fisher6200用-475HART协议调试方法HART协议是由Rosemount公司开发的一套通讯标准,协议采用标准的Bell202移频键控信号,以1200/2200波特率的正弦信号叠加在4-20mA直流信号上进行通讯。

它可使模拟信号和数字信号同时进行双向通讯而不互相干扰。

手操器和模拟信号发生器并联接入定位器的输入端。

DVC6200 调试步骤详解一、DVC6200 与475 通讯器阀门校检调试步骤二、定位器反馈调试使用说明三、DVC 自行程校检按钮激活四、DVC 整定设定五、DVC6200 与475 通讯器阀门引导设置校检调试步骤六、DVC6200 的模拟输出激活方法一、DVC6200 与475 通讯器阀门校检调试步骤1、进入界面,选择HART2、选择online 后enter(确认键)3、3、如有报警信号,选择YES 后enter(确认键)4、online 下拉菜单选择configure(组态)后按enter(确认键)5、选择calibration(校检)菜单后按enter(确认键)6、选择auto calibration7、警告菜单选择out of service8、选择CONTINUE 后enter(确认键)选择travel control9、阀门自动校验无须操作,只需等待直到下图界面10、自动校验完成 OK 键确认 11、选择OK12、修改成为 in service 状态,校检完成。

供气压力执行机构开关位二、定位器反馈调试使用说明1、在configure(组态)菜单选择manual setup2、选择模式保护将in service 改为OUT OF service3、选择改变仪表模式4、选择out of service。

Enter(确认键)后返回5、温馨提醒选择OK6、在manual setup 中选择outputs 用来设定定位器反馈7、选择output terminal 8、选择output terminal9、选择enable 后enter(确认键)10、一定要选择send 发送后完成反馈使用设置。

HART手操器调试fisher费希尔dvc6200阀门定位器

HART手操器调试fisher费希尔dvc6200阀门定位器

HART手操器调试fisher费希尔dvc6200阀门定位器HART调试FISHERdvc6200阀门定位器DVC6200与475通讯器阀门校检调试步骤进入界面,选择HART1、离线2、在线3 、多功能4、诊断选择online后enter找到两个非零状态码、忽略下一个50状态的发生1、供给压力低报警2、需要维护如有报警信号,选择YES后enter1、概述2、组态、配置3、维修工具online 下拉菜单选择configure(组态)后按enter1、引导设置2、手动设置3、报警设置4、校验选择calibration(校检)菜单后按enter1、自动校验2、手动校验3、校验类型4、校验时间5、校准器6、上次自动校准状态选择autocalibration警告菜单选择outofservice警告:校准会照成仪器的输出突然变化及其它损失1、继续2、退出选择CONTINUE 后enter选择travelcontrol阀门自动校验无须操作,只需等待直到下图界面自动校验完成OK键确认选择OK注意:要细调相应,使用性能调节器在仪器处于维修模式时,阀门可能会移动在服务/运行中止服务修改成为inservice状态,校检完成。

定位器反馈调试使用说明:1、引导设置2、手动设置3、报警设置4 、校准在configure(组态)菜单选择manualsetup1、模式与保护2、仪器3、行程、压力控制4、整定5、阀门与执行机构6、输出选择模式保护将inservice改为OUTOFservice1、仪器模式中止服务2、更换仪器3、写保护禁用4、更改保护帮助发送菜单选择改变仪表模式警告!在以下情况下输出将不跟踪输入模式以停用在服务中止服务选择o utofservice。

Enter后返回提醒:仪器必须返回到用于跟踪输入的输出服务温馨提醒OK手动设定1、模式与保护2、仪器3、行程、压力控制4、整定5、阀门与执行机构6、输出值保存菜单主页在manualsetup中选择outputs用来设定定位器反馈输出1、输出终端组态2、开关组态3、变送器输出4mA时=阀关4、HART变量分配选择outputterminal输出配置1、输出端激活/禁用2、功能发送器3、失败信号发射低/··选择outputterminalenable输出端选择启用禁用启用禁用选择enable后enter输出端配置1、输出启用2、功能变送器3、失败信号发射低/·发送主页一定要选择send发送后完成反馈使用设置。

fisher定位器的调试方法

fisher定位器的调试方法

f i s h e r定位器的调试方法IMB standardization office【IMB 5AB- IMBK 08- IMB 2C】请写出如何使用HART通讯器完成DVC6000系列定位器的自动校验(包括如何连接、如何设定等步骤)1)、连接:HART通讯器的红表棒接DVC6000系列定位器的4~20mA的“+”端,黑表棒接“-”端2)、自动校验设定:(1)打开HART的电源,然后按>>>键,进入1Instrumentmode选项选中o u t o f s e r v i c e,按O K确认。

(2)进入3Protection选项,选中NONE,按ENTER确认,根据HART通讯器的提示松开AUX“+”“-”端的短接线,按OK;再短接,按OK;最后再松开,按O K将保护出系。

(3)自动校验流程:Setup&Diag→Calibrate→AUTOCalibTravel→OK 如果是D V C6010系列,其自动校验流程是:S e t u p&D i a g→C a l i b r a t e→A U T O C a l i b T r a v e l→D e f a u l t→O K (4)校验完成恢复保护,定位器重新投入I n s e r v i c e fisherDVC6000系列气动执行器使用HART375调试方法FISHERDVC6000一Fisher气动执行机构Fisher气动调门上其配备的DVC6000系列数字式阀门控制器是可以通讯的、基于微处理器的电-气转换仪表,除了把电流信号转换成气动输出压力这一标准功能外,还可以通过275型HART通讯器很容易地访问对于过程操作至关重要地信息。

一、技术参数:输入信号:4~20mA直流,标准输出信号:为执行机构要求的气动信号,最大可达到气源压力的95%。

最少范围:(6psig)最大范围:(140psig)气源压力:推荐值:比执行机构要求的最大值高0..3bar(5psig)最大值:(150psig)或执行机构最大压力额定值,取两者中较低者二、275型HART通讯器由于Fisher气动执行机构的控制器是用275型的HART通讯器来校验的,所以应该了解和掌握HART通讯器的使用。

