电气主接线图

合集下载

变电站电气主接线图

变电站电气主接线图

第5、6章图形,.2×8MW(a)2×10MVA1G G1TG2G2T110KV 35KV2×8MW(b)20MVAG1G 2GG110KV2T2G(c)2×8MW2×10MVAG1G 1T G35KVTMY-100X8ZN21-10/1250配CD10ⅢLZZBJ-101000/5 0.5/10P 2×(ZR-YJV 22-6/3×240)RN2-6/0.5ASFWG8000-6/4950Ue=6.3kV Ie=916.45A COSφ=0.8LZX-10Q800/5 0.5/10PJ Y N 2-10-03(改)1G励磁变(厂家配套)励磁互感器(厂家配套)JDJ-6 36 0.1√3√J Y N 2-10-17J Y N 2-10-18RN2-6/0.5A 36 0.1 0.1JDZJ-63√√3J Y N 2-10-20√ 6 0.1 0.1√333JDZJ-6RN2-6/0.5AHY5WZ-10/302G同左ZN21-10/2500配CD10ⅢLFZJ-102000/5 0.5/0.5/10/10PJ Y N 2-10-03SF9-20000/110Y,d11121±3×2.5%/6.3kV U k %=10.5%LGJ-120GW4-110DW/630左接地LW25-1261250A,40kA GW4-110DW/630双接地LCWB 6-110100/50.2/0.5/10P/10PTYD-110/ -0.07H 3√LRD-60-B 50/5GW4-110DW/630双接地JDCF-110Y5W1-100/260√110 0.1 0.13√√33GW 13-60G/400Y1W-73/15ZN21-10/630配CD10ⅢLZZBJ-10100/5 0.5/10PJ Y N 2-10-03ZR-YJV 22-6/3×50SC9-800/6.3D,yn116.3±5%/0.4kV Ud%=7LMZ1-0.5 1200/5LMZ1-0.5 1200/5SC9-800/10D,yn1110±5%/0.4kV Ud%=7ZR-YJV 22-10/3×50LZZBJ-10100/5 0.5/10PZN21-10/630配CD10ⅢJ Y N 2-10-06(改)ZR-YJV 22-10/3×5010kV外来电源J Y N 2-10-19JDZJ-10HY5WZ-17/51RN2-10/0.5A10/0.1kV0.4kVLMY100×8-40×8DW15-1200DW15-1200DW15-12000.1LMY100×8-40×8G~G~TMY-100X8GW4-110DW/630左接地图5-19 某水电站电气主接线全图图5-20 地区变电所接线8回35kV220kV4 回2×120MVA至无功补偿装置6 回2×60MVA4回2×10MVA1T图5-21 终端变电所接线4回10kV2T110kV 35kVVV22-13×50+1×251#厂变进线V 42L6-A,0~150A DT864-2,380/220V,3(6A)42L6-V,0~450V说明:BT95O9为事故照明切换板,其直流电源用VV22-1-2×4电缆引至直流屏。

