ICS29.240Q/GDW 国家电网公司企业标准Q/GDW730—201212kV固体绝缘环网柜技术条件Specifications for12kV solid-insulated ring main units2012-03-02发布2012-03-02实施国家电网公司发布Q/GDW730—2012目次前言··································································································································································II1范围·····························································································································································12规范性引用文件··········································································································································13术语和定义··················································································································································24正常使用条件和特殊使用条件···················································································································25设备型号和定义··········································································································································26额定值·························································································································································27设计与结构··················································································································································48型式试验······················································································································································89出厂试验·····················································································································································1210交接试验···················································································································································1311选用导则···················································································································································1412查询、投标和订货时提供的资料············································································································1513运输、贮存、安装、运行和维护规则····································································································1514安全··························································································································································17编制说明··························································································································································18IQ/GDW730—2012II前言固体绝缘环网柜是国家电网公司重点推广的新技术成果之一。

XGN-12固体柜技术

XGN-12固体柜技术

HSXGN□-12(FZ)/T630-20HSXGN□-12(F Z·R)/T125-31.5箱型固定式固体绝缘交流金属封闭开关设备技术条件红苏电气科技有限责任公司技术条件HS.536.001JT共9页第2页2、产品采用和依据的标准GB3906-2006《3.6-40.5kV交流金属封闭开关设备和控制设备》;GB/T11022-2011《高压开关设备和控制设备标准的共用技术要求》;DL/T404-2007《3.6kV-40.5kV交流金属封闭开关设备和控制设备》;GB16926-2009《高压交流负荷开关-熔断器组合电器》、GB311.1-1997《高压输变电设备的绝缘配合》;GB762-2002《标准电流》;GB3804-2003《3.6KV-40.5KV高压交流负荷开关》;GB1985-2004《高压交流隔离开关和接地开关》;GB3309-1989《高压开关设备在常温下的机械试验》;DL/T593-2006《高压开关设备和控制设备的共用技术要求》;GB/T7354-2003《局部放电测量》3、使用环境条件a)环境温度最高温度:+40℃最低温度:-45℃b)环境湿度日平均相对温度:≤95%月平均相对温度:≤90%日平均饱和蒸气压:≤2.2*10-3MPa月平均饱和蒸气压:≤1.8*10-3MPa;c)海拨:不超过2000m;d)地震裂度:不超过8度;e)使用场所无易燃和爆炸危险、无化学腐蚀性气体以及激烈震动。

标记处数更改文件号签字日期标记处数更改文件号签字日期标记处数更改文件号签字日期4、技术参数4.1HSXGN□-12(FZ)/T630-20的主要技术参数见表1:表1序号名称单位参数值1额定电压kV12 2额定电流A630 3额定频率HZ504额定绝缘水平1min工频电压(相间、对地/断口)kV42/48雷电冲击电压(相间、对地/断口)75/855额定短时耐受电流(主回路和接地开关)kA 206额定峰值耐受电流(主回路和接地开关)50 7额定短路关合电流50 8额定短路持续时间s49额定有功负载开断电流A 63010额定闭环开断电流630 11切空载变压器电流15 12额定电缆充电开断电流25 13额定线路充电开断电流10 14额定开断接地故障电流75 15额定接地故障条件下线路和电缆充电电流4416机械寿命(负荷开关/隔离开关和接地一体开关)次10000/300017外壳防护等级IP4X18回路电阻μΩ≤20019触头开距mm9±120触头超行程mm3±121分闸速度(0-6mm行程)m/s 1.1±0.222合闸速度(6-0mm行程)m/s0.6±0.2标记处数更改文件号签字日期标记处数更改文件号签字日期标记处数更改文件号签字日期4.2HSXGN □-12(FZ·R)/T125-31.5的主要技术参数见表2:表29局部放电测量PC ≤205、技术要求5.1箱型固定式固体绝缘交流金属封闭开关设备的零部件制造与装配符合按规定程序批准的图纸和文件的要求,产品经调试后运动部分应灵活可靠。

环网柜技术规范

环网柜技术规范

环网柜技术规范书二〇一二年二月十三日1 总则1.1 本设备技术规范书仅限于户外10kV户外共箱式交流高压环网柜。

它提出了该设备的功能设计、结构、性能、安装和试验等方面的技术要求。

1.2 本设备技术规范书提出的是最低限度的技术要求,并未对一切技术细节作出规定,也未充分引述有关标准和规范的条文,卖方应提供符合或优于本规范书和工业标准的优质产品。

1.3 本设备技术规范书所使用的标准如遇与卖方所执行的标准不一致时,按较高标准执行。

1.4 本设备技术规范书经买、卖双方确认后作为订货合同的技术附件,与合同正文具有同等的法律效力。

1.5 本设备技术规范书未尽事宜,由买卖双方协商确定。

1.6 买方所指定产品厂家的元器件质量由卖方负责。

2 引用标准户外环网柜各项技术指标应完全满足或更优于下列有关标准:2.1 符合国际电工委员会IEC694、298、420、265、129、56、529标准。

2.2 符合有关国家标准。

GBll022-89 《高压开关设备通用技术条件》GB1984-2003 《交流高压断路器》GB/T16927.1-1997《高电压试验技术》GB3906-1991 《3-35KV金属封闭开关设备》GB763-1990 《交流高压电器在长期工作时的发热》DL/T402-1999 《交流高压断路器订货技术条件》DL/T593-1996 《高压开关设备的共用订货技术导则》GB1208-1997 《电流互感器》GB1207-1997 《电压互感器》GB4208-1993 《外壳防护等级》GB311.1-1997 《高压输变电设备的绝缘配合》GB11033.1-89 《额定电压26/35KV及以下电力电缆附件基本技术要求》GB3804-90 《3-63kV交流高压负荷开关》DL/T403-2000 《12KV~40.5KV高压真空断路器订货技术条件》DL/T404-1997 《户内交流高压开关柜订货技术条件》柜内所配全部设备及连接方式均应满足国标或者电力工业标准。

