可调压差式流量开关选型手册

合集下载

606 可调设定点气体压差开关使用说明书

606 可调设定点气体压差开关使用说明书

606可调设定点气体压差开关应用和特点用于监测空气等非可燃、非腐蚀性气体的过压、真空和压差状态技术指标量程范围:4种量程可选,详见选型表最大压力限制:7500Pa (-30~75°C)工作温度:-30~75°C (介质及环境)存储温度:-30~75°C压力连接:内径6.0mm塑料软管,“+”或“P1”为高压端,“-”为低压端开关寿命:106次以上输出:SPDT,0.2A/30VDC,1.5A/250VAC最大开关频率:6次/分钟电气连接:旗型端子或螺丝端子可重复性:±2%材质:PC壳体,PC上盖,硅胶膜片,银合金/ 镀金触点重量:含安装支架135克,不含安装支架85克防护:IP54安装:垂直,压力接口向下。

此为开关校准位置。

如必须水平安装时,实际设定点比刻度点加10Pa(封盖向上)或减约10Pa(封盖向下),详见使用说明书认证:CE安装配件(需单独订货)型号说明1001独立配件包,含透明PVC导气管2M,连接件(1003)2个,螺丝4个1002 透明PVC导气管2M1003 塑料连接件1个,一字型1008独立配件包,含透明PVC导气管2M,连接件(1009)2个,螺丝4个1009 塑料连接件1个,L型选型表型号606606可调设定点气体压差开关封装方式0带安装耳环1无安装耳环,带安装支架可调范围020~300Pa150~500Pa2100~1000Pa30.5~2.5kPa工程单位0Pa7mbar8inch wc9mm wc触点材质0银合金1 镀金端子0旗型端子1 螺丝端子回差表型号可调量程范围工厂设定回差606.X0XXX20-300Pa10±5Pa606.X1XXX50-500Pa20±8Pa606.X2XXX100-1000Pa50±15Pa606.X3XXX0.5-2.5kPa100±30Pa注:工厂设定回差客户不能自行调整1001 1002 10031008 1009本说明书以带支架安装(型号606.1XXXX)图示,带耳环安装(型号606.0XXXX)参照此执行。

MFM500D流量开关选型V1.0

MFM500D流量开关选型V1.0

传真:0917-3600755
3 GND (黑色) RL RL
2 PNP1 (黄色) 1 24VDC+ (红色) 4 PNP2 (蓝色)
-3-
MFM500D 型流量开关选型(V1.1)
选型指南
MFM500D
型流量开关 代号 供电电源
DC 24VDC AC 220VAC(继电器输出)
代号 压力接口形式 C1 M20×1.5 外螺纹 C3 G1/2 外螺纹
水 温:-20℃~80℃ 贮存温度:-30℃~85℃ 工作温度:-20℃~70℃ 防护等级:IP67 温度补偿:5℃~50℃补偿(水) 电磁兼容:GB/T 17626.2/3-2006,GB/T 17626.4-2008 振 动:≤ 20g (GB/T 2423.10-2008) 冲 击:≤ 50g/11ms (GB/T 2423.5-1995)
24V DC供电
24V DC供电
NPN输出
1 24VDC+ (红色) RL RL
2 NPN1 (黄色)
3 GND (黑色)
4 NPN2 (蓝色)
PNP输出

地址:陕西省宝鸡市高新开发区英达路 18 号 721006
电话:0917-3600901 3600902 3600903
MFM500D 型流量开关选型(V1.1)
MFM500D 型流量开关
产品特点
· 24VDC 或 220VAC 宽范围供电可选 · LED 液晶屏,数字百分比显示 · 全不锈钢外壳,IP67 防护 · 温度补偿 · 多种输出方式可选 · 无可动部件,免维护 · 开关量输出,控制点连续可调 · 外形小巧,支持显示反转 · 活接头可配不同接口,适合多种管径要求
选型提示

罗斯蒙特差压流量产品选型样本-

罗斯蒙特差压流量产品选型样本-

罗斯蒙特差压流量技术——工业的标准差压流量的测量是世界上应用量最广泛的流量测量技术,全球有超过50%的流量测量使用差压技术。

其性能的可靠性,得到广大用户的认可。

在气体,液体,蒸汽的测量过程中,差压技术被大量采用。

差压流量测量是应用一次元件(孔板,阿牛巴等)和二次仪表(差压变送器)构成。

长期以来罗斯蒙特公司已提供世界上最优秀的变送器而闻名,自从Dieterich Standard Inc.(DSI)公司加入罗斯蒙特公司后,我们可以同时提供一次测量元件(Annubar阿牛巴,孔板等)和二次仪表(差压变送器3051,3095等)并且是世界上唯一将二者在制造厂内结合成一体化的流量计Probar 和MassProbar,从而提供差压流量测量的全面解决方案.目录1、罗斯蒙特阿牛巴流量计系列―――――――――――――――――――― 12、罗斯蒙特285阿牛巴传感器―――――――――――――――――――-333、罗斯蒙特紧凑型孔板流量计系列――――――――――――――――――424、罗斯蒙特一体化孔板流量计系列――――――――――――――――――575、罗斯蒙特1495、1595、1496、1497孔板――――――――――――――726、罗斯蒙特3095多参数变送器―――――――――――――――――――85产品性能资料2006差压流量1阿牛巴流量计系列行业领先的一体化差压流量计通过将压力变送器电子元件与阿牛巴平均皮托管(APT )实现一体化,罗斯蒙特可提供具有最佳性能的插入式差压流量计。

