建筑人防设计计算书

一、人防临空墙及单元隔墙计算------------------------------------------------------------------- 计算项目: LKQ1------------------------------------------------------------------- [ 计算条件 ]墙长 = 6.00(m) 墙宽 = 4.17 (m) 墙厚 = 300 (mm)墙面均布荷载: 130.00 (kN/m^2)竖向均布荷载: 200.00 (kN/m)砼强度等级: C35纵筋级别: HRB400配筋计算as (mm):: 25 (mm)跨中弯矩调整系数: 1.00支座弯矩调整系数: 1.00支承条件:**** 下边右边上边左边固接固接简支固接[内力结果] (已乘弯矩调整系数)内力按塑性理论计算(适用于大偏心受压):跨中弯矩(kN-m/m):Ma = 35.28 Mb = 72.90垂直板边弯矩(kN-m/m):下右上左 -145.80 -70.55 0.00 -70.55 [配筋结果]轴压比: N/(A*fc)= 0.0333竖直方向配筋(mm^2/m):[注意: 配筋小于0表示超筋, 荷载作用面为外侧]上截面:非荷载侧= 600 荷载侧= 750(mm^2/m)中截面:非荷载侧= 750 荷载侧= 600(mm^2/m)下截面:非荷载侧= 600 荷载侧= 1226(mm^2/m) 水平方向单侧配筋(mm^2/m):[注意: 配筋小于0表示超筋]左中右750.00 750.00 750.00------------------------------------------------------------------- 计算项目: LKQ2------------------------------------------------------------------- [ 计算条件 ]墙长 = 3.00(m) 墙宽 = 4.17 (m) 墙厚 = 300 (mm)墙面均布荷载: 130.00 (kN/m^2)竖向均布荷载: 200.00 (kN/m)砼强度等级: C35纵筋级别: HRB400配筋计算as (mm):: 25 (mm)跨中弯矩调整系数: 1.00支座弯矩调整系数: 1.00支承条件:**** 下边右边上边左边固接固接简支固接[内力结果] (已乘弯矩调整系数)内力按塑性理论计算(适用于大偏心受压):跨中弯矩(kN-m/m):Ma = 29.73 Mb = 15.44垂直板边弯矩(kN-m/m):下右上左 -30.89 -59.47 0.00 -59.47 [配筋结果]轴压比: N/(A*fc)= 0.0333竖直方向配筋(mm^2/m):[注意: 配筋小于0表示超筋, 荷载作用面为外侧]上截面:非荷载侧= 600 荷载侧= 750(mm^2/m)中截面:非荷载侧= 750 荷载侧= 600(mm^2/m)下截面:非荷载侧= 600 荷载侧= 750(mm^2/m) 水平方向单侧配筋(mm^2/m):[注意: 配筋小于0表示超筋]左中右750.00 750.00 750.00------------------------------------------------------------------- 计算项目: GQ 六级-六级------------------------------------------------------------------- [ 计算条件 ]墙长 = 6.00(m) 墙宽 = 4.17 (m) 墙厚 = 300 (mm)墙面均布荷载: 50.00 (kN/m^2)竖向均布荷载: 200.00 (kN/m)砼强度等级: C35纵筋级别: HRB400配筋计算as (mm):: 25 (mm)跨中弯矩调整系数: 1.00支座弯矩调整系数: 1.00支承条件:**** 下边右边上边左边固接固接简支固接[内力结果] (已乘弯矩调整系数)内力按塑性理论计算(适用于大偏心受压):跨中弯矩(kN-m/m):Ma = 13.57 Mb = 28.04垂直板边弯矩(kN-m/m):下右上左 -56.08 -27.14 0.00 -27.14 [配筋结果]轴压比: N/(A*fc)= 0.0333竖直方向配筋(mm^2/m):[注意: 配筋小于0表示超筋, 荷载作用面为外侧]上截面:非荷载侧= 600 荷载侧= 750(mm^2/m)中截面:非荷载侧= 750 荷载侧= 600(mm^2/m)下截面:非荷载侧= 600 荷载侧= 750(mm^2/m) 水平方向单侧配筋(mm^2/m):[注意: 配筋小于0表示超筋]左中右750.00 750.00 750.00------------------------------------------------------------------- 计算项目: GQ1------------------------------------------------------------------- [ 计算条件 ]墙长 = 6.00(m) 墙宽 = 4.17 (m) 墙厚 = 200 (mm)墙面均布荷载: 50.00 (kN/m^2)竖向均布荷载: 200.00 (kN/m)砼强度等级: C35纵筋级别: HRB400配筋计算as (mm):: 25 (mm)跨中弯矩调整系数: 1.00支座弯矩调整系数: 1.00支承条件:**** 下边右边上边左边固接固接简支固接[内力结果] (已乘弯矩调整系数)内力按塑性理论计算(适用于大偏心受压):跨中弯矩(kN-m/m):Ma = 13.57 Mb = 28.04垂直板边弯矩(kN-m/m):下右上左 -56.08 -27.14 0.00 -27.14 [配筋结果]轴压比: N/(A*fc)= 0.0499竖直方向配筋(mm^2/m):[注意: 配筋小于0表示超筋, 荷载作用面为外侧]上截面:非荷载侧= 400 荷载侧= 500(mm^2/m)中截面:非荷载侧= 500 荷载侧= 400(mm^2/m)下截面:非荷载侧= 400 荷载侧= 854(mm^2/m) 水平方向单侧配筋(mm^2/m):[注意: 配筋小于0表示超筋]左中右500.00 500.00 500.002 人防地下室门框墙计算-------------------------------------------------------------------计算项目: MKQ1-------------------------------------------------------------------[ 计算条件 ]L = 350.00(mm) L1 = 316.00 (mm) L2 = 250.00 (mm)h = 300.00 (mm)qe = 200.00 (kN/m^2)qi = 121.20 (kN/m)砼强度等级: C35配筋计算 as : 25 (mm)纵筋级别: HRB400 箍筋级别: HRB335 箍筋间距(mm): 200[ 计算结果 ]弯矩(kN-m/m): M = 44.549剪力(kN/m): V = 171.200*****按悬臂构件计算*****------ 抗弯拉筋构造配筋: 配筋率Us=0.13% < Us_min=0.25%抗弯受拉筋: As = 750(mm^2/m)抗剪箍筋: Av = 0(mm^2/m)-------------------------------------------------------------------计算项目: MKQ2-------------------------------------------------------------------[ 计算条件 ]L = 400.00(mm) L1 = 366.00 (mm) L2 = 300.00 (mm)h = 300.00 (mm)qe = 200.00 (kN/m^2)qi = 109.50 (kN/m)砼强度等级: C35配筋计算 as : 25 (mm)纵筋级别: HRB400 箍筋级别: HRB335 箍筋间距(mm): 200[ 计算结果 ]弯矩(kN-m/m): M = 49.077剪力(kN/m): V = 169.500*****按悬臂构件计算*****------ 抗弯拉筋构造配筋: 配筋率Us=0.14% < Us_min=0.25%抗弯受拉筋: As = 750(mm^2/m)抗剪箍筋: Av = 0(mm^2/m)-------------------------------------------------------------------计算项目: MKQ3左-------------------------------------------------------------------[ 计算条件 ]L = 600.00(mm) L1 = 566.00 (mm) L2 = 500.00 (mm)h = 300.00 (mm)qe = 200.00 (kN/m^2)qi = 135.40 (kN/m)砼强度等级: C35配筋计算 as : 25 (mm)纵筋级别: HRB400 箍筋级别: HRB335 箍筋间距(mm): 200[ 计算结果 ]弯矩(kN-m/m): M = 101.636剪力(kN/m): V = 235.400*****按悬臂构件计算*****抗弯受拉筋: As = 880(mm^2/m)抗剪箍筋: Av = 0(mm^2/m)-------------------------------------------------------------------计算项目: MKQ3右-------------------------------------------------------------------[ 计算条件 ]L = 400.00(mm) L1 = 366.00 (mm) L2 = 300.00 (mm)h = 300.00 (mm)qe = 200.00 (kN/m^2)qi = 135.40 (kN/m)砼强度等级: C35配筋计算 as : 25 (mm)纵筋级别: HRB400 箍筋级别: HRB335 箍筋间距(mm): 200[ 计算结果 ]弯矩(kN-m/m): M = 58.556剪力(kN/m): V = 195.400*****按悬臂构件计算*****------ 抗弯拉筋构造配筋: 配筋率Us=0.17% < Us_min=0.25%抗弯受拉筋: As = 750(mm^2/m)抗剪箍筋: Av = 0(mm^2/m)未做计算的门框墙,参考《防空地下室设计》FG01~05(2007年合订本)中配筋。

(整理)人防设计结构计算书

(整理)人防设计结构计算书

结构设计计算书一、结构计算依据:1.设计相关规范:2.核工业西南勘察设计研究院有限公司2013年8月提供的《香颂城商住. 小区一期岩土工程勘察报告》(详细勘察)进行设计。

3.民用设计院提供的平时使用条件(模型及荷载)二、工程概况本工程为眉山市森林家园房产开发有限公司香颂城防空地下室,位于地下负一层和地下负二层。

共2个防护单元。

结构设计使用年限为50年。

本设计只对人防工程部分进行设计;非防护区部分不在本设计范围,按原设计(民用设计院设计)实施。

人防工程概况三、结构计算计算程序---中国建筑科学研究院PKPM(2012年6月版)材料:钢筋---HPB300(一级钢)、HRB335(二级钢)、HRB400(三级钢)混凝土--- 顶板: C30梁: C30柱: C30墙: C30底板: C301、顶板验算见附图(取平时和战时计算的最大值)2、顶板梁、柱验算见附图(取平时和战时计算的最大值)3、底板验算经验算原设计满足人防设计要求。