HART375连接FisherDVC6000定位器调试说明书

HART375连接FisherDVC6000定位器调试说明书

HART375连接FisherDVC6000定位器调试说明书进入离线模式HART Application→onlink→yes→①configure/setup→②Detailed setup→①Mode and Protection→①Insterument mode→OK→{ In service在线模式或者out of service离线模式}退出保护模式HART Application→onlink→yes→①configure/setup→②Detailed setup→①Mode and Protection→⑤Protection→{None无保护或者config&Calib保护模式}→OK →{提示open不要短接AUX接头,提示jumper时短接AUX接头}→OK查看当前定位器信号与反馈信息HART Application→onlink→yes→Device Variables用HART375发送指令HART Application→onlink→yes→Device diagonoise→stroke→step target→指令自动整定(直接整定)HART Application→onlink→yes→①configure/setup→③Calibrate→①Travel Calibration→①Auto tvl calib→OK自动整定(设置向导模式)HART Application→onlink→yes→①configure/setup→①Basic setup→①setup wizard→OK→Tru/Press select(行程/压力选择) 选择Travel control(行程控制)→Pressure units(压力单位) 选择PSI→Max supply press(最大供气压力) 选择(90PSI=0.62mpa)→Actuator manufacturer(执行机构制造商) 选择Fisher controls→Actuator model(执行机构型号) 选择(具体型号查看阀体铭牌,例如667)→Actuator size(执行就够尺寸) 选择(具体尺寸查看阀体铭牌,例如46)→setup wizard is ready to send config yo the Drc6000(安装向导准备发送配置到drc6000) 选择send(发送)→use factory default(使用工厂默认) 选择YES→To finish settiong up the value run Auto Travel Calib(完成阀门设置运行自动行程调校) 选择OK→Warning! Calibration will cause sudden changes in instrument output,continue?(警告!调校将造成仪表输出突然改变,是否继续?) 选择YES →select crossover adjust( 选择交叉点调整) 【①Manual手动②Last vale 上一次值③Default 默认值如果是初次校验行程,推荐选择Manual 调整】→定位器开始自动行程校验,校验解除后,将提示把定位器设置到in service在线模式。

FISHER定位器调试说明书

FISHER定位器调试说明书

FISHER(HART协议)定位器调试操作说明书一、1、定位器接线:(4—20mA信号、475手操器HART协议信号)接LOOP(+、‐)端子,如下图所示:2、定位器调试前必须查看磁条装配位置、是否碰到定位器,哈弗指针是否对准行程牌。

如下图所示:二、定位器修改位号和快速校验步骤:下图手操器界面说明:Power:电源Backlight:灯光Page up、Page down:上下翻页键Delete:下一级菜单键Back Space:返回键Fn+Backlight:手操器重启组合键1、2.。

9:为按钮键Tab:制表符1、按电源键打开475手操器,按Enter键点击HART图标后将进入下一步,如下图所示:2、按下键选择Online(使手操器处于在线模式)图标后按右键进入下一步,如下图所示:3、按下键选择Configure(配置)图标后按右键进入下一步,如下图所示:4、按下键选择Manual Setup(手动设置、相当于参数设置)图标后按右键进入下一步,如下图所示:5、按下键选择lnstrument(设备)图标后按右键进入下一步,如下图所示:(这一步是更改位号)6、按下键选择ldentification(识别)图标后按右键进入下一步,如下图所示:7、根据指示单位号进行修改,修改完成后按ENTER键,如下图所示:8、修改完HART Tag(位号)后,HART Tag(位号)图标前会出现*型标记,这时按SEND 键进行发送保存位号,如下图所示:9、修改完位号后,按左键返回到Manual Setup(手动设置、相当于参数设置)图标下,然后按下键到Calibration(校验)图标下后按右键进入下一步,如下图所示:(这一步开始快速整定定位器)10、选择Travel Calibration(行程校验)图标后按右键进入下一步,如下图所示:11、按下键选择Auto Calibration(自动校验)图标后按右键进入下一步,如下图所示:12、更改定位器模式(In Service(投用模式)、Out of Service(非投用模式)),按下键选择Out of Service(非投用模式),然后按ENTER键,进入下一步,如下图所示:定位器整定过程中,模式必须更改为Out of Service(非投用模式)手操器上显示的这句话意思:(警告:当模式更改为Out of Service(非投用模式)时,定位器的输出将不受输入信号控制)13、选择Continue(继续)图标后按ENTER键进入下一步,如下图所示:手操器上显示的这句话意思:(警告:设备的输出在校验过程中将发生改变)14、定位器开始整定(寻找阀门行程最高点、最低点、中间点、定位器开始模块运算和优化)如下图所示:15、自动校验完成后按OK键,然后把定位器模式改回In Service(投用模式),如下图所示:整定完成后必须把模式更改回In Service(投用模式),不然中控给定输入信号后,阀门将不动作。

fisher定位器的调试方法

fisher定位器的调试方法

请写出如何使用HART通讯器完成DVC6000系列定位器的自动校验(包括如何连接、如何设定等步骤)?1)、连接:HART通讯器的红表棒接DVC6000系列定位器的4~20mA的“+”端,黑表棒接“-”端2)、自动校验设定:(1)打开HART的电源,然后按>>> 键,进入1 Instrument mode选项选中out of service,按OK确认。

(2)进入3 Protection 选项,选中NONE,按ENTER确认,根据HART 通讯器的提示松开AUX“+”“-”端的短接线,按OK;再短接,按OK;最后再松开,按OK将保护出系。

(3)自动校验流程:Setup&Diag→Calibrate→AUTO Calib Travel→OK 如果是DVC6010系列,其自动校验流程是:Setup&Diag→Calibrate→AUTO Calib Travel→Default→OK(4)校验完成恢复保护,定位器重新投入In servicefisher DVC6000系列气动执行器使用HART375调试方法FISHER DVC6000一 Fisher气动执行机构Fisher气动调门上其配备的DVC6000系列数字式阀门控制器是可以通讯的、基于微处理器的电-气转换仪表,除了把电流信号转换成气动输出压力这一标准功能外,还可以通过275型HART通讯器很容易地访问对于过程操作至关重要地信息。

