麦克维尔离心机组通讯协议(MODBUS)离心机点表

麦克维尔离心机组通讯协议(MODBUS)离心机点表

ED15063-2Group : Controls Part Number: ED 15063Date : December 2005Supersedes: ED15063-1© 2005 McQuay InternationalMicroTech II®Chiller Unit Controller Protocol InformationModbus ® Protocol• WSC Water-Cooled Centrifugal, Single-Compressor • WDC Water-Cooled Centrifugal, Dual-Compressor • WPV Water-Cooled Centrifugal, Single-Compressor• HSC Water-Cooled Single-Compressor Centrifugal, Heat Recovery • HDC Water-Cooled Dual-Compressor Centrifugal, Heat Recovery • TSC Water-Cooled Single-Compressor Centrifugal, Templifier • WMC Water-Cooled Centrifugal, Magnetic Bearing • WCC Water-Cooled Centrifugal, Counterflow • AGZ Air-Cooled Global Scroll• ACZ Air-Cooled Scroll Condensing Unit • WGZ Water-Cooled Global Scroll • AGS Air-Cooled Global Screw • WGS Water-Cooled Global ScrewTable of ContentsTABLE OF CONTENTS (2)L IMITED W ARRANTY (4)N OTICE (4)R EVISION H ISTORY (4)S OFTWARE R EVISION (4)R EFERENCE D OCUMENTS (4)INTRODUCTION (5)C HILLER M ODELS (5)C ONTROLLER D ATA P OINTS (5)MODBUS PROTOCOL INFORMATION (6)C OMPATIBILITY (6)P ROTOCOL D EFINITIONS (6)V ALID F UNCTION C ODES (6)V ALID E RROR C ODES (6)M ODBUS D ATA P OINT (7)E XAMPLE D ATA P OINT: C HILLER O N O FF (7)C ONFIGURING THE U NIT C ONTROLLER (7)TYPICAL APPLICATION: MINIMUM INTEGRATION (8)S ET UP THE U NIT FOR N ETWORK C ONTROL (8)D ISPLAY I MPORTANT D ATA P OINTS (8)COMPREHENSIVE DATA POINT TABLES (9)M ODBUS D ATA P OINTS (9)DETAILED DATA POINT INFORMATION (11)A CTIVE S ETPOINT (12)A CTUAL C APACITY (12)C APACITY L IMIT O UTPUT (12)C APACITY L IMIT S ETPOINT (12)C HILLER E NABLE (12)C HILLER L IMITED (12)C HILLER L OCAL/R EMOTE (13)C HILLER M ODE O UTPUT (13)C HILLER M ODE S ETPOINT (13)C HILLER O N O FF (13)C HILLER S TATUS (13)C OMPRESSOR C URRENT (13)C OMPRESSOR D ISCHARGE T EMPERATURE (14)C OMPRESSOR P ERCENT RLA (14)C OMPRESSOR P OWER (14)C OMPRESSOR R UN H OURS (14)C OMPRESSOR S ELECT (15)C OMPRESSOR S TARTS (15)C OMPRESSOR S UCTION L INE T EMPERATURE (15)C OMPRESSOR V OLTAGE (15)C ONDENSER E NTERING W ATER T EMPERATURE (16)C ONDENSER F LOW S WITCH S TATUS (16)C ONDENSER L EAVING W ATER T EMPERATURE (16)C ONDENSER P UMP R UN H OURS (16)C ONDENSER R EFRIGERANT P RESSURE (16)C ONDENSER S ATURATED R EFRIGERANT T EMPERATURE (16)2 ED 15063-2C ONDENSER W ATER F LOW R ATE (16)C ONDENSER W ATER P UMP S TATUS (17)C OOL S ETPOINT (17)E VAPORATOR E NTERING W ATER T EMPERATURE (17)E VAPORATOR F LOW S WITCH S TATUS (17)E VAPORATOR L EAVING W ATER T EMPERATURE FOR U NIT (17)E VAPORATOR L EAVING W ATER T EMPERATURE FOR C OMPRESSOR (17)E VAPORATOR P UMP R UN H OURS (17)E VAPORATOR R EFRIGERANT P RESSURE (18)E VAPORATOR S ATURATED R EFRIGERANT T EMPERATURE (18)E VAPORATOR W ATER F LOW R ATE (18)E VAPORATOR W ATER P UMP S TATUS (18)H EAT R ECOVERY E NTERING W ATER T EMPERATURE (18)H EAT R ECOVERY L EAVING W ATER T EMPERATURE (18)H EAT S ETPOINT (18)I CE S ETPOINT (19)L IQUID L INE R EFRIGERANT P RESSURE (19)L IQUID L INE R EFRIGERANT T EMPERATURE (19)O IL F EED P RESSURE (19)O IL F EED T EMPERATURE (19)O IL S UMP P RESSURE (19)O IL S UMP T EMPERATURE (19)O UTDOOR A IR T EMPERATURE (20)P UMP S ELECT (20)R UN E NABLED (20)ALARMS (21)A LARM C LASSES (21)F AULT A LARMS (21)P ROBLEM A LARMS (21)W ARNING A LARMS (21)A LARM H ANDLING (21)A LARM D IGITAL O UTPUT (21)C LEAR A LARMS (21)A CTIVE A LARMS (22)INDEX OF DETAILED POINT INFORMATION (26)3 ED 15063-2Limited WarrantyConsult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to .Notice© 2005 McQuay International, Minneapolis MN. All rights reserved throughout the world.McQuay International reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this product is appropriate for his or her application.™ ® The following are trademarks or registered trademarks of their respective companies. Modbus is a registered trademark of Gould, Inc. Windows is a registered trademark of Microsoft Corporation. MicroTech II is a registered trademark of McQuay International.Revision HistoryED 15063-0May 15, 2003Preliminary release.ED 15063-1May 18, 2005Added points for Solid State Starter – Current, Voltage, Power and Power FactorCorrected some incorrect register listingsChanged doc to have only Holding Registers and CoilsAdded WGS and WMC dataAdded WMC, HSC HDC, and TSC to front page and Chiller Model tableED 15063-2Nov 22, 2005Added WCC to front page and Chiller Model tableCorrected Modbus Alarms tableAdded Compressor Current, Compressor Power and Compressor Voltage to theCompressor Select TableSoftware RevisionThis edition documents all versions of the standard MicroTech II® Chiller Unit Controller firmware and all subsequent revisions until otherwise indicated.Reference DocumentsCompany Number Title SourceMcQuay International IOMM WSC WDC The McQuay DISTINCTION Series Single/Dual CompressorCentrifugal Chillers Installation, Operating and Maintenance Manual McQuay International OM CentrifMicro II MicroTech II Controller for Centrifugal Chillers and TemplifiersOperating ManualMcQuay International IM 743MicroTech II Chiller Unit Controller Modbus Communication ModuleInstallation ManualMcQuay International IMM AGSIMM AGSB GeneSys? Air-Cooled Screw Compressor ChillerMcQuay International IOMM ACZ/AGZ Air-Cooled Scroll Condensing Unit & Air-Cooled Scroll Chillerw/Remote Evaporators Installation, Operation, and Maintenance ManualMcQuay International IOMM ACZ Air-Cooled Scroll Condensing Unit Installation, Operation, andMaintenance Manual McQuay International IOMM AGZIOMM AGZ1Air-Cooled Scroll Compressor Chiller & Air-Cooled Scroll CompressorWater Chiller Installation, Operation, and Maintenance ManualMcQuay International IOMM WGZ Water-Cooled Scroll Compressor Chiller Installation, Operation andMaintenance ManualMcQuay International IOMM WPV WPV Centrifugal Compressor Chillers Installation, Operating andMaintenance ManualMcQuay International OM AGS GeneSys? Air-Cooled Screw Compressor Chiller Operation Manual McQuay International IOMM TSC MicroTech II Templifier Single Compressor CentrifugalInstallation, Operation, and Maintenance ManualGould, Inc.Modbus® Application Protocol Gould, Inc.Modbus Over Serial Line 4 ED 15063-2IntroductionThis document contains the necessary information to incorporate a MicroTech II Chiller Unit Controller from McQuay International into your Building Automation System (BAS). It includes all necessary Modbus? variables and corresponding MicroTech II Chiller Unit Controller data points. Modbus terms and principles are not defined. Refer to the appropriate specifications for definitions and details.Chiller ModelsThe following table lists the model designators of McQuay International Chiller units and the corresponding description. WSC Water-Cooled Centrifugal, Single-CompressorWDC Water-Cooled Centrifugal, Dual-CompressorWPV Water-Cooled Centrifugal, Single-CompressorHSC Water-Cooled Single-Compressor Centrifugal, Heat RecoveryHDC Water-Cooled Dual-Compressor Centrifugal, Heat RecoveryTSC Water-Cooled Single-Compressor Centrifugal, TemplifierWMC Water-Cooled Centrifugal, Magnetic BearingWCC Water-Cooled Centrifugal, CounterflowAGZ Air-Cooled Global ScrollACZ Air-Cooled Scroll Condensing UnitWGZ Water-Cooled Global ScrollAGS Air-Cooled Global ScrewWGS Water-Cooled Global ScrewController Data PointsThe MicroTech II Chiller Unit Controller contains data points or unit variables that are accessible from three different user interfaces: the unit keypad/display, the Operator Interface Touch Screen, or a Modbus serial network. Not all points are accessible from each interface. This manual lists all important data points and the corresponding network path for each applicable interface. Refer to the applicable Operation Manual for keypad/display and Operator Interface Touch Screen details. See Reference Documents on page 4 for manual part numbers.5 ED 15063-2Modbus Protocol InformationCompatibilityThe MicroTech II Chiller Unit Controller can be configured in an interoperable Modbus network. The controller must have the corresponding Modbus Communication Module installed.The MicroTech II Chiller Unit Controller conforms to the Modbus Standards published at . See the Reference Documents on page 4.Protocol DefinitionsThe Modbus protocol is a standardized Application Level (OSI Level 7) protocol used in interoperable Industrial Control networks. Modbus provides the communication infrastructure necessary to integrate products manufactured by different vendors and to integrate control services that are now independent.It specifies how requests from the client are sent to a server and how servers reply. The client constructs a PDU (protocol data unit) and sends it to a specific server or broadcasts it to all servers. The PDU contains a function code that defines the action the client is requesting from the server(s). The PDU also includes a data field that further defines the action to the server, for