CAUTION : do not connect under voltage. Refer to the drive User Guide before commissionning.ATTENTION : procéder au raccordement hors tension. Se reporter à la notice Installation et mise en service pour lamise en œuvre du variateur.VORSICHT : die Verbindung muss bei ausgeschalteter Spannung durchgeführt werden. Siehe Getriebe-Handbuch zurInstallation und Inbetriebsetzung des Getriebes.ATTENZIONE : il collegamento deve essere effettuato in assenza di tensione. Consultare il manuale di installazione e messa in servizio del variatore.ATENCIÓN : efectuar el conexionado sin tensión. Hacer referencia al manual de instalación y puesta en servicio del variador.LET OP : niet aansluiten onder spanning. Raadpleeg de installatie- en ingebruikstellingsnota voor het gebruik van de variator.PX-Brake Contactor Secure1/24123PX-Brake Contactor Secure4.2 - Secure input - Entrée sécuritaire - Sicherheit- Eingange - Ingresso di sicurezza - Entrada de seguridad - VeiligheidsingangApplying secure input SDI2 together with digital input DI2.Complies to EN 954-1 category 2 or 3 safety standards without any line contactor.Utilisation de l'entrée sécuritaire SDI2 en redondance avec l'entrée logique DI2. Conforme à EN 954-1 catégorie 2 ou 3 sans contacteur de ligne.Verwendung des Sicherheits-Einganges SDI2 in Redundanz mit dem logischen Eingang DI2. Konform mit EN 954-1 Kategorie 2 oder 3 ohne Überstromschalter.Uso dell'ingresso di sicurezza SDI2 in ridondanza conl'ingresso logico DI2. Conforme a EN-954-1 categoria 2 o 3 senza contattore di linea.Uso de la entrada de seguridad SDI2 en redundancia con la entrada lógica DI2. Conforme a EN-954-1 categoría 2 ó 3 sin contactor de líneaGebruik van de veiligheidsingang SDI2 met de logische ingang DI2. Conform EN-954-1 categorie 2 of 3 zonder lijncontactor.2/24 - Wiring diagram - Schéma de raccordement - Verbindungsschema - Schema di collegamento - Esquema de conexión - Aansluitingsschema4.1 - Brake - Frein - Bremse - Freno- Freno-RemSecureS (§4.2)1 : Run / Stop - Marche / Arrêt - Gang / Anhalten - Marcia / Arresto -Marcha / Parada - Aan / Uit2 : Fault relay - Relais de défaut - Störungs-Relais - Relè di guasto -Relé de avería - Foutrelais3 : Safety relay - Relais de sécurité - Sicherheits-Relais - Relè disicurezza - Relé de seguridad - VeiligheidsrelaisBrake Frein Bremse Freno Freno RemDedicated digital output Sortie logique dédiéeZugeordneter logischer AusgangUscita logica dedicata Salida lógica dedicada Voorbehouden logische uitgangSpeisung Alimentazione Alimentación VoedingAC OUT U S。
NSC560变压器保护装置技术说明书(国电南自)09-09-10要点

NSC 560系列数字式变压器保护装置技术说明书国电南京自动化股份有限公司2005年6月* 本公司保留对此说明书修改的权利,请注意最新版本资料目次1 装置简介 (1)2 装置硬件 (3)2.1机箱结构 (3)3 保护原理 (4)3.1变压器(差动)保护原理(最大可判五侧差动) (4)3.2 二次谐波制动 (6)3.3TA断线报警及闭锁 (6)3.4非电量保护的事件记录及延时 (6)3.5 三段式复合电压闭锁方向过流保护 (8)3.6零序过电流元件 (9)3.7间隙保护元件 (9)3.8过负荷元件 (10)3.9TV断线检测 (10)3.10数据记录 (10)4 定值及整定说明 (11)4.1NSC565数字式变压器差动保护装置的整定值清单及说明 (11)4.2NSC566数字式变压器后备保护装置的整定值清单及说明 (12)5 附图 (16)附图1:NSC565主变差动保护装置背板端子图 (116)附图2:NSC566主变后备保护装置背板端子图 (12)1 装置简介NSC 560系列数字式变压器保护装置是适用于110kV及以下电压等级的成套变压器保护,提供二次谐波制动的比率差动保护,开关量保护,及反应相间故障的后备保护。
整套装置在硬件上由几个独立的单元构成:差动保护单元、开关量保护单元及按侧配置的后备保护单元,各部分在电气及结构上均互相独立,各侧的后备保护单元同时完成该侧的测量控制功能。
本保护装置每个电气保护单元的基本配置为两个CPU插件,其一为由32位微处理器构成的保护功能单元,该单元配置了大容量的RAM和Flash Memory,具有极强的数据处理、逻辑运算和信息存储能力;另一CPU由总线不出芯片的单片机构成通用的人机接口单元。
两个CPU插件之间相互独立,无依存关系。
各种保护功能及自动化功能均由软件实现。
1)装置特点1:全中文汉化液晶显示,人机界面友善,操作方面。
2:专用测量模块,包括电度计量在内的各种测量及计量精度可达0.5级3:提供累计脉冲电度的接入端4:配置了充足的开关量输入端,方便外部遥信量的接入5:装置自带操作回路及就地操作把手,不需附加其它设备即可直接跳合开关6:设置了高精度的时钟芯片,并配置有GPS硬件对时回路,便于全系统时钟同步7:配备高速以太网络通信接口,并集成了IEC 60870-5-103标准通信规约8:完善的故障录波功能2)完备的保护功能配置表1 本系列产品的型号及功能配置表功能NSC 565 NSC 566差动速断√二次谐波制动的比率差动√TA(1)断线闭锁差动√过流保护√过负荷√负序过电压闭锁√低电压闭锁√零序过流√间隙过流√间隙过压保护√电流启动风扇√电流闭锁调压过负荷告警√功能NSC 565 NSC 566 重瓦斯√调压重瓦斯√冷却故障√压力释放√轻瓦斯√调压轻瓦斯√油温高√遥控功能压板√遥测测量级TA √保护级TV √遥信√√遥控√电度脉冲计量√GPS对时√√防误闭锁√√远方管理√√3)NSC566装置的监控功能1:遥测:Ia,Ib,Ic,Ua,Ub,Uc,P,Q,f 等模拟量的遥测2:遥控:正常断路器的遥控分合3:遥信:16路遥信开入量的采集、装置遥信变位、事件遥信等4:遥脉:2路电度脉冲输入5:开出:装置具有13路开出,其中10路由于驱动出口跳闸继电器,3路用于预告警信号驱动。
NST 640系列变压器保护装置2008年7月版

Q/NS.JS.6000.06-2005NST 640系列变压器保护装置技术说明书使用说明书NST 640系列变压器保护装置技术说明书使用说明书编写汤小兵审核蔡振龙批准刘恢V3系列国电南思系统控制有限公司2008年07月*本公司保留对此说明书修改的权利,请注意最新版本资料。
目录第一部分------------------------------------------------------------------------------11. 装置简介---------------------------------------------------------------------------32. 技术参数---------------------------------------------------------------------------5 2.1 额定参数--------------------------------------------------------------------------5 2.2 主要技术性能----------------------------------------------------------------------5 2.3 绝缘性能--------------------------------------------------------------------------6 2.4 电磁兼容性能----------------------------------------------------------------------6 2.5 机械性能--------------------------------------------------------------------------72.6 环境条件--------------------------------------------------------------------------73. 装置硬件---------------------------------------------------------------------------7 3.1 机箱结构--------------------------------------------------------------------------8 3.2 交流插件--------------------------------------------------------------------------8 3.3 CPU插件---------------------------------------------------------------------------8 3.4 电源插件--------------------------------------------------------------------------9 3.5 逻辑及跳闸插件-------------------------------------------------------------------10 3.6 人机对话(MMI)插件--------------------------------------------------------------103.7 开关量保护插件-------------------------------------------------------------------114. 保护原理--------------------------------------------------------------------------11 4.1 差动速断元件---------------------------------------------------------------------11 4.2 比率差动元件---------------------------------------------------------------------11 4.3 二次谐波制动元件-----------------------------------------------------------------11 4.4 TA断线报警及闭锁-----------------------------------------------------------------12 4.5 非电量保护的事件记录及延时-------------------------------------------------------12 4.6 过电流元件-----------------------------------------------------------------------12 4.7 低电压闭锁元件-------------------------------------------------------------------12 4.8 负序过电压闭锁元件---------------------------------------------------------------13 4.9 过负荷元件-----------------------------------------------------------------------13 4.10 TV断线检测----------------------------------------------------------------------13 4.11自产3U0越限检测元件-------------------------------------------------------------134.12 数据记录------------------------------------------------------------------------135. 与变电站自动化系统配合------------------------------------------------------------136. 定值及整定说明--------------------------------------------------------------------146.1 NST 641数字式变压器差动保护装置的整定值清单及说明--------------------------------14 6.2 NST 641数字式变压器差动保护装置软压板清单----------------------------------------15 6.3 NST 642 数字式变压器后备保护装置的整定值清单及说明--------------------------------16 6.4 NST 642数字式变压器后备保护装置软压板清单:--------------------------------------18 第二部分-----------------------------------------------------------------------------19 注意事项-----------------------------------------------------------------------------20 1. 装置介绍--------------------------------------------------------------------------211.1 面板布置-------------------------------------------------------------------------212.1 键盘简介-------------------------------------------------------------------------221.3 背板及端子简介-------------------------------------------------------------------232. 菜单操作--------------------------------------------------------------------------28 2.1 功能简介-------------------------------------------------------------------------282.2 操作说明-------------------------------------------------------------------------283. 用户调试大纲----------------------------------------------------------------------37 3.1 装置通电前检查-------------------------------------------------------------------37 3.2 绝缘检查-------------------------------------------------------------------------38 3.3 上电检查-------------------------------------------------------------------------38 3.4 采样精度检查---------------------------------------------------------------------38 3.5 接点输出校验---------------------------------------------------------------------38 3.6 定值校验-------------------------------------------------------------------------383.7 校准时钟-------------------------------------------------------------------------384. 事件信息一览表--------------------------------------------------------------------38 4.1 NST 641主变差动保护事件信息一览表------------------------------------------------38 4.2 NST 641主变差动保护告警事件信息一览表--------------------------------------------39 4.3 NST 641主变差动保护压板信息一览表------------------------------------------------40 4.4 NST 641主变差动保护遥信量信息一览表----------------------------------------------394.5 NST 641主变差动保护遥测量信息一览表----------------------------------------------415. 附图------------------------------------------------------------------------------42 第三部分-----------------------------------------------------------------------------44 注意事项-----------------------------------------------------------------------------45 1. 装置介绍--------------------------------------------------------------------------46 1.1 面板布置-------------------------------------------------------------------------46 1.2 键盘简介-------------------------------------------------------------------------47 1.3 背板及端子简介-------------------------------------------------------------------482. 菜单操作--------------------------------------------------------------------------53 2.1 功能简介-------------------------------------------------------------------------532.2 操作说明-------------------------------------------------------------------------533. 用户调试大纲----------------------------------------------------------------------64 3.1 装置通电前检查-------------------------------------------------------------------64 3.2 绝缘检查-------------------------------------------------------------------------64 3.3 上电检查-------------------------------------------------------------------------64 3.4 采样精度检查---------------------------------------------------------------------65 3.5 接点输出校验---------------------------------------------------------------------65 3.6 定值校验-------------------------------------------------------------------------65 3.7 跳合闸电流保持试验---------------------------------------------------------------65 3.8 相序检查-------------------------------------------------------------------------653.9 校准时钟-------------------------------------------------------------------------654. 事件信息一览表--------------------------------------------------------------------66 4.1 NST 642变压器后备保护事件信息一览表----------------------------------------------66 4.2 NST 642变压器后备保护告警事件信息一览表------------------------------------------66 4.3 NST 642变压器后备保护压板信息一览表----------------------------------------------67 4.4 NST 642变压器保护遥测量信息一览表------------------------------------------------684.5 NST 642变压器后备保护遥信量信息一览表--------------------------------------------685.附图-------------------------------------------------------------------------------70第一部分NST640 系列变压器保护装置技术说明书安全标准NST 640系列数字式变压器保护装置符合各种安全标准。
低压保护器