这种完全一体化的流量计无需仪表配件、仪表管线、阀门、接头、阀组和安装支架,因此可以缩短焊接和安装时间。

采用创新测量技术提高测量性能阿牛巴正面开槽设计和创新造型可提高所有流量测量点的精度和重复性。

通过增加信号强度并降低信号噪声,实现严格的过程控制。

实时质量流量测量可采用一体化温度传感器设计获得专利的 T 形传感器包括密封的压力保持热电偶套管,只需要单个管道贯穿孔就可在所有尺寸的管线上进行质量流量测量。

SMC数字流量开关操作手册说明书

SMC数字流量开关操作手册说明书

Digital Flow Switch (Display Part) Operation Manual For AirPF2A300/301 SeriesPF2A310/311 SeriesFor Pure Water/Chemical Fluid PF2D300/301 SeriesFor WaterPF2W300/301 SeriesPF2W330/331 SeriesURL SAFETY2Model Indication Method4Name and Functions of Individual Parts 6Installation7Outline with Dimensions8Example of Internal Circuit and Wiring 9Setting 10Initialize11Display Function of Integrated Flow Rate Value 15Instantaneous Flow Rate Setting Mode16Integrated Flow Rate Setting Mode 19Output Selection 20Other Functions 23Specification24CONTENTSThank you for purchasing the SMC PF2*3**Series Digital Flow Switch.Please read this manual carefully before operating digital flow switch and understand digital flow switch, its capabilities and limitations.Please keep this manual handy for future reference.OPERATOR•This operation manual has been written for those who have knowledge of machinery and apparatus that use pneumatic equipment and have full knowledge of assembly, operation and maintenance of such equipment.•Please read this operation manual carefully and understand it before assembling, operating or providing maintenance service to the flow switch.32NOTEFollow the instructions given below when handling your flow switch.Otherwise, the switch may be damaged or may fail, thereby resulting in malfunction.•Do not drop it, bring it into collision with other objects or apply excessive shock (490m/s 2or more).•Wiring correctly.•Do not wiring while power is on.•Although the flow switch complies with the CE Marking, since it does not have the thunder serge protection, please carry out protection to thunder serge by the equipment side.•Although the flow switch complies with the CE Marking, since the equipment and apparatus which are made to generate the serge (Electro-magnetic lifter, High frequency induction furnace, Motor etc.) around the flow switch should perform measure against serge come out.•Do not use with power cable or high-voltage cable in the same wire route.•Do not use in a place in which water, oil, or a chemical splashes.•Do not push the setting buttons by a sharply pointed object.•Turn on the power supply of a flow switch for Air, when flow is zero.Some initial drift occurs during ten minutes after turning the power on.•Start measurement by the flow switch three seconds after turning on the power. (Also in momentary interception of the power supply by reset etc.) Please take a measure by the program of equipment etc.•Maintain the switch status for measurement output before setting when initializing or setting a flow rate of the flow switch.Measure after checking impacts to the equipment.Carry out a setup since a control system is shut down if required.The Digital Flow Switch and this manual contain essentialinformation for the protection of users and others from possible injury and property damage and to ensure correct handling.Please check that you fully understand the definition of the following messages (signs)before going on to read the text, and always follow the instructions.Please read the operation manuals of related apparatus and understand it before operating the flow switch.Do not disassemble, remodel (including change of printed circuit board) or repair.An injury or failure can result.Do not operate beyond specification range.Fire, malfunction or switch damage can result.Please use it after confirming the specification.Do not operate in atmosphere of an inflammable, an explosive and corrosive gas.Fire or an explosion can result.This flow switch is not an explosion-proof type.54NOTE 1:The new Measurement Low prohibits use in Japan of flowswitches with a unit selection function.NOTE 2:Fixed unit for instantaneous flow rate is :L/minfor integrated flow rate is :LSeparate Type Display PartA : AirD : Pure Water/Chemical Fluid W : Water•About sensor partThe type of the sensor part combined with a display part is indicated to be PF *5**with this manual.Refer to the following correspondence table for the sensor part type combined with each display part.BodyOutput (OUT1) Lamp (Green):Lit when OUT1 is ON. Flickers when an overcurrent erroroccurs.Output (OUT2) Lamp (Red):Lit when OUT2 is ON. Flickers when an overcurrent erroroccurs.LED Display:Displays a flow rate, set mode status, selected display unitand error code.Button (UP): Selects a mode and increases a set ON/OFF value.Button (DOWN): Selects a mode and decreases a set ON/OFFvalue.Button (SET): Changes the mode and sets a set value. RESETPressing the and buttons simultaneously will activate the RESET function.Use this function to clear errors when a trouble occurs.Panel Mount Adapter type ZS-22-EPanel Mount Adapter APanel Mount Adapter BBracket are includedMounting•Install the Display Part on the panel, once the Panel Mount Adaptor Bremoves.•Insert Panel Mount Adapter B supplied as an accessory intoSection A of Panel Mount Adapter A.Push Panel Mount Adapter B from behind till the display is fixedonto the panel.The pin of Panel Mount Adapter B engages the notched part ofPanel Adapter A to fix the display.•The switch can be mounted on a panel with a thickness of 1.0 to3.2mm.•See the illustration below for panel cut dimensions.Panel Cut Dimensions Accessories LED DisplayLamp (Red)SETButton (UP)7 698++0.5Panel Thickness: 1 to 3.2mmPanel Cut DimensionsOutput SpecificationBe sure to select a sensor in SMC PF *5**series for accurate measurement of flow rates.The display outputs only switch output.Analog output is output directly by the sensor part. See theoperation manual of the sensor part for the complete information. Connection•Turn the power off before making connection.•Install the cable separately from the route for power cable or high-voltage cable. Otherwise, malfunction may potentially result due to noise.•Use compression terminals for connection to the terminal board.See the full view of dimensions diagram for details of the terminal board.–0NPN Open Collector Output 2OutputsMax. 30V, 80mAInternal Voltage Drop 1V or less–1PNP Open Collector Output 2Outputs Max 80mAInternal Voltage Drop 1.5V or lessPF ∗5 SeriesPF ∗5 SeriesSetting ProceduresKeep pressing the button longer than two seconds. Remove the finger off the button when one of the characters of LED display column of the following table is displayed.1. Flow Rate Range SettingPress the button and select the flow rate range.Press thebutton to set.2. Display Mode SettingSelect whether to display instantaneous flow rate orintegrated flow rate.To change the Display mode, press thedesired flow rate to display. Then press the button.[d_1] and [d_2] respectively indicate the instantaneous flow rate and integrating flow rate.11103. Selecting Display Unit(In case [-M] is not assigned to unit specification in model indication) Refer to page 14.4. Output Method SettingThree output methods are available, namely, instantaneous switch, integrating switch and integrating pulse. The method for output to OUT1 or OUT2 is set as follows.1)First, the output method for OUT1 is set.*Press the button and select the instantaneous switch,integrating switch or integrating pulse.*Press the button to set.[o10] [o11] and [o12] respectively indicate the2)Select one output method for OUT2 from three output methods by pressing the button, as in OUT1.*Press the button to set.[o20] [o21] and [o22] respectively indicate theinstantaneous switch, integrating switch and integrating pulse.5. Output Mode SettingTwo output modes are available, namely, the Reverse Output modeand Non-Reverse Output mode. An output mode for OUT1 andOUT2 is set.1)First, the output method for OUT1 is set.*Press the button and select the Reverse Output mode or Non-Reverse Output mode.*Press the button to set.[1_n] and [1_P] respectively indicate the Reverse Outputmode and Non-Reverse Output mode.mode and Non-Reverse Output mode by pressing the button,as in OUT1.*Press the button to set.[2_n] and [2_P] respectively indicate the Reverse Outputmode and Non-Reverse Output mode.13 1215•Press the button first, then the button, to press both buttons simultaneously. Integration starts when [–] flickers.•Lower three digits of an integrated value are always displayed.Press the button when wishing to check upper three digits.•Pressing the button enables to display an instantaneous flow rate even during integration.•To stop integration, press the button first, then the button,to press both buttons simultaneously.The display will keep the present integrated value.To clear display of an integrated value, press both the and buttons simultaneously longer than two seconds.To further continue integration from the saved value, repress thebutton first, then the button, to press both buttons simultaneously.1716Manually set an actuation value of the instantaneous-value switch in case the instantaneous switch is selected in initialization.The output method is also set in accordance with the value set manually. Set the output method while referring to the output method described below.1.Keep pressing the button and remove the finger off when [F-1] is displayed.2.Repress the button to set for input of a set value in [n_1] (P_1 in the Non-Reverse Output mode) for OUT1.In case the Reverse Output mode is selected in initialization, [n_1]and the set value will be displayed alternately.(In case the Non-Reverse Output mode is selected in initialization,[P_1] and the set value will be displayed alternately.) 3.Press the or buttons to select a desired set value.Press the button to increase the set value or the button to decrease the set value.4.Press the button to set the set value and to move to the setting mode for [n_2] (P_2 in the Non-Reverse Output mode).In case the Reverse Output mode is selected in initialization, [n_2]and the set value will be displayed alternately.(In case the Non-Reverse Output mode is selected in initialization,[P_2] and the set value will be displayed alternately.) 5.Press the or buttons to select a desired set value.Press the button to increase the set value or the button todecrease the set value.6.Press the button to set the set value and to move to the setting mode for OUT2.Set the set value as in OUT1.In case the Reverse Output mode is selected for the OUT2 setting in initialization, [n_3] or [n_4] and the set value will be displayed alternately.In case the Non-Reverse Output mode is selected in initialization,[P_3] or [P_4] and the set value will be displayed pleting settings for [n_1] to [n_4] ([P_1] to [P_4] in the Non-Reverse Output mode) will finish flow rate setting and the mode will return to the Measurement mode.Manual1918The flow rate flowing through the flow switch will be set as areference value and a Hysteresis (H) will be set automatically at a value 3digits lower when setting auto preset input.The output method for setting by auto presetting is only hysteresis mode.1.Keep pressing the button and remove the finger off when [F_1] is displayed.2.Press the button and change [F_1] in the display to [F_2].3.Press the button and set the auto preset state of OUT1.The display will change to show [AP1] .(In case OUT1 setting is not needed, press the and button simultaneously.)4.Prepare the equipment to set the flow rate of OUT1 and flow fluid of the required flow rate.5.Pressing the button will automatically read the flow rate. A value 3digits lower will be set automatically as a Hysteresis (H).The display will show [A1L] and the set value alternately.6.Press the button and set auto preset state of OUT2.The display will change to show [AP2].(In case OUT2 setting is not needed, press the and buttons simultaneously.)7.Prepare the equipment to set the flow rate of OUT2 and flow fluid of the required flow rate.8.Pressing the button will automatically read the flow rate. A value 3digits lower will be set automatically as a Hysteresis (H).The display will show [A2L] and the set value alternately.9.Press the button to finish the Auto Presetting mode and themode will return to the Measurement mode.Auto Presetting•The switch is set to an integrated flow rate.•Integrated flow rate is displayed by switchingdividing into lower three digits and upper three digits. 1.Keep pressing the button and remove the finger off when [F_1] or [F_3] is displayed.Proceed to Step 3. if [F_3] is displayed.([F_1] will be displayed in case the instantaneous switch is selected for any switch output in initialization. In other cases,[F_3] will be displayed.)2.When [F_1] is displayed, push the button till the display shows [F_3]. The subsequent setting operation will be the same as that when [F_3] is displayed. Set as follows.3.Set as follows if [F_3] is displayed.1)Press the button and display the lower three digits of the integrated flow rate of OUT1.2)Press the or buttons and adjust the set value to the desired value.3)Press the button to set. The upper three digits of OUT1 will be displayed.4)Press the or buttons and adjust the set value to the desired value.5)Press the button to set. The lower three digits of OUT2 will be displayed.6)Press the or buttons and adjust the set value to the desired value.7)Press the button to set. The upper three digits of OUT2 will be displayed.8)Press the or buttons and adjust the set value to the desired value.9)Press the button to finish setting of an integrated flow rate and the mode will return to the Measurement mode.Instantaneous Switch Output MethodFour output methods can be selected by selecting an output modeOne of these four output methods can be selected for each output.•OUT1 and OUT2 can be set independently.•1digit flow rate conversion will be a minimum set unit. See thespecification for the set flow rate units.•When setting in the Auto Presetting mode, the Hysteresis mode willbe set automatically. Hysteresis in this case will be 3digits fixed.•In the Window Comparator mode, leave between [P_1] and [P_2]or between [n_1] and [n_2] values more than seven digits.•The following is given using OUT1 as an example. Thedescriptions for OUT2 are the same as those for OUT1, under theconditions that [n_1] and [n_2] should be replaced by [n_3] and[n_4] and [P_1] and [P_2] should be replaced by [P_3] and [P_4].20212322To reset display of Error 1, 2 or 4, press theandbuttons simultaneously.Integrating Switch Output•Two output methods can be selected by selecting an output mode.One of these two output methods can be selected for each output.•OUT1 and OUT2 can be set independently.•The following is given using OUT1 as an example. Thedescriptions for OUT2 are the same as those for OUT1, under the conditions that 1nL and 1nH should be replaced by 2nL and 2nH and 1PL and 1PH should be replaced by 2PL and 2PH.Integrating Pulse Output•Pulse output for integrated flow rate measurement.Key Lock FunctionThis function prevents errors such as changing a set value by mistake.Lock•Keep pressing the button longer than three seconds.The display will change to show [F_1] Æ[***] Æ[unL.]Remove the finger off the button when [unL] is displayed.([***]:Refer to the LED display column in the table, Page11)•Press the button to set the display to [Loc]•Press the button and return to the Measurement mode.Unlock •Press the button longer than three seconds. Remove the finger off the button when [Loc] is displayed.•Press the button to change the display to [unL]•Press the button and return to the Measurement mode.Error Display and TroubleshootingIn case an error occurs, take the following actions:2524*1:The flow rate indication range is corresponding to the flow rate range set up bythe initialization.*2:With a unit selection function(Without a unit selection function, fixed to SI units(L/min or L))*3:Two units in normal condition (0˚C/ 101.3kPa) or standard condition (20˚C/101.3kPa/ 65%RH) can be selected.*4:This is an overall accuracy combined with PF2A 5**.*5:Select whether to switch output or pulse output of integrated flow rate by theinitialization.*6:Window Comparator mode. Hysteresis (H) will be in 3digits.Separate [P_1] and [P_2], as well as [n_1] and [n_2], more than 7digits.(In case of the output 2, n_1,2 becomes n_3,4 and P_1,2 becomes P_3,4)*7:The display part conforms entirely to the CE standard.2627。