12KV环网柜使用说明书

12KV环网柜使用说明书

产品介绍环网柜是俗称,一般指用于环网线路中或终端的SF6负荷开关及SF6负荷开关+熔断器组合电器。

SF6负荷开关是近年来不少用户体会到的一种优良负荷开关,除电寿命长,开断力强等与真空负荷开关有共同的优点外,其突出优点是容易实现三工作位(接通、断开和接地),小电流(电感、电容)开断,抗严酷环境条件能力强。

适宜在城乡中压配电网推广应用。

负荷开关是带有简单灭弧装置的一种开关电器,使用SF6气体作为绝缘和灭弧介质的负荷开关称为SF6负荷开关,它可以作为关合和开断负荷电流及过载电流用,亦可以作为关合和开断空载线路、空载变压器及电容器组等,凡具有接通、断开和接地功能的三工作位负荷开关,都有结构简单、价格便宜的特点。

只是负荷开关不能断开短路电流。

SF6负荷开关+熔断器组合电器是由SF6负荷开关来承担过载电流(此过载电流对SF6负荷开关来说仍在负荷开关额定开断电流的范围以内)和正常工作电流的关合和开断,并且还要求承担"转移电流"的开断。

而变压器高压侧的短路保护和过载保护由高压限流熔断器来承担。

这时一组SF6负荷开关及三个带触发器的熔断器,只要任何一个触发器动作,其联动机构会使负荷开关三相同时自动分闸。

两者有机的结合起来,就可满足配电系统各种正常和故障下运行操作保护的要求。

中置柜指的手车柜,如KYN18,KYN28(GZS1),目前主要指KYN28(GZS1),可靠墙安装,现已系列化,国内生产厂家多,五防齐全,可配VS1,VD4,ZN63等进口或国产断路器。

首先要看你这个水处理项目是不是很重要,按照常规来讲,水处理设备不属于Ⅰ类负荷,而且变压器才500KVA,从变压器的容量可以看出,你这个水处理应该是个比较小的污水处理站(可能是某个厂矿在环保的压力下新建的用来处理污水用的),所以用环网柜足够了,2台环网柜的投资远远小于你用2台中置柜的,业主(甲方对你给他省钱他应该很高兴),而且从实际来讲,安装环网柜一般都是因为一个原因:负荷侧(因为污水处理一般都建在市区的边上或工厂的边上)距离高低压配电室比较远,所以变压器的进线前要有刀闸和断路器,以便将高压配电室到变压器之间的这段长电缆用环网柜做个隔离,万一电缆发生事故使其不致于直接波及变压器,另外,当变压器临时检修时好做就近断开电源用,环网柜之上还有高压柜(本身有综合保护),环网柜之下的低压进线还有断路器(建议你选用施耐德的MT断路器,各种保护比较全),所以保护的重任几乎就不大用环网柜来承担(好的环网柜的保护能力还是很强的),所以用环网柜是完全可以的。

固体绝缘环网柜的电气标准、产品结构及技术

固体绝缘环网柜的电气标准、产品结构及技术

固体绝缘环网柜的电气标准、产品结构及技术摘要:固体绝缘环网柜是我国电气设备中的一项重要组成部分,在社会经济的建设和发展过程中发挥了重要的作用。

在电力设备中,SF6是一种优异的灭弧和绝缘介质,应用比较广泛。

但是,在SF6的应用的过程中因为是温室气体,所以会受到环境因素的影响。

我国电力行业的迅速发展和电力技术的不断进步,促进了固体绝缘开关柜技术的发展。

关键词:固体绝缘;环网柜;电气标准;产品结构;技术固体绝缘开关柜的主要的绝缘介质是固体绝缘材料,属于电力设备开关柜的一种。

在我国电力技术的过程中,固体绝缘开关柜是一种具备全绝缘和全密封性的模块,可以再次进行组合或者扩展。

主要的组成部分是真空灭弧室、隔离开关、电导连接、主母线和分支母线和接地开关等,单一的主导回路或者组合的回路应用固体绝缘介质包覆封装而成,具有一定的功能。

这种固体绝缘环网柜,最大程度的保证了人身安全,具有紧凑的尺寸、较强的环境适应能力和环保等优点。

1 固体绝缘环网柜的电气标准1.1 固体绝缘环网柜的发展现状按照我国电力技术的规定,对固体绝缘环网柜具有一定的限制,额定电压等级必须保证是12 kV。

另外,固体绝缘环网柜的额定电流等级也被规定为630 A 和1 250 A。

目前,我国电力市场中应用的固体绝缘开关柜设备,大部分都是12 kV的额定电压等级,630 A的额定电流。

近些年,固体绝缘开关柜设备的研究技术不断的提高,日本的东芝公司对固体绝缘开关柜设备的研究获得了明显的效果,固体绝缘开关柜的开发已经达到了36 kV的电压等级。

从这种情况来看,这种固体绝缘开关柜仍然具有一定的市场,随着固体绝缘开关柜技术参数等级的不断升高,人们不断的研究和探索,固体绝缘环网柜的应用技术不断的完善,发挥更好的应用效果,在以后的电气市场中具有良好的市场前景。

1.2 固体绝缘环网柜的结构形式目前,按照布置方式的不同,固体绝缘开关柜可以分为两种。

区分的主要依据,是按照三相正面的布置方式划分。

12kV环网柜技术规范

12kV环网柜技术规范

12kV环网柜技术规范12k V环网柜技术规范12kV环网柜技术规范目录12kV环网柜技术规范 (1)1规范性引用文件 (1)2技术参数和性能要求 (2)3标准技术参数 (14)4使用环境条件表 (18)5试验 (19)5.6.15电磁兼容测试按GB/T 11022中的规定进行 (25)12kV环网柜技术规范1规范性引用文件下列文件对于本文件的应用是必不可少的。

