wcs2702电流传感器使用说明带比较
ECS系列电流传感器说明书
ECS SeriesCurrent SensorAvailable Models:SensorType . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Toroidal through hole wiringMode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Over or undercurrent, switch selectable on the unit or factory fixedTrip Point Range . . . . . . . . . . . . . . . . . . . . . .0.5 - 50A in 3 adjustable ranges or fixed Tolerance Adjustable . . . . . . .Guaranteed rangeFixed . . . . . . . . . . . .0.5 - 25A: 0.5A or ±5% whichever is less; 26 - 50A: ±2.5%Maximum Allowable Current . . . . . . . . . . .Steady – 50A turns; Inrush – 300A turns for 10s Trip Point Hysteresis . . . . . ... . . .. . . . . . . .≅ ±5%Trip Point vs. Temperature . . . . . . . . . . . . .±5%Response Time . . . . . . . . . . . . . . . . . . . . . . . .≤ 75ms Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . .45/500 Hz Type of Detection . . . . . . . . . . . . . .. . . . . . . .Peak detection Trip DelayType . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .AnalogRange Adjustable . . . . . . . . . .0.150 - 7s; 0.5 - 50s (guaran teed ranges) Factory Fixed . . . . . . .0.08 - 50s (±20ms, whichever is greater)Delay vs. Temperature . . . . . . . . . . . . . . . . .±15%Sensing Delay on Startup . . . . . . . . . . . . . . .Factory fixed 0 - 6s: +40%, -0%InputVoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 , 120, or 230VAC; 12 or 24VDCTolerance 12VDC & 24VDC/AC . . . . . .-15 - 20% 120 & 230VAC . . . . . . . . . . . . .-20 - 10% AC Line Frequency . . . . . . . . . . . . . . . . . . . .50/60 Hz OutputType . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Electromechanical relay Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Isolated, SPDTRating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10A resistive @ 240VAC; 1/4 hp @ 125VAC; 1/2 hp @ 250VACLife . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Mechanical – 1 x 106 ; Electrical – 1 x 105ProtectionCircuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . .EncapsulatedIsolation Voltage . . . . . . . . . . . . . . . . . . . . . .≥ 2500V RMS input to output Insulation Resistance . . . . . . . . . . . . . . . . . . .≥ 100 MΩ MechanicalMounting . . . . . . . . . . . . . . . . . . . . . . . . . . . .Surface mount with two #6 (M3.5 x 0.6) screws Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .3.5 x 2.5 x 1.75 in. (88.9 x 63.5 x 44.5 mm)Termination . . . . . . . . . . . . . . . . . . . . . . . . . .0.25 in. (6.35 mm) male quick connect terminals (5)EnvironmentalOperating / Storage Temperature . . . . . . .-40° to 60°C / -40° to 85°C Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95% relative, non-condensing Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≅ 6.4 oz (181 g)Features:• Toroidal through hole wiring • 0.5 - 50A trip points• Adjustable or factory fixed trip delays • Isolated, 10A, SPDT output contacts • 5% trip point hysteresis (dead band)Approvals:Auxiliary Products:• Female quick connect: P/N: P1015-13 (AWG 10/12)P/N: P1015-64 (AWG 14/16) P/N: P1015-14 (AWG 18/22)SpecificationsOrder Table:XSeries─ECS - Selectable over or undercurrent sensing ─ECSH - Overcurrent sensing ─ECSL - Undercurrent sensingXInput─1 - 12VDC ─2 - 24VAC ─3 - 24VDC ─4 - 120VAC ─6 - 230VACXTrip Point─Fixed - Specify 2-50A in 1A increments─0 - 0.5-5A adjustable ─1 - 2-20A adjustable ─H - 5-50A adjustableXTrip Delay─F - Specify: 0.08-50s factory fixed─A - 0.150-7s adjustable ─B - 0.5-50s adjustableXSensing Delay on Start Up─Blank - 0s ─C - 1s ─D - 2s ─E - 3s ─F - 4s ─G - 5s ─H - 6sECS20BC ECS21BC ECS21BH ECS2HBC ECS30AC ECS40A ECS40AC ECS40BC ECS40BD ECS41A ECS41AC ECS41BC ECS41BD ECS41BH ECS41F.08ECS4HBC ECS4HBH ECS60AH ECS60BC ECS61BC ECS6HAHECSH21F.08C ECSH30AC ECSH3HF0.08D ECSH40AC ECSH40AD ECSH41AD ECSH41BC ECSH41F.08D ECSH4HF.08D ECSH61AD ECSL31A ECSL40AC ECSL40B ECSL40BH ECSL41A ECSL41AD ECSL45F7ECSL4HBH ECSL61AH ECSL6HAC The ECS Series of single-phase AC current sensors is a universal, overcurrent or undercurrent sensing control. Its built-in toroidal sensor eliminates the inconvenience of installing a stand-alone current transformer. Includes onboard adjustments for current sensing mode, trip point, and trip delay. Detects over or undercurrent events like; locked rotor, loss of load, an open heater or lamp load, or proves an operation is taking place or has ended.For more information see:Appendix B, page 166, Figure 20 for dimensional drawing.Appendix C, page 169, Figure 17 for connection diagram.OperationInput voltage must be supplied at all times for proper operation. When a fault is sensed throughout the trip delay, the output relay is energized. When the currentreturns to the normal run condition or zero, the output and the delay are reset. If a fault is sensed and then corrected before the trip delay is completed, the relay will not energize and the trip delay is reset to zero.AdjustmentSelect the desired function, over or under current sensing. Set the trip point and trip delay to approximate settings. Apply power to the ECS and the monitored load. Turn adjustment and watch the LED. LED will light; turn slightly in opposite direction until LED is off. Adjustment can be done while connected to the control circuitry if the trip delay is set at maximum. To increase sensitivity, multiple turns may be made through the ECS’s toroidal sensor. The trip point range is divided by the number of turns through the toroidal sensor to create a new range. When using an external CT, select a 2VA, 0-5A output CT rated for the current to be monitored. Select ECS adjustment range 0. Pass one secondary wire lead through the ECS toroid and connect the secondary leads together.If desired part number is not listed, please call us to see if it is technically possible to build .NC = Normally Closed Contact A = Sensing Delay On Start Up TD = Trip DelayR = ResetOC = Monitored Cur rentAFFB9L; HLMU; SCR9LLLC4; LLC6; PLSECS; ECSWAppendix B - Dimensional DrawingsFIGURE 15FIGURE 16FIGURE 18DCSAFIGURE 22inches (millimeters)(ECS has spade connectors andECSW has terminal board)FIGURE 15 - HLV Series FIGURE 16 - KVM SeriesV = VoltageL = LEDS = Undervoltage SetpointNO = Normally OpenNC = Normally ClosedC = Common, Transfer ContactL1N/L2FIGURE 17 - ECS SeriesV = VoltageI> = OvercurrentI< = UndercurrentFIGURE 18 - ECSW SeriesMC = Motor ContactorM = MotorF = FusesOL = OverloadRSW = Reset SwitchPositiveSwitchingNegativeSwitchingSinkingSourcingFIGURE 19 - TCS SeriesFIGURE 20 - TCSA SeriesZ = Zero AdjustS = Span AdjustW = Insulated Wire Carrying Monitored CurrentPLC = PLC Analog Input or Meter InputAppendix C - Connection DiagramsW = Insulated WireCarrying Monitored CurrentRelay contacts are isolated .FSW = Fan or Float ContactsCR = Control RelayCS = Current SensorMCC = Motor Contactor CoilI> = Adjustable OvercurrentI< = Adjustable UndercurrentW = Monitored Wire∆T - Adjustable Trip DelayL = LoadV = VoltagePS = Power SupplyPLC = PLC Digital Input Module。
SITRANS LG270 操作说明书
制导雷达SITRANS LG270 4 … 20 mA/HART - 四线制同轴测量探头-20 … +250 ℃操作说明书 • 09/20172PBD-51041557SITRANS LG270 - 操作说明书49920-ZH-1710303PBD-51041557SITRANS LG270 - 操作说明书49920-Z H -171030目录1关于本文献资料 ............................................................................................................................................51.1 功能 .............................................................................................................................................................................51.2 对象 .............................................................................................................................................................................51.3 使用的标记.. (52)为了您的安全 ...............................................................................................................................................62.1 获得授权的人员.........................................................................................................................................................62.2 合规使用 .....................................................................................................................................................................62.3 谨防错误使用.............................................................................................................................................................62.4 一般安全提示.............................................................................................................................................................62.5 欧盟一致性.................................................................................................................................................................62.6 NAMUR 推荐 ............................................................................................................................................................62.7 在美国和加拿大进行安装和运行. (73)产品说明 ......................................................................................................................................................83.1 结构 .............................................................................................................................................................................83.2 作业方式 .....................................................................................................................................................................93.3 包装、运输和仓储 ..................................................................................................................................................103.4 附件与备件 (114)安装 ...........................................................................................................................................................124.1 一般提示 ...................................................................................................................................................................124.2 安装提示 . (125)与供电装置相连接 ......................................................................................................................................165.1 准备接线 ...................................................................................................................................................................165.2 连接 ...........................................................................................................................................................................175.3 双腔式外壳的接线图 ..............................................................................................................................................185.4 附加电子部件...........................................................................................................................................................195.5 启动阶段 . (206)用显示和调整模块进行调试 ........................................................................................................................216.1 使用显示和调整模块 ..............................................................................................................................................216.2 操作系统 ...................................................................................................................................................................226.3 参数化 - 快速调试 ..................................................................................................................................................236.4 参数化 - 扩展了的操作功能..................................................................................................................................236.5 对设置的参数数据的存储 .. (387)用 PACTware 进行调试 .............................................................................................................................397.1 连接计算机...............................................................................................................................................................397.2 通过 PACTware 设置参数.....................................................................................................................................407.3 通过快速调试来投入使用 ......................................................................................................................................407.4 对设置的参数数据的存储 .. (418)用其它系统进行调试 ...................................................................................................................................428.1 DD 操作程序............................................................................................................................................................428.2 Field Communicator 375, 475 . (429)诊断与服务 .................................................................................................................................................439.1 维护 ...........................................................................................................................................................................439.2 诊断储存器...............................................................................................................................................................439.3 状态信息 ...................................................................................................................................................................439.4 排除故障 ...................................................................................................................................................................469.5 更换电子插件...........................................................................................................................................................489.6 软件升级 ...................................................................................................................................................................499.7 需要维修时的步骤 .. (49)10 拆卸 ...........................................................................................................................................................5010.1 拆卸步骤 . (50)4PBD-51041557SITRANS LG270 - 操作说明书49920-ZH-17103010.2 废物清除 ...................................................................................................................................................................5011 附件 .. (51)11.1 技术参数 ...................................................................................................................................................................5111.2 尺寸 ...........................................................................................................................................................................5911.3 商标 (61)用于防爆区域的安全提示请在将仪表用于防爆应用领域时遵守专门针对防爆的安全说明。
ECSW系列单相窗口电流传感器用户手册说明书
Operation With Zero Current Detection Enabled: If the current decreases to zero within the trip delay period, then zero current is viewed as an acceptable current level. The unit's output remains in its normal operating state. This allows the monitored load to cycle ON and OFF without nuisance tripping the ECSW. Zero current is defined as current flow of less than 250 milliampturns. Note: When zero current detect is selected, the latching operation of switch SW2 is canceled; the output will not latch after a fault trip.
ECSW2AL1 02.18.03
Window Current Sensor ECSW Series Current Sensor
Description The ECSW Series of single phase, AC window current sensors includes adjustable overcurrent and undercurrent trip points. Detects locked rotor, loss of load, an open heater or lamp load, a broken belt, a jam or loss of suction. LED's aid in trip point adjustment and provide fault indication. The built-in toroidal sensor eliminates the need for an external current transformer. The output can be electrically latched after a fault, or automatically reset. Remote resetting of a latched output by removing input voltage. The unit includes switch selectable zero current detection and normally de-energized or energized output operation. Time delays are included to improve operation and eliminate nuisance tripping.