调节阀(执行机构)及辅助装置形式、材质、流量、尺寸、推力与允许差压选择方法

调节阀(执行机构)及辅助装置形式、材质、流量、尺寸、推力与允许差压选择方法

调节阀(执行机构)及辅助装置形式、材质、流量、尺寸、推力与允许差压选择方法一、调节阀的型式选择方法:(一)、调节阀选型的常见方法:1、现场观察法:现场观察法是根据现场实际工况来选型调节阀,其基本原则是“现场为准”。

2、实验法:实验法是根据实验结果,通过实验设备来确定调节阀的选型。

3、经验法:经验法是根据经验来选型调节阀,它是根据已有的经验和技术资料来确定调节阀的选型。

(二)、调节阀按工况及环境的选型方法:1、前后压差较小,要求泄漏量较小,一般可选用单座阀;2、调节低压差、大流量的气体,可选用蝶阀;3、调节强腐蚀性流体,可选用隔膜阀;4、既要求调节又要求切断时,可选用偏心旋转阀;5、噪音较大时可选用套筒阀,一般选用单阀座套筒型气动或者电动调节阀。

二、调节阀材质选择方法:1、根据介质的工作压力、温度、腐蚀性、气蚀冲刷是否严重等选材,一般应选铸钢。

2、使用要求不高时(120℃、1.6MPa以下)也可选用铸铁;3、高温高压(22~32MPa)场合应选用锻造合金钢;4、不锈钢可用于腐蚀性强的介质。

三、调节阀的流量特性选择:1、调节阀的流量特性是介质流过调节阀的相对流量与相对位移(调节阀的相对开度)间的关系,一般来说改变调节阀的阀芯与阀座的流通截面,便可控制流量。

2、由于多种因素的影响,如在截流面积变化的同时,还发生阀前后压差的变化,而压差的变化又将引起流量的变化。

3、在阀前后压差保持不变时,调节阀的流量特性称为理想流量特性,调节阀的流量特性有等百分比特性、线性特性、抛物线特性及快开特性四种。

就调节性能上讲,以等百分比特性为最优,其调节稳定,调节性能好。

可以根据实际使用场合的要求不同,挑选其中任何一种流量特性。

6、蒸汽系统中调节阀一般选择线性和等百分比流量特性。

四、调节阀尺寸的选择方法:1、确定管道尺寸:要正确选择调节阀的尺寸,首先需要明确连接管道的尺寸和法兰标准。

通常,在规划和设计管道系统时,需要提前确定阀门的位置和类型。

阀门选型手册

阀门选型手册

阀门选型手册-阀门选型的步骤和依据阀门选型手册-阀门选型的步骤和依据在流体管道系统中,阀门是控制元件,其主要作用是隔离设备和管道系统、调节流量、防止回流、调节和排泄压力。