4、外墙验算经验算外墙人防荷载不起控制作用,外墙按裂缝控制,故外墙配筋按原设计满足人防设计要求。

5、临空墙验算******************************************************************************************** 计算项目: 临空墙-1******************************************************************************************** [计算条件]墙高 = 3900.00(mm) 墙宽 = 3200.00(mm) 墙厚 = 300.00(mm) 竖向均布荷载(KN/M): 100.00 墙面均布荷载(KN/M2): 110.00 墙面三角形荷载(KN/M2): 0.00 砼强度等级: C30 配筋计算 as(mm): 30 钢筋级别 : HRB400(RRB400) 支撑条件:**** 上边 下边 左边 右边 简支 固定 固定 固定-32.200.00-47.83-47.8326.5717.89750750750251750750750750750750750750100.0110.039003200[ 内力计算 ]:轴压比 N/(A*fc)= 0.019382 跨中弯矩(kN-m/m):水平:26.57 竖向:17.89垂直板边弯矩(kN-m/m):上下左右 0.00, -32.20, -47.83, -47.83 [ 配筋结果 ]:竖直方向配筋(mm^2/m):上截面非荷载侧:750.08 荷载侧:251.00中截面非荷载侧:750.08 荷载侧:750.12下截面非荷载侧:750.12 荷载侧:750.08水平方向配筋(mm^2/m):左中右非荷载侧 750.12, 750.08, 750.12荷载侧 750.08, 750.12, 750.08[计算条件]墙高 = 3900.00(mm) 墙宽 = 4100.00(mm) 墙厚 = 300.00(mm)竖向均布荷载(KN/M): 100.00墙面均布荷载(KN/M2): 160.00墙面三角形荷载(KN/M2): 0.00砼强度等级: C30配筋计算 as(mm): 30钢筋级别 : HRB400(RRB400)支撑条件:**** 上边下边左边右边简支固定固定固定7277775-84.610.00-76.56-76.5645.0449.7775050750517505075050507500750100.0160.039004100[ 内力计算 ]:轴压比 N/(A*fc)= 0.019382 跨中弯矩(kN-m/m):水平 :45.04 竖向 :49.77 垂直板边弯矩(kN-m/m):上 下 左 右 0.00, -84.61, -76.56, -76.56 [ 配筋结果 ]:竖直方向配筋(mm^2/m):上截面 非荷载侧 :750.08 荷载侧 :251.00 中截面 非荷载侧 :750.08 荷载侧 :750.12 下截面 非荷载侧 :750.12 荷载侧 :750.08 水平方向配筋(mm^2/m):左 中 右 非荷载侧 750.12, 750.08, 750.12 荷载侧 750.08, 750.12, 750.08******************************************************************************************** 计算项目: 临空墙-2******************************************************************************************** [计算条件]墙高 = 3900.00(mm) 墙宽 = 5800.00(mm) 墙厚 = 300.00(mm) 竖向均布荷载(KN/M): 100.00墙面均布荷载(KN/M2): 110.00 墙面三角形荷载(KN/M2): 0.00 砼强度等级: C30 配筋计算 as(mm): 30 钢筋级别 : HRB400(RRB400) 支撑条件:**** 上边 下边 左边 右边 简支 固定 固定 固定58.98927507507750-106.160.00-48.00-48.0026.67750437505175075050750750100.0110.039005800[ 内力计算 ]:轴压比 N/(A*fc)= 0.019382 跨中弯矩(kN-m/m):水平 :26.67 竖向 :58.98 垂直板边弯矩(kN-m/m):上 下 左 右 0.00, -106.16, -48.00, -48.00[ 配筋结果 ]:竖直方向配筋(mm^2/m):上截面 非荷载侧 :750.08 荷载侧 :251.00 中截面 非荷载侧 :750.08 荷载侧 :750.12 下截面 非荷载侧 :750.12 荷载侧 :943.08水平方向配筋(mm^2/m):左 中 右 非荷载侧 750.12, 750.08, 750.12 荷载侧 750.08, 750.12, 750.08******************************************************************************************** 计算项目: 临空墙-3********************************************************************************************[计算条件]墙高 = 3900.00(mm) 墙宽 = 7000.00(mm) 墙厚 = 300.00(mm) 竖向均布荷载(KN/M): 100.00 墙面均布荷载(KN/M2): 160.00 墙面三角形荷载(KN/M2): 0.00 砼强度等级: C30 配筋计算 as(mm): 30 钢筋级别 : HRB400(RRB400) 支撑条件:**** 上边 下边 左边 右边 简支 固定 固定 固定103.89127507507750-187.010.00-58.05-58.0532.259227129225175075050922750100.0160.039007000[ 内力计算 ]:轴压比 N/(A*fc)= 0.019382 跨中弯矩(kN-m/m):水平:32.25 竖向:103.89垂直板边弯矩(kN-m/m):上下左右0.00, -187.01, -58.05, -58.05[ 配筋结果 ]:竖直方向配筋(mm^2/m):上截面非荷载侧:922.08 荷载侧:251.00中截面非荷载侧:922.08 荷载侧:750.12下截面非荷载侧:922.08 荷载侧:1712.07水平方向配筋(mm^2/m):左中右非荷载侧 750.12, 750.08, 750.12荷载侧 750.08, 750.12, 750.087、人防门框墙验算选用图集07FJ048、建筑结构的总信息/////////////////////////////////////////////////////////////////////////// | 公司名称: | | | | 建筑结构的总信息 | | SATWE 中文版 | | 2012年7月20日16时15分|| 文件名: WMASS.OUT | | | |工程名称 : 设计人 : | |工程代号 : 校核人 : 日期:2013/12/ 2 | ///////////////////////////////////////////////////////////////////////////总信息 ..............................................结构材料信息: 钢砼结构混凝土容重 (kN/m3): Gc = 26.00钢材容重 (kN/m3): Gs = 78.00水平力的夹角(Degree) ARF = 0.00地下室层数: MBASE= 2竖向荷载计算信息: 按模拟施工1加荷计算风荷载计算信息: 计算X,Y两个方向的风荷载地震力计算信息: 计算X,Y两个方向的地震力“规定水平力”计算方法: 楼层剪力差方法(规范方法) 结构类别: 框架结构裙房层数: MANNEX= 0转换层所在层号: MCHANGE= 0嵌固端所在层号: MQIANGU= 1墙元细分最大控制长度(m) DMAX= 1.00弹性板与梁变形是否协调是墙元网格: 侧向出口结点是否对全楼强制采用刚性楼板假定否地下室是否强制采用刚性楼板假定: 否墙梁跨中节点作为刚性楼板的从节点是计算墙倾覆力矩时只考虑腹板和有效翼缘否采用的楼层刚度算法层间剪力比层间位移算法结构所在地区全国风荷载信息 ..........................................修正后的基本风压 (kN/m2): WO = 0.30风荷载作用下舒适度验算风压(kN/m2): WOC= 0.30地面粗糙程度: B 类结构X向基本周期(秒): Tx = 0.00结构Y向基本周期(秒): Ty = 0.00是否考虑顺风向风振: 是风荷载作用下结构的阻尼比(%): WDAMP= 5.00风荷载作用下舒适度验算阻尼比(%): WDAMPC= 2.00是否计算横风向风振: 否是否计算扭转风振: 否承载力设计时风荷载效应放大系数: WENL= 1.00体形变化分段数: MPART= 1各段最高层号: NSTi = 2各段体形系数: USi = 1.30地震信息 ............................................振型组合方法(CQC耦联;SRSS非耦联) CQC 计算振型数: NMODE= 3地震烈度: NAF = 7.00场地类别: KD =II 设计地震分组: 三组特征周期 TG = 0.45地震影响系数最大值 Rmax1 = 0.08用于12层以下规则砼框架结构薄弱层验算的地震影响系数最大值 Rmax2 = 0.50框架的抗震等级: NF = 3剪力墙的抗震等级: NW = 3钢框架的抗震等级: NS = 3抗震构造措施的抗震等级: NGZDJ =不改变重力荷载代表值的活载组合值系数: RMC = 0.50周期折减系数: TC = 0.85结构的阻尼比 (%): DAMP = 5.00中震(或大震)设计: MID =不考虑是否考虑偶然偏心: 否是否考虑双向地震扭转效应: 否按主振型确定地震内力符号: 否斜交抗侧力构件方向的附加地震数 = 0活荷载信息 ..........................................考虑活荷不利布置的层数从第 1 到2层柱、墙活荷载是否折减不折算传到基础的活荷载是否折减折算考虑结构使用年限的活荷载调整系数 1.00------------柱,墙,基础活荷载折减系数-------------计算截面以上的层数---------------折减系数1 1.002---3 0.854---5 0.706---8 0.659---20 0.60> 20 0.55调整信息 ........................................梁刚度放大系数是否按2010规范取值:是托墙梁刚度增大系数: BK_TQL = 1.00梁端弯矩调幅系数: BT = 0.85梁活荷载内力增大系数: BM = 1.00连梁刚度折减系数: BLZ = 0.60梁扭矩折减系数: TB = 0.40全楼地震力放大系数: RSF = 1.000.2Vo 调整分段数: VSEG = 00.2Vo 调整上限: KQ_L = 2.00框支柱调整上限: KZZ_L = 5.00顶塔楼内力放大起算层号: NTL = 0顶塔楼内力放大: RTL = 1.00框支剪力墙结构底部加强区剪力墙抗震等级自动提高一级:是实配钢筋超配系数 CPCOEF91 = 1.15是否按抗震规范5.2.5调整楼层地震力IAUTO525 = 1弱轴方向的动位移比例因子 XI1 = 0.00强轴方向的动位移比例因子 XI2 = 0.00是否调整与框支柱相连的梁内力 IREGU_KZZB = 0薄弱层判断方式:按高规和抗规从严判断强制指定的薄弱层个数 NWEAK = 0薄弱层地震内力放大系数 WEAKCOEF = 1.25强制指定的加强层个数 NSTREN = 0配筋信息 ........................................梁箍筋强度 (N/mm2): JB = 270柱箍筋强度 (N/mm2): JC = 270墙水平分布筋强度 (N/mm2): FYH = 270墙竖向分布筋强度 (N/mm2): FYW = 270边缘构件箍筋强度 (N/mm2): JWB = 210梁箍筋最大间距 (mm): SB = 100.00柱箍筋最大间距 (mm): SC = 100.00墙水平分布筋最大间距 (mm): SWH = 200.00墙竖向分布筋配筋率 (%): RWV = 0.25结构底部单独指定墙竖向分布筋配筋率的层数: NSW = 0结构底部NSW层的墙竖向分布配筋率: RWV1 = 0.60梁抗剪配筋采用交叉斜筋时箍筋与对角斜筋的配筋强度比: RGX = 1.00设计信息 ........................................结构重要性系数: RWO = 1.00柱计算长度计算原则: 有侧移梁端在梁柱重叠部分简化: 不作为刚域柱端在梁柱重叠部分简化: 不作为刚域是否考虑 P-Delt 效应:否柱配筋计算原则: 按单偏压计算按高规或高钢规进行构件设计: 否钢构件截面净毛面积比: RN = 0.50梁保护层厚度 (mm): BCB = 25.00柱保护层厚度 (mm): ACA = 25.00剪力墙构造边缘构件的设计执行高规7.2.16-4: 是框架梁端配筋考虑受压钢筋: 是结构中的框架部分轴压比限值按纯框架结构的规定采用:否当边缘构件轴压比小于抗规6.4.5条规定的限值时一律设置构造边缘构件: 是是否按混凝土规范B.0.4考虑柱二阶效应: 否荷载组合信息 ........................................恒载分项系数: CDEAD= 1.20活载分项系数: CLIVE= 1.40风荷载分项系数: CWIND= 1.40水平地震力分项系数: CEA_H= 1.30竖向地震力分项系数: CEA_V= 0.50温度荷载分项系数: CTEMP = 1.40吊车荷载分项系数: CCRAN = 1.40特殊风荷载分项系数: CSPW = 1.40活荷载的组合值系数: CD_L = 0.70风荷载的组合值系数: CD_W = 0.60重力荷载代表值效应的活荷组合值系数: CEA_L = 0.50重力荷载代表值效应的吊车荷载组合值系数:CEA_C = 0.50吊车荷载组合值系数: CD_C = 0.70温度作用的组合值系数:仅考虑恒载、活载参与组合: CD_TDL = 0.60考虑风荷载参与组合: CD_TW = 0.00考虑地震作用参与组合: CD_TE = 0.00 砼构件温度效应折减系数: CC_T = 0.30地下信息 ..........................................