example, the location of the data to be read.A normal reply from a server includes the same function code and a response data field. In the case of a read operation, the response data field contains the requested data. In the case of a write operation, the response data field contains an echo of the write data of the request command. If the server detects an error in the transmission, the reply to the client includes and exception function code and the response data field contains an exception code.Controllers can communicate on standard Modbus networks using one of two transmission modes: ASCII or RTU. Users select the serial port communication parameters (baud rate, parity mode, etc), during configuration of the controller. The mode and serial parameters must be the same for all devices on a Modbus network. Transmission mode determines how information is packed into the message fields and decoded. In RTU mode, each byte contains two hexadecimal characters, and in ASCII mode, each byte contains one ASCII character. The MicroTech II Chiller Unit Controller uses the RTU mode only.The MicroTech II Chiller Unit Controller uses the following data structure: 8 data bits, 1 or 2 stop bits, and no parity bit. It uses data transmission rates from 1200 to 19200 bps.Valid Function CodesThe MicroTech II Chiller Unit Controller supports eight public function codes.Function Code Description Definition01 (0x01)Read Coils This function code reads status from 1 to 2000 contiguous coils in a remote device.02 (0x02)Read Discrete Inputs This function code reads status from 1 to 2000 contiguous discrete inputs in a remote device.03 (0x03)Read Holding Registers This function code reads the contents of a contiguous block of holding registers in a remote device.04 (0x04)Read Input Registers This function code reads from 1 to approx. 125 contiguous input registers in a remote device.05 (0x05)Write Single Coil This function code writes a single output to either ON or OFF in a remote device.06 (0x06)Write Single Register This function code writes a single holding register in a remote device.15 (0x0F)Write Multiple Coils This function code forces each coil in a sequence of coils to either ON or OFF in a remote device.16 (0x10)Write Multiple Registers This function code writes a block of contiguous registers (1 to approx. 120 registers) in a remote device.Valid Error CodesThe MicroTech II Chiller Unit Controller supports three error or exception codes.6 ED 15063-2Error Codes Description Definition01Illegal Function The function code received in the query is not an allowable action for the server (or slave). 02Illegal Data Address The data address received in the query is not an allowable address for the server (or slave). 03Illegal Data Value A value contained in the query data field is not an allowable value for server (or slave). Modbus Data PointEach data point accessible from a Modbus network is described with a table that gives the data type and index. If the data point represents an enumerated variable, the enumerations are also listed.Example Data Point: Chiller On OffThis output network variable indicates the current state of the chiller. The OFF state is represented by 0, and the ON state is represented by 1. (D2)Data Type Index Measurement Units Valid RangeCoil2Chiller State NA 0 = Off (Disable)1 = On (Enable)Data TypeData is represented as either single-bit elements or 16-bit elements. A single-bit element is referred to as a Discrete Input when it refers to read-only data and as a Coil when it refers to read-write data. A 16-bit element is referred to as a Input Register when it refers to read-only data and as an Holding Register when it refers to read-write data.IndexThere can be as many as 65,536 elements of each data type in a Modbus device. Data elements are numbered from 1 to 65,536 in each type. Data elements are addressed with an index in the range from 0 to 65,535. The index is not the address of the data element in the unit controller memory. The index is used in Modbus PDUs to specify the location the data in the unit controller. This means, for example, that data element number 1 is addressed using index 0 in the PDU. Valid RangeSome properties are standard data types and some are enumerated sets. If the property value represents a range of values, e.g., temperature or pressure, a range of values is given. If the property value is an enumerated set, all enumerated values and corresponding meaning are given.Configuring the Unit ControllerThe MicroTech II Chiller Unit Controller and the Modbus Communication Module together are designed, programmed, and configured at the factory to be a chiller unit controller accessible over a Modbus network. No additional programming is required to make this a chiller unit controller. The unit controller is ready to operate with the default values of the various parameters set at the factory. Default values may be changed with the unit keypad or via the network. Parameters must be adjusted to accommodate your particular network. See the appropriate Operation Manual for default values and keypad operating instructions and the Modbus Communication Module Installation Manual (see Reference Documents section for manual part numbers.)7 ED 15063-2Typical Application: Minimum IntegrationWhen you have integrated the unit into your network, you can monitor and control unit operation from your workstation. At a minimum, you can:• Display and monitor data points• Turn the unit on or off• Operate the unit safelySet up the Unit for Network ControlSetup for Centrifugal Chiller MicroTech II Network Control:1.Disable the chiller. The chiller should not be operating while performing this setup.2.At the chiller touch screen interface panel:a.In the SETPOINTS MODE screen, set the #9 setpoint, BAS Protocol to Modbus. Use the Operator Passwordof “2001.”b.In the SETPOINTS MODE screen, set the #3 setpoint, Control Source to Local3.Verify with the chiller/control company technician that the chiller is operational on BAS.4.In the SETPOINTS MODE screen, set the #3 setpoint, Control Source to BAS.Setup for all Other Chillers MicroTech II Network Control:1.Set the Set Unit Setpoint screen 1 initially to Source = Keypad.2.Verify that Modbus is selected as the Protocol in the applicable menu screen shown in the table below.3.Verify with the chiller/control company technician that the chiller is operational on a BAS.4.Set the Unit Setpoint screen 1 to Source = Network.Model AGZ-A ACZ-A AGZ-B ACZ-B AGS-B AGS-C WGS WGZMenu Screen969712141510Password20012001200120018945845387452001NOTE: Models AGZ-A/B, ACZ-A/B, and WGZ have one unit controller, while models AGS-B/C and WGS have one unit controller and multiple circuit controllers. Unit settings for AGS-B/C and WGS models are adjusted on the unit controller.Display Important Data PointsTypical workstation displays of MicroTech II Unit Controller attributes include the following significant data points (page number of detailed description in parenthesis). Each data point is identified with a number that also identifies it in the Comprehensive Data Point Tables. These data points are also shaded in the comprehensive tables so that you can distinguish them. References in the text of this section also identify these data points with a number and shading.Table 1: Significant Data PointsNo.Configuration No.Temperatures No.Setpoints No.Alarms1Chiller Status (12)5Evaporator EnteringWater Temperature (16)9Cool Setpoint (16)11Alarm Digital Output(20)2Chiller Mode Set-point(12)66 Evaporator LeavingWater Temperature (16)10Capacity Limit Setpoint(11)12Clear Alarms (20)3Actual Capacity (11)7Condenser EnteringWater Temperature (15)13Active Alarms (21)4Chiller Enable (11)8Condenser Leaving Water Temperature (15)You can display any number of additional data points based on job requirements or individual preference. See Modbus Data Points on page 7 for lists of all Modbus Variables available to the network. For a more detailed description of all available data points, see the Detailed Data Point Information section on page 11 of this document.8 ED 15063-2Comprehensive Data Point TablesModbus Data PointsChiller VariablesNote: See the appropriate Operation Manual for specific data ranges and default values.Network Control Property Page Read/WriteData Type DescriptionActive Setpoint12R Holding Register-40°- 199°FActual Capacity (3)12R Holding Register0 - 160%Capacity Limit (Output) (10)12R Holding Register0 - 160%Capacity Limit Setpoint (10)12W Holding Register0 - 160%Chiller Enable (Input) (4)12R/W Coil0=Off, 1=OnChiller Limited12R Coil0=Not Limited, 1=LimitedChiller Local/Remote13R Coil0=Remote, 1=LocalChiller Mode Output13R Coil1=ICE, 2=COOL, 3=HEATChiller Mode Setpoint13R/W Holding Register1=ICE, 2=COOL, 3=HEATChiller On Off13R Coil0=Chiller Off, 1=Chiller On*Chiller Status (1)13R Holding Register1=Off, 2=Start, 