CLS2容电水位传感器安装和操作指南说明书
Series CLS2 Capacitive Level SwitchSpecifications - Installation and Operating InstructionsBulletin L-26The CLS2 Capacitive Level Switch was designed to sense material level in a wide range of applications and environments using the dielectric properties of the sensed material. State of the art sensing technology in the CLS2, using impulse RF admittance measurement combined with an active guard, provides excellent level measurement and stability while being insensitive to material buildup. This technology also provides immunity to external RF sources like walkie-talkies and cell phones as well as minimal interference with radio communication or other electronic systems.The product features automatic calibration and 8 selectable sensitivity levels. Calibration may be initiated with either the internal switch or using the external calibration magnet allowing calibration without removing the cover. A selectable failsafe mode allows the relay to be active either normally open or normally closed. The unit also features an active guard mechanism that effectively eliminates the effects of material buildup on the probe. A selectable delay is provided to ensure false detection due to splashing or other tank disturbances will not cause nuisance triggering. A high brightness LED indicator is provided externally so that the level status can be easily seen even in bright sunlight. Three multicolored LEDs are provided internally for maintenance anddiagnostic use.OPERATING PRINCIPLECapacitance and DielectricsCapacitance is the property of two or more conductors to store a charge when there is a voltage difference between the conductors. In other words, capacitance relates the voltage between two conductors and the amount of charge that can be held on the conductors (i.e., the number of electrons). Capacitance is measured in Farads, but since a Farad of capacitance represents a very large charge storage capacity, most capacitance encountered is generally measured in micro Farads (µF, 10-6) or pico Farads (pF, 10-12). Capacitances encountered in level sensing applications are generally in the pico Farad range.The material between the conductors also affects the capacitance. Insulating materials do not allow free movement of electrons, however, in an electric field the molecules of these materials will tend to align with the field, thus storing energy. This is called the dielectric effect and these materials are often referred to as dielectrics. When placed between two conductors the energy storage capability of these dielectrics will allow more charge to be stored on the conductors for a given voltage difference thus increasing the capacitance between the conductors. The ratio of capacitance change caused by these dielectrics is referred to as the dielectric constant. Different materials have differing dielectric constants and will consequently change the capacitance between two conductors more or less depending on the value of this constant. This value ranges from 1.0 for a vacuum to over 100 for certain materials. The dielectric constant for air is very close to 1.0 and usually assumed to be exactly 1.0.Capacitive level sensors determine the level of material by changes in probe capacitance resulting from the movement of dielectric materials between the probe and the reference ground such as a tank wall. Since measuring very small capacitance changes (less than 1 pF) can be problematic in industrial environments, capacitance level sensing tends to be most effective for materials with a dielectric constant greater than about 1.2. Since the difference in capacitance is being measured, it is also possible to detect the level of two immiscible liquids that have different dielectricconstants such as oil and water.Level DetectionThe CLS2 uses the capacitance difference between the uncovered sensor and covered sensor to sense level such as the probe in air verses the probe in oil. This would allow, for instance, detection when the level in a tank is below a threshold and a pump must be started or when the level is above a threshold where the pump must be turned off.The CLS2 can be used in applications were the probe gets coated or covered with sticky, dusty, or clingy materials. The CLS2 has an active guard near the top that compensates for material that coats the probe preventing false alarms.When detecting level, two critical items must be established: a reference capacitance and the sensitivity. The reference capacitance is set through an automatic calibration process. The sensitivity is selected using an internal DIP switch which provides 8 sensitivity levels to accommodate differing material dielectric constants. See the calibration section for specific calibration instructions.The level detection is available to external systems through a double pole double throw (2-form C) relay. In any alarm or control system some consideration must be made for a power failure in one or more elements of the system. The CLS2 provides a fail-safe selection that allows the relay to operate in either a normally open or a normally closed state when the probe is uncovered.INSTALLATION UnpackingRemove the CLS2 from the shipping carton and inspect for damage. If damage is found, notify the carrier immediately.Mounting LocationThe CLS2 is designed to be mounted in a tank and is rated for industrial environments with few restrictions, however certain considerations must be made to ensure optimal sensing and extended operational life.• The process temperature and ambient temperature must be within the specified limits for the instrument.• Avoid locating the unit near or in high mechanical shock or vibration areas. • The probe must be located away from tank inlets or chutes where material may fall on the probe during filling or emptying.• Avoid mounting the probe close to tank structures as conductive product bridging between the guard and tank structure can cause false alarms. • In nonmetallic tanks a ground reference must generally be provided. If the probe is near the wall of the tank an adhesive backed metallic sheet may be applied to the outside of the tank wall nearest to the probe. Other metallic objects may be used also if they are in close proximity to the tank wall. If the probe is located further than 10 inches from the wall, an internal conductor must be providedparallel to and within 10 inches of the probe. These conductors must be connected to the case ground of the sensor. An external ground clamp is provided for this ifother grounding is not available.Note: Installation must be made in accordance with National Electric Code and local codes and regulations. When fishing wire through the conduit connection do not allow the wire to touch or press on components on the boards. Damage to the circuitry may result.The unit is to be wired to a switch or circuit breaker in close proximity to the unit. The switch or circuit breaker shall be marked as the disconnections device for the unit.The CLS2 has a 1/2˝ female NPT conduit connection. The conduit connection must be made such that condensation is not allowed to enter the housing.Grounding: The case of the CLS2 must be wired to a protective earth ground. This may be done by using a metal conduit or by wiring to one of the protective earth groundscrews in Figure 1 or Figure 2.The terminal block may be removed for easier connection. To remove, place a small screwdriver between the terminal block and the connector base and pry the terminal block forward. This will unlatch the block from the base allowing it to be removed. When installing the block, tip it forward on the connector base to snap it in the forward locking tab then rock the connector back onto the contacts until it snaps in place. Make sure the terminal block is securely in place.Strip 0.25˝ of insulation from the wires. Connect the power wires to terminals 1 and 2. If powered by DC, the polarity is not critical and either terminal may be selected for positive or negative. Connect control lines to the relay contact terminals (see Figure 1 for terminals). Torque terminals to 5 in-lb.Controls and Indicators (See Figure 2 and 3)Calibrate Switch —Pressing this switch twice initiates the automatic calibration process.Time Delay Potentiometer—This control selects a delay time from 0 to 60 seconds from the detection of a level change to the output.Dip Switch —This four section switch selects the sensitivity level and failsafe mode.Sensor LED —Yellow. This LED is illuminated immediately when the probe capacitance exceeds the setpoint threshold.Output LED —Red. This LED is illuminated when the relay is powered. It is affected by the failsafe setting and the delay.Power LED —Green. This LED is illuminated when the unit is powered and indicates that power is being supplied to the sensing circuitry.External LED—Red. The external LED indicator operates in conjunction with the internal Output LED.External Calibration Magnet —An external magnet is provided on the end of a chain to initiate calibration without having to open the case. Calibration is started by touching the magnet to the label target twice.Always install or service this device with the power off and whererequired install a disconnect lockout.For power line connections use NEC Class 1 wiring rated 75°C. Use 12 to 20 AWG copper only for line and load connections.Torque terminals to 5 in-lb. Strip the wires 0.25˝.Protective earthL1Figure 1: TerminalsExternal LED(YELLOW)Power LED (GREEN)(RED)Calibrate Time delay External calibration magnetProtective earthground screwFigure 2: Swiches and LED’sPrinted in U.S.A. 10/20FR# 443401-00 Rev. 9©Copyright 2020 Dwyer Instruments, Inc.Setup and Calibration1. Fail Safe Mode Selection: The relay will always be off when the power fails. In this case the contacts identified as normally open will be open. The fail safe switch selects whether the normally open contacts are open or closed when the probe is uncovered. There are two options for the failsafe condition that are selected by DIP switch S4 (see Figure 2). Selecting normally open (NO) will force the relay contacts to be open when the probe is uncovered and the output status LED to be off.Selecting normally closed (NC) will energize the relay when the probe is uncovered and light the output status LED.2. Sensitivity Selection: The sensitivity must be selected to match the dielectric constant of the material and its density. Eight sensitivity levels are provided by positioning DIP switches S1, S2, and S3 (see Figure 2). A high sensitivity setting is a low pF, and a low sensitivity setting would be a high pF. High sensitivity is used for materials such as plastic pellets, light powders, and dry grain. Mediumsensitivity is used for materials such as cement, petroleum products, and flour. Low sensitivity is used for products such as aqueous solutions. The switchpositions are summarized in Table 1. For best operation use the minimal sensitivity required for reliable operation.3. Calibration: Calibrate with the probe uncovered and the material at least 5 inches below the probe.To start the automatic calibration process press the calibrate switch twice (see Figure 2) or press the external magnet up to the housing at the marked location on the housing twice (see Figure 3). The external magnet is attached to the housing by a chain. The output status LEDs will begin to blink slowly, about once per second, when the calibration process has started. The automatic calibration will take approximately 10 to 15 seconds, and the output status LEDs will stop flashing at