Close-off pressures are variable and actuator dependent, consult Select Pro and/or Price Guide for specifics.
Application
These valves are designed to meet the needs of HVAC and commercial applications requiring bubble tight shut-off for liquids. Typical applications include chiller isolation, cooling tower isolation, change-over systems, large air handler coil control, bypass and process control applications. The large Cv values provide for an economical control valve solution for larger flow applications. Designed for use in Victaulic® piping systems.
Jobsite Note
Valve assembly should be stored in a weather protected area prior to
installation. Reference the butterfly valve installation instruction for additional information.
DR
A B C D
E
F
11.3” [286] 5.9” [150]15.7” [400]11.9” [302]
3.7” [95]
Safety Notes
WARNING: For Belimo products sold in California: these products do or may contain chemicals which are known to the State of California to cause cancer and or birth defects or other reproductive harms. For more information see .
F6150VIC Technical Data Sheet
Pressure Enhanced Rubber Seat
D a t e c r e a t e d , 09/11/2019 - S u b j e c t t o c h a n g e . © B e l i m o A i r c o n t r o l s (U S A ), I n c .
PK
A B C D
E
F
11.9” [302] 5.9” [150]20.7” [527]16.9” [428]
3.7” [95]
Dimensions (Inches [mm])
PR
A B C D
E
F
11.7” [298] 5.9” [150]18.2” [463]14.4” [366]
3.7” [95]
F6150VIC Technical Data Sheet
Pressure Enhanced Rubber Seat
D a t e c r e a t e d , 09/11/2019 - S u b j e c t t o c h a n g e . © B e l i m o A i r c o n t r o l s (U S A ), I n c .
Control Signal must be specified at time of order. Control cannot be changed via field wiring.
Safety Notes
WARNING: For Belimo products sold in California: these products do or may contain chemicals which are known to the State of California to cause cancer and or birth defects or other reproductive harms. For more information see .
DRCX24-3-T Technical Data Sheet
On/Off or Floating Point, Non-Spring Return, 24 V
D a t e c r e a t e d , 09/11/2019 - S u b j e c t t o c h a n g e . © B e l i m o A i r c o n t r o l s (U S A ), I n c .
Provide overload protection and disconnect as required.
Actuators may also be powered by 24 VDC.
For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller; the actuator internal
common reference is not compatible.
IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155).
16
Actuators are provided with a numbered screw terminal strip instead of
a cable.
Meets cULus requirements without the need of an electrical ground connection.
!
WARNING! LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
DRCX24-3-T Technical Data Sheet
On/Off or Floating Point, Non-Spring Return, 24 V
D a t e c r e a t e d , 09/11/2019 - S u b j e c t t o c h a n g e . © B e l i m o A i r c o n t r o l s (U S A ), I n c .。