5 Other Important Items 其他重要项目
No 序号
Item 项目
Actual Status 现有状况
Item 名称Summer Tem 夏季温度(℃)Humidity 湿度Winter Tem 冬季
温度(℃)
Humidity 湿度
Fresh Air 新风量
系统
Exhaust Air 排风系统
Public Areas, Offices &B.O.H. 公共区域,办公室和后台区
23
50%2140% 3.6m3/h.m2
无特殊要求,根据规范设为1.5次/h
Retail Spaces,
SnackBars & Pantries 零售店, 甜点吧和操作间2350%2140% 5.4m3/h.m2
Restaurants &
FunctionRooms 餐厅和会议室
2250%
2240%
7.2m3/h.m2 6 air changes per hour.
Bars, Ballroom &Ballroom Lobby
酒吧, 宴会厅和宴会厅前厅
2250%2240%
9m3/h.m2
Guestroom 客房
2350%2240%120m3/h.rm
Exhaust 102m3/hour through bathroom.
Guest Room Corridors 客房走廊2350%2140% 2 air changes per hour.
Public Toilet 公共卫生间2350%2140%12 air changes per hour.
Kitchen 厨房
≤29℃
≥20℃
无特殊要求,据规范设为10次/h
20次/h
Laundry and Valet 洗衣房
≤29℃≥20℃
15 to 60 air changes per hour of total exhaust air,according to the area.
Hilton Hotels Main MEP Requirements 希尔顿酒店机电设施要求要点
1 AV and Smoke Exhauting System 空调和防排烟系统
2 Water and Fire-fighting System 给排水和消防系统
3 Electricity System 强电系统
4 Security, BMS, Accounting, CCTV, Dimming System etc.弱电系统HILTON 要求
Parameter 参数的采用
1 AV and Smoke Exhauting System 空调和防排烟系统
1
No序号Item项目Actual Status 现有状况HILTON 要求
Swimming Pool 游泳池≤30℃
60%
≥24℃
60%
Variable with potential for 100% fresh air.
M&E Plant and
Equipment Room
机电设备房
≤38℃≥20℃7.2m3/h.m215-20次/h
Team Showers, Toilets
and Locker Rooms 员
工淋浴间,卫生间和更衣

≤25℃≥21℃12 air changes per hour.
Team Dinning Room
员工餐厅
≤25℃≥21℃ 5.4m3/h.m2
Computer Room
电脑房
≤22℃≥21℃ 1.8/h.m2
2Cold and Hot Source 冷热源设置
3A/C System 空调系统
4Ventilation System 通风系统
5Smoke Ventilation 防排
烟系统
1. The refrigeration plant shall consist of at least 3 machines, each rated at 50% of the peak design load. Stand-by capacity
extends to circulating pumps, and other auxiliaries. 2. Provide A/C including cold and hot during transition period. 3. Spare boiler
should be provided to ensure full continuity of heat outputs during periods of CHP failure or maintenance.
1. 制冷机、冷却塔要有一台备用;冷冻、冷却水泵均须有一台备用。

2. 过渡季节有同时供冷、供热要求,过渡季节应保证提供空调冷、热水。

3. 备用锅炉要能满足所有热水和采暖的负荷。

4. 冷冻水和冷却水要进行水处理.
Provide staircase pressurisation/ventilation and smoke extract systems to comply with NFPA code 101-92 A, 92B and 204 local
fire regulations. 楼梯间加压送风和排烟系统符合NFPA和中国规范.
1. 4 pipe system. For guestroom, F.C.U AND frshe air intake. For public area such as ballroom, meeting rooms, restaurants etc.
AHU with VAV system will be used. 2. Humidity provided by steam or electrical heating. 3. Provide steam for Kitchen and
Laundry. 4. Toilet areas shall be provided with their dedicated supply and extract systems. The extract system shall have duty /
stand by fans with auto-change over facility. 5. The kitchen extract system shall have duty / standby fans with auto changeover.
6.The fitness center HVAC system must have 100 percent makeup air capability. 1.空调水系统应采用四管制系
统,客房采用四管制风机盘管加新风系统。

