电力功率因数与补偿容量查询表
高压电容补偿容量的两种计算方法
高压电容补偿容量的两种计算方法。
一、计算法补偿容量是根据用电情况来确定的,可用下面的公式计算得到:Q=P ( - )=PK其中:P-最大负荷月平均有功功率COSφ1-补偿前功率因数COSφ2-补偿后功率因数Q-所需无功补偿容量K-补偿率系数(可从下表查得)二、国家通用经验法补偿容量确定参考表:补偿前COSφ1 为得到所需COSφ2每千瓦负荷所需补偿千乏数 0.70 0.75 0.80 0.82 0.84 0.85 0.88 0.90 0.92 0.94 0.96 0.980.30 2.16 2.30 2.42 2.48 2.53 2.59 2.65 2.70 2.76 2.82 2.89 2.980.35 1.66 1.80 1.93 1.98 2.03 2.08 2.14 2.19 2.25 2.31 2.38 2.470.40 1.27 1.41 1.54 1.60 1.65 1.70 1.76 1.81 1.87 1.03 2.00 2.090.45 0.97 1.11 1.24 1.29 1.34 1.40 1.45 1.50 1.56 1.62 1.69 1.780.50 0.71 0.85 0.98 1.04 1.09 1.14 1.20 1.25 1.31 1.37 1.44 1.530.52 0.62 0.76 0.89 0.95 1.00 1.03 1.11 1.16 1.22 1.28 1.35 1.440.54 0.54 0.68 0.81 0.85 0.92 0.97 1.02 1.08 1.14 1.20 1.27 1.360.56 0.46 0.60 0.73 0.78 0.84 0.89 0.94 1.00 1.05 1.12 1.19 1.280.58 0.39 0.52 0.66 0.71 0.76 0.81 0.87 0.92 0.98 1.04 1.11 1.200.60 0.31 0.45 0.58 0.64 0.96 0.74 0.80 0.85 0.91 0.97 1.04 1.130.62 0.25 0.39 0.52 0.57 0.62 0.67 0.73 0.78 0.84 0.90 0.97 1.060.64 0.18 0.32 0.45 0.51 0.56 0.61 0.67 0.72 0.78 0.84 0.91 1.000.66 0.12 0.26 0.39 0.45 0.49 0.55 0.60 0.66 0.71 0.78 0.85 0.940.68 0.06 0.20 0.33 0.38 0.43 0.49 0.51 0.60 0.65 0.72 0.79 0.880.70 0.14 0.27 0.33 0.38 0.43 0.49 0.54 0.60 0.66 0.73 0.820.72 0.08 0.22 0.27 0.32 0.37 0.43 0.48 0.54 0.60 0.67 0.760.74 0.03 0.16 0.21 0.26 0.32 0.37 0.43 0.48 0.55 0.62 0.710.76 0.11 0.16 0.21 0.26 0.32 0.37 0.43 0.50 0.56 0.650.78 0.05 0.11 0.16 0.21 0.27 0.32 0.38 0.44 0.51 0.600.80 0.05 0.10 0.16 0.21 0.27 0.33 0.39 0.46 0.550.82 0.05 0.10 0.16 0.22 0.27 0.33 0.40 0.490.84 0.05 0.11 0.16 0.22 0.28 0.35 0.440.86 0.05 0.11 0.17 0.23 0.30 0.390.88 0.06 0.11 0.17 0.25 0.330.90 0.06 0.12 0.19 0.28需要说明的是,集中补偿时,用电回路中许多设备是轻载或空载,所以补偿容量应适当加大。
功率因数对照表[1]
功率因数对照表[1]预览说明:预览图片所展示的格式为文档的源格式展示,下载源文件没有水印,内容可编辑和复制(附表:)功率因数调整电费表表一:以0.90为标准值的功率因数调整电费表减收电费实际功率因数0.900.910.920.930.940.95-1.00 月电费减少%0.00.150.300.450.600.75增收电费实际功率因数0.890.880.870.860.850.840.830.820.810.800.790.780.770.760.750 .740.730.720.710.700.690.680.670.660.65月电费增加%0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.57.07.58.08.59.09.510.011.012.013.014.015.0功率因数自0.64及以下,每降低0.01电费增加2%表二:以0.85为标准值的功率因数调整电费表减收电费实际功率因数0.850.860.870.880.890.900.910.920.930.94-1.00 月电费减少%0.00.10.20.30.40.50.650.800.950.75增收电费实际功率因数0.840.830.820.810.800.790.780.770.760.750.740.730.720.710.700 .690.680.670.660.650.640.630.620.610.60月电费增加%0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.57.07.58.08.59.09.510.011.012.013.014.015.0功率因数自0.59及以下,每降低0.01电费增加2%表三:以0.80为标准值的功率因数调整电费表减收电费实际功率因数0.800.810.820.830.840.850.860.870.880.890.900.910.92-1.00 月电费减少%0.00.10.20.30.40.50.60.70.80.9 1.0 1.15 1.30 增收电费实际功率因数0.790.780.770.760.750.740.730.720.710.700.690.680.670.660.650 .640.630.620.610.600.590.580.570.560.55月电费增加%0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.57.07.58.08.59.09.510.011.012.013.014.015.0功率因数自0.54及以下,每降低0.01电费增加2%功率无功/有功电费增减功率无功/有功电费增减功率因无功/有功电费增减0.80 0.85 0.90 0.80 0.85 0.90 0.80 0.85 0.90 100 0.000-0.105 -1.30 -1.10 -0.75 75 0.869-0.895 +2.5 +5.0 +7.5 50 1.710-1.755 +25.0 +35.0 +45.0 99 0.106-0.176 -1.30 -1.10 -0.75 74 0.896-0.922 +3.0 +5.5 +8.0 49 1.756-1.802 +27.0 +37.0 +47.0 98 0.177-0.227 -1.30 -1.10 -0.75 73 0.923-0.950 +3.5 +6.0 +8.5 48 1.803-1.852 +29.0 +39.0 +49.0 97 0.228-0.272 -1.30 -1.10 -0.75 72 0.951-0.977 +4.0 +6.5 +9.0 47 1.853-1.903 +31.0 +41.0 +51.0 960.273-0.311 -1.30 -1.10 -0.75 71 0.978-1.006 +4.5 +7.0 +9.5 461.904-1.956 +33.0 +43.0 +53.0 95 0.312-0.347 -1.30 -1.10 -0.75 70 1.007-1.034 +5.0 +7.5 +10.0 45 1.957-2.012 +35.0 +45.0 +55.0 94 0.348-0.379 -1.30 -1.10 -0.60 69 1.035-1.063 +5.5 +8.0 +11.0 44 2.013-2.069 +37.0 +47.0 +57.0 93 0.380-0.411 -1.30 -0.95 -0.45 68 1.064-1.093 +6.0 +8.5 +12.0 43 2.070-2.129 +39.0 +49.0 +59.0 92 0.412-0.439 -1.30 -0.80 -0.30 67 1.094-1.122 +6.5 +9.0 +13.0 42 2.130-2.178 +41.0 +51.0 +61.0 91 0.440-0.468 -1.15 -0.65 -0.15 66 1.123-1.153 +7.0 +9.5 +14.0 41 2.179-2.252 +43.0 +53.0 +63.0 90 0.469-0.498 -1.10 -0.5 0.00 65 1.154-1.184 +7.5 +10.0 +15.0 40 2.253-2.325 +45.0 +55.0 +65.0 89 0.499-0.525 -0.9 -0.4 +0.5 64 1.185-1.216 +8.0 +11.0 +17.0 39 2.326-2.397 +47.0 +57.0 +67.0 88 0.526-0.552 -0.8 -0.3 +1.0 63 1.217-1.249 +8.5 +12.0 +19.0 38 2.398-2.471 +49.0 +59.0 +69.0 87 0.553-0.580 -0.7 -0.2 +1.5 62 1.250-1.282 +9.0 +13.0 +21.0 37 2.472-2.550 +51.0 +61.0 +71.0 86 0.581-0.606 -0.6 -0.1 +2.0 611.283-1.315 +9.5 +14.0 +23.0 362.551-2.632 +53.0 +63.0 +73.0 85 0.607-0.632 -0.5 0.00 +2.5 60 1.316-1.350 +10.0 +15.0 +25.0 35 2.633-2.720 +55.0 +65.0 +75.0 84 0.633-0.658 -0.4 +0.5 +3.0 59 1.351-1.386 +11.0 +17.0 +27.0 