土的水平抗力系数的比例系数(MN/m4): MI = 3.00扣除地面以下几层的回填土约束: MMSOIL = 0回填土容重 (kN/m3): Gsol = 18.00回填土侧压力系数: Rsol = 0.50外墙分布筋保护厚度 (mm): WCW = 35.00室外地平标高 (m): Hout = -0.35地下水位标高 (m): Hwat = -20.00室外地面附加荷载 (kN/m2): Qgrd = 0.001层人防设计等级: Mars = 6级(常规) 人防地下室层数: Mair = 2地下室顶板竖向等效荷载 (kN/m2) QE1 =见PM定义地下室外围墙的人防水平人防等效(kN/m2) QE2 =见PM定义剪力墙底部加强区的层和塔信息.......................层号塔号1 12 1用户指定薄弱层的层和塔信息.........................层号塔号用户指定加强层的层和塔信息.........................层号塔号约束边缘构件与过渡层的层和塔信息...................层号塔号类别1 1 约束边缘构件层2 1 约束边缘构件层********************************************************** 各层的质量、质心坐标信息 **********************************************************层号塔号质心 X 质心 Y 质心 Z 恒载质量活载质量附加质量质量比(m) (m) (t) (t)2 1 61.966 98.877 7.400 42641.3 5029.80.0 2.60(>1.5)1 1 64.608 94.407 3.500 15332.8 3027.9 0.0 1.00活载产生的总质量 (t): 8057.707恒载产生的总质量 (t): 57974.102附加总质量 (t): 0.000结构的总质量 (t): 66031.812恒载产生的总质量包括结构自重和外加恒载结构的总质量包括恒载产生的质量和活载产生的质量和附加质量活载产生的总质量和结构的总质量是活载折减后的结果 (1t = 1000kg)********************************************************** 各层构件数量、构件材料和层高 **********************************************************层号(标准层号) 塔号梁元数柱元数墙元数层高累计高度(混凝土/主筋) (混凝土/主筋) (混凝土/主筋) (m) (m)1( 1) 1 3592(30/ 360) 280(30/ 360) 594(30/ 360) 3.500 3.5002( 2) 1 3505(30/ 360) 281(30/ 360) 610(30/ 360) 3.900 7.400********************************************************** 风荷载信息 **********************************************************层号塔号风荷载X 剪力X 倾覆弯矩X 风荷载Y 剪力Y 倾覆弯矩Y2 1 0.00 0.0 0.0 0.00 0.0 0.01 1 0.00 0.0 0.0 0.00 0.0 0.0===========================================================================各楼层等效尺寸(单位:m,m**2)===========================================================================层号塔号面积形心X 形心Y 等效宽B 等效高H 最大宽BMAX最小宽BMIN1 1 15178.61 63.45 90.39 90.39 171.11 171.26 90.102 1 15178.61 63.45 90.39 90.39 171.11 171.26 90.10=========================================================================== 各楼层的单位面积质量分布(单位:kg/m**2)===========================================================================层号塔号单位面积质量 g[i] 质量比 max(g[i]/g[i-1],g[i]/g[i+1])1 1 1209.65 1.002 1 3140.67 2.60===========================================================================计算信息=========================================================================== 计算日期 : 2013.12. 2 开始时间 : 18:30:25 可用内存 : 1953.00MB 第一步: 数据预处理第二步: 计算每层刚度中心、自由度、质量等信息第三步: 地震作用分析第四步: 风及竖向荷载分析第五步: 计算杆件内力结束日期 : 2013.12. 2时间 : 18:33:40总用时 : 0: 3:15=========================================================================== 各层刚心、偏心率、相邻层侧移刚度比等计算信息Floor No : 层号Tower No : 塔号Xstif,Ystif : 刚心的 X,Y 坐标值Alf : 层刚性主轴的方向Xmass,Ymass : 质心的 X,Y 坐标值Gmass : 总质量Eex,Eey : X,Y 方向的偏心率Ratx,Raty : X,Y 方向本层塔侧移刚度与下一层相应塔侧移刚度的比值(剪切刚度) Ratx1,Raty1 : X,Y 方向本层塔侧移刚度与上一层相应塔侧移刚度70%的比值或上三层平均侧移刚度80%的比值中之较小者RJX1,RJY1,RJZ1: 结构总体坐标系中塔的侧移刚度和扭转刚度(剪切刚度)RJX3,RJY3,RJZ3: 结构总体坐标系中塔的侧移刚度和扭转刚度(地震剪力与地震层间位移的比)===========================================================================Floor No. 1 Tower No. 1Xstif= 72.2977(m) Ystif= 123.6352(m) Alf = 15.0637(Degree) Xmass= 64.6079(m) Ymass= 94.4074(m) Gmass(活荷折减)= 21388.6523( 18360.7402)(t)Eex = 0.1610 Eey = 0.6085Ratx = 1.0000 Raty = 1.0000Ratx1= 2.6933 Raty1= 2.3458薄弱层地震剪力放大系数= 1.00RJX1 = 5.0771E+08(kN/m) RJY1 = 4.8663E+08(kN/m) RJZ1 = 0.0000E+00(kN/m)RJX3 = 1.5707E+08(kN/m) RJY3 = 2.6456E+08(kN/m) RJZ3 = 0.0000E+00(kN/m)---------------------------------------------------------------------------Floor No. 2 Tower No. 1Xstif= 74.9213(m) Ystif= 115.9582(m) Alf = 14.7865(Degree) Xmass= 61.9659(m) Ymass= 98.8770(m) Gmass(活荷折减)=52700.8672( 47671.0703)(t)Eex = 0.2666 Eey = 0.3493Ratx = 0.9076 Raty = 0.8945Ratx1= 1.0000 Raty1= 1.0000薄弱层地震剪力放大系数= 1.00RJX1 = 4.6079E+08(kN/m) RJY1 = 4.3530E+08(kN/m) RJZ1 = 0.0000E+00(kN/m)RJX3 = 8.3311E+07(kN/m) RJY3 = 1.6111E+08(kN/m) RJZ3 = 0.0000E+00(kN/m)---------------------------------------------------------------------------X方向最小刚度比: 1.0000(第 2层第 1塔)Y方向最小刚度比: 1.0000(第 2层第 1塔)============================================================================结构整体抗倾覆验算结果============================================================================抗倾覆力矩Mr 倾覆力矩Mov 比值Mr/Mov 零应力区(%)X风荷载 34773364.0 0.0 347733632.00 0.00Y风荷载 59527580.0 0.0 595275776.00 0.00X 地震 33155036.0 231216.8 143.39 0.00Y 地震 56757208.0 336237.0 168.80 0.00============================================================================结构整体稳定验算结果============================================================================ 层号 X向刚度 Y向刚度层高上部重量 X刚重比 Y刚重比1 0.157E+09 0.265E+09 3.50 921305. 596.70 1005.042 0.833E+08 0.161E+09 3.90 652530. 497.93 962.94该结构刚重比Di*Hi/Gi大于10,能够通过高规(5.4.4)的整体稳定验算该结构刚重比Di*Hi/Gi大于20,可以不考虑重力二阶效应*********************************************************************** 楼层抗剪承载力、及承载力比值 ***********************************************************************Ratio_Bu: 表示本层与上一层的承载力之比---------------------------------------------------------------------- 层号塔号 X向承载力 Y向承载力 Ratio_Bu:X,Y----------------------------------------------------------------------2 1 0.2493E+06 0.2262E+06 1.00 1.001 1 0.2551E+06 0.2471E+06 1.02 1.09X方向最小楼层抗剪承载力之比: 1.00 层号: 2 塔号: 1Y方向最小楼层抗剪承载力之比: 1.00 层号: 2 塔号: 19、楼梯计算梯段号:TB1,2,3(正向荷载作用)加下划线为输入数值正向等效荷载(KN/m2) 50梯板几何尺寸水平步级数n1 10垂直步级数n2 11踏步宽b1 270梯段净高H=n2*a1 1800梯段净跨L1=n1*b1 2700踢步高a1 163.6 上折平台跨L2 0下折平台跨L3 0楼梯斜板长L' 3245梯段全跨L0=(L1+L2+L3)2700斜板厚h=(L'+L2+L3)/30取整180梯板荷载计算斜板重(标准值)g1=25*h*L'/1000 14.60 步级重(标准值) g2=25*0.5*a1*n1/1000 5.52 20水泥沙浆面层(标准值)g3=20*20*(a1+b1)*n1/b1/1000 6.42 10纸筋灰底层(标准值)g4=17*10*(L'+L2+L3)/1000 0.55 梯级面层(一般为水磨石)容重Rm 0.65 梯级面层(一般为水磨石)自重g5=Rm*(a1+b1)*n1/1000 2.82 楼梯栏板自重glb 1.40 人防等效静载q1 50.00 总荷载(设计值) 1.2G+1.0Q 63.30 梯板内力计算跨中弯矩M=0.1*(G+Q)*L0*L0/1000000 46.14 梯板配筋计算梯砼等级C?(20,25,30,35,40) 30 砼抗压强度fc 21.45 梯钢筋等级HRB335fy(HRB335) 405 梯钢筋等级HRB400fy(HRB400) 432 板配筋HRB300As(HRB335) 800 板配筋HRB400As(HRB400) 750 选取的板筋直径 D 12 计算间距1000/(0.785D2) 150.8 最后选定斜板筋间距@ 150 平台配筋计算平台板厚t 150 平台跨度Lt 1600 平台荷载(设计值) Gt+Qt 63.65 平台跨中弯矩Mt=1/10*(Gt+Qt)*Lt*Lt/1000000 16.29 平台配筋HRB335As(HRB335) 345 选用的板筋直径(HRB335)d(HRB335) 10 计算间距1000/As1/(0.785D2) 228 最后选用平台板筋间距@ 150 楼梯平台梁配筋计算梯梁梁宽b b300 梯梁梁高h b500 梯梁梁跨Lb 3100-------------梯梁自重(设计值)g5=1.2*25*b b*h b 4.50 梯板传来荷载(设计值) g6=(G+Q)*L0/2/1000 85.45 平台传来荷载(设计值) g7=(Gt+Qt)*Lt/2/1000 50.92 总均布荷载(设计值)q=Gb+Qb 140.87 栏板传来集中力(设计值) P=1.2*glb*L' 5.45 梯梁支座弯矩Mb1=1/12*(Gb+Qb)*Lb*Lb/1000001 112.82 梯梁跨中弯矩Mb2=1/12*(Gb+Qb)*Lb*Lb+1/4*P*Lb 117.04 梁面纵筋(HRB400)As(HRB400) 601 梁底纵筋(HRB400)As(HRB400) 624 最后选定梁面纵筋(HRB400)条数n m 3最后选定梁面纵筋(HRB400)直径Dm 18 最后选定梁面纵筋(HRB400)面积763 最后选定梁底纵筋(HRB400)条数nb 3最后选定梁底纵筋(HRB400)直径Db 18 最后选定梁底纵筋(HRB400)面积763 梯梁端部剪力V=.5q*Lb+.5*P 221.08 梯梁截面强度验算[V]=0.7ft*b*h0 204.95 砼抗拉强度ft 2.145 是否构造配置梁箍筋计算配箍单肢抗剪箍筋HPB235(2-@100) Asv 4.50 单肢抗剪箍筋HRB335(2-@100)Asv 3.50 单肢抗剪箍筋HRB400(2-@100) Asv 3.28 最后选定梁单肢箍筋HPB23550.30-------------。