凡是注日期的引用文件,仅注日期的版本适用于本文件。

凡是不注日期的引用文件,其最新版本适用于本文件。

GB/T 191 包装储运图示标志(ISO 780-1997,MOD )GB 1094.11 电力变压器第11部分干式变压器(IEC 726-82,EQV) GB 1207 电磁式电压互感器(IEC 60044-2: 2003, MOD )GB 1208 电流互感器 (IEC 60044-1.2001. MOD)GB 1984 高压交流断路器(IEC 62271-100: 2001, MOD)GB 1985 高压交流隔离开关和接地开关(IEC 62271-102: 2002, MOD)GB/T 11022 高压开关设备和控制设备标准的共用技术要求GB 3804 3.6kV~40.5kV 高压交流负荷开关(IEC 60265-1-1998 ,MOD)GB 3906 3.6kV~40.5kV 交流金属封闭开关设备和控制设备(IEC 62271-200-2003,MOD )GB 4208 外壳防护等级(IP代码)(IEC 60529-2001,IDT)GB/T 5465.2 电气设备用图形符号第2部分:图形符号(IDT IEC 60417 DB:2007)GB/T 7354 局部放电测量(IEC 60270-2000,IDT)GB/T 10228 干式电力变压器技术参数和要求GB/T 11022 高压开关设备和控制设备标准的共用技术要求GB 11032 交流无间隙金属氧化物避雷器(IEC 60099-4-2006,MOD)GB/T 12022 工业六氟化硫(IEC 376,376A,376B.MOD)GB/T 12706.4 挤包绝缘电力电缆及附件试验要求(IEC 60502-4-2005,MOD)GB 15166.2 交流高压熔断器:限流式熔断器(IEC 60282-1-2005 ,MOD)GB 16926 高压交流负荷开关熔断器组合电器(IEC 6227-105-2002 ,MOD)GB 50150 电气装置安装工程电气设备交接试验标准DL/T 402 高压交流断路器订货技术条件(IEC 62271-100-2001,MOD)DL/T 403 12-40.5kV高压真空断路器订货技术条件DL/T 404 3.6kV~40.5kV交流金属封闭开关设备和控制设备(IEC 62271一200-2003,MOD)DL/T 486 高压交流隔离开关和接地开关(IEC 62271-102-2002,MOD)DL 538 高压带电显示装置(IEC 61958- 2000-11,MOD )DL/T 593 高压开关设备和控制设备标准的共用技术要求(IEC 60694-2002,MOD)DL/T 621 交流电气装置的接地DL/T 728 气体绝缘金属封闭开关设备订货技术导则(IEC 815-1986,IEC 859-1986)DL/T 791 户内交流充气式开关柜选用导则JB/T 8144.1 额定电压26/35kV及以下电力电缆附件基本技术要求SD 318 高压开关柜闭锁装置技术条件Q/GDW 741 配电网技术改造设备选型和配置原则Q/GDW 742 配电网施工检修工艺规范国家电网公司十八项电网重大反事故措施(修订版)国家电网公司交流高压断路器技术标准、交流隔离开关和接地开关技术标准国家电网公司关于印发《预防12kV~40.5kV交流高压开关柜事故补充措施》的通知国家电网公司关于印发《预防交流高压开关柜人身伤害事故措施》的通知国家电网公司物资采购标准高海拔外绝缘配置技术规范电力设备(交流部分)监造大纲电网设备及材料质量管控重点措施2技术参数和性能要求2.1环网柜技术参数环网柜技术参数见技术参数特性表。

(完整word)6南方电网公司12kV固体绝缘环网柜技术规范

(完整word)6南方电网公司12kV固体绝缘环网柜技术规范
GB/T 2423。1 电工电子产品环境试验第2部分:试验方法 试验A:低温
GB/T 2423。2 电工电子产品环境试验第2部分:试验方法 试验B:高温
GB/T 2424.3 电工电子产品环境试验第2部分:试验方法试验Cab:恒定湿热试验
GB/T 2900.1 电工术语 基本术语
GB/T 2900。15电工术语 变压器 互感器 调压器和电抗器
式中:H是海拔,用米表示。
为了简单起见,m取下述的确定值:
a)m=1 对于工频、雷电冲击和相间操作冲击电压;
b)m=0.9 对于纵绝缘操作冲击电压;
c)m=0。75 对于相对地操作冲击电压.
操作冲击的m取值可参考IEC 60071—2的4。2。2.
注1:在任一海拔处,内绝缘的绝缘特性是相同的,不需采取特别的措施。外绝缘和内绝缘的定义见GB/T 311.2。
技术要求51技术参数10kv固体绝缘环网柜根据设备类型应分别满足表2负荷开关与负荷开关熔断器组合电器主要参数表序号名称单位技术要求负荷开关柜熔断器组合电器柜额定电压kv12630125630125额定短时耐受电流有效值ka20序号名称单位技术要求负荷开关柜熔断器组合电器柜额定峰值耐受电流ka50熔断器预期短路开断电流有效值ka31510接地刀闸4s短时耐受电流ka2011额定负荷电流开断次数10012机械寿命真空负荷开关10000接地刀闸300013额定电缆充电开断电流2514绝缘水平单位技术参数额定短时工频耐受电压有效值隔离断口间kv48开关断口kv42相间相对地kv42额定雷电冲击耐受电压峰值隔离断口间kv85开关断口kv75相间相对地kv7515温升限值按gbt11022及dl593规定16弹簧操作机构手动或电动弹簧操作机构电动机额定功率240w17操作电压ac220110vdc1104824v18外壳防护等级ip3xip3x19柜体防护等级ip3x20一次部件防护等级ip6721整柜局放pc20注

12KV环网柜使用说明书

12KV环网柜使用说明书

产品介绍环网柜是俗称,一般指用于环网线路中或终端的SF6负荷开关及SF6负荷开关+熔断器组合电器。

SF6负荷开关是近年来不少用户体会到的一种优良负荷开关,除电寿命长,开断力强等与真空负荷开关有共同的优点外,其突出优点是容易实现三工作位(接通、断开和接地),小电流(电感、电容)开断,抗严酷环境条件能力强。

适宜在城乡中压配电网推广应用。

负荷开关是带有简单灭弧装置的一种开关电器,使用SF6气体作为绝缘和灭弧介质的负荷开关称为SF6负荷开关,它可以作为关合和开断负荷电流及过载电流用,亦可以作为关合和开断空载线路、空载变压器及电容器组等,凡具有接通、断开和接地功能的三工作位负荷开关,都有结构简单、价格便宜的特点。