各种变电站电气主接线图

各种变电站电气主接线图

各种变电站电气主接线图?TYD-110/ -0.07H3GW4-110DW/630左接地GW4-110DW/630双接地6-110LCWB100/5 0.2/0.5/10P/10PLW25-1261250A~40kAGW4-110DW/630左接地LGJ-120LRD-60-B 50/5GW4-110DW/630SF9-20000/110GW13-60G/400双接地Y,d11121?3×2.5%/6.3kVUk%=10.5%JDCF-110Y1W-73/15110 0.1 0.1 0.1???333 TMY-100X8Y5W1-100/260LFZJ-102000/5 0.5/0.5/10kV外来电源10/10PZN21-10/2500JYN2-10-03配CD10?TMY-100X8ZR-YJV22-10/3×50ZN21-10/630ZN21-10/1250ZN21-10/630RN2-6/0.5ARN2-10/0.5A配CD10?配CD10?配CD10?HY5WZ-10/30HY5WZ-17/51LZZBJ-10LZZBJ-10LZZBJ-10JDZJ-6JDZJ-10JYN2-10-20JYN2-10-19100/5 1000/5 100/5 JYN2-10-03 6 0.10.110/0.1kVJYN2-10-06(改)30.5/10P0.5/10P0.5/10P??33励磁互感器JYN2-10-03,改,,厂家配套,ZR-YJV22-6/3×50ZR-YJV22-10/3×50同RN2-6/0.5ASC9-800/6.3SC9-800/10D,yn11D,yn116 0.1 RN2-6/0.5AJDJ-6 ??JYN2-10-17336.3?5%/0.4kV10?5%/0.4kV左Ud%=7Ud%=7励磁变,厂家配套,JDZJ-6LMZ1-0.5 1200/5LMZ1-0.5 1200/5 6 0.1 0.12×(ZR-YJV223??33-6/3×240)LMY100×8-40×8LMY100×8-40×8GSFWG8000-6/4950G2G1GUe=6.3kVDW15-1200~~DW15-1200DW15-1200Ie=916.45A0.4kVCOSφ=0.8LZX-10Q800/5 0.5/10P 图5-19 某水电站电气主接线全图JYN2-10-184 回6 回220kV2×120MVA2×60MVA至无功补偿装置35kV8回图5-20 地区变电所接线110kV35kV1T2T2×10MVA10kV4回4回图5-21 终端变电所接线GGGGGG~~~~~~(a)(b)GGGGG~~~~~(c)(d)图6-1 设两台厂变的厂用电源引接方式?段?段cdabBDACefijghklmn图6-2 厂用负荷供电回路图6-3见“主接线厂用电实例”图6.3KV10kVRN1-6/10APRWG1-10/100SC-80/66.3?5##1厂变2厂变S9-80/35%/0.4KV10.5?2×2.5Y,yn0%/0.4KVKYN-28-10-78Uk%=4.0Y,yn0Uk%=4.0VV22-3×50+1×25VV22-3×50+1×25 DT864-2,380/220V,3(6A)DT864-2,380/220V,3(6A)42L6-A,0,150A42L6-A,0,150A42L6-V,0,450V42L6-V,0,450V42L6-A,0,100A42L6-A,0,100A42L6-A,0,150A42L6-A,0,100A42L6-A,0,100AkwhkwhAAAAAAAAAAAAAAAAAAAAAVVAI段380/220VBCLMY-40×4BT9509至直流屏GGD1-361-101-36GGDGGD配电屏型号1-36(改)GGD1-36(改)GGD配电屏编号 1 2 3 4 5集水井水安装场主厂房照明 1#机 2#机厂内油处理前池副厂房照事故照明整流器一整流器二馈线名称吊车母线分段备用备用1#厂变进线2#厂变进线备用生活区备用备用气系统备用泵动力箱动力箱分电箱室分电箱明分电箱分电箱动力盘动力盘动力箱回路电流,A, 25 23.6 34 11 281331.75725115115 1110.82710 28HD13BX-HD13BX-刀开关HD13BX-200/31HD13BX-200/31HD13BX-200/31HD13BX-200/31HD13BX-200/31200/31200/31DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DW15-DW15-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-DZ20J-断路器DW15-200/120A100/32A100/32A100/20A100/20A100/20A100/40A100/32A100/20A100/63A1 00/20A100/32A200/120A200/120A100/20A100/20A100/32A100/20A100/20A100/32A1 00/20A100/32A100/32ALMZ1-0.66,LMZ1-0.66,电流互感器LMZ1-0.66,100/5LMZ1-0.66,100/5LMZ1-0.66,100/5LMZ1-0.66,100/5LMZ1-0.66,100/5150/5150/5VV22-1VV22-1VV22-1VV22-1VV22-1VV22-1VV22-1VV22-1VV22-1VV22-1VV22-1VV22-1VV22-1 VV22-1VV22-1引出电缆型号截面VV22-1-4×63×25+1×103×4+1×2.5-2×43×6+1×43×6+1×43×50+1×253×6+1×43×4+1×2.53×6+1×43×44×63×6+1×43×50+1×253×10+1×63×4+1×2.5 G25 穿管管径 G25 G25 G25 G25 G25 G15 G32 G32 G25 G25 G25 G25 G32说明: BT95O9为事故照明切换板~其直流电源用VV22-1-2×4电缆引至直流屏。

电站变电所电气主接线图(含说明)

