12351020307multiple of rated current123510203018multiple of rated currentKSpace foriden t i fi c a t ion markerTripping leverTrip in d i c a t orOperatorOperatingmechanismElectro-magnetic pro t ec t ionThermal protection-bimetal Upper terminalFixed contactMoving contactLower terminalDIN rail holderArc chamberUL 1077CSA C22.2 No. 235VDE 0641IEC-898Cable protectionBDelivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryCUL 1077 CSA C22.2 - NO. 235VDE 0641 IEC-898Cable & equipment protectionS261-C1NA, 1P+NDelivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryDUL 1077 CSA C22.2VDE 0641 IEC-898Cable & equipment protectionS263-D63, 3 poleDelivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryK UL 1077CSA C22.2 - NO. 235VDE 0641IEC-898Cable & equipment protectionDelivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for delivery1 KS is for standard U.S. size.UL 1077 CSA C22.2 - NO. 235VDE 0660Cable & equipment protectionDelivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryUL 1077 CSA C22.2 - NO. 235VDE 0660Cable & equipment protection➀ For use with ring tongue or cable terminals only. Cannot be used with busbar system.2 No charge when ordered with the S280(W).Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryUL 1077 VDE 0660CSA 22.2 No. 235Cable and Equip m ent Protection Direct current applicationsThe S280UC differs from standard miniature circuit breakers in that the UC versions include a permanent magnet which aids in the extinguishing of the arc during medium and high level faults. It is necessary toobserve the correct polarity and current direction when connecting the UC breakers. Two examples of correct connection are shown below.Termination points are marked on all UC type MCBs, points one (1) and four (4) are negative and points two(2) and three (3) are positive. Four pole breakers are also available for voltage reversal applications.Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryLow Voltage Products & Systems14.13 Z UL 1077VDE 0660CSA 22.2No. 235Fast trip characteristicS281-Z16, 1 poleS282-Z32, 2 poleS283-Z32, 3 poleDiscount schedule CB7multiple of rated current multiple of rated current14.14 Low Voltage Products & SystemsVDE 0660Cable and equipment protectionDiscount schedule CB9480 VACDelivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryLow Voltage Products & Systems 14.151PhaseDiscount schedule CB8For use on load side (bottom) of S260, S270, S280 and line side (top) of S280 MCBs.Insulated busbar assembly contains 2 separate circuits for use with 1, 1+N or 2 pole MCBs.For use on load side (bottom) of S260, S270, S280 and line side (top) of S280 MCBs.Insulated busbar assembly contains 3 separate circuits for use with 1 or 3 pole MCBs.For use on load side (bottom) of S260, S270, S280 and line side (top) of S280 MCBs.Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryInsulated busbar assembly contains 4 separate circuits for use with 3+N1 or 4 pole MCBs.For use on load side (bottom) of S260, S270, S280 and line side (top) of S280 MCBs.14.16 Low Voltage Products & SystemsPhase with 1auxiliaryDiscount schedule CB8MCBs.(bottom) of S260, S270, S280 and line side (top) of S280 MCBs.Insulated busbar assembly contains 3 separate circuits for use with 1 or 3 pole MCBs. For use on load side (bottom) of S260, S270, S280 and line side (top) of S280 MCBs.(bottom) of S260, S270, S280 and line side (top) of S280 MCBs.Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryLow Voltage Products & Systems 14.17PhaseMCB Busbar accessoriesDiscount schedule CB8For use on line side (top) of S260 and S270 MCBs.Insulated busbar assembly contains 4 separate circuits for use with 1+N or 2 pole MCBs.For use on load side (bottom) of S260, S270, S280 and line side (top) of S280 MCBs.Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryInsulated busbar assembly contains 1 circuit for use with 1 pole MCBs.For use on line side (top) of S260 and S270 MCBs.NOTEALL BUSBARS MAY BE CENTER FED IN OR-DER TO DOUBLE THE AMPACITY RATING14.18 Low Voltage Products & SystemsFactory mountingAll accessories can be easily mounted in the fi eld. For factory mounting of any accessory devices, add $30 list to total price per breaker. To create complete catalog number, take suf fi x of accessory device following “S2-” and add suf fi x to end of breaker part number. Multiple suf fi xes must be added in alphabetical order.Example: S272-K20A1 $ 264 (2 pole, 20A breaker with type A1 shunt trip) S272-K20 @ $96 + A1@ $138 + factory mounting @ $30 = $264 S272-K20A2H11 $ 300 (2 pole, 20A breaker with type A2 shunt trip and H11 aux. contacts) S272-K20 @ $96 + A2 @ $138 + H11 @ $36 + factory mounting @ $30 = $300Auxiliary contacts and shunt trips may be mounted in combination.Discount schedule CB8NOTE: Above accesssories are for use with types S260, S270 and S280 breakers only.Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryLow Voltage Products & Systems 14.19SA1SA2MB-3PDMB-CLS500-ME2Discount schedule CB8Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for delivery14.20 Low Voltage Products & SystemsDiscount schedule CB8Low Voltage Products & Systems 14.21MountingUniversal mounting position using snap-on mounting to standard 35x7.5mm DIN rail.Miniature circuit breakers (MCBs) can also be mount e d to front of door using a panel cut-out with breaker handle pro t rud i ng through panel opening for external operation. Special front mount i ng kit type ME is avail a ble (see page 2.12).ConnectionTerminals are suitable for solid or fl exible conductors from 18 to 4 AWG (0.75 to 25mm 2) with no busbar connected. When max i m um busbar size of 36 mm 2 is used, maximum cable is 6 AWG (16 mm 2).Maximum tightening torque of 17.5 in-lb (2 Nm) for line/load terminals and 4.5 in-lb (0.5Nm) for ac c es s o r y device terminals.OperationMCBs are switched on by moving the handle to the upper po s i t ion. Stamped onto the handle switch, a “I” is visible con fi rming that the breaker is closed.The MCBs are “trip-free,” if the handle is being forced to the “ON” position, the breaker will still trip under fault conditions.The “O” marking indicates that the breaker is in the “OFF” position. The MCB is now open and the load is disconnected from line power.When a breaker has tripped, the MCB handle should fi rst be set to the full “OFF” position to make certain the trip mechanism has been reset. Once the fault has been determined and cleared the MCB can again be switched “ON”.MaintenanceABB miniature circuit breakers require no specialmaintenance; only normal electrical system maintenance pro c e d ures are required.Possible mounting arrangements of MCB accessoriesAuxiliary switch/bell alarmneutral disconnect Shunt trip and/or undervoltage releaseShunt trip or undervoltage release mounted with auxiliary switch14.22 Low Voltage Products & SystemsLower terminals can be bussed together with single phase or multi-phase busbars as shown. Upper ter m i n als can also be busbar con n ect e d.Dual function terminals provided in open position for connection to busbars. Pressing on screw head opens box terminal for cable insertion. Only the lower terminal is dual func t ion.Terminals allow for con n ec t ion of cable 18-4AWG. Conductors of different sizes may also be used in same terminal.Up to fi ve conductors, 16 AWG each, can be safely connected per terminal.Lower terminal can also be bussed with solidround con d uc t or.Cables can be connected to box terminals inaddition to busbar con n ec t ions on lower, dual function terminals.Thermal tripping is independent of frequency.1 Available for purchase. See page 14.19.Infl uence of frequency on electro-magnetic tripsMagnetic trip values shown on trip curves are valid for 50/60Hz ap p li c a t ions. For frequencies other than 50/60Hz, the mag n et i c (in s tan t a n eous) trip values are increased by the factor given below:16 2/3 - 60Hz100Hz 200Hz 400Hz DC Approx. factor 1 1.1 1.2 1.5 1.5Thermal tripping is independent of frequency.S260-BS280-KS270-KLet-through values I 2tFor other curves, please contact ABB Control.Version I 2t I PeakS260B TD9980 — S260C TD9981 — S260D TD9982 —S270K TD9972 TD9950 S280K TD9978 — S280Z TD9979 — S290C TD9985 —Version Amps Time-current tripS260B 6- 63 TD9725 S270K 0.5- 8 TD9705 10- 40 TD9706 50- 63 TD9707 S280K 0.2- 8 TD9708 10- 40 TD9709 50- 63 TD9710 S280Z 0.5- 63 TD9711DescriptionAll ABB miniature circuit breakers substantially reduce the maximum let-through current from the peak avail a ble short circuit current.I K - RMS current of fault I D - Max let-through of MCB V n - System voltage V B - Arc voltage of MCB t k - Breaking time of MCBType B, C, D Type K, ZCurrent carrying capacity of type “B”, “C”, “D”, “K” and “Z” thermal trip characteristics as a function of ambient tem p er a t ure.Terminal markingsInput optional from top or bottom.Miniature circuit breaker resistance valuesAmpacities for AWG wire are based on copper cable rated 75° C, except for 16AWG which is based on 60° C wire. Taken from UL508 Table 52.2.Consult applicable standards for futher detail and information. Comparison of IEC and AWG wire sizesS280S260 & S270 S290MB-CLFront mounting clipMB-3PDRHS2-MHandle mechanismAccessories12644126461265012652Many older styles of ABB miniature circuit breakers have been replaced by new and improved versions. Many of these newer styles can be directly interchanged, both electrically and physically, with the older version. There are also many international styles of ABB circuit breakers which are not normal stock items and may be inter-changed with stocked ABB versions.Note: MCB types S260/270 and S280 can be raised to the same height as older style S210 series MCBs through the use of a height adjuster (SZ-ES68/83; $ 30 list per 20). The height adjustor snaps onto the DIN rail and raises the height of com p o n ents 68mm to match that of the S210 series (83mm).S281U-K1S281UX-K1 S282UX-K10S283UX-K2014S281UX-K25LISTED10,00010001001010.10.01Current in multiples of breaker ampere rating1.02345681014.520301.0 1.35T i m e i n s e c o n d sTime –Current trip curveThermal release threshold:1.0-1.35X Magnetic release threshold:8-14.5X Ambient calibration temperature:25°CApproval UL489 UL File No. E212323 CE Marked Voltage240 VAC 1, 2, and 3 poleCurrent ratings (A) 0.2, 0.3, 0.5, 0.75, 1, 1.6, 2, 3, 4, 5, 6, 8,10, 13, 15, 16, 20, 25, 30, 32, 40, 50, 60, 63Interrupting capacity (A) 0.2 - 25A: 14kA @ 240VAC, 1, 2, and 3 pole 30 - 63A: 10kA @ 240VAC, 1, 2, and 3 pole Frequency 50/60 HzTerminals Dual function, up to (2) stripped wires plus fork style crimp terminals.Ring tongue terminal compatible Terminal range (1) 18 - 4 AWG or (2) 18 - 8 AWG (copper wire only) or (1) 18 - 4 AWG + (1) 18 - 14 AWGSolid or stranded wire, or mixedTerminal torque 18 lb.in., combination fl at blade /No. 2 posi-drive screw Service life 20,000 operations at rated loadHACR rating Heating, Air-Conditioning, and Refrigerationrating (marked on front of breaker)Ambient temperature 25° CThermal release (A) 1.0 - 1.35 x MCB amperage rating Magnetic release8 - 14.5 x MCB amperage ratingOperational temperature -25° to +55° C rangeScale 1:1141.0526.72.1053.43.1580.12.5464.51.77451.9950.5DINRAIL3.00763.54900.6917.5S281U-K_S281UX-K_S282UX-K_S283UX-K_UL 1077 CSA C22.2VDE 0641 IEC 947-2UL 1077 CSA C22.2VDE 0641 IEC 947-2Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryUL 1077 CSA C22.2VDE 0641 IEC 947-1S502-D13Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryUL 1077 CSA C22.2VDE 0641 IEC-898UL 1077 CSA C22.2VDE 0660Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryS502UC-K0.15UL 1077 CSA C22.2VDE 0660Factory mount only Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryBusbarsS500-RD3 Handle mechanism S5001 For use on 3p/3w systems, add jumper between 4 and 8N for operation of test button.Delivery ClassA - Standard item, stock to 2 weeks lead timeB - Stock to 4 weeks lead timeC - 6 to 8 week lead timeD - 10 to 12 week lead timeE - Call for deliveryApproximate dimensionsWiring diagram。