高精度:采用功能强大的微处理器芯片,尤其采用交流采样技术,电压测量精度为±1%,能分别显示
,保证全球通用(不能使用于变频器输出回路)。
,使低压保护器的规格大为减少,便于高可靠:采用独特的三相电源供电技术,即使在极低电压、甚至在缺相情况下,也能保证保护、报警、
相序保护器原理图
相序监测:当低压保护器通电时,如果相序正确并且所有三相带电,继电器吸合。
过欠压保护器原理
缺相保护器原理图
缺相检测:当缺相故障时,继电器断电。
正常工作(无故障)时继电器吸合。
当缺相时立即断电。
电压不平衡保护器原理图
A、B、C:“不平衡”字符闪烁D:“不平衡”字符长亮。
ERZ-V系列变压器保护器说明书

ERZ-V10D221ERZ-V05D221ERZ-V20D270ERZ-V20D470“ZNR” Transient/Surge Ab sorb ers (Type D)“ZNR” Transient/Surge Ab sorb ers (Type D)■Reference Guide to Standard ProductsPart N o.VaristorVoltage✽MaximumAllowableVoltageClampingVoltage@8/20µsMaximumEnergy(J)MaximumPeak Current@8/20µs(A)Recommended Applications (V)ACrms (V)DC (V)max.(V)Ip (A)10/1000 µs 2 ms 1 time 2 timesERZV05D18018 (16–20)111440 10.60.4250125For the low voltage circuitERZV07D18036 2.5 1.10.9500250 ERZV09D18036 5 2.6 2.21000500 ERZV10D18036 5 2.6 2.21000500 ERZV14D18036 10 5.2 4.320001000 ERZV20D18036 20131230002000 ERZV05D22022 (20–24)141848 10.70.5250125ERZV07D22043 2.5 1.3 1.1500250 ERZV09D22043 5 3.2 2.61000500 ERZV10D22043 5 3.2 2.61000500 ERZV14D22043 10 6.3 5.320001000 ERZV20D22043 20161430002000 ERZV05D27027 (24–30)172260 10.90.7250125ERZV07D27053 2.5 1.6 1.3500250 ERZV09D27053 5 3.9 3.21000500 ERZV10D27053 5 3.9 3.21000500 ERZV14D27053 107.8 6.520001000 ERZV20D27053 20191730002000 ERZV05D33033 (30–36)202673 1 1.10.8250125ERZV07D33065 2.5 2.0 1.6500250 ERZV09D33065 5 4.8 4.01000500 ERZV10D33065 5 4.8 4.01000500 ERZV14D33065 109.57.920001000 ERZV20D33065 20242130002000 ERZV05D39039 (35–43)253186 1 1.20.9250125ERZV07D39077 2.5 2.4 1.9500250 ERZV09D39077 5 5.6 4.71000500 ERZV10D39077 5 5.6 4.71000500 ERZV14D39077 10119.420001000 ERZV20D39077 20282530002000 ERZV05D47047 (42–52)3038104 1 1.5 1.1250125ERZV07D47093 2.5 2.8 2.3500250 ERZV09D47093 5 6.8 5.61000500 ERZV10D47093 5 6.8 5.61000500 ERZV14D47093 10141120001000 ERZV20D47093 20343030002000 ERZV05D56056 (50–62)35451231 1.8 1.3250125ERZV07D560110 2.5 3.4 2.7500250 ERZV09D560110 58.1 6.71000500 ERZV10D560110 58.1 6.71000500 ERZV14D560110 10161320001000 ERZV20D560110 20413630002000 ERZV05D68068 (61–75)4056150 1 2.2 1.6250125ERZV07D680135 2.5 4.1 3.3500250 ERZV09D680135 59.88.21000500 ERZV10D680135 59.88.21000500 ERZV14D680135 10201620001000 ERZV20D680135 20494430002000 ERZV05D82082 (74–90)5065145 5 3.5 2.5800600Telephone, Communication Line(DC 48 V)ERZV07D82013510 7 517501250 ERZV09D820135 25141035002500 ERZV10D820135 25141035002500 ERZV14D820135 50282060005000 ERZV20D8201351005640100007000“ZNR” Transient/Surge Ab sorb ers (Type D)■Reference Guide to Standard ProductsPart N o.VaristorVoltage✽MaximumAllowableVoltageClampingVoltage@8/20µsMaximumEnergy(J)MaximumPeak Current@8/20µs(A)Recommended Applications (V)ACrms (V)DC (V)max.(V)Ip (A)10/1000 µs 2 ms 1 time 2 timesERZV05D101100 (90–110)60 851755 4 3800600Telephone, Communication Line(DC 48 V)ERZV07D10116510 8.5 617501250 ERZV09D10116525 17 1235002500 ERZV10D10116525 17 1235002500 ERZV14D10116550 35 2560005000 ERZV20D101165100 70 50100007000 ERZV05D121120 (108–132)751002105 5 3.5800600ERZV07D12120010 10717501250 ERZV09D12120025 20 14.535002500 ERZV10D12120025 20 14.535002500 ERZV14D12120050 42 3060005000 ERZV20D121200100 85 60100007000 ERZV05D151150 (135–165)951252605 6.5 4.5800600ERZV07D15125010 139******** ERZV09D15125025 25 1835002500 ERZV10D15125025 25 1835002500 ERZV14D15125050 5337.560005000 ERZV20D151250100 10675100007000 ERZV05D201200 (185–225)1301703555 8.5 6800600AC 100 V Line–LineApplicationsERZV07D20134010 17.5 12.517501250 ERZV09D20134025 35 2535002500 ERZV10D20134025 35 2535002500 ERZV14D20134050 70 5060005000 ERZV20D201340100 140 100100007000 ERZV05D221220 (198–242)1401803805 9 6.5800600ERZV07D22136010 19 13.517501250 ERZV09D22136025 3927.535002500 ERZV10D22136025 3927.535002500 ERZV14D22136050 78 5560005000 ERZV20D221360100 155110100007000 ERZV05D241240 (216–264)1502004155 10.57.5800600AC 100 V to 120 V, Line–LineApplicationsERZV07D24139510 21 1517501250 ERZV09D24139525 42 3035002500 ERZV10D24139525 42 3035002500 ERZV14D24139550 84 6060005000 ERZV20D241395100 168 120100007000 ERZV05D271270 (247–303)1752254755 118800600ERZV07D27145510 24 1717501250 ERZV09D27145525 49 3535002500 ERZV10D27145525 49 3535002500 ERZV14D27145550 99 7060005000 ERZV20D271455100 190 135100007000 ERZV05D331330 (297–363)2102705705 139.5800600AC 100 V to 120 V, Line–LineApplicationsTelephone Line Applications,(250 V Insulation ResistanceTest Applicable)ERZV07D33154510 28 2017501250 ERZV09D33154525 58 4235002500 ERZV10D33154525 58 4235002500 ERZV14D33154550 1158060004500 ERZV20D331545100 228 160100006500 ERZV05D361360 (324–396)2303006205 16 11800600ERZV07D36159510 32 2317501250 ERZV09D36159525 65 4535002500 ERZV10D36159525 65 4535002500 ERZV14D36159550 1309060004500 ERZV20D361595100 255 180100006500“ZNR” Transient/Surge Ab sorb ers (Type D)■Reference Guide to Standard Products✽ Measuring Current of Varistor Voltage 5 Series : 0.1 mA, Others: 1 mA ✽✽example IEC60065Ed7 (Audio, video and similar electronic.)Part N o.VaristorVoltage ✽Maximum Allowable Voltage Clamping Voltage @8/20µs Maximum Energy (J)Maximum Peak Current @8/20µs(A)Recommended Applications(V)ACrms (V)DC (V)max.(V)Ip (A)10/1000 µs 2 ms1 time2 times ERZV05D391390(351–429)25032067551712800600AC 100 V to 120 V, Line–Line ApplicationsTelephone Line Applications,(250 V Insulation Resistance Test Applicable)ERZV07D39165010352517501250ERZV09D39165025705035002500ERZV10D39165025705035002500ERZV14D3916505014010060004500ERZV20D391650100275195100006500ERZV05D431430(387–473)27535074552013.5800600AC 100 V to 220 V, Line–Line andAC 100 V to 220 V,Line–Ground ApplicationsERZV07D431710104027.517501250ERZV09D43171025805535002500ERZV10D43171025805535002500ERZV14D4317105015511060004500ERZV20D431710100303215100006500ERZV05D471470(423–517)30038581052115800600AC 100 V to 220 V, Line–Line andAC 100 V to 220 V,Line–Ground ApplicationsERZV07D47177510423017501250ERZV09D47177525856035002500ERZV10D471✽✽77525856035002500ERZV14D471✽✽7755017512560004500ERZV20D471✽✽775100350250100006500ERZV07D511510(459–561)32041084510453217501250AC 100 to 240 V, Line–Line ApplicationsAC 100 to 240 V, Line–Ground ApplicationsERZV09D51184525926735002500ERZV10D511✽✽84525926735002500ERZV14D511✽✽8455019013660004500ERZV20D511✽✽845100382273100006500ERZV10D621✽✽620(558–682)385505102525926735002500ERZV14D621✽✽10255019013650004500ERZV20D621✽✽102510038227375006500ERZV10D681✽✽680(612–748)420560112025926735002500ERZV14D681✽✽11205019013650004500ERZV20D681✽✽112010038227375006500ERZV10D751✽✽750(675–825)4606151240251007035002500AC 380 V, Line–Line and Line–Ground Applications(For DC 500 V Insulating Test)ERZV14D751✽✽12405021015050004500ERZV20D751✽✽124010042030075006500ERZV10D821✽✽820(738–902)5106701355251108035002500ERZV14D821✽✽13555023516550004500ERZV20D821✽✽135510046032575006500ERZV10D911✽✽910(819–1001)5507451500251309035002500AC 415 V, Line–Line and Line–Ground Applications(For DC 500 V Insulating Test)ERZV14D911✽✽15005025518050004500ERZV20D911✽✽150010051036075006500ERZV10D102✽✽1000(900–1100)62582516502514010035002500AC 480 V, Line–Line and Line–Ground Applications(For DC 500 V Insulating Test)ERZV14D102✽✽16505028020050004500ERZV20D102✽✽165010056540075006500ERZV10D112✽✽1100(990–1210)68089518152515511035002500ERZV14D112✽✽18155031022050004500ERZV20D112✽✽181510062044075006500ERZV10D182CS ✽✽1800(1700–1980)1000146529702524718335002500Line–Ground Applications (For AC 1200 V Withstanding Test)ERZV14D182CS ✽✽29705051036050004500ERZV20D182✽✽2970100102072075006500ERZ-V10D221ERZ-V05D221ERZ-V20D270ERZ-V20D470。
ABB低压变压器产品说明书