一、技术参数:输入信号:4~20mA直流,标准输出信号:为执行机构要求的气动信号,最大可达到气源压力的95%。

最少范围:0.4bar(6 psig)最大范围:9.5bar (140 psig)气源压力:推荐值:比执行机构要求的最大值高0..3bar(5 psig)最大值:10.3bar(150 psig)或执行机构最大压力额定值,取两者中较低者二、 275型HART通讯器由于Fisher气动执行机构的控制器是用275型的HART通讯器来校验的,所以应该了解和掌握HART通讯器的使用。

375手操器调FISHER阀方法

375手操器调FISHER阀方法

375手操器调FISHER阀方法1.自动运行手操器选择HART到显示OFFLINE,ONLINF,和UTILTY菜单。

2.选择ONLINE后出现0,1两个菜单,一般的1代表就地设备,0代表TRI-LOOP.3.先选择0进行就地设备的设定,按照如下菜单进行:0/1 setup diag/2 detailea setup/1 burst enable/enable 选择ENTER SEND然后返回到ONLINE。

目的是设置触发模式为时钟。

4.选择1按照如下菜单:1/ 2 Baisc setup/ch1开始进行通道1的设定。

5.改为QV,0%-100% YES 改完后选择SEND 然后OK 退到ONLINE页面。

目的是对反馈的通道进行设定。

6.就地调校阀门。

7.首先需要确认阀门的工作方式,是气开还是气关。

气开式其锁定螺帽在最下部,气关式锁定螺帽在最上边。

然后确认接线以及气源.8.运行375到OFFLINE,ONLINF,和UTILTY菜单。

9.选择ONLINE,按照如下路径设定:0/1setup diag/2detailed setup/1 mode/1instrument mode(仪表模式)/选择OK/out of service(非投运状态)/选择enter/ok返回到上级菜单选择4calibrate/2 auto calib travel/ok/enter开始调校阀门。

此时阀门会自动运行几次。

画面检索完成后选择 2 digital adjust(数字)/enter/自动运行。

此时一般选择DONE,若有误差可选择别的选项对阀门进行调整,目的是反馈杆和阀门的本体成垂直关系。

正常后选择ENTER/ok/ok/ok/inservic (在线必须选择到,否则无法远操) ENTER/OK/OK。

退出到初始页面。

设定结束。

袁江波2005/04/03。

Fisher浮筒液位计校验HART475菜单

Fisher浮筒液位计校验HART475菜单

Fisher浮筒液位计校验标定校验:有两种方法1:灌液法,2:挂重法。

(在实际工作中通常采用灌液法,不需要动浮筒)。

标定:标定包括浮筒无液时标记零点然后以实际提高与降低液位来标定控制器,可以有3种标定方法:如能够在外部测量两点额度液位或界面,那就进行两点液位标定程序,这是最精确的标定方法;若不能从外部测量液位或界面,但能改变液位,使浮筒完全离开液面与完全浸没,则进行零点/量程标定;若不能降低液位使浮筒完全离开液面或不能升高液位使浮筒完全浸没,则进行单点液位标定方法,此方法要求必须能够在一点上即浮筒部分浸没时从外部可以测量液位或界面高低以及预先标记好零点。

A.标记干耦合点干耦合点的值用于内部计算,并可事后读取作为参考耦合点。

液位测量时,将浮筒脱离液面;界位测量时,浸没在密度最小的液位中。

由Online Menu选Basic Setup,Sensor Calibrate,及Mark Dry Coupling。

按照HART通信器上提示,标记零点。

提示:根据从外部测量液位的能力,选择下列三种方法之一进行标定。

B.两点液位标定本方法是标定智能液位控制器与浮筒测量室最精确的方法。

它使用可从外部测量的两个液位。

进行两点液位标定前,先完成标记零点程序。

由Online Menu中选Basic Setup,Sensor Calibrate及TWO Liquid Lvi Cal,按照HART通讯器上的提示标定智能液位控制器与浮筒测量室。

设定控制回路为手动控制。

调整液位到靠近浮筒底部。

用当前PV(过程变量)单位输入外部测量的液位下限值。

调整液位到靠近浮筒顶部。

用当前PV(过程变量)单位输入外部测量的液位上限值。

标定完成继续进行“设定PV范围值”。

C.零点/量程标定若液位的改变可另浮筒完全离开液面与完全浸没,但实际液位不知道,则可用此方法标定智能液位控制器与测量室。

本方法不如两点液位标定那么完全精确,但笔单点液位标定更精确。

费希尔DVC6000系列定位器的调校

费希尔DVC6000系列定位器的调校

费希尔DVC6000系列定位器的调校用HART手操器进行调校:①从On line(在线)菜单里选择Setup&Diag(设置和诊断)——Basic setup(基本设置)——Manual setup(手动设置)——Instrument Manual(仪表模式)——Out of service(非工作状态)。

②Basic setup (基本设置)——Auto setup (自动设置)——Auto Calib Travel(自动校验行程)剩余的自动校验步骤是自动进行的。

自动校验完成后,HART会提示您将仪表设置到In Service(投用状态)。

③如果在完成基本设置和校验之后,阀门还是振荡或过调(不稳定),或响应不灵(响应缓慢),您可以Auto Setup (自动设置)菜单中Performance Tune (性能优化整定)或Stabilize/Optimize(稳定/优化)改善调试结果;其中有两种选择:Standard(标准)、Advanced(高级)。

在Standard(标准)中如果阀门工作不稳定,用Decrease Response(削弱响应)来使阀门工作稳定;如果阀门响应缓慢,用Increase Response(增加响应)来使阀门响应灵敏。