3=Run, 4=Pre-Shutdown,5=ServiceCompressor Current13R Holding Register0 - 65,535Compressor Discharge Temperature14R Holding Register-460°- 621°FCompressor Percent RLA14R Holding Register0 -110%Compressor Power14R Holding Register0 - 65,535Compressor Run Hours14R Holding Register0 - 65,535Compressor Select15R/W Holding Register See page 13Compressor Starts15R Holding Register0 - 65,535Compressor Suction Line Temperature15R Holding Register-40°- 244°FCompressor Voltage15R Holding Register0 - 65,535*Condenser Entering WaterTemperature (7)16R Holding Register-40° - 244°FCondenser Flow Switch Status16R Coil0=No Flow, 1=Flow*Condenser Leaving WaterTemperature (8)16R Holding Register-40° - 244°FCondenser Pump Run Hours16R Holding Register0 - 65,535Condenser Refrigerant Pressure16R Holding Register-3276.8 – 3276.7 psiCondenser Saturated RefrigerantTemperature16R Holding Register-40° - 244°FCondenser Water Flow Rate16R Holding Register0 - 65,535Condenser Water Pump Status17R Coil0=Pump Off Request, 1=Pump On Request *Cool Setpoint (9)17R/W Holding Register10? - 120°F*Evaporator Entering WaterTemperature (5)17R Holding Register-40° - 244°FEvaporator Flow Switch Status17R Coil0=No Flow, 1=FlowEvaporator Leaving Water Temperaturefor Unit(6)17R Holding Register-40° - 244°F*Evaporator Leaving WaterTemperature for Compressor17R Holding Register-40° - 244°FEvaporator Pump Run Hours17R Holding Register0 – 65,535Evaporator Refrigerant Pressure18R Holding Register-3276.8 – 3276.7 psiEvaporator Saturated RefrigerantTemperature18R Holding Register-40° - 244°FEvaporator Water Flow Rate18R Holding Register0 - 65,535Evaporator Water Pump Status18R Coil0=Pump Off Request, 1=Pump On Request Heat Recovery Entering WaterTemperature18R Holding Register-40° - 244°FHeat Recovery Leaving WaterTemperature18R Holding Register-40° - 244°FHeat Setpoint18R/W Holding Register 50° - 120°F9 ED 15063-2Network Control Property Page Read/WriteData Type DescriptionIce Setpoint19R/W Holding Register15? - 35°F, Default=25°F Liquid Line Refrigerant Pressure19R Holding Register-22592 - 22591 psiLiquid Line Refrigerant Temperature19R Holding Register-40°- 244°FOil Feed Pressure19R Holding Register-22592 - 22591 psiOil Feed Temperature19R Holding Register-40° - 244°FOil Sump Pressure19R Holding Register-22592 - 22591 psiOil Sump Temperature19R Holding Register-40° - 244°FOutdoor Air Temperature20R Holding Register-40° - 244°FPump Select20R/W Coil0=Pump No. 1, 1=Pump No. 2 Run Enabled20R Coil0=OFF, 1=Run Allowed*Boldface indicates data points required for typical minimum integration.Chiller Alarm VariablesNetwork Control Property Page Read/WriteData Type DescriptionAlarm Digital Output (11)21R Coil0-No Alarm, 1=AlarmClear Alarms (12)21R/W Coil0=Normal, 1=Clear AlarmActive Alarms (13)22R Holding Register16 Holding Registers: Each bit representing analarm condition10 ED 15063-2Detailed Data Point InformationThis section lists the information (the data) that is available to the Industrial Control System via the Modbus RTU protocol. This information is used to safely operate and log the performance of the chiller. The systems integrator also uses this information when creating custom graphics.Table 2: Data Points for Chiller ModelsData Point WSC/WDC/WPV/WMC/WCC/HSC/TSC/HDCAGZ ACZ WGZ AGS WGSActive Alarms X X X X X X Active Setpoint X X X X X Actual Capacity X X X X X X Alarm Digital Output X X X X X X Capacity Limit Output X X*X*X X X Capacity Limit Setpoint X X*X X X X Chiller Enable X X X X X X Chiller Limited X X*X*X X X Chiller Local/Remote X X X X X X Chiller Mode Output X X X X X X Chiller Mode Setpoint X X X X X Chiller On Off X X X X X X Compressor Current***X X Compressor Discharge Temperature X X X Compressor Percent RLA XCompressor Power***X X Compressor Run Hours X X X X X X Compressor Select X X X X X X Compressor Starts X X X X X X Compressor Suction Line Temperature X X X Compressor Voltage***X X Condenser Entering Water Temperature X X Condenser Flow Switch Status X X Condenser Leaving Water Temperature X X Condenser Pump Run Hours XCondenser Refrigerant Pressure X X X X X X Condenser Saturated Refrigerant Temperature X X X X X X Condenser Water Flow Rate XCondenser Water Pump Status X X Cool Setpoint X X X X X Evaporator Entering Water Temperature X X X Evaporator Flow Switch Status X X X X X X Evaporator Leaving Water Temperature forCompressorXEvaporator Leaving Water Temperature for Unit X X X X X X Evaporator Pump Run Hours XEvaporator Refrigerant Pressure X X X X X X Evaporator Saturated Refrigerant Temperature X X X X X X Evaporator Water Flow Rate XEvaporator Water Pump Status X X X X X Heat Recovery Entering Water Temperature XHeat Recovery Leaving Water Temperature XHeat Setpoint XIce Setpoint X X X X X Liquid Line Refrigerant Pressure XLiquid Line Refrigerant Temperature X XNetwork Clear Alarm X X X X X X Oil Feed Pressure**XOil Feed Temperature**XOil Sump Pressure**XOil Sump Temperature**XOutdoor Air Temperature X X XPump Select XRun Enabled X X X X X *Dual circuit models only**Not in WMC model***Optional. Solid State Starter requiredActive SetpointThis output network variable indicates the current value of the setpoint temperature used to control the temperature of the Leaving Chilled Water or Leaving Hot Water. Based on the operating mode of the chiller, this value is derived from the Cooling Setpoint or the optional Heating Setpoint. The default mode is Cooling and is used unless changed by the Mode input. (A2)Data Type Index Measurement Units Valid Range Holding Register40003Temperature°F x 10-40°-199°FActual CapacityThis output network variable indicates the percent of capacity the chiller is currently producing. It may be more or less than the nominal capacity of the chiller. (A10)Data Type Index Measurement Units Valid Range Holding Register40011Percent of chiller capacity% x 100% to 160%Capacity Limit OutputThis output variable is a measure of the ratio of operating capacity to full capacity expressed in percent. This level may be adjusted via an operator workstation or other network device, but cannot be adjusted above a factory-specified limit. It indicates the current value of the Capacity Limit (Input) data point. (A42)Data Type Index Measurement Units Valid Range Holding Register40043Percent of maximum capacity% x 100% to 160%.Capacity Limit SetpointCapacity Limit is a measure of the ratio of operating capacity to full capacity expressed in percent. The variable can set the operating value (input). This input network variable sets the maximum capacity level of the chiller. This level may be adjusted via an operator workstation or other network device, but cannot be adjusted above a factory-specified limit.(A3).Data Type Index Measurement Units Valid Range Holding Register40004Percent of maximum capacity% x 100% to 160%.Chiller EnableThe Chiller Enable data point starts the chiller in a particular way. (D1)Data Type Index Measurement Units Valid RangeCoil2Chiller State NA 0 = Off (disable)1 = On (enable)Chiller LimitedThis output network variable indicates the main running mode and states of the Chiller. The Limited network variable indicates whether conditions may exist that prevent the chiller from reaching setpoint. (D6)Data Type Index Measurement Units Valid RangeCoil7Status NA 0 = Not Limited1 = LimitedChiller Local/RemoteThe Local/Remote network variable indicates whether the chiller is in local control or allowed to be controlled remotely over the network. (D5)Data Type Index Measurement Units Valid RangeCoil6Mode NA 0= Remote 1 = LocalChiller Mode OutputThis output data point indicates the current operating mode of the chiller. (I19)Data Type Index Measurement Units Valid RangeCoil40148HVAC Mode NA 1. ICE2. COOL3. HEATChiller Mode SetpointThe Chiller Mode data point sets the mode of operation of the chiller and provides the ability for another node on the network to place a chiller in another mode. (I17)Data Type Index Measurement Units Valid RangeHolding Register40146HVAC Mode NA 1. ICE2. COOL3. HEATChiller On OffThis output network variable indicates the current state of the chiller. The OFF state is represented by 0, and the ON state is represented by 1. (D2)Data Type Index Measurement Units Valid RangeCoil3Chiller State NA0 = Off 1 = On Chiller StatusThis output network variable indicates the main running mode and states of the Chiller. The mode provides the primary running states of a chiller and the state provides an indicator of other conditions present. (I18)Data Type Index Measurement Units Valid RangeHolding Register40147Chiller State NA 1. Off2. Start3. Run4. Pre Shutdown5. ServiceCompressor CurrentThis output network variable indicates the compressor current of the compressor selected with Compressor Select on page 15. (A26)Data Type Index Measurement Units Valid Range Holding Register40027Electric Current Amperes0 -65,535。