12Tran s f or me r sLow Voltage Products & Systems12.1TransformersDescription• Epoxy encapsulated coils up through 750VA • Epoxy resin impregnated coils 1 kVA to 5 kVA• Provides stepped down voltages formachine tool control devices and industrial control panels• Laminations of high quality silicon steel • Minimum core loss• Optimized performance• Copper magnet wire providing the highest quality and efficient operation • Molded-in terminals• 80°C rise, 130°C insulation system • 50/60 Hz• UL File # E175311• CSA File #LR27533• IP 20 Touch safe covers available as an optionT r a n s f o r m e r s12.2Low Voltage Products & Systems1 Consult factory for applications with different voltages.2 Whenever both secondary voltages are to be used at the same time, remove the secondary fuse clip and use a separate mounted 2 pole fuse block.3 Includes terminal and fuse covers.T - Industrial control transformer X - New generation industrial control transformer Primary voltage rating 14 - 460V , 230V & 208V 6 - 575V & 600VVA rating045 = 45VA 350 = 350VA 050 = 50VA 500 = 500VA 075 = 75VA 750 = 750VA 100 = 100VA 1K = 1000VA 150 = 150VA 1.5K = 1500VA 200 = 200VA 2K = 2000VA 250 = 250VA 3K = 3000VA 300 = 300VA 5K = 5000VAX 4 100 PS F1 /COption 3Add $15 to list priceIP 20 Terminal coversMeets finger safe or touch safe requirements for IEC specification 529. Available 50VA thru 750VA Secondary voltage(s) 2F = 24V 1 = 115VF1 = 115/24V dual secondary 2Fuse blocksP = primary fuse block (2 pole Class CC, less fuses)S = secondary fuse clip (13/32" x 1 1/2", less fuse)Example : T4100PSF1• ABB Industrial control transformer• Primary voltage: 460V , 230V and 208V • 100 VA rating• Primary & secondary fuse blocks provided • S econdary voltage 115/24V • Optional IP 20 terminal coversLow Voltage Products & Systems12.5Primary voltage — 460/230/208V , 480/240V , 440/220/200V Secondary voltage — 115/24V 2, 120/25V , 110/23VPrimary voltage — 460/230/208V , 480/240V , 440/220/200V Secondary voltage — 115V , 120V , 110V1 Primary & secondary fuse block provided as standard (750VA unit, only).2 Whenever both secondary voltages are to be used at the same time, remove the secondary fuse clip and use a separate mounted 2 pole fuse block.Discount schedule ATSide ViewSide ViewT op View Side ViewX4045SF1T41K1X4750PSF112.6Low Voltage Products & SystemsPrimary voltage — 600/575/550V Secondary voltage — 120/115/110VPrimary voltage — 575/460/230V Secondary voltage — 115 - 95VDiscount schedule ATT op ViewSide ViewT op View Side View。
ISA G系列变压器保护装置技术使用说明书 南网版 V

3.1 保护配置 .................................................................................................................... 6 3.2 差动保护接线及电流计算 ........................................................................................ 6 3.3 保护原理 .................................................................................................................... 7 3.4 整定计算和整定原则 .............................................................................................. 10 3.5 保护配置及整定说明 .............................................................................................. 11 3.6 保护动作事件类型定义 .......................................................................................... 13 3.7 装置端子接线 .......................................................................................................... 13
低压保护设备配置手册说明书

Deckblattbild Format 4:3 hier unter Logo einfügenConfiguration Manual06/2023 5SU1...FRFNFP/lowvoltageLegal informationQualified PersonnelThe product/system described in this documentation may be operated only by personnelqualified for the specific task in accordance with the relevant documentation, in particular itswarning notices and safety instructions. Qualified personnel are those who, based on theirtraining and experience, are capable of identifying risks and avoiding potential hazards whenworking with these products/systems.Proper use of Siemens productsSiemens products may only be used for the applications described in the catalog and in theTrademarksAll names identified by ® are registered trademarks of Siemens AG. The remaining trademarksin this publication may be trademarks whose use by third parties for their own purposescould violate the rights of the owner.Disclaimer of LiabilityWe have reviewed the contents of this publication to ensure consistency with the hardwareand software described. Since variance cannot be precluded entirely, we cannot guaranteefull consistency. The information provided is binding only when expressly agreed upon in aconcluded contract. However, the information in this publication is reviewed regularly andany necessary corrections are included in subsequent editions.Siemens AG Copyright © Siemens AG 2023 Smart Infrastructure Ⓟ 06/2023 Subject to change All rights reserved Electrical ProductsPostfach 10 09 5393009 RegensburgGERMANYTable of contents1Introduction (4)2Molded case circuit breaker as upstream device (5)2.13VA1 in combination with 5SU1...FRFNFP (5)2.23VA2 in combination with 5SU1...FRFNFP (7)3Motor starter protection as upstream device (8)3.13RV2 in combination with 5SU1...FRFNFP . (8)4Fuse as upstream device (10)4.13NA/3NE in combination with 5SU1...FRFNFP .. (10)4.25SE2 in combination with 5SU1...FRFNFP .. (12)5Molded case circuit breaker as upstream device (13)5.15SP4/5SY7/5SY8 in combination with 5SU1...FRFNFP (13)5SU1...FRFNFP1IntroductionProduct characteristics and limit values within this table are exclusively valid for orderableproducts in consideration of a possible suffix inside the product-order-number.Products w/o suffix are products with global marketing (MLFB Addition '-'). Limit values areexclusively valid for those product-variants.Special or regional product-variants are registered with specific suffix in product-order-number. (Examples: 5SY41016-CC11, 5SU13537-KL06, 3NA3001-RC) Tables and limit valuesreported with a specific MLFB-Addition like "CC" or "RC" or "OEZ" or "Electrium" are exclusivelyvalid for special or regional product-variants with this specific suffix inside the product-order-number.Notes regarding selectivity tablesFor breakers with adjustable trip unit: the limit current with selectivity Is [kA] apply to themaximum value Iimax.Limit values for total selectivity "T" refer to breaking capacity Icu of downstream MCB/RCBO.Notes regarding backup-protection tablesIndependent of any Backup value in this table, the maximum available current of the circuitwhere the upstream breaker is used may not exceed its short circuit rating (Icu).5SU1...FRFNFP2Molded case circuit breaker as upstream device 2.13VA1 in combination with 5SU1...FRFNFP5SU1...FRFNFP5SU1...FRFNFP2.23VA2 in combination with 5SU1...FRFNFP5SU1...FRFNFP3Motor starter protection as upstream device3.13RV2 in combination with 5SU1...FRFNFP5SU1...FRFNFP5SU1...FRFNFP4Fuse as upstream device4.13NA/3NE in combination with 5SU1...FRFNFP5SU1...FRFNFP5SU1...FRFNFP4.25SE2 in combination with 5SU1...FRFNFP5SU1...FRFNFP5Molded case circuit breaker as upstream device 5.15SP4/5SY7/5SY8 in combination with 5SU1...FRFNFP5SU1...FRFNFP。
变压器保护装置说明书