ABB-MNS低压柜服务手册

ABB-MNS低压柜服务手册

由下列事件而导致的一切后果,ABB将不承担任何责任:■不遵守安全及操作规程的行为■ 非专业人员进行不适当的维修■ 任何不经意的运输损坏■ 不当的使用■ 未得到专业人员的授权下修改低压开关柜系统技术保留■ 本样本所涉及的可拆卸式、导轨式技术不适用于中国市场■ 本样本的数据和图片将根据技术发展的要求进行修改目录1 技术说明 41.1 技术数据 41.2 结构设计 51.3 母线系统 51.4 标准模数的组件 142 包装与运输 192.1 概述 192.2 包装 192.3 开关柜各部件的处理 212.4 现场的卸车和运输 212.5 中间存储 232.6 备用抽屉的存储 232.7 到货后检验 232.8 装配要求 232.9 拆除运输外包装 233 安装与调试 243.1 安装 243.2 开关柜的固定 273.3 电缆的连接 283.4 保护导体的连接 333.5 中性排的连接 333.6 特殊信息 343.7 最终准备 343.8 检查 343.9 试车 354 使用操作 354.1 电气设备 354.2 固定式方法 354.3 插入、隔离、导轨式方法 354.4 SR型熔断器开关 384.5 8E/4和8E/2抽屉单元 384.6 4E到48E的抽屉单元 394.7 特别提醒 415 维护与保养 415.1 概述 415.2 插拔式、可拆卸式和导轨式技术 435.3 抽出式技术 455.4 更换和改变抽出式抽屉组件 455.5 设备检查时检查MNS的触头情况 475.6 接触部分的润滑 485.7 润滑抽出式抽屉互锁机构 495.8 安装一次插 495.9 油漆损伤 505.10 机械损伤 505.11 螺栓连接的扭力 505.12 无功功率补偿系统的试车与维护 515.13 测量绝缘电阻 525.14 维护间隔 5441.1 技术数据标准通过型式试验(TTA)的组装式开关柜*IEC 60439-1, CEI 60439-1,DIN EN 60439-1, VDE 0660 第500部分,BS 5486, UTE 63-412试验报告 ASTA英国(按IEC 61641及抗故障电弧试验IEC 60298, 附录AA)DRL德国宇航研究所,核电站震动安全测试振动和冲击试验符合德意志劳埃德 汉堡电气数据额定电压额定绝缘电压U i1000 V 3~, 1500 V- **额定电压Ue690 V 3~, 750 V-**额定脉冲耐压Uimp 6 / 8 / 12 kV **过电压等级II / III / IV **污染等级3额定频率至60 Hz额定电流主母线:额定电流Ie至6300 A额定峰值耐受电流Ipk至250 kA额定短时耐受电流Icw至100 kA配电母线:额定电流Ie至2000 A额定峰值耐受电流Ipk至176 kA额定短时耐受电流Icw至100 kA结构特性尺寸柜体和支件构件DIN 41488推荐高度2200 mm推荐宽度400, 600, 800, 1000, 1200 mm推荐深度600, 800, 1000, 1200 mm模数 E = 25mm 根据IEC43660表面保护/颜色框架覆铝锌板内部小室分隔覆铝锌板内部覆盖层覆铝锌板覆外部覆盖层 铝锌板和亮灰色电漆,RAL7035 防护等级按IEC 60529或者VDE 0470第1部分IP 00至IP 54塑料零件无卤素、自熄、无CFC、阻燃IEC 60707, DIN VDE 0304第三部分内部小室分隔装置小室-装置小室母线小室-电缆小室母线小室-装置小室装置小室-电缆小室小室底板附加说明涂料外壳定制颜色 (标准: RAL 7035)母线系统母线绝缘,镀银,镀锡特殊要求 试验报告见上述的试验报告 *TTA定义:不存在可能会影响性能的差异。

ABB断路器参数调试讲义全

ABB断路器参数调试讲义全

ABB 断路器参数调试讲义电控柜的断路器进行设置,在ABB 塑壳断路器(正面)下方有两个旋钮(见下图),通过调节旋钮的位置可以设置断路器的过流、过载保护值,具体设置方法如下:一、ABB 塑壳断路器过流、过载旋钮设置说明:1、过流调节旋钮,设置电控箱整个负载的过流保护值,调节范围从2000A —4000A ,从MIN —MED —MAX 共有9个档位,档位对应值如下: MIN (1)档—2000A; (2)档—2250A; (3)档—2500A; (4)档—2750A;MED (5)档—3000A; (6)档—3250A; (7)档—3500A; (8)档过流调节旋钮过载调节旋钮—3750A;MAX(9)档—4000A;2、过载调节旋钮,设置电控箱整个负载的过载保护值,调节范围从280A—400A,从MIN—MED—MAX共有9个档位,档位对应值如下:MIN(1)档—280A; (2)档—295A; (3)档—310A; (4)档—325A;MED(5)档—340A; (6)档—355A; (7)档—370A; (8)档—385A;MAX(9)档—400A;二、ABB断路器机型设置说明EBZ318H 380 200 349.5 400A 9档3档三ABB断路器低压断路器的参数详解3.1、空气断路器的框架电流Iu、额定电流Ie、额定电流整定值Ir的含义是什么?•框架电流Iu:又称为额定不间断电流。

指在规定条件下,电器在长期工作制下,各部件的温升不超过规定极限值时所承受的电流值。

•额定工作电流Ie:指在规定条件下,能保证电器正常工作的电流值。

它和额定电压、电网频率、额定工作制、使用类别、触头寿命及防护等级等因素有关。

有时被标识为In。

•额定电流整定值Ir:这是使用者通过断路器的脱扣器自行整定的一个电流值,断路器根据使用者整定的Ir对电路进行过载、短路保护。

•比如ABB的塑壳断路器S5N400 R320 PR112/LI FF 3P ,Iu=400A Ie=320A, Ir=( 0.4 – 1)Ie 可调。

ABB低压断路器用户手册

ABB低压断路器用户手册

13.4 用户界面序号说明1 LED预报警指示2 LED报警指示3 背景灯图表显示4 光标向上移动按钮5 光标向下移动按钮6 通过一个外部装置(PR030/B供电单元、BT030无线连接单元以及PR010/T单元)来连接或测试脱扣器的测试连接器7 输入数据确认键或页面切换 8 退出次级菜单或取消操作键(ESC)9 额定电流插件 10 保护脱扣器的系列编码11 “i test”按钮当有一个辅助供电或有最小母排电流或PR120/V供电时,LCD图像显示器即可显示,请参见13.2.2.1。

你可在“setting”菜单上通过特别的按钮调整显示器对比度(参见13.5.4.1)。

13.4.1按钮使用通过↑和↓键可进行选择,通过键进行确认。

进入你想进的界面后,你可使用↑和↓键从一个值移到另一个值。

如果想改变一个值,固定光标在那个值上(可改变的区域将由黑变白),然后使用键。

为了确定先前配置的参数,请按ESC一次,这样将完成一个检查和显示参数配置界面。

如果想回主页,请按ESC两次。

“i test”按钮必须在自供电模式下执行脱扣测试,这样就能看到相关信息和断路器分闸48小时内的最后一次脱扣。

13.4.2 阅读和编辑模式在“read”模式(仅仅读取数据)或“edit”模式(可设置参数),菜单显示所有可得到的界面和通过键盘可移动。

在任何界面,根据脱扣器的状态具有2种功能:1“read”功能,120s后将自动显示其默认界面2“edit”功能,120s后将自动显示其默认界面状态决定功能:“read”测量和历史数据的查看脱扣器单元配置查看保护参数配置查看“edit”“read”模式下的任何事情脱扣器单元配置保护参数配置脱扣器单元测试功能在可编辑的界面按键可进入“edit”模式,当然需要输入密码。

键盘使用方法如下:键盘功能界面间移动,菜单间移动,改变参数值结束设置阶段和确认结果,选择菜单从默认界面进入菜单,可回前一个界面和回到默认界面,退出参数设置阶段和取消变化在自供电模式,断路器分闸48小时内可激活显示器。

