.2.3 现场安装现场要求安装基础形式结构参数柜体装配接地安装后的检查操作投入使用准备工作启动操作开关配VD4断路器的可移开单元断路器接地开关212121222324242525262727272828*本材料所提供的信息仅供参考,如有更改,恕不另行通知版权所有。

禁止将本说明书的相关资料提供给第三者。

数据和图解未经许可不得更改。

江苏长江电器股份有限公司Contents1 1.1 1.2 1.32 2.1 2.23 3.1 3.2 3.3 3.44 4.1 4.2 4.3 4.45 5.1 5.2 5.2.1 5.3 5.4 5.56 6.1 6.1.1 6.1.2 6.2 6.2.1 6.2.2 6.2.3 SummaryGeneralStandards and specificationsService conditionsTechnical dataElectrical dataOutline dimension and weightPowerbloc KYN61-40.5 structureBasic structureEnclosure and partitionsCircuit-breaker CompartmentsInterlock/protectionagainst mis-operationTransport and storageCondition on deliverPackagingTransportDelivery and intermediate storageAssemmbly of the switchgear at siteGeneral requirements at siteFoundation frameStructrual dataAssembly of the switchgear panelsEarthing the switchgearConcluding installation workOperation of the switchgearCommissioningPreparatory workStart-upSwitching operationsWithdrawable circuit-breaker partCircuit-breakerEarthing switchPage4444445677771919202020212121222324242525262727272828Contents77.17.27.37.3.17.3.27.3.37.47.4.17.4.2MaintenanceAimGeneral requiresInspection and servicingInspectionServicingRepairTestTests on withdrawable Parts withcircuit-breakersTesting of interlock conditions*The data and illustrations arewithout engagement .Subject to change without notice.Page28282829292930303030We reserve all rights to this publication. Misuse, particularly including duplication and making available of this manual or-extracts-to third parties is prohibited. The information supplied is without liability. Subject to alternation.JIANGSU CHANGJIANG ELECTRIC CO.,LTD.1 概述Summary1.1 概要General●KYN61-40.5是一种高品质的并已通过型式试验认证的空气绝缘开关柜(以下简称开关柜)。

KYN61-40.5高压开关柜技术要求

KYN61-40.5高压开关柜技术要求

精心整理KYN61-40.5高压开关柜技术要求本技术要求主要对设备中柜体及元器件进行技术约定及品牌选择范围进行界定,请投标人仔细阅读,按要求编制投标文件,图纸与本技术说明有冲突部分,则以招标答疑方式提出解决。

一、高压总开关柜技术要求。

1、投标人提供的设备必须符合国家产品质量要求,适用于交流35(40.5)kV,频率50Hz电力系统,完整的成套开关柜设备,在符合使用环境条件情况下,接通电源即能运行;2、高压开关柜型式:KYN61-40.5型移开式高压开关柜;3、高压开关柜的尺寸:由投标人结合图纸和标准提供。

4、生产和验收应符合以下标准4.1高压开关柜设备的设计、制造、试验和包装除满足本规定外,尚需符合有关国家标准和电力行业标准及其引用标准(包括这些标准的修正内容且不限于下列标准),若标准之间出现矛盾时,以高标准为准。

选用标准应为签订合同时的最新版本。

GB3906-20063.6kV~40.5kV交流金属封闭开关设备和控制设备IEC60298额定电压1kV以上50kV及以下交流金属封闭开关设备和控制设备DL/T404-1997户内交流高压开关柜订货技术条件SD3180-1989高压开关柜闭锁装置技术条件GB/T11022-1999高压开关设备和控制设备标准的通用技术要求GB1985-2004交流高压隔离开关和接地开关GB15166.2-2008交流高压熔断器限流式熔断器GB1207-2006电磁式电压互感器GB1208-2006电流互感器GB16847-1997保护用电流互感器暂态特性技术要求DL/T403-200012kV~40.5kV高压真空断路器订货技术条件JB/T3855-2008高压交流真空断路器GB1984-2003高压交流断路器GB311.2-2013绝缘配合第2部分:使用导则GB/T762-2002标准电流等级GB11032-2010交流无间隙金属氧化物避雷器以上所引用技术标准均应按现行标准执行。