如果用Decrease Response或Increase Response后阀门超调还是很严重,需要选择Advanced(高级)项,除了Decrease Response(削弱响应) 和Increase Response(增加响应),还有Decrease Damping(降低阻尼) 选择允许阀门有更多过调的阻尼值和Increase Damping(增加阻尼) 选择减少阀门过调的阻尼值。

④对于FISHER DVC6000系列数字阀门定位器,典型的安装调试方式为:从On line(在线)菜单里选择Setup&Diag(设置和诊断)——Basic setup(基本设置) ——Auto setup (自动设置) ——Setup Wizard(设置诀窍),首先是选择所调试的执行机构制造商或执行机构型号,如果在Setup Wizard(设置诀窍)中没有列出,就选择Other(其它)来作为执行机构制造商或执行机构型号,被提示设定的参数如下:Actuator Type(执行机构类型)选项如下:Spring&Diaphragm(弹簧膜片式)、Piston Double-acting without spring(无弹簧双作用气缸式)、PistonSingle-acting with spring(带弹簧单作用气缸式)、Piston Double-acting with spring(带弹簧双作用气缸式)。

FISHER 调门调试步骤

FISHER  调门调试步骤

莱城电厂一期工程中的除氧器大小阀采用了带有FISHER-ROSEMOUT公司最新推出的FIELDVUE®DVC5000系列数字式阀门控制器的气动调阀。

运用此种数字式阀门控制器通过HART通讯器可以实现在集控室内对现场阀门进行操作、诊断、标定、组态。

HART 通讯协议是80年代中期由ROSEMONT公司开发的一种可寻址的远程传感器数据公路通讯协议(HIGHW AY ADDRESSABLE REMOTE TRANSDUCER)。

在BELL 202通讯标准基础上,采用移频键控制方式FSK(FREQUENCY SHIFT KEYING),使用 1.2KHZ和2.2KHZ载波在4-20mA模拟信号上完成数字信号传送。

一、简介除氧器大小阀的校验是通过275型HART通讯器完成的。

通讯器的外观如图一。

下面简单介绍一下其各部件的用途。

1.当显示屏上的条目未显示完时,屏幕上会出现↑或↓以提示,可?ü 颉 泄龆 ≡瘛?2.通过→键可以进入下一级子目录。

3.现在正在应用上标键。

4.心型标志不停跳动时,表示通讯器正在与就地设备通讯中。

5.当此符号出现时,表示电池需更换。

6.当此符号出现时,表示在子目录中,按←键可返回上一级目录。

< br>7.功能键F1~F4。

在操作过程中,在功能键的上方屏幕上会自动出现提示性字符,告诉你功能键此时的用途.常见的有:1) HELP 帮助了解正在显示的部分.2) SEND 将设定好的信息发送至就地设备.3) BACK 返回上一级目录.4) HOME 返回在线菜单.5) EXIT 从只读的信息中退出.6) ABORT 不保存信息或数据,退出.7) OK 进入下一目录.8) ENTER 将选定的信息送至就地设备。

9) DEL 删除以输入的信息。

10) ESC 不保存信息或数据,退回原目录.8.操作键。

1)I/O键:开关键。

2)↑键、↓键、→键、←键:方向键。

费希尔(FISHER)阀门定位器调试

费希尔(FISHER)阀门定位器调试

费希尔(FISHER)阀门定位器调试打开275/375手操器从主菜单(Main Menu)选择Hart应用(HART Application)从On line找到该定位器。

依次进入Setup&Diag ——Detailed Setup——Mode——Instument Mode (或者按手操器上快捷键直接进入)——警告!in service 模式被送到仪表当中时阀门也许会动(WARNING!Valve may move when in Service mode is sent to the instrument.)按OK 后进入仪表模式(Instrument Mode)选择Out of service 后按ENTER——提示“Instrument mode is already out of service!”后回到主界面依次进入 Setup&Diag——Basic Setup——Auto setup——Setup Wizard:1、选择你所使用的压力单位(Pressure units (psi))后ENTER ;2、输入最大供气压力(Max Supply Press (psi))后ENTER;3、选择执行机构的生产厂家(Actuator Manufcture)后ENTER 以上品牌没的话选OTHER ;4、如果执行机构单作用带弹簧选3 、双作用带弹簧选4 、双作用不带弹簧选2;5、选ROTARY 下一步根据阀门零信号时是开选2 关的话选1 下一步再选1 下一步选YES自动选择阀门转向及其增益大小;6、选择是否有加速器或者快速释放阀(Is a Volume Booster or Quick Release Present ? );7、提示执行机构的信息正被发送到仪表当中,请稍等“Actuator information is being sent to the instrument. Please wait…”;8、选择使用出厂默认设置Use Factory defaults for setup?(Yes is recommended for Initial Setup) Yes 后ENTER ;9、提示出厂默认设置正被发送到仪表当中,请稍等“Factory default are being sent to the instrument. Please wait…”;10、继续自动设置选择放大器调整“To continue Auto Setup.select Relay Adjust ”;11、你是否希望现在进行放大器调整?(Do you wish to run Relay Adjustment Calibration now ?) 假如是双作用选择Yes 单作用选择No后ENTER ;12、选择行程标定(To continue.select Auto Calib Travel.)按OK;13、你希望现在进行自动行程标定吗?(Do you wish to run Auto Travel Calib now ?Select YES if initial setup)选择Yes 后按ENTER;14、警告!标定将导致仪表的输出突然变化按 OK;15、选择交点的调整(Select Crossover Adjust)Manual/Last Value/Default 正常情况下选择 default 后 ENTER 假如默认的调整后精度比较差才会选择Manual手动;16、下面进入自动行程标定的过程,完成后仪表模式恢复到In service!。