低压断路器操作方法

低压断路器操作方法

低压断路器操作方法
低压断路器是一种电气保护设备,用于在电气系统发生过流、短路等故障时切断电路,保护设备和人员的安全。

下面是低压断路器的操作方法:
1. 确保断路器处于开启状态:当断路器的刀叉手柄平行于断路器本体时,表示断路器处于开启状态。

如果断路器处于关闭状态,应将刀叉手柄旋转至垂直方向。

2. 确保断路器相关的电源已关闭:在操作断路器之前,应先关闭与断路器相关的电源开关,确保电路中没有电流流经。

3. 选择合适的操作位置:根据电路系统的需要,选择合适的位置选择断路器的关闭操作位置。

有些断路器的刀叉手柄具有不同的位置用于不同的操作。

4. 关闭断路器:将刀叉手柄从开启位置旋转至关闭位置,使其垂直于断路器本体,表示断路器已关闭。

5. 打开断路器:如果需要打开断路器,应先确保与断路器相关的电源已关闭。

然后将刀叉手柄从关闭位置旋转至开启位置,使其与断路器本体平行,表示断路器已打开。

请注意,在操作断路器时,应严格按照操作规程和安全要求进行,以确保操作的安全性。

ABB低压开关说明书

ABB低压开关说明书

]`_\^ t25647.6/32v-27-0etu+cikiceeh geejdejy{ffgdy u|ty{ffgdy u|try{ffgdyo u|ty{ffgdyo u|tr |lnp p1-8Z E v e3:b ?-0000000000000000000000000000000000000000000000000000000000000000000RR303_u 000000000000000000000000000000000000000000000000000000000000000004V .[80000000000000000000000000000000000000000000000000000000000000000005B n c M|Es;0000000000000000000000000000000000000000000000000000000000RR503B n c 000000000000000000000000000000000000000000000000000000000000000RR504|Es;00000000000000000000000000000000000000000000000000000000000006N >S W 000000000000000000000000000000000000000000000000000000000000000000RR603xk 00000000000000000000000000000000000000000000000000000000000000000RR604z ~GX 0000000000000000000000000000000000000000000000000000000000000RRR 60403S ;Y 000000000000000000000000000000000000000000000000000000000000xxx 60404~I Y u ;Y 0000000000000000000000000000000000000000000000000000000RR605H\[*0000000000000000000000000000000000000000000000000000000000000RR606=11=n00000000000000000000000000000000000000000000000000000000000RRR 60603x E Y 3d k ?A >q 000000000000000000000000000000000000000000000000xxx 60604x E Y 3d k ?A >9000000000000000000000000000000000000000000000000xxx60605x >9<X 000000000000000000000000000000000000000000000000000000000R607HZxQ 0000000000000000000000000000000000000000000000000000000000000R608Z E9y 0000000000000000000000000000000000000000000000000000000000000RRR 60803xM ^U 0000000000000000000000000000000000000000000000000000000000xxx 60804xT ^U 00000000000000000000000000000000000000000000000000000000000xxx 60805xK ^U 00000000000000000000000000000000000000000000000000000000000xxx 60806xI ^U 0000000000000000000000000000000000000000000000000000000000xxx 60807x ,r N Q ?K V 000000000000000000000000000000000000000000000000000xxx 60808x ^U L r B t /n ^U PU 0000000000000000000000000000000000000000000xxx 60809x +|Y A :C L 000000000000000000000000000000000000000000000000000xxx 6080:x \K c x ^U Kgkpq 000000000000000000000000000000000000000000000000R6094[9y 000000000000000000000000000000000000000000000000000000000000RRR 60903x 1F 0*00000000000000000000000000000000000000000000000000000000xxx 60904x 9q i k 00000000000000000000000000000000000000000000000000000000R60:h j9y 000000000000000000000000000000000000000000000000000000000000RRR 60:03x Y u }m 00000000000000000000000000000000000000000000000000000000R60;WN 9y 000000000000000000000000000000000000000000000000000000000000RRR 60;03x r /Xc 00000000000000000000000000000000000000000000000000000000RRR 60;04x d [+N T ;C 000000000000000000000000000000000000000000000000000R6032|E 9y 00000000000000000000000000000000000000000000000000000000000RRR 603203xL731m3<X z \000000000000000000000000000000000000000000000000RRR 603204x S ]{}0000000000000000000000000000000000000000000000000000000RRR 603205x S }00000000000000000000000000000000000000000000000000000000000603206x U N }700000000000000000000000000000000000000000000000000000000v mI55555566666777777789::;;;3232323233333333333434343435R 6033b GXr 00000000000000000000000000000000000000000000000000000000000RRR 603303x Q .R /i 000000000000000000000000000000000000000000000000000000RRR 603304x y `L i l 9100000000000000000000000000000000000000000000000000RR6034u 03o 0000000000000000000000000000000000000000000000000000000000075b 0000000000000000000000000000000000000000000000000000000000000000R703hV 00000000000000000000000000000000000000000000000000000000000R704h <00000000000000000000000000000000000000000000000000000000000R705m 63{00000000000000000000000000000000000000000000000000000000R706qo=e 000000000000000000000000000000000000000000000000000000008g y c qn w 000000000000000000000000000000000000000000000000000000000R803ev 00000000000000000000000000000000000000000000000000000000000RR804f @8200000000000000000000000000000000000000000000000000000000R 80403g c z @8.00000000000000000000000000000000000000000000000000R 80404^U:Cz @00000000000000000000000000000000000000000000000000R805W A 00000000000000000000000000000000000000000000000000000000000RR 80503W 6?K 000000000000000000000000000000000000000000000000000000RR 80504Y U ?K 000000000000000000000000000000000000000000000000000009j R;l z o 00000000000000000000000000000000000000000000000000000000:[4B t MWN 000000000000000000000000000000000000000000000000000000RR:03;l r e 0000000000000000000000000000000000000000000000000000000;1T 0000000000000000000000000000000000000000000000000000000000000000R;03<==H<>@FG2321I w C h <v e 000000000000000000000000000000000000R;04<==H<>@FG2421C W A v e 0000000000000000000000000000000000000000R;05<==H<>@FG3421=zl 1T 0000000000000000000000000000000000000000R;06<==?>46K HDFH /r z g ta 0000000000000000000000000000000000000324Q Tz k ,Q 00000000000000000000000000000000000000000000000000000R3203Z E ub|bt I `,Q -,4P S 00000000000000000000000000000000000000R3204Z E ub|bt I `,Q -{4P S 00000000000000000000000000000000000000R3205Z E r I `,Q 00000000000000000000000000000000000000000000000033`5Ca 00000000000000000000000000000000000000000000000000000000000J353636363737373737383839393:424242424445454545454646464747483:b ?-7N KGE l O |+R QS334L rk\z C 1AQS3341Q*MTK+QS3341Q*MTKI+QS3341QF*MTK+QS3341QF*MTKI+303_uQS3341Q Q 0\z R Gv l O a z tL /i A4V .[8K<Y E C }7R F 2F 1<c |K ]l P k Cc ]e ?w W C O ?3A y k t <w e v +N ~R ?w z ]f 4Q y V y`c 9|zc z ad N jk,C C i R K V k t /i zQS334R >q >9b S r Q [<Y E C }7z504|Es;C0-CDD TCEG `SV68240223.d p i |U [8Dcibck+}I D <+b z 8+b r j CDD V ;9D0-CDD TCEG `SV68240224.d p i |U [8Dcibck+}I D <+b z 8+b r j CDD V ;95B n c M|Es;503B n cKGE82;69/4U M T C z a L Y A z a X U e x T604z ~GXh\9[M {H ]y :b R N S s A /+|72182Jw~327>g 822Jw >g 403B6Kk 37E B67/60403v :zQ k R ^U:C 8-m 39^W \~.k ~I Y u R \_z ][;j S ;YRY u L 4a S m M ~e x TB RY u V/T zW h ^U L r ^U R [i R Y 5H a x Y u AL ,Y u +2057*Kk 8~2072*Kk +}2O W }29l ,Y u +2042*Kk 8~2052*Kk +}2O W }2+t ,Y u +2037*Kk 8~2042*Kk +}2O W }2+}2OS ]G xGS ?6C z 60404/r z g :zc L r W \~S ;YR \_z ?D F pz \L ,d R ^U T,F ][;N /i ~I Y u f ^U L r ;Y +;p je x T e T e e x T N -M .k W @RY u ;Y +T Wf 2x A z [;r e ;@+^U L r W \f 2Q k Q R R~I ^U:C ;p }2O k `E ;\s j i W ~O R B R /i zc^U L r w i C T 1g =e T s @;o Z /i o T |1}2O n ]:Q .z Q k R ^U:C n z [91^W ji W [I 4W x R ]:Q .?D z \;j ^U L r 4[I 87[i~e x T z [h?x R d [M@8c ?