第五章 DSA321/322/326 变压器保护装置说明书
5.2 保护算法......................................................... 5-39 5.3 装置操作......................................................... 5-40 5.4 菜单说明......................................................... 5-41 6 装置介绍 ............................................................ 5-42 6.1DSA321/322 差动保护装置........................................... 5-42 6.2DSA3261 后备保护装置.............................................. 5-42 6.3DSA3262 后备保护装置.............................................. 5-43 6.4DSA3263 后备保护装置.............................................. 5-43 6.5DSA3264 后备保护装置.............................................. 5-43 6.6DSA3265 后备保护装置.............................................. 5-43 6.7DSA302 操作箱..................................................... 5-49 附录 5-1DSA321 主变差动保护原理图 ..................................... 5-50 附录 5-2DSA322 主变差动保护原理图 ..................................... 5-51 附录 5-3DSA326 主变高压侧后备保护原理图 ............................... 5-52 附录 5-4DSA321/322 差动保护背板端子图 ................................. 5-53 附录 5-5DSA326 后备保护背板端子图 ..................................... 5-54 附录 5-6 故障录波装置菜单说明.......................................... 5-57
低压箱变基础手册

低压箱变典型方案手册编制:韩学志专业严谨低压箱变典型方案手册专注创新目录前言 (1)1、低压箱变型号说明 (2)2、应用领域 (2)3、采用标准 (2)4、使用条件 (3)5、箱变方案要素 (3)6、箱体介绍 (5)7、变压器选择 (7)8、常规低压箱变系列 (8)8.1高压典型方案 (9)8.2低压典型方案 (10)8.3低压箱变参数配置对照表 (14)8.4常规低压箱变介绍 (16)8.4.1普通配电箱变 (16)8.4.2动力配电箱变 (16)8.4.3路灯箱变 (17)9、铁路信号箱变 (17)10、风电升压箱变 (17)11、其他类型 (17)12、箱变智能方案 (18)13、铜、铝排及铜芯线载流量表 (19)14、参考资料 (20)前言本手册是在学习了相关标准规范,了解了同行业低压箱变发展情况,总结以往工程的基础上编制的。
虽然低压箱变是很传统的电力设备,但目前我们的低压箱变产品还不成熟,工程业绩也不多,而且在项目的运作和执行过程中存在很多问题,从方案制定、设计生产到售后服务均存在一些问题,到目前即便常规的低压箱变也不够成熟。
但可以肯定最关键的因素是人力资源状况不佳,团队效率和人员知识水平有限,人员成长和发展缓慢,这些都是我们今后发展必须尽快克服的问题,低压箱变的发展不是一个人或几个人就能做好的事情,需要每一个人、每一个环节的努力,是一件要集思广益,齐心协力来做好做大的事业,因此不管是市场营销、技术支持还是设计生产和售后服务,我们都要努力改进。
由于时间和能力有限,手册所介绍的内容比较浅显,只能作为参考,还需不断充实和改进,目的是抛砖引玉,希望领导和专家批评指正。
1、低压箱变型号说明30~2500kV A)或0.69kV)或40.5kV)注:依据JB/T 8754-1998《高压开关设备型号编制办法》拟定。
2、应用领域工矿企业、城乡配网、市政照明、居民小区、商业中心、机场、景区、流动性施工工地、风电场、铁路系统等。
艾滕低压电流变压器产品说明说明书

Current TransformersGeneral DescriptionEaton’s low voltage current transformers areavailable in both solid core and split core designs. Engineered for electronic metering applications, all solid core designs and selected split core designs offer ANSI metering quality accuracy. The current transformer offering has a 5A secondary at the rated primary current.Split core CTs are specifically designed to be installed around primary conductors without disconnecting wires or breaking the circuit to be monitored. These current transformers are perfect solutions for energy management applications and are manufactured for installation ease.Application DescriptionFor new construction and retrofit applicationswhere no current transformer exists, Eaton offers a complete selection of low voltage (up to 600V) current transformers. These current transformers can be used in commercial grade applications such as control panels and panelboards. Additionally, they can be used for most industrial metering applications in switchboards, switchgear and motor control centers.Note:N Not for use with IQ 35M or IQ MESII.Current Transformers2Technical Data TD02601002EEffective March 2012Current T ransformerseaton corporationPrimary Current Rating Metering Class at 60 Hz (Accuracy in %)Window Size in Inches (mm)Figure Number for Dimensional Data Catalog Number 400 2.4 2.00 x 5.50(50.8 x 139.7)7M000-401500 2.4M000-501600 2.4M000-601800 1.2M000-8011000 1.2M000-10212000.6M000-12215000.6M000-15216000.6M000-16220000.6M000-202600 4.8 4.10 x 7.10(104.1 x 180.3)8M050-601750 4.8M050-751800 2.4M050-8011000 2.4M050-1021200 1.2M050-1221500 1.2M050-15220000.6M050-20225000.6M050-25230000.6M050-30235000.6M050-35240000.3M050-402Product Selection (cont.)Current Rating Accuracy at 60 Hz (in %)Window Size in Inches (mm)for Dimensional Data Catalog Number 100 5.00.80 x 1.95(20.3 x 49.5)9M030-101150 5.0M030-151200 4.0M030-201300 2.0M030-301400 2.0M030-401100 5.0 1.42 x 1.53(36.1 x 38.9)10M040-101150 4.0M040-151200 1.5M040-201300 1.5M040-301400 1.5M040-401200 1.02.75 x 2.70(69.9 x 68.6)11M060-201300M060-301400M060-401500M060-501600M060-601750M060-751800M060-8011000M060-1021200M060-122500 1.02.60 x 6.25(66.0 x 158.8)12M080-501600M080-601800M080-8011000M080-1021200M080-1221500M080-1521600M080-1622000M080-2022500M080-2523000M080-302Primary Current Rating Metering Class at 60 Hz (Accuracy in %)Size inInches (mm) Diameter Catalog Number Number for Dimensional Data Bracket Catalog Number 3000.31.56 (39.6)S050-3011S050BRAC400S050-401500S050-501600S050-601750S050-751800S050-8011000S050-1021200S050-12250 1.2 1.25 (31.8)S060-5002a1000.6S060-1011500.3S060-1512000.3S060-2014000.33.25 (82.6)S080-4013S080BRAC500S080-501600S080-601750S080-751800S080-8011000S080-1021200S080-1225000.34.25 (108.0)S090-5014S090BRAC600S090-601750S090-751800S090-8011000S090-1021200S090-1221500S090-1521600S090-1622000S090-2022500S090-2523000S090-3026000.36.31 (160.3)S025-6015S025BRAC750S025-751800S025-*******S025-*******S025-*******S025-*******S025-*******S025-*******S025-*******S025-*******S025-*******S025-402250.3Wound Primary W190-0256W190BRAC50W190-050a No mounting bracket required.Product Selection3Technical Data TD02601002EEffective March 2012Current T ransformerseaton corporation Dimensions in Inches (mm)4Technical Data TD02601002EEffective March 2012Current T ransformerseaton corporation Dimensions in Inches (mm) (cont.)5Technical Data TD02601002EEffective March 2012Current T ransformerseaton corporation Dimensions in Inches (mm) (cont.)6Technical Data TD02601002EEffective March 2012Current T ransformerseaton corporation Dimensions in Inches (mm) (cont.)7Technical Data TD02601002EEffective March 2012Current T ransformerseaton corporation Dimensions in Inches (mm) (cont.)Technical Data TD02601002EEffective March 2012Current T ransformersEaton CorporationElectrical Sector1000 Cherrington ParkwayMoon Township, PA 15108United States877-ETN-CARE (877-386-2273)/meters© 2012 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. TD02601002E / TN March 2012Eaton is a registered trademark of Eaton Corporation.All other trademarks are property of their respective owners.。
低压变压器电源包 使用说明书