the end of the calibration process. If during the calibration process the tank level changes or a sensor failure has occurred, the calibration process may fail. The output status LEDs will begin to flash rapidly (about 4 times per second). Makesure the probe is uncovered and retry the calibration step.Table 1: Switch position for sensitivityFigure 3: Magnent location4. Time Delay Selection: The time delay is the programmed time between when the probe senses the material and when the relay changes state from the sensed material. A time delay of 3 seconds or greater is required to meet CE requirements. Choose a delay setting appropriate for the specific application. Adjust the delay potentiometer to the desired delay (see Figure 2). The delay can be set anywhere from 0 to 60 seconds and a scale is printed on the sensor board. For verification of delay programming the yellow sensor LED will come on when material is sensed and the red output LED will come on with the relay after the programmed time delay.5. Verify Operation: Make sure the probe is uncovered, material at least 5 inches below the probe, and that the yellow sensor LED is off. Fill the tank until thematerial is at the desired threshold level and verify that the sensor LED is illuminated. If the sensor LED turns on before the material reaches the probe, reduce the sensitivity as needed. If when the probe is covered the sensor LED is notilluminated, increase the sensitivity. Water or other conductive liquids will activate the sensor when they just contact the probe. Low density and dielectric constantmaterial may require more of the probe to be covered.Note: Default values as the product ships from the factory is a follows: S1:off, S2:off, S3:on, S4:on, and time delay off.MAINTENANCEOther than the controls mentioned in this manual there are no user maintenance adjustments or routine servicing required for this product. Very heavy buildup on the probe may ultimately reduce sensitivity. Moderate buildup is compensated for by the active guard.The Series CLS2 Capacitive Level Switch is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization (RGA) number before shipping.When the CLS2 with a Sanitary Process Connection is to be used in a sanitary or hygienic application, the unit must be cleaned and/or sanitized in accordance with appropriate guidelines prior to installation. The CLS2 with a Sanitary ProcessConnection is suitable for “Clean In Place” methods.Explanation of Symbols:。
美国Omron公司MOS FET电流传感器说明说明书
110RoHS compliant!Note:The actual product is marked differently from the image shown here.■Application Examples•Semiconductor inspection tools •Measurement devices •Broadband systems •Data loggers■List of Models■DimensionsNote:All units are in millimeters unless otherwise indicated.■Terminal Arrangement/Internal Connections (Top View)■Actual Mounting Pad Dimensions (Recommended Value, Top View)Contact form Terminals Load voltage (peak value)Model Minimum packaging unitNumber per tape SPST-NOSurface-mounting terminals40 VACG3VM-41LR3---G3VM-41LR3(TR)1,500G3VM-41LR3Note:The actual product is marked differentlyfrom the image shown here.Weight: 0.03 gNote: A tolerance of ±0.1 mm applies toall dimensions unless otherwise specified.G3VM-41LR3G3VM-41LR3G3VM-41LR3 G3VM-41LR3■Absolute Maximum Ratings (Ta = 25°C)■Electrical Characteristics (Ta = 25°C)■Recommended Operating ConditionsUse the G3VM under the following conditions so that the Relay will operate properly.■Engineering DataLoad Current vs. Ambient Temperature G3VM-41LR3■Safety PrecautionsRefer to “Common Precautions” for all G3VM models.Item Symbol Rating Unit Measurement ConditionsInput LED forward current I F50mARepetitive peak LED forward current I FP1A100 µs plus, 100 ppsLED forward current reduction rate∆ I F/°C−0.5mA/°C Ta ≥ 25°CLED reverse voltage V R5VConnection temperature T j125°COutput Output dielectric strength V OFF40VContinuous load current I O80mAON current reduction rate∆ I ON/°C−0.8mA/°C Ta ≥ 25°CConnection temperature T j125°CDielectric strength between input andoutput (See note 1.)V I-O1,500Vrms AC for 1 minAmbient operating temperature T a−20 to +85°C With no icing or condensation Storage temperature T stg−40 to +125°C With no icing or condensation Soldering temperature---260°C10s Note: 1.The dielectric strength be-tween the input and out-put was checked byapplying voltage betweenall pins as a group on theLED side and all pins as agroup on the light-receiv-ing side.Item Symbol Mini-mum Typical Maxi-mumUnit MeasurementconditionsInput LED forward voltage V F 1.0 1.15 1.3V I F = 10 mA Reverse current I R------10µA V R = 5 VCapacity between terminals C T---15---pF V = 0, f = 1 MHz Trigger LED forward current I FT------4mA I O = 80 mA Output Maximum resistance with output ON RON ---2535ΩI F = 5 mA,I O = 80 mA, t = 10 msCurrent leakage when the relay is open I LEAK------ 1.0nA V OFF = 30 V, Ta = 50°C Capacity between terminals C OFF---0.6 1.4pF V = 0, f = 100 MHz,t < 1 sCapacity between I/O terminals C I-O---0.8---pF f = 1 MHz, Vs = 0 V Insulation resistance between I/O terminals R I-O1,000------MΩV I-O = 500 VDC,RoH ≤ 60%Turn-ON time tON------0.5ms I F = 10 mA, R L = 200 Ω,V DD = 20 V (See note 2.)Turn-OFF time tOFF------0.5ms Note: 2.Turn-ON and Turn-OFFTimesItem Symbol Minimum Typical Maximum UnitOutput dielectric strength V DD------32VOperating LED forward current I F10---30mAContinuous load current I O------80mAOperating temperature T a25---60°C111Common Precautions!WARNINGBe sure to turn OFF the power when wiring the Relay, other-wise an electric shock may be received.!WARNINGDo not touch the charged terminals of the SSR, otherwise an electric shock may be received.!CautionDo not apply overvoltage or overcurrent to the I/O circuits of the SSR, otherwise the SSR may malfunction or burn.!CautionBe sure to wire and solder the Relay under the proper soldering conditions, otherwise the Relay in operation may generate ex-cessive heat and the Relay may burn.Typical Relay Driving Circuit ExamplesUse the following formula to obtain the LED current limiting resis-tance value to assure that the relay operates accurately.Use the following formula to obtain the LED forward voltage value to assure that the relay releases accurately.Protection from Surge Voltage on the Input TerminalsIf any reversed surge voltage is imposed on the input terminals, insert a diode in parallel to the input terminals as shown in the fol-lowing circuit diagram and do not impose a reversed voltage value of 3V or more.Surge Voltage Protection Circuit ExampleProtection from Spike Voltage on the Output TerminalsIf a spike voltage exceeding the absolute maximum rated value is generated between the output terminals, insert a C-R snubber orclamping diode in parallel to the load as shown in the following circuit diagram to limit the spike voltage.Spike Voltage Protection Circuit ExampleUnused Terminals (6-pin models only)Terminal 3 is connected to the internal circuit. Do not connect anything to terminal 3 externally.Pin Strength for Automatic Mountingn order to maintain the characteristics of the relay, the force imposed on any pin of the relay for automatic mounting must not exceed the following.In direction A: 1.96 NIn direction B: 1.96 NLoadTransistor10 to 100 kΩLoadR1 =V CC− V OL− V F (ON) 5 to 20 mAV F (OFF) = V CC− V OH < 0.8 V4Load ConnectionDo not short-circuit the input and output terminals while the relay is operating or the relay may malfunction.Solder MountingPerform solder mounting under the following recommended con-ditions to prevent the temperature of the Relays from rising.<Flow Soldering>Through-hole Mounting (Once Only)Note:We recommend that the suitability of solder mounting be verified under actual conditions.<Reflow Soldering>Surface Mounting DIP or SOP Packages (Twice Max.) Surface Mounting SSOP Packages (Twice Max.)Note: 1.We recommend that the suitability of solder mounting be verified under actual conditions.2.Tape cut SSOPs are packaged without humidity resis-tance. Use manual soldering to mount them.Manual Soldering (Once Only)Manually solder at 350°C for 3 s or less or at 260°C for 10 s or less.SSOP Handling Precautions<Humidity-resistant Packaging>Component packages can crack if surface-mounted components that have absorbed moisture are subjected to thermal stress when mounting. To prevent this, observe the following precau-tions.1.Unopened components can be stored in the packaging at 5to 30°C and a humidity of 90% max., but they should be used within 12 months.2.After the packaging has been opened, components can bestored at 5 to 30°C and a humidity of 60% max., but they should be mounted within 168 hours.3.If, after opening the packaging, the humidity indicator turnspink to the 30% mark or the expiration data is exceeded, bake the components while they are still on the taping reel, and use them within 72 hours. Do not bake the same com-ponents more than once.Baking conditions: 60±5°C, 64 to 72 hExpiration date: 12 months from the seal date(given on the label)4. f the same components are baked repeatedly, the tapedetachment strength will change, causing problems when mounting. When mounting using dehumidifying measures, always take countermeasures against component damage from static electricity.5.Do not throw or drop components. If the laminated packag-ing material is damaged, airtightness will be lost.6.Tape cut SSOPs are packaged without humidity resistance.Use manual soldering to mount them.AC ConnectionDC Single Connection DC Parallel Connection LoadLoadLoadLoadSolder type Preheating SolderingLead solderSnPb150°C60 to 120 s230 to 260°C10 s max.Lead-free solderSnAgCu150°C60 to 120 s245 to 260°C10 s max.Solder type Preheating SolderingLead solderSnPb140→160°C60 to 120 s210°C30 s max.Peak240°C max.Lead-free solderSnAgCu180→190°C60 to 120 s230°C30 to 50 sPeak260°C max.Solder type Preheating SolderingLead solderSnPb140→160°C60 to 120 s210°C30 s max.Peak240°C max.Lead-free solderSnAgCu150→180°C120 s max.230°C30 s max.Peak250°C max.5。
基于安时积分法的电池SOC估算
基于安时积分法的电池SOC估算徐尖峰;张颖;甄玉;曹久鹤【摘要】安时积分法是蓄电池荷电状态估算过程中常用的方法,但是,安时积分法不能估算初始荷电状态,难于准确测量库伦效率和电池可用容量变化的问题.基于此问题,文章结合传统的开路电压法和负载电压法,对安时积分法估算蓄电池SOC的不足进行补偿,解决了安时积分法的缺陷.能够实时估算电池的荷电状态,并对估算过程中的不足通过负载电压法进行修正.结果表明,这种算法能得到了比较精确的估算效果.【期刊名称】《汽车实用技术》【年(卷),期】2018(000)018【总页数】4页(P9-11,23)【关键词】安时积分法;SOC状态估算;电池的荷电状态【作者】徐尖峰;张颖;甄玉;曹久鹤【作者单位】燕山大学,河北秦皇岛 066000;燕山大学,河北秦皇岛 066000;燕山大学,河北秦皇岛 066000;燕山大学,河北秦皇岛 066000【正文语种】中文【中图分类】U469.72+2随着能源危机问题的出现,节能环保是未来汽车发展的主要方向,我国作为目前世界上最大的纯电动汽车生产国与消费市场,掌握电动汽车的核心技术刻不容缓。
电池管理系统作为电动汽车电池,电机,电控三大技术的重要组成部分,肩负着实时监控和管理电池状态的重要任务。
准确估算电池荷电状态(SOC),对电池能量高效管理和整车性能提升有着重要的作用[1]。
电池的SOCs受到开路电压,充放电电流,温度,自放电,充放电次数等因素的影响,使得对其估算具有较大的困难[2]。
本文主要研究了锂离子等效电路模型,并且开发出基于安时积分法,开路电压法和负载电压法相结合的锂离子电池SOC估算算法[3]。
并经过了放电实验的验证,算法可行,估算精确。
电池SOC是反应电池剩余电量的重要参数,人们通常将电池的SOC作为评估电池电量的重要标志。
电池的荷电状态表示电池剩余容量占电池总容量的比值[3]。
安时积分法是估算电池SOC值是通过充放电过程中放电电流对时间的积分得出的电量变化值的方法。
PF3W7-L-SMW82EN数字流量传感器操作手册说明书