~+D 9a wee x T R z603xk6N >S WQS334^U L r W M ~CDD Gj_u x p t ke G k e x Tx ;R \`\z :C A ^U y }m y S r }}y ?K ;2y }7y e x T }}y C N >>L C N C;z O X p z ALm 3W V ;R ^U606=11=n60603>z 6d+Z p=1xx L731T [gk e L731I [gk<K e I _p j P :C R >q60604>z 6d+Z p=nxx L731T [lrq e L731I [lrq<K e I _p j P :C R >960605=nqyxx L731Q3A i W W i 3R w Y T >9xx L7319JA g =e T A /w Y T ?K >9xx L pT <X ;~~I Y u C ~+k6xx Y G Y ^Y u A 5C/472W CE*204C/322W FE+xx<X R v Y M A 3222W CExxL731ZP3A |^U L r d [}w Y T ?K >9xx DpT <X ;~~I Y u L S ;Y N Tz S k6xx Y G Y ^Y u A 207C/347W CE*205C/332W FE+xx<X R v Y M A 972W CE^U L r B~I Y u 7[P 5,/i N T xG ?6C zb j ~I Y u g H fV R v ;Q \H /i |3d 4u T };R |N KGE l O 82;72.82586/63.e cH l O 8C ^6=9Y u e ;v Y u r G m 507jC.KGE69:13+0605H\[*9[n a ;C n a ,f n at U T q 8QS334M q e x TB 9/47/{~92//62/{~;2/2~{-;:~s F w KQ52607HZxQxx CDD TCEG 8`;B t V +ST6:7.q U {3;.422`mpzMm 4~I Y u ;Yf ^U |M}y|T}y|K}L |I}R 0*Y u :w nl \33yK 4yK 5L K 6;Q ,d R +|:w n j q 3yq 4yq 5L q 6z~I |+^U L r R }2Ox b k,d R ;2;-;28P I |4~e ^U L r d [T u 4~z e x T [I w -d [T *TC+e T ;\+d [Y U <X *L73=ZP3+f N y ,d _u ?;2T o L z f\+*R ^U ;C x1j A q?L fp +*R ^U ;C x1j A q?L =K 4L j ,C z ,m~I |+M ^U TS ^U L r S {;Q \c^U 4i X r C b C f R ^U:C z c^U R d [+|~p +*+W i\z C x1m 2A 60803u Z ES s 7L y :t Lf +|Y A R |G }^U [I l Y q {z \R 0*:L +|:d |H }^U85R `+W \f 2\z l D di A30e Tl 4r \R +|40k7L e T X 4+|N k ~I Y u L QS2421L ?K L r +;c^U W ~|H }^U e T e x T 7W e T L_R +|z f m B E k x RY u ?K ^U L r W Q \z l D s 1=e A 30,Y u :R 72~^U 40,Y u :R 322~^Up +*I |^U |H }c xW Z O +^U |K }c x E+^U |F }7V A /W Z O +^U |E }\0*:c x\K ^U |Kgkpq}/n ^U |U}+|Y A ^U |L}608Z E9yxx QS334^U L r~Y f 4R L @B W V ;\z R ^U:C AN K d -34Kk +;A >D2097]N^U:C |M}y|T}L |I}R {D =e 4g m >gP 8Kk RY u V/T kA {Y u R 3S s 7:*I :C ~/I 6Kk +s 6+z f/I 8Kk +e ^U:C |K};b jd [+|Lt L S s 7:+|R7_;Q 5|`+Vz ;{D =e 4g m y :+:g a?D R z 4FGFj_uM;[I Q .W \F T eC f T ^U R _pK +^U:C z c^U GS ~I Y u o Z L I _pK +^U:C 8-60806059s n \+C ~zf 2c :C GS 2?m \X _p ^U L r R >9b *[TP+\Y A RY u {^U L r R >q b *[TK+k7R a z p H k75f ;-_p BY z X q e x T R >q b L Y x X q e x T R >9b d -4X R z6080404H +dYj Z EQ B ;K d 4A /Y u yK 34^U q z0*Y u ;L mj K k =+|L mj 6z 60804HZ EW \{i M ^U R j u ^:C a?D+b ^U z c^U 4g m |M}y C ;j -y C L 4f dm 3047*K 3+`+R d [+|zT ^U W \9[~\+**q?L+e p +*N Tz ;o Z W \C f z ~p +*+;d [+|W i\z C x1m 2A N K d @34Kk +;20976080303u Z E /O ]N K d @K 4+;Q B ;K d 4A /Y u ;L mj Kk B +|L mj 6z6080403HZ E /O ]N Ki o p +*`++W \i T ^U R j u ^:C a?D+b ^U z c^U 4g m |p}y C R ;j -y C L 4f dm 307uKk +`+*q 4+R d [+|z c^U Q n U E \M ^U j u ^z O~^U L r x X A I |e ][w -7T R 5*M +|7T ;we +|^43227R Q K +|-z z ,Vz P x A I |Q .i R +|;b ,d R O c d [+|zQS334k l D a Ia f 2j u ^z W X D 9[~QS334[Y +*R u ^R 4jm k C 4J W @+|j s n /^U L r d [R I |+;r X D W \9[~^U L r k[Y +*R C *y M p E N -R d [+|9QS3347N r \R \_a S D Q \/i\x l DB R X D z IHH G R JD @<FG =@M ]CBEQS334W \V ;l D c B R 7V A /^U z V/T R 5D h\:]-m 9zf m x A R ^U s 1or C i~UOE x]B z~=k L ,+|S ;Y +;I ^U =~X AY u 0m 206*Kk +k6z jN ,Y u R :/I 6*Kk +^U L r b 2Q 6j ,Y u A /j C f I ^U ze 7L kV/T g Hi r /I 37j -R O e D 5+L QS334k7R a *-504J 5C+;o Z -O e +g H w n ~V/T {L e x T {7V z _pK +^U:C [I 2Y A RY u {e x T e T j 2A /_p 3d ;\+Ch_p B R Q R t w 5,9[z p `Q2;p H ~|^U L r 3_}R +|{l |A /;,|^U L r 3_}e T j |^U L r 3}L |^U L r 2}or ][z j A /l |~|^U L r i}R +|{+;|^U L r 2}or ][;Bj ^6Q R _p 5,{D z>q b *[TK+W Y g o D k7424L r *P ,d R >9b [TP+z>9b *[TP+W Y g k754a S m Y u {RL r *P ,d R >q b [TK+zc^U l 4L r 7|Y -Pd j 5222z/i O e D 5+8-504J 5C+-O e +g H~K +>q b 8[TK+7V zc c B ^U 4[I w mV/T RkA {Y u P ^U L r B t R [C V/Tx ;j i @[C V/T Rk A i +b a p g A /Y u z W i <15Aj ANe x T.k A /Y u +;27Y u R .m L j 2;z ,7N A /\_b 9~6G C :z p H S 9[~2D 91;z @j A Ulo <pcica A Kkq6080603f b x dz kF3}w A Z E*5,L B E,Y u R .m L +K e ?K 3-K 4-K 5-K k 6080604f bJ dz kF3}wAZ E -z g V x Il .f mk@C k7i X R k M T y lY hL Y]h W \w i Wk D 7V A /^U ;p Y u 7V a x ^U z 2D ^U 4[I ~z a @C B >X L 7VX 7|P M X 4e 7L kV/T a -~R z 24L kV/T W \5f p g,d R A /Y u zp H S 9[~2D 91;z @j A Ulo <pcica A Guq60805BZ Ec^U jE+^U ;W C f z 60806AZ EW \2I ^U R d [Y A :C C f *Uogm A Pdd+z @+f m Q k R 7V A /;e x T r w -;j ^UL r =m _F N Tz *Gjcoeckav S n o ~}2Ox }2V2?w +zP608090i _p 9y Cc :C =~k ~I Y u o Z 9N QS2421L ?K L r /i u k6zf m +|Y A :C L j P ;C ~P l Y Y u 0*:L d [+|^U m I |^U M R `+;R W i [\z l 4:C A30e Tl 4_h +|8l Y p +*`+940k7L e T X 4+|8\+*W Z k7`+L p +*e T `+9N 0*:K j M ldd]+;W C fc^U z6080903*]i70i Ka 3?+|3e T 0*:Ka 4?+|4e T 0*:q*Ka 3+?+|3e T +|8Y 5d [+|3;2jp+q*Ka 4+?+|4e T +|8Y 5d [+|597jp+[I Q .W \F T eC f I ^U R _pK +:C z c^U GS ~I Y u o Z L T ^U _pK +:C *-6080404+s n \+C ~zc^U Q n U E \T ^U _pK +z 6080605AZ E +dYjM ~QS334L r B t R X 4>/T W \{}P ^U L r B t R n a ;R C p g A 7C f ^U L r H a B t A /Rv 5,n a z c^U k l 4_F m :A/N/I W X 4B \m :92/+;~k ~I Y u +W ~^U L r }2Ox }2_F ?w/N /I Wk 4B \m ::7/+;:k _F ?we ;p H K +o |PscoUcjmco Uogm}:C \W \wee x T 60808Z E v e x dk L Z E 2I6080904hV T *]\70i Ka 3?+|3k70*:Ka 4?+|4e T 0*:60807R b {D W A J2l 4^U d [`+L |H }^U R `+,H ;M k P 6UR 0*:L 6cR +|z d [`+W i |H }^U R `+;M s j u ^:C zN K @Ka 3+8Q +|`+9;f +|3l9e T 8s z ~+|e T T c^U ~6o Z }2|il_b 3lmck}?w z N K @Ka 4+8Q +|`+9;f +|4l9e T 8s z ~+|e T T c^U ~6o Z }2|il_b 4lmck}?w z S `*f +|3*e+|4+R ^U z [;GS~Y u }2U 4z Q *m Q 0z QN l ,e t ,Y u r N Q /I z \0*:K 8+;^U L r W l9_F ?K ;c^U W C f z r N Q U w d bm 2j A7Vk`_i <?*322;Q B K j_u L K jgk w n 4,Y u R Y G L Y 5:zK j_u /K jgkK j_u6094[9y609034[p PN ,L B E k Y u /I 20;*K 3:+8K 34H^U Q z R 0*:9;|t_okgke}MGF l E o Z ~}2O }21F ?w z 60904U a K ^Ny :b R /I 403+QS334^U L r b l91F ?w o Z |t_okgke}MGF l E *KGE;69/4,y H B ;N >gP 4*Kk +^U L rd -C ~y :b R -403+5,9[9zN K@Ka 4+8Q +|`+9;f +|3l9e T 8s z ~+|e T T c^U ~6o Z }2|il_b 4lmck}?w z S `*f +|3R ^U z [;GS~Y u }2U 4z Q *m Q 0z|Orj0CS}m 29D o E =k7RA C z|N_uCS}m 2C b E =k7R Y gA C 8W z :A 3{;E =k7z [9zN |Orj0CS C N_uCS}+L@<E =k78@+}2?w |_rql ocailpgke bgp_`icb}9z S `*@0:C ;g H f |Orj0CS}[q 8~^U L r z @x L z 9z 6080:0b A ~l Z E BMNPQc^U =kX Y B \+|R ^U `+z N ^U d [+;e x T [I d [+d 8TC 9e T z S 5f V z @Kgkpq ^U ;7N e x T R B K ;GS~^U L r [tQ 0J hl V Q2R X N ?D z \8-`9zc^U =C j CDD ,C k t ?D z \;o Z r C b C f zq*Ka 3+?+|E =k7RTI +|q*Ka 4+?+|e Tk7RTI +|N 0*:K j M ldd]+;W C fc^U z2l 4^U d [`+L |H }^U R `+,H ;M k P 6UR 0*:L 6cR +|z d [`+W i |H }^U R `+;M s j u ^:C zS E =k7+;S~W ZR qa 3+|O +T }k7zN K>Ka 3+8Q B \R +|`+qa 39;f +|3l9k78szKgkpq z \S +T C~`B p +T Cm m [t8ldd 9l V B ;p +T C R m @\`B R T u t w l 2IH6080:03p PmYjQS334^U L r V 4C ~S ;Y e ~I Y u ;Y +}m t ,y B E,L 7V A /Y u *Y u m :C +z |C}m 2Y u U m Y 5W }m :z |C}m 2@<Y u }m *7V A /Y u G m 6Kk+z7N K +B t |7V A /}V/T e 4K +e t |Y u 7V a x }V/T ;7VY uL k l D r \R J _z Y 5W }m Y u :4203Kk*h\:R 327+z Y G W }m :438Kkz60;04I `tF psc :C =~k ~I Y u o Z b j ^Ud [T ~I Y u >y 4JX 6T k6z ~S ;Y 91z ;.u q @U b 9~|Olq Cs_gi_`ic}V2?w z<^;N {;R 4Gj_u e x T <^RY U :8zk C <^;N R l M ?w ^r b e/^U L r R ^U:6;F 2?w ]l P d -f<^;N \_?D }~z <^;N4g m e x T Q 9D Re T A C L /AweR R fY u :7x R z 60;WN 9y60;032T Y[2CDD ,C k t p g ^U L r 9~A /+;1`\+V ;r /Xc K zCDD TCEG QS3341Q Tt<u0uu CDD TCEG ^U L r r /Xc K^U d [A C L sb A f QS334=Q j P 4b j MyTyKyIL U ^U c R R ^U d [A C60;0403I `tFO8O .Pmck A uuuuu u QSPU Mi A uuuuuC M4A uuuuuC M5A uuuuuC Oc A uuuuuC Xc_o A uuu 7Io A uuuuuCA /+M3L M4,Y u :A /+M5L O ,Y u :<^;N {L 7VY u :A 7VY u =f MTKI Bk6IIm 5Y u }mD a^U d [A C K ^U c x Y u G m Kat <^;N {b j Kgkpq ^U d [+;}2\z ?w 8@+.k A /+Y u :9<O .Pmck A uuuuu K QSPUTfloq agoargq Eroockq@Kat Xc_o<uuu ~60:03z k h j603203C73UF3qy 3{QS334B @X 4w Y T ;Q <X 4L73=m3z603204v |P hQS334^U L r C V ;C 4S r }7:C a f ^QC 9[~5,N Tz zU n V ;g m g =e T 9?R U 0>?K W -+{Y ^U L r o ~Q 9~A /+l9_F ?K *MGF n of N N Q H_riq <X +z 603205v hQS334L r j f ^5,9[W V ;\z }7Ai |Uogm Ucpq}:C a }7g =e T L d [+d~?q |Ucpq}x L z ;i 4W x R UGTU Q .a f 2}7z }75,+;e x T d -w -z ~S ;Y *K@2057Kk.L ,;Y ++L ~I Y u ;Y 91z ^W \f ^/i c :C zi |Crql Ucpq}:C a }7i W /i ;4z ac}7[I |Ucpq}x L z a f 2z p H }75,;,]l P \z 50:C 9[5,A /}2*Q k1J G X }2+/l E k kD 869/?I *6;f MTKI B 47+/q _F y ^U L r d [L ^U L r A /;2<XIJ~S ;Y *K@207Kk ;L ,;Y ++L ~I Y u ;Y 91z ^W \f ^/i c :C z ~=o N Tz .}7b b h p B<;Q k R ^U:C V 4k6R z [I Q |Scpcq}Q .W B<}7z~s n S ;Y e ~I Y u ;Y +;Q G C mW j M e x T R QSi42=D ,/a V ;*k7~54R }7k7Z x +z }7x L }2p z AQS334}7d [}7S ]}7bcXXY dkrsr dqmp dkrs[vvv \tso dkrs[vvvm 6L73=mi <X W K :603206w C h <[I QS2321U }7L r 8-;039W \f ^U L r ?D e4R }7z6033b GXrIKl q r s u t v*~}|{z y ,x wm m 7QS334L r 54`:T |1}2R W C O/U W }26D 424T |;Q f d a W Z z ~k ~I Y u +k `G E z /A ^U L r b jcT ;}2p z U 4A*,+m 2=~QS334=MTKI B K +9~z |C}m 2Y u U m Y 5W }m :*203Kk+z |C}m 2@<Y u }m *7V A /Y u G m 6Kk+zp H k |F 1}e |D u }?w+;b }2~c U 4RW XD z N/I X Y ?w+;R 1b /6G X }2~W XD x z [I ;W \GY}2?w *|K |3}9~~-Dl {4*+z /A Q5.W o U Q R ?w z S`*S ]}2;}A Q .