电站变电所电气主接线图(含说明)
220kV I母220kV II母110kV套管CT:3(TMY-125X10)HY5WZ-17/45W110kV中性点设备:YH1.5W-72/186WLJW1-10W,400/1AGW13-63W/630LRB-110,200,400,600/1A,(两只)LRB-60,200,400,600/1A,(两只)LR-110,1200,1800,2400/1A,(一组)LRB-110,1200,1800,2400/1A,(两组)GW13-110W/630ALJW1-10W,200/1AYH1.5W-144/320W220kV中性点设备:110kV中性点套管CT:220kV中性点套管CT:2xLGJX-500/45YH10W-108/281WYH10W-204/532WLRB-220,800,1200,1600/1A,(两组)LR-220,800,1200,1600/1A,(一组)Uk1-2=14% Uk1-3=50% Uk2-3=35%220%%P8X1.5%/115/10.5kV#1主变压器容量比:180/180/90 接线组别:YN,Yno,dll220kV套管CT:SFSZ9-K-180000/2200.5/0.2S4000A,50kAGW16-220(W)2500A,50kAGW16-220D(W)断路器弹簧机构2x600/1A2500A,50kA5P30/5P30电流互感器GW7-220IID(W)5P30/5P30/5P30C备用一BA出线二BCLGJX-630/55A#1主变间隔C备用三变主2xLGJX-500/45YH10W-108/281WYH10W-204/532W#2主变压器#1同(预留)#3主变压器(预留)#4主变压器#3主变间隔#2主变间隔#4主变间隔备用四CBABALDRE-130/116LDRE-130/116变主#1同隔间母联2x(LGJX-630/55)5P30/5P30/5P305P30/5P30/0.52x1200/1A电流互感器弹簧机构4000A,50kA断路器GW16-220D(W)2500A,50kA氧化锌避雷器LGJX-400/352500A,50kAGW16-220D(W)YH10W-204/532WTYD-220/ 3-0.0075H电压互感器(三相)220/ 3:0.1/ 3:0.1/ 3:0.1/ 3:0.1一同出线出线一BCA5P30/5P30/5P300.5/0.2S4000A,50kAGW16-220(W)2500A,50kAGW16-220D(W)断路器弹簧机构2500A,50kA5P30/5P302x1200/1A电流互感器GW7-220IID(W)B、C相:OWF-220/ 3-0.005HA相:TYD-220/ 3-0.005HXZK-1600-1.0/40XZK-1600-0.5/402x(LGJX-400/35) I母母线设备II母母线设备设母同 I母线备SC11-400/11LGJX-300/40LDRE-130/116LDRE-130/1162000A,40kAGW4-126IID(W)GW16-126(W)GW16-126D(W)2000A,40kA5P30/0.5/0.2S5P30/5P30/5P302x400/1A电流互感器3150A,40kA弹簧机构TYD-110/ 3-0.01H断路器A相:ACBCBA出线二出线一#1主变一出同线一出同线一同出线TBB22-10-100205组/334M-2BLXGN2B-12(Z)XHDCB-500/11DKSC-500/11 500kVA,ZN#1接地变10kV I段 3(TMY-125X10)XGN2B-12(Z)XGN2B-12(Z)#1母设10回#1站用变XGN2B-12(Z)ABCBAC出线三出线四#2主变同一出同线变#1主CBA#3母设#4母设10kV IV段10kV III段#3接地变#4接地变母联 Ⅱ母母线设备 Ⅲ母母线设备110kV Ⅰ母110kV Ⅳ母110kV Ⅱ母110kV Ⅲ母分段10回TBB22-10-100205组/334M-2BLTBB22-10-80165组/334M-2BL Ⅳ母母线设备 Ⅰ母母线设备2000A,40kALGJX-240/30TYD-110/ 3-0.02HYH10W-108/281W0.1/ 3:0.1/ 3:0.1220/ 3:0.1/ 3:GW4-126D(W)设母同 I母线备2000A,40kAGW16-126D(W)断路器3150A,40kA5P30/0.5/0.2S5P30/5P302xLGJX-500/45弹簧机构2x600/1A电流互感器母联CBACBA出线五#3主变ABC出线六一同出线断路器2xLGJX-500/453150A,40kAGW4-126IID(W)2000A,40kA5P30/0.5/0.2S5P30/5P30/5P30弹簧机构2x600/1A电流互感器2000A,40kAGW16-126D(W)GW16-126(W)备用 CBA#4主变备用 CBA备用 CBA出线七CBA备用4回一同出线图中实线设备为本期建设部分,虚线设备为预留扩建部分。