DPD火焰检测器说明书
DPD火检系统-培训
Sunman Control Engineering(Shanghai)Co.,Ltd.
2015-4-24
DPD探头的分类
DPD探头 光纤型IR, 带8芯插头,P/N 78195-74, 同:61-6625
DPD探头
DPD探头 DPD探头 DPD探头
光纤型IR, 带10芯插头,P/N 78195-05,
Sunman Control Engineering(Shanghai)Co.,Ltd.
2015-4-24
DPD技术规格
材料:压铸铝壳表面黑漆、防滑 电气要求:24VDC(可通过Forney放大器或者外部电源) 额定电流:100mA 温度:-4℉至+150℉-20℃至+65℃ 湿度:0—95%相对湿度,无凝结 重量:2.4lbs.(1.1Kg) 冷却空气:10m3@5Kpa直接看火,17m3@5Kpa光纤安装 认证:FM CE 传感器:紫外线型-超蓝硅元件/290-390nm 红外线型-硫化铅元件/700-2,500nm
Sunman Control Engineering(Shanghai)Co.,Ltd.
2015-4-24
远程通讯
Sunman Control Engineering(Shanghai)Co.,Ltd.
2015-4-24
远程通讯
默认文件值
Sunman Control Engineering(Shanghai)Co.,Ltd.
2015-4-24
编辑菜单
Sunman Control Engineering(Shanghai)Co.,Ltd.
2015-4-24
编辑菜单
缩略符 EDIT=YES EDIT=A COMM=0 FFRT=3 BFRT=3 OTD=2 TEMP=C F=GAS B=OFF AMP=5000 RFS=OFF AIM=60 编辑一个文件 选择一个文件去编辑 通讯地址 火焰熄火响应时间 背景火焰熄火响应时间 有火延时 火检内部温度 燃料种类 燃烧器种类 放大器类型 远程文件选择 扫描器瞄准装置 描述 Yes,No A,B,C,F 0-127 1-6秒 2-8秒(必须大于或等于FFRT) 2-4秒 Fahrenheit or Celsius华氏或摄氏 Gas,Other,Oil,Coal Off,Mech,Gun,LowNox,Cane,Ring,Bucket, Grate,其它。 5000,R900,2000,4000系列 OFF,ON,COMM 不可编程 允许值
火焰探测器安装使用说明书
〔安装、使用产品前,请先阅读本手册〕A710系列火焰探测器设计手册某某翼捷工业安防技术某某某某安誉智能科技某某一、工作原理火焰燃烧过程释放出紫外线、可见光、红外线,其中红外局部可分为近红外、中红外、远红外三局部.阳光、电灯、发热物体等均有热辐射,其辐射光谱随物体不同而不同,辐射光谱可能包括紫外线、红外线、可见光等如上图所示,自然界中按不同X围的波长分为紫外局部和红外局部,燃烧物体对应其不同波长的光谱,发出不同程度的辐射.火焰的闪烁频率为0.5Hz – 20Hz热物体、电灯等辐射出的紫外线、红外线没有闪烁特征通过检测火焰辐射出的紫外线来识别火灾0.18um-0.4um〔180nm-400nm〕太阳光中小于300nm的紫外线根本被大气层全部吸收,到达地球外表的紫外线都大于300nm优点:反响速度快缺点:易受干扰选用180nm-260nm的紫外传感器,对日光中的紫外线不敏感通过检测火焰辐射出的红外线来识别火灾红外线按照波长分为近红外、中红外、远红外空气中的气体〔如CO、CO2等〕对特定波长的红外线具有强烈的吸收作用选用两个波长的热释电红外传感器,来检测火焰辐射的红外线一个波长的热释电红外传感器用于检测含碳物质燃烧释放CO2引起的特定波长红外光谱的变化;一个波长的热释电传感器用于检测红外辐射的能量.两个不同波长的传感器向结合,有效区分发热体而非火焰释放的红外线,防止误报警.通过检测火焰辐射出的红外线来识别火灾.红外线按照波长分为近红外、中红外、远红外.空气中的气体〔如CO、CO2等〕对特定波长的红外线具有强烈的吸收作用.选用三个波长的热释电红外传感器,来检测火焰辐射的红外线两个波长的热释电红外传感器用于检测物质燃烧引起的两个特定波长X围的红外光谱的变化;一个热释电传感器用于检测红外辐射的能量.三个不同波长的传感器向结合,有效区分发热体而非火焰释放的红外线,防止误报警.通过检测火焰辐射的紫外线和红外线来识别火灾通过增加判据,提高探测可靠性.发热物体可以辐射出红外线,一般的低温物体通常不会辐射紫外线.只有火焰既辐射出紫外线,又辐射出红外线含碳物质燃烧发出的辐射在特定波长〔4.3um〕与热物体辐射的红外线具有明显区分,根据次区分,双波长可提高红外探测的可靠性.增加紫外探测判据,更大幅度提高探测可靠性如果没有外部辐射红/紫外线的物体存在,火焰探测器没有任何的响应.同理,如果火焰探测器没有设置主动红外辐射装置,火焰探测器就难以实现污染检测.上图可以看出,同一物体发出的红外辐射能量是一样的,但是假如处于不同的辐射角度,到达红外传感敏感源的能量是不同的,其关系相当于几何上的余弦函数〔COS〕关系,例如当辐射角度为0度〔垂直辐射〕时假如辐射能量为A,如此辐射角度为60度〔斜射〕时辐射能量为cos60 *A=A/2.这就是为什么所有的红外探测器的监视X围为什么为是抛物线锥体而不是等圆锥体的原因.二、性能特点通过特定的传感器选型、火焰识别技术、软件算法,使得活火焰探测器对日光、电弧焊、人工光源、热辐射、电磁干扰等具有极强的防误报警能力.能够有效识别背景噪声,结合软件算法,对火焰辐射敏感.3.自适应、自检测功能可靠的故障自诊断,自动根据探测窗口污染情况调节探测灵敏度轴线探测距离长〔最长大60米〕、监视角度大〔120度〕,保护X围大.防尘、防水、防爆,适用于各种恶劣环境.IP65EX dII CT6,DIP A20 TA.T6<粉尘防爆>火警、故障继电器输出,方便与各种报警系统配合使用灵活的视角调节方式探测器在日常使用一段时间后,需进展清洗维护工作,一般可直接用水清洗,对存在油污等情况下可直接用酒精清洗外监视窗口,无需专人、专用工具.三、技术参数四、适用场合1. A710火焰探测器系列产品分为普通场合应用和防爆场合应用两类产品.防爆型产品均在产品外壳的标签上标注产品防爆等级参数.没有标注防爆等级的产品只能用于没有防爆要求的普通场合,不能在有防爆要求的场所使用,有防爆要求的场所必须使用带有防爆等级标志的防爆型产品.2. A710 火焰探测器标准型产品的工作温度X围为0°C -50°C,超出此工作温度X围的使用应选用温度增强型产品,增强型产品的工作温度X围为-40°C -70°C.用户需要防爆型产品和温度增强型产品须在产品订货单上明确标明.3. A710系列火焰探测器的主要适用特点A710/IR2双波长红外火焰探测器适用于无烟液体和气体火灾以与产生烟的明火火灾探测,诸如含碳材料的明火燃烧〔木材、塑料、酒精、油类产品、气体等〕,具有探测灵敏度高、保护面积大、安装使用方便、防尘、防水和抗电磁干扰等特点;不适用于对某些化学物质〔如磷、钠、镁、硫、氢等物质〕燃烧的探测.A710/UV紫外火焰探测器既可以监测碳氢化合物火焰〔汽油、丙烷、甲烷、酒精等〕也可以识别非碳氢化合物火焰〔氢气<Hydrogen>, 硅烷〔Silane〕,肼〔Hydrazine〕, 镁〔Magnesium〕等〕.但不适用在经常产生焊接弧光、电弧的场所使用,也不适于在闪电光下暴露的场合使用.A710UV/IR2火焰探测器从根本上解决了紫外传感器容易受到闪电、电焊弧光、X射线等因素影响和红外传感器容易受到工业照明、太阳光、闪烁或移动的发热物体等因素的影响而造成探测器误报警的问题,适用于有较高火焰监测要求的各种场合.A710/IR3三波长红外火焰探测器适用于无烟液体和气体火灾以与产生烟的明火火灾探测,诸如含碳材料的明火燃烧〔木材、塑料、酒精、油类产品、气体等〕,具有探测灵敏度高、保护面积大、安装使用方便、防尘、防水和抗电磁干扰等特点;不适用于对某些化学物质〔如磷、钠、镁、硫、氢等物质〕燃烧的探测.该探测器具有极高的敏感性和大X围的探测能力,而且对错误报警还有最高的免疫力.包含三个窄带红外传感器和光学过滤器,对CO2发射光谱具有最高的灵敏性.大的探测X围意味着在某些特定区域所需探测器的数量减少,能极大的节约设备和安装本钱.4.适用特殊场所和防爆场合隧道、电厂;军需品、爆炸仓库;印刷企业;硅烷;化学制品装载区;非碳氢化合物〔氢气<Hydrogen>, 硅烷〔Silane〕,肼〔Hydrazine〕, 镁〔Magnesium〕等〕生产、储运;油、气、石化产品生产厂危险品仓库以与可燃物含碳物质的其他场合等.大空间、高蓬顶建筑物体育馆、剧院、电影院、仓库、飞机库、停车场、站台、地下室等.重要物品保管场所和文化财产建筑物电脑机房、档案室、博物馆、文化遗产建筑物、数据保管库等.五、设计方案➢取决于保护场所灵敏度要求➢取决于保护场所可能出现的火源情况➢可能出现的火源类型➢可能出现的火源大小用一只探测器监视房间<适用于中等大小的空间,边长小于42米,对角线小于60米> 用两只探测器监视房间<适用于方形较大空间,最大边长小于42米、对角线距离大于60米> 用两只探测器监视房间<适用于狭长空间,窄边小于42米,长边大于42米,小于84米>用四只探测器监视房间〔适用于超大空间,最大边长小于84米,对角线距离小于120米〕正视图侧视图俯视图六、安装指导A710火焰探测器配有固定安装支架,现场安装非常方便,探测器使用24V供电,输出信号接口的标准配置为一个继电器常开触点,其他方式的接口作为可选配件提供.➢选择恰当的安装角度,防止探测盲区.考虑到被保护区域的空间结构不同,红外火焰探测器的监视X围为抛物线锥体,其轴线方向探测距离最长.因此,在安装时应将红外火焰探测器的轴线方向正对〔或背对〕被保护区的方向,这样,使得红外火焰探测器的有效监视X 围覆盖危险的探测区域,防止探测盲区.➢选择恰当的安装高度,防止因障碍物引起的探测盲区.当被保护物体具有相当高度,容易造成遮挡等情况下,因此,为防止障碍物的遮挡,应尽量提高火焰探测器的安装高度,以俯视状态监视探测区域,能够最大限度地减少障碍物造成的探测盲区.➢探测器应该对警戒区内各可能发生的火灾均保持直接入射,尽量防止间接入射和反射.➢在探测器的有效探测X围内,不能受到障碍物的阻挡,其中包括玻璃等透明的材料和其他隔离物 .6.火焰探测器的安装方式图七、设备接线1.接线端子定义,接线端子如下:,FLD为公共端、FLK为常开端、FLB为常闭端,<负载能力2A/30VDC>FRK/FRD/FRB 火警继电器的触点输出,FRD为公共端、FRK为常开端、FRB为常闭端,<负载能力2A/30VDC>GND 可复位供电电源负极﹢24V可复位供电电源正极➢所有信号线均采用Rvs-2×1.5mm线,信号电缆要走单独缆架与动力电缆隔开.➢布线施工应当严格依据设计图纸.➢导线应当穿入金属电线管.➢施工中应当注意不要将导线的外皮拉破.➢导线的连接处应当焊接,采用绝缘包装处理,也可以采用专用夹件连接.