Visit our website at: Emailourtechnicalsupportat:******************************** When unpacking, make sure that the product is intactand undamaged. If any parts are missing or broken,please call 1-888-866-5797 as soon as possible.2020 by Harbor Freight T ools®. All rights reserved.No portion of this manual or any artwork contained herein may be reproduced in any shape or form without the express written consent of Harbor Freight T ools. Diagrams within this manual may not be drawn proportionally. Due to continuing improvements, actual product may differ slightly from the product described herein.ools required for assembly and service may not be included.Read this material before using this product. Failure to do so can result in serious injury. SAVE THIS MANUAL.Read all safety warnings, instructions, illustrations and specifications provided with this power tool. Failure to follow all instructions listed below may result in electric shock, fire and/or serious injury.1. WARNING: Risk of Electric Shock: Whenused outdoors, install only to a coveredClass A GFCI protected receptacle that isweatherproof, marked “Wet Location”, withthe power unit connected to the receptacle.If one is not provided, contact a qualifiedelectrician for proper installation. Ensure thatthe power unit and cord do not interfere withcompletely closing the receptacle cover.2. WARNING: Risk of Electric Shock: Installpower unit 5 feet (1.5m) or more from apool or spa and 10 feet (3.05m) or morefrom a fountain. Where the power unit isinstalled outdoors, connect power unit to areceptacle protected by a GFCI branch.3. Suitable for outdoor use only.4. Not for use with dimmers.5. Mount at least 1 foot (30cm) above ground.6. Do not connect two or more power supplies together.7. Do not use extension cords.8. For use with low voltage landscapelighting systems only.9. Use only with maximum 120W lamp load.10. Mount the power unit in or on non-combustiblemounting surfaces only.11. Main secondary wiring is intended for shallowburial - less than 6 inches (152mm).12. Not suitable for use with submersibleluminaries and pumps.13. Do not repair or tamper with the cord or plug.14. Do not submerge power unit in liquid.15. Do not connect light fixtures with power on.16. Assemble only according to these instructions.Improper assembly can create hazards.17. Wear ANSI-approved safety goggles andheavy-duty work gloves during assembly.18. Keep assembly area clean and well lit.19. Keep bystanders out of the area during assembly.20. Do not assemble when tired or when under theinfluence of alcohol, drugs or medication.21. This product is not a toy. Do not allowchildren to play with or near this item.22. Use as intended only.23. Inspect before every use; do not useif parts are loose or damaged.24. Maintain product labels and nameplates.These carry important safety information.If unreadable or missing, contactHarbor Freight Tools for a replacement.SAVE THESE INSTRUCTIONS.Page 2For technical questions, please call 1-888-866-5797.Item 57998GroundingTO PREVENT ELECTRIC SHOCK AND DEATH FROMINCORRECT GROUNDING WIRE CONNECTION:Check with a qualified electrician if you are in doubt as to whether the outlet is properly grounded.Do not modify the power cord plug provided. Never remove the grounding prong from the plug. Do not use the power unit if the power cord or plug is damaged. If damaged, have it repaired by a service facility before use. If the plug will not fit the outlet, have a proper outlet installed by a qualified electrician. Extension CordsNote: Extension cords must not be used with power pack.SpecificationsInput Rating120VAC / 60Hz / 1.2AOutput Rating12VAC / 10AMax Lamp120WWire16/2 16AWG/2-Conductor Low Voltage LandscapeItem 57998Page 3For technical questions, please call 1-888-866-5797.PhotoDisplayFunctionButtonsWhen used outdoors, install only to a covered Class A GFCI protected receptacle that is weatherproof, marked “Wet Location”, with the power unit connected to the receptacle. If one is not provided, contacta qualified electrician for proper installation. Ensure that the power unit and cord do not interfere with completely closing the receptacle cover. Do not plug in Power Cord until installation is complete. Landscape Wire SelectionThis data is provided as a general guideline.Calculate Lamp WattageThe Power Pack’s 120W circuit will power up to 96 watts of lights.Check wattage of individual light fixtures and add all wattage together. Do not exceed 96W total.Page 4For technical questions, please call 1-888-866-5797.Item 57998Page 5For technical questions, please call 1-888-866-5797.Item 57998InstallationWARNING! TO PREVENT SERIOUS INJURY: Verify that installation surface has no hidden utility lines before installing light fixtures.1. Place Power Pack close to GFCI outlet. Itmust receive maximum sunlight in order for photo sensor to work properly. 2. Lay Power Pack on its back on a sturdy surface.Do not plug in Power Pack.3. Connect Wires to Power Packa. Split conductors 2″, strip 3/4″ ofinsulation, twist strands together.b. Loosen screws. Insert each conductor under one screw. Screw connections must be tight. Do not mix solid and stranded type wires under one screw. Make sureinsulation clears Pressure Plate.4. Mount Power PackWARNING! TO PREVENT SERIOUS INJURY: Verify that installation surface has no hidden utility lines before drilling or driving screws.a. Using included template, mark and drill mounting holes.b. Insert two included anchors into the holes and two included screws into the anchors leaving about 1/4″ of threads exposed.c. Place large center of keyholes on back of Power Pack over screw heads and pull down gently to lock screws into keyholes. Do not plug in Power Pack.5. Install Light Fixturesa. Lay out light fixtures in desired locations. The first light fixture must be installed at least 10 feet from Power Pack.b. Lay out Landscape Wire from Power Pack along path of light fixtures.c. Install light fixtures, then connect to wire according to light fixture’s instructions.d. Bury wire no deeper than 6". 6. Plug in Power Cord. Do not usean extension cord.7. Press Up/Down buttons to scroll through menu.a. A = Auto - Dusk to dawn.b. 1 -9 = Hours on after dusk.c. O = Manual - On until manually turned off.Procedures not specifically explained in this manual mustbe performed only by a qualified technician.TO PREVENT SERIOUS INJURY FROM ACCIDENTAL OPERATION:Unplug the Power Pack from its electrical outlet before performing any procedure in this section.1. CLEAN PERIODICALLY with a damp towel.Do not clean with chemicals, solvents or harsh abrasives. Do not put too much pressureon the display or buttons while cleaning.2. WARNING! TO PREVENT SERIOUS INJURY: Ifthe plug or the supply cord is damaged, it mustbe replaced only by a qualified service technician.TroubleshootingPage 6For technical questions, please call 1-888-866-5797.Item 57998Record Serial Number Here:Note: If product has no serial number, record month and year of purchase instead.Note: Replacement parts are not available for this product. Refer to UPC 193175430588.Item 57998For technical questions, please call 1-888-866-5797.Page 7Harbor Freight Tools Co. makes every effort to assure that its products meet high quality and durability standards, and warrants to the original purchaser that this product is free from defects in materialsand workmanship for the period of 90 days from the date of purchase. This warranty does not apply to damage due directly or indirectly, to misuse, abuse, negligence or accidents, repairs or alterations outside our facilities, criminal activity, improper installation, normal wear and tear, or to lack of maintenance.We shall in no event be liable for death, injuries to persons or property, or for incidental, contingent,special or consequential damages arising from the use of our product. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation of exclusionmay not apply to you. THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS.To take advantage of this warranty, the product or part must be returned to us with transportation charges prepaid. Proof of purchase date and an explanation of the complaint must accompany the merchandise.If our inspection verifies the defect, we will either repair or replace the product at our election or we may elect to refund the purchase price if we cannot readily and quickly provide you with a replacement. We will return repaired products at our expense, but if we determine there is no defect, or that the defect resulted from causes not within the scope of our warranty, then you must bear the cost of returning the product.This warranty gives you specific legal rights and you may also have other rights which vary from state to state.26541 Agoura Road • Calabasas, CA 91302 • 1-888-866-5797。
艾特顿低压电力保护器指南说明书

Eaton MPN5084VEAXX2QEaton Magnum low voltage power circuit breaker, Magnum PXR,Narrow frame, 800 A, 50 kA, Four-pole, Fixed vertical mounting,PXR25 LSIAM trip unitGeneral specificationsEaton Magnum low voltage power circuitbreakerMPN5084VEAXX2Q78668959497814.6 in16.8 in16.3 in120 lbNEMA Compliant SABA Listed CCC MarkedCE Marked KEMA CertifiedLloyd's Register Certified ANSIUL ListedCSA CertifiedABS CertifiedDNV GL CertifiedProduct Name Catalog NumberUPCProduct Length/Depth Product Height Product Width Product Weight Compliances CertificationsNarrow Four-pole Magnum PXRNarrow Magnum PXR25 LSI ARMSFour-pole800 A50 kAIC50 kAIC800 AZone selective interlocking application paper Magnum circuit breakers with Power Xpert Release trip units product aid Selevctive coordination application paper - IA0120000E3Magnum PXR and PD-SB standard and narrow frame UL Certificate of ComplianceMagnum PXR and PD-SB double and double narrow frame UL Certificate of ComplianceMicrosoft Word - Power Xpert Protection Manager Quick Start Guide.docxPower Xpert Release trip unit for Magnum PXR circuit breakers PXR 20/25 user manualFrame Number of poles TypeFrame Series Trip TypeNumber of poles Rated uninterrupted current (Iu)Interrupt rating Interrupt rating Rated uninterrupted current (Iu)Application notesBrochuresCatalogsCertification reportsManuals and user guidesEaton Corporation plc Eaton House30 Pembroke Road Dublin 4, Ireland © 2023 Eaton. All Rights Reserved. Eaton is a registered trademark.All other trademarks areproperty of their respectiveowners./socialmediaMagnum PXR low voltage power circuit breakers user manual Power Xpert Protection Manager x64 22.6 1 Power Xpert Protection Manager x32 22.06 1 Eaton Specification Sheet - MPN5084VEAXX2Q Low voltage circuit breakers guide spec Magnum PXR 20/25 electronic trip units time current curves Safer by design: arc energy reduction techniques Molded case and low-voltage power circuit breaker health Cyber security white paperSoftware, firmware, and applications Specifications and datasheetsTime/current curvesWhite papers。
美达顿低压电力电路保护器说明书

Eaton MPN5164VEAXX2QEaton Magnum low voltage power circuit breaker, Magnum PXR,Narrow frame, 1600 A, 50 kA, Four-pole, Fixed vertical mounting,PXR25 LSIAM trip unitGeneral specificationsEaton Magnum low voltage power circuitbreakerMPN5164VEAXX2Q78668959721414.6 in16.8 in16.3 in120 lbNEMA Compliant CE Marked SABA Listed CCC Marked UL ListedANSIKEMA CertifiedCSA CertifiedLloyd's Register Certified DNV GL CertifiedABS CertifiedProduct Name Catalog NumberUPCProduct Length/Depth Product Height Product Width Product Weight Compliances CertificationsNarrow Four-pole Magnum PXRNarrow Magnum PXR25 LSI ARMSFour-pole1600 A50 kAIC50 kAIC1600 AZone selective interlocking application paper Magnum circuit breakers with Power Xpert Release trip units product aid Selevctive coordination application paper - IA0120000E3Magnum PXR and PD-SB double and double narrow frame UL Certificate of ComplianceMagnum PXR and PD-SB standard and narrow frame UL Certificate of ComplianceMicrosoft Word - Power Xpert Protection Manager Quick Start Guide.docxPower Xpert Release trip unit for Magnum PXR circuit breakers PXR 20/25 user manualFrame Number of poles TypeFrame Series Trip TypeNumber of poles Rated uninterrupted current (Iu)Interrupt rating Interrupt rating Rated uninterrupted current (Iu)Application notesBrochuresCatalogsCertification reportsManuals and user guidesEaton Corporation plc Eaton House30 Pembroke Road Dublin 4, Ireland © 2023 Eaton. All Rights Reserved. Eaton is a registered trademark.All other trademarks areproperty of their respectiveowners./socialmediaMagnum PXR low voltage power circuit breakers user manual Power Xpert Protection Manager x32 22.06 1 Power Xpert Protection Manager x64 22.6 1 Eaton Specification Sheet - MPN5164VEAXX2Q Low voltage circuit breakers guide spec Magnum PXR 20/25 electronic trip units time current curves Safer by design: arc energy reduction techniques Cyber security white paperMolded case and low-voltage power circuit breaker healthSoftware, firmware, and applications Specifications and datasheetsTime/current curvesWhite papers。
西门子低压变压器防炸保护安装说明书