FISHER调试步骤

FISHER调试步骤

1 基本设置将275型HART通讯器连接到数字式阀门控制器上。

在开始基本设置前,先要确认仪表安装正确,将4~20mA电流源连接到仪表上,将HART通讯器连接到仪表上,并打开HART通讯器。

1.1典型的安装方式Setup wizard(设置诀窍)设定必需的有关所选执行机构的制造商及型号的信息。

打开HART通讯器并按所示的菜单顺序启动setup wizard或在键盘上按快速键顺序号1-1-1-1进入。

按照HART通讯器显示的提示进行仪表设置,如果仪表所安装的执行机构没有在Setup wizard中列出,就选择OTHER作为执行机构制造商或执行机构型号。

在基本设置中,Setup wizard会问你是否要用工厂缺省值,如选择YES,那么基本设置会按常规设置参数。

在输入执行机构信息后,Setup wizard会提示调整气动放大器,气动放大器的校验完成后,在基本设置中下一步就是高校阀门行程。

按照HART通讯器显示的提示去进行阀位自动校验。

校验过程中使用阀门和执行机构的机械限位点作为0%和100%的校验点。

1.2自动校验阀门行程选择Auto Calib Travel(自动校验行程),然后按照HART通讯器显示的提示进行阀位自动校验。

如果反馈连接(Feedback Connection)是直通式-标准型(Sliding-Stem Standard),HART通讯器会提示选择交叉点调整:Manual(手动)、Last Value(上次值)、Default(缺省值)。

如是初次校验行程,推荐选择Manual调整。

按照HART通讯器的提示,改变电流源调整交叉点,直到反馈臂与阀杆成90度直角。

剩余的自动校验步骤是自动进行的。

自动行程校验完成后,HART通讯器会提示仪表设置到In Service(投作状态),并检查阀位是否能准确地响应电流信号。

如果仪表没法校验,查阅错误信息和可能的解决办法。

如果在完成基本设置和校验之后,阀门还是振荡和过调(不稳定)、或响应不灵(响应缓慢),可以从Auto Setup(自动设置)菜单中选择Performance Tuner(性能优化整定)或Stabilize/Optimize(稳定/优化)来改善调试结果。