*@+|K |3}4~+z603303W S w 5b`2x L B i YYY m 2R W K Bo W i 4e 5.a 8^o Z i a 0.fm zg c x ;N D ?q /A b R U 4T ;W \[I 4e 5.a ^D B r X s 4;S .k X 4C :+;GS Q ;N 2|K 9~~Q .y C R Z {+;LW \i 4e 5.a .k C :z fm =y C GS}A Q z .zGTE .i a c 9R x L e c a >H x L zSGTGU .i a f _u R?;2I L d [;2<X *m z UGTU .i a?D d [}7*-603205+z 603304h }B ]Lt 7}2O U 4x L B 5:C W \i Q .[I |y `}e |i l }91a 9D z Q W \9D R :Cp z A |y `}o y Y u }m :o y ^U L r y C z @o y 5^U:C y C z @o y ^U L r,C ?w|i l }zI /i~|y `}z R Q k :C f ^U L r R z @f 5^U:C y C z @/i |UGTU}Q .6034u 03oQS334^U L r~9.+5y C q z :p z A]ecc^ad`X[vvvvv\`Y[vvvvv\`Z[vvvvv\ak[vvvvv\TVU_qotnj[vvvvv\ILIMm 8<mz @*,+m 2QS334L_[,/9;+R z @75b703hVf md -ji W ?D R z \;]N 2Q 0c 9|9D z2R LW \^6|N ,CGv l O ;o h ^U L r 9[~5D e ;L Y?[H z z ]U n J ]+R B K ;7V k7L b +R Y w /i Pd z 704h <~/i W ;QS334W \g i |S }}:C a?D }7z }79H }2~W C Ox z g i |d [}7}:C ;W \f d [a x?D }7z 9H 5,+e x T d -w -z 705m 63{p H QS334487M ~e x TB R ;j/e x TC 5f /i ;CDD ,C k t b ?D,d z @*p e x T B K ;EU B K 000+zp H QS334L_[j L /;d +;d -ji W S r 25y C 5fz @zd -J ]P QS334~Me x T 9.+;CDD [Ef 27y C [o ,F z @*-<mz @m 8+z i W ~/i QS3347W]7N GS Q y z \/4W F .R y C z 706qo=eS ?q |i l }91;D g HS >q X 4GmC T 3+*803+42223+z i 4e 5.W \B 2000;C TB K +;Q .f \T }?D z X 4C T R K +z >fG 4C T T ;p ?D 3+Q 6z p H 3+5f R X ;D L B |y `}91?q P o |i l }91*y C W 9~o ]l P W \8.y C R v ]E l +z p H 3+>q D u R X ;L b 9~\z ?w Abirruoqjw gWVVVhfqonl pirruoqjo Z b4J9~8P Q z GTE.8e1>w C R|3T9z~>q3+R I3B;W\Q GTE.13z[z3+~x A][T Y-k>w C R k6P;p H k0T q R d[_F e^U L r R;2<X b*m T k6P b,x E=t+zN D?q=X4U4M.k l M y C W\8.R+S;^U L r ng=m|y`}91B p H3+ng k6;p W z6}~k y C W\F.R W Vz;S?q|i l}91=G~LR Q Array-T qo~|L kgq alkdgero_qglk}x L f;=S23+z@j|2222}p W a4f3+R G^.l M+S W\f 2B|y`}91P|i l}91R8^zp H GS}z@=3++;B|L kgq alkdgero_qglk}x L K+|Tcq Q_pptlob}p W z8g y c qn w803evINIO804f @82p H .y `e z @C N ;=G ~L Q GTE .LW \k\z H x L }2~~;g i 4y 5y GTE .LW \~H x L f Y ]y y `Q k R ,C L @L y C z @o z D W \Q.a7<8Caacmq moe 9=R 8.e Q GTE .aMR Bj /i K R z @8Vkbl moe 9z \zU 4b 9~A30Elkdge01Qoleo_j 40Cjjcqco 50Ucpq60Pqfco HrkaqglkpCaacmq moe<>GOUGS@Vkbl moe<>GTECQG@A TqlocbCaacmq moe<>GOUGS@Vkbl moe<>GTECQG@AOPU pqlocbe2l 4U 4]l P =R C N 4z b 2:C;z p H 4T 1;QS334L r ng /i x X A f 2R k6z \z 80403J [3o 82p H QS334L r~_F N Tz @<?D y C F .zf QS334L r Rg c 8.^d -~|i l }91z ?D z \z Bo 4~}2Ox }2R 8-60339AGuq0qlo0Kk<uuuC ED Guu/Cuuuu uuuhCET Kk <uuuuCK +/i M D 7V A /R ^U C 1A p H i B @R [C+d ^U K +\Kkq];p H i e @R [C+d y g i |Y u 7V a x }^U:C a ^U K +\Guq]8c K0=~MTKI B K z k69xK +/i e t [C V/T a di |Y u 7V a x }^U:C K +e x T ^z Y u :K +Y u >/T *ET+h\Y u :;\EU :J A Kk :R z \D u or e/5^U:C R -*;>>/Y u R }2:D u zxM_ker_ec <uuuu0QS2421L rkgq <uuu Ocq Hocnrckav<uuJw Ocrqo_i pci0<uuu ~K +}2oP}24z /i QS2421L ?K L r K +di Rh\M {K +B E,Y u R 4\:8\,Y u R U w d :m 29Tcq Q_pptlob<\,,,,]PscoUcjmco0Uogm<uuu Ngk0Vk`_i0Qf_pc<uuu L731mM <uuuuuuuu~i l 91z 8.=3+z T JU 44Oct Q_pptlob<2\,,,,]L Elkdgoj QTX<2\,,,,];GS}>q =3+fmK +~/n ^U +8n aEP :7/94z h e x T Z -zI,r N Q Y 5:K +W K +>9<X z \;W \V ;R K +-603203m 6Ulo0pcica0<uuu0IP 80404Z E9y3of QS334L r Rg c8.^d-~|i l}91z?D zct w zIi W f QS334QV;R^U:C?D i l/i.~@U n p9R4>q Rsn L W C R C N.j C m^U:C R Q R s@U E]y V|608^U:C}t w z\z Bo4F7p M f^U:C MyTyK L I R z@Al W A f^U:C TyK L I W\K+C f z f:C T L I\W\8.`+c B zK30*:R z\;~K3J h4S]L9\P K m2R C:q3d[`+R K+K+4z di M^U R j u^:CT/QSPU<q?uuuuu.uuul W A f^U:C TyK L I W\K+C f z f:C T L I\W\8.`+c B0*:R z\;~QJ h4S]L9\P K m2R C:d[`+R K+8f K^U s@K+9f^U T W\K+4z di j u^:C B f^U T L I W\K+4z di_pk P:C B f^U I W\K+~^Ut+9B T4zl9h e x T d[R8s p H/i o QS242L T;7N/i91R r\9~\z U4AMPCF<Pmck3/Pmck4Ka3<uuu~K3.q?q3,316Ka4<uuu~K3.q?q3,31491A e Tl4+|K+e T W X4+|R0*:K+e T Wk4+|R0*:MPCF<Eilpc3/Pmck3Ka3<uuu~K3.q?uuupKa4<uuu~K3.q?q3,314N_uCS<u Orj0CS<u91A k7L e T X4+|k7+|R0*:L,d TI+|e T+|R0*:>g L[E E k7A C4030Ujcj<uuu Twlkc<uuuK4<u0uKk2uuuuuCq4<u0uupca0M/QSPUGEUKPO<q?h1g,4K3<u0uuKk2uuuuuCq3<uuupca025,K3Ufcoj_i Ncjlov<uuum@^U L r z@R W K:839s}K+M D`+;Y5d[+|^4972jp*S r^U+849N K+\+*`+8q?h9+;:o Q p r he;\W\K+q4?jgk85927u*r h4g m\z y z R A/^U L r~{D N Tz S;Y8v S]8d9/l,e t,Y u;Y~\x y z\_7e R u*r h p z AIQ805W A80503Z E9y 3o80504z ~W Am 32Y U ?K[I Q |Scpcq}Q .W \`*?I L <XR N T z O6cQ .~S ;Y L k ~I Y u N Tz ^k6zr e ~S ;Y T 034p W \f X 4U=R |]7T }///SGTGU Y oT 6Y ;2/Q ~eY e s ~I Y u +;W \^6>y ~85+B W \[X A *m z [847/9zp H SGTGU Y oT T .Y +;\W \i M ^U L r L I R QS3421D Y u L r *m z~2D \_z ;V W \g i N -+d eh :N -Q G fe x T N -z ^U L r~N -Tp +|6;jf K R *m ,G TI 34p T z9j R;l z o\z m 2B 8m o ,-A /R W C sb L :Q Z n z J 5A3y ~y V \z m 27W ;]{t ]}2Ox W XD B R V2?w z 4y OH ;o v QS334A /z5y m 2B R 1`ng s n :Q qW+;]j x CDD ~5VR}t k t zJHm ;W 6?Km33,-A/H:JI:[4B t MWN\z p9o k C D u z@y X V F1y^U:C V2L Q R ki?w R5A zJJ Z E9y\X[4m34?w5Aqo=e3y r S f ^U L r *m z4y u y z4@X 4_u ?I o L z5y p H k ~I Y u ;?q P |M_pq Uogm}U 4d a d [C N z6y .k ~I Y u +;i QS3421D *Y5+u y zQ k ^U:C R z @z7y u y z e x T B K y k C y L @,/yKk :y x p K 8-`59L r /Xc K z8y O a X xi S R Z -5A *\`p M +Z -D Z o g y A D 4z /A^~\R N Tz D 4,-R R +|D g 0RY M D gGRY u D -3A C z E ~D {{99y 4e Q8m PR ?w ;k \e x T Q ~RY U `36d D Y A R CDD }t k t z:03;l r ep HY Z QS334k A /;e 1Y Z QS334u ][;r 1b +D N 29D\z z [Aw R f 4L O f E f CDD R s @w v v,k [I ;\+R T C [I i W BW C \R :Q qW zg i TCEG QS2321U U N }7L r ;W \[I 9]e S ]Rs 1f QS334^U L r R >q >9y ^U |H }|K }|F }|E }L |Kgkpq}R 0*:L +|?D }7z @e ;\W \d a }7_1L8.z \z ;1T;03<==H<>@FG2321I w C h <v e8g k C QS2321U R -\;]y y Q i W 9|z;04<==H<>@FG2421C W A v e[I B t V +k7P QS3341Q R TCEG QS2421L ?K L r ;g i Q S {R<X W \;2^U:C R N T yQS3341Q B t <XR N T T zP M L z [R -\;]y y Q i W 9|zK L r g Hi O e D 5+L QS3341Q k7R a 8-504J 5D 9;o Z r C /I 37j -zD 5+R O et w g H~QS2421L L e x T {^7V z;05<==H<>@FG3421=zl 1TQS3421D 4[I 4W k7RY5,/8g i }7k7Z 9z c ,/4M QS3341Q ^U L r R l O L @;g i Rs }e x T ~,-N T 8N 1w -y }71k7m @y k 1s ~I Y u 9^W \y `e8.^U L r R z @zc Y u W \^6-x 55+R y `y 8.z [z M p H QS3421D Ti a [}78Uogm qcpq.Tcid/qcpq 9z [RY u .Q Y5:8b ,d O c zJKFE46W TNQT*3UOG;83223S2223+4[I b R H k7R~I Y u ;d L ^U,/;4Gj_u ^U L r R b +L @z c ,/K 07N Gj_u ^U L r R s @U Xj z t ;R :o ;Y 7e ;\V ;X GR ^U:C z g i Rs }e x T ~,-N T 8N 1w -y }71k7m @y 5Y u 9^W \y `e8.^U L r R z @;o Z ^U L r [I `E 0n }2O?;/i W C @~O R R E +Y /z 5,z [zc ,/V ;Gj_u ^U L r Q G RY C R \+;f S {B t Y x L n a yGj_u ^U L r R {D N T ?D {6;f ^Gj_u ^U L r R 5,/i ;j r >m l |N Z R \C z ;06<==?>46K HDFH /r z g taP M L z [R -\;]y y Q i W 9|z324Q /z k ,Qc 2]`=469oW C R K +r h 8-804049z3203Z E ub|bt I `,Q -|,4P.JL3204Z E ub|bt I `,Q -|{4P.JM3205Z E A I `,Q33`5Cam3W V;R^U0000000000000000000000000000000000000000000000000000000000000000000000006 m4~I Y u U E0000000000000000000000000000000000000000000000000000000000000000000000007 m5Y u}mD a0000000000000000000000000000000000000000000000000000000000000000000000033 m6L731m3<X W K:00000000000000000000000000000000000000000000000000000000000000000034 m7QS334L r54`:00000000000000000000000000000000000000000000000000000000000000000035 m8<mz@00000000000000000000000000000000000000000000000000000000000000000000000000037 m9^U z@R W K:00000000000000000000000000000000000000000000000000000000000000000003: m:^U:Cz\W K:000000000000000000000000000000000000000000000000000000000000000003: m;W6?K00000000000000000000000000000000000000000000000000000000000000000000000000042 m32Y U?K00000000000000000000000000000000000000000000000000000000000000000000000000042 m33,-A/H:0000000000000000000000000000000000000000000000000000000000000000000000043 m34?w5A00000000000000000000000000000000000000000000000000000000000000000000000000044 JN。