只是负荷开关不能断开短路电流。

SF6负荷开关+熔断器组合电器是由SF6负荷开关来承担过载电流(此过载电流对SF6负荷开关来说仍在负荷开关额定开断电流的范围以内)和正常工作电流的关合和开断,并且还要求承担"转移电流"的开断。

而变压器高压侧的短路保护和过载保护由高压限流熔断器来承担。

这时一组SF6负荷开关及三个带触发器的熔断器,只要任何一个触发器动作,其联动机构会使负荷开关三相同时自动分闸。

两者有机的结合起来,就可满足配电系统各种正常和故障下运行操作保护的要求。

中置柜指的手车柜,如KYN18,KYN28(GZS1),目前主要指KYN28(GZS1),可靠墙安装,现已系列化,国内生产厂家多,五防齐全,可配VS1,VD4,ZN63等进口或国产断路器。

首先要看你这个水处理项目是不是很重要,按照常规来讲,水处理设备不属于Ⅰ类负荷,而且变压器才500KVA,从变压器的容量可以看出,你这个水处理应该是个比较小的污水处理站(可能是某个厂矿在环保的压力下新建的用来处理污水用的),所以用环网柜足够了,2台环网柜的投资远远小于你用2台中置柜的,业主(甲方对你给他省钱他应该很高兴),而且从实际来讲,安装环网柜一般都是因为一个原因:负荷侧(因为污水处理一般都建在市区的边上或工厂的边上)距离高低压配电室比较远,所以变压器的进线前要有刀闸和断路器,以便将高压配电室到变压器之间的这段长电缆用环网柜做个隔离,万一电缆发生事故使其不致于直接波及变压器,另外,当变压器临时检修时好做就近断开电源用,环网柜之上还有高压柜(本身有综合保护),环网柜之下的低压进线还有断路器(建议你选用施耐德的MT断路器,各种保护比较全),所以保护的重任几乎就不大用环网柜来承担(好的环网柜的保护能力还是很强的),所以用环网柜是完全可以的。

12KV环网柜使用说明书

12KV环网柜使用说明书

产品介绍环网柜是俗称,一般指用于环网线路中或终端的SF6负荷开关及SF6负荷开关+熔断器组合电器。

SF6负荷开关是近年来不少用户体会到的一种优良负荷开关,除电寿命长,开断力强等与真空负荷开关有共同的优点外,其突出优点是容易实现三工作位(接通、断开和接地),小电流(电感、电容)开断,抗严酷环境条件能力强。

适宜在城乡中压配电网推广应用。

负荷开关是带有简单灭弧装置的一种开关电器,使用SF6气体作为绝缘和灭弧介质的负荷开关称为SF6负荷开关,它可以作为关合和开断负荷电流及过载电流用,亦可以作为关合和开断空载线路、空载变压器及电容器组等,凡具有接通、断开和接地功能的三工作位负荷开关,都有结构简单、价格便宜的特点。

只是负荷开关不能断开短路电流。

SF6负荷开关+熔断器组合电器是由SF6负荷开关来承担过载电流(此过载电流对SF6负荷开关来说仍在负荷开关额定开断电流的范围以内)和正常工作电流的关合和开断,并且还要求承担"转移电流"的开断。

而变压器高压侧的短路保护和过载保护由高压限流熔断器来承担。

这时一组SF6负荷开关及三个带触发器的熔断器,只要任何一个触发器动作,其联动机构会使负荷开关三相同时自动分闸。

两者有机的结合起来,就可满足配电系统各种正常和故障下运行操作保护的要求。

中置柜指的手车柜,如KYN18,KYN28(GZS1),目前主要指KYN28(GZS1),可靠墙安装,现已系列化,国内生产厂家多,五防齐全,可配VS1,VD4,ZN63等进口或国产断路器。

首先要看你这个水处理项目是不是很重要,按照常规来讲,水处理设备不属于Ⅰ类负荷,而且变压器才500KVA,从变压器的容量可以看出,你这个水处理应该是个比较小的污水处理站(可能是某个厂矿在环保的压力下新建的用来处理污水用的),所以用环网柜足够了,2台环网柜的投资远远小于你用2台中置柜的,业主(甲方对你给他省钱他应该很高兴),而且从实际来讲,安装环网柜一般都是因为一个原因:负荷侧(因为污水处理一般都建在市区的边上或工厂的边上)距离高低压配电室比较远,所以变压器的进线前要有刀闸和断路器,以便将高压配电室到变压器之间的这段长电缆用环网柜做个隔离,万一电缆发生事故使其不致于直接波及变压器,另外,当变压器临时检修时好做就近断开电源用,环网柜之上还有高压柜(本身有综合保护),环网柜之下的低压进线还有断路器(建议你选用施耐德的MT断路器,各种保护比较全),所以保护的重任几乎就不大用环网柜来承担(好的环网柜的保护能力还是很强的),所以用环网柜是完全可以的。

12kV环网柜采购标准 第2部分:12kV气体绝缘环网柜专用技术规范

12kV环网柜采购标准 第2部分:12kV气体绝缘环网柜专用技术规范

12kV环网柜采购标准
第2部分:12kV气体绝缘环网柜
专用技术规范
Purchasing standard for 12kV ring main units
Part 2: Special technical specification for 12kV gas-insulated ring main units
QI GDW 13091. 2—2018
前j 言
为规范12kV环网柜的采购,制定本部分。

《12kV环网柜采购标准》分为3个部分:
第1部分:通用技术规范;
第2部分:12kV气体绝缘环网柜专用技术规范;
第3部分:12kV空气绝缘环网柜专用技术规范。

本部分为《12kV环网柜采购标准》的第2部分。

本部分代替Q/GDW13091.2—2014,与Q/GDW13091.2—2014相比,主要技术性差异如下:增加或替换自2014年以来新发布的国家、行业和国网企业标准与本采购规范相关的标准;
为提升环网柜绝缘能力,增加“环网柜整体局部放电量Cl.I Ur) :s;2opC,单个绝缘件C l.lUr) :s;3pc"要求。