Instruction ManualDigital Flow Switch – IO-Link compatible PF3W7##-L seriesThe intended use of the digital flow switch is to monitor and display flow information while connected to the IO-Link communication protocol.These safety instructions are intended to prevent hazardous situations and/or equipment damage. These instructions indicate the level of potential hazard with the labels of “Caution,” “Warning” or “Danger.”They are all important notes for safety and must be followed in addition to International Standards (ISO/IEC) *1), and other safety regulations. *1)ISO 4414: Pneumatic fluid power - General rules relating to systems. ISO 4413: Hydraulic fluid power - General rules relating to systems.IEC 60204-1: Safety of machinery - Electrical equipment of machines. (Part 1: General requirements)ISO 10218-1: Manipulating industrial robots -Safety. etc.• Refer to product catalogue, Operation Manual and Handling Precautions for SMC Products for additional information. • Keep this manual in a safe place for future reference.• This product is class A equipment intended for use in an industrial environment. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted or radiated disturbances.Caution Caution indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury.WarningWarning indicates a hazard with a medium level of riskwhich, if not avoided, could result in death or serious injury.DangerDanger indicates a hazard with a high level of risk which, ifnot avoided, will result in death or serious injury.Warning• Always ensure compliance with relevant safety laws and standards.• All work must be carried out in a safe manner by a qualified person in compliance with applicable national regulations.• Do not disassemble, modify (including changing the printed circuit board) or repair. An injury or failure can result.• Do not operate the product outside of the specifications. Fire, malfunction or damage to the product can result. • Do not use with flammable or highly permeable fluids. Fire, explosion, damage or corrosion can result. • If using the product in an interlocking circuit:Provide a double interlocking system, for example a mechanical system.• Check the product for correct operation.Otherwise malfunction can result, causing an accident.• Do not touch the terminals and connectors while the power is on. Otherwise electric shock, malfunction or product damage can result. • Do not touch the piping or its connected parts when the fluid is at high temperature.Ensure the piping has cooled sufficiently before touching to avoid burns.• Refer to the operation manual on the SMC website (URL: https:// ) for more safety instructions.2 Specifications2.1 IO-Link specificationsC o m m u n i c a t i o n s p e c . (D u r i n g I O -L i n k m o d e )IO-Link type Device IO-Link versionV1.1Communication speed COM2 (38.4 kbps) Min. cycle time 3.5 msProcess data length Input Data: 6 bytes, Output Data: 0 byte On request data communication Available Data storage function Available Event function Available Vendor ID 131 (0x0083)Device IDRefer to direct parameters• Refer to the operation manual on the SMC website (URL: https:// ) for more specification details.3.1 PF3W7##-L (with flow adjustment valve)ElementDescriptionConnector Connector for electrical connections.Lead wire with M8 connector Lead wire to supply power and transmit output signals.Piping port Port to connect the fluid inlet at IN and fluid outlet at OUT.Bracket Bracket for mounting the product. Temperature sensorSensor for detecting the fluid temperature. Flow adjustment valveRestricting valve to adjust the flow rate. Flow adjustment knob Knob for adjusting the flow rate.Lock ring Ring for locking the flow adjustment valve. DisplayDisplays the flow, settings and error codes (See below).Element DescriptionMain screen (2-colour display) Displays the flow, the status of setting mode and error code.Sub screen Displays the accumulated flow, set value, peak/bottom value, fluid temperature and line names.Output display (Indicator LED) Displays the output status of OUT1 and OUT2. When ON: Orange LED is ON. Unit display Displays the unit selected.UP button Selects a mode and the display shown at the sub screen, and increases the ON/OFF set values. SET button Press this button to select mode and to confirm a set value.DOWN button Selects a mode and the display shown at the sub screen, and decreases the ON/OFF set values. IO-Link status indicator lightLED is ON when OUT1 is used in IO-Link mode. (LED is OFF in SIO mode)• Refer to the operation manual on the SMC website (URL: https:// ) for more details of IO-Link indicator light operation and display.ORIGINAL INSTRUCTIONSRefer to Declaration of Conformity for relevant DirectivesModel PF3W704PF3W 720PF3W 740PF3W 711PF3W 721Applicable fluid Water and ethylene glycol solution with aviscosity of 3 mPa•s (3 cP) or lessDetection method Karman vortexRated flow range 0.5 to 4 L/min 2 to 16 L/min 5 to 40 L/min 10 to 100 L/min50 to 250 L/minDisplay flow range 0.35 to 5.50 L/min 1.7 to 22.0 L/min 3.5 to 55.0 L/min 7 to 140 L/min 20 to 350 L/min Switch point range 0.35 to 5.50 L/min 1.7 to 22.0 L/min3.5 to 55.0 L/min7 to 140 L/min 20 to 350 L/minMin. setting unit 0.01 L/min 0.1 L/min1 L/minConversion of accumulated pulse(Pulse width = 50 ms) 0.05 L/pulse0.1 L/pulse 0.5 L/pulse1 L/pulseFluid temperature 0 to 90 o C (No freezing andcondensation)0 to 70 oC (No freezin g and conden sation)Display unit L/min for real-time flow and L for accumulatedflowAccuracy ±3%F.S. Repeatability ±2%F.S.Temperature characteristics ±5%F.S. max. (25 o C reference)Operatingpressure range Refer to graph of operating pressure and proofpressureProof pressure Pressure loss Refer to graph of pressure lossAccumulated flow range 999,999,999.9 L9,999,999,999 LBy 0.1 LBy 1 LSwitch output Select from NPN or PNP open collector outputMax. load current 80 mAMax. applied voltage 30 V (during NPN output) Internal voltage drop 1.5 V or less (Load current 80 mA) Delay time 3.5 ms or lessVariable at 0 to 60 s / 0.01 stepH y s t e r e s i s Hystere sis mode Variable from 0Windo w compar ator mode Output protection Short circuit protectionO u t p u t m o d e FlowSelects one of output (hysteresis or window comparator mode), output for the accumulated flow, the accumulated pulse output, error outputand switch OFF. Temp. Selects the output for fluid temperature (hysteresis mode or window comparator mode).Model PF3W 704PF3W 720PF3W 740PF3W 711PF3W 721Display method 2-screen display (main screen, sub screen) Main screen: 4-digit, 7-segment, 2-colour;red/greenSub screen: 9-digit, 11-segment (5th digit is 7-segment only), White Display update frequency 5 times/sec.Indicator light Output 1 and 2: OrangeS u p p l y v o l t a g e Used as switch output device 12 to 24 VDC, including ripple (p-p) 10%Used as IO-Link device 18 to 30 VDC, including ripple (p-p) 10%Currentconsumption 50 mA max.Digital filter Select from 0.5 s/1.0 s/2.0 s/5.0 s/10.0 s/15.0s/20.0 s/30.0 sE n v i r o n m e n tEnclosure IP65Operating temp. range 0 to 50 oC (No freezing and condensation) Operating humidity range Operation, Storage: 35 to 85%R.H. (Nocondensation) Withstand voltage 1000 VAC, for 1 minute betweenterminals and housing Insulation resistance 50 M Ω min. (with 500 VDC) betweenterminals and housing Standards and regulations CE marked (EMC directive, RoHS directive)Material of fluidcontact parts PPS, SUS304, FKM, SCS13 PPS, SUS304FKM Grease free Piping port size 3/8 3/8, 1/2 1/2, 3/4 3/4、1 11/4、11/24.1 InstallationWarning•Do not install the product unless the safety instructions have been read and understood.•Use the product within the specified operating pressure andtemperature range.•Proof pressure could vary according to the fluid temperature. Check the characteristics data for operating pressure and proof pressure. 4.2 EnvironmentWarning•Do not use in an environment where corrosive gases, chemicals, salt water or steam are present.•Do not use in an explosive atmosphere.•Do not expose to direct sunlight. Use a suitable protective cover. •Do not install in a location subject to vibration or impact in excess of the product’s specifications.•Do not mount in a location exposed to radiant heat that would result in temperatures in excess of the product’s specifications.4.3 Mounting•Never mount the product in a location where it will be used as a support.•Mount the product so that the fluid flows in the direction indicated by the arrow on the side of the body.•Check the flow characteristics data for pressure loss and the straight inlet pipe length effect on accuracy, to determine inlet piping requirements.•Do not sharply reduce the piping size.•The monitor with integrated display can be rotated. It can be set at 90o intervals clock and anticlockwise, and also at 45o and 225o clockwise.Rotating the display with excessive force will damage the end stop.Bracket mounting (PF3W704 / 720 / 740)Mount the product (with bracket) using themounting screws supplied (M4 x 4 pcs).For models with flow adjustment valveattached, fix using 8 mounting screws.Bracket thickness is approx. 1.5 mm.Bracket mounting (PF3W711)Mount the product (with bracket) using themounting screws supplied(M5 x 4 pcs).Bracket thickness is approx. 2 mm.Direct mounting (PF3W704 / 720 / 740)Mount using self tapping screws(nominal size: 3.0 x 4 pcs).For models with flow adjustmentvalve attached, mount using 8 selftapping screws. Tightening torquemust be 0.5 to 0.7 Nm.Direct mounting (PF3W711)Mount using self tapping screws(nominal size: 4.0 x 4 pcs).Tightening torque must be 1.0 to 1.2Nm.Self tapping screws should not be re-used.Refer to the operation manual on the SMC website (URL: https://) for mounting hole details and outline dimensions. 4.4 PipingCaution•Before connecting piping make sure to clean up chips, cutting oil, dustetc.•When installing piping or fittings, ensure sealant material does notenter inside the port.•Ensure there is no leakage after piping.•When connecting piping to the product, a spanner should be used onthe metal piping attachment only.Using a spanner on other parts may damage the product.In particular, do not let the spanner come into contact with the M8connector. The connector can be easily damaged.Width across flats of attachment3/8 20.9 mm1/2 23.9 mm3/4 29.9 mm1 41 mmAfter hand tightening, apply a spanner of the correct size to thespanner flats on the product, and tighten it for 2 to 3 rotations, to thetightening torque shown in the table below.Nominal thread size Tightening torqueRc(NPT)3/8 15 to 20 NmRc(NPT)1/2 20 to 25 NmRc(NPT)3/4 28 to 30 NmRc(NPT)1 36 to 38 NmRc(NPT)1 1/4 40 to 42 NmRc(NPT)1 1/2 48 to 50 NmIf the tightening torque is exceeded, the product can be damaged. Ifthe correct tightening torque is not applied, the fittings may becomeloose.4.5 WiringCaution•Do not perform wiring while the power is on.•Confirm proper insulation of wiring.•Do not route wires and cables together with power or high voltagecables.Otherwise the product can malfunction due to interference of noise andsurge voltage from power and high voltage cables to the signal line.Route the wires (piping) of the product separately from power or highvoltage cables.•Keep wiring as short as possible to prevent interference fromelectromagnetic noise and surge voltage.Do not use a cable longer than 20 m.•Ensure that the FG terminal is connected to ground when using acommercially available switch-mode power supply.When used as switch output deviceNo. NameWirecolourFunction1 DC(+) Brown 12 to 24 VDC2N.C./OUT2WhiteNot connected /Switch output 2 (SIO)3 DC(-) Blue 0 V4 OUT1 Black Switch output 1When used as IO-Link deviceNo. NameWirecolourFunction1 L+ Brown 18 to 30 VDC2N.C./OUT2WhiteNot connected /Switch output 2 (SIO)3 L-Blue 0 V4 C/Q BlackIO-Link data /Switch output 1 (SIO)∗: Wire colours are for lead wire included with the PF3W7 series.5.1 Measurement modeThe mode in which the flow is detected and displayed, and the switchfunction is operating.This is the basic operating mode; other modes should be selected for set-point and other function setting changes.5.2 Switch operationWhen the flow exceeds the set value, the switch will be turned ON.When the flow falls below the set value by the amount of hysteresis ormore, the switch will be turned OFF.If the operation shown below is acceptable, keep this setting.5.3 3-step setting mode1. Press the SET button in measurement mode to display set values.