ABB断路器参数调试讲义全

ABB断路器参数调试讲义全

ABB断路器参数调试讲义电控柜的断路器进行设置,在ABB塑壳断路器(正面)下方有两个旋钮(见下图),通过调节旋钮的位置可以设置断路器的过流、过载保护值,具体设置方法如下:过载调节过流调节旋钮旋钮一、 ABB塑壳断路器过流、过载旋钮设置说明:1、过流调节旋钮,设置电控箱整个负载的过流保护值,调节范围从2000A—4000A,从 MIN—MED—MAX共有 9 个档位,档位对应值如下:MIN(1)档— 2000A; (2)档— 2250A; (3)档— 2500A; (4)档—2750A;MED(5)档— 3000A; (6)档— 3250A; (7)档— 3500A; (8)档学习资料整理分享—3750A;MAX(9)档— 4000A;2、过载调节旋钮,设置电控箱整个负载的过载保护值,调节范围从280A— 400A,从 MIN—MED—MAX共有 9 个档位,档位对应值如下:MIN(1)档— 280A; ( 2)档— 295A; (3)档— 310A; (4)档—325A;MED(5)档— 340A; ( 6)档— 355A; (7)档— 370A; (8)档—385A;MAX(9)档— 400A;二、 ABB断路器机型设置说明供电电油泵功率系统电流断路器参数设置机型号断路器容过载值调过流值调压( V)( KW)值量整整EBZ100型380 55 115.0 400A 1 档 1 档EBZ132型380 55 134.0 400A 1 档 1 档380 75 143.5 400A 1 档 1 档380 75 159.7 400A 1 档 1 档EBZ160型380 90 171.4 400A 1 档 1 档380 110 181.7 400A 1 档 1 档EBZ200型380 110 206.1 400A 3 档 1 档380 132 218.1 400A 4 档 1 档EBZ200H型380 110 206.1 400A 3 档 1 档380 132 218.1 400A 4 档 1 档EBZ100 380 55 196.7 400A 2 档 1 档EBZ132型380 55 231.7 400A 5 档 1 档380 75 248.9 400A 6 档 1 档380 75 277.1 400A 8 档 2 档EBZ160型380 90 297.1 400A 9 档 2 档380 110 315.1 400A 9 档 2 档EBZ230 380 132 252.1 400A 7 档 2 档EBZ260H 380 132 277.2 400A 7 档 2 档380 160 290.4 400A 8 档 2 档学习资料整理分享EBZ318H 380 200 349.5 400A 9 档3 档三 ABB断路器低压断路器的参数详解3.1 、空气断路器的框架电流 Iu 、额定电流 Ie 、额定电流整定值 Ir 的含义是什么?框架电流 Iu :又称为额定不间断电流。

(完整版)ABB双电源使用说明与接线图

(完整版)ABB双电源使用说明与接线图

ABB双电源自动切换装置工作原理DPT/SE装置主要用于控制和自动切换两路带有机械和电气联锁的低压断路器:一个4 位置转换开关用于设定四种工作模式:- 自动模式:转换开关置于“自动 (AUTO)”位置-正常供电模式:转换开关置于“正常 (NET)”位置- 应急供电模式:转换开关置于“应急 (EMER)”位置- 关断模式:转换开关置于“关断 (OFF)”位置。

当系统投入运行时,需将运行开关置于“运行 (RUN)”位置,而“复位 (RESET)”按钮可使运行程序恢复到初始状态。

自动模式(自投自复):当转换开关置于“自动 (AUTO)”位置时,系统会处于自动切换方式下:•当正常供电电源正常时,正常供电断路器闭合,而应急供电断路器断开•当正常供电失压和缺相时,柴油发电机起动,正常供电断路器断开,在缺相时系统报警。

•当柴油发电机或应急电源电压达到稳定状态时,则应急供电断路器会闭合•当正常供电恢复正常时,则应急供电断路器断开。

正常供电断路器将闭合投入供电,系统发出停止柴油发电机的信号,并返回正常运行状态。

正常供电模式当转换开关置于“正常 (NET)”位置时,系统会处于单一正常供电模式。

在此模式下,系统并不考虑正常供电电压是否存在,只执行下列操作:•如果柴油发电机还在运行,则将其停止•如果应急供电断路器处于闭合状态时,则将其断开•闭合正常供电断路器•当正常供电缺相时,正常供电断路器会断开,而系统会自动报警•当正常供电失压时,正常供电断路器会保持闭合。

应急供电模式当转换开关置于“应急 (EMER)”位置时。

系统会处于单一应急供电模式,并不考虑实际的正常供电电压是否存在,它将执行下列操作:•如果正常供电断路器处于闭合状态时,则将其断开。

•起动柴油发电机。

•当柴油发电机或应急电源电压达到稳定状态时,应急供电断路器会闭合•当应急供电缺相或失压时,应急供电断路器将断开。

而缺相时,系统会自动报警。

关断模式当转换开关置于“关断 (OFF)”位置时。

abb低压电器元件 - 选用手册

abb低压电器元件 - 选用手册

abb低压电器元件 - 选用手册1. 引言在现代工业生产和家庭生活中,电气设备已经成为必不可少的一部分。

而abb作为全球领先的电气设备制造和解决方案提供商,其低压电器元件备受信赖。

在选择abb低压电器元件时,掌握其选用手册是至关重要的。

2. abb低压电器元件概述abb低压电器元件包括断路器、接触器、继电器、隔离开关等,涵盖了电气系统中各种重要的功能。

这些元件的选用与性能直接关系到电气系统的安全可靠性和稳定运行。

3. abb低压电器元件选用手册abb低压电器元件选用手册是abb官方提供的一本重要参考资料,其中包含了各种abb低压电器元件的技术参数、选型指南、安装要求等详细信息。

通过研读选用手册,用户可以全面了解abb低压电器元件的特性以及如何正确选型和使用。

4. 深入探讨abb低压电器元件的选用要点(1)技术参数分析在选用abb低压电器元件时,首先需要仔细研读选用手册中的技术参数。

断路器的额定电流、额定短路容量,接触器的触点额定电流、额定短路保护等。

这些参数直接关系到元件在电气系统中的使用范围和可靠性。

(2)选型指南abb低压电器元件选用手册还会详细介绍不同型号的元件适用的场合和用途。

针对不同的负载类型,abb会推荐适合的断路器和接触器型号,并提供详细的选型方法。

(3)安装要求在选用abb低压电器元件后,正确的安装和使用也是至关重要的。

选用手册中会包含元件的安装要求,包括安装尺寸、接线方法、绝缘要求等,用户需要严格按照要求进行安装,以确保元件的正常运行。

5. abb低压电器元件的未来发展abb作为全球领先的电气设备制造商,其低压电器元件在性能和稳定性上都有着显著的优势。

随着数字化技术的不断应用,abb低压电器元件也在不断创新,未来将更加智能化和便捷化。

6. 个人观点和总结通过研读abb低压电器元件选用手册,我深切感受到abb在电气设备领域的技术实力和丰富经验。

在未来的工作和生活中,我将继续关注abb低压电器元件的发展,努力将其应用到实际生产和生活中,为提升电气系统的安全稳定性作出贡献。

ABB低压元器件选型手册

ABB低压元器件选型手册

目 录页1.断路器空气断路器 - New Emax 空气断路器 - Megamax 塑壳断路器 - Isomax 漏电保护组件/漏电保护继电器 塑壳断路器 - Tmax 双电源自动切换装置 - DPT 配电智能化元件 - IPD 2.工控产品软起动器接触器建筑用接触器 - ESB (导轨安装)手动电机起动器 - MS 系列短路保护电器和接触器及热继电器的配合电机控制/保护器件指示装置接线端子3.开关及熔断器组开关熔断器组 - PowerLine 负荷开关 - SwitchLine 熔断器开关 - EasyLine/FastLine 4.终端配电保护产品建筑电器元件电涌保护器 - OVR 5.箱体终端配电箱 - ACM/ACP/ACF 系列三相配电箱 - SDB 系列动力配电箱 - MDS 系列6.电网质量产品无功补偿控制器件有源谐波滤波器7.断路器保护配合表断路器保护配合表因产品技术不断改进,所有数据应以本公司最新确认为准。

ABB 公司对本手册的接受或使用无任何商业承诺或保证,由使用者根据具体应用考虑本手册的适应性。

0/1ABB 低压电器元件选用手册1234567.............................................................................. 1/1-4................................................................................ 1/5-6................................................................................ 1/7-12........................................................................ 1/13.................................................................................. 1/14-17............................................................................ 1/18............................................................................... 1/19-20..................................................................................................... 2/1-7........................................................................................................... 2/8........................................................................ 2/9......................................................................... 2/10-12.......................................................... 2/13................................................................................... 2/14-22................................................................................................. 2/23-24................................................................................................. 2/25-26............................................................................... 3/1.................................................................................. 3/2-3................................................................... 3/4-5............................................................................................... 4/1-8........................................................................................... 4/9..................................................................... 5/1................................................................................. 5/2-3................................................................................. 5/4-5........................................................................................ 6/1-4.............................................................................................. 6/5........................................................................................ 7/1-53/1开关熔断器组 - OS/OESA (32…800A )开关熔断器组 - P o w e r L i n e 3说 明:1. 开关熔断器组不包括熔断器,熔断器需另行订购2. 熔断器应符合 IEC 有关标准。

ABB变频器ACS510-01用户手册

ABB变频器ACS510-01用户手册

*******************************低压断路器的结构和工作原理(一)*************************低压断路器的结构和工作原理:低压断路器也称为自动空气开关,可用来接通和分断负载电路,也可用来控制不频繁起动的电动机。