II。

环网柜技术规范及相关要求

环网柜技术规范及相关要求

环网柜技术规范及相关要求1、通用技术标准及规范IEC60298《1kV以上及52kV以下交流金属封闭开关设备和控制设备》GB/T311.1-1983 《高压输变电设备的绝缘配合》GB/T11022-1999 《高压开关设备和控制设备标准的共用技术条件》GB1984-2003 《高压交流断路器》GB/T4109 《高压套管技术条件》GB/T4208-1993 《外壳防护等级》SD318- 89 《高压开关柜闭锁装置技术条件》GB1985-2004 《交流高压隔离开关和接地开关》GB763-90 《交流高压电气在长期工作时的发热》GB3906-2006 《3-35kV交流金属封闭开关设备》GB3804-2004 《3.6-40kV交流高压负荷开关》2、设备主要技术参数环网柜内SF6开关选用*、*等品牌,柜内SF6开关技术参数:主要技术参数:额定电压 12kV额定频率 50Hz额定电流 630A(可以安装125A的熔芯)额定雷电冲击耐受电压 75kV 相间对地85kV 断口间75kV真空灭弧室额定工频耐受电压 42kV 相间对地48kV 断口间额定短短时耐受电流 20kA额定动稳定电流 50kA机械寿命 5000次(负荷开关) 2000次(接地开关)3、主要结构特点3.1环网柜的性能要求环网柜的结构保证工作人员的安全,且便于运行、维护、检查、监视、检修和试验。

要求免维护、防盗,满足全工况运行和凝露试验要求。

3.2环网柜具备防止误入带电隔室措施。

3.3环网柜外壳采用厚度不低于2mm冷轧钢板,经数控剪切/冲压/折弯成型,由螺栓及铆栓连接组装而成,部分焊接。

3.4环网柜柜体各部件有环氧树脂粉末喷涂,柜内元器件安装支架镀锌处理。

3.5主回路的一切组件均安装在金属外壳内,外壳的防护等级不低于IP3X。

3.6开关及其操动机构牢固的安装在支架上,支架不因操作力的影响而变形;操作时产生的振动不影响柜上的仪表、继电器等设备的正常工作。

12kV、24kV环网柜通用技术规范

12kV、24kV环网柜通用技术规范

(2009年版)国家电网公司物资采购标准(开关柜卷环网柜册)12kV、24kV环网柜通用技术规范(编号:1016006-0000-00)国家电网公司二〇〇九年十二月对应的专用技术规范目录目录1 总则 (3)1.1一般规定 (3)1.2投标人应提供的资格文件 (3)1.3适用范围 (4)1.4对设计图纸、说明书和试验报告的要求 (5)1.5标准和规范 (7)1.6投标人必须提交的技术参数和信息 (8)1.7备品备件 (8)1.8专用工具与仪器仪表 (9)1.9安装、调试、性能试验、试运行和验收 (9)2 结构要求 (9)2.1环网柜技术参数 (9)2.2通用要求 (9)2.3负荷开关(断路器) (14)2.4负荷开关-熔断器组合电器 (15)2.5隔离开关 (15)2.6接地开关 (15)2.7电流互感器 (15)2.8电压互感器 (16)2.9避雷器 (16)2.10母线 (16)3 试验 (16)3.1型式试验 (16)3.2出厂试验 (17)3.2现场交接试验 (17)4 技术服务、设计联络、工厂检验和监造 (18)4.1技术服务 (18)4.2设计联络会 (19)4.3工厂检验和监造 (19)5 一、二次及土建接口要求 (20)5.112K V环网柜要求 (20)5.224K V环网柜要求 (28)1 总则1.1 一般规定1.投标人应具备招标公告所要求的资质,具体资质要求详见招标文件的商务部分。

2.投标人须仔细阅读包括本技术规范(技术规范通用和专用部分)在内的招标文件阐述的全部条款。

投标人提供的12kV、24kV环网柜应符合招标文件所规定的要求。

3.本招标文件技术规范提出了对环网柜的技术参数、性能、结构、试验等方面的技术要求。

4.本招标文件提出的是最低限度的技术要求,并未对一切技术细节做出规定,也未充分引述有关标准和规范的条文,投标人应提供符合本技术规范引用标准的最新版本标准和本招标文件技术要求的全新产品,如果所引用的标准之间不一致或本招标文件所使用的标准与投标人所执行的标准不一致时,按要求较高的标准执行。

12kV环网箱(开闭所)

12kV环网箱(开闭所)

(2018年版)12kV环网箱(开闭所) 供应商资质能力核实红苏标准一、环网箱(箱式开闭所)本体型式试验项目强制性的型式试验※1、绝缘试验※2、回路电阻测量※3、温升试验(1.1倍额定电流,负荷开关-熔断器组合电器除外)※4、机械操作和机械特性试验※5、短时耐受电流和峰值耐受电流试验※6、关合和开断能力试验※7、防护等级检验※8、内部电弧试验适用时强制性的型式试验1、气候防护试验2、温升试验、短时耐受电流和峰值耐受电流试验、绝缘试验、内部电弧试验需要至少2个功能单元拼装在一起进行。

二、配套元器件的型式试验项目断路器强制性的型式试验※1、绝缘试验※2、主回路电阻测量※3、温升试验(1.1倍额定电流)※4、机械试验※5、短时耐受电流和峰值耐受电流试验※6、关合和开断能力试验适用时强制性的型式试验1、密封试验2、气体水份含量测量(≤150ppm)3、局部放电试验4、电磁兼容性试验5、真空灭弧室X射线测量试验6、环境试验负荷开关强制性的型式试验※1、绝缘试验※2、主回路电阻测量※3、温升试验(1.1倍额定电流)※4、机械试验※5、短时耐受电流和峰值耐受电流试验※6、关合和开断能力试验适用时强制性的型式试验1、密封试验2、气体水份含量测量(≤150ppm)3、局部放电试验4、电磁兼容性试验5、真空灭弧室X射线测量试验6、环境试验负荷开关-熔断器组合电器强制性的型式试验※1、绝缘试验※2、主回路电阻测量※3、温升试验※4、关合和开断能力试验※5、脱扣联动试验※6、熔断器的机械震动试验适用时强制性的型式试验1、密封试验2、气体水份含量测量(≤150ppm)3、局部放电试验4、电磁兼容性试验5、真空灭弧室X射线测量试验6、环境试验附录C主要生产设备※1、数控折弯机(或具备折剪冲功能的数控加工中心)※2、数控剪板机(或具备折剪冲功能的数控加工中心)※3、数控冲床(或具备折剪冲功能的数控加工中心)※4、母排加工机5、起重设备6、叉车7、切割机8、焊机9、喷涂设备附录D主要试验设备※1、工频耐压装置※2、二次回路工频耐压装置※3、回路电阻测试仪※4、机械特性测试仪※5、绝缘电阻测试仪※6、微水检测仪(气体绝缘环网箱适用)※7、SF6气体检漏仪(气体绝缘环网箱适用)7、局部放电测试仪(固体绝缘环网箱适用)9、伏安特性综合测试仪附录E 出厂试验项目1、主回路的绝缘试验2、辅助和控制回路的试验3、主回路电阻测量4、机械操作和机械特性试验5、设计和外观检查6、密封试验(气体绝缘环网箱适用)7、充气隔室的压力试验和气体状态测量(气体绝缘环网箱适用)。