人防墙计算

人防墙计算

人防外墙1(RFWQ1) 计算计算假设:按单向板。

已知条件:材料:混凝土C35:fc= 16.7 N/mm2 ftk= 2.2 N/mm2ft= 1.57 N/mm2; Ec= 31500 N/mm2墙主筋HRB400:fy=360N/mm2; Es=200000N/mm2在人防等效静载作用下,材料动力强度提高系数(材料强度综合调整系数):混凝土:ft-1.5×0.8=1.2(用于抗剪计算); fc-1.5(用于抗弯计算); Ec-1.2。

钢筋:强度HPB235:fy-1.5; HRB335:fy-1.35; HRB400:fy-1.20; 弹模Es-1.0。

在人防等效静载作用下,材料动力强度:混凝土C35:ftd= 1.884 N/mm2; fcd= 25.05 N/mm2;Ecd= 37800 N/mm2钢筋:HPB235:fyd=315N/mm2; Es=210000N/mm2HRB400:fyd=432N/mm2; Es=200000N/mm2最小配筋率:非人防计算μmin=max(0.20%,45ft/fy)= .2 %; 人防计算μmin= .25 %。

配筋计算时,考虑受压区钢筋,偏于安全,受压区钢筋仅计入按最小配筋率的钢筋量,当按双筋计算受拉区钢筋大于不考虑受压区钢筋的结果时,按不考虑受压区钢筋的单筋计算。

地下室层高H= 3.95m墙厚Bh= 350mm钢筋保护层厚:迎水面c= 40mm; 其他面c= 20mm墙上下端支座情况:上端铰接,下端固接。

一、荷载:地下室顶板低于室外地面:h1= 1.2m,地下水位(从室外地面算起):h2= .5m土容重r= 19kN/m3;水容重rw=10kN/m3静止土压力系数Ka= .5室外地面荷载:q= 10 kN/m2室外地面荷载引起的水平力:gp=ka*q= 5 kN/m2土压力(未扣除地下水水位以下土浮重)墙顶处土压力:E1=Ka*r*h1= 11.4 KN/m2地下水水位以下土浮重减少的土压力(墙顶部处):E1a=10*(h1-h2)*kA=-3.5 KN/m2 墙底处土压力:E2=ka*r*(h+h1)= 48.925 KN/m2地下水水位以下土浮重减少的土压力(墙底部处):E2a=-10ka*(h+h1-h2)=-23.25 KN/m2地下水压力(墙顶部处):Ew1= 7 KN/m2地下水压力(墙底部处):Ew=rw*(h+h1-h2)= 46.5 KN/m2人防等效静荷载标准值:qe2= 55KN/m2二.内力计算:组合1:用于裂缝计算:Sk=土+水+地面活荷载组合2:用于配筋计算:S=1.2土+1.3水+1.4地面活荷载组合3:在人防等效静载作用下:用于配筋计算:S=1.2土+1.3水+1.0人防组合1(标准值组合):组合后三角形荷载1: gsj1= 37.52 KN/m2, 荷载分布高度H5= 3.95 m组合后三角形荷载2: gsj2= 19.75 KN/m2, 荷载分布高度H4= 3.95 m组合后均布荷载1: gjb1= 19.89 KN/m2, 荷载分布高度H5= 3.95 m跨中最大弯矩位置(从上端计)y= 1.639 m,内力标准值:底部:Mbk= 98.38 KN.m; 跨中:Mzk= 48.02 KN.m; 上端:Mak= 0 KN.m组合2(非人防、设计值组合):组合后三角形荷载1: gsj1= 45.03 KN/m2, 荷载分布高度H5= 3.95 m组合后三角形荷载2: gsj2= 29.95 KN/m2, 荷载分布高度H4= 3.95 m组合后均布荷载1: gjb1= 25.98 KN/m2, 荷载分布高度H5= 3.95 m跨中最大弯矩位置(从上端计)y= 1.639 m,内力设计值:底部:Mb= 128.68 KN.m、Vb= 182.63 KN; 跨中:Mz= 62.8 KN.m; 上端:Ma= 0 KN.m; Va= 68.11 KN组合3(人防、设计值组合):组合后三角形荷载1: gsj1= 45.03 KN/m2, 荷载分布高度H5= 3.95 m组合后三角形荷载2: gsj2= 29.95 KN/m2, 荷载分布高度H4= 3.95 m组合后均布荷载1: gjb1= 18.98 KN/m2, 荷载分布高度H5= 3.95 m组合后均布荷载1: gjb2= 55 KN/m2, 荷载分布高度H= 3.95 m跨中最大弯矩位置(从上端计)y= 1.566 m,内力设计值:底部:Mb= 222.29 KN.m、Vb= 301.13 KN;跨中:Mz= 115.13 KN.m;上端:Ma= 0 KN.m、Va= 139.21 KN三.计算结果:1.非人防荷载作用下:(1).墙下端:c= 40 mm;h0= 300 mm受弯计算配筋:M= 128.68kN.m As= 1247mm2裂缝计算配筋:Mk= 98.38kN.m As= 1627mm2按钢筋直径(mm):d=14计算裂缝宽度:Wmax= .198mm< .2mm; OK!抗剪验算:[Vc]=0.7ft*h0= 329.7 KN>Vb= 182.63 KN; OK!(3).墙跨中:c= 20 mm;h0= 320 mm受弯计算配筋:M= 62.8kN.m As= 875mm2裂缝计算配筋:Mk= 48.02kN.m As= 875mm2按钢筋直径(mm):d=14计算裂缝宽度:Wmax= .124mm< .3mm; OK!2.人防荷载作用下计算结果:(1).墙下端:c= 40 mm;h0= 300 mm受弯计算配筋:M= 222.29kN.m As= 1809mm2抗剪验算:[Vcd]=0.7*0.8ftd*h0= 474.768 KN>Vb= 301.13 KN; OK!(3).墙跨中:c= 20 mm;h0= 320 mm受弯计算配筋:M= 115.13kN.m As= 875mm2人防外墙2(RFWQ2) 计算已知条件:材料:混凝土C35:fc= 16.7 N/mm2 ftk= 2.2 N/mm2ft= 1.57 N/mm2; Ec= 31500 N/mm2墙主筋HRB400:fy=360N/mm2; Es=200000N/mm2在人防等效静载作用下,材料动力强度提高系数(材料强度综合调整系数):混凝土:ft-1.5×0.8=1.2(用于抗剪计算); fc-1.5(用于抗弯计算); Ec-1.2。