➢导线之间、导线和电线管之间的绝缘阻抗应当达到20兆欧.八、探测器灵敏度设定火焰探测器分三级灵敏度,针对由近到远的三个探测距离分别对应3级、2级、1级灵敏度.通过磁铁吸合探测器前段的灵敏度调节用干簧管,可现场调节探测器灵敏度,根据上电期间显示灯的闪烁频率,可查看当前灵敏度.标准出厂产品灵敏度设置为3级灵敏度,用户可根据现场情况修改探测器灵敏度,假如有其他灵敏度要求须在订货单上说明.九、与火灾报警系统连接火焰探测器可以任意厂家的消防火灾报警控制系统连接,通过输入模块,将火焰探测器的火警、故障等信号传送至火灾报警控制系统.如如下图所示:十、维护与保养探测器报警测试建议每个月对火焰探测器进展一次报警试验,使用专用的报警信号发生器,距离探测器探测窗口10cM的地方〔场所允许的情况下可使用打火机近距离点燃测试〕,启动报警信号发生器,探测器应该能在大约10秒钟左右报火警.探测器窗口污染清理需经常检查探测器探测窗口外表积灰和受污染情况,建议每个月对探测器镜头进展清洗,可以用酒精和清水擦洗.用户不得自行拆卸探测器,当探测器出现问题,应向供货商咨询相应的处理方法,必要时应返回生产厂家进展维护或维修.十一、故障分析、排除十二、运输、储存探测器在运输、储存、安装、调试、维护过程中要轻拿轻放,防止跌落、碰撞、挤压、摩擦等情况造成损伤.我们将尽力确保产品资料的准确和与时更新,本手册不能涵盖所有的具体应用和表现产品所有的技术特性.由于产品与技术的进步,个别细节可能变化而毋需事先通知.如需要更多或更新的资料,请联系我公司.某某翼捷工业安全公司:021-********:021-********:201204地址:某某浦东莲溪路1210号3号楼。
火焰色谱仪使用说明书
火焰色谱仪使用说明书一、简介火焰色谱仪是一种常用的分析仪器,适用于气体和液体样品的分析。
本说明书将详细介绍火焰色谱仪的结构、工作原理、操作方法以及维护保养等内容,以帮助用户正确使用该仪器。
二、结构与原理1. 结构火焰色谱仪主要由供气系统、进样系统、火焰系统、检测系统、数据处理系统等部分组成。
2. 工作原理火焰色谱仪通过样品的分离与检测来定量或定性分析物质的成分。
样品在进样系统中蒸发并进入火焰系统燃烧,物质在火焰中产生特定的发射光谱。
检测系统测量并记录这些光谱信号,通过数据处理系统进行分析和结果显示。
三、操作方法1. 准备工作a. 确保火焰色谱仪与电源连接正常,并打开主电源开关。
b. 检查气体供应系统是否正常,如氢气、空气、燃料气等供应是否充足。
c. 打开数据处理系统,确保仪器与计算机的连接正常。
2. 样品进样a. 将待测样品按要求制备好,保证其纯度和溶解度符合分析要求。
b. 将样品注入进样器,并设置进样体积、进样速度等参数。
c. 样品进入火焰系统进行燃烧分析。
3. 仪器运行a. 确保火焰色谱仪的各项参数符合分析要求,如温度、流速等参数的设置。
b. 启动火焰系统,使火焰稳定并选择合适的火焰类型。
c. 启动检测系统,调节检测器灵敏度,并实时监测和记录检测信号。
四、维护保养1. 定期检查气体供应系统,确保气源充足且气体供应管道畅通。
2. 定期清洗进样系统和火焰系统,防止污染和堵塞。
3. 校准和维护检测系统,确保仪器的准确性和灵敏度。
4. 确保仪器的周围环境干燥、无尘,并保持通风良好。
五、故障排除在使用火焰色谱仪时,可能会遇到一些常见问题,如信号不稳定、噪声过大等。
以下是一些可能的原因和对应的解决方法:1. 检查气源是否正常,确保气体供应充足。
2. 检查进样系统是否清洁,清洗进样器和样品枪等部件。
3. 检查火焰系统温度是否正常,调节并稳定火焰。
4. 检查检测器是否正常,校准或更换检测器。
六、安全事项在使用火焰色谱仪时,请务必注意以下安全事项:1. 确保仪器接地良好,避免因静电产生的安全隐患。
油火检探头说明书
4.2 火焰检测系统我厂用的火焰监示系统包括FORNEY 公司生产的DPD(数字剖面)火焰检测器和DP 7000 数字剖面放大器,4.2.1火焰检测器1)概述 FORNEY 公司生产的数字剖面火焰监测器(简称DPD 火检)可用于鉴别单燃烧器或多燃烧器燃烧环境中目标火焰的存在于否。
DPD 火焰检测器采用了微处理器技术和专用软件,对目标火焰的频率和振幅特性不断地进行监测。
每个火焰有其独特的剖面特性,就犹如“指纹”一样。
在“学习”模式下,DPD 火检对目标火焰交流信号的频谱进行实时分析以确定被监测火焰的类型(如:燃烧器有火、相邻燃烧器窜火、背景火焰、无火)以及火焰频谱的特定剖面形状;在“运行”模式下,火焰检测器则不断地将目标火焰信号与所学的剖面特性进行比较从而准确地判断火焰的状态。
2)特点:智能显示——用于快速设置、精确瞄准以及火焰信号显示。
八位持续滚动的LED 显示提供火检所有设定值和火焰状况的瞬时读数显示。
编程简单可靠按钮键盘可直接对火检进行编程和显示。
但是为了避免未经授权的参数改动,在火检的后盖板下面装有编程驱动”Program Enable”锁定按钮。
灵活的运行参数可选择火焰熄火响应时间(FFRT):2-6 秒可选择背景火焰熄火响应时间(BFRT):2-8 秒可选择有火信号延时:2-4 秒可选择华氏或摄氏温度显示适用于任何结构的燃烧器适用于低Nox、枪式、摆动式、棒式、环式、层燃式等结构的燃烧器。
适用于任何燃料Super-blue 型DPD 火焰检测器可适用于大多数燃料的火焰监测,而Classic 型DPD 火检适用于煤/油的火焰,我厂所用是Classic 型DPD 火检。
在摆动式燃烧器或者空间受限制的应用中可选用光纤光纤可穿过拥挤的燃烧器空间使火焰检测器实现远程安装。
串行通讯——对火焰参数进行直接、实时的监测和分析通过RS485 接口将参数上载/下载至计算机或其它智能设备。
24 伏直流工作电压3). 安装概述:⑴. 用转动安装接头和六角螺钉将DPD 火检安装好。
FORNEY UNIFLAME火检说明书 一体式
UNIFLAME一体化火焰检测器模件IR/UV/DS概述FORNEY UNIFLAME系列火焰检测器是基于微处理器设计的火焰检测器,采用了固态的红外传感器(IR)、紫外传感器(UV)和双传感器(IR+UV)。
检测器均带有内部火焰继电器,并可调整 ON/OFF 门槛值,因此不需要远程火焰放大器。
UNIFLAME系列检测器兼有FORNEY DPD火焰检测器的原理和特性,可以检测单燃烧器或多燃烧器工况下目标火焰的有或无。
UNIFLAME系列检测器检测目标火焰产生的调制振幅(即火焰的闪烁特性)。
在检测器的设定程序中,选择可产生最佳火焰ON/OFF分辨率的调制频率特性。
并可手动调节或自动调节来选定合适的调制频率和检测器增益。
UNIFLAME 系列检测器带有自动编程(自学习)功能;21种火焰闪烁频率选择;4个可选编程文件来存储设定值;还增加了通过使用FORNEY基于WINDOWS95/98/NT的用户应用软件的远程通讯功能。
所有的UNIFLAME检测器均需要24VDC电源,配有12芯快装接头,有电子自检功能(不再需要机械快门)。
检测器带有一个8位数字/字母LED显示和4个按钮,便于使用者观察操作参数和选择设定值。
目录概述 (1)目录 (2)运行 (3)UNIFLAME检测器特征 (3)应用 (3)尺寸 (4)技术规格 (4)安装注意事项: (5)安装程序 (5)检测器安装附件 (7)机械辅件 (8)电气辅件 (9)检测器接线 (10)远程文件选择 (11)装配说明快装接头 (12)远程通讯接线 (14)通讯接线盒的使用 (15)接地和屏蔽技术 (17)UNIFLAME检测器的编程 (18)UNIFLAME菜单结构 (18)状态菜单 STATUS MENU (20)编辑菜单 (23)文件复制描述 (28)错误讯息 (28)手动设置编辑菜单 (29)自动调谐菜单 (30)探头设定程序Scanner Set-up Procedure(适用于所有型号) (33)错误信息 (34)注意 (35)WARRANTIES (35)运行UNIFLAME检测器测量目标火焰产生的振幅频率。
FORNEY DPD火焰检测器的应用
—
fi7 I。c 6。1 L
V I 1
Q9
一
~
o 0
X啦 ! o — —
ol叶
o 0 3l — 一321: 一 l Ld 。f。L —
。
~
儿
几。
n D匹
一
1 sQ5 0 平台降
、】21 2
7
—
——ຫໍສະໝຸດ _ —’ 。 平台磁
U -一
s 平台械
张 海 燕 , 白建 云
(太原 电力 高等 专科 学校 信 息系 , 山西 太 原 030013)
摘 要 :火焰检测器是 锅炉炉膛安全监控和灭 火保 护 的关键环 节。FORNEY公 司生产的DPD型火焰检测器在 过 程控制 中取得 了较好 的检 测效果 ,主要介绍其检测原理 、机械安装及编程步骤。 关键词 :火焰检测 ;DPD;红外光 中 图分 类 号 :TK223.6 1 文献 标 识 码 :B
(4) 必须考 虑 到燃烧 器 二次风 的旋 转 (一 些 燃烧 器具 有顺 时针空气旋 转 ,而其他 则是逆 时针旋 转)。如 果燃 烧 器空气 以较 高速 度 的旋转运 动 进入 锅炉 时 ,足 以使 点火器 的火 焰在旋 转方 向上发生偏 转 ,则 需将检 测器定位于点火器下风 向的 10。~3O。位置 ,并使检测 器和点火器位于 以主燃烧器为中心 的圆周上 ,见图 3。
立新文 件 、存储 、执行 此文件 ,实现 DPD的编程 ,该 文件包 含 了其配 置 的设 定及 “学 习 ”到 的火 焰 形态 。 在 DPD中安装 了一个 厂家缺 省文件 “F”,以此作 为出 发 点 ,其他 3个用户 可配 置的文件 A、B、C可 由用户 来创 建 、存储 、加 载 、编辑 。文件 存储在 非易失性存 储器 (E2PROM)中,不需设置后 备 电池 。
火焰试验仪操作说明书
火焰试验仪操作说明书一、操作流程1. 准备工作:在进行火焰试验前,确保环境安全,并进行以下准备工作:- 检查火焰试验仪是否处于正常工作状态。
- 确保试验室或工作场所通风良好。
- 确认试验仪器已经连接电源,并检查电源电压是否与试验要求相符。
2. 开机与校准:- 按下电源按钮启动火焰试验仪,待指示灯亮起。
- 进行校准操作,将试验仪器调整至标定状态,并确保准确度达到要求。
3. 样品准备:- 根据试验要求,选择合适的样品,并确保其表面清洁干燥。
- 若需对样品进行预处理,请按照相应的预处理要求进行操作。
4. 开始试验:- 将样品放置于试验仪器适当的位置,确保样品与火焰点火装置的距离符合要求。
- 调节试验参数如火焰高度、时间等,按下开始按钮。
5. 结束试验:- 在试验结束后,按下停止按钮,火焰试验仪停止工作。
- 将样品从试验仪器中取出,进行下一步处理或评估。
二、操作注意事项1. 安全操作:- 在操作火焰试验仪时,务必遵循相关的安全操作规程。
- 避免在无专业指导或经验不足的情况下操作试验仪器。
2. 维护与保养:- 定期检查试验仪器的工作状态,并进行必要的维护与保养。
- 清洁试验仪器的外部表面,并定期清理试验仪器内部的灰尘等杂物。