/switchgearSwitchgear Instruction and Installation GuideType 2B Arc Resistant WL Low Voltage Metal-Enclosed SwitchgearIMPORTANTThe information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation, and maintenance of the equipment purchased. Siemens reserves the right to make changes in the specifications shown herein or to make improvements at any time without notice or obligations. Should a conflict arise between the general information contained in this publication and the contents of drawings or supplementary material or both, the latter shall take precedence.NOTEThese instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired, or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the local Siemens sales office.The contents of this instruction manual should not become part of or modify any prior or existing agreement, commitment, or relationship. The sales contract contains the entire obligation of Siemens Industry, Inc. The warranty contained in the contract between the parties is the sole warranty of Siemens Industry, Inc. Any statements contained herein do not create new warranties or modify the existing warranty.2Switchgear Instruction and Installation Guide Type 2B Arc Resistant WL Low Voltage Metal-Enclosed Switchgear Table of ContentsIntroduction and SafetyIntroduction 4Qualified person 4Signal words 4Dangerous procedure 4Field Service Operation 4General DescriptionIntroduction 5Scope 5General Description 5Special FeaturesSwitchgear – Rear 6Switchgear – Front 7Breaker Compartment 7Auxiliary Compartment 8Bottom Compartment Breaker Cradle 8Riser Base 8InstallationDimensional Data for Rear Connected Arc Resistant Switchgear 9 - 12Arc Resistant Gear with Overhead Plenum 13Dimensional Data for Front & Rear Connected – Wall Mounted 14 - 15Dimensions – Floor Mount (Requires Rear Access) 16Switchgear Dimensions – Side View (Without Overhead Plenum) 17Dimensions – Incoming Section – Cable Entry Top 18Dimensions – Incoming Section – Cable Entry Bottom 19Dimensions – Left Incoming Section – Sentron Busway Top and Bottom 20Dimensions – Right Incoming Section – Sentron Busway Top and Bottom 21Dimensions – Feeder Cable Section (Area) – Cable Entry Top 22Dimensions – Feeder Cable Section (Area) – Cable Entry Bottom 23Installation Instructions for Overhead Plenum 24 - 273Switchgear Instruction and Installation GuideIntroductionType 2B Arc Resistant WL low voltage switchgear is designed to meet all applicable UL, ANSI, NEMA and IEEE standards.It is designed and performance tested to ANSI C37.20.7 to provide an additional degree of personnel protection from internal arcing faults. Successful application and operation of this equipment depends as much upon proper installation and maintenance by the user as it does upon the careful design and construction by Siemens.The purpose of this Instruction Manual is to assist the user in developing safe and efficient procedures for the installation, maintenance and use of the equipment. This Instruction Manual acts a supplement to Siemens Rear and Front Connected Type WL Low Voltage Switchgear Instruction and Installation Guides.Application of Arc Resistant Low Voltage Switchgear meeting the requirements of IEEE C37.20.7 does not eliminate the requirements of Personal Protection Equipment (PPE). Contact the nearest Siemens representative if any additional information is desired.Qualified PersonFor the purpose of this manual and product labels, a Qualified Person is one who has the skills and knowledge related to the construction and operation of the electrical equipment and installations and has received safety training to recognize and avoid the hazards involved. In addition, this person has the following qualifications:• Training and authorization to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices.• Training in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses, faceshields, flash clothing, etc., in accordance with established safety procedures.• Training in rendering first aid. Signal WordsThe signal words “Danger,” “Warning” and “Caution” usedin this manual indicate the degree of hazard that may be encountered by the user. These words are defined as:Danger – Indicates an imminently hazardous situation which if not avoided, will result in death or serious injury.Warning – Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.Caution – Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury Dangerous ProceduresIn addition to other procedures described in this manual as dangerous, user personnel must adhere to the following: 1. Always work on de-energized equipment. Alwaysde-energize a breaker and remove it from the switchgear before performing any tests, maintenance or repair.2. Always discharge energy from closing and opening(tripping) springs before performing maintenance on circuit breakers.3. Always let an interlock device or safety mechanismsperform its function without forcing or defeatingthe device.Field Service OperationSiemens Industrial Services Division can provide the following support services for Type WL low voltage switchgear.Call 1-800-333-7421 to obtain additional information and schedule an appointment.• Start-up and Commissioning• Component and System Testing• Maintenance (Scheduled and Preventative)• Repair and Refurbishing• On Site Operational TrainingType 2B Arc Resistant WL Low Voltage Metal-Enclosed Switchgear Introduction and Safety4Switchgear Instruction and Installation GuideIntroductionSiemens Type 2B Arc Resistant Metal-Enclosed Low Voltage Switchgear is designed to provide an additional degree of protection for personnel performing normal operating duties in proximity to the energized equipment. Such duties include opening or closing breakers, closed door racking of breakers, reading of instruments, or other such activities that do not require the opening of doors or removal of covers except doors or covers of compartments specifically identified aslow-voltage control or instrumentation compartments. It is designed and performance tested to ANSI C37.20.7 to provide an additional degree of protection from internal arcing faults. Should additional information be desired, including replacement instruction books, contact yourSiemens representative.ScopeThese instructions cover the installation and maintenanceof Siemens Type 2B WL Arc Resistant metal enclosed low voltage switchgear assemblies, using the Type WL UL -1066 low voltage power circuit breakers. A typical indoor Type 2B WL arc resistant switchgear assembly is shown in Figure 1.This instruction manual acts as a supplement to Siemens Rear and Front Connected Type WL Low Voltage Switchgear Instruction and Installation Guides. This manual discusses the special features and maintenance associated with arc resistant switchgear.General DescriptionType 2B Arc Resistant WL switchgear is an assembly of an indoor enclosure and mounting base with arc plenum. It has an insulated bus bar system, removable rear cover panels/ doors secured with captive screws, section barriers and cable compartment barriers. (Sections Barriers & Cable compartment barriers are Optional for FC). Flame retardant barriers and shutters are provided in power circuit breaker compartments. One piece circuit breaker compartment doors with insert panels for fuses, indicating lights and control switches are used when required.The following must be maintained for proper functioning of Arc Resistant switchgear. 39” (990) minimum front aisle (FS3 4 Pole breaker require 42” [1066] minimum), and 36” (914) minimum rear aisle (Rear Connected only). Working space requirements around electrical equipment are specified in the National Electrical Code® (NEC 110.26 2017). Minimum Ceiling Height Requirement 36” (900) above vent stack (NEC 408.18 2017):136” (3454) – Arc Resistant switchgear WITHOUT Overhead PlenumAlternate Manufacturer’s Requirement 18” (457)above vent stack (For Non-Combustible* Ceiling)118” (2997) – Arc Resistant switchgear WITHOUTOverhead Plenum120” (3048) – Arc Resistant switchgear WITHOverhead Plenum*Non-Combustible as defined by AHJ and/or NECThe arc resistant ratings are listed on the switchgearrating label. Ratings are given for:(1) Accessibility Type,(2) Arcing SHORT-CIRCUIT current and voltage, and(3) Arcing duration.Type 2B Arc Resistant WL Low Voltage Metal-Enclosed SwitchgearGeneral DescriptionFront view of switchgear.56Switchgear Instruction and Installation GuideRear Isometric view of Front Connected SwitchgearTop cover plate pressure relief flaps (Rear Connected)• The top cover flaps are applicable with Arc Resistant Construction without Overhead Plenum• These flaps are closed under normal conditions.• The flaps open outward in the event of an arcing fault to relieve internal pressure.• The opening of flaps should not be blocked by cables, conduits, bus duct, etc.• A clear space of 22” must be maintained above the flaps. Rear cover pressure dams (Rear Connected)• All the vents in the rear side of switchgear have pressure dam flaps installed inside.• During normal operation the flaps should be open by 2” to 3” for venting.• These flaps close in the event of arcing fault to prevent arc gases from exiting the rear of the equipment.• The flaps should not be modified, removed or blocked open.Enclosure and Rear Covers (Rear and Front Connected)• Reinforced enclosure to withstand pressure from internal arcing faults.• Reinforced bolted rear covers/doors.• Ensure that all screws are in place and tightenedTop vent stack pressure relief flaps (Front Connected)• The flaps are applicable with Arc Resistant Construction without Overhead Plenum.• These flaps are closed under normal conditions.• The flaps open outward in the event of an arcing fault to relieve internal pressure.• The opening of flaps should not be blocked by cables, conduits, bus duct, etc.Type 2B Arc Resistant WL Low Voltage Metal-Enclosed SwitchgearSpecial FeaturesSwitchgear – RearRear Isometric view of Rear Connected Switchgear7Switchgear Instruction and Installation GuideSwitchgear – FrontBreaker CompartmentFront view of SwitchgearFront View of Breaker CompartmentFront view of Breaker CompartmentEnhancements• Reinforced and gasketed front doors with additional hinges and latching means. Ensure that all doors are properly secured before placing gear in service.•placed back into service.• be installed under the switchgear.Type 2B Arc Resistant WL Low Voltage Metal-Enclosed SwitchgearSpecial FeaturesBreaker compartment partsBreaker compartment gap protection parts provide protection in the event of arcing fault.Flame Retardant parts are attached on the back of metal gap protection partsThese parts must be in place during normal operation.If they are removed during installation or servicing, they must be replaced before gear is energized.8Switchgear Instruction and Installation GuideAuxiliary compartmentRiser BaseFront view of Riser BaseAuxiliary compartment parts• Auxiliary bucket gap protection parts provide protection in the event of arcing fault.• Flame Retardant parts are attached on the back of metal gap protection parts.• These parts must be in place during normal operation.• If they are removed during installation or servicing, they must be replaced before gear is energized.Gap between Switchgear and Riser Base• The gap between the Mounting Base and the Switchgear must be closed after installation with silicone caulking compound. Silicone caulking compound is installed at the factory if the switchgear is shipped installed on the Mounting Base. If the Mounting Base is shipped separately, a tube of silicone caulking compound is furnished withthe switchgearBreaker Cradle Button Plug• The button plug must be replaced after installing or servicing anchor bolt.• This part must be in place during normal operation.Bottom Compartment Breaker CradleIsometric view of D-CompartmentIsometric view of Auxiliary CompartmentType 2B Arc Resistant WL Low Voltage Metal-Enclosed SwitchgearSpecial featuresSwitchgear Instruction and Installation GuideSwitchgear Instruction and Installation Guide1213Dimensional Data for Front and Rear Connected Arc Resistant Gear with Overhead Plenum10.0Front View: WL Arc Resistant Switchgear with Overhead PlenumNote: Dimensions shown in inches and (mm). Drawings are not to scale.1. 118 (2997) minimum room ceiling height is required for ventilation of arc products for LV Arc resistant switchgear without overhead plenum.2. 120 (3048) minimum room ceiling height is required for LV Arc resistant switchgear with overhead plenum.3. Custom designed exhaust duct is provided when the exit is towards the front to clear the overhead hoist. Cross-sectional area of the exhaust duct remains same as shown in figure. Wall cutout required is same at 104 (2641) from floor.4. Siemens to provide weatherproof box to be installed outside the exterior wall over the exhaust duct exit.5. The area outside the exhaust duct vent needs to be kept clear of personnel and equipment due to the potential for pressurized exhaust gasses being expelled in the area as a result of arcing fault in the switchgear. An area of 4 feet X 4 feet centered on exhaust duct vent needs to be clear at all times.6. Exhaust duct is not self-supporting, recommended support every 6 linear feet minimum. The duct supports are not supplied by Siemens and must be supplied by the purchaser or the installing contractor.7. LV Arc Resistant switchgear with and without overhead plenum is to be installed on a solid surface to maintain the arc ratings. Consult factory for site conditions where a solid floor is not an option.Typical Drop Rod/Unistrut trapeze hanger arrangement shownExhaust DuctUnistrut5.0(127)2.1 (53)3.0 (76)Space for secondaryleads from above. Available onSections with removable conduit plate. Not available with Overhead PlenumoptionSpace for secondary leads from above & below.Above: All Sections2.0 (51)1.0 (25)7.0(179)(2) Holes for .50 (12mm)Grade 5 anchor bolts(Not furnished with equipment) 0.5 (13)Rear Space for secondaryleads from below: Breaker sections 5.0 (127) Space for secondary leads from above. Available on Sections with removable conduit plate. Not available with Overhead Plenum option2.0 (51)1.0 (25)2X for” anchors 0.5 (13)Front ViewRiser Base4.0 (102)2X for anchors38.0 (965) Anchor Bolt5.0(127) Space for secondaryleads from above.Available on Sections withremovable conduit plate.Not available withOverhead Plenum option1.0 (25)2.0 (51)Space for secondaryleads from below:Breaker sections4X for”anchorsFront Compartment BusCompartment30 (762) MinimumAisle Spacerecommended forFloor Mount BracketsinstallationRear Floor Mount(optional)0.5 (13)Maximum available conduit space at Top27.5 (699)2.25 (57) Typ13.9 (353)15.9 (404)Front Plan ViewFig - 5 RearW = 32 Section Width1.75 (44) Typ.Front Plan ViewFig- 614.5 (368)28.5 (724) Available conduit space at BottomAvailable Bottom Conduit Area when Lineup has Center Incoming and Sectionincludes a Bottom Through Bus16.2 (411)10 (254)Additional Space: 28.5 (724) X 10 (254)When Lower Auxiliary Compartment NOT present13.65 (347)21 (533)8.75 (222)Not Available at 4000A & 5000A: 28.5(724) X 5(127)5 (127)RearFront13 (330)22.4 (569)Plan View15.5 (394)D RearBusway Phase Orientation (ØA, ØB, ØC, N Front to Back)ØAØBØCN Cut-out area at Top. Bottom is open.14 (356)Fig- 7ESentron Busway Plug Rating (Cu)D 22 (559)RearCut-out area at Top. Bottom is openFront Plan ViewFig- 8GF13 (330)15.5 (394)Busway Phase Orientation (ØA, ØB, ØC, N Front to Back)ØAØBØCN 22.4 (569)14(356)Sentron Busway Plug Rating (Cu)F 22 (559)Maximum available conduit space at TopHSection Width W = 22, H = 17.5 (445) Section Width W = 30, H = 25.5 (648) Section Width W = 40, H = 35.5 (902)WSection Width2.25 (57) Typ.RearFront Plan View13.9 (353)15.9 (404)Fig- 9Available conduit space at BottomFront 1.75 (44) Typ.Additional conduit space available when Compartment D breaker not presentJSection Width W = 22, J = 18.5 (470) Section Width W = 30, J = 26.5 (673) Section Width W = 40, J = 36.5 (927) 25 (635) 3.7 (94)6.5 (165)11.75 (298)Not Available at 4000A & 5000A:J X 5(127)5 (127)RearPlan View Fig- 1024Switchgear Instruction and Installation GuideType 2B Arc Resistant WL Low Voltage Metal-Enclosed SwitchgearInstallation Instructions for Overhead PlenumOverhead Plenum assembly over the Switchgear section consists of two main components as shown:Plenum Vent Stack Front Iso View – End SectionSection PlenumA. Installation of Plenum Vent stack to the Switchgear sectionPlenum Vent Stack attaches to the Left and Right Lifting-Eye plate tab holes.Lifting eye plate25Switchgear Instruction and Installation GuideB. Installation of Section Plenum to the Switchgear sectionType 2B Arc Resistant WL Low Voltage Metal-Enclosed SwitchgearInstallation Instructions for Overhead PlenumFront Iso View – End SectionAdjacent SectionSection Plenum attaches to the Plenum Vent Stack.Slide the adjacent Section Plenums in the splice groove.Attach the Section Plenum to the Vent Stack.26Switchgear Instruction and Installation GuideC. Installation of Section Plenum when Duct Exit is Rear/Front of the Switchgear sectionD. Installation of Exhaust Duct to the Switchgear sectionType 2B Arc Resistant WL Low Voltage Metal-Enclosed SwitchgearInstallation Instructions for Overhead PlenumThe blow open trap doors need to align with the direction of exit path if front or rear duct is usedSlide the Exhaust Duct in the splice groove and attach toSection Plenum27Switchgear Instruction and Installation GuideE. Installation of End Exhaust Duct section Type 2B Arc Resistant WL Low Voltage Metal-Enclosed SwitchgearInstallation Instructions for Overhead PlenumOutside of BuildingOutside of BuildingInside ofBuildingInside ofBuildingExhaust Duct End Section10.05.50Exterior Wall of BuildingExhaust Duct End Section and Exterior Wall of Building ShownWeatherproof AssemblyCalk allCalk allseamsLeft ViewLeft ViewIsometric ViewIsometric ViewNote:1. The exhaust duct end section must not be extended more than 10 inches outside the building for proper functioning of exhaust flap when weather proof assembly is installed over the exhaust duct.Notes:1. The weatherproof assembly must be mounted 5.50 inches above theexhaust duct section for proper functioning of exhaust flap.2. The weatherproof assembly can extend up to 10 feet.Weatherproof SectionPublished bySiemens Industry, Inc. 2019.Siemens Industry, Inc.5400 Triangle ParkwayNorcross, GA 30092For more information, please contactour Customer Support Center.Phone: 1-800-241-4453E-mail: *******************/switchgearOrder No.: LVIM-ARCII-1019 BA(Siemens Internal Part Number 11-C-9887-01Rev. 2)Printed in U.S.A.© 2019 Siemens Industry, Inc.The technical data presented in this document is based on an actual case or on as-designed parameters, and therefore should not be relied upon for any specific application and does not constitute a performance guarantee for any projects. Actual results are dependent on variable conditions. Accordingly, Siemens does not make representations, warranties, or assurances as to the accuracy, currency or completeness of the content contained herein. If requested, we will provide specific technical data or specifications with respect to any customer’s particular applications. Our company is constantly involved in engineering and development. For that reason, we reserve the right to modify, at any time, the technology and product specifications contained herein.。
美汀低压电源保护电路断路器产品说明说明书

