AIR CONDITIONER
Cassette type
DESIGN & TECHNICAL MANUAL
DR_AU017EF_05
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Copyright © 2018 Fujitsu General Limited. All rights reserved.
CONTENTS
Part 1. INDOOR UNIT (1)
1. Specifications (2)
2. Dimensions (4)
2-1. Models: AUU9RLF, AUU12RLF, and AUU18RLF (4)
3. Wiring diagram (7)
3-1. Models: AUU9RLF, AUU12RLF, and AUU18RLF (7)
4. Capacity table (8)
4-1. Cooling capacity (8)
4-2. Heating capacity (11)
5. Fan performance (13)
5-1. Air velocity distributions (13)
5-2. Airflow (19)
6. Operation noise (sound pressure) (22)
6-1. Noise level curve (22)
6-2. Sound level check point (24)
7. Safety devices (25)
8. External input and output (26)
8-1. External input (26)
8-2. External output (28)
8-3. Fresh-air control output (29)
9. Remote controller (30)
9-1. Wired remote controller (30)
10. Function settings (32)
10-1.Function settings on indoor unit (32)
10-2.Function settings by using remote controller (34)
10-3.Function settings on wired remote controller (40)
11. Accessories (42)
12. Optional parts (43)
12-1.Controllers (43)
12-2.Cassette grille (44)
12-3.Others (44)
CONTENTS (continued)
Part 2. OUTDOOR UNIT (45)
1. Specifications (46)
2. Dimensions (47)
2-1. Models: AOU9RLFC, AOU12RLFC, and AOU18RLFC (47)
2-2. Installation space (48)
3. Refrigerant circuit (51)
3-1. Models: AOU9RLFC, AOU12RLFC, and AOU18RLFC (51)
4. Wiring diagrams (52)
4-1. Models: AOU9RLFC and AOU12RLFC (52)
4-2. Model: AOU18RLFC (52)
5. Capacity compensation rate for pipe length and height difference (53)
5-1. Models: AOU9RLFC and AOU12RLFC (53)
5-2. Model: AOU18RLFC (54)
6. Additional charge calculation (55)
6-1. Models: AOU9RLFC and AOU12RLFC (55)
6-2. Model: AOU18RLFC (55)
7. Airflow (56)
7-1. Model: AOU9RLFC (56)
7-2. Model: AOU12RLFC (56)
7-3. Model: AOU18RLFC (56)
8. Operation noise (sound pressure) (57)
8-1. Noise level curve (57)
8-2. Sound level check point (58)
9. Electrical characteristics (59)
10. Safety devices (60)
11. Accessories (61)
Part 1. INDOOR UNIT
CASSETTE TYPE:
AUU9RLF
AUU12RLF
AUU18RLF
1. Specifications
0918C A S S E T A U U 09-18
0918C A S S E T T E T Y P A U U 09-18R L F
2. Dimensions
2-1. Models: AUU9RLF, AUU12RLF, and AUU18RLF
20-7/8 (530): Hanging bolt position
4 (102)
5-5/16 (135)
9-13/16 (250)
2-15/16 (75)
1-3/16 (30)
1-3/16 (30)
10-5/16 (262)
21-1/4 (540): H a n g i n g b o l t p o s i t i o n
22-7/16 (570): I n d o o r u n i t
a (C e i l i n g o p e n i n g s )
•Cassette grille mounting state
T op view
5-14/16 t o 7-7/8 (150 t o 200
)
M i n . 17-11/16 (450)
Min. 17-11/16 (450)
Maintenance space
Side view
8-7/16 (215)
4-13/16 (123)
2-5/16 (58)
4-1/2 (114)
5-3/4 (146)
4-1/4 (108)
4 (102)
9-5/8 (245)
1-3/16 (30)
1-9/16 (40)
3-7/8 (99)
Drain port
Control box
Ceiling
Drain port
Be sure to leave maintenance space for future service at the designated position.
Unit: in (mm)
a (Ceiling openings size):
0918 09-18
27-9/16 (700)2 7 -9 / 1 6 ( 7 0 0 )
Bottom view
1
-
3
/
1
6
(
3
)
1
-
1
5
/
1
6
(
4
9
) Side view
•Grid type grille (UTG-CCGFG)
24-7/16 (620)2 4 -7 / 1 6 ( 6 2 0 )
Bottom view Side view
1
-
3
/
1
6
(
3
)
1
-
1
5
/
1
6
(
4
9
)
•3-way direction setting
Unit: in (mm)
NOTES:
•*: When installing the indoor unit, be careful about the maintenance space.
•To set “3-direction”, optional Air outlet shutter plate (UTR-YDZB) must be installed, and the “out-let-direction” need to be switched to “3-way” by remote controller.
•The ceiling height cannot be set in the 3-way outlet mode. Therefore, ceiling height setting
change by function setting 20 is prohibited. For details, refer to "Contents of function setting" on page 36.
C A A U
3. Wiring diagram
3-1. Models: AUU9RLF, AUU12RLF, and AUU18RLF
0918 09-18
4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)For heating capacity: Total Capacity (TC) and Input Power (IP)
4-1. Cooling capacity
¢Model: AUU9RLF
0918 09-18
C A
C A
4-2. Heating capacity
NOTE:Values mentioned in the table are calculated based on the maximum capacity.