由于管道系统选择最适合的阀门显得非常重要,所以,了解阀门的特性及选择阀门的步骤和依据也变得至关重要起来。

阀门行业到目前为止,已能生产种类齐全的闸阀、截止阀、节流阀、旋塞阀、球阀、电动阀、隔膜阀、止回阀、安全阀、减压阀、蒸汽疏水阀和紧急切断阀等12大类、3000多个型号、4000多个规格的阀门产品;最高工作压力为600MPa,最大公称通径达5350mm,最高工作温度为1200℃,最低工作温度为-196℃,适用介质为水、蒸汽、油品、天然气、强腐蚀性介质(如浓硝酸、中浓度硫酸等)、易燃介质(如笨、乙烯等)、有毒介质(如硫化氢)、易爆介质及带放射性介质(金属钠、-回路纯水等)。

阀门承压件材质铸铜、铸铁、球墨铸铁、高硅铸铁、铸钢、锻钢、高、低合金钢、不锈耐酸钢、哈氏合金、因科镍尔、蒙乃尔合金、双相不锈钢、钛合金等。

并且能够生产各种电动、气动、液动阀门驱动装置。

面对如此众多的阀门品种和如此复杂的各种工况,要选择管道系统最适合安装的阀门产品,我以为,首先应了解阀门的特性;其次应掌握选择阀门的步骤和依据;再者应遵循选择阀门的原则。

1.阀门的特性一般有两种,使用特性和结构特性。

使用特性:它确定了阀门的主要使用性能和使用范围,属于阀门使用特性的有:阀门的类别(闭路阀门、调节阀门、安全阀门等);产品类型(闸阀、截止阀、蝶阀、球阀等);阀门主要零件(阀体、阀盖、阀杆、阀瓣、密封面)的材料;阀门传动方式等。

结构特性:它确定了阀门的安装、维修、保养等方法的一些结构特性,属于结构特性的有:阀门的结构长度和总体高度、与管道的连接形式(法兰连接、螺纹连接、夹箍连接、外螺纹连接、焊接端连接等);密封面的形式(镶圈、螺纹圈、堆焊、喷焊、阀体本体);阀杆结构形式(旋转杆、升降杆)等。

8种常用阀门及闸阀选型使用说明手册

8种常用阀门及闸阀选型使用说明手册

8种常用阀门及闸阀选型使用说明手册1、闸阀的选型说明:⑴、一般情况下,应首选闸阀。

闸阀除适用于蒸汽、油品等介质外,还适用于含有粒状固体及粘度较大的介质,并适用于放空和低真空系统的阀门。

⑵、对带有固体颗粒的介质,闸阀阀体上应带有一个或两个吹扫孔。

⑶、对低温介质,应选用低温专用闸阀。

2、截止阀选型说明:⑴、截止阀适用于对流体阻力要求不严的管路上,即对压力损失考虑不大,以及高温、高压介质的管路或装置,适用于DN<200mm的蒸汽等介质管道上;⑵、小型阀门可选用截止阀,如针形阀、仪表阀、取样阀、压力计阀等;⑶、截止阀有流量调节或压力调节,但对调节精度要求不高,而且管路直径又比较小时,宜选用截止阀或节流阀;⑷、对于剧毒介质,宜选用波纹管密封的截止阀;⑸、截止阀不宜用于粘度较大的介质和含有颗粒易沉淀的介质,也不宜作放空阀及低真空系统的阀门。

3、球阀选型说明:⑴、球阀适用于低温、高压、粘度大的介质。

大多数球阀可用于带悬浮固体颗粒的介质中,依据密封的材料要求也可用于粉状和颗粒状的介质;⑵、全通道球阀不适用于流量调节,但适用于要求快速启闭的场合,便于实现事故紧急切断;⑶、通常在密封性能严格、磨损、缩口通道、启闭动作迅速、高压截止(压差大)、低噪音、有气化现象、操作力矩小、流体阻力小的管路中,推荐使用球阀。

⑷、球阀适用于轻型结构、低压截止、腐蚀性介质中;⑸、球阀还是低温、深冷介质的最理想阀门,低温介质的管路系统和装置上,宜选用加上阀盖的低温球阀;⑹、选用浮动球球阀时其阀座材料应承接球体和工作介质的载荷,大口径的球阀在操作时需要较大的力,DN200mm的球阀应选用蜗轮传动形式;⑺、固定球阀适用于较大口径及压力较高的场合;⑻、用于工艺剧毒物料、可燃介质管道的球阀,应具有防火、防静电结构。

4、节流阀选型说明:⑴、节流阀适用于介质温度较低、压力较高的场合;⑵、适用于需要调节流量和压力的部位,不适用于粘度大和含有固体颗粒的介质,不宜作隔断阀。

SMC流量开关PF3W 中文操作手册

SMC流量开关PF3W 中文操作手册
返回功能设定模式。
5.完成
~ 12 ~
○输出规格
*在迟滞模式或窗口比较模式下,流量波动可能会导致输出的波动。
~ 13 ~
在此情况下,设定值请保持充分的余量以确保输出的稳定性。
*选择累计脉冲输出时,输出指示灯会熄灭。
■[F2]OUT2 设定
可选择 OUT2 输出模式。
屏幕显示颜色不可在 OUT2 中设定。
~7~
带温度传感器
项目
说明
出厂设置
输出模式
选择流体温度输出为迟滞模式或上下限比较
模式。
迟滞模式
反向输出
选择反向或非反向输出模式。
非反向输出
设定值பைடு நூலகம்
设置开关输出的 ON/OFF 点。
50℃
迟滞
设定迟滞可避免发生振荡。
5℃
•其他设定
项目
页码
出厂设置
[F3] 响应时间
见 19 页
1s
[F10]副屏幕设定
见 19 页
功能设定
功能选择模式
在测量模式下,按住
[F
键保持 2 秒以上,将会显示[F1]。
]可改变各项功能设定。
持续按住
键保持 2 秒以上,可返回测量模式。
*副屏幕交
替 显 示功能
内 容 及功能
设定。
功能序号可通过

键来切换,并通过
键进入所需设定的功能项。
■出厂设置
出厂设置如下表所示。如需改变请进入功能选择模式。
最大 28 V, 80 mA
内部电压降不超过 1 V
NPN + 模拟输出型
最大 28 V, 80 mA
内部电压降不超过 1 V
C: 模拟输出1 ~ 5 V

罗斯蒙特差压流量计产品手册说明书

罗斯蒙特差压流量计产品手册说明书

差压流量产品手册更具灵活性的流量测量方式“罗斯蒙特差压流量”更具灵活性的流量测量方式应用领域 – 液体,气体,蒸汽流量测量面临的挑战技术标准的不确定性带来的高风险潜在泄漏点带来的安全隐患特殊工况无法实现停车检修双向流、腐蚀介质、小管道流量导致测量难度大读数误差、小流量测量和直管段不足会降低测量精度大管径管道测量带来的高成本测量时压损过大带来的能源损失降低使用风险一体化流量计出厂前通过整体标定保证系统测量精度一体化设计和出厂前泄漏检测可大幅减少泄漏点,从而避免潜在安全隐患严格的原材料管理体系,保证所有物料可追溯,实现产品质量有效控制应对特殊工况针对无法停车检修的工况,可采用在线插拔安装方式一次元件可提供多种不同材质,来应对腐蚀工况面对双向流测量,可根据实际情况,提供更理想解决方案减少运营成本一体化安装可降低施工及维护成本阿牛巴流量计,在保证超强差压信号的前提下,更大程度减少永久压损调整型孔板大幅降低直管段需求,从而降低管道成本性能出色实时动态多参量补偿,提高流量测量精度可提供15年稳定性,15年质保流量计量程比大,适用范围广Rosemount差压流量计的优势13051SMV实时动态补偿实现蒸汽质量流量的精准测量挑战石化行业蒸汽总管线与分支管线流量差值很大,平衡率仅为70%。