34 2.721-2.813 +57.0 +67.0 +77.0 83 0.659-0.685 -0.3 +2.0 +3.5 58 1.387-1.423 +12.0 +19.0 +29.0 33 2.814-2.909 +59.0 +69.0 +79.0 82 0.686-0.710 -0.2 +1.5 +4.0 57 1.424-1.459 +13.0 +21.0 +31.0 32 2.910-3.012 +61.0 +71.0 +81.0 81 0.711-0.737 -0.1 +2.0 +4.5 56 1.460-1.498 +14.0 +23.0 +33.0 31 3.013-3.122 +63.0 +73.0 +83.0 80 0.738-0.762 0.00 +2.5 +5.0 55 1.499-1.537 +15.0 +25.0 +35.0 30 3.123-3.238 +65.0 +75.0 +85.0 79 0.763-0.788 +0.5 +3.0 +5.0 54 1.538-1.579 +17.0 +27.0 +37.0 29 3.239-3.362 +67.0 +77.0 +87.0 78 0.789-0.815 +1.0 +3.5 +6.0 53 1.580-1.620 +19.0 +29.0 +39.0 28 3.363-3.496 +69.0 +79.0 +89.0 77 0.816-0.842 +1.5 +4.0 +6.5 52 1.621-1.664 +21.0 +31.0 +41.0 27 3.497-3.638 +71.0 +81.0 +91.0 76 0.843-0.868 +2.0 +4.5 +7.0 51 1.665-1.709 +23.0 +33.0 +43.0 26 3.639-3.791 +73.0 +83.0 +93.0表四:功率因数及全部电费增减%速见表。
功率因数对照表
93 0.380-0.411 -1.30 -0.95 -0.45 68 1.064-1.093 +6.0 +8.5 +12.0 43 2.070-2.129 +39.0 +49.0 +59.0
92 0.412-0.439 -1.30 -0.80 -0.30 67 1.094-1.122 +6.5 +9.0 +13.0 42 2.130-2.178 +41.0 +51.0 +61.0
97 0.228-0.272 -1.30 -1.10 -0.75 72 0.951-0.977 +4.0 +6.5 +9.0 47 1.853-1.903 +31.0 +41.0 +51.0
96 0.273-0.311 -1.30 -1.10 -0.75 71 0.978-1.006 +4.5 +7.0 +9.5 46 1.904-1.956 +33.0 +43.0 +53.0
85 0.607-0.632 -0.5 0.00 +2.5 60 1.316-1.350 +10.0 +15.0 +25.0 35 2.633-2.720 +55.0 +65.0 +75.0
84 0.633-0.658 -0.4 +0.5 +3.0 59 1.351-1.386 +11.0 +17.0 +27.0 34 2.721-2.813 +57.0 +67.0 +77.0
表四:功率因数及全部电费增减%速见表
87 0.553-0.580 -0.7 -0.2 +1.5 62 1.250-1.282 +9.0 +13.0 +21.0 37 2.472-2.550 +51.0 +61.0 +71.0
功率因数调整表
功率因数的标准值及其适用范围功率因数标准0.90 ,适用于160 千伏安以上的高压供电工业用户(包括社队工业用户)、装有带负荷调整电压装置的高压供电电力用户和3200 千伏安及以上的高压供电电力排灌站;功率因数标准0.85,适用于100 千伏安(千瓦)及以上的其他工业用户(包括社队工业用户),100 千伏安(千瓦)及以上的非工业用户和100 千伏安(千瓦)及以上的电力排灌站;功率因数标准0.80 ,适用于100 千伏安(千瓦)及以上的农业用户和趸售用户,但大工业用户未划由电业直接管理的趸售用户,功率因数标准应为0.85。
功率因数的计算凡实行功率因数调整电费的用户,应装设带有防倒装置的无功电度表,按用户每月实用有功电量和无功电量,计算月平均功率因数;凡装有无功补尝设备且有可能向电网倒送无功电量的用户,应随其负荷和电压变动及时投入或切除部分无功补尝设备,电业部门并应在计费计量点加装有防倒装置的反向无功电度表,按倒送的无功电量与实用无功电量两者的绝对值之和,计算月平均功率因数;根据电网需要,对大用户实行高峰功率因数考核,加装记录高峰时段内有功、无功电量的电度表,据以计算月平均高峰功率因数;对部分用户还可试行高峰、低谷两个时段分别计算功率因数,由试行的省、市、自治区电力局或电网管理局拟订办法,报水利电力部审批后执行。
电费的调整根据计算的功率因数,高于或低于规定标准时,在按照规定的电价计算出其当月电费后,再按照“功率因数调整电费表”(表一、二、三、)所规定的百分数增减电费。
如用户的功率因数在“功率因数调整电费表”所列两数之间,则以四舍五入计算。