12kV24kV环网柜通用技术规范

12kV24kV环网柜通用技术规范

(2009年版)国家电网公司物资采购标准(开关柜卷环网柜册)12kV、24kV环网柜通用技术规范(编号:1016006-0000-00)国家电网公司二〇〇九年十二月对应的专用技术规范目录目录1 总则 (3)1.1一般规定 (3)1.2投标人应提供的资格文件 (3)1.3适用范围 (4)1.4对设计图纸、说明书和试验报告的要求 (5)1.5标准和规范 (7)1.6投标人必须提交的技术参数和信息 (8)1.7备品备件 (8)1.8专用工具与仪器仪表 (9)1.9安装、调试、性能试验、试运行和验收 (9)2 结构要求 (9)2.1环网柜技术参数 (9)2.2通用要求 (9)2.3负荷开关(断路器) (14)2.4负荷开关-熔断器组合电器 (15)2.5隔离开关 (15)2.6接地开关 (15)2.7电流互感器 (15)2.8电压互感器 (16)2.9避雷器 (16)2.10母线 (16)3 试验 (16)3.1型式试验 (16)3.2出厂试验 (17)3.2现场交接试验 (17)4 技术服务、设计联络、工厂检验和监造 (18)4.1技术服务 (18)4.2设计联络会 (19)4.3工厂检验和监造 (19)5 一、二次及土建接口要求 (20)5.112K V环网柜要求 (20)5.224K V环网柜要求 (28)1 总则1.1 一般规定1.投标人应具备招标公告所要求的资质,具体资质要求详见招标文件的商务部分。

2.投标人须仔细阅读包括本技术规范(技术规范通用和专用部分)在内的招标文件阐述的全部条款。

投标人提供的12kV、24kV环网柜应符合招标文件所规定的要求。

3.本招标文件技术规范提出了对环网柜的技术参数、性能、结构、试验等方面的技术要求。

4.本招标文件提出的是最低限度的技术要求,并未对一切技术细节做出规定,也未充分引述有关标准和规范的条文,投标人应提供符合本技术规范引用标准的最新版本标准和本招标文件技术要求的全新产品,如果所引用的标准之间不一致或本招标文件所使用的标准与投标人所执行的标准不一致时,按要求较高的标准执行。

1250A环网柜技术规范

1250A环网柜技术规范

1250A环网柜技术规范中标单位:红苏电气科技有限责任公司目录1规范性引用文件 (1)2技术参数和性能要求 (2)3标准技术参数 (11)4使用环境条件表 (15)5试验 (15)12kV环网柜技术规范1规范性引用文件下列文件对于本文件的应用是必不可少的。

凡是注日期的引用文件,仅注日期的版本适用于本文件。

凡是不注日期的引用文件,其最新版本适用于本文件。

GB/T 191 包装储运图示标志(ISO 780-1997,MOD )GB 1094.11 电力变压器第11部分干式变压器(IEC 726-82,EQV)GB 1207 电磁式电压互感器(IEC 60044-2: 2003, MOD )GB 1208 电流互感器(IEC 60044-1.2001. MOD)GB 1984 高压交流断路器(IEC 62271-100: 2001, MOD)GB 1985 高压交流隔离开关和接地开关(IEC 62271-102: 2002, MOD)GB/T 11022 高压开关设备和控制设备标准的共用技术要求GB 3804 3.6kV~40.5kV 高压交流负荷开关(IEC 60265-1-1998 ,MOD)GB 3906 3.6kV~40.5kV 交流金属封闭开关设备和控制设备(IEC 62271-200-2003,MOD )GB 4208 外壳防护等级(IP代码)(IEC 60529-2001,IDT)GB/T 5465.2 电气设备用图形符号第2部分:图形符号(IDT IEC 60417 DB:2007)GB/T 7354 局部放电测量(IEC 60270-2000,IDT)GB/T 10228 干式电力变压器技术参数和要求GB/T 11022 高压开关设备和控制设备标准的共用技术要求GB 11032 交流无间隙金属氧化物避雷器(IEC 60099-4-2006,MOD)GB/T 12022 工业六氟化硫(IEC 376,376A,376B.MOD)GB/T 12706.4 挤包绝缘电力电缆及附件试验要求(IEC 60502-4-2005,MOD)GB 15166.2 交流高压熔断器:限流式熔断器(IEC 60282-1-2005 ,MOD)GB 16926 高压交流负荷开关熔断器组合电器(IEC 6227-105-2002 ,MOD)GB 50150 电气装置安装工程电气设备交接试验标准DL/T 402 高压交流断路器订货技术条件(IEC 62271-100-2001,MOD)DL/T 403 12-40.5kV高压真空断路器订货技术条件DL/T 404 3.6kV~40.5kV交流金属封闭开关设备和控制设备(IEC 62271一200-2003,MOD)DL/T 486 高压交流隔离开关和接地开关(IEC 62271-102-2002,MOD)DL 538 高压带电显示装置(IEC 61958- 2000-11,MOD )DL/T 593 高压开关设备和控制设备标准的共用技术要求(IEC 60694-2002,MOD)DL/T 621 交流电气装置的接地DL/T 728 气体绝缘金属封闭开关设备订货技术导则(IEC 815-1986,IEC 859-1986) DL/T 791 户内交流充气式开关柜选用导则JB/T 8144.1 额定电压26/35kV及以下电力电缆附件基本技术要求SD 318 高压开关柜闭锁装置技术条件Q/GDW 741 配电网技术改造设备选型和配置原则Q/GDW 742 配电网施工检修工艺规范国家电网公司十八项电网重大反事故措施(修订版)国家电网公司交流高压断路器技术标准、交流隔离开关和接地开关技术标准国家电网公司关于印发《预防12kV~40.5kV交流高压开关柜事故补充措施》的通知国家电网公司关于印发《预防交流高压开关柜人身伤害事故措施》的通知国家电网公司物资采购标准高海拔外绝缘配置技术规范电力设备(交流部分)监造大纲电网设备及材料质量管控重点措施2技术参数和性能要求2.1环网柜技术参数环网柜技术参数见技术参数特性表。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