由于无法准确计量各装置蒸汽用量,导致很难准确核算能耗成本。

解决方案采用罗斯蒙特3051SMV多参量变送器,测量差压、静压和温度数值,实现实时温压补偿。

同时实时计算动态补偿的质量流量,并修正来自于流量系数、密度、气体膨胀以及粘度的误差,从而提高测量精度。

方案优势提高测量的准确性和可重复性,实现更好的工艺控制通过精确的流量控制,帮助工厂有效的进行能源管理,能耗平衡率达到92%以上2多参量流量变送器大幅提高流量测量精度一流的性能变送器最高精度可达到读数的0.04%一台表可以同时测量并计算六个流量相关的变量:差压、压力、温度、质量/体积流量、热量累积器 兼容不同种类流量测量元件严格的流量计量标准内嵌IAPWS-IF97数据库: 水蒸汽计量全球标准 符合国家标准蒸汽热值输出标准动态补偿为流量方程中多达25个流体变量参数提供实时动态补偿优化能源计量提高收益变送器直接显示补偿后的质量流量或能量流量变送器三合一卓越特性Calendar-Van Dusen 传感器匹配提高温度测量精度提高精度 75%真正的表压传感器更容易标定简化维护小流量信号切除可停止无流量时的累计改善精度差压传感器静压传感器减少管道开孔,降低安装成本易于组态和标定EA 软件实现快速且简单的过程组态 可兼容市面上不同种类的差压流量测量元件节约安装和维护成本3差压变送器压力变送器温度变送器阿牛巴的广泛应用大管道的蒸汽流量精确测量流量计,压损小,测量精度高,不仅精确测蒸汽流量,还可实现蒸汽的热值输出。

流量开关原理结构、技术参数、选型参考

流量开关原理结构、技术参数、选型参考

德国科威尔柱塞式流量开关科威尔柱塞式流量开关FP54原理结构:在线式安装,机械式流量开关,用于液体或气体介质。

坚固的塑料,铝或不锈钢外壳可选。

介质推动柱塞弹簧至设定位置即可通过磁场作用于干簧管输出无源通断信号,并提供瞬时流量大小刻度的指示。

科威尔主要特点:极小的压力损失,良好的重复性,抗污能力。

机械部分与电子部分完全隔离,带有开关设定刻度表。

现场瞬时流量可视,用户可在现场设定。

LED显示开关动作状态,适用于小流量经济型。

3倍于原FP50的活塞行程使设定精度更加精确。

科威尔应用:气液两用型,工业自动化/ 机械设备/ 空气压缩工业/ 制冷及空调科威尔性能概述:FFP54型流量开关,适用介质:水、乙二醇溶液、油基液体、空气。

最大工作压力200 bar.介质温度-10…160℃。

电源:DC24V AC220V AC380V。

保护级别IP65.适用管径DN8~DN32,材质可选:POM塑料、阳极氧化铝、青铜合金、316L不锈钢,流量报警设定值0.1L~70/min科威尔技术参数:外壳柱塞弹簧密封磁体FP54…FP 材质POM工程塑料POM工程塑料316L不锈钢SUS1.4310NBR 钡FP54…FA 材质阳极氧化铝POM工程塑料316L不锈钢SUS1.4310NBR 钡FP54…FK 材质316L不锈钢POM工程塑料316L不锈钢SUS1.4310NBR 钡FP54…FB 材质青铜合金UNI EN12165 CW617NPOM工程塑料316L不锈钢SUS1.4310NBR 钡设定范围: 详见参数表精确度: ±2.5%总量程迟滞: 视开关点而定,最小0.5L/Min LED显示:接插头交流直流配电均有LED显示开关状态。

开关设定刻度: 介质为水,温度20℃,水平安装状态进行标定的安装位置,介质和温度变化会对开关值略有影响。

接线方式:直接附线输出: 无源干簧开关 , 容量 24VDC/ 250VAC ,1.5A耐压:15bar(POM塑料)50bar(铝型) 50bar(黄铜)100bar(不锈钢) 定制型200bar可选平均压力损失:0.25bar(在25L/min) 防护等级:IP65 介质温度: 最大160℃科威尔选型表:FP54- 008 F D K 015 B /HT 详述FP54- FP54系列柱塞式流量开关适用管径008 螺纹接口 G1/4 名义口径DN8 010 螺纹接口 G3/8 名义口径DN10 015 螺纹接口 G1/2 名义口径DN15 020 螺纹接口 G3/4 名义口径DN20 025 螺纹接口 G1 名义口径DN25 032 螺纹接口 G11/4 名义口径DN32连接方式F 内螺纹 (母接头)M 外螺纹 (公接头)FL 法兰连接式Q软管快速接头(订货时需备注软管内径)配电明细D 直流配电24V±20%DCW 交流配电220V±15%ACZ 交流配电380V±15%ACG 交直流通用型(无LED报警灯)材质描述P POM加强塑料过液本体A 阳极氧化铝过液本体B 青铜合金结构过液本体K 316L不锈钢过液本体报警设定区间min.正常流量小于等于5L(特定客户备选项)008设定范围:0.6…8L/min (下线报警0.1…7L/min)015 设定范围:1…15L/m in028 设定范围:2…28L/min070 设定范围:27…70L/min电气连接方式C1 直接附线1米C2 直接附线2米CN 直接附线客户指定线长(特殊备选项)VARIO /HT 耐高温160℃(材质为不锈钢时可选)。

阀门选型配置技术手册指导书.docx

阀门选型配置技术手册指导书.docx

阀门选型配置技术手册为了规范给排水、消防水、空调水系统常用阀门的选型与配置,明确相关阀门的技术要求,指导各项目公司对阀门集采清单列项的选用,特制订本技术手册, 包含的阀门类别有:蝶阀、闸阀、浮球阀、止回阀、过滤器、倒流防止器、减压阀、泄压阀、截止阀、软接头。

本手册适用范围为万达广场各业态。

一、根据各管道系统以及阀门特点的不同,确定阀门配置标准如下,并附图示。

A、铜制阀门(公称压力1.6Mpa)适用于公称直径DN<50的管道系统,其中1、给水系统(生活冷水系统、热水系统、中水系统)1)管径VDN25的管道上:若有流量调节要求时,选用铜截止阀;否则,选用铜闸阀;2)管径DN32VDNVDN50的管道上:铜闸阀。

2、消防水系统(包括消火栓系统、喷洒系统、消防水泡系统):1)管径<DN50的管道上:铜闸阀。

3、空调水系统:1)管径DNW25的管道上(连接风机盘管的支管):铜闸阀或铜球阀;2)管径32<DN<5。

的管道上:采用铜闸阀;3)风机盘管进出水处:不锈钢波纹连接管。

4、采暖系统:1)管径VDN25的管道上:若有流量调节要求时,选用铜截止阀;否则,选用铜闸阀;2)管径32WDN <50的管道上:铜闸阀;3)采暖入户小室采用黄铜锁闭闸阀。

5、蒸汽系统1)管径DNW5。

的管道上:采用铜截止阀。

B、钢制阀门(球墨铸铁或铸钢类)适用于公称直径DN>65的管道系统,其中-)公称压力1.6MPa钢制阀门Is给水系统(生活冷水系统、中水系统):1)泵房外管道上:暗杆式弹性座封闸阀;2)泵房内管道上:明杆式弹性座封闸阀;3)生活水箱补水处:100X遥控浮球阀;4)水泵出水端:300X缓闭止回阀;5)水泵进水端:丫型过滤器;6)生活水泵进出水处:不锈钢软接头;7)中水水泵进出水处:橡胶软接头;8)分区供水需减压时,选用200X减压阀;9)市政给水接驳处水表附近:倒流防止器。