人防墙计算

人防墙计算
参数输入 人防等效静荷载q(KN/m2) 墙高 l1(m) 墙长 l2(m) 墙厚 h(mm) 截面有效高度 h0 (mm) 混凝土抗压强度 fc(N/mm ) 钢筋强度 fy(N/mm )
2 2
270 6.2 7 400 365 28.65 432
计算截面位置 由静力计算手册查弯矩系数 每米弯矩设计值M (KN.m) α s=M/(fcbh02) 相对受压区高度ξ As=ξ fcbh0/fy (mm )
结果输出 每米弯矩设计值M=1/10*q*l2 (KN.m) 2 α s=M/(fcbh0 ) 相对受压区高度ξ =1-(1-2α s)^0.5 As=ξ fcbh0/fy (mm2)
196.83 0.1633 0.1794 2014.72
7.门框墙(侧向悬挑)
参数输入 直接作用静荷载q1(KN/m2) 门板作用线荷载q2(KN/m) 墙长 l(m) 墙厚 h(mm) 截面有效高度 h0 (mm) 混凝土抗压强度 fc(N/mm ) 钢筋强度 fy(N/mm2)
2
108 0.1362 0.1470 1338.67
6.风井临空墙2(两侧支承)
参数输入 人防等效静荷载q(KN/m2) 墙长 l(m) 墙厚 h(mm) 截面有效高度 h0 (mm) 混凝土抗压强度 fc(N/mm ) 钢筋强度 fy(N/mm )
2 2
270 2.7 300 265 17.16 405
2
583.8075 0.1530 0.1669 4039.54
2.防护单元分隔墙(上下支承)
参数输入 人防等效静荷载q(KN/m2) 墙高 l(m) 墙厚 h(mm) 截面有效高度 h0 (mm) 混凝土抗压强度 fc(N/mm ) 钢筋强度 fy(N/mm )

人防计算书

人防计算书

200厚填充墙线荷〔9×0.2+0.4×2〕×2.5=6.5KN/m 2普通板面荷18×0.01+20×0.02+24×0.04+0.4=1.96取2 KN/m 2卫生间厨房18×0.01+20×0.02+24×0.05+0.4=2.18取2.2 KN/m 2屋面(机房,出屋面楼梯间所在楼面层)为上人屋面。

≥24层,外墙到第二道腰线处以上弯200 门窗洞口宽度为建筑洞宽+40北外墙地下室人防核6常6,顶板q =70 KN/m 2外墙q =40 KN/m 2底板q =55 KN/m 2Q 活=10 KN/m 2Q 活侧=10/19×19×0.4=4 KN/m 2Q 覆土=19×0.875×0.4=6.65 KN/m 2 Q 土水上=19×0.125×0.4=0.95KN/m 2 Q 土水下=11×3.78×0.4=16.632 KN/m 2 Q 水=10×3.78=37.8KN/m 2人防M B K=KNm 245.768905.340822-=⨯=-ql 活M B K=KNm 624.78905.34822-=⨯=-ql 覆土M B K=KNm 676.128905.365.6822-=⨯=-ql 人防M max K=KNm 888.428905.3409128922-=⨯⨯=-ql X =4m 46.18905.3383=⨯=l 活M maxK =KNm 289.4128905.3492=⨯⨯覆土M maz K=KNm 13.7128905.3492=⨯⨯水上土活M B K=KNm 0025.05316125.095.053162222=⎪⎪⎭⎫⎝⎛-⨯-=⎪⎪⎭⎫ ⎝⎛--ααqa 905.3125.0=α R A =()KN ql qb 275.1905.378.34905.3878.395.042323=⎪⎭⎫⎝⎛-⨯⨯=-β m q R a X A 467.1=+= M maz =KNm q R a R A A 015.12=⎪⎪⎭⎫⎝⎛+ 水下土+水 M BK=⎪⎪⎭⎫⎝⎛+-⨯-=⎪⎪⎭⎫ ⎝⎛+--53342478.3432.545334242222ββββqb 96799.0905.378.3==β m qbR b a X A768.12=+=R A =KN l qb 433.1951823=⎪⎭⎫⎝⎛-β M max =KNm qb R b a R A A 713.23232=⎪⎪⎭⎫⎝⎛+ M B =1.35×(12.676+0.0025+1.807+53.737)+0.7×1.4×7.624+76.245=175.8KNmM max =1.35×(7.13+0.0047+1.015+23.713)+0.7×1.4×4.289+42.888=90.1KNm M B K=12.676+0.0025+1.807+53.737+7.624/2=72KNm M max K=7.13+0.0047+1.015+23.713+4.289/2=34KNm M B =175.8KNmC25砼 Ⅲ级钢 f c =16.7 f tk =2.201327.02305.110007.160.1108.17526=⨯⨯⨯⨯⨯=s α 9285.02211=-+=ss αγ2619062303602.19285.0108.175mm A s =⨯⨯⨯⨯=16@100(2015) M max =90.10575.02505.110007.160.1101.9026=⨯⨯⨯⨯⨯=s α9703.02211=-+=ss αγ268602503602.19703.0101.90mm A s =⨯⨯⨯⨯=12/14@150(890)As min =0.25%⨯300⨯1000=0.0134504.00134.093.1782.265.01.1⨯⨯⨯-=ϕmm mm 2.018.00134.01608.0509.110293.178504.01.25<=⎪⎭⎫⎝⎛⨯+⨯⨯⨯⨯⨯=ω以内 26/64.17525089087.01034mm N sk=⨯⨯⨯=σ 286.001.064.1752.265.01.101.0=⨯⨯-==ϕρte mm mm 2.0105.001.01308.0309.110264.175286.01.25<=⎪⎭⎫⎝⎛⨯+⨯⨯⨯⨯⨯=ω次口楼电梯临空墙C35 f c =16.7 &=300 h 0=260M B K=KNm 8.2478905.3130822=⨯=ql M maz =KNm 4.139128905.313092=⨯⨯ 外1463.02605.110007.160.1108.24726=⨯⨯⨯⨯⨯=s α 9205.02211=-+=ss αγ2623972603602.19205.0108.247mm A s =⨯⨯⨯⨯=22@150(2534) &=350外1099.03005.110007.160.1108.24726=⨯⨯⨯⨯⨯=s α 9416.02211=-+=ss αγ2620313003602.19416.0108.247mm A s =⨯⨯⨯⨯=20@150(2095), 18@125(2039)0618.03005.110007.160.1104.13926=⨯⨯⨯⨯⨯=s α968.02211=-+=ss αγ2611123003602.1968.0104.139mm A s =⨯⨯⨯⨯=14/16@150(1183)As min =0.25%⨯350⨯1000=875mm 2 &=300 内0823.02605.110007.160.1104.13926=⨯⨯⨯⨯⨯=s α957.02211=-+=ss αγ2612972603602.1957.0104.139mm A s =⨯⨯⨯⨯=16@150(1340)扩散室临空墙单向板简支KNm qM 8.158.1832=⨯=&=30001.025010005.17.160.1108.1526=⨯⨯⨯⨯⨯=s α 99.02211=-+=ss αγ261482503602.199.0108.15mm A s =⨯⨯⨯⨯=As min =750mm 212@150(1340)上简支,下固定梁式板 12@150 ,四边简支64.0905.35.2==y x l l , 7.195.23902652.0610764.02=⨯⨯⎪⎭⎫ ⎝⎛⨯+=x m6.95.2390764.06102652.02=⨯⨯⎪⎭⎫⎝⎛⨯+=y m12@150扩散室悬板活门临空墙&=300KNm MBK8.2478905.31302-=⨯-=049.045010005.17.160.1108.24726=⨯⨯⨯⨯⨯=s α 9749.02211=-+=ss αγ2613084503602.19749.0108.247mm A s =⨯⨯⨯⨯=As min =0.25%×1000×500=1250mm 2 14@100(1539)四边简支922.025002305==y x l l KNm m x 3.34305.213003606.06104357.02=⨯⨯⎪⎭⎫ ⎝⎛⨯+=KNm m y 9.29305.213004357.06103606.02=⨯⨯⎪⎭⎫⎝⎛⨯+=通道(人防主口) 侧墙:&=300上水q 水上=10×2.9=29 下水q 水下=10×3.45=34.5水上土q 土水上=19×0.75×0.4=5.7 水下土q 土水下=11×2.9×0.4=12.767 侧土q 侧土=11×3.45×0.4=15.18 活q 活=10×0.4=4 人防q 防=4085.345.3=α 1039.085.34.0==β49.675.1418.155.34523=⎪⎪⎭⎫ ⎝⎛+=αβqa R A ⎪⎭⎫ ⎝⎛-=52122αqa R A6.1547.3518.155.34531222--=⎪⎪⎭⎫⎝⎛--=αqa M B 214.1==qaR ax A 26.594.1118.155.34232max ==qa R Ra M A()4.1822.881.4167.5777.576.127.5294046883=+-=ααqa R A ()2268α-=qa R B()72.2215.1065.5124.7112.776.127.5294042822-----=--=αqa M B m qR x A44.1==27.1393.514.3057.4116.476.127.5294042max 2=-=g R M A()KNm M B K 39.21056.383.206212.772.2265.5124.7147.356.15=--=-++++-=C35 f c =16.7 &=300 h 0=230mm1588.023010005.17.160.11039.21026=⨯⨯⨯⨯⨯=s α 913.02211=-+=ss αγ2623202303602.1913.01039.210mm A s =⨯⨯⨯⨯=18@100(2545) &=350 h 0=270mm1152.027010005.17.160.11039.21026=⨯⨯⨯⨯⨯=s α9386.02211=-+=ss αγ2619222703602.19386.01039.210mm A s =⨯⨯⨯⨯=16@100(2011)()KNm M B 02.19012.70.7 4.172.2215.1065.5147.356.1535.1-=⨯⨯-++++⨯-=1561.027010005.17.160.11002.19026=⨯⨯⨯⨯⨯=s α 915.02211=-+=ss αγ2621382703602.1915.01002.190mm A s =⨯⨯⨯⨯=KNm M B K 15.139-=26/57.294201127087.01015.139mm N s ⨯⨯⨯=σ0145.010003505.02545=⨯⨯=te ρ6775.00145.076.2322.265.01.1=⨯⨯-=ψ3.00145.01608.0509.110276.2326775.01.25=⎪⎭⎫⎝⎛⨯+⨯⨯⨯⨯⨯=ω &=400 h 0=320mm1561.032010005.17.160.11002.19026=⨯⨯⨯⨯⨯=s α 941.02211=-+=ss αγ261753320360941.01002.190mm A s =⨯⨯⨯=选用 16@100(2011)0145.010004005.02011=⨯⨯=te ρ525.001.05.2482.265.01.1=⨯⨯-=ψ31.001.01608.0509.11025.248525.01.25=⎪⎭⎫⎝⎛⨯+⨯⨯⨯⨯⨯=ω 26/5.248201132087.01015.139mm N sk ⨯⨯⨯=σ选用 18@100(2545)26/4.196254532087.01015.139mm N sk⨯⨯⨯=σ 0127.010004005.02454=⨯⨯=te ρ528.00127.04.1962.265.01.1=⨯⨯-=ψ23.00127.01808.0509.11024.196528.01.25=⎪⎭⎫⎝⎛⨯+⨯⨯⨯⨯⨯=ω 人防配筋&=400 M B =210.39082.032010005.17.160.11039.21026=⨯⨯⨯⨯⨯=s α 957.02211=-+=ss αγ2615913202.1360957.01039.210mm A s =⨯⨯⨯⨯=KNm M 19.11008.211.108216.427.1393.514.3057.4126.594.11max =+=++++++=防0359.035010005.17.160.11019.11026=⨯⨯⨯⨯⨯=s α 98.02211=-+=ss αγ1000%25.07443502.136098.01019.11026=<=⨯⨯⨯⨯=bh mm A s取 16@200()KNmM 91.9316.498.027.1393.514.3026.594.1135.1max =⨯+++++⨯=0459.035010007.160.11091.9326=⨯⨯⨯⨯=s α9765.02211=-+=ss αγ267643503609765.01091.93mm A s =⨯⨯⨯=26/43.217100535087.01054.66mm N sk =⨯⨯⨯=σ 01.0=te ρ4423.001.043.2712.265.01.1=⨯⨯-=ψ mm mm 2.019.001.01608.0209.110243.2174423.01.25<=⎪⎭⎫ ⎝⎛⨯+⨯⨯⨯⨯⨯=ω。