对于客人公共区,如宴会厅、会议厅、餐厅等,空调系统的设计采用因室内温度的要求
而自动改变风量的空调系统(VAV)。

2.加湿应采用蒸汽或电热加湿。

3.洗衣房及厨房提供蒸汽系统.4.卫生间排气采用集中排气,
每处两台排风机相互切换,互为备用。

5.厨房通风机应考虑故障备用,并能自动切换。

6. 健身房HVAC系统必须能提供100%补风能
力。

7、客房采用风机盘管加新风式系统,新风通过风管直接送入客房. 8、客房层走道设置新风,电梯休息厅可以设置风机盘管。

9. 所有风盘要安装过滤器.
1. Kitchen ventilation need to be advised by Kitchen Consultant.
2. There are range hood exhaust, general kitchen exhaust and
dishwashing exhaust. 3. Provide only metallic ductwork. Avoid internal duct liner on all supply air ductwork. Where internal liner is
required for acoustical purposes, use Armacell Armaflex duct liner or sound traps to obtain noise reduction only, and use bare
metallic ductwork for the remainder. Cleaning access doors for air duct shall be at every change of direction and every 5 meters
of straight run. 4. Kitchen extract system requires access doors at every 3 meters.. 5. The range hood exhaust ducts are to be
fabricated of stainless steel. 7. Volume control dampers shall be provided to allow the system to be effectively
balanced/commissioned. Duct access doors shall be provided to all fire dampers, volume control dampers, duct mounted control
items and for cleaning purposes.
1.厨房通风需与厨房顾问协商。

2.厨房需提供厨房排油烟系统、全面排风系统、洗碗间排风系统。

3. 只能使用铁皮风道, 避免在送风
管道内使用衬垫.空调风道直管道每5米设清洗门, 每个转弯处设清洗门. 4.厨房排烟管道每3米设清洗口.5.厨房烟罩排油烟风道用不朽钢材
No 序号Item 项目Actual Status 现有状况
HILTON 要求
6
Noise and Vibration Control 噪音、减振控制
7控制系统
8AHU room 风柜机房
9
Split A/C Installation(OP)
分体空调安装(OP)
No 序号
Item 项目Actual Status 现有状况
A 1
Water consumption standard 用水量标准
2
Water quality
requirement 供水水质、
及硬度
3
Hot water supply
teperature 热水供水温度
4
Water supply and Water
tank storage 供水及生
活水箱储水量
5
Water supply pressure 供水压力6
Pipe material 水管材质
Provide digital thermostat with back-lit LCD digital display of space temperature, fan mode, temperature set point, and on/off
indication, and connect to RCU system. Thermostat shall have the capacity of passive infrared occupancy sensor, space humidity control, and wirelesss interface with building artomation system 。

安装数字式液晶温控器, 能显示风机模式,温度设定和开关状态并和房控系统. 冷冻站, 风柜, 室外灯光, 锅炉房等接入楼宇自控系统。

Design Standard 设计标准
1. Two manin pipe water supply.
2. The water supply to the hotel, including storage, must be adequate for both the daily total
water requirement and the instantaneous peaks. The water supply must be reliable with a proven history of continuous supply. 3.
Adequate 2 compartment / or 2 tank water storage facility must be provided.
1. 两路供水.
2. 至少存储24h 酒店用水量.
3. 必须采用2个水箱储备.
Noise standards:主要房间 噪音标准Guestroom 客房 30NC
Meeting room 会议室 40NC
Coffeeshop/Restaurant 咖啡厅/餐厅 40NC Reception/SPA 接待处/SPA 40NC Office 办公室 45NC BOH 后勤区 45NC Lobby 大堂 40NC
Hot water is generated and started at: 60℃ 供水温度:60℃
Minimum pressure at any outlet 140 Kpa (20 psig)
Maximum pressure at any outlet 520 Kpa (75 psig) 最小出口压力:0.14Kpa
最大出口压力:0.52Kpa
Shall have water supplying and drainage pipe. Floor are water proof.要有给水管和排水管道, 地面防水.
2 Water and Fire-fighting System 给排水和消防系统
All water in the hotel must be potable water and conforms to the world Health Organisation standards(latest edition). For laundry
equipment, kitchen dish and glass washers, and boiler feed, water has zero hardness and a minimum PH of 6.9. 供水水质需满足
饮用水要求并达到WHO 标准(最新版本), 对于锅炉房、洗衣房、厨房洗碗机、洗杯机用水, 硬度要求为零硬度, PH 值不得小于6.9.
The average consumption per guest night is between .50M3 - 1.4M3 per guest night. 冷水平均用水定额为0.50m3-1.40吨/人.天。