2、生活热水系统锅炉房及换热站一次水侧:1)热水锅炉进出水管道的第一个阀门:铸钢截止阀;2)循环水泵进出水处:不锈钢软接头;3)循环水泵出水端的止回阀可根据设计要求进行选定。

FlowCon 可调自动流量控制阀

FlowCon 可调自动流量控制阀

FlowCon K可调压自动流量控制阀FlowCon KFlowCon K 系列是为用于不受循环加热或冷却系统内的压力波动影响而设计,始终保持特定流速的恒定流量阀。

FlowCon K 主要用于终端平衡。

选定应用所需的流速,其他都交给FlowCon K来处理,即可拋弃耗时且昂贵的手动平衡。

无论是用于空调还是暖气、是终端设备还是支路的平衡、是固定还是可调节的流量,FlowCon K总是能够以最准确和最灵活的方式完全自动的平衡水力系统。

功能和优点- 自动平衡:使每条管路自动地达到正确的流速。

- 动态平衡:因为每个阀门都能对系统中的压力波动作出补偿,所以能够保持正确的流速。

- 无需使用分支或分岐平衡阀:从而减少了每个项目中所用阀门的总数量。

- 易于检修的阀芯:便于调节或维护流速。

- 精度为±5%。

- 压力/温度测量插头:验证操作压差范围。

选配在选择一款FlowCon K阀时,必须先明确以下所需的信息:1)流速,2)压差的范围3)管道的尺寸。

1)流速选择在确定流速时,必须先确定该管路究竟是恒定流量还是可调节的系统。

如果阀门是安装在一个恒定流量的系统中,只需要从流速选择图表(请查阅目录:FlowCon阀芯) 中选择最接近所需要的设计流速。

如果阀门是安装在可调节流量的应用环境(用于调节控制阀系列)中, 只需选择最接近管道最大设计流速的速率。

之后 FlowCon K会将流量限制在这个指定的最大流速以内。

低于最大值时,阀门将作为固定节流装置将极小的压力损耗加入到系统中。

从而让调节阀以最高的阀权度来达到管路的最大设计流速。

对于用作控制水以外流体的应用环境,都需要根据具体的比重、粘度和操作温度进行适当的选择。

阀芯的标准操作环境是使用大约16°C的水。

阀芯的流速可能会受到水以外的其他流体的影响(例如,标准为2升/秒的一个阀门在使用浓度为25%的乙二醇和水的混合液的应用环境中,该阀门的额定流速将调整为1.969升/秒)。

压差式流量开关的安装和使用

压差式流量开关的安装和使用

编号:FS-QG-52884压差式流量开关的安装和使用
Installation and use of differential pressure flow switch
说明:为规范化、制度化和统一化作业行为,使人员管理工作有章可循,提高工作效率和责任感、归属感,特此编写。

压差式流量开关可广泛应用在使用钎焊板式换热器、套管式换热器和壳管式换热器的模块式风冷热泵机组水流量控制并兼有部分防冻保护的功能
压差式流量开关是根据HVAC设备的阻力和流量的曲线设计的。

我们知道HVAC设备的换热器、水过滤器、水泵及阀门等装置都有其阻力与流量的性能曲线,通过检测其两端的进出水压差,并与该装置的预先设定值进行比较,就可以准确控制流量。

压差式流量开关与靶式流量开关相比它是一种精确的流量控制方式,它具有准确的流量控制值。

它直接安装在机组内,避免用户安装不正确的情况出现。

如果在机组内安装从压差开关连接两根铜管至换热器的进出口,测量其进出口的压差,即反映出流量。

而用户现
场不需要安装和接线,也就避免了靶式水流开关的安装不准确导致机组故障的隐患。

压差式流量开关具有流量控制准确、对系统不再额外增加阻力、又对水管管径没有要求以及无水流扰动干扰等特性,可取代任何形式的靶式流量开关作为HVAC水系统的流量控制。

相对于靶式流量开关它可以避免水泵气蚀引起的假流量(实际流速很大,但水中混有空气而实际流量并不大)。

请输入您公司的名字
Foonshion Design Co., Ltd。

AA-0012C-R1.0 阀门选定手册

AA-0012C-R1.0 阀门选定手册

i
本手册的定位
本手册是选定阀门时所需要的资料。 阀门选定手册的定位如下所示。
阀门选定手册
一般事项篇AA-0012C来自ii目录
前言 本手册的组成 本手册的定位 A. 阀门的选定
1. 阀门的型号 ........................................................................................................................... A-1 1.1 各部分的名称 .............................................................................................................. A-1 1.2 按端口数分类 .............................................................................................................. A-2 1.3 按内阀型号分类 ........................................................................................................... A-3 2. 阀门的流量特性 ................................................................................................................... A-8 2.1 快速打开特性 .......................................

阿牛巴流量计-选型说明书

阿牛巴流量计-选型说明书

DPT4阿牛巴流量计Provent technologyHigh accuracyWith display and HARTEEx-certificationsEasy installation and quick start-upinstrumentationunderstanding measurement analysis control integration optimization目 录1、概 述 (1)2、工作原理 (1)3、特 点 (1)4、技术参数 (2)5、传感器结构形式与外形尺寸 (2)6、安装说明 (3)7、阿牛巴流量计的使用与维护 (4)8、包装、运输及储存 (4)9、型号说明 (5)一 、 概 述Fischer&Porter公司DPT4系列阿牛巴流量计由阿牛巴传感器、三阀组、差压变送器等构成。

该流量计具有无可动件的可靠结构、安装维护简单、压损小(仅为孔板的5%以下)、长期运行精度高、稳定性好等特点;可安装于圆形、矩形管路,特别是用于大口径管路;适于各种气体、液体、蒸汽流量的测量,尤其是高温高压流体,如高温高压蒸汽、锅炉引送风,热风炉助燃空气等;广泛应用于石油、化工、天然气、冶金、钢铁、电力、水利、制药、纺织、饮料,能源、环保及城市公用事业等行业。

三、、 特 点特 点二、 工作原理Qv=aεA2ρ△p式 中: △p—— 全压与静压之差(Pa)P1 —— 全压(Pa)P2 —— 静压(Pa)Qv —— 体积流量 (m3/s)α —— 流量系数ε —— 流束膨胀系数A —— 管道内截面面积 (m2)ε —— 压缩系数不可压缩性流体: ε=1可压缩性流体 : ε<1● 结构简单,安装方便,便于维修● 无可动部件,使用寿命长,稳定性好● 压损小(仅为孔板的5%以下),节能效果显著。

● 长期运行精度高、稳定性好● 应用范围广,可安装于圆形、矩形管路,特别是用于大口径管路;适于各种气体、液体、蒸汽流量的测量,尤其是高温高压流体 ;对于具有高密度的尘埃物质的介质,可以使用在线吹扫装置,以保障多种工况下的灵活运用● 范围度与孔板相同,输出差压较低,测量气体流量时,需配微差压变送器● 配备球阀和提升机构,可在线安装、拆卸仪表,不影响工艺流程的正场操作,检测杆清洗方便● 仪表在标准装置上逐台标定出厂,保证了测量精确度。

SLK智能流量开关选型说明书

SLK智能流量开关选型说明书

SLK智能流量开关使用说明泉州日新流量仪器仪表有限公司选型说明SLK智能流量开关采用应变靶式流量计工作原理,可广泛应用于流体过程控制。

其具备可视化的操作控制界面,用户可根据需要自行设定上下限瞬时流量来控制执行机构;报警方式;还可与电动、气动调节阀互控达到智能控制瞬时流量,实现自动控制调节阀门或执行机构,实现系统自动控制。