3. 试验参数设置:- 根据具体试验要求,正确设置试验仪器的参数。
- 每次试验前,确保参数设置符合试验要求,并与相关标准进行验证。
4. 数据记录与分析:- 在试验过程中,及时记录与保存试验数据。
- 对试验数据进行合理的分析与评估,为后续工作提供参考。
三、故障排除1. 无法启动:- 检查电源连接是否正常。
- 确认电源开关是否关闭或损坏。
- 检查电源电压是否正常,并确保符合试验仪器要求。
2. 火焰不稳定:- 检查试验仪器与样品的距离是否符合要求。
- 检查火焰点火装置是否损坏或堵塞。
- 清洁试验仪器中的灰尘或杂物。
3. 数据异常:- 检查数据记录仪器是否正常工作。
- 确认试验参数设置是否准确。
火焰光度计使用说明书
火焰光度计使用说明书使用准备:1. 确保火焰光度计已经连接电源,并处于正常工作状态。
2. 确保火焰光度计与待测试的火焰源之间没有任何障碍物,以避免干扰光线的传输。
测量操作:1. 打开火焰光度计,并等待其进行自检程序,确保仪器正常工作。
2. 将待测试的火焰源放置在火焰光度计的测量范围内,并确保火焰源与仪器的光线传感器保持一定的距离。
距离应根据具体情况进行调整,以确保测量结果的准确性。
3. 按下火焰光度计上的测量按钮,开始测量火焰源的光度。
4. 仪器将会自动记录测量结果,并显示在屏幕上。
同时,还可以将测量结果保存在内存中供之后的分析使用。
5. 对于不同的火焰源,可以选择不同的测量模式,以获得更准确的测量结果。
请参考火焰光度计的用户手册,了解各个测量模式的具体用途和使用方法。
数据分析与处理:1. 火焰光度计可以提供一些基本的数据分析和处理功能,以帮助用户更好地理解测量结果。
用户可以通过仪器上的按键或触摸屏来访问这些功能。
2. 数据分析功能包括峰值检测、光强曲线绘制等。
用户可以根据需要选择相应的功能,并根据屏幕上的指引进行操作。
3. 火焰光度计还可以将测量结果导出至计算机,以便进行更复杂的数据处理和分析。
用户需要连接计算机与仪器,并按照软件指引来完成数据的导出操作。
注意事项:1. 使用过程中,请勿将火焰光度计暴露在过高的温度下,以免损坏仪器。
2. 在测量前,请确保火焰源已经稳定燃烧,并尽量保持其不受外界干扰。
3. 在进行测量时,应尽量避免其他光源的干扰,以确保测量结果的准确性。
4. 定期清洁仪器的光线传感器和光学系统,以保持仪器的灵敏度和测量精度。
故障排除:1. 若火焰光度计无法正常启动或显示异常,请先检查电源连接是否正确,并尝试重新启动仪器。
2. 若上述方法无效,请参考用户手册中的故障排除部分,按照指引进行故障的排查与处理。
封存与保养:1. 当您不再需要使用火焰光度计时,请将其关机,并拔掉电源线。
2. 将仪器放置在干燥、通风的地方,并保持仪器表面的清洁。
DPD火检编程步骤
DPD火检调试作业指导1:概述FORNEY公司DPD系列是基于微处理器的火焰检测器,可用于鉴别单燃烧器或多燃烧器燃烧环境下的目标火焰的有无。
为提高检测的准确性,DPD火检在设计上采用“二合一”的方式,即DPD火检放大器可以同时连接A、B两个DPD火检探头,可以同时接收、单独或混合处理来自A、B两个DPD火检探头的信号,输出一路火焰信号和火检状态信号到DCS。
DPD系列火检具有先进的联网通讯功能,可以通过双绞通讯线连接1-128个火检探头,通过远程PC机对在线探头进行各项参数设置和“有火”、“无火”的学习。
其友好的软件界面和简单的操作大大降低了火检调试工作的难度。
2:调试上电前的准备工作上电主要指给DPD放大器柜电源上电。
在系统上电之前,应对柜内各组件进行检测,应做的工作如下:1:检查柜内有无脱落的螺栓、螺母及其他异物。
2:检查柜内各接线端有无脱落、松动。
3:检查各接地端是否合理、可靠。
4:将柜内各电源开关闭合,根据设计,用万用仪表检测各组电源的输入、输出端有无短路等异常现象。
5:将各火检放大器卡件拔出至和底座不接触。
6:检查放大器电路板上短接线设置。
7:将柜内各电源开关断开。
8:逐一闭合各电源开关。
9:逐一插入并固定各放大器卡件。
3:DPD火检编程步骤第一步:按下Program Enable按钮使火检置于Setpoints Menu (设定值菜单)状态。
第二步:选择所要编辑的文件。
第三步:根据燃料类型、燃烧器类型以及其它运行参数进行初步设定。
第四步:AIM(瞄准)火检。
第五步:进行有火(FLAME ON)特征学习。
第六步:进行无火(FLAME OFF)特征学习(只在多燃烧器应用中需要)。
第七步:保存文件第八步:运行文件具体如下:第一步将火检置于编程模式:当火检通电以后,按下Program Enable按钮,首次显示的编程菜单为EDIT NO。
按下Change键使显示为EDIT YES,然后按下Advance键使编程继续。
DPD火焰检测器说明书
安装转动接头 火检安装转动接头,部件号:7819567,用于火检安装后调整火检的视角。
孔板 孔板用于限制目标火焰区域的视角范围,减少气流,维持空气滞留以提高灵敏度。孔板是用 孔板固定圈来固定于转动安装接头球内的。可购买孔板套件,部件号为 4201626304。
火检瞄准火焰区域的理想范围应为目标火焰前沿截面积为 8-25 平方英寸(50-150cm2)处。 火焰前沿为燃烧空间中的一个区分未燃尽燃料和燃尽燃料区域的平面。例如:如果一个直径 为 1/2”的孔板置于距探头透镜 1 英尺的安装接头球中,而转动接头位于 4 英尺深的燃烧器 上,而且如果稳定火焰范围为燃烧器风箱外 5 英尺,那么火焰前沿的目标区域为 19.6 平方 英尺,如图 5 所示。注意:鉴别力与灵敏度之间存在着反向的关系。
- 6-
-
美国FORENY公司中国工程服务中心
向下倾斜安装以免垃圾和灰尘在管中聚集。 火焰检测器探头通过 LED 显示的反馈信息来调整安装角度。请参阅“DPD 火检编程” 章节中的 AIM(瞄准)功能。
图4
7、 经运行测试并对 AIM 功能的设定,证实已获得满意的瞄准角度后,拧紧转动安装接头 圈上的六角螺钉使转动球固定。
- 1-
-
美国FORENY公司中国工程服务中心
- 适用于任何结构的燃烧器 适用于低 Nox、枪式、摆动式、棒式、环式、层燃式等结构的燃烧器。
- 适用于任何燃料 Super-blue 型 DPD 火焰检测器可适用于大多数燃料的火焰监测,而 Classic 型 DPD 火 检适用于煤/油的火焰。
- 在摆动式燃烧器或者空间受限制的应用中可选用光纤 光纤可穿过拥挤的燃烧器空间使火焰检测器实现远程安装。
8、 为便于使用,火焰检测器探头应安装在观察管上以便读取 LED 显示。如果无法这样做, 安装火检探头时应将快装接头面向下。(LED 显示不受安装位置的限制)。
火焰测试仪使用方法说明书
火焰测试仪使用方法说明书一、概述火焰测试仪是一种用于测试材料燃烧性能的仪器,广泛应用于各个行业中。
本说明书将详细介绍火焰测试仪的使用方法,旨在帮助用户正确操作并获得准确的测试结果。
二、使用环境1. 温度:火焰测试仪的使用环境温度范围为5℃至40℃。
2. 湿度:相对湿度不超过85%,避免长时间暴露在潮湿环境中。
3. 电源:220V交流电源,确保电源供电稳定。
4. 平稳台面:将火焰测试仪放置在平稳的台面上,确保其稳定性和安全性。
三、仪器操作1. 打开火焰测试仪:先检查电源线和仪器连接是否正常,再插入电源,并确保电源开关处于关闭状态。
然后按下电源开关,等待仪器启动。
2. 等待预热:仪器需要预热一段时间,待温度稳定后开始进行测试。
通常,预热时间为15分钟至30分钟。
3. 准备测试样品:根据测试要求准备好需要测试的样品,并确保其形状和尺寸符合仪器测试要求。
4. 安装样品:小心地将待测试样品安装在火焰测试仪上,并确保样品与仪器之间没有明显的间隙。
5. 设置测试参数:使用仪器上的控制面板来设置测试参数,如火焰高度、时间等。
根据样品的要求和测试标准,调整参数至合适的数值。
6. 开始测试:确认设置的参数正确无误后,按下开始测试按钮,观察测试过程并记录相应的数据。
7. 结束测试:当测试时间到达设定值后,按下停止测试按钮,等待仪器停止并显示测试结果。
8. 关闭火焰测试仪:将电源开关置于关闭状态,拔掉电源线,待仪器冷却后可以移动或存放。
四、注意事项1. 使用过程中,避免将手指或其他物体靠近测试区域,以免发生意外。
2. 在测试过程中,及时观察仪器状态,如有异常情况出现,应立即停止测试并检查原因。
3. 尽量选择空气流通良好的环境进行测试,避免有害气体积聚。
4. 在使用过程中,请勿将火焰测试仪靠近易燃物或易爆物,以防发生火灾或爆炸事故。
5. 如需清洁仪器,请先断开电源,并使用干净柔软的布进行轻柔擦拭。
切勿使用含有酸、碱等物质的清洁剂。
火焰光度计使用方法说明书
火焰光度计使用方法说明书一、前言火焰光度计是一种用于测量火焰强度和光谱信息的仪器。
本使用方法说明书旨在向用户提供详细的操作指南和注意事项,以确保正确且安全地使用火焰光度计。
二、器材准备1. 火焰光度计主机及相关附件2. 电源线或电池组3. 标准火焰源4. 笔记本电脑或数据采集系统(可选)三、操作步骤1. 准备工作a) 确保火焰光度计主机和附件完好无损。
b) 确认电源线或电池组的电量充足。
c) 准备标准火焰源,并确保其稳定燃烧。
2. 连接电源a) 若使用电源线供电,请将其正确插入火焰光度计主机的电源接口。
b) 若使用电池组供电,请将电池组正确安装至火焰光度计主机的电池槽。
3. 主机开机a) 打开火焰光度计主机的电源开关。
b) 确认主机屏幕上显示正常,显示界面无异常现象。
4. 连接标准火焰源a) 使用专用连接线将标准火焰源与火焰光度计主机连接。
b) 确保连接牢固,无松动。
5. 光度计校准a) 在主机操作界面上选择校准功能,并按照界面提示进行操作。
b) 确保校准过程中环境光线较暗,并确保标准火焰源的光谱特性与仪器的校准参数相匹配。
6. 测试测量a) 在主机操作界面上选择测量功能。
b) 将火焰光度计指向待测火焰,并保持适当的距离和角度。
c) 等待一段时间,直到主机屏幕上显示出火焰强度和光谱信息。
7. 火焰光度计移除a) 关闭火焰光度计主机的电源开关。
b) 断开标准火焰源与火焰光度计主机的连接。
c) 若使用电源线供电,请将电源线拔出主机的电源接口。
d) 若使用电池组供电,请将电池组从主机的电池槽中取出。
8. 关机及保养a) 将主机屏幕显示恢复至初始界面,并关闭电源开关。
b) 清洁火焰光度计主机外壳,使用干净而柔软的布进行轻柔擦拭。
c) 将火焰光度计主机及配件存放在干燥通风的地方,避免阳光直射和潮湿环境。
四、注意事项1. 在使用前,请阅读并理解本使用方法说明书,并按照说明书的操作步骤进行操作。
2. 火焰光度计主机及附件应由专业人员进行安装和维修,非专业人士请勿擅自拆卸或维修。
火焰光度计说明书
火焰光度计说明书
火焰光度计是一种常用的化学分析仪器,用于测量物质的光吸收程度。
以下是火焰光度计的说明书,供参考:
1. 概述