Eaton MPN8504CEAXX2QEaton Magnum low voltage power circuit breaker, Magnum PXR,Double narrow frame, 5000 A (NNABCABC), 85 kA, Four-pole,Drawout horizontal with motorized racking mounting, PXR25LSIAM trip unitGeneral specificationsEaton Magnum low voltage power circuitbreakerMPN8504CEAXX2Q78668960661916.3 in16.8 in32.4 in177 lbSABA Listed CCC Marked NEMA Compliant CE Marked ANSIKEMA CertifiedLloyd's Register Certified UL ListedCSA CertifiedABS CertifiedDNV GL CertifiedProduct Name Catalog NumberUPCProduct Length/Depth Product Height Product Width Product Weight Compliances CertificationsDouble narrow Four-pole Magnum PXRDouble narrow Magnum PXR25 LSI ARMSFour-pole5000 A85 kAIC85 kAIC5000 AZone selective interlocking application paper Magnum circuit breakers with Power Xpert Release trip units product aid Selevctive coordination application paper - IA0120000E3Magnum PXR and PD-SB standard and narrow frame UL Certificate of ComplianceMagnum PXR and PD-SB double and double narrow frame UL Certificate of ComplianceMicrosoft Word - Power Xpert Protection Manager Quick Start Guide.docxMagnum PXR low voltage power circuit breakers user manualFrame Number of poles TypeFrame Series Trip TypeNumber of poles Rated uninterrupted current (Iu)Interrupt rating Interrupt rating Rated uninterrupted current (Iu)Application notesBrochuresCatalogsCertification reportsManuals and user guidesEaton Corporation plc Eaton House30 Pembroke Road Dublin 4, Ireland © 2023 Eaton. All Rights Reserved. Eaton is a registered trademark.All other trademarks areproperty of their respectiveowners./socialmediaPower Xpert Release trip unit for Magnum PXR circuit breakers PXR 20/25 user manualPower Xpert Protection Manager x64 22.6 1 Power Xpert Protection Manager x32 22.06 1 Eaton Specification Sheet - MPN8504CEAXX2Q Low voltage circuit breakers guide spec Magnum PXR 20/25 electronic trip units time current curves Molded case and low-voltage power circuit breaker health Cyber security white paperSafer by design: arc energy reduction techniquesSoftware, firmware, and applications Specifications and datasheetsTime/current curvesWhite papers。
厂用低压变的保护-站用变-干式变压器的保护课件