1、选型含义表头结构 X:普通型:防爆型外壳材料 Z:碳钢:不锈钢:特定材质公称压力 A:常规型≤2.5MPa特殊型>2.5MPa介质温度 C:常温型 +10℃~+70℃:宽温型 -196℃~+250℃高温型 +250℃~+500℃公称口径为管道公称通径单位为mm介质类型 Y:液体:气体连接方式 G:管锥螺纹式F:法兰连接式D:插入式产品代号:SLK智能流量开关2、技术指标连接方式管锥螺纹式法兰管道式插入式公称口径 DN15~50(1/2″~2″) DN15~300 DN100~2000控制方式上、下限瞬时流量限流控制;智能配合调节执行机构控制上、下限瞬时流量实现期段稳流。

精度等级 2.0; 3.0量程比1:10 1:15输出控制两路常开常闭的开关量输出;250VAC/5A操作方式可视化的操作界面,数字控制一目了然显示方式背光液晶显示:当前瞬时流量工作电压 24VDC防护等级 IP65表头型式防爆型(内置按键操作)普通型(外置按键操作)目录一、概述二、工作原理三、技术原理四、按键功能说明五、操作界面功能1、“功能”键操作界面功能2、“切换”键操作界面功能3、“置零”键操作界面功能4、“系数”键操作界面功能a、上限流量报警值设定b、下限流量报警设定c、报警回差值设定d、报警开关量输出状态设定e、小信号切除设定f、流量系数设定g、报警输出信号方式设定六、安装要求七、调整校对1、零点值刷新2、流出系数调整a 、实流校准b、干式(吊重法)瞬时流量基本误差校验Ⅰ砝码挂重的质量换算Ⅱ标准瞬时流量值计算公式Ⅲ瞬时流量值基本误差Ⅳ流出系数修正八、接线图九、应用举例订货咨询一、概述SLK智能流量开关,是采用应变靶式流量计的计量工作原理,为液晶背光显示界面,具备人机可视操作,用户使用一目了然。

差压式流量计设计说明书

差压式流量计设计说明书

一、流量测量的依据1. 流量与差压换算公式依据流体力学公式,对于差压式流量计中流量和差压的关系式可以简化为Q=C 其中0C 即作为本设计中流量系数,修改0C 即可以修正Q 与P ∆的关系。

2. 流量与电流换算公式本设计中流量范围为0~1000L/min ,流量计输出信号4~20mA ,依据流体力学公式和信号转换特点有如下关系式:max Q Q max P I-4=P 16∆∆ 即可得到Q 与I 的关系式:max Q Q 若假设流量为500L/min ,依据计算公式可知,2500I=16+4=8 mA 1000⎛⎫⨯ ⎪⎝⎭二、差压式流量计的结构设计1. 整体结构框图,如图所示2. 电容式差压传感器(差动电容)如图所示,即为一种电容式差压传感器。

当流量计的两路过程压力从测量容室的两侧施加到隔离膜片后,经硅油灌冲液传至中心膜片上,中心膜片是一个边缘张紧的膜片,在压力作用下,产生相应的位移,该位移即形成差动电容变化。

将该差动电容接入一个LC 振荡回路(或LRC 振荡回路)中,差动电容的容值变化将会导致振荡电路的振荡频率改变。

3. f-V 转换电路(频率-电压转换电路)频率电压转换电路可实现频率到电压的转换。

这里选用美国NS 公司生产的精密频率电压转换芯片LM331。

LM331性能价格比高、外围电路简单、可单电源供电、低功耗的集成电路。

LM331动态范围宽达100dB ,工作频率低到0.1Hz 时尚有较好的线性度,数字分辨率达12位。

LM331的输出驱动器采用集电极开路形式,因此可通过选择逻辑电流和外接电阻来灵活改变输出脉冲的逻辑电平,以适配TTL 、DTL 和CMOS 等不同逻辑电路。

LM331可工作在4.0V ~40V 之间,输出可高达40V ,而且可以防止VCC 短路。

这里假设频率范围0~10KHz 进行设计,电路图如图,转换后电压范围0~5V 。

改变Rs 的阻值可以调节转换后电压范围。

()4. 调理电路由于f-V 转换电路后的输出电压已经在0~5V 范围内,故暂不需要放大电路。

差压式流量计(标准孔板)使用说明书

差压式流量计(标准孔板)使用说明书

LGB型差压式流量计(标准孔板)使用说明书开封青天伟业流量仪表有限公司目录一、用途及特点 (1)二、工作原理 (2)三、型号、名称及常规适用范围 (3)四、结构及简图 (3)五、安装与使用 (4)六、供应的成套性和订货须知 (7)七、差压式流量计(标准孔板)订货咨询单 (9)LGB型差压流量计(标准孔板)使用说明书开封青天伟业流量仪表有限公司生产制造的LGB型差压式流量计(标准孔板),其设计安装和使用均符合IS05167国际标准、GB/T2624国家标准。

一、用途及特点1、用途:标准孔板与差压变送器、流量积算仪等配套组成差压式流量计,是安装于管道上进行流量测量的一次元件。

主要用于测量流经圆管道的各种气体(纯净的或含粉尘的)、蒸汽(饱和或过热)和液体(导电或不导电;强腐蚀性;粘稠或含有微小颗粒脏污等)流量。

2、特点差压式流量计(标准孔板)是最早被采用、历史最悠久也是目前用量最大应用最广的流量计,它具有以下优点:1)标准节流装置无须实流标定即可确定其测量精确度。

(目前流量计中的唯一)2)适用被测介质宽广,几乎可用于所有气体、蒸汽和液体的流量测量。

3)管径范围广,DN50~DN800mm(或更大);4)使用压力可高达32MPa;也可用于负压。

5)介质温度范围:-185℃~+650℃,其它流量计尚无可能。

6)非标准节流装置结构型式多样,几乎可适用各种各样流体流量测量。

7)可通过设置差压变送器量程在现场改变流量范围。

8)使用、操作简单、易掌握,日常维护量小。

二、工作原理差压式流量计(标准孔板)测量流量的原理是依据著名的伯努力流体力学原理。

如图(1)所示在管道中安放一只节流件,则有流体流过节流件时会在接节流件两侧产生一个压力差(差压p),这时的流量与差压的平方根成正比即:图(1) 节流装置测量原理体积流量:式中:A——常数C——流出系数β——直径比(=D/d)d——节流件孔径(mm)ε——可膨胀性系数△Pa——节流件前后的差压(Pa)ρ:工况下流体密度(kg/m3)三、型号、名称及常规适用范围本公司生产的LGB型差压式流量计(标准孔板)的型号规格见表(一)表(一)型号、名称及常规适用范围类型型号管径范围(mm)使用流体范围角接(钻孔)取压孔板LGB-Z DN50-DN800 各种温度、压力的气体、液体、蒸汽角接(环室)取压孔板LGB-H DN50-DN800 各种温度、压力的气体、液体、蒸汽法兰取压孔板LGB-F DN50-DN800 各种温度、压力的气体、液体、蒸汽D—D/2取压孔板LGB-J DN50-DN800 各种温度、压力的气体、液体、蒸汽四、结构及简图图2标准孔板的结构及简图图(2)为标准孔板的结构和简图,仅供用户参考五、安装与使用差压式流量计(标准孔板)的使用精确度必须由以下两个方面严格的标准化工作才能得以保证。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