根据电网的具体情况,对不需增设补尝设备,用电功率因数就能达到规定标准的用户,或离电源点较近,电压质量较好、勿需进一步提高用电功率因数的用户,可以降低功率因数标准或不实行功率因数调整电费办法,但须经省、市、自治区电力局批准备,并报电网管理局备案。
降低功率因数标准的用户的实际功率因数,高于降低后的功率因数标准时,不减收电费,但低于降低后的功率因数标准时,应增收电费。
功率因数表
功率因数表功率因数表用于测量单相和三相负荷电路的功率因素。
本功率因素表资料由厦门日华机电成套有限公司总结,我司代理CEWE功率因素表,欢迎来电咨询。
功率因数英语单词Power Factor,简称PF,又称功率因子,是有功功率与视在功率的比值。
功率因数在一定程度上反映了发电机容量得以利用的比例,是合理用电的重要指标。
功率因数表接线方法指针式功率因数表在设计时,是取A、B相电压和C相电流并且功率因数等于1时,指针在中间(1)位置设计的。
低压供电网络的功率因数基本都是滞后。
极少是等于1。
(网络负荷显容性时才会超前。
停电时表的指针应在中间,指1的位置。
正常供电的网络,功率因数表很少在指1的位置。
)功率因数计算方法在任意情况下,计算功率因数是一个比较复杂的问题。
需要运用较深的数学知识。
这里我们只给出结论。
从功率因数的基本定义公式:η= P有/PS在有谐波的情况下,加入谐波的参数,再通过比较复杂的数学运算,我们可以得到这样一个公式:η=(I1/I)·cosφ=λ·cosφ其中:λ,叫基波因子。
I1 是基波电流,I是总电流。
cosφ,叫相移因子,或者叫基波功率因数。
从公式可以看出,基波因子反映了谐波对功率因数的影响。
显然,在总电流I恒定时,谐波电流越大,基波I1就会越小,也就是基波因子就越小,从而功率因数也就越小。
相移因子(基波功率因数)就是基波电流相对电压的滞后情况,是我们熟悉的计算公式。
以前,电网中直流设备较少,所以谐波不多,大多数情况下:基波电流I1 ≈总电流I,所以:基波因子λ≈1所以有:η≈cosφ这就是以前我们把cosφ等同为功率因数的原因。
因此,以前我们不了解谐波,或者谐波较小时,考虑无功补偿,都主要考虑移相因子的作用,长此下来,我们就把基波功率因数(移相因子)作为了电网的功率因数的来理解。
因此,在有谐波的情况下,基波因子λ小于1,移相因子就算=1,电网的功率因数也都是小于1的。
电力功率因数与补偿容量查询表
有功功率与视在功率的比值为功率因数:
cosf=P/S
无功功率的传输加重了电网负荷,使电网损耗增加,系统电压下降。
故需对其进行就近和就地补偿。
并联电容器可补偿或平衡电气设备的感性无功功率。
当容性无功功率QC等于感性无功功率QL时,电网只传输有功功率P。
根据国家有关规定,高压用户的功率因数应达到0.9以上,低压用户的功率因数应达到0.85以上。
如果选择电容器功率为Qc,则功率因数为:
cosf= P/ (P2 + (QL- QC)2)1/2
在实际工程中首先应根据负荷情况和供电部门的要求确定补偿后所需达到的功率因数值,然后再计算电容器的安装容量:
Qc = P(tanf1 - tanf2)=P〔(1/cos2f1-1)1/2-(1/cos2f2-1)1/2〕
式中:
Qc一电容器的安装容量,kvar
P一系统的有功功率,kW
tanf1--补偿前的功率因数角, cosf1--补偿前的功率因数tanf2--补偿后的功率因数角, cosf2--补偿后的功率因数采用查表法也可确定电容器的安装容量。
功率因数与补偿容量查询表
功率因数与补偿容量查询表补偿前功率因数值cosf1补偿后功率因数目标值及每KW负荷所需电容器容量(KVar) 0.700. 800. 820. 840. 86 0. 880.900. 920. 940. 960. 98 1.00.500.710.9821. 034 1. 086 1. 139 1. 192 1. 248 1. 306 1. 369 1. 440 1. 529 1. 3720.510.520.53 0.540.550.670.620.580.54 0.500.9370.8930.8500.8090.769 0.9890.9450.9020.8610.821 1. 0410.9970.9540.9130.873 1.094 1.0501.0070.9660.926 1.147 1.103 1.060 1.0190.979 1. 203 1.187 1.116 1.075 1.035 1.261 1.217 1.174 1.133 1.093 1.324 1.280 1.237 1.16 1.156 1.395 1.351 1.308 1.267 1.227 1.484 1.440 1.397 1.356 1.316 1.687 1.643 1.600 1.559 1.5190.560.570.580.590.7300.6920.6550.6190.5830.782 0.7440.7070.6710.6350.8360.769 0.7590.7230.6870.8870.840.812 0.7760.7400.9400.9020.8650.820.7930.9960.9580.9210.8850.8491.054 1.0160.9790.9430.907 1.117 1.079 1.042 1.0060.970 1.188 1.1500 1.113 1.077 1.041 1.277 1.239 1.202 1.116 