火焰光度计是一种基于光吸收原理的化学分析仪器,通过检测样品在火焰中的吸收程度来测量其化学成分。
它通常由光源、探测器、温度控制系统和仪器本身等组成。
2. 工作原理
火焰光度计使用黑体作为样品,在火焰中加热,使其转化为激发态。
激发态物质会吸收特定波长的光线,并将其发射回来。
探测器接收反射回来的光线并测量其能量,转化为化学信号,输入到电脑或其他分析设备中。
3. 操作步骤
以下是火焰光度计的基本操作步骤:
3.1 准备样品
将待测物质制成均匀的薄片或粉末,并放置在样品盘上。
3.2 安装光源和探测器
将光源和探测器安装到仪器的顶部和底部,确保光线和探测器能够均匀分布在样品上。
3.3 启动火焰
点燃火焰光度计的火焰源,等待火焰燃烧完全,使样品充分加热。
3.4 测量吸收
将样品片或粉末放置在探测器下方,并启动测量程序。
等待一段时间后,再次测量吸收。
重复此过程,直到达到预设的测量时间。
3.5 清理和校准
在使用结束后,需要清理仪器的顶部和底部,确保火焰源和探测器能够均匀分布在样品上。
校准火焰光度计以确保其测量精度。
4. 仪器维护
定期清洁火焰光度计以确保其正常运行。
此外,需要定期检查温度控制系统和探测器是否正常工作。
如果仪器出现问题,请联系专业人员进行维护和修理。
希望以上内容可以帮助您使用火焰光度计进行化学分析。
火焰检测器使用手册说明书
This document is FD User Manual/2003/Issue 1Flame DetectorUser ManualGeneralDescriptionThe flame detector is designed for use where open flaming fires may be expected. It responds to thelight emitted from flames during combustion. The detector discriminates between flames and otherlight sources by responding only to particular optical wavelengths and flame flicker frequencies. Thisenables the detector to avoided false alarms due to such factors as flicking sunlight.Electrical ConsiderationsThe flame detector can be connected in many different electrical configurations depending on theapplication. The detector requires a 24Vdc (14Vmin. to 30Vmax.) supply to operate. The detector canbe connected as a two-wire loop powered device increasing its supply current to signal that a flamehas been detected. See Fig 8. The supply connections to the detector are polarity sensitive.Also available are volt free contacts from two internal relays RL1 (Fire) and RL2 (Fault or pre-alarm).Using the relay contacts connected in a four-wire configuration the detector status can be signalledback to control equipment. See Fig 9.Removing the detector front cover provides accesses the detector terminals and configuration DILswitch. See Fig.4.Information in this guide is given in good faith, but the manufacturer cannot be held responsiblefor any omissions or errors. The company reserves the right to change the specifications ofproducts at any time and without prior notice.Alarm Response ModesThe detector is normally configured to latch into an alarm state when a flame is detected. The supplyto the detector has to be broken in order to reset the detector.The configuration DIL switch within the detector can be set to place the detector into a non-latchingmode. The detector can then also produce proportional analogue current alarm signals i.e. 8-28mA or4-20mA. In non-latching mode the detector only produces an alarm signal when a flame is in viewresetting itself to normal when the flame has gone.• • • • • • • Application for Flame DetectorsFlame detectors are used when detection is required to be:Unaffected by convection currents, draughts or wind Tolerant of fumes, vapours, dust and mist Responsive to a flame more than 25m away Fast reactingThe detector is capable of detecting the optical radiation emitted by burning material even non-carbonaceous materials. e.g. HydrogenNumerous other potential fire sources can be detected such asLiquids Solids Gases ● Aviation Fuels (kerosene) ● Coal ● Butane ● Ethanol ● Cotton ● Fluorine ● Methylated Spirits ● Grain & Feeds ● Hydrogen ● n-Heptane ● Paper ● Natural Gas ● Paraffin ● Refuse ● Off Gas ● Petrol (gasoline) ● Wood ● PropaneTypical applications examples are:● Agriculture ● Coal handling plant ● Pharmaceutical ● Aircraft hangars ● Engine rooms ● Power plants ● Atria ● Generator rooms ● Textiles ● Automotive industry ● Metal fabrication ● Transformer stations - spray booths ● Paper manufacture ● Waste handling - parts manufacture ● Petrochemical ● WoodworkingApplications and Locations to Avoid:● ambient temperatures above 55°C ● large IR sources – heaters, burners, flares ● close proximity to RF sources ● obstructions to field of view ● exposure to severe rain and ice ● sunlight falling directly on the detector optics ● large amounts of flickering reflections ● spot lighting directly on the detector opticsQuantities Required and Positioning of DetectorsThe number of detectors required and their position depends on:the anticipated size of the flamethe distance of the flame from the detector the angle of view of the flame detectorThe flame detector is designed to have a class 1 performance as defined in BS EN54-10:2002 on the high sensitivity setting. That is the ability to detect an n-heptane (yellow) fire of 0.1m² or methylated spirit (clear) fire of 0.25m² at a distance of up to 25m within 30 seconds.The detector can be set to have to a lower sensitivity setting equivalent to class 3 performance. Class 3 performance is defined as detecting the same size fires as for class 1 but at a distance of only 12m.Functional TestingWhen 24Vdc