离心式冷水机组操作维护手册(麦克维尔)教材

离心式冷水机组操作维护手册(麦克维尔)教材

目录介绍概述┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄3 应用┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄3安装机组结构┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄4 收货与起吊┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄8 落位与安装┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄8 水路系统┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄9 水泵┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄9 蒸发器与冷凝器水路┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄9 油冷却器管路┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄10 水冷式油冷却器┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄10 制冷剂冷却油冷却器┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄14 安全排空管道┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄14 电气┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄16 制冷电气系统基本原理┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄16 动力线的接线┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄17 配有启动器的机组动力线的接线┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄19 控制器的接线┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄19 调试控制线路┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄20 保护电容┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄20操作操作者职责┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄22 铭牌┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄22 MicroTech 控制器┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄22 能量控制系统┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄27 导叶操作┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄27 测量值┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄30 导叶速度调整┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄30 油路系统┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄31 油泵┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄32 热气旁通系统┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄34维护例行维护┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄35 润滑油┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄35 更换油过滤器┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄35 制冷循环┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄36电气系统┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄ 39 清洁和保护—┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄39 季节性维护┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄39 一年一次停机┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄40 一年一次开机┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄40 系统检修(如果必要的话)┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄ 41 压力安全阀的更换┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄ 41 抽储┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄41 试压┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄ 41 检漏┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄ 41 抽真空┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄ 42 制冷剂充注┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄ 42表格开机前的机组检查表┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄43维护时间表┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄44离心机组运行日志┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄┄46介绍概述McQuay的PE、WS系列离心式冷水机组在优化的制冷系统匹配的基础上,利用先进的自动控制系统,精确的控制机组在运行中的各个环节,使机组始终处在最佳的运行状态。

麦克维尔空调离心机组开机实操说明材料

麦克维尔空调离心机组开机实操说明材料

市场区离心机开机步骤(一)启动前检查工作:(1)检查冷冻水和冷却水的补水系统是否正常;观察冷冻水、冷却水泵进出水管网压力表上是否有压力,最好大于0.4Mpa,阀门必须打开冷却塔的水位是否正常。

(2)检查冷冻水泵、冷却水泵、冷却塔冷却风机、冷水机组的启动柜或配电柜的电压表,确认供电电源在正常范围内10KV(范围9000V---10KV)。

检查电动机启动柜(机头)检查冷冻泵、冷却泵、冷却塔动力柜、控制柜有无异常(3)检查冷水机组润滑油油位、油温是否正常;注:主机停止运作(超过一个小时)要关闭油泵两个阀门,来电要重新开启,长期不用也要开启。

主机有无泄漏现象或其他异常现象。

(4)确认需要开机的冷水机组号,并检查需要开机的冷水机组冷却水和冷冻水进出口阀门是否完全打开,其他不需要开启的冷水机组进出口阀门是否关闭。

open”(开启)状态,. 检查压力表数值是否有压力。

冷冻水阀门需要六角扳手(二)开机步骤:(1)前往“冷冻机房控制室”开启冷却水泵、冷冻水泵(一二级泵)、冷却塔组4台机组与4台冷却塔编号需一致,下步工作(2)前往“空调补水房”开启冷却塔补水一般情况下已经打自动,先打手动(确认可运行)→自动(3)检查“操作面板”冷却水循环、冷冻水循环等水循环操作完成约10分钟后,点击“输入/出”按钮,观察操作面板查看“冷冻水循环”、“冷却水循环”是否变为绿色,必须灯变绿,方可进行下一步操作!(4)检查“操作面板”上的“油槽温度”达到允许范围,才可下步操作操作:操作面板上的“油槽温度”42℃为宜,上下浮动5℃(即37℃~47℃之间).系统开关向上为开,向下为关操作:先开“系统开关”(活动臂旁,箱子外侧按钮),然后开箱内的“机组开关”,如只开一个压缩机,则只开一个“压缩机开关”(1#或2#)。

如要机组两个机头全部开启,则要将箱内三个开关全开。

注:操作面板如死机。

可拔掉插槽排线、电脑电源线。

重启即可(6)控制面板点击“自动”开启主机操作:等以上操作均正常了,点击“自动”开启主机(三)运行中记录(每两小时查看):(1)观察油泵:液位、是否有杂质(2)记录运行数据(三大项):冷凝器、蒸发器、供油系统点击“蒸发器”,记录右侧罗列数据在主界面,记录“供油系统”数据,包含吸气压力、排气压力。

WMC磁悬浮离心机技术介绍培训

WMC磁悬浮离心机技术介绍培训

磁悬浮式离心压缩机
速度控制
2 stage centrifu 两级叶轮 gal compres sor 压力和温 度传感器 导叶
同步直 流电机
Motor and bearing control
磁悬浮电机驱动技术
可靠的断电保护功能
系统突然断电时,高速旋转的压缩机电机转换为发电机, 为线圈提供电流以产生磁力,承托轴承直到其停止并轻 落在陶瓷轴托上。
1 3 5 7 9 11 13 15 17 19
时间(月)
磁悬浮机组
螺杆机组
离心机组
换热管表面无油,换热效率提高20%
空调系统的投资公式
空调系统总投入=
设备初投资
+ 运行费用
+ 维护费用
IPLV
50% 45% 40% 35% 30% 25% 20% 15% 10% 5% 0% 25% 50% 75% 100% 负荷百分比
国内其他品牌
从事大型冷水机组生产时间短,购 买特灵的压缩机生产普通离心机。 经验少,品牌优势少 在国内拥有少量项目(如深圳的招 商南海意库展厅) 无ARI认证 压缩机本身控制或其他控制公司开 发的控制系统 海尔(4~10)机头、 290~1160冷吨 维修大型冷水机的经验少。但有独 立的具有相关资质的安装公司
轴承系统
两级叶轮
无需油润滑系统
• 不需油系统,可以显著增加机组可靠性 • 不需定期进行油检,保养简单方便
永磁铁
电机
电磁铁
常规螺杆机系统图
常规离心机油路系统图
.
常规离心机制冷剂系统图
.
磁悬浮离心机系统原理图
.
电子膨胀阀精确供液
• 控制步数6386 • 相对普通电子膨胀阀(2000-3000步) 供液控制更精确