(2012年版)国家电网公司物资采购标准(开关柜卷环网柜册)12kV固体绝缘环网柜通用技术规范(编号:1016006-0010-A0)国家电网公司二〇一二年五月对应的专用技术规范目录采购标准技术规范使用说明1、本物资采购标准技术规范分为标准技术规范通用部分和标准技术规范专用部分。

2、项目单位根据需求选择所需设备的技术规范。

技术规范通用部分条款、专用部分标准技术参数表和使用条件表固化的参数原则上不能更改。

3、项目单位应按实际要求填写“项目需求部分”。

如确实需要改动以下部分,项目单位应填写专用部分“表6 项目单位技术偏差表”,并加盖该网、省公司物资部(招投标管理中心)公章,与辅助说明文件随招标计划一起提交至招标文件审查会:①改动通用部分条款及专用部分固化的参数;②项目单位要求值超出标准技术参数值范围;③根据实际使用条件,需要变更污秽等级、海拔高度、耐受地震能力、压力释放能力、环境温度等要求。

经招标文件审查会同意后,对专用部分的修改形成“项目单位技术偏差表”,放入专用部分表6中,随招标文件同时发出并视为有效,否则将视为无差异。

4、投标人逐项响应技术规范专用部分中“1标准技术参数表”、“2项目需求部分”和“3投标人响应部分”三部分相应内容。

填写投标人响应部分,应严格按招标文件技术规范专用部分的“招标人要求值”一栏填写相应的投标人响应部分的表格。

投标人还应对项目需求部分的“项目单位技术偏差表”中给出的参数进行响应。

“项目单位技术偏差表”与“标准技术参数表”和“使用条件表”中参数不同时,以偏差表给出的参数为准。

投标人填写技术参数和性能要求响应表时,如有偏差除填写“表7 投标人技术偏差表”外,必要时应提供证明参数优于招标人要求的相关试验报告。

5、对扩建工程,项目单位应在专用部分提出与原工程相适应的一次、二次及土建的接口要求。

6、技术规范范本的页面、标题等均为统一格式,不得随意更改。

7、各专业要求(如有)目录1总则 (2)1.1一般规定 (2)1.2投标人应提供的资格文件 (2)1.3适用范围 (2)1.4对设计图纸、说明书和试验报告的要求 (4)1.5标准和规范 (5)1.6投标人必须提交的技术参数和信息 (6)1.7备品备件 (6)1.8专用工具与仪器仪表 (6)1.9安装、调试、性能试验、试运行和验收 (7)2结构要求 (7)2.112K V固体绝缘环网柜技术参数 (7)2.2通用要求 (7)2.3负荷开关(断路器) (10)2.4负荷开关-熔断器组合电器 (11)2.5隔离开关和接地开关 (11)2.6电流互感器 (11)2.8电压互感器 (11)2.9避雷器 (11)2.10母线 (11)3试验 (11)3.1型式试验 (11)3.2出厂试验 (12)3.2现场交接试验 (13)4技术服务、工厂检验和监造 (13)4.1技术服务 (13)4.2工厂检验和监造 (14)5一、二次及土建接口要求 (14)5.112K V固体绝缘环网柜要求 (14)1总则1.1 一般规定1.投标人应具备招标公告所要求的资质,具体资质要求详见招标文件的商务部分。

2.投标人须仔细阅读包括本技术规范(技术规范通用和专用部分)在内的招标文件阐述的全部条款。

投标人提供的 12kV固体绝缘环网柜应符合招标文件所规定的要求。

3.本招标文件技术规范提出了对 12kV固体绝缘环网柜的技术参数、性能、结构、试验等方面的技术要求。

4.本招标文件提出的是最低限度的技术要求,并未对一切技术细节做出规定,也未充分引述有关标准和规范的条文,投标人应提供符合本技术规范引用标准的最新版本标准和本招标文件技术要求的全新产品,如果所引用的标准之间不一致或本招标文件所使用的标准与投标人所执行的标准不一致时,按要求较高的标准执行。