power is applied to the detector the green supply on indicator LED will illuminate. The fault relay RL2, if selected with the DIL switch, will energise and the contact between terminals 7 and 8 will close. If 24Vdc is applied to terminals 3 and 4 or terminal 3 is linked to terminal 1 the detector will perform a self-test. It does this by causing internal optical test sources to simulate the behaviour of flames and the detector will alarm. Alternatively a portable flame sensor test unit is available to generate simulated flame behaviour and test the detector a few metres in front of the detector. See Fig 12.Finally, provided it is safe to do so, carry out a flame test using a flickering flame source, such as a portable Bunsen burner. See Fig 13.A still non-flickering flame will not produce a response from the detector.Fig 12 Portable Flame Detector Test Unit Fig 13 Portable Bunsen BurnerService & RepairsServicing of the fire protection system should be carried out by competent persons familiar with this type of system, or as recommended by the local regulations in force. Only the manufacturer or equivalent authorised body may carry out repairs to the flame detectors. In practical terms this means that flame detector may be repaired only at the manufacturers factory.Fig 9 4 Wire Connection DiagramThe circuit shown above enables the flame detectors to interface with most type of fire alarm control systems. The fire relay RL1 is used to switch the required alarm load ‘R’ to generate a fire alarm signal. An end of line device ‘EOL’ mounted in the last detector provides the system with the ability to monitor the detector fault relay RL2 and the integrity of the interconnecting cables.InstallationIt is important that the detectors are installed in such a way that all terminals and connections are protected to at least IP20 with the detector cover fitted. The earth bonding terminals are provided for convenience where continuity of a cable sheath or similar if required.Adjustable mounting brackets and weather shields are available as shown below.Fig 10 Stainless Steel Adjustable MountFig 11 Stainless Steel Weather ShieldIn fact, the flame detector will detect fires at distances of up to 40 metres, but the flame size at such distances needs to be proportionally greater in order to be sure of reliable detection. Thus the yellow flickering flame that can be detected at 25m, provided that its size is not less than 0.1m², will have to be 0.4m² in order to be detected at 40metres.In a rectangular room the distance from the flame detector to the fire is calculated by the formula:Maximum distance = √ L² + W² + H²In the example shown in fig 1 the room in which the flame detector is to be installed measures 20m x 10m x 5m; the maximum distance from the detector to the flame will therefore be;Fig 1 Calculation of distance from detector to flameField of ViewThe flame detector has a field of view of approximately 90°, as shown in the diagram below.Fig 2 Conical field of view of the flame detectorFig 3 Detector Field of View PlotThe flame detector should be positioned at the perimeter of the room, pointing directly at theanticipated flame or at the centre of the area to be protected. If the detector cannot ‘see’ the whole of the area to be protected, one or more additional detectors may be required.The flame detector is not affected by normal light sources but should be positioned so that sunlight does not fall directly onto the viewing window.Detector Window ContaminationIt is important to keep the detector window clean and checks should be carried out at regular intervals – determine locally according to the type and degree of contamination encountered – to ensure optimal performance of the flame detector. Although the IR detectors can detect flames when the window is contaminated, there may be a reduction of sensitivity as shown in Table 1.Contamination Typical percentage of normal responseWater spray75%Steam 75%Smoke 75%Oil film 86% Salt water film 86% Dry salt deposits86%Table 1 IR Detector window contaminationUV/IR detectors are more susceptible to window contamination and must be kept clean.Connection Information-90°90°DetectorFig 8 Basic 2 Wire Connection DiagramThe simplest method of connecting the flame detector is in a 2-wire configuration as shown above. With a 24Vdc supply the current (i ) drawn by a detector/detectors can be monitored to determine the detector status. The DIL switches within the detector can be set to produce different current values (i ) to suit control systems.Detector Supply Currenti @ 24Vdc DIL Switch SettingNormal Quiescent Current Alarm (Fire) Current 1 2 3 4 Comment3mA 9mA 0 0 0 0 Lowest