Copper, to ensure quiet operation and to prevent water hammer, shock absorbing devices are installed as required. 铜管.保证无噪音运转、防止水锤发生,根据需要安装防晃动设施.
HILTON 要求
puter room.
2.Power substation room.
3.Elevator room.
4.PABX room.
5.CATV room.
TV and Fire Control Center.
7.All
cold dish rooms,chocalate room, pastry room. 8.Garbage room.
1.电脑房
2.配电房
3.电梯机房
4.交换机房
5.电视机房
6.监控中心.
7.所有冷菜间,巧克力房,裱花间.
8.垃圾房
No序号Item项目Actual Status 现有状况HILTON 要求
7Fire fighting water supplying standard 消防用水标准
B
1Domestic water supply system 冷水供水系统
2Hot water supply and return system 热水供、回水系统
3Foul water drainage 排水系统
4Rainwater system 雨水系统
5Waste water system中水系统
6Sprinkler system 自动喷淋系统
7Fire hydrant system 室内消火栓系统
8Foam extinguish system 气体灭火系统
9Movable extinguish
system
灭火器的配置系统
1. Install pipework fittings and accessories to ensure that appliances drain quickly, quietly and completely at all times without
nuisance. 2. Soil vent pipes are to be installed to terminate 450mm above finished roof level and be complete with a copper wire
balloon. 3. At no time should cleanouts in drainage system be spaced at intervals greater than 15.4m. 4. Avoid condensate
drainage direct connections to drainage system. 5. Drainage within suspended ceilings are to be manufactured in cast iron. 6.
Traps shall retain a water seal of not less than 25mm water gauge.
1.排水系统应保障立管内迅速排水及房间内的安静。

2.通气管超出屋面最少450mm,顶部设置铜丝球。

3.清扫口间距不大于15.4m。

4.冷凝水避免直接接入污水管。

5.室内立管吊顶内管线采用铸铁管.
6. 设置水封时,水封深度不小于25mm。

1、Fire-fighting system must be installed according to local rule and regulation and NFPA. 消防系统必须符合当地防火规章,并应
满足NFPA 相关标准。

1. Install pipework fittings and accessories to ensure that appliances drain quickly, quietly and completely at all times without
nuisance. 2. Drainage within suspended ceilings are to be manufactured in cast iron. 3. The system shall be designed so that it
can be adequatedly tested, cleaned and maintained.
1. 排水系统应保障立管内迅速排水及房间内的安静。

2. 雨水立管及吊顶内管线采用铸铁管。

3. 系统设计要能方便调试,清理和维修。

1. Cooking equipment and appliances in kitchen.
2. Computer and PABX room.
3. Shall be connected with Fire Control Centre
and gas valve so that can cut off gas supply when fire happens.
1. 厨房烟罩(Ansul).
2.电脑房和交换机房(FM-200).
3. 要和消防控制中心,燃气电动阀相连接以保证发生火情时能够关闭燃气.
1. Reliable, supply consistently.
2. Water flow rate is 1.85m/s Maximum. 1.系统可靠,满足瞬时流量,保障连续供给。

2. 给水流速不得大于1.85m/s,特殊设备可修正此参数。

1. Reliable, supply consistently.
2. Return water flow rate is 0.5m/s maximum.
3. Thermostatic valve should be installed for
shower area of bathroom.4. Provide electromagnatic scal inhibitors in the flow connection to each plate heat exchanger.1.系统可
靠,满足瞬时流量,保障连续供给。

2.回水流速不得大于0.5m/s. 3.客房内卫生间淋浴混合阀要有温度控制器.4.热水系统要安装除垢
仪.
In most cases recyled water can be used economically for road cleaning and irrigation and cooling tower.中水用作冲洗道路、灌
溉, 冷却塔补水等用。