Fisher Audio监视器HART通信器说明书

Fisher Audio监视器HART通信器说明书

Audio Monitor for HART ® Communications, for HART Communicating FIELDVUE ™ InstrumentsThe frequencies used for HART communications are in the audible range—you can hear them! The 1200 and 2200 Hz waveforms sound similar to the sounds you hear from a FAX machine's phone modem. This document outlines how to assemble a device to monitor these audible waveforms and a few suggestions on how to use it for troubleshooting.The audio monitor is shown in figure 1. The cable can also be used as an input to a cassette recorder if recordings of the HART messages are desired.Figure 1. Audio Monitor for HART CommunicationsMINI AMPLIFIER/SPEAKERINPUT JACK0.1 μF DISCCERAMIC CAPACITOR 470K OHM RESISTORWIRE TIEPC BOARDPHONE PLUGW6943HART Protocol—A Little BackgroundThe HART communication protocol has a “question‐answer” format; the HART master asks a question and the HART slave answers back. The slave will not communicate unless a master first asks a question. With the audio monitorpowered up and attached to a FIELDVUE instrument which is communicating with a 475/375 Field Communicator or a PC running ValveLink software or AMS Suite: Intelligent Device Manager, a series of “squawks” are heard. Often the pattern heard is “dot dot dash ...dot dot dash...dot dot dash...” that occur at intervals of about once a second with a slight pause in between. The first “dot” is the master asking the question and the remaining “dot dash” is the instrument's response.It is possible to have two HART masters communicating simultaneously with one HART slave. This is done by having one master be “primary” and the second master be “secondary”. The HART protocol provides time for each master to alternate making “question‐answer” exchanges with the slave. The pattern heard would then be “dot dot dash dot dot dash dot dot dash dot dot dash” with no pauses in between exchanges. Assuming the communications are within HART waveform specifications, no communication errors should normally occur.Some analog output circuits used to generate the 4 to 20 milliamp control signal are adversely affected by the HART communications waveforms. The usual result is that the impedance of the output circuit is substantially reducedApril 2017during communications. Good HART communications depend on the master device creating the waveform in a circuit where the load from the FIELDVUE instrument and the current source are roughly equal such that the signal is uniform throughout the loop. If the output circuit's impedance drops, the HART waveform is unevenly split (as in a voltage divider) and the signal received by the FIELDVUE instrument is reduced. The HART filter blocks the HART waveform from being detected by the analog output circuitry and prevents the source impedance from dropping.Another thing to understand is the Field Communicator has a broadcasting mode called the “shout” mode. If it doesn't receive an answer to its initial “question”, it will ask again with a larger signal strength. Demonstrate this by connecting the audio monitor to the Field Communicator without a FIELDVUE digital valve controller attached. Power on the Field Communicator and listen to the HART messages. The pattern will be something like this:“dot...dot...DOT...DOT...DOT” where the capitalization indicates the louder attempt. Troubleshooting Communications Problems with the AudioMonitorSeveral HART communication problems can be identified with use of the audio monitor, a little knowledge of the HART protocol, and a little experience by the user in hearing differences between normal HART communications and faulty ones.1. No response by slave device—Polling by a master device that is not answered by a slave device would sound like “dot...dot...dot...” and would continue for only a few times before the master device would display a message stating that no device was found. Corrective action would be to determine why slave is not communicating.2. Two masters of the same gender—If two masters set to the same “gender” (primary or secondary) were trying tocommunicate with the same slave device, both would try to share their “half” of the bandwidth. The basic pattern would still be “dot dot dash ... dot dot dash...” as if there were only one master but there might be some distortion or extra characters as the messages overlap. The pause in the middle would still be present. The master device might suffer communications errors or stop updating its readback values while in conflict. Corrective action would be to have only one primary and/or one secondary HART master communicating at a time.3. Current loop might need a FIELDVUE HART filter—To determine if a current loop needs a HART filter, configureValveLink software as “primary” master and connect both it, a Field Communicator, and the audio monitor to a FIELDVUE instrument powered by the current loop in question. Start both masters communicating to the FIELDVUE instrument (something that keeps asking for information, such as displaying the status of the instrument condition information). Listen to the waveforms on the audio monitor. If there are no “Communication Errors” displayed on the masters and the pattern sounds like “dot dot dash dot dot dash dot dot dash dot dot dash”, things are probably OK without a filter. If the pattern sounds like “dot dot dash DOT DOT DASH dot dot dash DOT DOT DASH” where one series is noticeably louder than the other or like “DOT DOT DASH...DOT DOT DASH...” where it sounds as if there is only one master, a HART filter should be tried and the test repeated. The louder sound or presence of only one master's messages where two should be present indicates that the Field Communicator is operating in the “shout” mode to overcome a poor HART circuit.4. Noise on the HART circuit—If noise is present on the HART circuit, depending on the frequency, it can sound likeclicks or static, tones which last for a period of time, or a wavering of the existing HART signal. Listen both while the HART messaging is occurring and while there is no HART communication (to sense the background noise). The main thing about listening to noise is that it is most likely random in nature but may be due to system layout, construction methods, or the unshielded operation of nearby equipment. For trouble shooting purposes, use the audio monitor before and after corrective action to reduce noise as a way to detect whether the change isbeneficial.23ConstructionFigure 2 is the circuit diagram for the audio monitor. Parts for constructing the audio monitor are listed under Parts List.Figure 2. HART Communications Audio Monitor Circuit DiagramMINI AMPLIFIER/SPEAKERRED BANANA PLUGBLACK BANANA PLUG0.1uFOUTPUT TO SPEAKERTO FIELDVUE DIGITAL VALVE CONTROLLERCut the circuit board material down to approximate dimensions listed in the parts list. Solder the capacitor, resistor and input and output wires together on the circuit board. Secure the input and output wires to the circuit board with the wire ties. Cover the whole assembly with electrician's tape.Allow about one foot of wire on the output side and attach the 1/8” phone plug (red wire to the center post, black wire to shield). On the input side allow about 3 feet of wire and attach the red banana plug to the red wire and the black banana plug to the black wire.The 1/8” phone plug is connected to the input jack of the amplifier/speaker box. The banana plugs are eitherconnected to the Field Communicator cable or are used with alligator clips or mini‐grabber‐style clips and connected to the “TALK +/-” terminals of the FIELDVUE instrument.Parts ListNoteRadio Shack rcomponent part numbers are specified as a suggested way to obtain the components locally. This is by no means an endorsement of Radio Shack, or its products, or a guarantee of their service,functionality, or availability. QuantityRadio Shack Description Required Part NumberMini Amplifier/Speaker 127710080.1uF ceramic disc capacitor12720135 QuantityRadio Shack Description Required Part Number470K ohm carbon resistor 12710009General‐purpose Component PC Board 0.5” x 1.75”276014918AWG two‐conductor stranded wire 4 feet approx 2780567Banana plugs1 pair 27407301/8” Phone Plug12740286Nylon wire ties, 4 inch long 2Electrician's tapeas neededApril 2017Related Fisher DocumentsDVC6200 and DVC6200 SISD DVC6200 Series Digital Valve Controller Quick Start Guide (D103556X012)D DVC6200 HW1 Digital Valve Controller Instruction Manual (D103409X012)D DVC6200 HW2 Digital Valve Controller Instruction Manual (D103605X012)D DVC6200 SIS Digital Valve Controller Instruction Manual (D103557X012)DVC6000 HW2D DVC6005 Series Remove Mount Digital Valve Controller Quick Start Guide (D103784X012)D DVC6200 HW2 Digital Valve Controller Instruction Manual (D103785X012)DVC2000D DVC2000 Digital Valve Controller Quick Start Guide (D103203X012)D DVC2000 Digital Valve Controller Instruction Manual (D103176X012)MiscellaneousD HF340 Filter Instruction Manual (D102796X012)D LC340 Line Conditioner instruction manual (D102797X012)DLC3010D DLC3010 Digital Level Controller Quick Start Guide (D103214X012)D DLC3010 Digital Level Controller Instruction Manual (D102748X012)DVC6000 and DVC6000 SIS (Supported)D DVC6000 Digital Valve Controllers Instruction Manual (D102794X012)D DVC6000 SIS Digital Valve Controllers for Safety Instrumented System (SIS) Solutions Instruction Manual (D103230X012)Documents are available from your Emerson sales office, Local Business Partner, or at .Emerson Automation Solutions Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 FranceDubai, United Arab Emirates Singapore 128461 SingaporeThe contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.Fisher, FIELDVUE, and ValveLink are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co.Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a registered trademark of FieldComm Group. All other marks are the property of their respective owners.Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.。

fisher定位器的调试方法

fisher定位器的调试方法

f i s h e r定位器的调试方法本页仅作为文档封面,使用时可以删除This document is for reference only-rar21year.March请写出如何使用HART通讯器完成DVC6000系列定位器的自动校验(包括如何连接、如何设定等步骤)1)、连接:HART通讯器的红表棒接DVC6000系列定位器的4~20mA的“+”端,黑表棒接“-”端2)、自动校验设定:(1)打开HART的电源,然后按>>> 键,进入1 Instrument mode选项选中out of service,按OK确认。

(2)进入3 Protection 选项,选中NONE,按ENTER确认,根据HART 通讯器的提示松开A UX“+”“-”端的短接线,按OK;再短接,按OK;最后再松开,按OK将保护出系。

(3)自动校验流程:Setup&Diag→Calibrate→AUTO Calib Travel→OK如果是DVC6010系列,其自动校验流程是:Setup&Diag→Calibrate→AUTO Calib Travel→Default→OK(4)校验完成恢复保护,定位器重新投入In servicefisher DVC6000系列气动执行器使用HART375调试方法FISHER DVC6000一 Fisher气动执行机构Fisher气动调门上其配备的DVC6000系列数字式阀门控制器是可以通讯的、基于微处理器的电-气转换仪表,除了把电流信号转换成气动输出压力这一标准功能外,还可以通过275型HART通讯器很容易地访问对于过程操作至关重要地信息。