它功能相当于闸刀开关、过电流继电器、失压继电器、热继电器及漏电保护器等电器部分或全部的功能总和,是低压配电网中一种重要的保护电器。

低压断路用具有多种保护功能(过载、短路、欠电压保护等)、动作值可调、分断能力高、操纵方便、安全等优点,所以目前被广泛应用。

一般选用原则:最常见的负载有配电线路、电动机和家用与类似家用(照明、家用电器等)三大类。

以此相对应的便有配电保护型、电动机保护型和家用及类似家用保护型的断路器。

这三类断路器的保护性质和保护特性是不相同的。

1、住户配电箱总开关一般选择2P32——2P63A 小型断路器或隔离开关。

2、照明回路一般选择10-16A 小型断路器。

3、插座回路一般选择16-20A 的漏电保护断路器。

4、空调回路一般选择16-25A 小型断路器。

或严重过载时,过电流脱扣器的衔铁吸合,使自由脱扣机构动作,主触点断开主电路。

当电路过载时,热脱扣器的热元件发热使双金属片上弯曲,推动自由脱扣机构动作。

当电路欠电压时,欠电压脱扣器的衔铁释放。

也使自由脱扣机构动作。

分励脱扣器则作为远距离控制用,在正常工作时,其线圈是断电的,在需要距离控制时,按下起动按钮,使线圈通电,衔铁带动自由脱扣机构动作,使主触点断开。

低压断路器分类:按灭弧介质分类,有空气断路器和真空断路器等;按用途分类,有配电用断路器、电动机保护用断路器、照明用断路器和漏电保护断路器等。

配电用低压断路器按保护性能分,有非选择型和选择型两类。

非选择型断路器,一般为瞬时动作,只作短路保护用;也有的为长延时动作,只作过负荷保护用。

选择型断路器,有两段保护、三段保护和智能化保护。

两段保护为瞬时或短延时与长延时两段。

ABB 低压自动转换开关商品说明说明书

ABB 低压自动转换开关商品说明说明书

Enclosed automatic transfer switches ABB low voltage component capabilities for critical power applicationsCritical power applications require a constant and reliable power supply to keep fundamental services running and prevent serious consequences arising due to interruption or absence of the electrical grid. This need is even stronger nowadays because of the increasing significance of the key role, capacity and features of these systems.Selection of a source of switching, control and protection components capable of sustaining the needs of a critical power application is paramount, ABB has a well proven track record within this environment.2 Critical Power Automatic Transfer SwitchesIn today’s world, electrical power plays a key role in almost every activity of our life. For some equipment a reliable, uninterruptible and free of disturbance power supply is an absolute essential. Fromthis point of view, a fault in the power supply of communications systems, hospital apparatus, security systems, water and gas distribution devices, banking computers and many other crucial applications may bring about serious problems, with consequences that can be devastating.All these applications can be identified as “Critical Power” applications: ABB can offer a wide range of components for on board installation and complete power distribution systems.These products include:- automatic transfer switches (ATS) and automatic control units (ACU), manual and motorised change-over switches, isolators, switch-disconnectors air, moulded-case and miniature circuit breakers, protection devices against overvoltages, contactors, current sensors and many other devices.ABB products comply with the most important international standards - either European or North American - andwith the requirements of the Navy Registry; they are also designed and built on the basis of the most modern and advanced environmental standards. ABB products are backed by a consolidated experience in power and automation technologies. They are supported through a global assistance and service network which covers more than 100 countries all over the world.Critical Power Automatic Transfer Switches 3Enclosed automatic transfer switches functionality & featuresAs industrial processes and ITapplications diversify, a securepower supply is becoming anincreasingly important assetin the drive to cut productionand maintenance costs.In emergency situations,the system logic of powerdistribution can becomecomplex with mechanicaldevices looking after making, breaking, conducting and isolating power. Loadsmay sometimes need to be transferred from one supply to another — this will be the case when energy use is restricted or when the supply source is overloaded. High performance levelIn change-over applications where the loaded switch may need to be operated remotely, adequate durability has been ensured by testing against the IEC 60947-6-1 standard in the specification of endurance requirements.Utilisation categories:− AC-31 for non-inductive or slightly inductive load− AC-33 for motor loads or mixed loads including motors ABB change-over switches are rated according toIEC 60947-6-1 standard.4 Critical Power Automatic Transfer SwitchesCritical Power Automatic Transfer Switches5FunctionalityIncludes automatic control unit OMD300_OMD800_Manual operation with handlex x Local operation with front panel keypad xxMeasurementsThree phase voltage measurement on LINE 1 & 2x x Single phase voltage measurement on LINE 1 & 2x x Frequency on LINE 1 & 2x x Source failure detections No voltage x x Undervoltage x x Overvoltage x x Phase missing x x Voltage unbalance x x Invalid frequencyxx Incorrect phase sequence xConfiguration By DIP switches x By rotary switches x By keypad and LCDx Voltage threshold setting xx Voltage hysteresis setting x Frequency threshold setting x Frequency hysteresis setting x Time delays Switching delay x 1)x Delay on transfer 2)x Dead band time I-II (stop switching to position O)x Back-switching delayx 3)x Dead band time II-I (stop switching to position O)x Generator stop delayx 4)x Status of time delays on the LCDxFeaturesIncludes automatic control unit OMD300_OMD800_Generator start and stop x x Off-load test sequence x x On-load test sequencex x Source status via front panel xx Source status via digital outputs x Switch position via front panel xx Modbus interface x Event/alarm logx Counter for number of operations x Auxiliary voltage supplyx Programmable digital inputs (eight) and digital outputs (six)x Secondary load control (load shedding)x Digital input - Allow transfer to secondary x Digital input - Generator alarmx Digital input - Remote control to positions I, O and II xOperating mode Line priorityx 5)x 6)Manual back-switchingxx Automatic operation to position O, in case ofsource failurex1) Four options: 0, 5, 10 or 30 seconds2)Delaying the switching sequence before transferring to generator,guaranteeing that in cold locations the generator is properly warmed up 3)Two options: the duration of back-switching delay is the same as switching delay,i.e. the time delay is same for I - II and II - I, or the back-switching delay is fixed 300 seconds 4)Two options: the duration of generator stop delay is the same as Switching delay or fixed 5 min 5)Two options: No line priority, or Source 1 is the priority source 6)Three options: No line priority, Source 1 or Source 2 is the priority sourcex = included as standard6 Critical Power Automatic Transfer SwitchesEnclosed automatic transfer switchesselectionDescriptionRated Current (A)Enclosure Size (mm)HWDATS 40A 40600600250ATS 63A 63600600250ATS 125A 125600600250ATS 160A 160600600250ATS 250A 250600600250ATS 400A 400800600300ATS 630A*6301000800400ATS 800A*8001000800400ATS 1000A*10001400800500ATS 1250A*12501400800500ATS 1600A*16001400800500* Floor standing plinths from accessories below. Bypass options are available on request.Other wall mounting and floor standing versions available on request.Optional extrasAccessoriesEnclosed automatic transfer switches, I-O-II operation, open transitionATS 4 pole with OMD300 & OMD800controller, blank door, wall mountableEnclosed Automatic Transfer Switch with ATS2PL & ATSDMC optional extrasCritical Powerother ABB productsMoulded case & Air Circuit BreakersThe moulded case circuit breakers of Tmax XT series coverlow voltage applications up to 250A, while the Tmax Tfamiliy offer current ratings up to 3200A.The Emax air circuit breakers up to 6300A and it ensuresshort circuit perfomances up to 150kA.Block Contactors- AF series three poles contactors from9A to 2050A (AC1, 40°C), with electronic interface coil- A and AF series four poles contactors up to125A (AC1, 40°C)- EK series four poles contactors from110A to 1000A (AC1, 40°C)ABB offers a range of installation contactors up to 63A forDIN Rail enclosures.Manual Motor StarterManual Motor Starter covers a range up to 100 A formotors protection up to 45 kW / 400 V.Electronic products and relays (EPR)The versatile range of electronic products and relays offers a maximum of security,economic efficiency and capacity. The range covers products from analog signal converterup to measuring and monitoring relays and time relays.Residual current devicesABB range of modular and front panel residual current devicesincludes F200 RCCB, DS200 RCBO and RD residual current relays.Arc MonitorTVOC-2 is ABB’s state-of-the-art solution for arc faultprotection in all applications, providing functional safety.Residual current devicesABB range of modular and front panel residual current devicesincludes F200 RCCB, DS200 RCBO and RD residual current relays.Critical Power Automatic Transfer Switches 7Contact usABB Ltd Tower CourtFoleshill Enterprise Park Courtaulds Way Coventry CV6 5NXTel: ***********Fax: ***********/lowvoltageemail:*******************.com Twitter follow us @ABBUKLVPP u b l i c a t i o n N u m b e r : 9A K K 105713A 8079Power and productivityfor a better worldTM。

abb eki pconnect 智能型断路器操作手册说明书

abb eki pconnect 智能型断路器操作手册说明书

—E A S E OF I NTER AC TI O NEkip ConnectAccess the full potential of your ABB circuit breakercommissioning software to unlockthe full potential of circuit breakers,and improve the efficiency of theplant.day-by-day process.For this reason, it is vital that the installation anduse of the circuit breaker are made as error-free andsimple as possible.From commissioning to implementation, throughmonitoring, testing and analysis, Ekip Connect isthe perfect tool to drive the user in the managementof ABB circuit breakers throughout the wholeproduct life cycle.Ekip Connect is the ABB commissioning andprogramming software allowing full exploitation ofEkip trip unit’s potential. Using Ekip Connect, theuser can manage power, acquire and analyzeelectrical values and test protection, maintenanceand diagnostic functions.If the Ekip architecture takes the circuit breakers tothe next level, Ekip Connect software becomes theuser’s key to access that level and exploit the newunique features developed by ABB.Ease of useImagine you are a panel builder. You have to commission a circuit breaker and you need to save time.Using Ekip Connect – instead of managing it manually – you can cut commissioning time up to 50%.Providing a stress-free relationship with the device complexity, Ekip Connect is an easy-to-use software that has all the answers you need.Ekip Connect simple and intuitive interface guarantees, from the very start, easy navigation throughout the tool and quick access to every circuit breaker operation.At a glance, the user can see all the information he needs, thus being able to quickly and effectively assess any situation.Full exploitationImagine you are a facility manager. You need to perform fast and precise diagnosis to have everything under control and avoid failures.Using Ekip Connect you can exploit the full capabilities of your device and, thanks to the customizable dashboard, you can organize your windows to manage any function of the device just the way you want it.It is possible to manage all the circuit breaker settings and specifications directly with Ekip Connect, the perfect instrument for exploring and using the breaker.Diagnostics are easy too: it is possible to consult and download event log, alarms and trips, thereby facilitating identification and understanding of any anomalies.One single software to manage all ABB low-voltage circuit breakers equipped with an electronic trip unit, granting full integration between air and molded case circuit breakers. Product enhancementImagine you are a consultant or a system integrator and you want to implement advanced features while avoiding any risk of mistakes.Using Ekip Connect you can implement complex logics with just a few clicks.To add, set and manage advanced functions has never been so easy. Cloud platform, automatic transfer switch logic, load shedding, advanced protection and demand management can be managed and easily set through the Ekip Connect software. Expand your software features by purchasing and downloading software packages for advanced functions directly using Ekip Connect.Panel builder- 50% commissioning timeFacility manager+100% full exploitation of your device Consultant/System integratorComplex logics at your fingertipAccessing the full potential of ABB low-voltage circuit breakers at your fingertips.Thanks to Ekip Connect software, you can achieve the full exploitation with few clicks of your mouse.ConfigurationProduct implementation Monitoring & analysis Testing & reporting• Set protections• Configure system andcommunication parameters • Circuit breaker start-up• Set advanced protections • Logics activation• Enable advanced functions• View circuit breaker status and measures • Read event list• Circuit breaker diagnostics• Check correct functionality • Test performance • Report exportEkip Connect is available for free download at /abblibrary/DownloadCenter/1S D C 210102D 0201 - 2018.03/lowvoltage—ABB SACEA divison of ABB S.p.A.L.V. Breakers Via Pescaria, 524123 Bergamo - Italy Phone: +39 035 395.111Fax: +39 035 395.306-433—We reserve the right to make technical changes or modify the contents of this document without prior notice. With re-gard to purchase orders, the agreed par-ticulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.We reserve all rights in this document and in the subject matter and illustrations con-tained therein. Any reproduction, disclo-sure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB. Copyright© 2017 ABB All rights reserved。

ABB低压断路器用户手册

ABB低压断路器用户手册

13.4 用户界面序号说明1 LED 预报警指示2 LED 报警指示3 背景灯图表显示4光标向上移动按钮5光标向下移动按钮6 通过一个外部装置(PR030/B 供电单元、BT030 无线连接单元以及PR010/T 单元)来连接或测试脱扣器的测试连接器7输入数据确认键或页面切换8 退出次级菜单或取消操作键(ESC)9 额定电流插件10 保护脱扣器的系列编码11 “i test”按钮当有一个辅助供电或有最小母排电流或PR120/V 供电时,LCD 图像显示器即可显示,请参见13.2.2.1。

你可在“setting”菜单上通过特别的按钮调整显示器对比度(参见13.5.4.1)。

13.4.1 按钮使用通过↑和↓键可进行选择,通过键进行确认。

进入你想进的界面后,你可使用↑和↓键从一个值移到另一个值。

如果想改变一个值,固定光标在那个值上(可改变的区域将由黑变白),然后使用键。

为了确定先前配置的参数,请按ESC 一次,这样将完成一个检查和显示参数配置界面。

如果想回主页,请按ESC 两次。

“i test”按钮必须在自供电模式下执行脱扣测试,这样就能看到相关信息和断路器分闸48 小时内的最后一次脱扣。

13.4.2 阅读和编辑模式在“read”模式(仅仅读取数据)或“edit”模式(可设置参数),菜单显示所有可得到的界面和通过键盘可移动。

在任何界面,根据脱扣器的状态具有2 种功能:1“read”功能,120s 后将自动显示其默认界面2“edit”功能,120s 后将自动显示其默认界面状态决定功能:“read”测量和历史数据的查看脱扣器单元配置查看保护参数配置查看“edit”“read”模式下的任何事情脱扣器单元配置保护参数配置脱扣器单元测试功能在可编辑的界面按键可进入“edit”模式,当然需要输入密码。