5.如果投标人没有以书面形式对本招标文件技术规范的条文提出差异,则意味着投标人提供的设备完全符合本招标文件的要求。

如有与本招标文件要求不一致的地方,必须逐项在“技术差异表”中列出。

6.本招标文件技术规范将作为订货合同的附件,与合同具有同等的法律效力。

本招标文件技术规范未尽事宜,由合同签约双方在合同谈判时协商确定。

7.本技术规范中涉及有关商务方面的内容,如与招标文件的《商务部分》有矛盾时,以《商务部分》为准。

8.本招标文件技术规范中通用部分各条款如与技术规范专用部分有冲突,以专用部分为准。

1.2 投标人应提供的资格文件投标人在投标文件中应提供下列有关资格文件,否则视为非响应性投标。

1.投标人或制造商投标产品的销售记录(按技术规范专用部分附录A的格式提供)及相应的最终用户的使用情况证明。

2.投标人或制造商应提供权威机关颁发的ISO–9000、ISO-14000、ISO-28000系列的认证书。

3.投标人或制造商应提供履行合同所需的技术和主要设备等生产能力的文件资料。

4.投标人应提供有能力履行合同设备维护保养、修理及其他服务义务的文件。

5.投标人或制造商应提供投标产品全部有效的型式试验报告和省级及以上的产品鉴定证书。

6.投标人或制造商应提供一份详细的投标产品中重要外购或配套部件供应商清单及检验报告。

7.投标人或制造商应提供投标产品中进口关键元件供应商的供货承诺函。

1.3 适用范围1.本规范的适用范围仅限于本工程的投标产品。

内容包括设计、结构、性能、安装、试验、调试及现场服务和技术服务。

2.中标人应不晚于签约后天内,向买方提出一个详尽的生产进度计划表(见表1),包括产品设计、材料采购、产品制造、厂内测试以及运输等详情,以确定每部分工作及其进度。

表1 生产进度计划表合同号:;项目名称:;设备名称:;型号规格:;工作日期:至;制造商名称及地址:__________________;技术规范号:_________________;工作号:_____________;离岸日期:______________;到岸日期:______________;到达交货地点日期:。

1.4 对设计图纸、说明书和试验报告的要求1.4.1 图纸及图纸的认可和交付1.所有需经买方确认的图纸和说明文件,均应由卖方在合同生效后的天内提交给买方进行审定认可。

这些资料包括固体环网柜的外形图、剖面图、布置图、组装图、基础图、电气原理图、运输尺寸、运输质量、重心、总质量及二次线布置图等。

买方审定时有权提出修改意见。

买方在收到需认可图纸天后,将一套确认的或签有买方校定标记的图纸(买方负责人签字)返还给卖方。

凡买方认为需要修改且经卖方认可的,不得对买方增加费用。

在未经买方对图纸作最后认可前任何采购或加工的材料损失应由卖方单独承担。

2.卖方在收到买方确认图纸(包括认可方修正意见)后,应于天内向买方提供最终版的正式图纸和一套供复制用的底图及正式的光盘,正式图纸必须加盖工厂公章或签字。

3.完工后的产品应与最后确认的图纸一致。

买方对图纸的认可并不减轻卖方关于其图纸的正确性的责任。

设备在现场安装时,如卖方技术人员进一步修改图纸,卖方应对图纸重新收编成册,正式递交买方,并保证安装后的设备与图纸完全相符。

4.图纸的格式:所有图纸均应有标题栏、相应编号、全部符号和部件标志,文字均用中文,并使用SI国际单位制。

对于进口设备以中文为主,当买方对英文局部有疑问时,卖方应进行书面解释。

卖方免费提供给买方全部最终版的图纸、资料及说明书。

其中图纸应包括 1.4.1第1款所涉及的图纸和卖方自带的电缆清册,并且应保证买方可按最终版的图纸资料对所供设备进行维护,并在运行中进行更换零部件等工作。

1.4.2 说明书的要求1.固体环网柜的使用条件和技术参数。

2.固体环网柜及主要元件的结构、安装、调试、运行、维护、检修和全部附件的完整说明和技术数据。

3.开箱和起吊:运输单元的质量,起吊和开箱的注意事项及专用的起吊用具等。

4.组装:运输单元应有清楚的标志和代号,注有运输单元号的组装示意图。

5.安装准备:基础施工的要求,外部接线端子的尺寸,电缆进入地点位置,接地以及各种管道的连接方式、尺寸和布置等资料。

6.最终的安装验收:现场交接试验项目及试验方法。

7.维护:主要元件的维护说明以及维修工作的分类、程序和范围。

8.运行检修:运行中应注意的事项及控制指标,主要元件的检修周期和检修方案。

9.固体绝缘环网柜各个元件和所有附件的技术数据。

10.表示固体绝缘环网柜和操动机构的结构图及对基础的技术要求的说明。

11.结构特征、设备及其元件的更详细的说明。

12.操动机构特征的说明。

13.备品备件、专用工具和专用仪器仪表的使用说明。

14.说明书使用中文。

1.4.3 试验报告卖方应提供下列试验报告:1.固体环网柜的型式试验报告和出厂试验报告。

2.固体环网柜主要元件的型式试验报告和出厂试验报告。

3.当产品的设计、工艺、生产条件或使用的材料及主要元件发生重大改变而影响到产品性能时,应做相应的型式试验并提供试验报告。

1.4.4 图纸、说明书及试验报告等资料的交付时间、数量卖方应向买方提供的资料、图纸、试验报告见表2,但不限于表2的内容。

1.51.合同中所有设备、备品备件,包括卖方从第三方获得的所有附件和设备,除本规范中规定的技术参数和要求外,其余均应遵照最新版本的电力行业标准(DL)、国家标准(GB)和IEC标准及国际单位制(SI),这是对设备的最低要求。

投标人如果采用自己的标准或规范,必须向买方提供中文和英文(若有)复印件并经买方同意后方可采用,但不能低于DL、GB和IEC的有关规定。

2.执行的标准IEC 62271-100 高压交流断路器GB 1207 电压互感器GB 1208 电流互感器GB 1984-2003 高压交流断路器GB3804-2004 3.6kV~40.5kV高压交流负荷开关GB 16926-2009 高压交流负荷开关熔断器组合电器GB 1985-2005 高压交流隔离开关和接地开关GB 3906-2006 3.6kV-40.5kV交流金属封闭开关设备和控制设备GB/T 11022 高压开关设备和控制设备标准的共用技术要求GB 11032-2000 交流无间隙金属氧化物避雷器GB 15166.2 交流高压熔断器:限流式熔断器GB 50150-2006 电气装置安装工程电气设备交接试验标准DL/T 402-2007 高压交流断路器订货技术条件DL/T 404 3.6kV-40.5kV交流金属封闭开关设备和控制设备DL/T 486 高压交流隔离开关和接地开关DL/T728-2000 气体绝缘金属封闭开关设备订货技术导则Q / GDW 730-2012 12kV固体绝缘环网柜技术条件国家电网生[2004]634号输变电设备技术标准:《交流隔离开关和接地开关技术标准》。

3.所有螺栓、双头螺栓、螺纹、管螺纹、螺栓夹及螺母均应遵守国际标准化组织(ISO)和国际单位制(SI)的标准。