¢Model: AUU9RLF
¢Model: AUU12RLF
0918 0918
¢Model: AUU18RLF
0918C A S S E T T A U U 09-18
5. Fan performance
5-1. Air velocity distributions
¢Model: AUU9RLF
•Air velocity distribution
0918 09-18
•Air velocity distribution
•Air temperature distribution
0918C A S S E T T E T Y A U U 09-18R L F
¢Model: AUU12RLF
•Air velocity distribution
0918C A S A U U 0918
•Air velocity distribution
•Air temperature distribution
0918C A S S E T T E T Y A U U 09-18R L F
¢Model: AUU18RLF
•Air velocity distribution
0918C A S A U U 0918
•Air velocity distribution
•
Air temperature distribution
0918C A S S E T T E T Y A U U 09-18R L F
5-2. Airflow
Conversion factor:
• 1 m 3/h = 0.2778 l/s = 0.5886 CFM • 3.6 m 3/h = 1 l/s • 1.699 m 3/h = 1 CFM
¢Model: AUU9RLF
Cooling
Heating
0918 0918
Heating
Heating
6. Operation noise (sound pressure)6-1. Noise level curve
¢Model: AUU9RLF
Cooling
O c t a v e b a n d s o u n d p r e s s u r e l e v e l , d B : (0 d B =0.00020 μb a r )
Octave band center frequency, Hz
Heating
O c t a v e b a n d s o u n d p r e s s u r e l e v e l , d B : (0 d B =0.00020 μb a r )
Octave band center frequency, Hz
010
20
30
40
50
60
70
80
¢Model: AUU12RLF
Cooling
O c t a v e b a n d s o u n d p r e s s u r e l e v e l , d B : (0 d B =0.00020 μb a r )
Octave band center frequency, Hz 01020
30
40
50
60
70
80
Heating
O c t a v e b a n d s o u n d p r e s s u r e l e v e l , d B : (0 d B =0.00020 μb a r )
Octave band center frequency, Hz
10
20
30
40
50
60
70
80
0918 09-18
¢Model: AUU18RLF
Cooling
O c t a v e b a n d s o u n d p r e s s u r e l e v e l , d B : (0 d B =0.00020 μb a r )
Octave band center frequency, Hz 01020
30
40
50
60
70
80
63
125
250
500
1,000
2,000
4,000
8,000
Heating
O c t a v e b a n d s o u n d p r e s s u r e l e v e l , d B : (0 d B =0.00020 μb a r )
Octave band center frequency, Hz
63
125
250
500
1,000
2,000
4,000
8,000
0918C A A U 0918
6-2. Sound level check point
Microphone
60 in (1.5 m)
0918C A S S A U U 0918
7. Safety devices
*PCB: Printed Circuit Board
0918C A S S E A U U 09-18
8. External input and output
8-1. External input
•“Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).•The wire connection should be separate from the power cable line.
¢Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
Unit operation is started at the following contents by adding the contact input of a commercial on/off switch to a connector on the external control PCB and turning it on.
0918C A S A U U 09-18
Circuit diagram example
•When function setting is "Operation/Stop" mode
Operation
Stop
On Off
Input signal
Indoor unit
•When function setting is "Forced stop" mode
Remote controller
Input signal
Indoor unit
Command
operation invalidity
On Off
Operation
Stop
Forced stop
Normal
Optional part
0918C A S S E T T A U U 09-18
8-2. External output
With using external output function, operating status of this product can be transmitted to the exter-nal device, and also, this product can be inter-connected with the external device.
¢Operation status output
Air conditioner operation status signal can be output.
Circuit diagram example
Indoor unit
Connected unit
•*: Make the distance from the PCB to the connected unit within 33 ft (10 m).•Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
On
Off
Operation
Stop Indoor unit
Output signal
Optional part
0918 0918
8-3. Fresh-air control output
Signal linked to the indoor unit fan on can be output.
NOTE:In cold-air prevention control operation, the signal becomes off.
Circuit diagram example
Indoor unit
•*: Make the distance from the PCB to the connected unit within 33 ft (10 m).•Relay spec: Rated DC 12 V, 50 mA or less.
On
Off
Operation
Stop Indoor unit
Output signal
Optional part
NOTE:This wire is included in both Fresh air intake kit.
0918 0918
9. Remote controller 9-1. Wired remote controller
¢Overview
0918 09-18
¢Specifications
Dimensions and other specifications on the wired remote controller are as follows.
Wiring specifications
0918C A A U 0918
10. Function settings
To adjust the functions of this product according to the installation environment, various types of function settings are available.
NOTE:Incorrect settings can cause a product malfunction.
10-1. Function settings on indoor unit
By using some components on the PC board, you can change the function settings.Related components on the PC board and the applicable settings
¢Component location
Components on the indoor unit main PC board used for the function settings are located as
shown in the following figure.