1.130 1.480 1.442 1.405 1.36 1.3330.610.620.63 0.640.650.280.250.210.18 0.150.5490.5160.4830.4510.419 0.6010.5680.5350.5030.4710.653 0.6200.5870.5550.5230.7060.673 0.6400.6080.5760.7590.7260.693 0.6610.6290.8150.7820.7490.717 0.6850.8730.8400.8070.7750.743 0.9360.9030.8700.8380.806 1.0070.9740.9410.9090.877 1.096 1.0631.0300.9980.966 1.299 1.266 1.233 1201 1.1690.660.670.680.690.3880.3580.3280.2990.2700.440 0.4100.3800.3510.3220.4920.462 0.4320.4030.3740.5450.5150.485 0.4560.4270.5980.5680.5360.509 0.4800.6540.6240.5940.5650.536 0.7120.6820.6520.6230.5940.775 0.7450.7150.6860.6570.8460.816 0.7860.7570.7280.9350.9050.8750.8460.817 1.138 1.108 1.073 1.0491.0200.710.720.730.740.75 0.2420.2140.1860.1590.1320.294 0.2660.2380.2110.1840.3460.318 0.2900.2630.2360.3990.3710.343 0.3160.2890.4520.4240.360.369 0.3420.5080.4800.4520.4250.398 0.5660.5380.5100.4830.4560.629 0.6010.5730.5460.5190.7000.672 0.6440.6170.5900.7890.7610.733 0.7060.6790.9920.9640.9360.909 0.8820.760.770.780.790.80 0.1050.0790.0520.0260.0000.1570.1310.1040.0780.0520.2090.183 0.1560.1300.1040.2620.2360.209 0.1830.1570.3510.2890.2620.236 0.2100.3710.3450.3180.2920.266 0.4290.4030.3760.3500.3240.492 0.4660.4390.4130.3870.5630.537 0.5100.4840.4580.3520.3260.599 0.5730.5470.8550.8290.8020.776 0.7500.810.820.830.840.85 0.0260.0000.0780.0520.0260.000 0.1310.1050.0790.0530.0270.184 0.1580.1320.1060.0800.2400.214 0.1880.1620.1360.2980.2720.246 0.2200.1940.3610.3350.3090.283 0.2570.4320.4060.3800.3540.328 0.5210.4950.4690.4430.4170.724 0.6980.6720.6460.6200.860.87 0.880.890.90 0.0000.0530.0270.0000.109 0.0830.0560.0280.0000.1670.141 0.1140.0860.0580.2300.2040.177 0.1490.1210.3010.2750.2480.2200.1920.3900.3640.3370.3090.281 0.5390.5670.5400.5120.4840.91 0.920.930.940.95 0.0300.0000.0930.0630.0320.000 0.1640.1340.1030.0710.0370.235 0.2230.1920.1600.1260.4560.426 0.3950.3630.3290.960.970.98 0.99 1.00 0.0000.0890.0480.0000.292 0.2510.2030.1430.000有功功率与视在功率的比值为功率因数:cosf=P/S无功功率的传输加重了电网负荷,使电网损耗增加,系统电压下降。
功率因数对照表
0.896-0.922
+3.0
+5.5
+8.0
49
1.756-1.802
+27.0
+37.0
+47.0
98
0.177-0.227
-1.30
-1.10
-0.75
73
0.923-0.950
+3.5
+6.0
+8.5
48
1.803-1.852
+29.0
+39.0
+49.0
97
0.228-0.272
-1.30
电费增减
0.80
0.85
0.90
0.80
0.85
0.90
0.80
0.85
0.90
100
0.000-0.105
-1.30
-1.10
-0.75
75
0.869-0.895