1. It confirms to NFPA and local codes take precedence.
2. In fire control room, display pump status of opreation, malfunction and
automode. 3. Sprinkler head is flush type in all guest area. 1. 以当
地规范为优先,并应满足NFPA相关标准 2.所有喷淋泵和辅助泵必须在消防控制室有运转、错误及自动模式的状态显示
3. 所有客用区的喷头用隐藏式的.
4. 柴油发电机房和锅炉房采用水喷雾系统.
System design 系统设计
1. It confirms to NFPA and local codes take precedence.
2. In fire control room, display pump status of opreation, malfunction and
automode.
1. 必须符合当地防火规范,并应满足NFPA相关标准。

2. 所有消防泵和辅助泵必须在消防控制室有运转、错误及自动模式的状态显示。

Type, size, quantity and location as applicable to area to comply with local and fire regulations.
灭火器的型号, 数量和位置要符合中国的消防规范.
No 序号Item 项目Actual Status 现有状况
HILTON 要求
10
Pool system 泳池系统
11
Gas system 燃气系统
12
Pipe materail 管材
13
Cold and hot water accounting system 冷热水系统计量
No 序号
Item 项目
Actual Status 现有状况
1Power supply 系统供电2Transformer 变压器选型
3
Power correction factor 无功补偿
1. Location of meter 设置水表的区域:
(1) Pool 泳池 (2) SPA (3)Night Club and KTV 夜总会和KTV (4) Beauty Salon 美容美发(5) BAR 酒吧 (6) Make-up water for cooling tower 冷却塔补水(7) Make-up water for chillers 冷机补水(8) Kitchen 厨房(9) Laundry 洗衣房(10)Locker 更衣间(11) Guestroom 客房(12)Make-up water for hot water system 热水补水 2. Meter need to be connected to BMS. 计量表要求连接到BMS 系统
HILTON 要求
3 Electricity System 强电系统
At least 2 source electricity feeder which each can take 100% load.最少两路电源输入; 每一路能带所有负荷.
Transformers shall be sized with 20% spare capacity.至少有20%备用容量
Gas leakage detecting system shall be connected with Fire Control Centre and gas valve so that can cut off gas supply when gas leakage happens. 厨房燃气泄漏报警系统与消防控制中心和燃气电动阀相连以保证发生泄漏时能够安全关闭燃气系统.Domestic hot/cold water pipe: copper or stainless steel 生活冷热水管: 铜管Underground water pipe: cast iron pipe 埋地冷水管:铸铁管Fire-fighting pipe: steel pipe 消防管道:钢管Gas pipe: steel or copper 燃气管:钢管或铜管
Pool, fountain and irrigation: PVC 泳池、喷泉、灌溉:PVC Drainage pipe: cast iron 排水管:铸铁管Rainwater pipe: cast iron 雨水管:铸铁管
Kitchen Hood and exhaust duct: 厨房排油烟管道为不朽钢.
1. Suggest adverse current type.
2. Shall be designed by pool consultant.
3. Provide an automatic drain blockage relief or pump shutdown device on pool equipment.
4. Provide an emergency equipment shut-off switch/button located adjacent to the whyirlpool that will shut off all jet pumps/blower & re-circulationg pumps.
5. An approved ground fault circuit interrupter shall be installed on electrical circuits providing power to the pool equipement, lighting and electrical outlets in the immediate vicinity of the pool.
1. 建议采用逆流式.
2. 由专业泳池公司设计.
3. 提供排水管道堵塞水泵自动停止设施.
4.在冲浪池近处安装能切断所有冲浪池所有设备的紧急按钮.
5. 所有设备,灯具和插座要有安全的接地保护.
Automatic stepped power factor correction of 0.95 lagging or better shall be provided.补偿容量使功率因数cos Φ ≥0.95。