麦克维尔磁悬浮离心特点

麦克维尔磁悬浮离心特点

麦克维尔磁悬浮离心特点麦克维尔磁悬浮离心是一种新型的离心机技术,它利用磁悬浮技术将转子悬浮在气膜中,从而实现了高速旋转。

与传统的离心机相比,麦克维尔磁悬浮离心具有以下特点:1. 高速旋转能力:麦克维尔磁悬浮离心的转子可以实现高速旋转,最高转速可达几万转每分钟。

这一特点使得磁悬浮离心在很多领域都有广泛的应用,如制药、生物技术、食品工业等。

高速旋转能力可以大大提高离心过程中的分离效率和产能。

2. 高精度悬浮控制:麦克维尔磁悬浮离心采用磁悬浮技术,通过磁力对转子进行悬浮控制。

这种控制方式可以实现非接触悬浮,并且对转子的悬浮位置进行高精度的控制。

通过精确的悬浮控制,可以有效地减少转子与离心机主体之间的摩擦,降低机械损耗,提高使用寿命。

3. 低振动、低噪音:由于麦克维尔磁悬浮离心的转子悬浮在气膜中,几乎没有与主体接触的部件,因此可以实现非常低的振动和噪音水平。

这对于精密实验和对样品要求比较高的应用非常重要,可以提高实验的可靠性和准确性。

4. 易于清洗和维护:麦克维尔磁悬浮离心的转子与主体之间没有接触,因此转子的清洗变得更加容易。

在传统离心机中,转子与主体接触的部件可能很难清洗,甚至需要经过拆卸才能进行清洗。

而磁悬浮离心的转子可以直接放入清洗液中,大大简化了清洗过程。

此外,磁悬浮离心的结构相对简单,维护成本也较低。

5. 多功能应用:麦克维尔磁悬浮离心具有很强的适应性和灵活性,可以用于多种不同的应用。

除了常见的离心分离外,磁悬浮离心还可以用于凝胶电泳、DNA 提取、核酸纯化等实验室分析和制备的过程中。

通过不同的转子和程序设置,可以实现不同样品的分离和处理,满足不同的实验需求。

总之,麦克维尔磁悬浮离心以其高速旋转能力、高精度悬浮控制、低振动低噪音、易洗涤维护和多功能应用等特点,在科学研究和工业生产中有着广泛的应用前景和价值。

随着科学技术的不断发展,磁悬浮离心将会进一步完善和应用,为相关领域的研究和生产带来更好的效果和效益。

麦克维尔开利离心机技术规范

麦克维尔开利离心机技术规范

机组参数品牌麦克维尔 McQuay ®产地 中国 武汉型式 水冷离心式冷水机组型号 WSC079LAR35F/E2609/C2209每台制冷量 冷吨300耗电指标kW/Ton 0.654输入功率 kW 196.1制冷剂类型HFC—134a 压缩机形式半封闭离心式单机压缩动力传送齿轮增速能量调节范围10%-100%无级调节驱动方式电机驱动防喘振散流滑块与前置导流叶片联动(无热气旁通)供油系统油泵类型齿轮式冷却方式水冷板式换热器油过滤器10μm 紧急润滑系统自动供油蒸发器式样/型号壳管满液式/E2609载冷剂水出口温度℃7进口温度℃12流量m3/h 181.8压降kPa 72.4水侧承压MPa 1.0进出水管公称直径mm DN200污垢系数m 2℃/kW 0.0176换热管壁厚mm 0.635流程数2换热管螺纹加强型铜管保温材料19mm聚乙烯板水接管形式右接冷凝器式样/形式壳管满液式/C2209进口温度℃32出口温度℃37流量m3/h 214.2压降kPa 38.4水侧承压MPa 1.0进出水管公称直径mm DN200污垢系数m 2℃/kW 0.044流程数2换热管材料螺纹加强型铜管换热管壁厚mm 0.635水接管形式右接电气启动形式星—三角配电电源380V/3Ph/50Hz 电机形式鼠笼引入式转速RPM 2980满载电流A 349启动电流A 846电机冷却方式冷媒冷却减震方式9mm避震橡胶减震垫外形尺寸长X宽X高mm 3360X1245X1971机组重量机组重量kg 4518运行重量kg 4987上表中的制冷量根据下述条件而定:冷冻水出水温度7℃;冷冻水进水温度12℃;冷却水进水温度32℃;冷却水出水温度37℃麦克维尔McQuay ®离心式冷水机组技术资料工程名称:设备名称:McQuay ®麦克维尔半封闭单级压缩离心式冷水机组高压保护器及微电脑感应微电脑控制及微电脑感应油压保护器及微电脑感应过载保护器及微电脑感应Surge Guard防喘振装置独有的后备供油系统电压感应保护微电脑控制微电脑控制水流压差控制器微电脑控制微电脑控制最高电量限流及过载保护微电脑控制最高电量限流及过载保护微电脑控制如有非标项目,请在会发生变动相应的选项后打"√",并将该项的参数更改为非标工况离心式冷水机组安全控制及保护措施麦克维尔McQuay ®单螺杆式冷水机组供货范围电气控制屏(马达启动器)电机过载保护电压过高/过低保护相序保护随机技术资料McQuay ®麦克维尔半封闭单级压缩离心式冷水机组MicroTech II 微电脑控制器蒸发器及低温部分原厂保温冷冻水出水温度控制橡胶减震垫冷冻及冷却水系统压差开关进口HFC—134a制冷剂及润滑油压缩机高压保护蒸发器低压保护油压过高/过低保户油泵过载保护重新循环启动超负荷控制压缩机排气温度过高保护水流循环系统联锁负荷过低(喘振状态)电源紧急中断。

麦克维尔PEH进口和国产的离心机组操作维护手册

麦克维尔PEH进口和国产的离心机组操作维护手册

你 的 冷 暖 我 关 怀 , 因 为 专 注 、 所 以 专 业 、 因 为 专 业 、 所 以 卓 越 , 专 门 解 决 疑 难 问 题 , 降 低 费 用 , 有 二 手 空 调 主 机 设 备 租 赁 和 销 售 ( 包 调 试 ) 约 克 YORK、 开 利 Carrier、 特 灵 中 央 空 调 配 件 销 售 、 维 修 保 养 、 安 装 调 试 服 务 热 线 18680288140
3
麦克维尔进口和国产离心式冷水机组安装、操作和维护手册
安装
机组结构:
McQuay 离心式冷水机组具有优越的制冷系统、先进的控制系统和合理的结构 装配。 系统流程结构:
压缩机 压缩
排气
吸气
吸气
冷凝器
高压
低压
蒸发器
节流
前 后

节流机构
图1
机组系统结构流程图
图 2-1
PEH 系列机组结构图
4
你 的 冷 暖 我 关 怀 , 因 为 专 注 、 所 以 专 业 、 因 为 专 业 、 所 以 卓 越 , 专 门 解 决 疑 难 问 题 , 降 低 费 用 , 有 二 手 空 调 主 机 设 备 租 赁 和 销 售 ( 包 调 试 ) 约 克 YORK、 开 利 Carrier、 特 灵 中 央 空 调 配 件 销 售 、 维 修 保 养 、 安 装 调 试 服 务 热 线 18680288140
你 的 冷 暖 我 关 怀 , 因 为 专 注 、 所 以 专 业 、 因 为 专 业 、 所 以 卓 越 , 专 门 解 决 疑 难 问 题 , 降 低 费 用 , 有 二 手 空 调 主 机 设 备 租 赁 和 销 售 ( 包 调 试 ) 约 克 YORK、 开 利 Carrier、 特 灵 中 央 空 调 配 件 销 售 、 维 修 保 养 、 安 装 调 试 服 务 热 线 18680288140