高压接地开关安全操作规程及保养模版

高压接地开关安全操作规程及保养模版

高压接地开关安全操作规程及保养模版第一章总则第一条为了保证高压接地开关的安全操作和使用,保障人员安全和设备的正常运行,制定本操作规程。

第二条本规程适用于高压接地开关的安全操作和保养工作。

第三条高压接地开关的操作人员必须熟悉高压设备的工作原理,具备一定的电气技术知识和操作经验。

第四条高压接地开关的操作人员必须参加过相关培训,持有相应的操作证书,做到熟练掌握操作技能。

第五条所有操作人员必须严格按照本规程的要求操作,不得随意变更操作顺序和方式,牢记安全第一的原则。

第六条高压接地开关的保养工作必须按照设备制造商的要求和要点进行,保证设备的正常运行和使用寿命。

第二章操作规程第一节操作前准备工作第七条操作人员必须佩戴符合要求的个人防护装备,如绝缘手套、绝缘鞋、绝缘胶鞋等。

第八条操作人员必须检查设备的工作环境,确保无其他危险因素存在,如有必要,需要设置警示标识。

第九条操作人员必须检查设备的电气接地是否良好,确认无漏电现象存在。

第十条操作人员必须检查设备的电源是否正常,确认电压和频率符合要求。

第十一条操作人员必须熟悉设备的操作界面和操作按钮,确保能正确操作。

第二节操作流程第十二条操作人员必须按照设备的启动和停止流程进行操作,确保操作正确。

第十三条操作人员必须掌握设备的运行状态,及时处理设备的异常情况,确保设备的安全运行。

第十四条操作人员必须按照设备的操作要求进行定期巡视,对设备进行检查和维护,确保设备的正常工作。

第十五条操作人员必须按照设备的要求,对设备进行隔离、停电、拆卸等操作,确保设备的安全运行。

第十六条操作人员必须按照设备的要求,对设备的故障进行诊断和处理,确保设备的正常运行。

第十七条操作时间结束后,操作人员必须对设备进行归档,记录操作时间、操作内容和问题解决情况。

第三节操作安全第十八条操作人员必须遵守设备操作标准和规定,不得随意增加设备负荷和操作频率。

第十九条操作人员必须保持设备周围的整洁和清洁,防止杂物和灰尘对设备的磨损和影响。

(6)KYN --40.5安装使用说明书-10

(6)KYN  --40.5安装使用说明书-10

1.概述1.1 产品特点kYN □--40.5铠装式金属封闭开关设备(以下简称开关柜)是西安高压电器研究所与有关生产厂家近期共同研制开发的新产品,其主要特点是柜架按金属封闭铠装移开式结构设计,柜内配用新型全绝缘真空断路器或六氟化硫断路器。

柜体采用组装结构,使产品具有外形美观,提高了手车与柜体的配合精度,能迅速组织生产、装配,及时交货,提高装配所需占地面积的利用率,易于形成批量生产等优点。

可实现闭门操作。

开关柜的各项正常操作,包括断路器分合闸,断路器手车推到工作位置和退出到试验/隔离位置,以及接地开关的分合闸,都能在高压隔室门关闭条件下进行。

本产品符合GB3906-91《3~35kV 交流金属封闭开关设备》及IEC-298 《1~52kV 交流金属封闭开关设备和控制设备》标准。

1.2 用途和使用范围该产品使用于40.5kV 三相交流50Hz 电力系统中,做为发电厂、变电所及工矿企业的配电室接受与分配电能之用;对电路具有控制、保护和监测等功能。

除广泛用于一般电力系统外,还可使用于频繁操作的场所。

使用环境条件按GB3906《3—35KV 交流金属封闭开关设备》所规定的正常使用条件。

1.3型号含义 描 写日 期 签 字底图总号旧底图总号描 校资 料 来 源 提出部门 批准文号日 期 编制 校对 标准化审定批准 签 字 更改文件号 处数 标记 第1页共 9 页 KYN -40.5交流金属封闭开关设备安装使用说明书 OXG.412.110 西 安高压电器研究所K Y N □--40.5□/□--□□□□----环境特征------操作方式--------设计序号---------额定开断电流-------------额定电流--------------断路器种类------------------额定电压 (千伏)------------------------设计序号--------------------------使用条件 户内----------------------------结构特征:移开式(手车式) ------------------------------产品名称(金属铠装式)1.4正常使用环境条件a. 环境温度:上限 +40 C下限 –10 C;b. 海拔高度不超过1000米;c. 空气相对湿度:日平均值不大于95% ,月平均值不大于90% ; d .地震烈度不超过8度; e .不适用于有腐蚀性或可燃性气体、水蒸气等明显污染的场所。

KYN61-40.5产品说明书(新)资料

KYN61-40.5产品说明书(新)资料

KYN61-40.5产品说明书(新)资料华核电气股份有限公司KYN61-40.5 户内交流金属铠装移开式开关设备华核电气股份有限公司1.KYN61-40.5型交流金属铠装移开式开关设备(后简称开关设备),系三相交流50Hz、额定电压40.5KV的户内成套配电装置。