No 序号Item 项目Actual Status 现有状况
HILTON 要求4
Emergency power(Back-up generator)应急电源(备用发电机)
5
Electricity meter 电能计量6
Emergency lighting 应急照明
7UPS 电源
8
Electricity distribution in guestrooms and ballroom
客房和宴会厅配电
No 序号
Item 项目
Actual Status 现有状况
Entrance ceiling down and down light inside bathroom is emergency light connecting with EPS, when door open, the light will turn on by magnetic system; A/C shall be controlled by Room Control Unit system; There should be 2 electrical line controlling corridor light. At least 100kw spare switch for big performance in Ballroom.
客房入口处廊灯为应急灯连接EPS 电源, 当开门时,廊灯通过门磁开关点亮; 客房空调的控制可由房控系统来控制; 客房走廊和天花上的灯具应由两个供电回路供电。

宴会厅要有至少100kw 的备用开关以备大型演出等用.
IT 系统提供至少4小时的不间断电源
In the event of a mains failure, the gensets shall start within 15 seconds. The engine shall be sized for required rating,shall be continuously rated and shall include 25% overload capacity. The genset shall be provided with a day storage fuel tank, capable of supplying the generator with fuel for min24 hours continnuous run. Back-up gensets should provide power for Fire-fighting and Life Safety system , guest lifts and kitchen refrigeration when power off. Mainly include following: 1. Guestlifts. 2. All firehydrants and sprinkler system(pumps and jockey pumps). 3. Smoke dectector and alarming system. 4. PABX. 5. Kitchen lighting, cooling rooms and refrigerators. 6. Generator power. 7. Sump pumps and sewer lift station. 8.Sewage treatment plant. 9. Dometic hot and cold water distribution pumps. 10. All pressurized equipment and smoke exhausting equipment. puter room including Air Conditioning Split unit, IT and UPS. 12. CCTV system. 13. Emergency broadcasting and lighting system. 14. Car park entry/exit barrier system. 15. Major communication system 100% lighting provided area: 1. Fire Control Centre. 2. PABX. 3. Computer Room. 4.Front Desk. 5. Power substation. 6.Power distribution room. 7. Generator room. 8. Fire fighting Pumps room.
9. Smoke exhaust and pressurization room. 10. Chiller room. 11. Boiler room. 12. Domestic Pump Room. 13. Magic Center.
14.Lift room.15.Staircase. 16.Fire lift foyer. 在市电发生故障时,发电机能在15秒内自动起动供电. 发电机能够容许有25%的超载功能. 有储存24小时用的油箱.自启动备用发电机在市电全停
和紧急状态时保障全部消防和生命安全系统用电、客梯、厨房照明及冷库等重要负荷。

主要包括以下:动力部分:
1. 客梯.
2. 所有消防栓和喷淋系统(水泵,稳压泵).
3. 烟感和报警系统
4. 程控交换机
5. 所有冷库和冰箱.
6. 所有污水泵和消防电梯集水坑水泵
7. 中水处理站
8.生活供水泵(包括冷热水).
9.所有消防加压送风和排烟风机. 10. 电脑房,电脑房分体空调电源,IT 系统和UPS. 11. 保安监控系统.12. 消防广播. 13. 停车场的道闸系统. 14. 主要通讯系统.
照明部分:100%照明部分:1.消防控制室.2.交换机房.3.电脑房4.总服务台.5.变配电房.6.配电间.7.发电机房.8.消防水泵房.9.防排烟机房.10制冷机房.11.锅炉房.12.生活水泵房.13.总机房(服务中心).14.电梯机房.15.楼梯间. 16.消防前室. 17.出口指示和疏散指示.30%照明部分:1.走廊.2.大厅.
15%照明部分:1.餐厅.2.宴会厅/多功能厅,厨房和洗衣房以及其它公共区域.
4 Security, BMS, Accounting, CCTV, Dimming System etc.弱电系统
HILTON 要求
Emergency and standby lighting provision shall be provided by a static inverter central battery system(EPS). Duration of
autonomy to be minimum 3 hours. Emergency lighting system to be monitored and shall be controlled by BMS. Areas shall be 100% lit of emergency lighting : 1. Fire Control Centre. 2. PABX. 3. Computer Room. 4. Front Desk. 5. Power substation. 6.Power distribution room. 7. Generator room. 8. Fire fighting Pumps room. 9. Smoke exhaust and pressurization room. 10. Chiller room.11. Boiler room. 12. Domestic Pump Room. 13. Magic Center. 14.Lift room.15.Staircase. 16.Fire lift foyer. 17.Exit and evacuation indicator.
1.应急照明电源为EPS ,持续至少3h ,应急照明应由BMS 系统监控。