麦克维尔空调机组及技术交流

麦克维尔空调机组及技术交流

专利散流滑防喘振技术; 最低负荷低至5%
R134a环保冷媒
离心产品系列
WSC/HSC
300
1300
WDC
60 0
2560
WSC高压
600
1500
WDC高压
WMC WME
140
300 290
160 0
258 0
R134a
700
TONS
Centrifugal
Page 2
空调的基本构成
空调机组一般由四大部件构成
1、压缩机---压缩冷媒,提供动力
2、蒸发器---蒸发吸热 3、冷凝器----冷凝放热 4、节流元器件---改变压力,控制冷媒流量 对于蒸气压缩式制冷,其工作原理就是使制冷剂
在压缩机、冷凝器、节流阀和蒸发器等热力设备
中进行压缩、放热、接流和吸热四个主要的热力 过程,以完成制冷循环。

大中文触摸屏显示 标配Modbus通讯协议 BAS联网及多机联控 实现远程监控及通信功能 压缩机超前-滞后平衡功能
Page 42
PFS机组机载启动柜
启动柜内,每个压缩机对应一个 空气开关,维护更加方便。
压缩机可以独立维护,减少用户 极端情况下的制冷需求。
每个压缩机对应一组启动装置, 任何一个出现故障时,不影响另 外一台正常运行。
Page 35
Page 36
机组具备抗震改良能力
已有抗震2级的设备的供货经验——中核404核废料处理厂
中国核动力研究设计院的抗震分析认可书
Page 37
ARI认证选型软件
Page 38
ARI认证选型软件
McQuay采用ARI认证的选型软件进行ຫໍສະໝຸດ 型,充分保证的 数据的真实性和可靠性。

麦克维尔空调离心机组开机实操手册

麦克维尔空调离心机组开机实操手册

麦克维尔空调离心机组开机实操手册1. 引言麦克维尔离心机组(以下简称机组)是一种高效、可靠、节能的制冷设备,广泛应用于大型商业建筑、高端酒店、医院、电信机房等场所中。

本文档旨在介绍该机组的开机实操手册,帮助使用者掌握正确的操作流程,确保机组能够正常运行。

2. 开机前的准备工作在启动机组之前,需要进行以下准备工作:2.1 装机确保机组已经完成了安装工作,包括:•圆形管道的安装和连接;•机组和周围环境之间的隔离;•冷凝水管道的布置;•排水系统的设置。

2.2 检查检查机组是否符合以下条件:•通风良好,有足够的空间;•电源充足,电线完整;•弹性支座按规定安装,地脚螺栓拧紧;•环境温度和湿度符合机组的技术要求;•冷却水管路和空气管路连接正确,散热排风良好。

3. 开机操作流程3.1 打开凸轮箱门机组开机前,应当打开凸轮箱门,观察凸轮、连杆、锻件、凸轮轴和连杆轴承等部件是否处于正常状态,无变形等问题。

3.2 启动水泵启动水泵前,先确保水泵联轴器处于分离状态,然后按照以下步骤启动水泵:1.将水泵手动开启电源;2.转动切换开关,将手动模式改为自动模式;3.按下启动按钮,水泵开始启动;4.等待水泵自动完成排气,并确保水泵进水管路畅通无阻。

3.3 开启机组在水泵正常工作后,可以开始启动机组了。

按照以下步骤操作:1.将机组控制器切换至“手动”模式;2.设置机组的开机参数,如供水温度、供水流量等;3.按下“启动”按钮,整机系统开始启动,主电机开始加速;4.观察凸轮箱中各部件的运转情况,确保机组运转平稳。

3.4 监测机组运行情况启动机组后,需要进行实时监测,确保机组运行正常。

常见的监测方法有:•温度监测:观察供水温度、回水温度等参数是否符合机组的技术要求;•压力监测:观察系统水泵的进出口压力,确保机组流量正常;•电气监测:观察机组的用电情况,确保电流稳定;•声音监测:观察机组的运行声音是否正常,无异常响声。

4. 停机操作流程当机组需要停机时,应当按照以下步骤进行停机操作:1.将机组控制器切换至“停机”模式;2.待主电机完全停止后,关闭水泵电源;3.关闭机组的排放阀门以及配气阀门;4.将机组装置加注抗冻液。

高压离心机与380V离心机的比较(麦克维尔)

高压离心机与380V离心机的比较(麦克维尔)

大冷吨冷水机组采用高压电机的科学及合理性离心制冷压缩机额定电压有380V,3KV,6KV,10KV。

采用高压供电对用户可节省投资30%~50%,还能减少维护费用。

大型离心制冷站宜采用高压启动,在机组启动时,启动电流小,对电网的冲击较小;在机组运行时,运行电流小,会节省一定的电能。

选用高压电机的配置方案,可以从整个机房配置、变配电设计及运行费用上,大大的提高建设方的经济效益。

高压电机适用范围。

根据中华人民共和国工业用电规程规定,在电机容量大于200KW 时,电力驱动设备宜选用高压电机。

我国电网标准供电为高压电,离心式冷水机组又适合采用高压电机,所以现在市场上采用高压电机冷水机组的用户已经越来越多。

直接采用高压电机可省去变压器等电器设备投资,减少变压器的运行损耗。

高压电机的启动电流远小于380V电机,可以采用直接启动,其变配电设备、备用发电机的容量可以远小于380V电机,大大减少用户综合投资,也大大减少有色金属材料的使用量。

高压机组与低压机组投资成本及综合性能分析表:综上所述,在电机容量大于200KW时,从冷机整体初投资的经济性、冷机长期运行电费的经济性以及其他供电和用电设备的可靠性来综合考虑,适宜采用高压电机冷水机组的方案,该方案充分考虑了系统的简便性、适应性及节能性各个方面,并有效解决冷水机组启动时对电网存在较大冲击的问题。

目前,国内采用高压机组的项目正呈直线上升趋势,曾得到用户一致好评的项目,主要有:保定英利、韩国SACI SAMSUNG、红沿河核电站、宁德核电站、阳江核电站、大連热电厂、富士康、北汽富田、长城汽车、东风日产汽车等上百家企业用户。

其中富士康集团采购项目亦再次向麦克维尔公司征询高压系统方案。

高压电机冷水机组适宜场合的应用优势之多,代表了较大冷量冷水机组的发展方向,已经成为越来越多客户的首选方案。

高压启动与与低压启动机组的优缺点比较:1、高压启动相对于低压启动的冷水机组相比,机组本身投资将要略大;2、如果计算上相关的变压器(可取消)、电缆(变细了)、桥架(电缆变轻了)、配电室中相关设备(变配电柜不要了)和节约的机房面积,高压启动将占优势;3、高压供电电流小,电路损失小,另外没有变压器,避免了变压器的铜损和和铁损,节省运行费用,而且电流小,运行更安全;4、380V系统需要一个变压器,对电网而言,变压器要吃掉电网的部分无功功率,供电局收费是按10AKV侧的功率因素收费,所以用380V时将要增加许多的功率因素补偿设备投资;5、节约机房面积;6、由于高压启动机组系统大大简化,使安装费用大大降低;7、高压电机效率高,技术成熟,操作简单;。

约克特灵开利麦克维尔离心机讲课文档

约克特灵开利麦克维尔离心机讲课文档
现场连接水管路
需要现场接水管路冷却润滑油, 冷却效果受水温影响,并可能由于断水而停机,降低可靠性
第二十六页,共85页。
麦克维尔复杂的管路,降低机组的可靠性
第二十七页,共85页。
麦克维尔复杂的管路,降低机组的可靠性
第二十八页,共85页。
麦克维尔复杂的电路,降低机组的可靠性
第二十九页,共85页。
麦克维尔复杂的管路,降低机组的可靠性
约克特灵开利麦克维尔离心机
第一页,共85页。
离心机组比较
公司 型号 冷量 19XR3 Eff. (kw/Ton) 19XR4 Eff. (kw/Ton) 19XR5 Eff. (kw/Ton) 制冷剂 噪声
压缩级数
叶轮转速 压缩机数量
电机型式
电机电压 控制显示语言 显示型式 抽气回收装置
制冷剂流量控制
主要特点和优势
R134a 喷液冷却电机 内置润滑油冷却 24V安全控制电压 19XR4带SRD RS485标准接口
开利
约克