人防外墙计算书

人防外墙计算书

人防外墙计算书人防外墙计算书本计算依据《人民防空地下室设计规范》GB50038-2005简称《规范》,其余规范按国家统一标准。

条件:地下室覆土高度Lo=500mm,层高L=5000mm,侧墙厚度d=400mm,保护层厚度c=50mm,混凝土强度等级为C30,fc=14.3N/mm ,材料调整系数γd=1.5钢筋等级为HRB335,fy=300N/mm ,材料调整系数γd=1.35本工程设防水位高于底板且低于顶板,水位高Lw=4500mm,地面堆载q1=10kN/m ,等效人防荷载qr=60kN/m顶板与侧墙固接,侧墙弯矩调幅系数μ=0.8,静止土压力系数K=0.5土容重γ=18kN/m ,浮容重γ1=11kN/m计算:1、荷载计算:地面堆载qd=q1×K=10×0.5=5.00kN/m土压力:qt1=K×γ×Lo=0.5×18×0.50=4.50kN/mqt2=K×γ×(Lo+L-Lw)=0.5×18×(0.50+5.00-4.50)=9.00kN/m qt3=qt2+K×γ1×Lw=9.00+0.5×11×4.50=33.75kN/m水压力:qw=10×Lw=10×4.50=45.00kN/m人防荷载qr=60.00kN/m2、弯矩计算:(本计算仅仅计算侧墙底部弯矩,上部配筋按下部做法)堆载弯矩:Md=qd×L /12=5.00×5.00 /12=10.42kN.m土弯矩:Mt=qt3×L /20=33.75×5.00 /20=42.19kN.m(简化计算)水弯矩:Mw=qw×L /20=45.00×5.00 /20=56.25kN.m(简化计算)人防弯矩:Mr=qr×L /12=60.00×5.00 /12=125.00kN.m3、内力组合:(本工程按受弯构件、单向板简化计算)(1)、战时强度计算内力组合:Mq=1.2×(Mt+Mw)+1.0×Mr 按《规范》4.10.2-1 ∴Mq=1.2×(42.19+56.25)+1.0×125.00=243.13kN.m(2)、平时裂缝计算内力组合:Mk=Md+Mt+Mw 按标准组合。

人防外墙计算书(2006版规范)

人防外墙计算书(2006版规范)

4.水压力计算:
E0wB := γw ⋅ d0 5.内力计算:
E0wB = 35000Pa
恒荷载分项系数
γG := 1.2
等效静荷载分项系数:γQ1 := 1.0
上部竖向力标准值: P1 := γ ⋅ Ls ⋅ Lh ⋅ H1
活载分项系数 P1 = 140400N
γQ2 := 1.4
内力设计值:
( ) P := γQ1 ⋅ B ⋅ qe1 ⋅ Ls + γG ⋅ B ⋅ h ⋅ H ⋅ γcg + P1
fsd
Es ⋅ ε cu
8.砼受压区等效高度计算
ε cu = 0.0033 ξb = 0.494
按GB50010 − 2002中 7.3.4条
σs := fsd
对称配筋按GB50010 − 2002 式 7.3.4 − 1计算x
x :=
P
α1 ⋅ fcd ⋅ B
x = 0.012m
截面受压 := "满足GB50010-2002式7.2.1-4" if x ≥ 2as "按GB50010-2002式7.2.5计算正截面受压承载力" otherwise
⋅ E0Br
+
5 8

E0Ar⎞⎠
⎤ ⎦
⋅ B⋅ H
V = 268019.35N
混凝土的动力强度折减系数 γc := 0.8
材料参数:fcuk := C
α1 := 1.0
γds := 1.35
γdc := 1.5
fcd := γc ⋅ γdc ⋅ fc fsd := γds ⋅ fy
6.承载力计算参数
η otherwise
η = 1.034