3、 零序过流保护:该保护为厂低变低压侧过流保护,动作后跳开变压器高、低压 侧全部开关,液晶显示屏上显示保护动作信息,且保护屏上“报警”、“跳闸” 灯亮,厂低变控制屏上“保护动作”光字亮。
7、 油温高:该保护只动作于信号,动作后,保护屏上“油温高”灯亮,厂低变控 制屏上“温度”光字亮。
故障低压变的保护
电运五班:XXX
厂用低压变保护概述
• 变压器保护装置主要由速断保护、过流保 护、高压侧接地保护、零序过流保护、非 电量保护构成。非电量保护设有变压器本 体重瓦斯、轻瓦斯、油温高保护。
厂低变保护在一次回路图配置
各保护出口情况介绍
1、 速断保护:该保护动作后跳开变压器高、低压侧全部开关,液晶显示屏上显示 保护动作信息,且保护屏上“报警”、“跳闸”灯亮,厂低变控制屏上“保护 动作”光字亮。
4、 高压侧接地保护:该保护为厂低变高压侧接地保护,动作后液晶显示屏上显示 保护告警信息,且保护屏上“报警”灯亮及厂低变控制屏上“告警”光字亮。
5、 本体重瓦斯保护:该保护动作后跳开变压器高、低压侧全部开关,保护屏上 “本体重瓦斯”、“跳闸”灯亮,厂低变控制屏上“瓦斯动作”、“保护动作” 光字亮。
6、 本体轻瓦斯保护:该保护只动作于信号,动作后,保护屏上“本体轻瓦斯”灯 亮,厂低备控制屏上“瓦斯信号”光字亮。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
NS 913低压变压器保护测控装置说明书V1.1南京南自科技发展有限公司2003年12月*本说明书可能会被修改,请注意最新版本资料目录1.概述 (1)2.主要技术参数 (3)3.保护功能 (6)4.测量、控制以及事件记录功能 (8)5.硬件结构说明 (9)6.使用操作说明 (11)7.装置参数一览 (13)1 概述NS 913S低压变压器保护测控装置适用于低压变压器的保护、测量及控制。
可以在开关柜就地安装,也可以集中组屏安装。
1.1 装置主要特点⏹高速的DSP处理器采用高性能DSP芯片,提供了高速的数据处理能力,保证了高性能实时算法的实现,提高了装置的可靠性和整体性能。
⏹快速、高精度采样采用快速14位高精度采样芯片,并采用频率自动跟踪技术,保证了很高的保护和测量计算精度。
⏹强大的通讯功能采用CAN网作为主通讯接口,传输速率可达1Mb/s,系统响应速度快。
⏹可靠的操作箱功能独立的跳、合闸启动和保持回路设计。
⏹高可靠的电磁兼容设计标准背插式工业机箱,电路板采用表面贴装技术以及多层板工艺,选用快速瞬变电压抑制器件,使装置具有很强的电磁兼容能力。
1.2 保护功能配置⏹相间过流保护◆速断保护◆定时限过流保护◆反时限过流保护◆过负荷保护⏹高压侧零序过流保护⏹低压侧零序过流保护1.3 数据采集功能⏹实时采集电流、电压、有功、无功、功率因数、频率⏹8路遥信量1.4 事件记录及故障录波⏹保护动作记录⏹告警事件记录⏹遥信变位记录⏹操作命令记录1.5 控制功能⏹就地/远方分闸、合闸控制⏹远方定值修改⏹远方保护投/退1.6 操作箱功能⏹跳位、合位指示⏹可靠的自保持及防跳设计1.7 通信功能⏹CAN总线⏹RS-485总线2 主要技术参数2.1 额定参数2.1.1 直流电源额定电压:220V或110V(订货说明)允许偏差:-20%~15%纹波系数:<5%功耗:<15W2.1.2 交流参数交流电压:100V交流电流:5A或1A(订货说明)频率:50HZ交流电流功耗:<0.5V A/相(额定电流5A)<0.1V A/相(额定电流1A)交流电压功耗:<0.1V A/相交流电流过载能力:2倍额定电流连续工作20倍额定电流连续工作10秒40倍额定电流连续工作1秒交流电压过载能力: 1.2倍额定电压连续工作2.2 保护参数2.2.1 电流元件动作电流:0.1~20In级差:0.01A误差:<3%2.2.2 整组动作时间(包括继电器固有时间)1.2倍整定值:30ms2.3 测量精度电流、电压:0.2级有功、无功:0.5级2.4 绝缘性能2.4.1 绝缘电阻装置的带电部分和非带电部分及外壳之间,以及电气上无联系的各电路之间,用开路电压500V的兆欧表测量其绝缘电阻值,均大于100MΩ。
2.4.2 介质强度在正常试验大气条件下,装置能承受频率为50Hz,历时1min的工频耐压试验而无击穿闪络及元器件损坏现象,试验电压2kV。
2.4.3 冲击电压在正常试验大气条件下,装置的直流电源输入回路、交流输入回路、输出触点回路对地以及回路之间,能承受1.2/50μs的标准雷电波的短时冲击电压试验,开路试验电压5KV,装置应无绝缘损坏。
2.5 机械性能2.5.1 振动技术条件:装置能承受GB7621中16.3规定的严酷等级为Ⅰ级的振动耐久能力试验。
2.5.2 冲击技术条件:装置能承受GB7621中17.5规定的严酷等级为Ⅰ级的冲击耐久能力试验。
2.5.3 碰撞技术条件:装置能承受GB7621第18章规定的严酷等级为Ⅰ级的冲击耐久能力试验。
2.6 气候条件2.6.1 环境温度工作温度:-20℃~+55℃存储温度:-25℃~+70℃2.6.2 相对湿度:≤95%,无凝露2.6.3 大气压力:70~106 KPa2.7 电磁兼容2.7.1 静电放电抗干扰度通过GB/T 14598.14-1998标准、静电放电抗干扰4级试验。
2.7.2 电快速瞬变脉冲群抗扰度通过GB/T 14598.10-1996标准、电快速瞬变脉冲群抗扰度3级试验。
2.7.3 浪涌(冲击)抗扰度通过GB/T 17626.5-1999标准、浪涌(冲击)抗扰度3级试验。
2.7.4 脉冲群抗扰度通过GB/T 14598.13-1998标准、脉冲群抗扰度3级试验。
3 保护功能3.1 相间过流保护本装置的相间过流保护配置了两段式定时限过流保护以及独立的反时限过流保护。
3.1.1 反时限特性本装置提供三种反时限特性(依据IEC225-4标准),可以通过整定控制字选择其中一种,构成反时限过流保护。
其中T P 为时间常数,I P为启动电流。
3.2高压侧过负荷保护过负荷保护可选择发信或跳闸。
过负荷元件监视三相电流,当有一相电流值大于定值时动作。
3.3高压侧零序过流保护本装置采用零序互感器获取低压变压器高压侧的零序电流,构成低压变压器高压侧的单相接地保护。
3.4低压侧零序过流保护装置采集变压器低压侧中线线电流,构成低压侧零序过流保护。
为便于与下一级保护配合,装置提供定时限零序过流保护以及反时限过流保护,反时限包括一般反时限、非常反时限以及极端反时限。
4 测量、控制以及事件记录功能4.1 测量功能4.1.1 交流量装置可实时采集电压、电流、有功功率、无功功率、频率及功率因数。
4.1.2 状态量装置设有8路外部开关量接口,用于保护投退、刀闸等开关量的采集;装置还设有4路内部状态量的采集,用于操作回路如跳位、合位等信号的采集。
4.2 控制功能装置可接收遥控命令实行开关的远方分、合控制。
还可通过菜单手动命令对开关进行手动分合操作。
保护定值的修改、保护功能的投退均可由远方控制。
4.3 事件记录功能装置的事件记录保存了在运行时发生的重要事件,失电后不丢失。
共有四类记录:动作事件记录、告警事件记录、遥信变位事件记录和操作命令记录。
每一类记录均为16条,采用循环覆盖的保存方式。
动作事件记录的内容为作用于跳闸的保护动作时间、保护名称。
告警事件记录的内容为作用于告警信号的保护动作时间,名称,以及装置自检出错告警等。
遥信变位事件记录的内容为接入装置的遥信量发生变位时的状态和时间。
操作命令记录的内容为在本机或遥控修改定值、就地或遥控分、合闸等操作的发生时间和操作名称。
事件记录中的操作命令记录是不可删除的,其他事件记录可以手动删除。
5 硬件结构说明5.1 机箱结构装置采用标准5U机箱,由模拟量模件、DSP模件、信号出口模件、电源模件、显示面板组成。
装置机箱采用背插式结构,各模件功能相对独立,便于调试和维护工作。
机箱示意和开孔尺寸见附图。
5.2 模拟量模件模拟量模件包括交流电流输入回路、交流电压输入回路和直流量输入回路。
交流电流输入回路由电流互感器和滤波电路组成,交流电压输入回路由电压互感器和滤波回路组成,直流量输入回路由光耦和滤波回路组成。
模拟量模件将系统二次侧的电流、电压以及直流量变换为装置可以使用的模拟量,提供给DSP模件。
同时模拟量输入回路还具有很强的隔离屏蔽和滤波功能,可以隔离和抑制系统中可能出现的干扰信号。
5.3 DSP模件DSP模件是装置的核心部分,模件内包括高效的DSP芯片和大规模可编程器件,配合高速存储器和高精度采样芯片,保证了装置的可靠性和先进性。
插件采用多层印制板及表面贴装工艺,提高了装置的稳定性及抗电磁干扰能力。
5.4 信号出口模件信号出口模件由信号继电器、出口继电器及开关操作回路组成,对外提供信号空接点、跳闸空接点,以及开关的防跳回路和位置信号。
其中开关操作回路部分完全独立,简化了设计和调试工作,进一步提高了装置可靠性。
5.5 电源模件电源模件提供装置的工作电源。
该模件还包括8路遥信量回路(可扩展到16路),为提高遥信回路的抗干扰能力,遥信采用强电(DC220V或DC110V)输入,完善、周到的设计可防止回路电缆接地引起的遥信状态变位。
5.6 面板显示面板包括液晶屏、键盘和信号灯。
其中液晶显示为全中文菜单,空闲状态时显示屏背光和显示可以自动关闭。
5.7 指示灯装置面板上有指示灯,其中“运行”和“跳位”灯为绿色,其它为红色,具体意义如下。
表2.1 面板指示灯意义5.8 键盘表2.2 面板键盘意义6 使用操作说明6.1 上电运行装置在上电前,信号端子中的“装置故障”信号接点处于闭合状态。
上电后,该接点打开。
正常情况下面板上的“运行”指示灯会连续闪烁,周期大约为1秒。
装置上电后自动进行自检,如果在运行中出现故障,“运行”指示灯会停止闪烁,保持常亮或熄灭状态,同时信号端子中的“装置故障”信号接点会自动闭合。