╳ ╳
特灵

麦克维尔
╳ ╳
第五页,共85页。
开利
第六页,共85页。
开利
第七页,共85页。
开利离心机组
1、设计主要来源于收购的西屋公司70 年代的技术,最早针对于R12设计的系 统。机组提供分支的制冷系统保证电机 和油冷却器的冷却,内置润滑油冷却装 置,无需现场接水管,管路简洁。 2、全中文显示,并可切换显示包括英文、 日文等多种语言;同时可切换公制和英 制不同单位显示。 16行40各字符液晶显 示。 3、提供远程控制和网络控制。可与开利 舒适网络直接通讯;可实现与其他楼宇 控制系统的通讯;可通过CSM开利冷水 机组管理系统控制管理包括外围水泵、 冷却塔在内的多台机组系统。 4、控制系统电源采用24V安全电压, 5、无需现场安装流量开关。进出水管处 安装有压力传感器,微电脑控制系统通 过压差检测自动识别。无需现场另外安 装机械式流量开关。

麦克维尔离心式冷水机组结构

麦克维尔离心式冷水机组结构

麦克维尔离心式冷水机组结构【最新版】目录一、麦克维尔离心式冷水机组概述二、麦克维尔离心式冷水机组的结构特点三、麦克维尔离心式冷水机组的工作原理四、麦克维尔离心式冷水机组的应用范围及优势五、结语正文一、麦克维尔离心式冷水机组概述麦克维尔离心式冷水机组是一种用于制冷的设备,主要通过压缩制冷剂来实现制冷效果。

离心式冷水机组结构紧凑、运行稳定,广泛应用于商业建筑、工业生产和住宅等领域。

二、麦克维尔离心式冷水机组的结构特点麦克维尔离心式冷水机组主要由压缩机、蒸发器、冷凝器、膨胀阀和控制系统等组成。

其中,压缩机采用离心式压缩技术,具有结构简单、运行平稳、维护方便等特点;蒸发器和冷凝器分别负责吸收冷量和排放热量,以实现制冷效果;膨胀阀则负责调节制冷剂的流量,以保证机组运行稳定。

三、麦克维尔离心式冷水机组的工作原理当麦克维尔离心式冷水机组运行时,压缩机将低温低压的制冷剂吸入,经过压缩后,制冷剂的压力和温度都升高。

高温高压的制冷剂进入冷凝器,释放出热量,冷凝为高压液体。

高压液体经过膨胀阀节流后,压力和温度降低,进入蒸发器吸收冷量,实现制冷效果。

在制冷过程中,制冷剂不断循环流动,实现连续制冷。

四、麦克维尔离心式冷水机组的应用范围及优势麦克维尔离心式冷水机组具有结构紧凑、制冷能力强、运行稳定等优点,广泛应用于商业建筑、工业生产和住宅等领域。

在商业建筑中,离心式冷水机组可用于空调、冷藏、冷冻等系统;在工业生产中,可用于冷却机器设备、降低生产环境温度等;在住宅领域,可用于提供舒适的居住环境。

五、结语麦克维尔离心式冷水机组凭借其结构紧凑、运行稳定、制冷能力强等优点,在多个领域得到了广泛应用。

离心机的维护保养及注意事项及技术交流

离心机的维护保养及注意事项及技术交流

离心机的维护保养及注意事项及技术交流离心机是利用离心力,分别液体与固体颗粒或液体与液体的混合物中各组分的机械。

离心机紧要用于将悬浮液中的固体颗粒与液体分开,或将乳浊液中两种密度不同,又互不相溶的液体分开(例如从牛奶中分别出奶油);它也可用于排出湿固体中的液体,例如用洗衣机甩干湿衣裳;特别的超速管式分别机还可分别不同密度的气体混合物;利用不同密度或粒度的固体颗粒在液体中沉降速度不同的特点,有的沉降离心机还可对固体颗粒按密度或粒度进行分级。

学会合理的维护保养离心机,有利于与延长仪器的使用寿命,节省成本。

保养与维护1、离心机的维护使用水或柔和的清洁剂清洗转子室及转子,不应使用碱性溶液或对材料有磨蚀的溶剂。

使用抹布或镊子移出转子室内的赃物碎片。

离心机未使用时打开顶盖,保持转子室干燥,以避开电机轴承磨损。

有毒、放射性、污染样品时必需有特别的安全保护措施。

2、离心机附件的维护如有离心管显示颜色变化、变形、泄露等必需停止使用。

对离心管进行高温高压消毒时不要拧上管帽,避开管子变形。

每种离心管消毒可耐温度见用户手册此节列表。

离心机尽量与其它用电设备保持确定距离,并有良好的接地措施,且进行定期检查。

离心机和转子不得用高强度UV 辐射或长时间受热。

清洗时应用中性洗涤剂。

如需要,转子可更换。

重新安装后,上紧转头螺钉。

3、转头销钉转头销钉需常常用润滑油润滑,确保离心机运转平稳。

4、冷凝器的维护冷凝器用来冷却冷冻剂,安装于离心机后部,接受风冷方式。

冷凝器应定期清理灰尘,以免传热受阻。

可用压缩空气吹洗此处。

5、转子腔体及附件的灭菌和消毒全部常规的消毒剂都可使用。

由于离心机及附件由不同材料制成,所以必需考虑到消毒剂的相容性。

6、操作检查操应确保离心机紧要部件完好,紧要指:1)电机悬挂稳定2)转轴无偏离3)转子和附件没有腐蚀4)螺钉连接紧固。

此外,地线必需定期检查。

注意事项1、离心机运转前应先切断电源并先松开离心机刹车,可以手试转动转鼓,看有无咬煞情况。

麦克维尔离心式冷水机组电气与控制

麦克维尔离心式冷水机组电气与控制

• 触摸式操作屏 (OITS)
触摸式操作屏(OITS),一个提供每台冷水机组的信息和主要参数设定的输入装置。 无论是单压缩机还是双压缩机冷水机组均只需一个触摸式操作屏OITS。
该屏幕无控制功能。 操作者可以通过安装的OITS监视所有操作条件并进行校正工作。 • • • • • 如果一个错误状况发生,控制器将使压缩机停机并发出报警信号。 新的OITS里面的报警记录可以直接用U盘拷贝。C:/PLAN/Alarms 系统安全保护采用一个只接受被授权进入的密码方案。 密码可通过OITS 或 M2控制器键区输入。 OITS是首选的输入方法。 当设定值需改变时,操作者必须输入正确的密码。
压缩机控制器接收处理和传递数据至其它控制器装置压缩机启动柜或变频器vfd18training菜单键回车键箭头键键屏路径菜单按钮将显示可到达的菜单组路径将指向可到达的菜单组箭头按钮可以选择菜单组回车键按钮执行设定点命令19training20trainingoits21training22training23training24training25training26training动态运行趋势分析可提供rs485接口实现4台压缩机联控usb接口用以数据下载oits27training压缩机e
油泵接触器 控制电源断路器 油泵过载 油泵电容器
信号转换板
24VAC 变压器
电机热保护板
压力变送板
15
Training and Development ©
Micro Tech II (电机热保护板)
热敏电阻接口
输入工作电源
输出信号
电热调节器保险丝
16
Training and Development ©
可选 modem
内部 pLAN 口
相关主题
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