power configuration, RL1 only 4mA 20mA 0 0 1 0 For 4-20mA systems, no relays 8mA 14mA 1 1 1 0 Lowest power configuration & relays 8mA 20mA111For 4-20mA systems & relays 8mA28mA 1111Fire control panelsTable 4 Detector Supply & Alarm CurrentsIf the detector supply current falls below the normal quiescent current consumption then a fault is present. This could be simply an open circuit cable fault or a fault within the detector possibly due to the detector being taken over its rated temperature.Detectors can be connected in parallel increasing the overall quiescent current required. The alarm current signal will remain the same with the additional quiescent current drawn from other detectors.21Control Unit(Supplied by others)Flame Detector Single pair cable, also see note 1i++24Vdc Normal(Break supply to reset if detector set to latch)--NOTE 1Screened cable should be used with one end of the screen connected to earth. Also care should be taken not to run the detector cable next to power cables.Theory of OperationThe detector responds to low-frequency (1 to 15 Hz.) flickering IR radiation emitted from flames during combustion. IR flame flicker techniques enable the sensor to operate through a layer of oil, dust, water vapour, or ice.Most IR flame sensors respond to 4.3µm light emitted by hydrocarbon flames. By responding to 1.0 to 2.7µm light emitted by every fire all flickering flames can be detected. Gas fires not visible to the naked eye e.g. hydrogen may also be detected. The dual (IR²) and triple (IR³) IR photoelectric detectors, responding to neighbouring IR wavelengths, enable it to discriminate between flames and spurious sources of IR radiation. The combination of filters and signal processing allows the sensor to be used with little risk of false alarms in difficult situations characterised by factors such as flickering sunlight.Signal ProcessingThe detector views the flame at particular optical wavelengths. The more differing optical wavelength signals available the better the detector is at discriminating between flames and false optical sources. So although IR², IR³ and UV/IR² detectors can detect similar sized flames at the same distances, the UV/IR² detector willgive the greatest optical false signal immunity as it has the most diverse selection of optical wavelengths.The detector processes the optical signal information to determine if a flame is in view. This is achieved by comparing the signals with known flame characteristics stored within the detector.Fig 7 Block Diagram of the Detector Signal ProcessingIf the detector has interpreted the optical signals as a fire then it produces the required output responses. This will be in the form of supply current changes and the illumination of the red fire LED. The fire relay will also change state if required. The detector is constantly checking itself to ensure it is performing correctly. If a fault occurs the detector supply current will reduce, the fault relay will de-energise and the green supply LED will no longerilluminate constantly.FlameDetector InteriorFig 4 Detector with Front Cover removedElectrical ConnectionsThe flame detector has eight connection terminals as show in Fig 5. Removing the front cover of the flame detector accesses the connections. The cable is passed through the gland holes in the base of the detector.Fig 5 Electrical Connection TerminalsSupply ON (Green) - Steady if detector functioning correctly IR Optics -IR optical flame sensors & filtersFire (Red) - Indicates a FIRE detected Test (Yellow) - Indicates detector in test modeUV Optics (Option) -UV optical flame sensor if fittedDIL Switch -Select detector functionsConnection Terminals+IN -IN Test Input+R -RFLAME (N/O) Relay RL1FAULT (N/C) Relay RL2+24Vdc SupplyInputConnection Terminal DescriptionsTerminalNo. Mnemonic Function1 +IN Power Supply +V. +IN is the power supply input to the flame detectorand is normally 24Vdc with respect to terminal 2. The currentconsumption of detector can be monitored to determine the detectorstatus (Fault, Normal, Pre-alarm, Fire). If the detector is in latchingmode then this supply line must be broken in order to reset thedetector. A thermal fuse within the detector will blow and break the +INconnection if the detector operating temperature is exceeded.2 -IN Power Supply 0V. –IN is the return path for the detector supply current.-IN is also internally connected to terminal 4.3 +R Remote Detector Test Input +V. No connection to +R is necessary ifthe detector optical and circuit test feature is not required. If 24Vdc isapplied to terminals 3 and 4 the detector internal optical test sourceswill activate to simulate a flame. The detector yellow test LED willflicker to indicate an optical test is progress. The detector will thenalarm indicating that the test was successful.4 -R Remote Detector Test Input 0V. No connection to -R is necessary if thedetector optical and circuit test feature is not required.