(The item to be changed is displayed on the sub display)Set value on the right side of the sub screen flashes.2. Press the UP or DOWN button to change the set value.The UP button is to increase and the DOWN button is to decrease.•Press the UP button once to increase by one digit, or press and holdto continuously increase.•Press the DOWN button once to decrease by one digit, or press andhold to continuously decrease.3. Press the SET button to finish the setting.•For setting of hysteresis, perform the settings referring to [F 1] Settingof OUT1.•Note that the set value and hysteresis are limited by each other.•For more detailed settings, set each function in Function selectionmode.6.1 Function selection modeIn measurement mode, press the SET button for 3 to 5 seconds to display[F ] on the main screen.Select to display the function to be change [F ].Press and hold the SET button for 2 seconds or longer in functionselection mode to return to measurement mode.The function number is increased and decreased by the UP and DOWNbuttons. Display the required function number and press the SET button.6.2 Sub screen displayIn measurement mode, the sub screen display can be temporarilychanged by pressing the UP or DOWN buttons.After 30 seconds, it will automatically reset to the display selected in[F10].Example shown is for the 16 L/min type.6.3 Default settingsItem Default setting[F 0][Unit] Display units [ L] L/min, o C[N orP] Switch outputNPN/PNP[PnP] PNP output[F 1][oUt1] Output mode(OUT1)[HYS] Hysteresis mode[1ot] Switch operation(OUT1)[1_P] Normal output[P_1] Set value (OUT1) 50% of maximum rated flow[H_1] Hysteresis (OUT1) 5% of maximum rated flow[dtH1] Delay time at ON [0.00] 0.00 s[dtL1] Delay time at OFF [0.00] 0.00 s[CoL] Display colour(OUT1)[1SoG] ON: GreenOFF: Red (OUT1)[F 2]Notemp.sensor[oUt2] Output mode(OUT2)[HYS] Hysteresis mode[2ot] Switch operation(OUT2)[2_P] Normal output[P_2] Set value (OUT2) 50% of maximum rated flow[H_2] Hysteresis (OUT2) 5% of maximum rated flow[dtH2] Delay time at ON [0.00] 0.00 s[dtL2] Delay time at OFF [0.00] 0.00 s[CoL] Display colour(OUT2)[1SoG] ON: GreenOFF: Red (OUT2)[F 2]Withtemp.sensor[oUt2] Output mode(OUT2)[tHYS] TemperatureHysteresis[2ot] Switch operation(OUT2)[2_n] Reverse output[tn_2] Set value (OUT2) 50% of maximum rated temp.[ t H_2] Hysteresis (OUT2) 0% of maximum rated temp.[dtH2] Delay time at ON [0.00] 0.00 s[dtL2] Delay time at OFF [0.00] 0.00 s[CoL] Display colour(OUT2)[1SoG] ON: GreenOFF: Red (OUT2)ItemDefault setting[F 3][ FiL] Digital filter setting[ 1.0] 1.0 s[F10][ SUb] Sub screendisplay setting[ dEF] Standard (OUT1 setvalue displayed)∗: When a temperature sensor is not connected. [ dEF] Standard (fluidtemp. displayed)∗: When a temperature sensor is connected. [F30] [ SAvE] Accumulated flowvalue storage[ oFF] Not saved [F80] [ diSP] Display OFFmode[ on] Normal display [F81] [ Pin] Security codesetting[ oFF] OFF [F90] [ ALL] Setting of allfunctions[ oFF] OFF[F98] [ tESt] OUT1 output testmode[ n] Normal output [F99] [ ini] Reset to thedefault settings[ oFF]OFF• Snap shot function • Key-lock functionRefer to the operation manual on the SMC website (URL: https:// ) for setting these functions. 9.1 General MaintenanceCaution• Not following proper maintenance procedures could cause the product to malfunction and lead to equipment damage.• If handled improperly, compressed air can be dangerous.• Maintenance of pneumatic systems should be performed only by qualified personnel.• Before performing maintenance, turn off the power supply and be sure to cut off the supply pressure. Confirm that the air is released to atmosphere.• After installation and maintenance, apply operating pressure and power to the equipment and perform appropriate functional and leakage tests to make sure the equipment is installed correctly.• If any electrical connections are disturbed during maintenance, ensure they are reconnected correctly and safety checks are carried out as required to ensure continued compliance with applicable national regulations.• Do not make any modification to the product.• Do not disassemble the product, unless required by installation or maintenance instructions.• How to reset the product after a power cut or when the power has been unexpectedly removedThe settings of the product are retained from before the power cut or de-energizing.The output condition also recovers to that before the power cut or de-energizing, but may change depending on the operating environment. Therefore, check the safety of the whole system before operating the product.10.1 Error indicationIf the error cannot be reset after the above measures are taken, or errors other than the above are displayed, please contact SMC.Refer to the operation manual on the SMC website (URL: https:// ) for more detailed information about troubleshooting.11 How to OrderRefer to drawings/catalogue for ‘How to Order’.12 Outline Dimensions (mm)Refer to drawings/catalogue for outline dimensions.13 Limitations of Use8.1 Limited warranty and Disclaimer/Compliance Requirements Refer to Handling Precautions for SMC Products.14 ContactsRefer to Declaration of Conformity and URL: https:// for contacts.URL : https:// (Global) https:// (Europe) 'SMC Corporation, Akihabara UDX15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101 0021Specifications are subject to change without prior notice from the manufacturer. © 2019 SMC Corporation All Rights Reserved. Template DKP50047-F-085H。
银河电气电流传感器使用说明书
CSA200-G050T01电流传感器使用说明书V1.2感谢您选用银河电气电流传感器本手册为湖南银河电气有限公司产品电流传感器用户手册,本手册为用户提供安装调试、操作使用及日常维护的有关注意事项,在安装、使用前请仔细阅读。
本手册随产品一起提供,请妥善保管、以备查阅和维护使用。
声明我们非常认真的整理此手册,但我们对本手册的内容不保证完全正确。
因为我们的产品一直在持续的改良及更新,故我方保留随时修改本手册的内容而不另行通知的权利。
同时我们对不正确使用本手册所包含内容而导致的直接、间接、有意、无意的损坏及隐患概不负责。
安全操作知识◆产品使用前,请您务必仔细阅读用户手册。
◆需对产品进行搬动时,请您务必先断电并将与之相连的所有连接线缆等拔掉。
◆如果发现机壳、稳固件、电源线、连接线缆,或相连的设备有任何损坏,请您立即将装置与电源断开。
◆如果对设备的安全运行存在疑虑,应立即关闭设备和相应附件,并在最快时间内与本公司技术支持部门取得联系,沟通解决。
1.产品概述CSA200-G050T01是一种能在原边、副边完全隔离条件下测量直流、交流、脉冲以及各种不规则波形的电流传感器,它主要用于要求准确度高的计量检定和计量校准领域,以及要求高灵敏度、高稳定性和高可靠性的电能质量分析、功率分析仪、医疗、航空航天、导弹、舰艇等领域。
2.技术特点●极高的准确度●极好的线性度●极高的稳定性●极高的灵敏度●极高的分辨率●极低的温度漂移●极低的失调电流●极低的插入损耗●抗干扰能力强●响应速度快●极低的噪声●极小的角差●宽频带●模拟量输出3.应用场合●计量检定与校准●实验室电流测量●仪器仪表(如功率分析仪)●医疗设备(如核磁共振MRI)●电池组检测●电力控制●电源●舰船●新能源●轨道交通●航空航天●工业测量4.电气性能项目符号测试条件数值单位最小标称最大原边额定电流I PN-- -- ±20 -- Adc 测量范围I PM1分钟/小时-- -- ±24 Adc 工作电压V c全范围±12 -- ±15 Vdc 电流消耗I c I PM范围内±10 ±50 ±80 mA 电流变比K N输入:输出500:1 -- 额定输出电流I SN原边额定电流--±40--mAVc:±12,I PN:±20 Adc 0 -- 150 Ω测量电阻R MVc:±15,I PN:±20 Adc 0 -- 200 Ω5.精度-动态参数项目符号测试条件数值单位最小标称最大精度X e输入直流,@25±20℃-- -- 0.03 % 线性度εL-- -- -- 50 ppm 零点失调电流I o25±10℃-- -- 15 uA 零点失调电流I oT全工作温度范围内-- -- 30 uA 响应时间t r-- -- -- 1 us 电流跟随速度di/dt -- 200 -- -- A/us 频带宽度(- 3 dB) F -- 0 -- 100 kHz6.一般特性项目符号测试条件数值单位最小标称最大工作温度范围T A-- -40 -- +85 ℃存储温度范围T S-- -45 -- +90 ℃质量m 58±5 g 7.安全特性项目符号测试条件数值单位最小标称最大耐受电压原、副边之间副边与外壳之间V d50Hz,1min 5 kV瞬态隔离耐压原、副边之间V w50us 10 kV 相比漏电起痕指数CTI IEC-60112 275 V8.外形尺寸及端口定义8.1、外形尺寸(单位:mm)图1 外形图外形图说明:外形尺寸、安装定位尺寸公差按照GB/T1804-2000 C级标准执行。
Hubbell H-MOSS 双技术感应器系列产品说明书
AD1277I1AD1277I1N AD1277W1Key Features• All-Digital, Dual Technology Sensor• Adaptive Technology – No Manual Adjustment Required • Built-In Photocell with SuperSaver Mode•Two Relays for Two Level Switching or Dual Load Control (AD1277x2 and AD1277x2N )• Zero Arc Point Switchingeliminating the need for manual adjustment. This helps provide true maintenance free “Install and Forget” operation. The AD1277 Series also feature selectable operating modes - automatic ON/OFF or manual ON/automatic OFF , and a built-in photocell for automatic daylight harvesting.Hubbell's Adaptive Technology Occupancy Sensors Features and BenefitsFeaturesBenefitsAdaptive TechnologySensor automatically determines optimum setting. Self-adjusting timer and passive infrared sensitivity.No manual sensitivity and timer adjustments required – providing maintenance free “Install and Forget” operation.Automatic false-on, false-off correction.All-Digital, Dual Technology sensor Combines excellent ultrasonic minor motion detection with outstanding passive infrared long-range motion detection.Auto ON or Manual ON operating modes Provides Auto ON / Auto OFF or Manual ON / Automatic OFF operation.Two relays for two level switching or dual load controlControls two circuits independently (120V AC or 277V AC) — AD1277x2 and AD1277x2N .No minimum load requirement Allows for connection of loads from 0 to full load capacity.Hard lensImpact resistant IR lens.Built-in photocell with manual SuperSaver mode for daylight harvesting.Increases energy savings by preventing the lights from turning on when there is sufficient natural lightManual SuperSaver mode – in addition to above, turns lights off duringperiods of occupancy if ambient light levels increase sufficiently to illuminate the area.• Auto On or Manual On Operating Modes • Dual 120/277V AC Operation • Hard Lens• No Minimum Load Requirement •1000 Sq. Ft., 180° Area of CoverageH5241-ADSpecificationsTimer Timeout Automatic mode: 4-30 minutes, self adjusts based on occupancy; Fixed mode: 4, 8, 15 and 30 minutes; Test mode: 5 seconds Coverage1000 sq. ft., 180°Power Requirements 120/277V AC, 50/60HzElectrical Ratings 120V AC: 800W Incandescent, 1000W Fluorescent, 1/6 HP 277V AC: 1800W Fluorescent, 1/6 HP Load Requirements No minimum loadOperating Environment Indoor use only; Operating temperature: 32° – 104°F (0° – 40°C) 0% to 95% relative humidity, non-condensing Ultrasonic Output 40kHz outputPassive Infrared Dual element pyrometer and 12 element cylindrical hard lensPhotocell Adjustable ambient light override ranges from 10 foot-candles to 500 foot-candles Construction Housing – high impact, injection-molded plastic (UL-94-5V); Impact resistant lens; Color-coded leads are 6" longSize & Weight Size: 4.2" x 1.8" x 2.1", extends out .37"; Weight: 2.9 ozMounting Single gang NEMA style switch box (Decorator style wall plate not included)Certifications C-UL USColor White and Ivory (Light Almond, Gray and Black - special order, minimum requirements)Warranty5 yearsRange DiagramWiring Diagram for Single and Dual CircuitsAdaptive Technology, Dual Technology50/60Hz, 1000 sq. ft. coverage with photocell,800W IN., 1000W FL at 120V AC, 1800W FL at 277V ACCircuit ButtonCatalog NumbersSingle 1 Button for manual/auto control AD1277x 1Single Auto control with no button AD1277x 1N Dual 2 Buttons for manual/auto control AD1277x 2DualAuto control with no buttonAD1277x 2NSensors are available in two standard and three special order colors. To order, replace “x ” with I (Ivory) or W (White). Special order colors, LA (Light Almond), GY (Gray) or BK (Black), have minimum ordering requirements and minimum lead times. Please call customer service for further information. Wallplates are sold seperately.AD1227W1AD1227W1NAD1227W2AD1227W2NViolet Load 2BlueWired for Single CircuitAD1277I1AD1277I1N AD1277W1。
SMC 传感器用户手册说明书
