B315-029-029
Application
Chrome Plated Brass Ball and Nickel Plated Stem, 1/2", NPT Female Ends
Type overview
Type
DN B315-029-029
15
Technical data
Functional data
Valve size [mm]0.5" [15]
Fluid
chilled or hot water, up to 60% glycol Fluid Temp Range (water)43...180°F [6...82°C]Body Pressure Rating 232 psi Close-off pressure ∆ps 50 psi Differential pressure Δpmax 15psi Flow characteristic linear
Servicing maintenance-free Flow Pattern 6-way Leakage rate
0%
Controllable flow range sequence 1 (angle 0...30°), dead zone (30...60°), sequence 2 (angle 60...90°)Seq 1 Cv 0.29Seq 2 Cv
0.29
Materials
Valve body Nickel-plated brass body Stem nickel-plated brass Stem seal EPDM (lubricated)Seat
PTFE
Characterized disc chrome plated steel Pipe connection NPT O-ring EPDM
Ball
chrome plated brass
Product features
The 6-way characterized control valve is ideal for chilled beams, radiant ceilings, and fan coil units offering reduced wiring by using a single actuator instead of two. It eliminates the need for a change-over valve and enables the use of a single coil for heating and cooling.
B315-029-029 Operation A loop pressure relief is designed into port number two (2). This allows the increased pressure
to dissipate to the supply loop on port number one (1). This is intended to release any pressure
build up in the loop (coil) when the valve is in the closed position and is isolated from the system
expansion vessel. The change in pressure occurs due to a change in the media temperature in
the coil while isolated from the pressure vessel. The pressure relief does not affect the efficiency
of the system because cross-flow cannot occur between the heating and cooling loops. The
system loops (heating/cooling) should share a common expansion vessel to keep the system
pressure and volume balanced.
Flow/Mounting details
Accessories
Mechanical accessories Description Type
Fixing bracket for 6-way valve DN 15/20ZR-004 Dimensions
Type DN Weight
B315-029-02915 2.43 lb [1.1 kg]
A B C D E F G H1H2
7.2" [182] 3.1" [78]7.9" [201] 6.8" [173] 1.6" [40] 1.6" [40] 1.7" [44] 1.2" [30]0.6" [15]
LRX24-MFT
Modulating, Non-Spring Return, 24 V, Multi-
Function Technology®
Technical data
Electrical data
Nominal voltage
AC/DC 24 V Nominal voltage frequency 50/60 Hz
Nominal voltage range
AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 2.5 W Power consumption in rest position 1.2 W Transformer sizing 5 VA
Electrical Connection
18 GA plenum cable with 1/2" conduit
connector, degree of protection NEMA 2 / IP54, 1 m 3 m and 5 m
Overload Protection electronic thoughout 0...90° rotation Electrical Protection
actuators are double insulated Functional data
Operating range Y 2...10 V
Operating range Y note 4...20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor)Input Impedance
100 kΩ for DC 2...10 V (0.1 mA), 500 Ω for 4...20 mA, 1500 Ω for PWM and On/Off Operating range Y variable Start point 0.5...30 V End point 2.5...32 V
Operating modes optional variable (VDC, on/off, floating point)Position feedback U 2...10 V Position feedback U note Max. 0.5 mA Position feedback U variable VDC variable
Direction of motion motor selectable with switch 0/1Manual override external push button Angle of rotation 90°
Angle of rotation note adjustable with mechanical stop Running Time (Motor)150 s / 90°Running time motor variable 35...150 s Noise level, motor 35 dB(A)
Position indication
Mechanically, pluggable Safety data
Power source UL
Class 2 Supply Degree of protection IEC/EN IP54Degree of protection NEMA/UL NEMA 2
Enclosure UL Enclosure Type 2
Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU Quality Standard ISO 9001
UL 2043 Compliant
Suitable for use in air plenums per Section 300.22(C) of the NEC and Section 602 of the IMC
Ambient humidity
Max. 95% RH, non-condensing
LRX24-MFT
Footnotes
Safety data
Ambient temperature -22...122°F [-30...50°C]Storage temperature -40...176°F [-40...80°C]Servicing
maintenance-free Weight Weight
1.5 lb [0.70 kg]
Materials
Housing material Galvanized steel and plastic housing
†Rated Impulse Voltage 800V, Type action 1.B, Control Pollution Degree 3.
Accessories
Gateways
Description
Type Gateway MP to BACnet MS/TP UK24BAC Gateway MP to Modbus RTU UK24MOD Gateway MP to LonWorks
UK24LON Electrical accessories
Description
Type Battery backup system, for non-spring return models NSV24 US Battery, 12 V, 1.2 Ah (two required)NSV-BAT Auxiliary switch 1 x SPDT add-on S1A Auxiliary switch 2 x SPDT add-on
S2A
Feedback potentiometer 140 Ω add-on, grey P140A GR Feedback potentiometer 1 kΩ add-on, grey P1000A GR Feedback potentiometer 10 kΩ add-on, grey P10000A GR Feedback potentiometer 2.8 kΩ add-on, grey P2800A GR Feedback potentiometer 500 Ω add-on, grey P500A GR Feedback potentiometer 5 kΩ add-on, grey
P5000A GR Tools
Description
Type
Connection cable 10 ft [3 m], A: RJ11 6/4 ZTH EU, B: 3-pin Weidmüller and supply connection
ZK4-GEN Service Tool, with ZIP-USB function, for programmable and communicative Belimo actuators, VAV controller and HVAC performance devices
ZTH US
Electrical installation
INSTALLATION NOTES
Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power consumption and input impedance must be
observed.
Actuators may also be powered by DC 24 V.
Only connect common to negative (-) leg of control circuits.
A 500 Ω resistor (ZG-R01) converts the 4...20 mA control signal to 2...10 V.
Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 V line.For triac sink the Common connection from the actuator must be connected to the Hot
connection of the controller. Position feedback cannot be used with a triac sink controller; the
actuator internal common reference is not compatible.
IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155).
Actuators with plenum cable do not have numbers; use color codes instead.
Meets cULus requirements without the need of an electrical ground connection.
Warning! Live electrical components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
LRX24-MFT Wiring diagrams
On/Off Floating Point
VDC/mA Control PWM Control
Override Control。