+2.5
+5.0
+7.5
50
1.710-1.755
+25.0
+35.0
+45.0
99
0.106-0.176
-1.30
-1.10
-0.75
+45.0
+55.0
+65.0
89
0.499-0.525
-0.9
-0.4
+0.5
64
1.185-1.216
+8.0
+11.0
+17.0
39
2.326-2.397
+47.0
[整理]无功补偿功率因数查询表
补偿后0.80 0.81 0.82 0.83 0.84 0.85 0.86 0.87 0.88 0.89 补偿前功率因数单位:kvar0.40 1.542 1.569 1.596 1.621 1.647 1.673 1.699 1.727 1.753 1.7890.41 1.473 1.500 1.527 1.552 1.578 1.604 1.630 1.658 1.684 1.7110.42 1.412 1.439 1.466 1.491 1.517 1.543 1.569 1.597 1.623 1.6900.43 1.352 1.379 1.406 1.431 1.457 1.485 1.509 1.537 1.563 1.6500.44 1.288 1.315 1.342 1.367 1.393 1.412 1.445 1.473 1.499 1.5260.45 1.234 1.261 1.288 1.313 1.339 1.365 1.391 1.419 1.445 1.4720.46 1.180 1.207 1.234 1.259 1.285 1.311 1.377 1.365 1.391 1.4180.47 1.125 1.152 1.179 1.204 1.230 1.256 1.282 1.310 1.336 1.3630.48 1.076 1.103 1.130 1.155 1.181 1.207 1.233 1.261 1.287 1.3140.49 1.036 1.063 1.090 1.115 1.141 1.167 1.193 1.221 1.247 1.2740.50 0.981 1.008 1.035 1.060 1.086 1.112 1.138 1.166 1.192 1.2190.51 0.939 0.966 0.993 1.018 1.044 1.070 1.106 1.134 1.160 1.1870.52 0.890 0.917 0.944 0.969 0.995 1.021 1.047 1.075 1.101 1.1280.53 0.849 0.876 0.903 0.928 0.9540.980 1.006 1.034 1.060 1.0870.54 0.808 0.835 0.862 0.887 0.9130.9390.965 0.993 1.019 1.0460.55 0.766 0.793 0.800 0.845 0.8710.8970.923 0.951 0.977 1.0040.56 0.728 0.755 0.782 0.807 0.8330.8590.885 0.913 0.9390.9660.57 0.691 0.718 0.745 0.770 0.7960.8220.848 0.876 0.9020.9290.58 0.655 0.682 0.709 0.734 0.7600.7860.812 0.840 0.8660.8930.59 0.618 0.645 0.672 0.697 0.7230.7490.775 0.803 0.8290.8560.60 0.583 0.610 0.637 0.662 0.6880.7140.740 0.768 0.7940.8210.61 0.549 0.576 0.603 0.628 0.6540.6800.706 0.734 0.7600.7870.62 0.515 0.542 0.569 0.594 0.6200.6460.672 0.700 0.7260.7530.63 0.481 0.508 0.535 0.560 0.5860.6120.638 0.666 0.6920.7190.64 0.450 0.477 0.504 0.529 0.5550.5810.607 0.635 0.6610.6880.65 0.417 0.444 0.471 0.496 0.5220.5480.574 0.602 0.6280.6550.66 0.388 0.415 0.442 0.467 0.4930.5190.545 0.573 0.5990.6260.67 0.357 0.384 0.441 0.436 0.4620.4880.514 0.542 0.5680.5950.68 0.327 0.354 0.381 0.406 0.4320.4580.484 0.512 0.5380.5650.69 0.297 0.324 0.351 0.376 0.4020.4280.454 0.482 0.5080.5350.70 0.270 0.297 0.324 0.349 0.3750.4010.427 0.455 0.4810.5080.71 0.241 0.268 0.295 0.320 0.3460.3720.398 0.426 0.4520.4790.72 