Insertion of batteriesSlide the cover of the case open to insert the batteries.Use 2 x AA (LR6) alkaline dry cell batteries.When inserting the batteries, pay attention to the polarities and insert them inthe correct direction.After insertion, ensure the cover is closed correctly.AssemblyPeak hold: "P"Power button(2 pcs.)Mounting of the high voltage measuring handle (option)1. Insert the sensor into the handle in thedirection shown.2. Fix the cable to the handle as shown.3. The assembly is complete and the handle isnow ready for use.Procedure1. Insert the batteries.2. Connect the ground wire.Connect the ground wire to a point suitable for connection to an externalprotective earthing system.The position for attaching the ground wire to the Handheld meter is shownbelow.button.4. Move the sensor closer to the position 50 mm away from the measured target.Gradually bring the sensor closer to the measured target from a distance, andstop measurement immediately if the displayed value indicates overflow(HHH) or underflow (LLL).(The target has a high charged potential that is highly dangerous. Themeasured value does not change even if the distance is shortened.)5. Check the display.t∗Names of individual parts•DisplayFunction settingsis pressed with the powerturned on.All indications are displayed for 1 s.after the power supply is turned on.•Sensoris pressed for 3 s. or more with theoff the power supply.(For details, refer to Auto power-OFF function.)Turn off the power supply after using the product to keep the life of batteriesas long as possible.Auto power-OFFIf no button is pressed for 5 min. or more with thepower supply on, the power supply will turn offautomatically.is pressed for 6 s. or more with the power supply off, the(When this auto power-off extension is activated, indications on the displaywill keep flashing for 3 s.)is pressed with thewill be changed to instantaneousvalue, peak hold value, bottomhold value and instantaneousvalue, in that order.∗•Peak hold valueThe maximum charged potential and "P" are displayed.The maximum charged potential is continuously detected and updated fromwhen the peak hold is started. If the value over the held maximum chargedpotential is detected, the display will change.•Bottom hold valueThe minimum charged potential and "b" are displayed.The minimum charged potential is continuously detected and updated fromwhen the bottom hold is started. If the value under the held minimumcharged potential is detected, the display will change.Zero clearA displayed value can be adjusted to zero atmeasured charged potential in a range of ±5%F.S. ofdefault potential.(There will be a slight displacement, depending onthe deviation of the sensor itself and ambientare pressed for 6 s. or more with the power supply on,recovered automatically.Once the power supply is turned off, the offset value for zero clear is cleared.is pressed while the charged potentialbutton again to turn off the back light.Battery lowWhen the battery voltage becomes low "L" will bedisplayed. The display will vary depending on howmuch battery is left.The display resolution changes depending on the measured charged potentialvalue.value indicationHandheld ElectrostaticMeterOperation ManualIZH10Thank you for purchasing an SMC IZH10 Series Handheld Electrostatic Meter.Please read this manual carefully before operating the product and make sure youunderstand its capabilities and limitations.Please keep this manual handy for future reference.To obtain more detailed information about operating this product, pleaserefer to the SMC website (URL ) or contact SMCdirectly.These safety instructions are intended to prevent hazardous situations and/orequipment damage.These instructions indicate the level of potential hazard with the labels of"Caution", "Warning" or "Danger". They are all important notes for safety and mustbe followed in addition to International standards (ISO/IEC) and other safetyregulations.OperatorSafety Instructions TroubleshootingError IndicationThis function is to display error location and content when a problem or an error occurs.contact SMC.±1 to ±20 kVMinimum display unit:0.1 kV0 to±0.99 kVMinimum display unit:0.01 kV<Display example>Akihabara UDX 15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, JAP ANPhone: +81 3-5207-8249 Fax: +81 3-5298-5362URL Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.© 2011 SMC Corporation All Rights ReservedSpecificationsOutline with Dimensions (in mm)Refer to the product catalogue or SMC website (URL ) formore information about the product specifications and outline dimensions.Refer to the SMC website (URL ) for more informationabout troubleshooting.。
西门电气 RFS流量传感器使用说明书
RFS流量传感器安装使用说明书选型、安装及使用参考无机械运动部件,安装、使用维护方便低功耗温敏传感器,灵敏度高,精度高先进数字化处理技术,抗干扰能力强,结构紧凑,体积小,安装维护方便1 产品概述RFS流量传感器是一种流速传感监测装置,主要功能是检测流速的大小,当流速未达到设定的流速阀值时发出报警信号,并由控制系统进行报警或启动连锁保护装置关闭关键设备,及时制止在生产中的突发事故,因此该装置是保证生产安全、降低企业经济损失的不可缺少的重要装置,它具有不可估量的作用。
2 工作原理RFS流量传感器由两个温度传感器、电源、信号Array处理器及输出继电器或NPN/PNP晶体管输出组成。
该类型的温度传感器使用特殊的半导体制造。
这两个传感器物理特性非常接近,且以一定距离相互分离,相互间热影响可以忽略。
传感器配对跟踪介质的温度。
这些传感器的电压降与温度成正比,并准确的宽温度范围内工作。
将其中的一个传感器(Sensor1)进行加热,使其高于介质温度。
另一个传感器(Sensor2)与介质温度相同,我们基准传感器。
相等的恒流流经两个传感器产生电压差,其大小与Sensor1上被介质吸收带走的热量多少成反比。
由于介质的流速与带走热量成正比,故通过测量两个传感器的电压差,可知介质此时的流速,从而通过计算知道介质的流量。
3 产品应用1. Tank inlet flowdetection2. High level detection3. Low level detection4. Low flow pumpprotection5. Lube oil flowdetection6. Seal leak flowdetection7. Lube oil bearingflow detection8. Chemical injectionflow monitoring9. Level and interfacedetection10. Off-gas flowdetection4 技术参数4.1 LW塑料外壳继电器输出工作电压:DC 24V工作电流:≤60mA输出:继电器(2SPDT)开关电压:≤250V AC/60VDC开关电流:1-10A介质温度范围:- 50℃- +100℃工作环境温度范围:- 20℃- +80℃流量工作点范围(可调):0.03-10m/s(标准介质:水)开关特性典型3秒(1-12秒)开时间典型3秒(1-12秒)关时间典型3秒(1-12秒)温度变化响应时间 10秒温度梯度250℃/min耐压等级5MPaLED指示红灯亮电源正常;红灯灭电源不工作绿灯灭流速低于设定值;绿灯亮流速等于或大于设定值探头材料不锈钢或者铜由用户选择外壳材料ABSG1/2”螺纹扭矩 100Nm(也可根据用户制造)防护等级 IP65选择型号:RFS-D-010LW 输入电源DC24V 输出触点 250V AC 1A RFS-D-020LW 输入电源DC24V 输出触点 250V AC 5A RFS-D-100LW 输入电源DC24V 输出触点 250V AC 10A RFS-A-010LW 输入电源 AC220V 输出触点 250V AC 1A RFS-A-020LW 输入电源 AC220V 输出触点 250V AC 5A RFS-A-100LW 输入电源 AC220V 输出触点 250V AC 10A 随机附带专用电气插头1套4.2 LM金属外壳继电器输出工作电压:DC 24V工作电流:≤60mA输出:继电器(SPDT)开关电压:≤250V AC/60VDC开关电流:1-10A介质温度范围:- 50℃- +100℃工作环境温度范围:- 20℃- +80℃流量工作点范围(可调):0.03-10m/s(标准介质:水)开关特性典型3秒(1-12秒)开时间典型3秒(1-12秒)关时间典型3秒(1-12秒)温度变化响应时间 10秒温度梯度250℃/min耐压等级5MPaLED指示红灯亮电源正常;红灯灭电源不工作绿灯灭流速低于设定值;绿灯亮流速等于或大于设定值探头材料不锈钢或者铜由用户选择外壳材料铝合金G1/2”螺纹扭矩 100Nm(也可根据用户要求制造)防护等级 IP55选择型号:RFS-D-010LM 输入电源DC24V 输出触点 250V AC 1A RFS-D-020LM 输入电源DC24V 输出触点 250V AC 5A RFS-D-100LM 输入电源DC24V 输出触点 250V AC 10A RFS-A-010LM 输入电源 AC220V 输出触点 250V AC 1A RFS-A-020LM 输入电源 AC220V 输出触点 250V AC 5A RFS-A-100LM 输入电源 AC220V 输出触点 250V AC 10A 随机附带专用电气插头1套5 安装指南5.1 管道安装流量传感器与介质管道的连接形式为G1/2”螺纹(也可根据用户要求另行提供其他螺纹连接),可直接插入管道(管径D大于1”),也可通过三通连接管道(管径D小于或等于1”),更换快捷、方便、简单。
wcs27电流传感器使用说明带比较
电流检测和过流检测模块简易使用说明1本模块的功能:电流检测和过流检测集一体;本电流采样模块采用WCS2702,检测电流范围2-200A具体电流大小可以通过更换传感器来达到,接触型:WCS2705 -5A-5AWCS2720 -20A-5AWCS2750 -50-50A穿孔型WCS1500 WCS1600,WCS1700, WCS1800实物应用图:图.1该模块实际原理图图如下:图 21.1 检测电流与模拟信号输出的关系如下: 模拟信号输出:()2o a a Vcc v i K i =±*其中电流检测脚实际流过的电流,K 为线性度; 电流从正方向流进时:公式+2o a Vcc v i K =*;(1.1-1) 电流从反方向流进时:公式2o a Vcc v i K =*-;(1.1-2) 如果是交流信号时:2o a Vcc v i K =±*;(1.1-3) K 为线性度:m /;V A WCS2702 的线性度为K=1000客户可以根据自己的要求选择适合的型号。
1.2 数字信号输出该模块采用模拟信号与设定的基准电压进行比较,原理图如下:图31.2.1理论值:当逆时针旋转可调电阻R3时, V REF 电压值增加12o2_o ref o v V v V led <当时,输出低电平,红色灯亮;当顺时钟旋转可调电阻R3时, V REF 电压值减小.12o2_o ref o v V v V led >当时,输出高电平,红色灯不亮;为了让电路可靠稳定工作,本比较电路组成一个带有迟滞功能的比较电路:454*()HIGH LOW R Vr Vr V V R R +--=-+;(1.2-1) 其中41;R k =5430;R k = 1*(50.05)0.0115()431u V ∆=-=;(1.2-2) 可以通过设定4R ,5R 值,改变电路迟滞灵敏度。
我们在实际调试中,实测到u ∆实际值为0.04V ,本模块可以检测电流变化值如下: 2702m /WCS V A 的线性度为1000,可以检测40mA 以上变化电流;鉴于迟滞功能的存在,小的变化电流不能稳定检测出来,请客户根据自己的要求选择本模块。
感应式电流保护器C系列产品说明说明书
| C SERIES (CA, CM, CDA, CDM)2 TO 40 AMP COMMERCIAL THERMAL CIRCUIT BREAKERSPECIFICATIONSThe C series thermal breakers are designed to protect wiring and meet the harshest environmental requirements. The C series closed construction circuit breakers are weatherproof sealed for protection against moisture, dust, grease, fuel vapors and other harsh environments. The C series breakers are compact, lightweight and designed to interrupt short circuits or overloads, and combine trip-free protection with fast response time. Typical applications are protection of wire cable of accessory circuits, equipment and battery protection in construction and off-road equipment, marine, recreational vehicles (RV’s), mining, agricultural equipment and electric (hybrid) vehicles.FeaturesIntroduction• 30VDC or 120VAC, 2 to 40 Amps • Open and closed construction• Automatic and manual reset options • Ignition protected SAE J1171• Weatherproof SAE J553• UL Recognized E36869ORDERING OPTIONSDERATING CURVE: Leave blank for none I: Optional mounting nutsPerformance characteristics are based on room temperature (77°F, 25°C). Consult derating curve for ambient temperatures significantly higher or lower than standard room temperature.Example: At 77°F (25°C) the device is calibrated to hold at 100% of rated current (1) and trip at 135% of rated current (2). At 140°F (60°C), the same device will hold at approximately 78% of rated current (3), and trip at approximately 115% of rated current (4).Sensata Technologies, Inc. (“Sensata”) data sheets are solely intended to assist designers (“Buyers”) who are developing systems that incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible for using its independent analysis, evaluation and judgment in designing Buyer’s systems and products. Sensata data sheets have been created using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that specifically described in the published documentation for a particular data sheet. Sensata may make corrections, enhancements, improvements and other changes to its data sheets or components without notice.Buyers are authorized to use Sensata data sheets with the Sensata component(s) identified in each particular data sheet. HOWEVER, NO OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, ANDNO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATA SHEETS ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATA SHEETS OR USE OF THE DATA SHEETS, EXPRESS, IMPLIED OR STATUTORY, INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD TO SENSATA DATA SHEETS OR USE THEREOF.All products are sold subject to Sensata’s terms and conditions of sale supplied at SENSATA ASSUMES NO LIABILITY FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER AmericasFlame Enterprises Contact Name:Bob Correa, Director of Product Management Direct Phone: +1 (240) 236-9802E-mail:***************************************|WebTel: 1-800-854-2255 or 1-818-700-2905Fax: 1-818-407-5080Peerless Electronics Contact Name:Steve Gunther, National Sales Manager Direct Phone: +1 (516) 594-3509E-mail:***************************************************************|Web Tel: 1-800-285-2121Fax: 1-800-222-8096Europe, Middle East & Africa Flame Enterprises Contact Name:Bob Correa, Director of Product Management Direct Phone: +1 (240) 236-9802E-mail:***************************************|WebTel: 1-800-854-2255 or 1-818-700-2905Fax: 1-818-407-5080CONTACT USAUTHORIZED DISTRIBUTORSAUTHORIZED SALES REPRESENTATIVESCountry Representative Contact E-mailPhoneBrazil Sonnensys Technologies Maury Sampaio ***************************+55 12 99768 1100Austria Telemeter Robert Jall ******************49 906 70693-26Belgium JB Controls Jean Jacques Boher *********************33 (0)1 46 91 93 30Czech Republic TelemeterRobert Jall ******************49 906 70693-26Denmark Sensor Control Nordic Peter BJÖRKDAHL **********************46 (0)8 122 006 92Estonia Sensor Control Nordic Peter BJÖRKDAHL **********************46 (0)8 122 006 92Finland Sensor Control Nordic Peter BJÖRKDAHL **********************46 (0)8 122 006 92France JB Controls Jean Jacques Boher *********************33 (0)1 46 91 93 30Germany Telemeter Robert Jall ******************49 906 70693-26Greece PanSystem Stefano Vitone ****************************39 335 7169958Israel Admati Dori Shifman ***************972 (0)50 331 4700Italy PanSystemStefano Vitone ****************************39 