人防地下室墙体计算书

人防地下室墙体计算书

WQ1地下室侧壁计算书条件:1、土质参数:容重γ=18kN/mmγ` = 11kN/mm K=0.50,地下水位设防高度为5100mm;2、地下室参数:覆土层厚h1=1000mm,地下室侧墙计算跨度Lo=4800mm,临水面保护层为40mm;地面堆载q=10kN/mm d=350mm,截面有效高度ho=300mm3、材料参数:混凝土强度等级为C35,fc=16.7 N/mm fy=360N/mm 计算:1、荷载计算,土压力按静止土压力计算[《全国民用建筑工程设计技术措施》2.6.2]堆载折算为土压力q1=K×q=0.50×10=5.00kN/mm地下水位以上土压力q2=K×γ×h1=0.50×18×1.00=9.00kN/mm地下水位以下土压力q3=K×γ`×(h2 + h3)=0.50×11×(0.30+4.80)=28.05kN/mm水压力q4=γw×(h2 + h3)=10×(0.30+4.80)=51.00kN/mm2、支座弯距计算,按单向板底端固定顶端简支计算,查静力计算手册m1=q1×Lo/8=5.00×4.8/8=14.40kN.mm2=q2×Lo/15=9.00×4.8/15=13.82kN.mm3=q1×Lo/15=28.05×4.8/15=43.08kN.mm4=q1×Lo/8=51.00×4.8/15=78.34kN.m3、强度计算:土压力及水压力均按恒载考虑,[《全国民用建筑工程设计技术措施》2.6.2],按支座调幅计算m=0.80×1.35×(m1+m2+m3+m4)=161.62kN.mξb=0.8÷{1+360÷[20000×(0.0033-<35-50>×0.00001)]}=0.5257 《砼》规公式7.1.4x=ho-√(ho-2×m/α1/fc/b)=300-√(300-2×161.62×1000000/1/16.7/1000) 《砼》规公式7.2.1-1=34.21mm<ξb×ho=157.71mmAs=α1×fc×b×x/fy 《砼》规公式7.2.1-2=1×16.7×1000×34.21/360=1,587mm4、裂缝计算:弯距标准组合Mk=m1+m2+m3+m4=14.40+13.82+43.08+78.34=149.64kN.m实配钢筋为:18@75钢筋面积As=3,393mm带肋钢筋的相对粘结特性系数υ=1.0矩形截面受弯构件,构件受力特征系数αcr =2.1对矩形截面的受弯构件:Ate=0.5×b×h=0.5×1000×300=175000mmρte=As/Ate=3,393/175000=0.0194纵向受拉钢筋的等效应力σsk=Mk/(0.87×ho×As)=150×1000000/(0.87×300×3,393)=169 N/mm 钢筋应变不均匀系数ψ=1.1-0.65×ftk/ρte/σsk=1.1-0.65×2.2/0.02/169/=0.6635最大裂缝宽度ωmax=αcr×ψ×σsk×(1.9×c+0.08×deq/ρte)/Es=2.1×0.6635×169×(1.9×40+0.08×18/0.02)/200000=0.1769mm5、人防计算:本工程为6级人防地下室。

人防计算书

人防计算书

1. 人防地下室外墙计算墙厚250mm 砼强度等级C40 钢筋级别HRB400土内摩擦角 Φ=22° 土容重 r=18KN/m 3地下室底板顶标高-5.100m ; 覆土厚1.5m地下室底板标高 –1.500m 处① 考虑地面活荷载影响(消防车) 取 q=20KN/㎡产生的土压力荷载 (折合为荷载作用高度)h=q/r=20/18=1.11mq 1=rhk 0=18×1.11×0.63=12.6 KN/㎡{ EMBED Equation.DSMT4 |0k =1-sin =0.63② 土压力产生的荷载:q 2=rhk 0=18×3.6×0.63=41KN/㎡③ 地下室顶板到室外,室内外高差300mm ,1.2m 范围内土体产生的荷载q 3=rhk 0=18×1.2×0.63=13.6KN/㎡④ 人防荷载外墙等效静荷载根据《人防规范》表4.8.3-1 湿陷性黄土考虑上部结构影响 λ=1.1 (4.8.3)25×1.1=27.52. 配筋计算<1> 战时矩形荷载:q a = 1.2×13.6+1.4×27.5×0.63=41KN/㎡三角形荷载:q b= 1.2×41=49.2KN/㎡上端:简支下端:固定左端:固定右端:固定Ly/Lx=3.6/4.8=0.75①矩形荷载作用下:Mx=0.03333×ql2=0.0333×41×3.62=17.7KN·m My=0.0107×ql2=0.0107×41×3.62=5.7KN·mMx0=-0.0748×ql2=-0.0748×41×3.62=-39.8KN·m My0=-0.0571×ql2=-0.0571×41×3.62=-30.3KN·m ②三角形荷载作用下Mx max=0.0096×49.2×3.62=6.1KN·mMy max=0.0161×49.2×3.62=10.3KN·mMx0 max=-0.0338×49.2×3.62=-2.2KN·m My0 max=-0.0482×49.2×3.62=-3.1KN·m Mx=Mx maxMy=My maxMx0 = Mx0 max弯距设计值叠加为:Mx=17.1+6.1=23.8 KN·mMx=5.7+10.3=16 KN·mMx0=-39.8-2.2=-42 KN·mMy0=-30.3-3.1=-33.4 KN·m19.1×1.5=28.65360×1.2=432X向配筋Y向配筋<2> 平时矩形荷载:q a= 1.2×13.6+1.4×12.6=34KN/㎡三角形荷载:q b= 1.2×41=49.2KN/㎡Ly/Lx=3.6/4.8=0.75①矩形荷载作用下:Mx=0.03333×ql2=0.0333×34×3.62=14.7KN·mMy=0.0107×ql2=0.0107×34×3.62=4.7KN·mMx0=-0.0748×ql2=-0.0748×34×3.62=-33KN·mMy0=-0.0571×ql2=-0.0571×34×3.62=-25.2KN·m②三角形荷载作用下Mx =0.0096×49.2×3.62=6.1KN·m+14.7=20.8 KN·mMy =0.0161×49.2×3.62=10.3KN·m+4.7=15 KN·mMx0 =-0.0338×49.2×3.62=-21.6KN·m-33=-54.6KN·mMy0 =-0.0482×49.2×3.62=-31KN·m-25.2=56.2 KN·mX向配筋12@140Y向配筋12@180。

人防计算书

人防计算书

人防计算书(暖通部分)【参考文献及设计依据】《人民防空地下室设计规范》GB50038-2005《防空地下室通风设计》07FK01~02【人防概况】本工程人防等级为二等人员掩蔽所,设二个人防单元,设在地下四层,平时作汽车库用。

人防面积(m^2):3236人防掩蔽面积(m^2):2104人防掩蔽人数(人):2104【人防单元一】人防面积(m^2):1404人防掩蔽面积(m^2):913人防掩蔽人数(人):913【通风部分】:清洁通风新风指标(m^3/p):6清洁通风新风量(m^3/h):5478滤毒通风新风指标(m^3/p):3.0滤毒通风新风量(m^3/h):2739防毒通道实际换气次数(h-1):>40【防护通风】:1.清洁式通风新风量:L1=913*6=5478(m^3/h)2.滤毒式通风新风量:(1).按人数计算:LR=913*3=2739(m^3/h)(2).按保证防毒通道换气次数计算:L3=11.5*3.3*40=1520(m^3/h)保证人防工程计算漏风量:Lf=913*3.3*7%=211(m^3/h)LH=L3+Lf=1520+211=1731(m^3/h)因为LR>LH 所以滤毒通风新风量应取:L2=LR=2739(m^3/h)设计滤毒通风新风量应不小于2739(m^3/h) 【设备选型】:1.粗效过滤器:设计计算风量: 5478(m^3/h)选用:LWP-X-1600型过滤器单个处理风量:1400(m^3/h)需要油网过滤器个数:3.91实际选型个数:52.吸收器数量:设计计算风量: 2739(m^3/h)选用:RFP-1000型吸收器单台额定风量:1000(m^3/h)需要吸收器个数:2.74实际选型个数:33.自动排气阀:设计计算风量: 2739(m^3/h)选用:PS-D250排气阀单个排气量:800(m^3/h)需要排气阀个数:3.16实际选型个数:44.电动脚踏二用风机:设计计算风量: 5478(m^3/h)(清洁式通风)2739(m^3/h)(滤毒式通风) 选用:DJF-1型电动脚踏二用风机单台风量:2421(m^3/h) (清洁式通风)1225(m^3/h) (滤毒式通风) 需要电动脚踏二用风机台数:2.26/2.24实际选型台数:35.排风机:SWF-III型高效低噪声混流式通风机No.4风量:6801 (m^3/h)风压:710(Pa)功率:4.0(KW)【隔绝防护时间】:t=1000V(C-Co)/N.C1V=913x3.4=3104 m3C=2.5%Co=0.40%N=913 人C1=20 L/P.ht=3.47 h本工程需要隔绝防护时间:3h本工程实际隔绝防护时间:3.47h实际隔绝防护时间>需要隔绝防护时间,所以满足要求!【人防单元二】人防面积(m^2):1832人防掩蔽面积(m^2):1191人防掩蔽人数(人):1191【通风部分】:清洁通风新风指标(m^3/p):5.5清洁通风新风量(m^3/h):6550滤毒通风新风指标(m^3/p):2.5滤毒通风新风量(m^3/h):2977防毒通道实际换气次数(h-1):>40【防护通风】:1.清洁式通风新风量:L1=1191*5.5=6550(m^3/h)2.滤毒式通风新风量:(1).按人数计算:LR=1191*2.5=2977(m^3/h)(2).按保证防毒通道换气次数计算:L3=11.5*3.3*40=1520(m^3/h)保证人防工程计算漏风量:Lf=1191*3.3*7%=275(m^3/h)LH=L3+Lf=1520+275=1795(m^3/h)因为LR>LH 所以滤毒通风新风量应取:L2=LR=2977(m^3/h)设计滤毒通风新风量应不小于2977(m^3/h) 【设备选型】:1.粗效过滤器:设计计算风量: 6550(m^3/h)选用:LWP-X-1600型过滤器单个处理风量:1400(m^3/h)需要油网过滤器个数:4.68实际选型个数:52.吸收器数量:设计计算风量: 2977(m^3/h)选用:RFP-1000型吸收器单台额定风量:1000(m^3/h)需要吸收器个数:2.98实际选型个数:33.自动排气阀:设计计算风量:2977(m^3/h)选用:PS-D250排气阀单个排气量:800(m^3/h)需要排气阀个数:3.38实际选型个数:44.电动脚踏二用风机:设计计算风量: 6550(m^3/h)(清洁式通风)2977(m^3/h)(滤毒式通风) 选用:DJF-1型电动脚踏二用风机单台风量:2421(m^3/h) (清洁式通风)1225(m^3/h) (滤毒式通风) 需要电动脚踏二用风机台数:2.70/2.43 实际选型台数:35.排风机:SWF-III型高效低噪声混流式通风机No.4风量:6801 (m^3/h)风压:710(Pa)功率:4.0(KW)【隔绝防护时间】:t=1000V(C-Co)/N.C1V=1191x3.4=4049.4 m3C=2.5%Co=0.43%N=1191 人C1=20 L/P.ht=3.41 h本工程需要隔绝防护时间:3h本工程实际隔绝防护时间:3.41h实际隔绝防护时间>需要隔绝防护时间,所以满足要求!。