应急照明达到正常照明(100%)照度的区域::1.消防控制室.
2..交换机房.
3.电脑房
4.总服务台.
5.变配电房.
6.配电间
7.发电机房.
8.消防水泵房.
9.防排烟机房.10制冷机房.11.锅炉房.12.生活水泵房.13.总机房(服务中心).14. 电梯机房.15.楼梯间. 16.消防前室. 17.出口指示和疏散指示. Meter shall be installed in different location and linked to BMS. See attached format.对不同的区域进行计量并接入BMS 系统. 详见附表.
No序号Item项目Actual Status 现有状况HILTON 要求
1BMS
楼宇控制系统
2RCU 房控系统
3Energy accounting system
能源计量系统
4
(A)CCTV system 监控系统
(B)Safety alarming system 保安报警系统
(C)Door maganet and patrol system
门禁、巡更系统
5 CATV system
有线电视及卫星电视系统
6Car park control system 停车场管理系统
7Fire alarming system
火灾自动报警系统
Security system安全系统
Provision areas: Front desk, safe deposit room, casher points, swimming pool etc. Panic bar and maganetic alarming at
emergency exit.
在酒店前台、贵重物品存放处、收银处、游泳池等处需设置相关紧急报警装置。

在紧急疏散出口设逃生锁及门磁报警。

To provide an automatic car park control system entry and exit to the car park, payment and car park capacity.
要提供车场自动管理系统,负责车辆进、出和车场付费以及车位的信息。

Metering electricity, water, gas and steam and connecting with BMS.
对电、水、气、蒸汽等能源消耗进行计量并与BMS相连.
To control the temperature and equipment operation inside guestroom and receiving inputs from the Property management
system(Fidelio or OnQ) to automatically control the the temperature setpoint dependant on occupancy within the guestrooms. The
system shall be accessed via the check in/out desk.
Provision of patrol: all entrance and exit, staircase and corridor etc. Maganetic door: safe deposit room, general cashier etc. 在所
有出入口、楼梯走道等处设置巡更系统。

在如大堂贵重物品室、总出纳室等处设置门禁系统。

Cover: Main entrance(include staff entrance0, car park, forecourt,lift lobby, lift cabin, guest corridor,front dest,restaurant,bar,wine
and spirit store,important dry store,pool,gymnasium,SPA,loading bay,safe adn safe deposit rooms,cash points,general
cashier,luggage room,power substation,generator,firehydrant room,domestic pump room,hotel perimeter; Backup storage devices
shall be capable of storing 30 days continual recording data.
主要包括酒店主要出入口(包括员工出入口),停车场,室外庭院,电梯厅,电梯轿厢,客房走廊,前台,餐厅,酒吧,红酒和白酒库房,重要干货
仓库,游泳池,健身房,SPA,卸货区,贵重物品存放处,收银点, 总出纳室,行李房, 配电房,发电机房, 消防泵房,生活泵房, 锅炉房, 制冷机房,
电梯机房. 通向屋顶的通道.酒店外围等区域;中心设备能够存储30天的记录.
The equipment must be comprised fo Underwriters Laboratory approved equipment and devices. Strobe notification appliances
shall be provided. A manual fire alarm pull station capable of sounding a general alarm must be located behind the front desk.
The panel must not be located in the back wall facing the registration desk. Guestroom and each livable space of a suite shall be
equipped with smoke detectors which shall be hard-wired and locally annuciated(within each room)
客房内采用带蜂鸣器底座的烟感器;在残疾人专用客房内需设置声光报警设备及警铃设备。