主要应用于发电厂、变电所及工矿企事业、高层建筑的配电中作为接受和分配电能之用,并对电路实行控制、保护和监测。

满足GB3906、DL/T404等标准要求,并具备完整的“五防”功能。

型号含义2. 性能指标GB3906 《3.6kV~40.5kV 交流金属封闭开关设备和控制设备》GB/T 11022 《高压开关设备和控制设备标准的共用技术要求》IEC 60298 《3.6kV~40.5kV 交流金属封闭开关设备和控制设备》DL/T404 《3.6KV~40.5KV交流金属封闭开关设备和控制设备》3. 使用环境条件3.1正常使用条件(1) 海拔高度:不超过1000m;(2) 环境温度:额定电压kV40.5+40℃,且24h内侧得的平均值不超过35℃,12 额定电流 A 1250、1600、2000、25003 额定频率Hz 504 额定短时耐受电流kA 25 31.55 额定峰值耐受电流kA 63 806 额定短路持续时间s 47 额定绝缘水平1min工频耐受电压(有效值)kV相间、相对地:95隔离断口:115 雷电冲击耐受电压(峰值)kV相间、相对地:185隔离断口:2158 辅助回路1min工频耐压kV 29 主回路电阻μΩ≤8510 防护等级外壳:IP4X 内部:IP2X11 开关设备外形mm 1400x2800x2600(宽x深x高)5.2真空断路器主要技术参数:序号名称单位数值1 额定电压kV 40.52 额定绝缘水平1min工频耐受电压(有效值)kV 953 雷电冲击耐受电压(峰值)kV 1854 额定频率Hz 505 额定电流 A 1250、1600、2000、25006 额定短路开断电流kA 25 31.57 额定短路关合电流kA 63 808 额定短时耐受电流kA 25 31.59 额定峰值耐受电流kA 63 8010 额定短路持续时间s 411 额定操作顺序O-0.3s-CO-180s-CO12 合闸时间ms 50-10013 分闸时间ms 35-6014 回路电阻uΩ2500A≤45 1600-2000A≤60 1250A≤8015 开断时间ms ≤8016 额定短路电流开断次数次2017 额定操作电压V -110(~110);-220(~220)18 机械寿命次100006. 开关设备结构介绍6.1开关设备的基本结构开关设备按GB3906《3.6KV~40.5kV 交流金属封闭开关设备和控制设备》IEC 62271-200《高压开关设备和控制设备》标准而设计。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

JN6-40.5型户内35kV高压接地开关的概述及说明
JN6-40.5户内高压接地开关(以下简称接地开关)系户内高压电器设备,适用于额定电压35KV,三相交流50Hz的电力系统中,作为高压电器设备在检修时可靠地接地,以保障设备和维护人员的安全。

其操作方式为齿轮式操作。

一、 JN6-35型户内齿轮式高压接地开关的使用环境
1.1海拔高度不超过2000m;
1.2环境温度:最高40℃,平均值不超过35℃,最低 -25℃;
1.3相对湿度日平均不大于95%,月平均值不大于90%;水蒸气压力日平均值不大于
2.2×103Mpa,月平均值不大于1.8×103Mpa;
1.4地震烈度不超过8度;
1.5周围空气没有明显的尘埃、烟雾,腐蚀性或可燃性气体,水蒸气或盐雾污染。

二、JN6-40.5型户内高压接地开关的技术参数
2.1 额定电压: 40.5kV
2.2 最高工作电压: 40.5kV
2.3 4s额定短时耐受电流:20kA、 25kA、 31.5kA
2.4 额定峰值耐受电流: 50kA、 63kA、 80kA
2.5 关合电流: 50kA 、 60kA
2.6 额定绝缘水平:1min工频耐压: 95kV
雷电冲击耐受电压: 185kV
二次回路1min工频耐压:2kV
三、型号规格含义如下:
四、结构及工作原理
JN6-40.5、JN12-40.5接地开关由底架、触刀,电压显示装置绝缘子、合闸弹簧、触头及三相短路连接铜排组成。

JN6-35型户内高压接地开关的底架,由弯板和角钢焊接而成,端梁上有供主轴转动的圆孔,触刀安装在主轴上,靠合闸弹簧驱动转轴,带动触头合闸,关合短路电流。

电压显示装置绝缘子安装在底架上,电压显示装置绝缘子上装有触头,拐臂式为T型触头和触指,齿轮式为L型触头。

分、合闸时,只要操作手柄转动与主轴相连的传动轴,弹簧过死点后靠弹簧力加速合闸,合闸后主轴与操作轴连接拐臂成死点。

所以关合短路电路,动、热稳定电流试验时,触刀不会打开。

五、JN6-40.5型户内高压接地开关的安装与调试
本开关适用于各种安装方式,安装应对开关用机构进行检查证实完好无损时方可安装。

1 安装前的检查及准备工作。

1.1 开箱后,检查产品备品备件及随附的技术文件是否齐全,检查产品在运输、保管中是否由损伤。

1.2 检查铭牌数据与订货是否一致。

1.3 清除产品上的污物、仔细擦拭绝缘子底架上的接地部位表面。

1.4 在触刀的接触部位和机构的转动部位边涂工业凡士林。

2 安装
2.1 将接地开关用四个M22(齿轮式)、M16(拐臂式)的螺栓紧固在所要固定
的基座上。

2.2 检查和调整每个单相的触头接触情况,保证要求三分之二以上的视在接触面。

2.3 检查三相触头合闸情况,其三相刚合位置不同期性不大于3mm。

2.4 用手合、分闸五次,动作应正常。

3 接地开关的外形及安装尺寸见下图:齿轮式操作。

六、订货须知
1 订货时必须注明产品型号、规格、相距、齿轮式还是拐臂式。

2 用户如对JN6-40.5型户内高压接地开关,有特殊需要时,亦可与我公司技术部门协商解决。

相关文档
最新文档