键盘使用方法如下:键盘功能界面间移动,菜单间移动,改变参数值结束设置阶段和确认结果,选择菜单从默认界面进入菜单,可回前一个界面和回到默认界面,退出参数设置阶段和取消变化在自供电模式,断路器分闸48 小时内可激活显示器。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

13.4 用户界面序号说明1 LED 预报警指示2 LED 报警指示3 背景灯图表显示4光标向上移动按钮5光标向下移动按钮6 通过一个外部装置(PR030/B 供电单元、BT030 无线连接单元以及PR010/T 单元)来连接或测试脱扣器的测试连接器7输入数据确认键或页面切换8 退出次级菜单或取消操作键(ESC)9 额定电流插件10 保护脱扣器的系列编码11 “i test”按钮当有一个辅助供电或有最小母排电流或PR120/V 供电时,LCD 图像显示器即可显示,请参见13.2.2.1。

你可在“setting”菜单上通过特别的按钮调整显示器对比度(参见13.5.4.1)。

13.4.1 按钮使用通过↑和↓键可进行选择,通过键进行确认。

进入你想进的界面后,你可使用↑和↓键从一个值移到另一个值。

如果想改变一个值,固定光标在那个值上(可改变的区域将由黑变白),然后使用键。

为了确定先前配置的参数,请按ESC 一次,这样将完成一个检查和显示参数配置界面。

如果想回主页,请按ESC 两次。

“i test”按钮必须在自供电模式下执行脱扣测试,这样就能看到相关信息和断路器分闸48 小时内的最后一次脱扣。

13.4.2 阅读和编辑模式在“read”模式(仅仅读取数据)或“edit”模式(可设置参数),菜单显示所有可得到的界面和通过键盘可移动。

在任何界面,根据脱扣器的状态具有2 种功能:1“read”功能,120s 后将自动显示其默认界面2“edit”功能,120s 后将自动显示其默认界面状态决定功能:“read”测量和历史数据的查看脱扣器单元配置查看保护参数配置查看“edit”“read”模式下的任何事情脱扣器单元配置保护参数配置脱扣器单元测试功能在可编辑的界面按键可进入“edit”模式,当然需要输入密码。

键盘使用方法如下:键盘功能界面间移动,菜单间移动,改变参数值结束设置阶段和确认结果,选择菜单从默认界面进入菜单,可回前一个界面和回到默认界面,退出参数设置阶段和取消变化在自供电模式,断路器分闸48 小时内可激活显示器。

13.4.3 改变参数在主菜单内查看,你可以看到与配置和参数设置有关的所有界面,可以去改变参数值。

你需要确认/取消/改变你已经做的任何变化和它不适合所有可改变的情况。

下面例举2 个例子:一个是不需要对你做的变化进行确认,另一个是需要确认。

不需要确认例如,为了设置系统系统日期,正确方法如下:从默认界面按ESC 进入主界面在主界面选择“SETTING“,按键选择“SYSTEM“,按键选择DATE,按键此时将要求输入密码(参见13.3.6),按键通过↑和↓键改变日期,通过键进行确认。

按ESC 两次回到主界面。

需要确认例如,为了改变L 保护曲线,正确方法如下:从默认界面按ESC 进入主界面在主界面选择“PROTECTIONS“,按键选择“L PROTECTION “,按键选择CURVE,按键此时将要求输入密码(参见13.3.6),按键从例表中选择你需要的,然后按键确认。

按ESC 两次在进入主界面之前,将出现一下信息:接受新配置拒绝新配置(保持原来配置)改变前一次输入值通过↑和↓键进行选择,通过键进行确认。

13.4.3.1 更改基本参数注:当PR122/P 在报警状态时,不能设置任何参数。

脱扣器参数配置必须在EDIT 模式下进行。

遵循13.4.3 的说明,参见以下信息:改变系统日期改变系统时间选择系统语言如果要改变密码,选择相关菜单和按键,你将被要求输入旧密码,然后再输入新密码两次。

按ESC 两次进入主菜单。

在进入主界面之前,将出现一下信息:接受新配置拒绝新配置(保持原来配置)改变前一次输入值13.4.4 默认设定ABB SACE 预先设定了下列PR122/P 参数:# 保护on/off 门限时间曲线T.M ZS 脱扣13.5 操作方法13.5.1 菜单与前面介绍的一样,PR122/P可用一种逻辑和直观的方式显示信息、图像和菜单。

下面是大体分布:显示如何进入主菜单界面。

*菜单显示,脱扣器中带可选性模块PR120/V。

每次脱扣器被通电,或在键盘上没有任何动作2 分钟,显示器将显示如下(默认):相对额定值的真实电流和电压百分比最大负载下显示相应相(L1,L2,L3,N)最大负载下电流值13.5.2 保护菜单你可按ENTER 进入各种保护菜单。

使用↑和↓键,你可看到各种保护菜单。

当可选性模块PR120/V 被安装后,可显示各种数据:L,S,I,G,U,UV,OV,RV,OF,OT,LOAD PROTECTION浏览保护菜单的例子:你可在保护菜单主界面上按ENTER 进入L 保护菜单。

可使用↑和↓键选择相关项,和按键进行确认。

这时将要求输入密码,然后你可选择与L 保护相关的功能。

如何选择曲线同样,为了进入其它保护菜单,请参见保护菜单表。

13.5.2.1 保护菜单表保护参数/功能注:对于单个保护和它们的设置以及相应曲线,请参见13.2.913.5.3 测量菜单PR120/V 的具体描述,请参见15.1。

下面是一个可在PR122/P 单元得到的参数表13.5.3.1 测量菜单表设置参数/功能值注历史数据脱扣最后一次脱扣事件事件记录仪测量电流Imax 复位测量峰值因数触头磨损断路器触头的磨损率13.5.4 设置菜单在设置菜单上配置参数有密码进行保护。

在你选择的最重要的值之间,请注意中性线门限(50%,100%,150%,200%),外部线圈大小(100A,250A,400A,800A),主频率(50HZ,60HZ)。

对于更具体的模块参数描述,请参见模块文件(15 章节)。

13.5.4.1 设置菜单表参数/功能值注断路器激活中性线保护中性线门限接地保护仅仅在使用外部线圈的情况下,提供保护外部线圈SGR 线圈大小Rc 线圈大小主频率模块如果有参见如果有参见如果有参见数据记录仪激活采样频率停止事件停止延迟重起停止测量间隔从5min 到120min,间隔5min谐波失真失真超过2.1,显示报警系统数据时间语言新密码显示对比度关于PR120/V 主界面浏览总表请参见15.3 和PR021/K 单元参见16.113.5.4.2 N 极调整N 极保护一般设为相的50%。

在一些情况中,特别是高谐波发生时,中性线上的电流可能高于相电流。

对于SACE PR122/P 脱扣器,保护可被设置为以下值:In N=50% - 100% - 150% - 200%* In。

在断路器型号和保护门限In 之间,下表给出N 极调整值各种可能的组合:13.5.4.2.1 N 极调整表I1 门限调整值(L 保护)断路器型号注1:I1=1 In 是最大的过载保护调整值。

真正最大的可允许调整值必须考虑任何降温、接线端子和纬度。

没有设置好I1 和In N 可能损坏断路器,甚至危及操作者。

任何情况下,脱扣器记录I1 和中性线设置电流之间的任何错误,并通过报警指示(参见13.6.3)。

13.5.4.3 主频率设置在主频率菜单中,你可选择频率值:50HZ,60HZ。

13.5.4.4 模块当进入设置菜单后,有大量与模块相关的菜单可供选择。

13.5.4.4.1 PR120/V - 测量模块在测量模块中,你必须输入一个密码和可选择有无电压传感器。

而且,你可选择原边值(100,115,120…1000V)和付边值(100,110…230V),供电方向从低–高–低。

当输入密码后,你可选择是否连接中性线。

另外,相序和信号可激活与关闭,也可选择相应的门限值(参见15.1)。

13.5.4.4.2 PR120/D-M – COM 模块当输入密码后,可选择本机或远程模式,可显示串地址和波特率能够设置在9600 和19200bit/s。

可提供选择:(8,E,1),(8,0,1),(8,N,2),(8,N,1)。

串地址可选择标准Modbus 或ABB。

对于PR120/D-M 通讯模块,请参见手册15.2。

13.5.4.4.3 PR120/K - 信号模块对于信号模块的彻底检查,请参见15.3 相应模块部分。

13.5.4.4.4 PR120/D – WL-COM 模块这个模块基于PR122/P 保护脱扣器和一个掌上电脑或带蓝牙端口的膝上型电脑之间的蓝牙标准,实现无线通讯。

可参见15.4 章节模块描述。

13.5.4.4.5 本地总线单元设置如果PR021/K 被连接,通过选择“PRESENT”来激活本地总线。

13.5.5 测试菜单进入测试菜单需要输入密码。

菜单显示断路器的状态、储能状态和断路器位置,在其子菜单中,你也能使得断路器分闸或合闸。

使用“trip test”按钮,你能激活脱扣或关闭。

如果被激活,断路器将分闸。

这个功能仅仅在零母排电流情况下才可得到(使用V aux,PR030/B 或PR010/T)。

在这个界面上,你可使用Vaux 来查看断路器状态“status”,因而确保输入被正确连接。

浏览步骤请参见下表:13.5.5.1 测试菜单表参数/功能值注断路器状态分/合不确定自动测试脱扣测试激活/关闭PR120/D-M 模块储能状态储能/不储能断路器位置隔离/抽出断路器分闸断路器合闸PR120/K 模块输入ON自动测试区域选择性S 保护输入ON/OFF输出脱扣器输出G 保护输入ON/OFF 输出脱扣器输出13.5.6 信息菜单信息菜单可以看到与保护单元相关的数据和脱扣器类型:13.5.6.1 脱扣信息和分闸数据PR122/P 保存有关保护脱扣类型、分闸数据、日期和时间的所有信息。

使用“i test”按钮可以显示所有数据,勿需辅助供电电源。

如果有辅助供电电源,显示器将直接显示信息,勿需按“i test”按钮(显示将保持直到你按键盘)。

断路器分闸或没有任何电流流经母排时,48 小时内皆可得到信息。

脱扣器可保存最后20 次脱扣信息。

通过连接PR030/B 电池单元或BT030 无线通讯单元,你可检索最后20 次脱扣信息。

通过测量菜单中的Historical 子菜单可看到分闸数据,可参见下例:说明:由于保护和脱扣测试产生的分闸次数保护脱扣显示相、Ne 和G 电流值(如果G 功能已经导致脱扣)在测量菜单中,你能看到触头磨损百分比,它显示断路器触头电气寿命。

任何情况下,脱扣器功能不因触头磨损信息而改变。

预报警信息(大于80%,报警LED 亮)显示磨损已经达到一个很高的程度,报警信息(100%磨损,报警LED亮)显示需要检查触头磨损状态。

触头磨损百分比由断路器和绝对间断电流引起的分闸次数决定。

13.6 PR122/P 单元的报警和信号指示13.6.1 Led 信号信号指示描述警告黄色LED 亮. 预报警门限已被超过;一相或更多相电流范围在0.9*In< I <1.05*I1 (Ne 电流由选择模式决定;例如,在50%,表示为相电流的一半)。