应安装火灾自动报警副盘在总机房
(MAGIC CENTER).
Cover: all guestrooms, restaurants, private room, lobby bar, bar, nightclub and KTV, executive lounge, swimming pool,
gymnasium, SPA and Sauna private room, meeting rooms, team relaxation room, team restaurant etc.在所有客房, 餐厅, 餐厅包
房, 大堂吧, 酒吧, 夜总会和KTV, 行政酒廊, 游泳池, 健身房, SPA 和桑拿包房, 会议室内, 员工活动室内, 员工餐厅等提供电视点位.
The system shall include air handling units, external and flood lighting, energy accounting system, chillers, boilers, pumps,
cooling towers and elevators. 楼宇系统应包括风柜, 室外灯光和泛光照明, 能源计量系统, 制冷机, 锅炉, 泵, 污水泵, 污水坑水位, 水
箱水位, 冷却塔和电梯. 此系统应放在配电房值班室(工程部值班室), 当有故障信号时应伴有声音报警.
No序号Item项目Actual Status 现有状况HILTON 要求
8Emergency broadcasting and background music system
应急广播与背景音乐广播系统
9Dim Lighting智能照明
10Signal boosting system 手机信号增强系统
11Walk-talkie and paging system
酒店无线对讲系统及内部传呼系统
12Room Control Units System
酒店客房控制系统
No序号Item项目Actual Status 现有状况1Laundry 洗衣房
2Kitchen厨房
3Linen chute
污衣井道
Dimming system shall be installed in Lobby, Lobby Bar, Restaurants, Function rooms, Ballroom, Nightclub, Bar, Executive
Lounge, SPA and Sauna.
酒店大堂, 大堂吧, 所有餐厅, 会议室, 宴会厅, 夜总会, 酒吧, 行政酒廊, SPA和桑拿等采用智能照明控制和调光系统.
HILTON 要求
The floor is to be designed to accommodate a live load of 250lbs.per sq.ft.(1220 kilograms per Meter Square) Isolated slabs are
strongly recommended. Line chute termination must clear a five-foot high(1.5m) cart. Provide at least one small machine of 50-75
pound capacity in each hotel. Size dryers to process 40% or greater of the wash load. Ironer will process 60-70% of the wash
load. Ironer must be able to process 2.9mx3.2m sheets. Provide an independent mechanically refrigerated HVAC system for the
laundry. Provide exhaust canopy over all ironers. Provide water softening for laundry if domestice water supply exceeds five
grains of hardness. A minimum light level of eight(800 foot-candles,(861 lux) measured at 36''(900mm) above finished floor, must
be provided in the laundry. The central air compressor plant is to consist of at least 2 compressors. Provide 80-100 psi(5.5-
7.0bar) compressed air to washer/extractors, large dryers and folders as required. The air intake from the compressors is to draw
air from a cool area other than the machine room. Provide a tough drain under th centerline of the washers at least 14 inches
wide(0.3m) and 18 inches deep(0.4m). Hot water shall be supplied to washer/extractor at 165''F(74C).
Stainless steel angle sheet covering wall corner; See through glass on the door and kick plate for low part of door; Grease
interceptor for each kitchen and general inceptor for all kitchen outside hotel; Floor and gully grating must be anti-slippery.
厨房灶台上烟道用不朽钢材料, 所有阳角要用不朽钢板100mmx100mm包裹; 通道门上部设透视窗,下部两面用不朽钢板包裹; 各厨
房设隔油池并在室外设总隔油池;地面和排水沟盖板要防滑.
Minimum diameter 600mm; Fire rating 2hrs; Fusible link at bottom door; Vent extending minmum 1200mm above roof comprising
with bird screen; Doors shall be interlocked to ensure only one access door may be opened at a time; Type 304 stainless steel;
Sprinkler head on top of chute.
内径最小600mm;最短耐火2小时;最底层门用易燃金属丝悬挂;伸出屋顶1200mm,并用防虫网罩住;每个门之间电子互锁,同时只能开启
一个门;304不朽钢板;污衣口门能自动关闭并锁上; 井道顶部和每隔一层侧部安装喷淋头.
Speaker inside guestroom and bathroom connecting with fire-fighting system; 5 background music source for chinese restaurant,
coffee shop, speciality restaurant, pool , SPA and other public areas; Volume switch for different area adn private room; Volume
switch for guestroom floor; Volume switch for lift cabin.
客房内应设置应急广播扬声器,卫生间安装吸顶式扬声器与电视伴音相连并能消防强切; 背景音乐音源要有5路音源,提供给中餐厅,西
餐厅,风味餐厅,游泳池,SPA,其它公共区域; 每个区域和包房内要设音量开关; 客房每个楼层设音量开关; 客用电梯内背景音乐设单独
的音量开关.
RCU shall connect with PMS and control guestroom temperature.
与酒店管理系统连接,对客房内温度进行监控。