335 7169958Latvia Sensor Control Nordic Peter BJÖRKDAHL **********************46 (0)8 122 006 92Lithuania Sensor Control Nordic Peter BJÖRKDAHL **********************46 (0)8 122 006 92Luxembourg JB Controls Jean Jacques Boher*********************33 (0)1 46 91 93 30Netherlands TBDNorway Sensor Control Nordic Peter BJÖRKDAHL **********************46 (0)8 122 006 92Poland Radiotechnika Tomasz Półtoraczyk ******************************.pl 48 7132 70 765Portugal PanSystem Stefano Vitone ****************************39 335 7169958Slovakia Telemeter Robert Jall ******************49 906 70693-26Spain PanSystemStefano Vitone ****************************39 335 7169958Sweden Sensor Control Nordic Peter BJÖRKDAHL **********************46 (0)8 122 006 92Switzerland JB Controls Jean Jacques Boher *********************33 (0)1 46 91 93 30Turkey Eltronik Ergn Kosem ******************90 312 440 7815UK Charcroft Julie Protheroe *****************************01591 612240Australia AeroDefense Trent Ralph *********************.au +61 7 5503 0552China Pomic Ltd.James Cai **********************+1 (360) 915-7806China (ACCBs only)Shanghai Jin Feng Electronics & Inst CoWang Min-Gang *******************.com +86-21-62712648India Hical Technologies VB Venkatesh **********************+91 98450-12341Indonesia Precision Technologies Aaron Lim ********************.sg +65 (62) 73 45 73 x125Japan Intertek Industries Masa Ikeda ****************************+1 (310) 309-9661Korea Aero Sensors Corp.Jonathan Jo **********************.kr +82 2 557 5355Malaysia Precision Technologies Aaron Lim ********************.sg +65 (62) 73 45 73 x125New Zealand AeroDefense Trent Ralph *********************.au +61 7 5503 0552Singapore Precision Technologies Aaron Lim ********************.sg +65 (62) 73 45 73 x125TaiwanSensata TechnologiesBob Jacques********************+1 (805) 716-0586。
科学物理实验室三角形电流传感器说明书
3B SCIENTIFIC® PHYSICSInstrucciones de manejo05/18 ALF1 Clavija guía2 Clavijas de contacto3 Placa de cátodo4 Espiral de calefacción5 Rejilla6 Ánodo7 Espiga enchufable de 4-mm para la conexión delánodoLos tubos catódicos incandescentes sonampollas de vidrio, al vacío y de paredes finas.Manipular con cuidado: ¡riesgo de implosión!∙No someter los tubos a ningún tipo deesfuerzos físicos.∙No someter a tracción el cables deconexión.∙El tubo se debe insertar únicamente en elsoporte para tubos S (1014525).Durante el funcionamiento de los tubos, puedenpresentarse tensiones peligrosas al contacto yaltas tensiones en el campo de conexión.∙Para las conexiones sólo deben emplearsecables de experimentación de seguridad.∙Solamente efectuar las conexiones de loscircuitos con los dispositivos dealimentación eléctrica desconectados.∙Los tubos solo se pueden montar odesmontar con los dispositivos dealimentación eléctrica desconectados.Las tensiones excesivamente altas y lascorrientes o temperaturas de cátodo erróneaspueden conducir a la destrucción de los tubos.∙Respetar losparámetros operacionalesindicados.Durante el funcionamiento, el cuello del tubo secalienta∙De ser necesario, permita que los tubos seenfríen antes de desmontarlos.El funcionamiento durante largo tiempo condescarga de gas muy fuerte puede conducir aun desgaste del material de los electrodos, elcual se deposita en el tubo de vidrio conducien-do a que éste se oscurezca.El cumplimiento con las directrices referentes ala conformidad electromagnética de la UE sepuede garantizar sólo con las fuentes dealimentación recomendadas.El tríodo de gas hace posible el registro de lacurva característica I A–U A de un tiratrón, laobservación de la descarga autónoma, de ladescarga no autónoma y la entrega de energíadiscontinua de los átomos de He durante elchoque inelástico con electrones libres.El tríodo de gas es un tubo lleno de helio con unfilamento calefactor (cátodo) de tungsteno puro,una placa metálica redonda (ánodo) y una rejillade alambre entre los dos electrodos, todo dentrode una ampolla de vidrio transpa-rente. Cátodo,ánodo y la rejilla de alambre están ordenados paralelamente entre sí. Esta forma de construcción planar corresponde al símbolo tradicional de un tríodo. Una placa metálica redonda fijada en una de las entradas de alimentación del filamento calefactor hace que se cree un campo eléctrico uniforme entre el cátodo y el ánodo.Llenado de gas: NeónTensión de caldeo: ≤ 7,5 V AC/CCTensión anódica: max. 400 V CC Corriente anódica: tipo 10 mA con U A = 300 V Tensión de rejilla: max. 30 VAmpolla de vidrio: aprox. 130 mm Ø Longitud total: aprox. 260 mmPara la realización de pruebas con el tríodo de gas se necesitarán los siguientes aparatos adicionales:1 Soporte de tubos S 1014525 1 Fuente de alimentación CC 500 V@115 V 1003307 ó@230 V 1003308 2 Multímetro analogico ESCOLA 100 10135274.1 Colocación del tubo en el portatubo∙Montar y desmontar el tubo solamente con los dispositivos de alimentación eléctrica desconectados.∙Introducir el tubo en la toma hembra del portatubos presionando ligeramente hasta que las clavijas de contacto estén colocadas correctamente en la toma, asegurándose de que la clavija-guía está en la posición correcta.4.2 Retirada del tubo del portatubos.∙Para retirar el tubo, presionar desde atrás la clavija-guía con el dedo índice de la mano derecha, hasta que las clavijas de contacto queden libres. A continuación, retirar el tubo.5.1 Descarga, comprobación de losportadores de carga positivos∙Se monta el circuito de acuerdo con la fig. 1. ∙Para la comprobación de los portadores de carga positivos (Iones de Ne+) se mide la corriente I G durante la descarga de gas, manteniendo la tensión de caldeo U F en máximo, teniendo en cuenta el signo.5.2 Descarga no autónoma∙Se monta el circuito de acuerdo con la fig. 2. ∙Se mide la curva característica I A–U A(= U G) para diferentes tensiones de caldeo U F(5 V …7,5 V).Con una tensión de aprox. 25 V la corriente de ánodo I A aumenta fuertemente en el tríodo de gas. Esta subida está compañada de una luminiscencia violeta. En el transporte de cargas participan más portadores de carga que en el tríodo de alto vacío (además de los electrones de incandescencia también los iones de Ne+).5.3 Descarga autónoma∙Se monta el circuito de acuerdo con la fig. 3. ∙Se aumenta lentamente la tensión de ánodo U A y se determina la tensión de encendido U Z para la descarga del gas .∙Se reduce nuevamente la tensión de ánodo U A hasta que se detenga la descarga autónoma. Se registra la tensión de apa-gado U L.5.4 Disposición de Frank-Hertz simplificada Experimento para la comprobación de la entrega de energía discontinua durante los choques inelásticos de los electrones con los átomos de Neón. Los electrones se mueven en un campo contrario activo entre la rejilla y el ánodo. Ellos logran llegar al ánodo sólo cuando tienen suficiente energía cinética y contribuyen a la corriente I A del ánodo a masa.∙Se monta el circuito de acuerdo con la fig. 4. ∙Con una tensión contraria U R de 6 V, se aumenta lentamente la tensión de aceleración U A desde 0 hasta 70 V y midien-do al mismo tiempo la corriente de ánodo I A. ∙Se representa gráficamente la corriente de ánodo I A en dependencia con la tensión de aceleración.Hasta una tensión de aceleración de aprox. 24 V la corriente aumenta para luego caer brúscamente. Con un aumento adicional de la tensión de aceleración, la corriente ánodo vuelve a aumentar y después de otros 20 V aprox. vuelve a caer.En el curso de la corriente de ánodo se deben observar 2 máximos bien definidos. En caso de que no sea así, se reduce la un poco la tensión de caldeo.Fig. 1 Comprobación de los portadores de carga positivosFig. 2 Descarga no autónomaFig.3 Descarga autónomaFig. 4 Disposición de Franck-Hertz3B Scientific GmbH ▪ Rudorffweg 8 ▪ 21031 Hamburgo ▪ Alemania ▪ 。
银河电气电流传感器使用说明书
CSA301-G062T01电流传感器使用说明书V1.02本手册为湖南银河电气有限公司产品电流传感器用户手册,本手册为用户提供安装调试、操作使用及日常维护的有关注意事项,在安装、使用前请仔细阅读。
本手册随产品一起提供,请妥善保管、以备查阅和维护使用。
声明我们非常认真的整理此手册,但我们对本手册的内容不保证完全正确。
因为我们的产品一直在持续的改良及更新,故我方保留随时修改本手册的内容而不另行通知的权利。
同时我们对不正确使用本手册所包含内容而导致的直接、间接、有意、无意的损坏及隐患概不负责。
安全操作知识◆产品使用前,请您务必仔细阅读用户手册。
◆需对产品进行搬动时,请您务必先断电并将与之相连的所有连接线缆等拔掉。
◆如果发现机壳、稳固件、电源线、连接线缆,或相连的设备有任何损坏,请您立即将装置与电源断开。
◆如果对设备的安全运行存在疑虑,应立即关闭设备和相应附件,并在最快时间内与本公司技术支持部门取得联系,沟通解决。
1. 产品概述CSA301-G062T01是一种能在原边、副边完全隔离条件下测量直流、交流、脉冲以及各种不规则波形的电流传感器,它主要用于要求准确度高的计量检定和计量校准领域,以及要求高灵敏度、高稳定性和高可靠性的电能质量分析、功率分析仪、医疗、航空航天、导弹、舰艇等领域。
2. 技术特点●极高的准确度●极好的线性度●极高的稳定性●极高的灵敏度●极高的分辨率●极低的温度漂移●极低的失调电流●极低的插入损耗●抗干扰能力强●响应速度快●极低的噪声●极小的角差●宽频带●模拟量输出3. 应用场合●计量检定与校准●实验室电流测量●仪器仪表(如功率分析仪)●医疗设备(如核磁共振MRI)●电池组检测●电力控制●电源●舰船●新能源●轨道交通●航空航天●工业测量4. 电气性能项目符号测试条件数值单位最小标称最大原边额定电流I PN-- -- ±300 -- Adc 测量范围I PM1分钟/小时-- -- ±360 Adc 工作电压V c I PM范围内±15 -- ±18 Vdc 电流消耗I c I PM范围内±10 ±160 ±200 mA 电流变比K N输入:输出2000:1 -- 额定输出电流I SN原边额定电流--±150--mA测量电阻R M V c:±15,I PN:±300 Adc 0 -- 20 ΩV c:±15,I PN:±360 Adc 0 -- 10 ΩV c:±18,I PN:±300 Adc 0 35 ΩV c:±18,I PN:±360 Adc 0 25 Ω5. 精度-动态参数项目符号测试条件数值单位最小标称最大精度X e输入直流,@25±20℃-- -- 0.1 % 线性度εL-- -- -- 0.01 % 零点失调电流I o25±10℃-- -- 30 uA 零点失调电流I oT全工作温度范围内-- -- 200 uA 响应时间t r-- -- -- 1 us 电流跟随速度di/dt -- 100 -- -- A/us 频带宽度(- 3 dB) F -- 0 -- 100 kHz6. 一般特性项目符号测试条件数值单位最小标称最大工作温度范围T A-- -10 -- +70 ℃存储温度范围T S-- -20 -- +85 ℃质量m 130±10 g7. 安全特性项目符号测试条件数值单位最小标称最大耐受电压原、副边之间副边与外壳之间V d50Hz,1min 5 kV瞬态隔离耐压原、副边之间V w50us 10 kV 相比漏电起痕指数CTI IEC-60112 275 V8. 外形尺寸及端口定义8.1、外形尺寸(单位:mm)图1 外形图外形图说明:外形尺寸、安装定位尺寸公差按照GB/T1804-2000 C级标准执行。
火闸传感器使用指南说明书
TM WST-600 AUDIO DETECTOR US Patent # 9,087,447Installation Manual & Users GuideSPECIFICATIONSFrequency: 433.92MHz Operating Temperature: 32°-120°F (0°-49°C) Battery: One3Vdc lithium CR123A (1550 mAh) Operating Humidity: 5-95% RH non condensingBattery life: 4 years Compatible with 433MHz DSC Security SystemsDetection distance: 6 in max Supervisory signal interval: 64 min(approx.)OPERA TIONThe FireFighter™ sensor is designed to listen to any smoke, carbon or combo detector. Once confirmed as an alarm, it will transmit a signal to the alarm control panel which if connected to a central monitoring station, will dispatch the fire department.ENROLLINGFollow the instructions provided by your control panel, or wireless receiver manual. The 6 digit serial number is printed on back of each device. To monitor smoke alarms, when prompted by the panel, enter the 6 digit serial number as printed on the device. Use either zone type 88 ( Standard 24hour fire) or type 87 (Delayed 24 hour fire). Remember to set the wireless bit (bit 8) for that zone attribute.To monitor a CO detector, take the printed serial number and replace the first digit with an 8. For example if the number printed is 436A48, you woulduse 836A48 as the serial number for the CO portion. Use zone type 81 (24 hour Carbon Monoxide).MOUNTING (see IMAGE: 2)Included with this device is a mounting bracket, hardware and double sided tape. To ensure proper operation ensure the side of the device with the small holes is directly facing the sounder holes on the smoke detector. Secure the mounting bracket to the wall or ceiling using thetwo mounting screws and double sided tape provided, then secure the audio detector to the mounting bracket using the small screw provided. The FireFighter™ must be mounting within 6 inches of the detector for optimal operation.