Endress+Hauser Liquiline CM44x HART设备软件更新指南说明书
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
for users regarding software updates (following the NAMUR recommendation 53)
Docu Code /22.05.2015
1T y p e o o f d d e v i c e
Field device /signal processing device
Monitoring-/operation system /hand held terminal etc.
Manufacturer
:Endress+Hauser Device
:Liquiline Type
:CM44x Fieldbus /Interface
:Fieldbus HART Device Type 0x119C
2F i r m w a r e , H H a r d w a r e I I
Firmware Hardware I
Old firmware version
:1.05.01New firmware version :1.05.02
How can the previous Firmware /Hardware I version number be identified:
Standard Fieldbus communication,FieldCare/DTM,Display Description of the modification in comparison with the predecessor version:
∙
New language Vietnamese ∙
Activation of service mode by dip switch for fixed IP address ∙
Simple SAC zero point correction implemented ∙
Integration of CLS82D /4pole conductivity sensors ∙
Integration of COS81D /oxygen sensors ∙
Entry of correction factor for CUS51D calibration ∙
Integration of new Ethernet board for simultaneous operation with 6current outputs ∙
Flash frequency adjustable for nitrate and SAC for clear water applications ∙
Field Data Manager Software -online connection implemented ∙
New process value UVT 10mm for UV disinfection applications ∙
Sensor input with HOLD multi-select for multiple cleaning programs ∙
Conductivity concentration tables editable in %or mg/l ∙
Simultaneous measurement of conductivity and concentration ∙
New conductivity concentration table NaOH 25%-50%∙Menu ‘System test’and ‘Reset’split into two menus
for users regarding software updates
(following the NAMUR recommendation53)
3C o m p a t i b i l i t y ((F i r m w a r e, H H a r d w a r e I I)
Is the new Firmware version compatible with the previous version,the installed device drivers,the operating tool compatible/is the new Harware I version compatible with the previous version?
Yes
No,description:
Is a Firmware/Hardware I update generally recommended?
Yes,reason:
The update/exchange can be performed by means of…
•SD card
No,reason:
Update only necessary,if function enhancements are desired.
4I n s t r u c t i o n m m a n u a l
Is a new instruction manual necessary due to the modification of the software?
Yes
No
Which manual corresponds to the new firmware and/or hardware I:
CM44x All BA00444CEN.pdf
BA01245CEN.pdf Operating instruction Liquiline Operating instruction Memosens
The new instruction manuals can be referred in Internet:
-area…DOWNLOAD“
-declaration of the device and kind of manual 5P r i c e
Change in price of device in comparison with the predecessor version?
for users regarding software updates
(following the NAMUR recommendation53)
Yes,new list price and update costs(without installation)are enclosed No。