0918 09-18
¢DIP switch setting
•Remote controller address setting
When operating a number of indoor units by using a wired remote controller, DIP switch set-ting for assigning unit number to each indoor unit is required.DIP switches are normally set to make the unit number 00.
0918 0918
10-2. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting proce-dure and the content of each function setting, select appropriate functions for your installation envi-ronment.
¢Setting procedure by using wired remote controller
The function number and the associated setting value are displayed on the LCD of the remote con-troller. Follow the instructions written in the local setup procedure supplied with the remote controller,and select appropriate setting according to the installation environment.
Before turning on the power of the indoor unit, reconfirm following items:•Piping air tight test and vacuuming have been performed firmly.•There is no wiring mistake.1.Turn on the power.
2.
Press the SET TEMP. buttons () () and FAN button simultaneously for more than 5 sec-onds to enter the function setting mode.
3.
Press the SET BACK button to select the indoor unit number when you set the remote con-troller address setting.
4.
Press the set time buttons to select the function number.
5.
Press the SET TEMP. buttons () () to select the setting value. The display flashes during
setting value selection.
6.
Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a few sec-onds until the setting value stops flashing. If the setting value display changes or if “- -” is dis-played when the flashing stops, the setting value has not been set correctly. (An invalid setting value may have been selected for the indoor unit.)
0918 0918
7.
Repeat steps 3 to 6 to perform additional settings. Press the SET TEMP. buttons () () and FAN button simultaneously again for more than 5 seconds to cancel the function setting mode.In addition, the function setting mode will be automatically canceled after 1 minute if no opera-tion is performed.
8.
After completing the function setting, be sure to turn off the power and turn it on again.
CAUTION
After turning off the power, wait 30 seconds or more before turning on the power again. The func-tion setting will not become active unless the power is turned off then on again.
0918 0918
¢Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-ment.
NOTE:Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
1)Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
2)Ceiling height
Select the appropriate ceiling height according to the place of installation.
For the specific height for each setting value, refer to “Installation space” in Chapter 2. "Dimensions"on page 4.
In case of cassette type models:
The ceiling height values are for the 4-way outlet. Do not change this setting in the 3-way outlet mode.
9,000 Btu/h models cannot be installed in high ceilings. Do not change this setting.3)Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
0918 0918
4)Room temperature control for indoor unit sensor
NOTE:Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re-quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-er’s recommended value).
*When Function 95-01 (High insulation) is set, the Standard setting "00" will be the same as "No cor-rection 0.0 °F (0.0 °C)" (01).
5)Auto restart
Enables or disables automatic restart after a power interruption.
NOTE:Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or exter-nal device.6)Room temperature sensor switching (Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE:Remote controller sensor must be turned on by using the remote controller.
0918 0918
7)Remote controller custom code (Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
8)External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
9)Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired re-mote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is possi-ble by setting function setting 30 and 31 too.
0918C A 0918
10)Room temperature control for wired remote controller sensor
NOTE:Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re-quired. Select the appropriate control setting according to the installed environment.To change this setting, set Function 42 to "Both" (01).
Ensure that the thermo sensor icon is displayed on the remote controller screen.
11)Heat insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment.
"Standard insulation" (00) allows system to rapidly respond to the cooling or heating load changes."High insulation" (01) is when the heat insulation structure of the building is high and does not re-quire system to rapidly respond to cooling or heating load changes.When "High insulation" (01) is selected:
•Overheating (overcooling) is prevented at the start-up.
•All room-temperature control settings (Function 30, 31, 92, and 93) will reset to "No correction 0.0 °F (0.0 °C)".
NOTE:When changing Function 95, perform this setting before other room-temperature control
settings (Function 30, 31, 92, and 93). If Function 95 is not set first, room-temperature con-trol settings (Function 30, 31, 92, and 93) will be reset and you must re-do them again.
0918 0918
10-3. Function settings on wired remote controller
By using some components on the wired remote controller, you can change the function settings re-lated on the remote controller.
¢Component location
Components on the wired remote controller used for the function settings are located as shown in the following figure.
NOTE:Do not use DIP switch 2.
¢DIP switch setting
By switching each slide switch on the DIP switch 1, you can change the function settings for the remote controller.
*: Switches are fixed at OFF initially.
•SW2: Dual remote controller setting
Number of remote controller can be changed.
123123
123
Indoor unit
Primary unit
Secondary unit
Remote controllers
Remote controller cable
0918 0918
•SW4: °F/°C switch
Displayed unit for temperature can be switched between Fahrenheit (°F) and Celsius (°C).
•Set to ON to use the batteries for memory backup. If the batteries are not used, all of the set-
tings stored in the memory will be deleted if there is power failure.
0918C A S S A U U 0918
11. Accessories
0918C A S S E A U U 09-18
12. Optional parts 12-1. Controllers
NOTE:Available functions may differ by the remote controller. For details, refer to the operation
manual.
0918 09-18
12-2. Cassette grille
12-3. Others
0918C A S S E A U U 09-18
Part 2. OUTDOOR UNIT
SINGLE TYPE:
AOU9RLFC
AOU12RLFC
AOU18RLFC
1. Specifications
918O U T D O O R U N I T A O U 9-18R L F C。