说 明:3(TMY-125X10)YH10W-108/281W10kV IIA段 3(TMY-125X10)线5回馈母同I#2A母设设母同#1#2接地变器同I母电容#2站用变变#1同接地变站同#1TBB22-10-100203组/334M-2BLTBB22-10-100202组/334M-2BL10kV IIB段 3(TMY-125X10)器同I母电容5P20/5P20/0.2S 15VA/15VA/15VA 3台ZN28-4000-50kA 1台GN30-10/4000A,40kA,1组LMZJ-10Q,4000/1/1/1 XGN2B-12(Z)GN30-10/4000A,1组LMZJ-10Q,4000/1/15P20/0.5,15VA/15VA 3台LZZBJ9-10Q,400~600~800/15P20/0.5/0.2S 15VA, 3台ZN28-1250-31.5kA 1台GN30-10D/1250A,31.5kA,1组GN30-10/1250A,31.5kA,1组HY5WZ-17/45 1组JN15-12,1组TY-LJK%%C160J,75/1A,5VA,1只LZZBJ9-10Q,800/1 ,5P20/0.5/0.2S 15VA 3台ZN28-1250-31.5kA 1台GN30-10D/1250A,31.5kA,1组GN30-10/1250A,31.5kA,1组HY5WZ-17/45 1组JN15-12,1组TY-LJK%%C160J,75/1A,5VA,1只XGN2B-12(Z)ZR-YJV22-8.7/15-1*400GN30-10D/1250A,31.5kA,1组10/√3:0.1/√3:0.1/√3:0.1kV0.2/0.5/3P 30/40/150VA HY5WZ-17/45 1组LZZBJ9-10Q,150/1 ,5P20பைடு நூலகம்0.5/0.2S 15VA 3台ZN28-1250-31.5kA 1台GN30-10D/1250A,31.5kA,1组GN30-10/1250A,31.5kA,1组HY5WZ-17/45 1组JN15-12,1组TY-LJK%%C160J,75/1A,5VA,1只XGN2B-12(Z)LZZBJ9-10Q,150/1 ,5P20/0.5/0.2S 15VA 3台ZN28-1250-31.5kA 1台GN30-10D/1250A,31.5kA,1组GN30-10/1250A,31.5kA,1组HY5WZ-17/45 1组JN15-12,1组TY-LJK%%C160J,75/1A,5VA,1只GN30-10/4000A,1组LMZJ-10Q,4000/1/1 15VA/15VA 3台5P20/0.5XGN2B-12(Z)GN30-10/4000A,1组LMZJ-10Q,4000/1/1 15VA/15VA 3台5P20/0.5XGN2B-12(Z)XGN2B-12(Z)ZN28-4000-50kAGN30-10/4000A, 1台50kA,1组ZR-YJV22-8.7/15-3*240ZR-YJV22-8.7/15-3*240XGN2B-12(Z)5P20/5P20/0.2S 15VA/15VA/15VA 3台ZN28-4000-50kA 1台GN30-10/4000A,40kA,1组LMZJ-10Q,4000/1/1/1 XGN2B-12(Z)GN30-10/4000A,1组LMZJ-10Q,4000/1/15P20/0.5,15VA/15VA 3台#2B母设设母同#1线5回馈母同IJW6-252W/630AJW6-252W/630A电流互感器2x600/1A5P30/5P305P30/0.5/0.2S断路器,弹簧机构3150A,40kAGW4-126D(W)2000A,40kAGW4-126D(W)2000A,40kA11%%P2X2.5%%%/0.4kV 400kVAUd=4%%%,D,yn11SC11-400/1111%%P2X2.5%%%/0.4kV 400kVAUd=4%%%,D,yn11设母同 I母线备设母同 I母线备母同 I母联C备用二BA2006.04.25例比APPROVED BY审 定AUDITED BY核 定设 计DESIGNED BYCHECKED BY校 核NO图 名图号TITLEPROJECT工程名施工时间TIME审 核AUDITED BY设计阶段220kV XX变电站 工程电气主接线图专业会签日期专业会签日期QQ:447255935Email:xingxinsucai@ TEL:星欣设计图库QQ:396271936