-R is internally connected to terminal 2.56 RL1Flame Relay RL1. This volt free contact is normally open (N/O) andonly closes when a flame has been detected. If the detector is inlatching mode (see DIL switch settings) the contact will remain closedonce a flame has been detected. Only when the detector supply +IN isbroken will the detector reset and the contact open once again. Thecontact can be changed to a normally closed (N/C) state by moving thelink on JP1 in the rear of the detector.Maximum relay contact ratings: Power=3W, Current=0.25Amp,Voltage=30Vdc. Resistive loads only.78 RL2Fault or Pre-alarm Relay RL2. This volt free contact is normally closed(N/C) if the detector has no faults and the supply voltage betweenterminals +IN and –IN is the correct value. If the detector mode ischanged (see DIL switch settings) this relay can be de-energised toreduce the detector current consumption. Alternatively RL2 can be setto provide a pre-alarm fire signal. The normal contact state can bechanged state by moving the link on JP2 in the rear of the detector.Maximum relay contact ratings: Power=3W, Current=0.25Amp,Voltage=30Vdc. Resistive loads only.Table 2 Connection Terminal Descriptions Selectable Detector Functions(DIL Switch Settings)Fig 6 DIL Switch with Detector Front Cover Removed (Normal factory settings shown)Selectable Functions DIL Switch Settings Relay RL2 Function: 1 2 RL2 off (No fault relay) – For lowest detector current consumption. 0 0 RL2 off, or UV pre-alarm, flame or electrical sparks detected. 1 0RL2 energised on IR pre-alarm0 1RL2 detector fault relay (Energised if detector powered and no faults) 1 ~ 1 Detector Supply Current (Detector Status): [-/ = see Output Mode below] 3 4 Low current mode, 3mA / 9mA (RL1 Only), 8mA / 14mA (RL1 & RL2) 0 0 Two-wire current signalling only. No relays operating. 4-20mA, 4/20mA 1 0 Two-wire current signalling 8-20mA, 8/20mA and both relays operating. 0 1 Two-wire current signalling 8/28mA and both relays operating. 1 ~ 1 Output Mode: 5(-) Proportional analogue supply current. Non-latching fire alarm signalling. (-) 0(/) Step change, supply current. Latching fire alarm signalling. (/) ~ 1 Response Time: 6 7Slowest ≈ 8s 0 0Medium ≈ 4s 1 ~ 0Fast ≈ 2s 0 1 Faster response times reduce the optical interference immunity. Very Fast ≈ 1s 1 1 Sensitivity: See EN 54-108Low Class 3 0High Class 1 ~ 1Factory settings ~Table 3 DIL Switch Settings。
火焰光谱仪操作指南说明书
火焰光谱仪操作指南说明书一、引言火焰光谱仪(以下简称“仪器”)是一种常用的光谱分析仪器,用于测量物质在火焰中的光谱特性。
本操作指南将详细介绍仪器的使用方法和注意事项,以帮助用户顺利进行光谱分析实验。
二、仪器概述1. 仪器组成仪器由光源、光栅、检测器、信号处理器等部件组成。
2. 仪器原理仪器利用物质在火焰中激发产生的光谱进行分析,通过检测物质特定的光谱线来确定其成分和浓度。
三、仪器使用步骤1. 仪器准备a) 确保仪器连接正常,各部件工作正常;b) 确保光源、光栅等清洁,无灰尘和污垢;c) 检查样品架和样品槽是否完好。
2. 样品制备根据需要进行样品的预处理,如溶解、稀释等。
3. 仪器校准a) 使用标准样品进行校准,确保仪器的准确度和稳定性;b) 校正仪器在样品浓度范围内的线性和灵敏度。
4. 仪器操作a) 打开仪器电源,并启动预热程序;b) 设置温度和流量参数,确保火焰的稳定;c) 调节光源和光栅,使其工作在最佳状态;d) 将样品放入样品槽,确保与火焰光源接触良好;e) 启动数据采集程序,记录样品的光谱数据。
5. 数据处理将采集到的光谱数据导入分析软件,进行数据处理和结果分析。
四、使用注意事项1. 安全操作a) 在操作仪器时,遵守实验室的安全规定;b) 注意火焰的温度,避免烫伤或烧伤。
2. 仪器保养a) 每次使用后清洁仪器各部件,确保无残留物;b) 定期检查和维护仪器,如更换灯泡、光栅等。
3. 样品处理a) 样品的选择和制备应符合操作规范;b) 严格控制样品的浓度,避免超出仪器测量范围。
4. 实验环境a) 保持实验室的环境干净整洁;b) 避免阳光直射和强烈震动,以防影响仪器的正常工作。
五、故障排除1. 仪器无法启动a) 检查仪器电源是否连接正常;b) 检查电源开关和线路是否正常;c) 若以上检查均正常,联系售后服务。
2. 光谱信号弱或无信号a) 检查光源是否正常工作,如需要更换灯泡;b) 检查光栅是否干净,如需要清洁;c) 若以上检查均正常,联系售后服务。
火焰离子探测器使用方法说明书
火焰离子探测器使用方法说明书使用方法说明书一、产品概述火焰离子探测器是一种多功能、高精度的火焰检测设备,主要用于监测和探测各种火焰源。
本产品结构紧凑,使用方便,可广泛应用于工业、建筑、交通等领域。
二、产品组成本产品包含以下主要部件:1. 火焰感应器:负责接收和感应火焰信号;2. 控制面板:提供操作和设置功能;3. 报警器:用于发出火灾报警信号;4. 电源适配器:提供电力供应;5. 操作手册:详细说明产品的使用方法和安全注意事项。
三、安全注意事项在使用火焰离子探测器之前,请务必阅读并理解以下安全注意事项:1. 在安装过程中,请确保设备与电源完全断开,避免触电风险;2. 请勿随意拆解或修改设备内部部件,以免引发故障或安全事故;3. 在使用过程中,应注意防止水或其他液体进入设备,以免损坏设备或引发短路;4. 请将探测器安装在离火源较远的位置,避免误报或过早报警。
四、安装步骤1. 将火焰感应器固定在需要监测的区域,确保安装牢固;2. 将控制面板安装在室内便于观察和操作的位置,并连接电源;3. 检查设备的连接线路,确保连接牢固、无松动;4. 按照操作手册中的步骤进行各项设置和调试。
五、操作方法1. 使用操作手册中提供的操作界面说明,熟悉探测器的各项设置和功能;2. 根据需要,设置探测器的灵敏度和报警阈值;3. 定期检查设备连接是否正常,保证正常工作;4. 如需清洁设备,请先断开电源,使用干布轻轻擦拭。
六、故障排查与维护如果设备出现故障或异常情况,请按以下步骤进行排查与维护:1. 检查电源接口是否松动或供电不稳定;2. 检查感应器接线是否正常,排除接线松动或短路情况;3. 清洁设备,确保没有灰尘或杂物引起故障;4. 如有故障无法排除,请联系厂家或专业技术人员进行维修。
七、常见问题与解答1. 问:如何调整灵敏度?答:可在控制面板中进行相应设置,根据实际需求调整灵敏度参数。
2. 问:火焰离子探测器是否适用于户外环境?答:本产品主要适用于室内环境,在户外环境使用时需额外保护措施。
火焰点测试仪维护说明书
火焰点测试仪维护说明书一、概述火焰点测试仪是广泛应用于石油化工行业,用于测定液体的闪点和火焰点的仪器。
为了确保测试仪的准确性和可靠性,保证测试结果的科学性和可比性,本说明书详细介绍了火焰点测试仪的维护方法和注意事项。
二、维护方法1. 定期清洁保持测试仪器的清洁对于准确测试至关重要。
应定期清洁外壳和内部零部件,尤其是光反射镜、蜡涂层和试管。
使用干净、柔软的布擦拭外壳,使用适量的清洁剂清洗内部零部件。
注意不要使用过量或强酸碱性清洁剂,以免损坏仪器结构。
2. 定期校准火焰点测试仪的准确性与其校准状态息息相关。