***** It is possible that the sensor can hear other smoke detectors in close proximity so it is important to choose and to install the sensor close to a detector that is relatively isolated from other detector. It that is not possible, the sensor will still function it will however take longer to register and transmit to the panel. Smoke detectors to avoid are typically ones mounted in hallways outside of bedrooms that will also have additional smoke detectors.WARNING: Non-interconnected smoke detectors require an audio detector by each smoke detector sounder.This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72, (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269). Printed information describing proper installation, operation, testing, maintenance, evacuation planning, and repair service is to be provided with this equipment. Warning: Owner’s instruction notice: ’Not to b e removed by anyone except occupant’.TESTING (see IMAGE: 1)To test the RF transmission from the mounted position you can either generate a tamper by removing the cover or press the learn button located next to the tamper switch. Press and release ONCE to send a Smoke signal or press and HOLD for 2 seconds to send a Carbon signal.Within the first hour of power up the sensor is in a test mode. This mode is designed to work with the test button of the smoke detector so that only 1 or 2 temporal patterns is required to trigger the sensor. After the 1 hour has elapsed the sensor will require at least 3 rounds of either temporal 3 (smoke) or temporal 4 (CO) before it will send a transmission to the control panel. . Ensure the FireFighter™ cove r is on and that you wear hearing protection when doing the audio testing. Then simply press and hold the smoke detector test button.If 24 Hr, delay fire zone type is used the alarm must be active for 30 second before the panel will transmit to the Central Station.NOTE: This system must be checked by a qualified technician at least once every three (3) years. Please test the unit once per week to ensure proper functionality.Legacy Smoke DetectorsAll Smoke detector should be replaced after 10 year. If you encounter a smoke detector that does not support Temporal 3 pattern, that smoke should be replaced as per the manufacturer recommendation.If replacement is not an option the FireFighter can be program to detect non-temporal detectors.** In this mode, the sensor must not be located near any other audible device, like the security keypad or sounder. Those can be misconstrued as a valid smoke alarm. To enter this mode press and hold the tamper button while inserting the battery. Release the tamper switch and note the LEDONE flash: Only a Temporal 3 and 4 signal will trigger an alarm (Default)TWO flashes: Generic listening mode. (Will trigger after 30 seconds of continuous sound)You can verify the mode the device is in by simply removing the battery and replacing it. The LED will flash once or twice depending on the mode it is in. Repeat the steps above to change the mode as required.REPLACING THE BATTERYWhen the battery is low a signal will be sent to the control panel. To replace the battery:1. Remove the top cover to reveal the battery. This will send a tamper signal to the control panel.2. Replace with a Panasonic CR123A battery ensuring the + side of the battery faces as indicated on the device.3. Re-attach the cover, you should hear a click when the cover engages properly.WARNING: While the audio detector monitors its own battery, it does not monitor the battery in the smoke detectors. Batteries should be changed as per the original smoke detector manufacturer’s instructions. Always test the audio detector and smoke alarms after battery installation to confirm proper operationFCC COMPLIANCE STATEMENTThis equipment has been tested and found to comply with the limits for Class B digital devices, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:• Re-orient or relocate the receiving antenna• Increase the separation between the equipment and receiver• Connect the equipment to an outlet on a different circuit from the receiver• Consult the dealer or an experienced radio/TV contractor for help.WARNING: Changes or modifications not expressly approved by Ecolink Intelligent Technology Inc. could void the user’s authority to operate the equipment.This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.FCC ID: XQC-WST600 IC: 9863B-WST600WARRANTYEcolink Intelligent Technology Inc. warrants that for a period of 2 years from the date of purchase that this product is free from defects in material and workmanship. This warranty does not apply to damage caused by shipping or handling, or damage caused by accident, abuse, misuse, misapplication, ordinary wear, impropermaintenance, failure to follow instructions or as a result of any unauthorized modifications. If there is a defect in materials and workmanship under normal use within the warranty period Ecolink Intelligent Technology Inc. shall, at its option, repair or replace the defective equipment upon return of the equipment to the original point of purchase. The foregoing warranty shall apply only to the original buyer, and is and shall be in lieu of any and all other warranties, whether expressed or implied and of all other obligations or liabilities on the part of Ecolink Intelligent Technology Inc. neither assumes responsibility for, nor authorizes any otherperson purporting to act on its behalf to modify or to change this warranty, nor to assume for it any other warranty or liability concerning this product. The maximum liability for Ecolink Intelligent Technology Inc. under all circumstances for any warranty issue shall be limited to a replacement of the defective product. It is recommended that the customer check their equipment on a regular basis for proper operation.THE LIABILITY OF ECOLINK INTELLIGENT TECHNOLOGY INC. , OR ANY OF ITS PARENT OR SUBSIDIARY CORPORATIONS ARISING FROM THE SALE OF THIS SMOKEALARM DETECTOR OR UNDER THE TERMS OF THIS LIMITED WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACEMENT OF A SMOKE ALARM DETECTOR AND, IN NO CASE, SHALL ECOLINK INTELLIGENT TECHNOLOGY INC. , OR ANY OF ITS PARENT OR SUBSIDIARY CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSSES OR DAMAGES RESULTING FROM THE FAILURE OF THE SMOKE ALARM DETECTOR OR FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE COMPANY’S NEGLIGENCE OR FAULT.The Firefight er™ detector does not detect the presence of smoke, heat, or fire directly. It relies solely on the presence of an audio alar m signal generated by anexisting smoke or fire detector in proximity to the Firefighter™ detector to make such a determination. The Firefighter™ detector must be used with smoke detectors certified according to UL Standards, and in strict accordance with the installation and operation instructions provided with such detectors. It is the owner’sresponsibility to ensure that smoke or fire detectors used in conjunction with the Firefighter™ detector are maintained and tested on a regular basis in accordance with the manufacturer’s instructions. Ecolink Intelligent Technology Inc. expressly disclaims any responsibility for the failure o f the Firefighter™ detector to detect the presence of smoke or fire due to the failure of any smoke or fire detector used in conjunction with the Firefighter™ dete ctor to operate properly due to any condition, including improper installation, operation, maintenance or testing of such smoke or fire detector .LEARN BUTTON TAMPER SWITCH2055 Corte Del NogalCarlsbad, California 92011 1-855-632-6546PN WST-600 R1.00REV DATE: 12/07/16IMAGE 1: ENROLLING / TEST / TAMPER BUTTONIMAGE 2: INSTALLATION DISTANCE 6” MAX。
CT取电LoRa无线电流传感器产品说明书
【上海数采物联网科技有限公司】无线电流采集终端产品说明书版本:V 1.1修订记录目录1 产品概述 (3)2 服务理念 (4)3 产品特性 (4)3.1电流采集特性 (4)3.2温度采集特性(可选项) (4)3.3电气特性 (4)3.4互感器通信特性 (5)3.5网关通信特性 (5)3.6结构特性 (5)3.7电磁兼容 (5)3.8工作环境 (6)4 产品核心优势 (6)5 数据上报通信协议 (6)5.1协议解析说明 (6)5.2协议定制 (7)6 平台对接 (7)6.1默认平台 (7)6.2用户指定平台 (8)7 应用案例 (9)8 安装与维护 (9)8.1电池更换 (9)8.2指示灯 (9)9 设备尺寸 (10)1产品概述SC-LP-CTLoRa无线电流温度采集传感器终端配备低功耗高灵敏度的开口式互感器,通过电磁感应原理将一次侧大电流转换侧二次侧小电流,进而用于电流监测,能够很敏感的探测线路电流的大小,监测回路电流大于产品启动电流,传感器进入正常工作模式,采集温度、电流及其他相关数据,通过无线通讯上传至采集装置。
若线路处于空载或负载电流小于启动电流,则传感器使用内部电池供电保持工作状态。
传感器终端支持采用GPRS/4G/NB-IOT/LoRa/WiFi通信方式(外接电源默认采用GPRS 通信方式,电池供电默认采用NB-IOT/LoRa通信方式),克服现场特殊环境导致的无线通信遮挡,大大简化现场部署时间和降低施工费用。
测量电流范围宽,采用优质磁芯材料,开合式结构,易于安装,用于交流电机,照明设备,空气压缩机,采暖通风与空调装置,建筑物的自控制系统,工业中城网,农网改造项目等场景的电流监测采集。
2服务理念我司郑重承诺:您购买的不仅仅是产品,还有细致、周到的技术支持服务( =^_^= ) 本产品,现场只需普通工人接电安装即可! 无需调试!我们免费提供远程指导,远程配置调试服务,将数据发送至用户指定的云平台。
WD-C互感器校验仪说明书
WD-C互感器校验仪武汉武高电测电气有限公司一、互感器检验仪简介1.11电流互感器电流互感器::电流互感器电流互感器和变压器很相像,变压器接在线路上,主要用来改变线路的电压,而电流互感器接在线路上,主要用来改变线路的电流,所以电流互感器从前也叫做变流器。
后来,一般把直流电变成交流电的仪器设备叫做变流器,把改变线路上电流大小的电器,根据它通过互感的工作原理,叫做电流互感器。
线路上为什么需要变电流呢?这是因为根据发电和用电的不同情况,线路上的电流大小不一,而且相差悬殊,有的只有几安,有的却大至几万安。
要直接测量这些大大小小的电流,就需要根据线路电流的大小,制作相应为几安直到几万安不同的许多电流表和其他电气仪表。
这样就会给仪表制造带来极大的困难。
此外,有的线路是高压的,例如22万伏或1万伏等高压输电供电线路,要直接用电气仪表测量高压线路上的电流,那是极其危险的,也是绝对不允许的。
如果在线路上接入电流互感器变电流,那么就可以把线路上大大小小的电流,按不同的比例,统一变成大小相近的电流。
只要用一种电流规格的电气仪表,例如通用的电流为5A的电气仪表,就可以通过电流互感器,测量线路上小至几安和大至几万安的电流。
同时电流互感器的基本结构和变压器很相像,它也有两个绕组,一个叫原边绕组或一次绕组;一个叫副边绕组或二次绕组。
两个绕组之间有绝缘,使两个绕组之间有电的隔离。
电流互感器在运行时一次绕组W1接在线路上,二次绕组W2接电气仪表,因此在测量高压线路上的电流时,尽管原边电压很高,但是副边电压却很低,操作人员和仪表都很安全。
由此可见,电流互感器除了可以将线路上大小不一的电流变成一定大小的电流,以便于测量之外,还可以起到与线路绝缘的作用,以保证操作人员和仪表的安全。
1.1.1测量用电流互感器测量用电流互感器的用途,主要有下列两方面:⑴用来测量高压线路上的电流和功率,起绝缘隔离的作用,以保证操作人员和仪表的安全。
⑵来测量高压或低压线路上的大电流和大功率,使用统一的5A的二次线路和测量仪表。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
WCS2702电流检测和过流检测模块简易使用说明
实物图1
1 本模块电气参数:
电源电压:3-12V;
电源电流:3.5mA;
工作温度:-20度~125度;
隔离电压:1.5KV;
检测电流范围:-2A-2A;
限流电流范围:0.03A~2A;
板子尺寸:45mm*34mm;
2本模块的性能特点:
(1)响应时间快(100us);
(2)开关信号电平切换稳定;
(3)电流设置方便;
(4)电流大小设置精准;
3应用领域:
1) 交/直流电流检测;
2) 电机堵转检测;
3) 多通道电流检测;
4 发货清单:
◆ WCS2702电流检测及限流模块 一块;
◆ 4色排线 一条;
◆ 电子档使用说明书 一份
5 该模块实际原理图图如下:
图 2
检测电流与模拟信号输出的关系如下: 模拟信号输出:()2
o a a Vcc v i K i =±*其中电流流经IP+,IP-,K 为线性度; 以输入1A 为例,Vcc=5V , m /;V A WCS2702 的线性度为K=1000
我们简单说下WCS2702 检测电流与输出电压的对应关系
电流从正方向IP+流进,IP-流出时: 公式+2
o a Vcc v i K =*;(1.1-1),对应输出:V O =(2.5+1)V=3.5V 电流从反方向IP-流进,IP+流出时:
公式2o a Vcc v i K =
*-;(1.1-2),对应输出:V O =(2.5-1)V=1.5V 如果是交流信号时:2o a Vcc v i K =±*;(1.1-3);V O 对应输出范围:3.5V-1.5V 。
以上为理想数值,实际数值会有一定微小精度误差。
6 数字信号输出Dout2
该模块采用轨对轨运放将模拟信号与设定的基准电压进行比较,原理图如下:
图3
理论值:
当逆时针旋转可调电阻R3时, V REF 电压值增加
o2_ref V V led <当Aout1时,Dout2输出低电平,红色灯亮;
当顺时钟旋转可调电阻R3时, V REF 电压值减小
o2_ref V V led >当Aout1时,Dout2输出高电平,红色灯不亮; 通过旋转Vref 可以调节我们需要的限流电流值。
为了让电路可靠稳定工作,本比较电路组成一个带有迟滞功能的比较电路:
454
*()HIGH LOW R Vr Vr V V R R +--=-+;(1.2-1) 其中41;R k =5430;R k = 1*(50.05)0.0115()431
u V ∆=-=;(1.2-2) 可以通过设定4R ,5R 值,改变电路迟滞灵敏度。
我们在实际调试中,实测到u ∆实际值为0.03V, 以2702m /WCS V A 的线性度为1000来
计算,本模块可以限流的电流范围为0.03A-2A:
采用此电路的好处如下:
数字比较最麻烦的地方,就是怕出现震荡,导致系统工作不正常。
市面上的其他比较电路仅采用简单的LM393做比较,这样在(模拟信号与设定的基准电压)两数值的临界点会出现振荡现象。
而我们采用轨对轨运放做比较,有以下两方面的好处,
◆正反馈电路响应时间快100us;
◆电路临界点稳定工作,电平切换稳定,不会出现错误动作;
6.1下面我们可以从以下波形分析来证实该运放比较电路的稳定性;
图4
根据我们实测的图4可以看出,当比较输出信号从低电平跃变成高电平,响应时间是100us ,没有出现震荡,可以很好被单片机识别.
图5
根据我们实测的图5可以看出,比较输出信号从高电平跃变成低电平,响应时间是136us左右,虽然在高电平的时候有3处明显的电平波动(这是比较器的特点),但此电平最低值都保持在4V以上,4V是属于高电平数值的范围,单片机I/O还是会识别为高电平,因而我们可以说,临界点没有出现震荡。
现在让我们来对比市面上其他家的ACS712电流比较模块的波形,基本上都是采用简单的LM393比较电路,它们在临界点的波形状态如下图6:
图6
从以上图6波形可以看出,信号最低值为2V,2V是单片价I/O不好识别的电压,有可能被识别为高电平,也有可能被识别为高电平,因此是不稳定的状态。
鉴于迟滞功能的存在,小的变化电流不能稳定检测出来,请客户根据自己的要求选择本模块。
本模块可以限流的电流范围为30mA-2A。
7 基准电压如何设定才合适
这里我们重点讲下如何设定基准电压与实际电压进行比较;
该板子上有一个V o2_work发光LED,我们讲述其代表的重要意义;
(1)V o2_work LED指示灯
当设定的基准电压Vref > Aout1(实际输出电压)时Vo2_work亮;
当设定的基准电压Vref < Aout1(实际输出电压)时Vo2_work灭;
通过CH1_Work亮或灭的状态,我们方便判断此时基准电压大小,因而可设定我们需要的基准电压;
往逆时钟方向,拧可调电阻R17 ,Vref增加;
往顺时钟方向,拧可调电阻R17 ,Vref减小;
(2)基准电压如何设定跟实际检测电压接近:
板子上电后,同时将检测对象的功率设备正常启动工作,此时我们看下板子V o2_work状态;
如果此时Vo2_work为灭的状态,我们往逆时钟方向拧可调电阻R3,一直拧到Vo2_work亮为止,此时一定要注意,CH1_Work由灭到亮的这个临界点,找到临界点后,我们还需再做一件事,将可调电阻R3往逆时钟方向再拧过一点,具体多少,需要客户自己根据设定电流值大小来调节。
设定完成后,当被检测的设备的电流超过设定电流值时,Vo2_work为灭的状态。
Dout2开关信号由低电平变为高电平。
如果此时Vo2_work为亮的状态,我们往顺时钟方向拧可调电阻R3,一直拧到Vo2_work灭为止,此时一定要注意,V o2_work由亮到灭的这个临界点,找到临界点后,我们还需再做一件事,将可调电阻R17往逆时钟方向拧,将V o2_work重新拧为亮的状态, 具体多少,需要客户自己根据限定的电流值大小来调节。
设定完成后,当被检测设备的电流超过设定电流值时,V o2_work为灭的状态。
Dout2开关信号由低电平变为高电平。