变电所电气主接线图、配电干线系统图

变电所电气主接线图、配电干线系统图
**EE1-10.51.1.1.51.59.14.KVT+--MQ+HL1YB1M2M1~380V 免维护阳光电池 220V 20AhFU1FU2VT+-YB2VT+-YB3-MQ+HL2降压装置绝缘检测仪5SX5-10/2PYJV-0.6/1-2*4微机综保装置电源5SX5-10/2PYJV-0.6/1-2*4控制回路电源5SX5-10/2PYJV-0.6/1-2*4信号回路电源FU3FU4%%p220V%%p220V注:选用小型一体化智能高频开关直流操作电源装置,型号ZGD33-20/220/10Y1;充电模块型号HD22010,微机监控模块型号PSM-A3;外形尺寸:800W*600D*2260H。QK交流电源输入充\P电\P模\P块充\P电\P模\P块直\P流\P电\P压\P采\P样直\P流\P电\P流\P采\P样直\P流\P电\P流\P采\P样直\P流\P电\P压\P采\P样直\P流\P电\P压\P采\P样控制电源WC(L1)WC(L3)信号电源WS(L3)WS(L1)QF4KA ~220VKA ~220V配电箱低压电源TI2QF5KA KA KA ~220V至接地检查继电器TI1WV(L1)~100VWV(L3)电压互感器至接地检查继电器接地检查继电器375KV 91113486WV(L1)至控制电源1210SA 14电压测量WV(L2)WV(L3)PVPVPVVVV电压小母线QF1uTV QF2vQF3wFTA11K21K11K21K1TA2熔断器控制电源电笛解除音响\P中间继电器FU2WS(L3) HA1KA1KA1KA1信号电源监视音响试验\P按钮HY1KA1HW1事\P\P故\P\P信\P\P号音响解除\P按钮FU1WS(L1) WFSSB1SB2(兼值班室)出线电缆桥架低压开关柜封闭式母线槽封闭式母线槽AA5AA2AA1AA3AA4