注:其它介质请在定货时说明。

水空气

可调压差式流量开关是为少量使用且对压差值有不同要求时的应用
场合而开发的,常用在工程中检测水过滤器、泵、热交换器、冷水机组及盘管等设备的压差。

当系统中的水流量(压差)上升或下降到设定值时,输出开关信号提供给自控系统。

可调压差式流量开关
也可以用作指示泵或水过滤器的状态。

可调压差式流量开关可以根据客户的要求由工厂直接标定,并在产品标签上打印标定值,用户在现场不需再作调整。

客户也可以根据设备要求的压差通过专业仪表进行标定,ACOL公司可以提供相关的技术服务。

可调压差式流量开关在HVAC应用中与固定压差式流量开关具有相同的性能,它们均是靶式流量开关的替代品,避免了冷水机组每年需检查或更换靶式流量开关的弊病。

可广泛应用在中大型冷水机组蒸发器和冷凝器的水流保护、泵状态反馈以及压差旁通控制。

ACOL公司为满足客户多样化的使用要求,特开发了双可调压差式流量开关,用作压差的上下限控制。

在HVAC系统中用作水冷冷凝器和蒸发器以及其它换热器的流量过少、过大及换热器结垢或污物堵塞造成的流量过少控制。

可选本地指示灯显示状态,具有靶式流量开关无可比拟的优点。

△使用介质温度范围: -20~82℃
△高低压侧连接口: 1/4 SAE(7/16-20UNF)-黄铜材质 、 G1/4-316不锈钢材质可选△最大允许静压: 10bar △最大允许压差: 8bar △设定点重复性偏差: ±1%
△输出形式: 一组SPDT干接点输出,端子排接线 △开关参数: 3A(max.)250V(max.)△外壳防护等级: IP54
1/4 SAE外丝~G1/4外丝
1/4 SAE内丝~φ6卡套接头
1/4 SAE内丝~G1/2外丝
1/4 SAE外丝~G1/2外丝
两头1/4 SAE内丝毛细管组件
注:所有的可选转换接头仅适用于
WFS11...AA和WFS14...AA系列,若需要选用,在订货时加以注明。

A
B C
D
E
G
H
1/4 SAE内丝~φ6气动管接头
F
注:以无压差时为常开型为例,设定点:压差达到此设定值时,开关闭合;回差:开关由闭合到断开的压差差值。

(回差=闭合值-断开值)
注:高压侧和低压侧接口类型必须是一致的。

WFS1系列压差式流量开关是ACOL公司长期从事中央空调研发和工程施工的技术人员,洞悉目前HVAC水系统流量控制产品的诸多弊端而开发的,它是ACOL公司整套HVAC水流量控制产品的一个重要系列,它具有紧凑的外形、卓越的性能和具竞争性的价格是取代任何形式的靶式流量开关的最佳选择。

可广泛应用在使用板式换热器、套管式换热器和壳管式换热器的大中小型风冷或水冷冷水机组中作水流量控制及水泵和水过滤器状态的监控。

对于水流量的测量,可通过测量阀门、孔板等两端的压降,再通过查阀门或孔板的压降和流量曲线即可得到准确的流量,通过压降的方法得到流量,目前已广泛用在HVAC的水侧系统及流量测量仪表。

压差开关在HVAC系统中的应用主要是根据HVAC设备的阻力与流量曲线进行控制的,HVAC中的水侧换热器(套管式、壳管式、管板式和常用的板式换热器)、水过滤器、阀门和水泵等都有其压降与流量的性能曲线,只要将压差开关两侧的测量压差与预先设定值进行比较,就可以准确控制流量。

压差开关用作HVAC中的流量控制具有流量控制准确,对水系统不再额外增加阻力,又对水管管径没有要求以及无水流扰动干扰等特性,可取代任何形式的靶式流量开关,相对于靶式流量开关它可以避免由
水泵气蚀引起的假流量,又有非常准确的复位流量和断开流量。

压差开关用作换热器水流量控制是HVAC系统中最重要的应用,它是替代靶式流量开关的最优的选择。

它具有精确的复位流量和断开流量。

复位流量是检验用户水系统首次开机是否满足要求的最低流量,断开流量是保护用户正在运行时由于错误采用二通电动阀或水过滤器堵塞造成当水流经过过滤器筒体流出,在过滤器产生压力差,随着过滤的进行,压差会升高,当压差达到预设定值时(通常为50kPa)时,压差开关闭合,输出一个开关信号。

如果是自动清洗过滤器,则此信号送到控制盘,控制器执行清洗指令,启动电机或电动阀开始做循环反冲清洗,同时打开排污阀;如果是手动清洗过滤器,则提供警报信号提醒用户清洗过滤器。

自动清洗过滤器
压差式流量开关安装示意图
手动清洗过滤器
压差式流量开关安装示意图通常水泵进出口两端的压差在负荷恒定时是稳定的,当系统中负载的阻力发生变化时,水泵进出口的压差是变化的,水泵两端压差与水泵流量的对应关系可以参照水泵的性能曲线,因此压差开关用作水泵状态检测同时也可以用作控制水泵的最小流量。

当水泵过出口的压差超过压差开关的设定值时,压差开关输出一个干触点信号给自控系统,告知水泵已有流量。

如果我们选择了带指示灯的压差开关,压差开关的本地指示灯将指示水泵的状态变化,压差开关免维修和高可靠性的特性,使其作为替代靶式流量开关用作水泵水流状态的检测得到了众多空调自控工程商的青睐。

水泵状态检测
压差式流量开关安装示意图
板式换热器以体积小、传热效率高,目前已广泛应用在中小型冷水机组中作为蒸发器或冷凝器,但板式热器的特定结构注定要加强对其的防冻保护。

板式换热器冻坏的一个最主要的原因是流经板式换热器的水流量小于额定流量,板式换热器冷媒侧温度低于冰点,造成板式换热器水侧结冰。

大量的试验表明当板式换热器在制冷时通过的水流量小于额定流量的50%就有结冰的危险,因此精确控制板式换热器的水流量不小于额定流量的50%已经成为防冻保护的一项重要措施。

根据板换的压降和流量曲线,查找50%额定水流量下板式换热器的压降,此压降即为板式换热器流量保护的下限压差值,根据此值选择适当的压差开关并安装在整机上进行流量测试验证其流量保护值。

我们建议批量生产的客户选择固定设定点的压差式流量开关,标定其压差或流量值可由ACOL公司在专门的测试设备上完成,这样可以保证您的设定值正确且又避免不正确的改动设定值对设备产生的影响。

对于板式换热器用作冷凝器时,其通过适当的水流量可以确保冷凝压力控制在要求的范围内,有利于机组运行稳定。

板式换热器
压差式流量开关安装示意图
板式换热器压降-流量曲线
套管式换热器
压差式流量开关安装示意图
壳管式换热器在大中型冷水机组中用作蒸发器和冷凝器,对于主机来讲蒸发器和冷凝器的水流量不稳定直接影响主机可靠的工作,因此正确控制壳管式换热器的水流量可确保主机的运行稳定。

我们可以根据壳管式换热器的压降和流量的曲线查找70%额定流量(推荐值)下的压降,ACOL公司认为这个压降是主机流量保护的下限,如果没有压降流量曲线可通过现场测量的方式得到压降值,具体测试方法可向ACOL公司进行相关的技术咨询。

对于壳管式冷凝器我们还建议选择可调双设定点压差开关,其中一个还可用于换热器结垢清洗状态指示,原因是由于换热器结垢造成其进出口压降增加,只要设定适当的压差值并选择本地指示就可以看到当换热器结垢到一定程度时指示灯就点亮,提醒用户
及时清洗换热器,避免由于传热效果下降造成的能源浪费及对主机可靠工作的影响。

壳管式换热器
压差式流量开关安装示意图
壳管式换热器压降图
固定设定流量的压差式流量开关在板式换热器中的应用
压差式流量开关在螺杆机组上
安装示意图。

相关文档
最新文档