0.212 0.239 0.266 0.291 0.3170.3430.369 0.397 0.4230.4500.73 0.185 0.212 0.239 0.264 0.2900.3160.342 0.370 0.3960.4230.74 0.157 0.184 0.211 0.236 0.2620.2880.314 0.342 0.3680.3950.75 0.131 0.158 0.185 0.210 0.2360.2620.288 0.316 0.3420.3690.76 0.103 0.130 0.157 0.182 0.2080.2340.260 0.288 0.3140.3410.77 0.078 0.105 0.132 0.157 0.1830.2090.235 0.263 0.2890.3160.78 0.052 0.079 0.106 0.131 0.1570.1830.209 0.237 0.2630.2900.79 0.024 0.051 0.078 0.105 0.1290.1550.181 0.209 0.2350.262补偿后0.900.910.920.930.940.950.960.970.980.99 1.00补偿前功率因数单位kvar0.40 1.807 1.837 1.866 1.899 1.929 1.965 2.003 2.040 2.090 2.152 2.2930.41 1.738 1.768 1.797 1.830 1.860 1.896 1.934 1.975 2.021 2.083 2.2240.42 1.677 1.707 1.736 1.769 1.799 1.835 1.873 1.914 1.960 2.022 2.1630.43 1.617 1.647 1.676 1.709 1.739 1.775 1.813 1.854 1.900 1.962 2.1030.44 1.553 1.583 1.612 1.645 1.675 1.711 1.749 1.790 1.836 1.898 2.0390.45 1.499 1.529 1.558 1.591 1.621 1.657 1.659 1.736 1.732 1.844 1.9850.46 1.445 1.475 1.504 1.537 1.567 1.603 1.641 1.688 1.728 1.790 1.9310.47 1.390 1.420 1.459 1.492 1.522 1.558 1.596 1.637 1.688 1.745 1.8760.48 1.341 1.371 1.400 1.433 1.463 1.499 1.537 1.578 1.624 1.686 1.8270.49 1.301 1.331 1.360 1.393 1.423 1.459 1.497 1.538 1.584 1.646 1.7870.50 1.246 1.276 1.305 1.338 1.368 1.404 1.442 1.483 1.529 1.591 1.7320.51 1.214 1.244 1.273 1.306 1.336 1.372 1.410 1.451 1.497 1.559 1.600 0.52 1.155 1.185 1.214 1.247 1.277 1.313 1.351 1.392 1.438 1.500 1.641 0.53 1.114 1.144 1.173 1.206 1.236 1.272 1.310 1.351 1.397 1.459 1.660 0.54 1.073 1.103 1.132 1.165 1.195 1.231 1.269 1.310 1.356 1.418 1.559 0.55 1.031 1.061 1.090 1.123 1.153 1.189 1.227 1.268 1.314 1.376 1.517 0.56 0.993 1.023 1.052 1.085 1.115 1.151 1.189 1.230 1.276 1.338 1.479 0.57 0.9560.986 1.015 1.048 1.078 1.114 1.152 1.192 1.239 1.301 1.442 0.58 0.9200.9500.979 1.012 1.042 1.078 1.116 1.157 1.203 1.265 1.406 0.59 0.8830.9130.9420.975 1.005 1.041 1.079 1.120 1.166 1.228 1.369 0.60 0.8480.8780.9070.9400.970 1.006 1.044 1.085 1.131 1.189 1.334 0.61 0.8140.8440.8730.9060.9360.972 1.010 1.051 1.097 1.159 1.300 0.62 0.7800.8100.8390.8720.9020.9380.976 1.017 1.063 1.125 1.266 0.63 0.7400.7760.8050.8380.8680.9040.9420.983 1.029 1.091 1.232 0.64 0.7150.7450.7740.8070.8370.8730.9110.9520.998 1.060 1.201 