变电站电气主接线图

变电站电气主接线图

精心整理学习帮手精心整理学习帮手精心整理学习帮手精心整理学习帮手精心整理学习帮手精心整理学习帮手精心整理学习帮手精心整理学习帮手2×8MW(a)2×10MVA1G G1TG2G2T110KV 35KV2×8MW(b)20MVAG1G 2GG110KV2T2G(c)2×8MW2×10MVAG1G 1T G35KV精心整理 学习帮手TMY-100X8ZN21-10/1250配CD10ⅢLZZBJ-101000/5 0.5/10P 2×(ZR-YJV 22-6/3×240)RN2-6/0.5ASFWG8000-6/4950Ue=6.3kV Ie=916.45A COSφ=0.8LZX-10Q800/5 0.5/10PJ Y N 2-10-03(改)1G励磁变(厂家配套)励磁互感器(厂家配套)JDJ-6 36 0.1√3√J Y N 2-10-17J Y N 2-10-18RN2-6/0.5A 36 0.1 0.1JDZJ-63√√3J Y N 2-10-20√ 6 0.1 0.1√333JDZJ-6RN2-6/0.5AHY5WZ-10/302G同左ZN21-10/2500配CD10ⅢLFZJ-102000/5 0.5/0.5/10/10PJ Y N 2-10-03SF9-20000/110Y,d11121±3×2.5%/6.3kV U k %=10.5%LGJ-120GW4-110DW/630左接地LW25-1261250A,40kA GW4-110DW/630双接地LCWB 6-110100/50.2/0.5/10P/10PTYD-110/ -0.07H 3√LRD-60-B 50/5GW4-110DW/630双接地JDCF-110Y5W1-100/260√110 0.1 0.13√√33GW 13-60G/400Y1W-73/15ZN21-10/630配CD10ⅢLZZBJ-10100/5 0.5/10PJ Y N 2-10-03ZR-YJV 22-6/3×50SC9-800/6.3D,yn116.3±5%/0.4kV Ud%=7LMZ1-0.5 1200/5LMZ1-0.5 1200/5SC9-800/10D,yn1110±5%/0.4kV Ud%=7ZR-YJV 22-10/3×50LZZBJ-10100/5 0.5/10PZN21-10/630配CD10ⅢJ Y N 2-10-06(改)ZR-YJV 22-10/3×5010kV外来电源J Y N 2-10-19JDZJ-10HY5WZ-17/51RN2-10/0.5A10/0.1kV0.4kVLMY100×8-40×8DW15-1200DW15-1200DW15-12000.1LMY100×8-40×8G~G~TMY-100X8GW4-110DW/630左接地图5-19 某水电站电气主接线全图精心整理学习帮手精心整理 学习帮手图5-20 地区变电所接线8回35kV220kV4 回2×120MVA至无功补偿装置6 回2×60MVA4回2×10MVA1T图5-21 终端变电所接线4回10kV2T110kV 35kV第六章图形精心整理学习帮手精心整理学习帮手精心整理学习帮手精心整理 学习帮手VV22-13×50+1×251#厂变进线V 42L6-A,0~150A DT864-2,380/220V,3(6A)42L6-V,0~450V说明:BT95O9为事故照明切换板,其直流电源用VV22-1-2×4电缆引至直流屏。

变电站电气主接线图.

变电站电气主接线图.

2×8MW(a)2×10MVA1G G1TG2G2T110KV 35KV2×8MW(b)20MVAG1G 2GG110KV2T2G(c)2×8MW2×10MVAG1G 1T G35KV图5-18 例5-2方案接线图(a )方案5-2-1接线,(b)方案5-2-2接线,(c)方案5-2-3接线注:图5-19见:“主接线厂用电实例”图TMY-100X8ZN21-10/1250配CD10ⅢLZZBJ-101000/5 0.5/10P 2×(ZR-YJV 22-6/3×240)RN2-6/0.5ASFWG8000-6/4950Ue=6.3kV Ie=916.45A COSφ=0.8LZX-10Q800/5 0.5/10PJ Y N 2-10-03(改)1G励磁变(厂家配套)励磁互感器(厂家配套)JDJ-6 36 0.1√3√J Y N 2-10-17J Y N 2-10-18RN2-6/0.5A 36 0.1 0.1JDZJ-63√√3J Y N 2-10-20√ 6 0.1 0.1√333JDZJ-6RN2-6/0.5AHY5WZ-10/302G同左ZN21-10/2500配CD10ⅢLFZJ-102000/5 0.5/0.5/10/10PJ Y N 2-10-03SF9-20000/110Y,d11121±3×2.5%/6.3kV U k %=10.5%LGJ-120GW4-110DW/630左接地LW25-1261250A,40kA GW4-110DW/630双接地LCWB 6-110100/50.2/0.5/10P/10PTYD-110/ -0.07H 3√LRD-60-B 50/5GW4-110DW/630双接地JDCF-110Y5W1-100/260√110 0.1 0.13√√33GW 13-60G/400Y1W-73/15ZN21-10/630配CD10ⅢLZZBJ-10100/5 0.5/10PJ Y N 2-10-03ZR-YJV 22-6/3×50SC9-800/6.3D,yn116.3±5%/0.4kV Ud%=7LMZ1-0.5 1200/5LMZ1-0.5 1200/5SC9-800/10D,yn1110±5%/0.4kV Ud%=7ZR-YJV 22-10/3×50LZZBJ-10100/5 0.5/10PZN21-10/630配CD10ⅢJ Y N 2-10-06(改)ZR-YJV 22-10/3×5010kV外来电源J Y N 2-10-19JDZJ-10HY5WZ-17/51RN2-10/0.5A10/0.1kV0.4kVLMY100×8-40×8DW15-1200DW15-1200DW15-12000.1LMY100×8-40×8G~G~TMY-100X8GW4-110DW/630左接地图5-19 某水电站电气主接线全图图5-20 地区变电所接线8回35kV220kV4 回2×120MVA至无功补偿装置6 回2×60MVA4回2×10MVA1T图5-21 终端变电所接线4回10kV2T110kV 35kVVV22-13×50+1×251#厂变进线V 42L6-A,0~150A DT864-2,380/220V,3(6A)42L6-V,0~450V说明:BT95O9为事故照明切换板,其直流电源用VV22-1-2×4电缆引至直流屏。