机型 WSC126/850TR WSC126/1000TR WSC126/1200TR WSC126/1200TR WSC126/1098RT WSC126/1000TR WSC100/700TR WSC126/1200TR WSC126/1000TR WSC126/542TR WSC126/1200TR WSC126/1100RT WSC126/1100RT WSC126/1100RT WSC126/1000RT WSC100/1000RT
37℃
38.5℃
32℃
双级压缩WTC高压机
制冷量:1100-1500RT 制冷剂:HFC-134a 双叶轮两级压缩
制冷量 输入功率 COP 满载电流 启动电流 尺寸
RT Kw Kw/kw 直接 直接/电抗/自耦 长*宽*高
1500 816.3 6.04(最高可超过6.4) 59 440/286/185 5009*2807*3024
序号 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
地区 吉林长春 江苏南京 江苏南京 江苏南京 江苏南京 浙江嘉兴 浙江嘉兴 新疆乌鲁木齐 新疆乌鲁木齐 山东烟台 重庆 重庆 深圳 河南郑州 山东济南 山东济南
项目 吉林通海高科 南京华晶电子 南京华晶电子 苏北人民医院 红太阳家居广场 恒诺微电子(嘉兴)有限公司 恒诺微电子(嘉兴)有限公司 华凌广场 新疆美克化工公司 烟台万华聚氨酯公司 四川维尼纶厂 重庆环球石化有限公司 富士康 郑州天隆商贸城 山东西王生化科技公司 山东西王生化科技公司
数量 4 1 1 2 3 1 1 3 2 1 1 3 3 2 3 3
备注 6KV 6KV 6KV 10KV 10KV 6KV 6KV 10KV 6KV 10KV 6KV 10KV 3KV 10KV 10KV 10KV
Page 24
17 18 19 20 21 22 23 24 25 26
湖南衡阳 河北 北京 北京 天津 广州 上海 南京 江苏 上海
目前国内城市电源电压 一般为10KV,可以直接 供给用户或者再通过变 配电设备供给用户
一般的公共建筑/厂房都设计有变配电室 冷水机组或其它大型生产设备 推荐 变压至380V 水泵电机,冷却塔风机,风柜风 机,电梯,机房设备等 变压至220V
总电源10KV
照明,风机盘管,电子 设备等
10KV驱动系统 10KV 10KV
运行费用低 1. 低压驱动方式中较多的变配电设备的存在,在功率传送 过程中有能耗损失。特别是变压器的能耗损失往往比重 较大 2. 较多的变配电设备的增加了运行及维护费用。 3. 由于在同功率下10KV高压电机电流比低压电机小很多, 电机及电缆损耗(I2R)能量损耗小,电线连接处接触电阻 发热损耗也小。
1
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700
冷量范围RT
Page 12
单机头WSC高压机
制冷量:700-1700RT 制冷剂:HFC-134a 最新160机头高效机组
麦克维尔高压离心机技术交流
Page 1
空调机组10KV电压拖动问题的提出
1) 根据我国国情,中压电力网络,即城镇供电及地方工业企业供电 网络的额定电压规定为10KV。 2) 根据《JGJ-T16 民用建筑电气设计规范》“用电设备容量在250 kw以上或需用变压器容量在160KVA以上者宜以10kV供电”。 3) 市面各大冷水机组厂家产品低压机组只生产到1300TR装机容量, 更大冷量机组一般采用10kV供电,因此对于总冷量较大的项目, 如果采用低压机组则需要采用多台主机。 4) 如使用0.38,3或6KV电动机时要增加10KV的降压变压器、高压 柜、控制柜、配电设施,此外更有变压器的电能损耗及增容费等。 这一来大大增加了投资及运行管理费用。
Page 25
谢谢
Question?
科技营造自然
Page 26
6, 3KV驱动系统 10KV
380V驱动系统
开关柜
开关柜
开关柜 变压器
高压启动器
变压器
高压启动器
开关柜
低压启动器
冷水机组
6
冷水机组
(6, 3KV电机)
冷水机组
(380V电机)
(10KV电机)
点和优点
1) 系统简单 2) 整体投资节省
3) 电流小,对其他设备影响小
4) 节省空间
5) 运行费用低
整体投资省 如果将空调系统的投资范围延伸至变配电系统的采购、安装 和调试,则10KV冷水机组的总投资与常规相差不大,而且当 电机容量超过一定规格时,前者的总投资将少于常规系统。
COP=5.4 COP=5.7 COP=5. 串联 7℃
大温差
WCC双压缩机离心机组 1600RT~2500RT
压降低
并联 12℃
COP=5.4
6.5℃ 32.5℃ 38.5℃ COP=5.4
7℃
12℃
9℃ 29.5℃
6.5℃ 29.5℃ 36.0℃ COP=5.7
原理 解说
32.5℃ 37℃
32℃
Page 17
启动柜分类-直接启动柜
Page 18
启动柜分类-电抗启动柜
Page 19
启动柜分类-电抗启动柜
Page 20
启动柜分类-自耦启动柜
Page 21
启动柜分类-自耦启动柜
Page 22
麦克维尔用户
• 唯有用户信赖,方有麦克维尔的 生存之道
Page 23
McQuay® 中央空调设备 高压用户
寿命长
制冷量:1600-2600RT 制冷剂:HFC-134a
电流低
单台压缩机优先启动,启动电流更低。
OP
9.0 8.0 7.0 6.0 5.0 4.0 3.0 2.0 1.0
WSC单压缩机离心机组1600冷吨
0 10 20 30 40 50 60 70 80 90 100
age 14
基于12/7 32/37℃工况, 冷却水水温变化
百年品牌
• 1872年 成立于美国明尼苏达州 • 1988年 收购美国著名空气过滤器生产商AAF • 1995年 收购英国著名冷冻公司J&E HALL 世界著名暖通空调企业
Page 10
麦克维尔高压离心系列产品
冷水机组
WTC (两级离心机)
4
WCC 双机头串联机组 WDC 双机头并联机组
3
2
WSC 单级离心机
WSC126/900RT
WDC126/1250/2200 WSC126/1251RT WSC126/1000RT WSC126/1300RT WSC126/900RT WDC126/2200RT WSC126/1100RT WSC126/1000RT
7
20 4 1 1 1 4 2 2
6KV
6.6KV 10KV 10KV 10KV 10KV 10KV 10KV 10KV
3
10KV 10KV 10KV 10KV 10KV 6KV 6.6KV 6.6KV 6KV 6.6KV
1
6 2 3 8 2 6 4 4
27
28 29 30 31 32 33 34 35
上海
江苏 石家庄 南京 成都 南京 石家庄 石家庄 南京
先进半导体
龙腾电子 东方银座 江苏长电科技滨江厂 新疆华凌市场陶瓷城 徐州德客乐置业有限公司 保定英利新能源 保定英利新能源 江苏长电科技股份有限公司
% 负荷
Page 14
双机头WCC高压机-串联
串联双压缩机技术(WCC)
效率高
满负荷效率高,特别适用工业及大冷量项目。 工业项目通常负荷较稳定,满负荷效率高将大 大节能。 WCC机组两台压缩机串联使用,将原本由一台压 缩机提供的提升力由两台压缩机提供,在大提 升力场所如大温差,将会有更好的能效表现。 WCC机组采用单流程设计,水压降在40-60kPa之 间,常规机组通常在150-200kPa左右,水泵节 能超过20%以上。
自耦起动 0.65 UE 0.4225 I QE 0.4225MQE 1.起动电流小 2. 起动力矩较大 3. 不能频繁起动 4. 体积大 (2) 5. 成本高 (2.5~2.8) 6. 换接时有冲击电流 设备有影响
起动方式的特点和应用 5. 成本低 (1) 6. 起动时冲击电流大 设备有影响很大
7.起动时的冲击对机械 7. 换接时的冲击对机械 7. 换接时的冲击对机械 8. 704HP以下建议采用 8.750HP 以上建议采用 8.750HP 以上建议采用
建滔(衡阳)实业公司 乐凯胶片有限公司 国家会议中心 中粮广场 712工程 白云机场 上海南证 非力浦电子 金东集团 贝岭电子
WSC113/568RT wdc126/2000RT wdc126/2000RT wdc126/1900RT WSC126/1100RT WDC126/2000RT PEH126/1000RT PEH126/1000RT PEH126/1050RT WDC126/2200RT
制冷量 输入功率 COP 满载电流 启动电流 尺寸
RT Kw Kw/kw 直接 直接/电抗/自耦 长*宽*高
1500 876.8 6.02 56 308/200/130 5868*2603*2829
Page 13
双机头WDC高压机-并联
效率高
部分负荷效率高,节能性好。舒适性空调系 统中,一年中有70%以上的时间运行在设计 冷量的60%负荷以下。 单台压缩机运行时,使用2倍的换热面积, 可提供60%机组设计冷量,压缩机互为备用。 延长整机寿命25%
Page 16