一、技术参数:输入信号:4~20mA直流,标准输出信号:为执行机构要求的气动信号,最大可达到气源压力的95%。

最少范围:(6 psig)最大范围: (140 psig)气源压力:推荐值:比执行机构要求的最大值高0..3bar(5 psig)最大值:(150 psig)或执行机构最大压力额定值,取两者中较低者二、 275型HART通讯器由于Fisher气动执行机构的控制器是用275型的HART通讯器来校验的,所以应该了解和掌握HART通讯器的使用。

HART375连接FisherDVC6000定位器调试说明书

HART375连接FisherDVC6000定位器调试说明书

HART375连接FisherDVC6000定位器调试说明书HART375连接FisherDVC6000定位器调试说明书进入离线模式HARTApplication→onlink→yes→①configure/setup→②Detailed setup→①Mode and Protection→①Insterument mode→OK→{ In service在线模式或者out of service离线模式}退出保护模式HARTApplication→onlink→yes→①configure/setup→②Detailed setup→①Mode and Protection→⑤Protection→{None无保护或者config&Calib保护模式}→OK →{提示open不要短接AUX接头,提示jumper时短接AUX接头}→OK查看当前定位器信号与反馈信息HART Application→onlink→yes→Device Variables用HART375发送指令HART Application→onlink→yes→Device diagonoise→stroke→step target→指令自动整定(直接整定)HARTApplication→onlink→yes→①configure/setup→③Calibrate→①Tr avel Calibration→①Auto tvl calib→OK自动整定(设置向导模式)HARTApplication→onlink→yes→①configure/setup→①Basicset up→①setup wizard→OK→Tru/Press select(行程/压力选择) 选择Travel control(行程控制)→Pressure units(压力单位) 选择PSI→Max supply press(最大供气压力) 选择(90PSI=0.62mpa)→Actuator manufacturer(执行机构制造商) 选择Fisher controls→Actuator model(执行机构型号) 选择(具体型号查看阀体铭牌,例如667)→Actuator size(执行就够尺寸) 选择(具体尺寸查看阀体铭牌,例如46)→setup wizard is ready to send config yo the Drc6000(安装向导准备发送配置到drc6000) 选择send(发送)→use factory default(使用工厂默认) 选择YES→To finish settiong up the value run Auto Travel Calib(完成阀门设置运行自动行程调校) 选择OK→Warning! Calibration will cause sudden changes in instrument output,continue?(警告!调校将造成仪表输出突然改变,是否继续?) 选择YES →select crossover adjust( 选择交叉点调整) 【①Manual手动②Last vale 上一次值③Default 默认值如果是初次校验行程,推荐选择Manual 调整】→定位器开始自动行程校验,校验解除后,将提示把定位器设置到in service在线模式。

简论FISHER调节阀的校验

简论FISHER调节阀的校验

简论FISHER调节阀的校验独石化炼油厂仪表蒋少华摘要:简论FISHER调节阀的校验关键词:自动校验一设置1 用HART的热键选Protection为None,过程中按HART的提示把辅助端子AUX+和AUX-短接。

2 将Instrumenc mode设置为Out of service,Control mode设置为Analog(模拟),Feedback char(反馈特征)设置为slidip stem(滑杆)。

二自动校验1 进入Auto Calibrate Travel(自动校验)选择交点的调整方法Manual。

2 选择Analog,HART提示你调节电流源,直至反馈臂与执行机构的滑杆成90度角,按Ok。

3 自动校准程序的余下部分是自动进行的,当Calibrate菜单出现时,校验完成。

4 设置仪表于In Service状态,检验调节阀行程.三手动校验1 进入Calibrate状态,再进入Man Calib Travel状态。

2 选择Analog Calib Adiv(模拟信号)。

3 控制室给出阀位信号,直到调节阀动作,按Ok。

4 HART提醒你设定交点,由控制室给阀位信号,直到反馈臂与执行机构滑杆成90度角,按Ok 键。

5 根据提示给信号0%,此时阀行程应在0%位,按Ok。

6 根据提示给信号100%,此时阀行程应在100%位,按Ok。

7 根据提示给信号50%,此时阀行程应在50%位,按Ok。

8 根据提示反复调较几遍.9 当Clibrate菜单出现时,校验完成.10 设置仪表于In Service状态,检验调节阀行程.四优化如果阀门看起来还是不平稳或响应不灵,可以按热键选择Stablize/Dptimize(稳定),或从Auto Setup菜单中选Stablize/Dptimize(稳定)来改变阀门的运行壮况.通过选择Decreace Response(降低响应灵敏度)从F改到E;如选择Increase Response(增加响应灵敏度)从F改到G,使阀门更灵敏.五小结1 校验前一定要先设置正确,否则无法校验.2 找交点非常重要,交点不准确,阀行程也不准确.3 校验完成后,必须回到In service状态.4 在校验过程中出现其它情况,可根据HART提示进行处理.DVC5010智能式阀门定位器校准方法[262]1、自动校准行程。

FISHER气动执行机构调试参考

FISHER气动执行机构调试参考

FISHER气动执行机构调试1.分配气源箱过来的压缩空气(0.6-0.8MPa)通过减压阀后减压到:0.3-0.4 MPa,一支进入定位器,另一支进入气动保位阀2.输入电流信号(4-20MA)的改变,定位器中的电/气转换器的输出信号压力也随之改变,控制喷嘴的角度来影响进入气动阀的压缩空气流通面积的改变,从而来调节定位器中动力气源压力在(20-100KPa)线性的变化,通过阀杆的轴线位移来调节阀门动作。

(注:减压调节时通过定位器上的减压孔来排压)3.气动保位阀作用:当气源失气时,上图虚线支路的压力减少到丧失,从而导致气动保位阀关闭,从而锁住薄膜阀内压力使阀门保持在原位置。