热电厂工程电气主接线CAD图

热电厂工程电气主接线CAD图
电气主接线综合自动化保护、测量、计量配置图WUCA相电压BC相电压有功电度无功电度WhVARhUbcI-I频率HzUaA相电压ccaUUbB相电压C相电压有功功率A相电流VARaA无功功率abcUAC0SΦbAB相电流功率因素C相电流AB相电压50/550/5Ⅰ-4AH: KYN28-12-18Ⅰ-6AH: KYN28-12-02Ⅰ-5AH: KYN28-12-02/0.2/0.5300/5300/550/550/5Ⅲ-6AH: KYN28-12-02Ⅰ-3AH: KYN28-12-45Ⅲ-2AH: KYN28-12-02Ⅲ-4AH: KYN28-12-02Ⅰ-2AH: KYN28-12-0250/5200/5HY5WS3/0.2/0.550/5Ⅱ-2AH: KYN28-12-02Ⅱ-5AH: KYN28-12-02Ⅲ-8AH: KYN28-12-02Ⅱ-3AH: KYN28-12-45Ⅱ-4AH: KYN28-12-1850/5Ⅱ-6AH: KYN28-12-02HY5WS3SCB9-1250/10.510.5±2×2.5%/0.4KV准人人图计D/Yn11Uk=6%1250KVA 1#厂用变LZZBJ9-10XRNP-10-17/50TMY-40X4LXK-Φ120备用LZZBJ9-1031.5KA0.5/5P20800AJN15-12300/5Ⅱ-8AH: KYN28-12-0210KVⅡ段TMY-3(120X10)TMY-50X5ZN21-12800A31.5KATMY-50X5ZN21-122、 同期点为:发电机出口断路器、10kV母联断路器、110kV线路断路器、主变低压侧断路器、110kV母联断路器。共9点。1、 10kV高压开关柜的外形尺寸为:宽×深×高=1000×2000×2335mm。说 明0.4KVⅡ段(2#炉)0.4KV Ⅲ 段(Ⅲ#炉)负负批程工制专设业责责0.4KV

变电站电气主接线图 (2)

变电站电气主接线图 (2)

2×8MW(a)2×10MVA1G G1TG2G2T110KV 35KV2×8MW(b)20MVAG1G 2GG110KV2T2G(c)2×8MW2×10MVAG1G 1T G35KVTMY-100X8ZN21-10/1250配CD10ⅢLZZBJ-101000/5 0.5/10P 2×(ZR-YJV 22-6/3×240)RN2-6/0.5ASFWG8000-6/4950Ue=6.3kV Ie=916.45A COSφ=0.8LZX-10Q800/5 0.5/10PJ Y N 2-10-03(改)1G励磁变(厂家配套)励磁互感器(厂家配套)JDJ-6 36 0.1√3√J Y N 2-10-17J Y N 2-10-18RN2-6/0.5A 36 0.1 0.1JDZJ-63√√3J Y N 2-10-20√ 6 0.1 0.1√333JDZJ-6RN2-6/0.5AHY5WZ-10/302G同左ZN21-10/2500配CD10ⅢLFZJ-102000/5 0.5/0.5/10/10PJ Y N 2-10-03SF9-20000/110Y,d11121±3×2.5%/6.3kV U k %=10.5%LGJ-120GW4-110DW/630左接地LW25-1261250A,40kA GW4-110DW/630双接地LCWB 6-110100/50.2/0.5/10P/10PTYD-110/ -0.07H 3√LRD-60-B 50/5GW4-110DW/630双接地JDCF-110Y5W1-100/260√110 0.1 0.13√√33GW 13-60G/400Y1W-73/15ZN21-10/630配CD10ⅢLZZBJ-10100/5 0.5/10PJ Y N 2-10-03ZR-YJV 22-6/3×50SC9-800/6.3D,yn116.3±5%/0.4kV Ud%=7LMZ1-0.5 1200/5LMZ1-0.5 1200/5SC9-800/10D,yn1110±5%/0.4kV Ud%=7ZR-YJV 22-10/3×50LZZBJ-10100/5 0.5/10PZN21-10/630配CD10ⅢJ Y N 2-10-06(改)ZR-YJV 22-10/3×5010kV外来电源J Y N 2-10-19JDZJ-10HY5WZ-17/51RN2-10/0.5A10/0.1kV0.4kVLMY100×8-40×8DW15-1200DW15-1200DW15-12000.1LMY100×8-40×8G~G~TMY-100X8GW4-110DW/630左接地图5-19 某水电站电气主接线全图图5-20 地区变电所接线8回35kV220kV4 回2×120MVA至无功补偿装置6 回2×60MVA4回2×10MVA1T图5-21 终端变电所接线4回10kV2T110kV 35kV第六章图形VV22-13×50+1×251#厂变进线V 42L6-A,0~150A DT864-2,380/220V,3(6A)42L6-V,0~450V说明:BT95O9为事故照明切换板,其直流电源用VV22-1-2×4电缆引至直流屏。

