电力系统的接地形式(图示)

合集下载
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

N

= N eutral Conductor

PE

= P rotection- E arth Conductor PEN

= P rotectitive- E arth- N eutral- Conductor T

= T erre = Earthing I

= I solation S

= S eparated Neutral and Protective Conductor C

= C ombined Neutral and Protective Conductor Abb. 6 TN-S-System

Abb. 7 TN-C System Abb. 8 TN-C-S System Abb.9 TT System Abb. 10 IT System

Network configuration Power systems Network configuration Network configurations are differed as per kind of – direct current, alternating current – “number of active conductors and the kind of earth connection” using the following characters: First letter: earthing of the current source (part 300, VDE 0100): T – direct earthing of a point I - insulation of all active parts of earth

or connection of a point with the earth via an impedance. Second letter: earthing of elements of electrical machine:

T – element is directly earthed, independent of the earthing of a point of a current source

N – element is directly connected to the operating earth electrode

(in networks of alternating voltage the earthed point is mostly the neutral point).

Further letters: arrangement of neutral conductor and protective conductor in the TN-system:

S – functions of neutral and protective conductor by separate conductors

C – functions of neutral and protective conductor combined in one conductor (PEN). In TN-systems a point is directly earthed (operating earth

electrode). The elements of the electrical machine are connected to this point via PE- or PEN-conductor.

Three types of TN-systems are to be differed (part 300, VDE 0100):

TN-S-system

- Separated neutral and protective conductor in the entire network (diagram 6)TN-C-system

- Functions of neutral and protective conductor are combined in the entire network in one conductor, the PEN- conductor (diagram 7).TN-C-S-system

- In one part of the network the neutral and the protective conductor are combined (PEN-

conductor) (diagram 8).

In the TT-system a point is directly earthed (operating earth electrode). The elements of the electrical machine are connected with earth electrodes, that are separated from the operating earth electrode (diagram 9).

The IT-system has no direct connection between active conductors and earthed parts. The elements of the electrical machine are earthed (diagram 10).