(注:一般气动保位阀失气需要一段时间从而导致阀门位移发生一段小位移,在实际观察中发现的,不知道对不对?)4.反馈连杆随阀门上下运动从而改变反馈电流在4-20MA线性变化来表征阀杆位移5.气开阀门和气关阀门的原理相同•阀门调整1.调整前检查性校准通过控制室操作装置(操作器或CRT),先发出量程的0%,25%,50%,75%,100%输出信号,然后发出100%,75%,50%,25%,0%输出信号,依次记录每一校准点位置反馈值、执行机构和操作装置的实际位置定位器表面涂层应光洁、完好,无剥落、碰伤及划痕等缺陷;紧固件不应有松动和损伤等现象;铭牌及标志内容应正确;2手动进汽使阀门的开度大致为50%左右,使定位器的连接臂为水平位置;3调整定位器供气压力在规定范围内,在规定的输入信号气源压力时,调节定位器的零点和量程螺丝,使调节机构在全程范围内的基本误差不大于允许误差;3当气源压力偏离额定值±10kPa时,定位器的行程变化应不大于允许误差限的绝对值。

4位置变送器的校准对应于控制指令0%和100%,位置变送器输出电流应分别为4mA和20mA;5位置变送器的基本误差不大于执行机构允许误差。

6执行机构的基本误差应小于±1.5%的额定行程,其回程误差应小于1.5%的额定行程;7阀位输出的基本误差应小于±2%的额定行程,其回程误差应小于3%的额定行程。

相关主题
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

f i s h e r用H A R T协议调
试方法
Revised by Chen Zhen in 2021
HART协议是由Rosemount公司开发的一套通讯标准,协议采用标准的Bell202移频键控信号,以
1200/2200波特率的正弦信号叠加在4-20mA直流信号上进行通讯。

它可使模拟信号和数字信号同时进行双向通讯而不互相干扰。

手操器和模拟信号发生器并联接入定位器的输入端。

DVC6200 调试步骤详解
一、DVC6200 与475 通讯器阀门校检调试步骤
二、定位器反馈调试使用说明
三、DVC 自行程校检按钮激活
四、DVC 整定设定
五、DVC6200 与475 通讯器阀门引导设置校检调试步骤
六、DVC6200 的模拟输出激活方法
一、DVC6200 与475 通讯器阀门校检调试步骤
1、进入界面,选择HART
2、选择online 后enter (确认键)
3、3、如有报警信号,选择YES 后enter(确认键)
4、online 下拉菜单选择configure(组态)后按enter(确认键)
5、选择calibration(校检)菜单后按enter(确认键)
6、选择auto
calibration
7、警告菜单选择out of service
8、选择CONTINUE 后enter(确认键)选择travel control 9、阀门自动校验无须操作,只需等待直到下图界面
10、自动校验完成 OK 键确认 11、选择OK
12、修改成为 in service 状态,校检完成。

供气压力
执行机构
开关位
二、定位器反馈调试使用说明
1、在configure(组态)菜单选择manual setup
2、选择模式保护将in service 改为OUT OF service
3、选择改变仪表模式
4、选择out of service。

Enter(确认键)后返回
5、温馨提醒选择OK
6、在manual setup 中选择outputs 用来设定定位器反馈
7、选择output terminal 8、选择output terminal
9、选择enable 后 enter(确认键) 10、一定要选择send 发送后完成反馈使用设置。

记得将阀门改回in service 状态。

三、DVC 自行程校检按钮激活
激活前必须将阀门设置成out of service 状态,参考定位器反馈调试说明设置成为
out of service。

1、在manual setup 菜单下选择instrument
2、选择terminal box
3、选择calibration button 按右键
4、选择autocal 后enter(确认键)
5、选择send 发送完成接线盒自行程校检按钮设置。

四、DVC 整定设定
Dvc 整定设定主要用来调节定位器输出,阀门动作快慢,改善偏差。

同样是
在 manual setup 菜单下进行设定。

1、选择tuning
2、选择travel tuning
3、选择travel tuning set
4、通过上下键选择从C –M 阀门动作速度增快。

5、行程整定设置完成后务必点击send 发送。

(此步完成后
选择合适整定后确认阀门整定设置完成,记得所有设定后,阀门一定要设置成 In service 状态。


五、DVC6200 与475 通讯器阀门引导设置校检调试步骤
1、进入界面,选择HART
2、选择online 后enter(确认键)
3、如有报警信号,选择YES 后enter(确认键)
4、online 下拉菜单选择configure(组态)
后按enter(确认键)
5、选择guided setup(引导设置)菜单后按
6、选择device setup
enter(确认键)
7、警告菜单选择out of service 8、压力单位选择可任意,选择PSI
9、放大器类型,选择A OR C 用于单作用和 10、选择travel control
双作用放大器,B 为反作用定位器。

11、执行器制造厂商选择fishe 12、执行器的型号更具执行器名牌选择。

13、执行器尺寸型号选择根据执行器名牌 14、失电阀门开或者关,据条件选择
进行输入
15、选择YES 16、定位器自动捕行程传感器方向。

等待下图界面弹出
17、是否含有快排和气体流量放大器, 18、发送设备设置数据给仪表,按enter(确认键)没有选择NO。

否则YES
19、等待发送,发送完成后如下图界面 20、使用工厂默认设置选择YES
21、发送工厂默认数据中,等待完成后出 22、设备设置完成选OK,按Enter(确认键)
现下图界面
23、运行阀门行程校验,选择OK 后enter(确认键) 24、选择yes
25、阀门自动校验中
26、阀门校检完成ok 后按enter(确认键) 27、选择OK
28、校验完成后恢复到in service 状态。

阀门自动校验步骤完成
六、DVC6200的模拟输出激活方法
要激活DVC6200 的自动校验按钮,首先将475 手操器连接到定位器上,按附件中菜单树上的标示,找

然后进入1 Calibration Button中,选择Autocal 选项并确认,然后点击“send”键发送就行。

上午说的激活DVC6200 的4—20mA 输出的操作,最后也要点击“send”键发送才行。

要激活DVC6200 的4—20mA输出,首先将475 手操器连接到定位器上,按附件中菜单树上的标示,找到
然后进入1 Output Teminal Enable中,选择Enable 选项并确认就行,至于 2 Function和3 FailSignal 也可以按自己的需要进行组态。