35kV线变组电气主接线图01

35kV线变组电气主接线图01
35kV进线
1I1
氧化铸避雷器 HY5WZ-51/134J ill级防百 配在线监测仪
35kV电磁式电压互感器〈 两台)
A ‘ B相
m JDZB-35 , 级防污
35/0.22kV容量300\J
bHA
G\,/5-35D/630 E级im

B� C相
配手动操作机构

35kV柱上智能真空断路器 Z\,/32-40.5
氧化铮避雷器 YSWS-17/50J ill级防污
lOkV出线
圃’7陕饵’-10/刷 E甸回i.7/1’副a 撞撞’!GI町i 10.町
小嚣嚣电血阻,0. . 5-甜llt-10 - L1I"Z1-0t.2l0lOJJ1剧/1A
说明: 1、35kV台架变包含:主变压器1台,容量:6300kV及以下J
35/10kV;35kV 、 10kV出线各1 回. 2、台架变电气主接线如本图.
XXXX川 XXXXXXXXXXXXXXX有限川 公司
川一
-H
一川
-u
一叫
XX供电局35千伏配电站
工程|方案::
电气主接线图
回号
附固01
630A 内置CT:[ J/1A10P2Fra bibliotek 20(10)VA
35kVJ容量6300kVA及以下 三相两卷有载调压变压器 〈优先利用闲置物资〉
10kV柱上智能真空断路4 Z\,/32-12
630A 内置CT:[ J/1A 10P10 5-10-15VA 外置1台三相五柱式电压互感器 10/ J3 : 0.38/ J3 输出电压380V (容晕。( VA) )220V (容量300VA) 隔离开关G\,/1-lOD/630 10kV 630A 20kA ffl级防污
相关主题
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
户外配电装置的架构采用钢筋混凝土结构。母线架 构为门型。
110KV侧母线为LGJ-150,馈线侧为2×LGJ-185,采 用悬式绝缘子悬挂在门型架构上。
隔离开关、互感器、避雷器等安装在2.5米高的钢筋 混凝土支柱上。SF6断路器采用混凝土基础,用矩 形钢管支架固定在基础锚栓上引入所内。设事故油池。中性点设隔离开关、流互、 避雷器安装在混凝土支柱上。
长度大于7米的高压室配电装置应有两个出口。 二楼的配电装置(如电容室)其中一个出口 通向楼梯平台。配电装置室的门向外开,并 装弹簧锁。
6、牵引变电所户外配电装置的结构 与配制原则
根据电气设备和母线布置的高度,户外配电装置一 般有低型、中型、高型三种类型。徐连线牵引变电 所户外设备采用中型布置。即所有电气设备安装在 较低基础和支架上,处在同一平面内。母线采用软 母线用悬式绝缘子悬挂在较高水平面的门型架构上。
5、牵引变电所户内配电装置的结构 与配制原则
27.5Kv主接线中的同一支路的电气设备布置在同一 间隔内。单元间隔采用网栅和钢板制成的小间。间 隔上设置有单元门和断路器配电箱。
单元间隔可单列或双列靠墙布置,双类布置时电源 类间隔如27.5Kv进线、27.5Kv压互(避雷器)、 27.5Kv隔离开关、补偿电容组断路器等放置在一侧, 负荷类间隔如27.5Kv馈线间隔等放置在另一侧,以 方便运行和维护。
配电装置的结构及其中电气设备的布置、安 装状况通常采用平面布置图、配置图和断面 图来表示。
2、平面布置图
平面布置图按比例画出,用以反映配电装置的结构 尺寸、设备内容及电气设备的连接关系,布置状况 等。
以邳州变电所举例说明: 高压侧高压电气设备采用室外中型布置;27.5Kv侧
馈线侧避雷器采用户外布置,其余高压设备均采用 户内布置。设高压室、电容器室及主控室;所内设 独立避雷针,作为直击雷防护;设变压器事故油池; 所区周围设2.7米高的实体围墙。平面布置预留了高 次谐波装置用场地。 牵引变电所生产房屋与辅助房屋合建,二层楼房布 置,一层27.5Kv设高压室、检修室、主控室及值守 房屋、通信机械室等房屋,二层设电容器室、材料 室等。
电气主接线图
电气主接线一般应满足下列要求: (1)保证对牵引负荷和地区负荷供电的可靠性,并力求经
济性。 牵引负荷是国家电力系统的Ⅰ级负荷,它应有独立的双回路
电源供电。独立的双回路电源是指互不影响的两回110(或 220)Kv线路,即:两回110Kv电源线路来自不同的电源点; 来自同一电源点的不同分段母线上。 (2)主接线应简单、清晰、操作方便。 由于接触网事故比较多,检修频繁,牵引变电所的停、送电 操作、倒闸作业较多,故主接线设计的简单清晰,可减少操 作程序,避免误操作。 (3)主接线应运行灵活,检修、维护安全方便。 主接线的任何一个元件检修检修、试验时应很容易退出运行, 并且不影响其他元件的正常工作。 (4)主接线应具有将来发展的可能性。即应考虑远景规划 中增加设备的可能性。 总之,电气主接线应在电路转化、设备检修和事故处理 等情况下,保证向牵引负荷经济、安全、可靠的供电。
直流自用电:所内操作电压为直流110V。设带监控装置的免 维护铅酸蓄电池直流电源成套装置。容量为150Ah。
二、平面布置图
1、高压配电装置
按主接线图,由开关设备、保护电器、测量 电器、母线和必要的辅助设备、辅助电工建 筑物组成的用以接受和分配电能的装置称为 高压配电装置。牵引变电所配电装置一般分 为室内配电装置和室外配电装置。
配置原则:主接线中每一支路的电气设备组成一个 单元间隔,即由电源进线间隔、变压器间隔、互感 器间隔、断路器间隔等组成。配电装置的纵向距离 与母线的套数、架构的形式大牛股因素有关。电气 设备布置应整齐有规律,进出线避免交叉,维修、 运输设备安全方便。
以邳州变电所为例说明: 110Kv电源引入线纵向引入。
2、邳州牵引变电所电气主接线举例
(1)引入两路110Kv电源,进线电源设置设有隔离 开关1001、1002分段的跨条。
设置两台三相平衡牵引变压器,一台运行,一台固 定备用,并设置备用电源自投装置。计费采用高压 侧计费方式。
(2)27 .5Kv侧采用单母线隔离开关分段接线形式。 馈线断路器采用固定备用方式。
(3)为改善牵引供电系统的功率因数并吸收部分 高次谐波,两相母线设置并联电容补偿装置。
(4)110Kv进线采用“H”型架构。
(5)继电保护及自动化装置:按远动化设计,有人值守, 无人值班。采用了带安全监控的综合自动化系统。
牵引变压器设重瓦斯、纵差动、低电压启动过电流保护,动 作于跳闸;设轻瓦斯、过负荷、过热法预告信号。
高压室内27.5Kv硬母线分相布置,采用支持绝缘子 垂直或水平固定在墙上。并涂漆以分别相别,A相 为黄色,B相为绿色,中性为黑色。
电缆沟设在操作走廊地下,控制电缆经电缆 沟与每个单元间隔的电气设备和主控制室相 连。电缆沟用钢盖板覆盖,并铺设绝缘胶片 防护。
电容器组可采用高层结构组装,以减小占地 面积。周围设金属网栅防护。
3、配置图
户内配电装置通常采用配置图来分析配电装 置的布置方案和统计所用的主要电气设备。 即把进出线、断路器、避雷器、变压器等电 气设备合理分配于各配电间隔中,并标出母 线和电气设备在各间隔中的轮廓合和连接关 系。它不要求按比例绘制,这种表示布置关 系的示意图叫做配置图。
4、断面图
断面图用来表示配电装置中所取断面里(如 某配电间隔断面)的设备内容、连接关系和 结构尺寸。按比例绘制,断面图和平面布置 图结合,能够反映整个配电装置的结构尺寸, 便于施工。如照片所示。
馈线设两段距离、一次重合闸、过流速段、高阻保护动作于 跳闸。
并联电容补偿装置设差电压、差电流、过电流、谐波过电流、 失压、过电压保护。
电源进线设备用电源自投装置,主变压器设自投装置。
(6)自用电系统:
交流自用电:变电所设两台三相所用变压器,一台引自本所 27.5母线,另一台引自铁路10Kv电力贯通线。所用变容量为 80KVA。
相关文档
最新文档