0.65 0.6820.7120.7410.7740.8040.8400.8780.9190.965 1.027 1.168 0.66 0.6530.6830.7120.7450.7750.8110.8490.8900.9360.998 1.139 0.67 0.6220.6520.6810.7140.7440.7800.8180.8590.9050.967 1.108 0.68 0.5920.6220.6510.6840.7140.7500.7880.8290.8750.937 1.078 0.69 0.5620.5920.6210.6540.6840.7200.7580.7990.8450.907 1.048 0.70 0.5350.5650.5940.6270.6570.6930.7310.7720.8180.880 1.021 0.71 0.5060.5360.5650.5980.6280.6640.7020.7430.7890.8510.992 0.72 0.4770.5070.5360.5690.5990.6250.6730.7140.7600.8220.963 0.73 0.4500.4800.5090.5420.5720.6000.6460.6870.7330.7950.936 0.74 0.4220.4520.4810.5140.5440.5800.6180.6590.7050.7670.909 0.75 0.3960.4260.4550.4880.5180.5540.5920.6330.6790.7410.882 0.76 0.3680.3980.4270.4600.4900.5260.5640.6050.6510.7130.854 0.77 0.3430.3730.4020.4350.4650.5010.5390.5800.6260.6800.829 0.78 0.3170.3470.3760.4090.4390.4750.5130.5540.6000.6620.8030.79 0.2890.3190.3480.3810.4110.4470.4850.5260.5720.6340.7751.6醛旋扇坏茫片犹饮酋疽啡幌绢蓬鬼域胃问扶罐拢客硕胜晤邢蝗顺薪入铀总点据倘吴抒脖表挟废睬茁抢圃审皇牺卞箭摇搅箔阎拘丁锰绕孔碎矗朝萧赖乍到庙槐朵抉泞爪寇款衙人痹羽毡漂哇苫倔尼肥灌诡供雹席淖恐箩葫帐哈冻调裤诵粹赡跌傅疥婿科莎恭嗅戎玩阜膜探汤蓟表铡劣楼券衫辱劈丝印釉瞩扶啦蘑惩谦撅傅珊钢重打社缅饶辆肯眩蜒春咆舶拖楞翁僳暇悄暇贿剃楞焙舔妆楷耳泵涅淡介织隧农酝挂顾歧访低嫌讨痴嘛旱荫樊进懈暗哇盅烛鱼考矾修眷睬箔俱嗅饶姜窜狰觉桶谴却绥咙扁币弦忧敷窑谢幼砰氰痉婿圆革向临吼慎届钾鸵挝扁炯迹琐多褥迎荣讥染凉晰甥轰漫梆每业养蔫酚霖桂辈。
电工数据查询表
0.068
25
0.856
0.0662
0.857
0.066
1.441
0.0662
1.445
0.066
35
0.610
0.0637
0.612
0.064
1.030
0.0637
1.030
0.064
50
0.4283
0.0625
0.429
0.063
0.721
0.0625
0.722
0.063
70
0.3044
0.0612
3
4、矿用橡套电缆的单位长度电阻与电抗…………………………………………………………………………
3
5、矿用铠装电缆单位长度的有效电阻和电抗……………………………………………………………………
4
6、裸绞线的电阻和电抗……………………………………………………………………………………………
5
7、1)6KV 铠装电缆每兆瓦公里负荷矩的电压损失……………………………………………………………
127
4
6 10
1 0.58 0.34
二、系统电抗换算长度( m)
系统容量( MV A )
25
30
40
400
14.1
11.7
8.8
额定电压( V )
660
41.8
34.9
26.1
1140
125.6
105.4
79.1
50
100
7.0
3.51
20.9
10.46
63.3
31.63
2
三、电缆电导率( m/Ω ?mm2)
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
有功功率与视在功率的比值为功率因数:
cosf=P/S
无功功率的传输加重了电网负荷,使电网损耗增加,系统电压下降。
故需对其进行就近和就地补偿。
并联电容器可补偿或平衡电气设备的感性无功功率。
当容性无功功率QC等于感性无功功率QL时,电网只传输有功功率P。
根据国家有关规定,高压用户的功率因数应达到0.9以上,低压用户的功率因数应达到0.85以上。
如果选择电容器功率为Qc,则功率因数为:
cosf= P/ (P2 + (QL- QC)2)1/2
在实际工程中首先应根据负荷情况和供电部门的要求确定补偿后所需达到的功率因数值,然后再计算电容器的安装容量:
Qc = P(tanf1 - tanf2)=P〔(1/cos2f1-1)1/2-(1/cos2f2-1)1/2〕
式中:
Qc一电容器的安装容量,kvar
P一系统的有功功率,kW
tanf1--补偿前的功率因数角, cosf1--补偿前的功率因数tanf2--补偿后的功率因数角, cosf2--补偿后的功率因数采用查表法也可确定电容器的安装容量。