5. Other Items 其他项目Shall be installed to easy communication inside hotel.安装方便酒店内部联络.
Shall install signal boosting system and cover all areas.应安装手机信号增强系统,使所有区域都能覆盖。

No 序号Item 项目Actual Status 现有状况
HILTON 要求
4
Guest elevators 客梯
5
Service elevators 服务电梯
6
Freight elevators 运货电

7
Handicapped Room 残疾
人房间
Location 位置Cold Water 冷水Hot Water 热水Steam 蒸汽Electricity 电Gas and fuel oil 燃气和燃油Actual Status 现有状况
Guest rooms 客房 X
X
X Ballroom 宴会厅 X Meeting rooms 会议室 X Business Centre 商务中心
X Restaurant 餐厅
X
SPA and Sauna 水疗和桑

X X X Pool 游泳池
X X X Beauty salon 美容美发 X
X Health Clubs 健身中心 X KTV and Night Club 夜总
会和KTV X
X BAR 酒吧
X X
Cooling tower make up
冷却塔补水
X
Mimimum load 载重量不小于2250kg; Minimum cabin size 最小轿箱净尺寸不小于2200WX2400DX2800H
Mimimum load 载重量不小于1800kg; Minimum cabin size 最小轿箱净尺寸不小于2200WX2400DX2800H
Hilton Hotel’s Utilities Metering Requirement
符合NFPA 和当地规范非要求.
Maximum waiting time interval 最长等梯时间42秒; 85% occupancy 开房率; 2.4 occupants per room 2.4个客人每间房; Handling capacity 处理能力12-15%.Have at least one accessible elevator(1350kg)至少1部残疾人客梯; Minimum load 客梯最小载重量
1350kg;Size 尺寸2000(W)×1400(D)×2300(H); Door size 门尺寸2100(H)×1100(W); Decoration Load 装修荷载Emergency light 有应急灯;Emergency Call between elevator, fire control centre and magic centre 在电梯, 消防中心和总机房实现三方对讲; Intercom connected to a constantly mornitor location 停靠位置监控显示; An electronic infra-red screen curtain type detector for door
protection 光幕; Travel path indicator in cab 电梯内运行方向指示灯;Door bell 到站钟; Auto stop on floor level when power cutoff suddenly 停电时自动平层功能; LCD display LCD 显示屏;Background music speaker(also for emergency broadcasting)背景音乐;Double control panel 双控制盘; Operating panels must clearly identify the major levels, i.e. lobby, restaurants, ballroom,wimming pool, executive lounge etc 控制盘上酒店功能区显示;
Audible signal and travel path indicator in elevator lobby 电梯厅到站钟和运行方向指示.Card key access to executive floors. 用房卡控制到行政楼层.Split A/C for cabin. 轿箱顶部的分体空调安装.
"Do Not Use Elevator in Case of Fire, Use Stairs" must be installed in each elevator cab and in a prominent location on the
wall beside the elevator entrance on each floor."火灾时, 不要使用电梯, 使用楼梯"的标识安装在电梯轿箱内和每层电梯的入口处.
HILTON 要求
No序号Item项目Actual Status 现有状况
Chilled water make up 制
冷系统补水 X
Kitchen 厨房 X X X X X
Laundry 洗衣房 X X X X
Lifts电梯 X
Shops 商店 X
Staff Housing 员工宿舍
X
Public areas 公共区域 X
Back of House 后台区域
X
External Lighting 室外照
明 X
Lockers 员工更衣室 X X
Car parks 停车场
X
Chillers & cooling tower
制冷机和冷却塔
X X
Water pumps 水泵 X
Gardens irrigation 绿化灌
溉 X
Make-up to hot water热
水补水 X
Boiler make-up锅炉补水
X
Boiler 锅炉X X X。