建议定期校准仪器,以确保测试结果的可靠性。
可以选择专业的仪器维修和校准机构进行校准,或者根据国家标准方法标定仪器。
3. 防尘防潮火焰点测试仪器一定要放置在清洁、干燥的环境中,避免灰尘和湿气进入仪器内部,以免影响仪器的正常运行和测量精度。
同时,在长时间不使用时,应将仪器放置在防尘罩或密封盒内。
4. 手柄使用注意火焰点测试仪的手柄是操作的重要部分。
在使用时,请务必轻拿轻放,避免摔落或撞击。
同时,手柄上的按钮也需要注意轻按,避免使用过力或长时间按压,以免影响仪器的正常使用寿命。
5. 定期更换试剂火焰点测试仪通常使用特定的试剂进行测试,这些试剂在使用一段时间后会因为使用频繁而变质。
因此,为确保测试结果的准确性,应定期更换试剂,并注意试剂保存的环境和过期时间。
6. 维护记录建议建立火焰点测试仪的维护记录,包括清洁时间、校准时间、试剂更换时间等,以便在需要时查阅和参考。
维护记录不仅可以帮助用户了解仪器的使用状况,还可以作为后续维护和保养的依据。
三、注意事项1. 注意安全火焰点测试仪在使用过程中涉及到易燃液体和火焰,因此,在操作仪器时务必注意安全。
禁止在密闭环境下操作,避免火灾和爆炸的风险。
同时,在使用过程中避免接触火焰点测试仪的火焰部分,避免烫伤或其他伤害。
2. 学习使用说明在使用火焰点测试仪之前,请仔细阅读和理解使用说明书,了解仪器的结构、操作和安全要求。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
路时所用。 装运重量:2.4 磅(1.1 公斤),尺寸见图 1。
- 4-
-
美国FORENY公司中国工程服务中心
电气要求:
电源:+24VDC,取自 DP7000 放大器,或+24VDC(+10%,-15%)取自外部电源。每个 火焰检测器的额定电流为 100mA。
- 6-
-
美国FORENY公司中国工程服务中心
向下倾斜安装以免垃圾和灰尘在管中聚集。 火焰检测器探头通过 LED 显示的反馈信息来调整安装角度。请参阅“DPD 火检编程” 章节中的 AIM(瞄准)功能。
图4
7、 经运行测试并对 AIM 功能的设定,证实已获得满意的瞄准角度后,拧紧转动安装接头 圈上的六角螺钉使转动球固定。
图5
热绝缘管 热绝缘管用于阻断热量从观察管至火检探头的传输,同时也用于探头与大地之间的绝缘,并 减少产生热量和噪音。每个 DPD 火检探头都配供一个热绝缘管。
带石英窗的密封短管 当探头的连接管中需装联管节或密封时应装密封短管。石英窗可防止炉膛压力、热气体/烟 灰直接接触到探头污染透镜。密封短管的尺寸为 1”美国标准锥管螺纹(1”NPT)。当使用密 封短管时,在其下游处必需从 1”三通接头处连接吹扫风(堵住火检上的 3/8”开孔)。
- 串行通讯 —— 对火焰参数进行直接、实时的监测和分析 通过 RS485 接口将参数上载/下载至计算机或其它智能设备。
- 24 伏直流工作电压
启动
安装概述:
1、 用转动安装接头和六角螺钉将 DPD 火检安装好。(见后面的“机械安装”部分)。 2、 通过扁电缆和火检电缆将火检与 24 伏直流电源连接。(见后面的“电气安装”部分)。 3、 通上电源。经过 12 秒左右的回路试验。 4、 按以下八个步骤对 DPD 火检进行编程(请阅读后面“DPD 火检编程”的全部说明)。
DPD 火焰检测器 产品说明书
美国FORENY公司中国工程服务中心
DPD(数字剖面)火焰检测器
FORNEY 公司生产的数字剖面火焰监测器(简称 DPD 火检)可用于鉴别单燃烧器或 多燃烧器燃烧环境中目标火焰的存在于否。已获专利的 DPD 火焰检测器采用了微处理器技 术和专用软件,对目标火焰的频率和振幅特性不断地进行监测。
-20℃ - +65℃ 湿度: 0-95%相对湿度,非凝结
吹扫风 风源:清洁的环境 所需的流量:3/8”螺纹外壳进口处流量为 4SCFM(113L/min)或位于火焰检测器瞄准管 1” 三通处的流量为 4 SCFM。当工作温度接近温度上限时或使用不洁燃料时所需的流量可能达 到 15 SCFM(425L/min)。
在通常使用清洁燃料且环境温度适中的情况下,4 SCFM(133L/min)的吹扫风流量一般 已够,对于会产生大量飞灰或烟灰的燃料,或是环境较热的情况下,吹扫风的流量可能 需要达到 15 SCFM(425L/min),以保证火检的内部温度维持在规定范围内。
- 7-
-
火焰检测器附件的使用
美国FORENY公司中国工程服务中心
机械安装
1、当火焰检测器的视线与燃烧器中心线相交有一个轻微的角度(如 5 度)且能看到最大量 的主燃烧区域时可获得最佳效果,如图 2 所示。如果每个燃烧器只使用一个火焰检测器, 则火焰检测器的视线同时也应与点火火焰相交。
2、 当使用不同的火检来检测主燃料火焰和点火火焰时,主燃料火焰检测器的视线应检测不 到点火火焰。
3、 火焰检测器的视野应不受阻碍,对于如调风器叶片等障碍物应予以排除或切除,使这些 障碍物不在视线范围内,见图 2。修整调风器叶片之前应与燃烧器制造商联系。
- 5-
-
图 2、火检探头的角度
美国FORENY公司中国工程服务中心
4、 应考虑到燃烧器二次风的转向问题(有些燃烧器的二次风顺时针方向旋转,而有些逆时 针旋转)。当燃烧风以足够的的旋转速度进入炉膛时会使点火火焰随旋转方向偏移,应将 火检安装于点火器下游 10 至 30 度的位置 (见图 3) 所示,并使之靠近燃烧器喇叭口的边 缘 (见图 2)。 图 3、火检与二次风旋转方向的相对位置
的视线(此时 LED 显示为最低值) 步骤 5:学习有火时的火焰信号 步骤 6:学习无火时的火焰信号 Nhomakorabea- 2-
-
美国FORENY公司中国工程服务中心
步骤 7:保存文件(包括组态和火焰的信号参数) 步骤 8:运行文件
目录
1、 2、 3、 4、 5、 6、 7、 8、 9、 10、 11、 12、 13、 14、 15、 16、 17、
8、 为便于使用,火焰检测器探头应安装在观察管上以便读取 LED 显示。如果无法这样做, 安装火检探头时应将快装接头面向下。(LED 显示不受安装位置的限制)。
9、 由于 DPD 火检采用了微处理器设计,必须使用所供的热绝缘短管使火检探头隔热。 10. 火检透镜必须保持清洁无污染(油、飞灰、烟灰、赃物),火检温度不得超过它的最高
DPD 火焰检测器的先进性还体现在其使用的便利上。先进的电子线路便于用户进行火 检的瞄准和编程,而不必化数小时的时间反复调试;自诊断功能和按钮编程也使火检的其它 操作极为方便。
特点:
- 智能显示 —— 用于快速设置、精确瞄准以及火焰信号显示。 八位持续滚动的 LED 显示提供火检所有设定值和火焰状况的瞬时读数显示。
- 1-
-
美国FORENY公司中国工程服务中心
- 适用于任何结构的燃烧器 适用于低 Nox、枪式、摆动式、棒式、环式、层燃式等结构的燃烧器。
- 适用于任何燃料 Super-blue 型 DPD 火焰检测器可适用于大多数燃料的火焰监测,而 Classic 型 DPD 火 检适用于煤/油的火焰。
- 在摆动式燃烧器或者空间受限制的应用中可选用光纤 光纤可穿过拥挤的燃烧器空间使火焰检测器实现远程安装。
DPD 火焰检测器是对火焰的三维特性进行分析,这些特性会受到燃料品种和燃烧器类 型的影响。气体燃料火焰(丙烷、甲烷、天然气)往往会产生大量的紫外线,而固态(煤粉) 和液态(油)燃料燃烧的火焰会产生大量的红外线,而燃烧器的类型会影响火焰的闪动频率。
红外线火焰检测器会识别目标火焰中的红外线辐射,但不能看穿火焰去检测相邻或相对 燃烧器的火焰;红外线火焰检测器能会监测到气体燃料目标火焰中的红外线辐射,但也会直 接穿过气体火焰去采集相对燃烧器火焰中的红外线信号。技术先进的 DPD 火焰检测器对这 些火焰变量进行分析,从而对火焰的有无作出可靠准确的判断。
- 9-
-
美国FORENY公司中国工程服务中心
22 号线规导线构成。所有六根导线均封闭于聚酯屏蔽套中,电缆外壳材料 Hypalon, 电缆外 径为 0.425”(最大)。如果不使用连接电缆时,火检电缆可直接与探头上的快装接头连接。
- 编程简单可靠 按钮键盘可使用户直接对火检进行编程和显示。但是为了避免未经授权的参数改动,在 火检的后盖板下面装有编程驱动”Program Enable”锁定按钮。
- 灵活的运行参数 可选择火焰熄火响应时间(FFRT):2-6 秒 可选择背景火焰熄火响应时间(BFRT):2-8 秒 可选择有火信号延时:2-4 秒 可选择华氏或摄氏温度显示
连接:快装接头(提供)。 火检电缆:部件号 9101647,最大长度:1000 英尺 接线电缆:部件号随长度的不同而不同。
键盘/显示屏 . 8 位数字字母 LED 显示(滚动显示功能) . 3 个按键 . 塑料滤光软性键盘
Program Enable (编程驱动) 按钮
运行条件: 温度范围:-4℉ - +150℉
步骤 1:按下盖板下面的 Program Enable 按钮使火焰监测器置于编程菜单状态 (Programming Menu)。
步骤 2:编辑文件 F 驱动自动增益控制向火检放大器发送脉冲信号使火焰继电器得电。 步骤 3:根据燃料种类、燃烧器类型、以及其它运行参数生成一个文件 步骤 4:在燃烧器投运时对火焰检测器进行瞄准,通过使用瞄准 AIM 功能来获得最佳
额定温度 150℉(65℃)。过高的温度会缩短火检的使用寿命。从 3/8”入口处或转动接头 前“Y”型三通处连续不断地注入冷却风,可满足上述两个要求,如图 4 所示。当使用密 封短管的时候,1”三通接口用于注入吹扫风,3/8”开孔堵住。
在所有的装置上使用密封接管(部件号 9102849)是一个很好的做法,这样可以保证避 免不必要的锅炉正压损坏火检透镜。
- 8-
-
美国FORENY公司中国工程服务中心
电气安装
连接电缆 连接电缆为火检探头的连接以及远程通讯提供了方便。使用远程通讯时需运行串接布置中的 两根通讯线,而不要直接运行返回火焰放大器的通讯线。为了便于串接布置,FORNEY 提 供了几种长度的接线电缆(10’、15’、20’和 30’)。电缆一端的插座与火检探头上的插头配 用。电缆的另一端有一个接线盒,内装一个有 20 个端子的 U 形接线端子排,其中 8 个端子 已与快装接头插座预接,其余的 12 个端子用于连接探头至放大器的返回信号(24VDC、电 源、快门、公共点、火焰信号、远程文件 1、2 选择),以及与其它探头进行通讯用的两芯通 讯电缆(22 AWG,#8451)连接。
每个火焰有其独特的剖面特性,就犹如“指纹”一样。在“学习”模式下,DPD 火检 对目标火焰交流信号的频谱进行实时分析以确定被监测火焰的类型(如:燃烧器有火、相邻 燃烧器窜火、背景火焰、无火)以及火焰频谱的特定剖面形状;在“运行”模式下,火焰检 测器则不断地将目标火焰信号与所学的剖面特性进行比较从而准确地判断火焰的状态。
5、 满意的火检位置应能在所有风量和炉膛负荷的情况下,都能确保对主燃料火焰/点火火 焰的检测。