人防地下室钢筋砼外墙计算书

人防地下室钢筋砼外墙计算书

人防地下室钢筋砼外墙计算书项目名称构件编号日期设计校对审核执行规范:《混凝土结构设计规范》(GB 50010-2010), 本文简称《混凝土规范》《建筑结构荷载规范》(GB 50009-2001), 本文简称《荷载规范》《人民防空地下室设计规范》(GB 50038-2005), 本文简称《人防规范》钢筋:d - HPB300; D - HRB335; E - HRB400; F - RRB400; G - HRB500; P - HRBF335; Q - HRBF400; R - HRBF500-----------------------------------------------------------------------1 基本资料2 计算(1)荷载计算 (2)内力计算 (3)配筋计算 (4)裂缝验算荷载说明:永久荷载:土压力荷载,上部恒载-平时,可变荷载:地下水压力,地面活载,上部活载-平时 平时组合:平时荷载基本组合 战时组合:战时荷载基本组合准永久组合:平时荷载咱•组合(用于裂缝计算)2.1 荷载计算2.1.1 墙上竖向压力平时组合(kN/m ):1.200×50.000+1.400×50.000=130.000 准永久组合(kN/m ):50.000+0.500×50.000=75.000 2.1.2 侧压荷载计算 (1) 土压力标准值(kPa)水土分算,土侧压按静止土压力计算,静止土压力系数k = 0.500 地下室顶面,标高0.000,在地面(-0.300)以上 =p 0=p w 0土压力起算位置,标高-0.300 =p 0=p w 0-1层底,标高-3.320,总埋深3.020,地下水位以上0.500,地下水位以下2.520=+=+=p k γh 1k ( )-γs a t γw h 2⨯⨯0.5180.5⨯⨯0.5( )-2010 2.52 17.1 ===p w γ w h ⨯10 2.52 25.2-2层底,标高-6.320,总埋深6.020,地下水位以上0.500,地下水位以下5.520=+=+=p k γh 1k ( )-γs a t γw h 2⨯⨯0.5180.5⨯⨯0.5( )-2010 5.52 32.1 ===p w γ w h ⨯10 5.52 55.2 地下水位处, 标高-0.800,埋深0.500 ===p k γh ⨯⨯0.5180.5 4.5=p w 0 式中:p --------土压力(kN/m 2) p w --------水压力(kN/m 2)k --------土压力系数r --------土的天然容重(kN/m3)r sat--------土的饱和容重(kN/m3)r w--------水的重度(kN/m3)h1--------地下水位以上的土层厚度(m)h2--------地下水位以下的土层厚度(m) (2)地面上活载等效土压力(标准值,kPa):p=kG k=0.500×20.000=10.000-1层顶高出外地坪面,为了简化内力计算,使用插值法修正了顶面处的侧压荷载值2.2 内力计算按连续梁计算竖向弯矩按连续梁模型计算,水平向弯矩仍按板块模型计算结果不进行调幅平时组合弯矩图准永久组合弯矩图2.3 配筋及配筋成果表2.3.1 配筋说明:(1)配筋方法水平按纯弯配筋,竖向取压弯与纯弯配筋的大值(2)单位说明:以下各表格中单位除说明外,配筋面积单位:mm2/m,裂缝宽度单位:mm,弯矩单位kN.m/m,轴力单位kN/m,配筋率:%2.4 裂缝验算按实际配筋,及相应于准永久组合的弹性内力进行计算实际配筋简图-----------------------------------------------------------------------【理正结构设计工具箱软件 6.5】计算日期: 2012-05-17 15:49:51地下室外墙计算项目名称构件编号日期设计校对审核执行规范:《混凝土结构设计规范》(GB 50010-2010), 本文简称《混凝土规范》《建筑结构荷载规范》(GB 50009-2001), 本文简称《荷载规范》《人民防空地下室设计规范》(GB 50038-2005), 本文简称《人防规范》钢筋:d - HPB300; D - HRB335; E - HRB400; F - RRB400; G - HRB500; P - HRBF335; Q - HRBF400; R - HRBF500-----------------------------------------------------------------------1 基本资料板边支撑条件表2 计算(1)荷载计算 (2)内力计算 (3)配筋计算 (4)裂缝验算荷载说明:永久荷载:土压力荷载,上部恒载-平时,可变荷载:地下水压力,地面活载,上部活载-平时 平时组合:平时荷载基本组合 战时组合:战时荷载基本组合准永久组合:平时荷载咱•组合(用于裂缝计算)2.1 荷载计算2.1.1 墙上竖向压力平时组合(kN/m ):1.200×50.000+1.400×50.000=130.000 准永久组合(kN/m ):50.000+0.500×50.000=75.000 2.1.2 侧压荷载计算 (1) 土压力标准值(kPa)水土分算,土侧压按静止土压力计算,静止土压力系数k = 0.500 地下室顶面,标高0.000,在地面(-0.300)以上 =p 0=p w 0土压力起算位置,标高-0.300 =p 0=p w 0-1层底,标高-3.320,总埋深3.020,地下水位以上0.500,地下水位以下2.520=+=+=p k γh 1k ( )-γs a t γw h 2⨯⨯0.5180.5⨯⨯0.5( )-2010 2.52 17.1 ===p w γ w h ⨯10 2.52 25.2-2层底,标高-6.320,总埋深6.020,地下水位以上0.500,地下水位以下5.520=+=+=p k γh 1k ( )-γs a t γw h 2⨯⨯0.5180.5⨯⨯0.5( )-2010 5.52 32.1 ===p w γ w h ⨯10 5.52 55.2 地下水位处, 标高-0.800,埋深0.500 ===p k γh ⨯⨯0.5180.5 4.5=p w 0 式中:p --------土压力(kN/m 2) p w --------水压力(kN/m 2)k --------土压力系数r --------土的天然容重(kN/m3)r sat--------土的饱和容重(kN/m3)r w--------水的重度(kN/m3)h1--------地下水位以上的土层厚度(m)h2--------地下水位以下的土层厚度(m) (2)地面上活载等效土压力(标准值,kPa):p=kG k=0.500×20.000=10.000-1层顶高出外地坪面,为了简化内力计算,使用插值法修正了顶面处的侧压荷载值2.2 内力计算平时组合:按弹性板计算准永久组合:按弹性板计算2.2.1 竖向压力(设计值,kN/m)平时组合:130.000准永久组合:75.0002.2.2 弯矩(1) 弯矩正负号规定内侧受拉为正,外侧受拉为负算。

人防临空墙计算书

人防临空墙计算书

------------------------------------------------------------------- 计算项目: 人防临空墙 1------------------------------------------------------------------- [ 计算条件 ]墙长 = 4.95(m) 墙宽 = 2.90 (m) 墙厚 = 300 (mm)墙面均布荷载: 130.00 (kN/m^2)竖向均布荷载: 0.00 (kN/m)砼强度等级: C40纵筋级别: HRB400配筋计算as (mm):: 15 (mm)跨中弯矩调整系数: 1.00 支座弯矩调整系数: 1.00支承条件:**** 下边右边上边左边固接固接简支固接[内力结果] (已乘弯矩调整系数)内力按塑性理论计算(适用于大偏心受压):跨中弯矩(kN-m/m):Ma = 14.72 Mb = 43.06垂直板边弯矩(kN-m/m):下右上左 -86.11 -29.45 0.00 -29.45 [配筋结果]轴压比: N/(A*fc)= 0.0000竖直方向配筋(mm^2/m):[注意: 配筋小于0表示超筋, 荷载作用面为外侧]上截面:非荷载侧= 900 荷载侧= 900(mm^2/m)中截面:非荷载侧= 900 荷载侧= 600(mm^2/m)下截面:非荷载侧= 600 荷载侧= 900(mm^2/m) 水平方向配筋(mm^2/m):[注意: 配筋小于0表示超筋]左中右荷载侧 900 900 900非荷载侧 900 900 900------------------------------------------------------------------- 计算项目: 人防临空墙 2------------------------------------------------------------------- [ 计算条件 ]墙长 = 7.65(m) 墙宽 = 2.90 (m) 墙厚 = 400 (mm)墙面均布荷载: 130.00 (kN/m^2)竖向均布荷载: 0.00 (kN/m)砼强度等级: C40纵筋级别: HRB400配筋计算as (mm):: 15 (mm)跨中弯矩调整系数: 1.00支座弯矩调整系数: 1.00支承条件:**** 下边右边上边左边固接固接简支固接[内力结果] (已乘弯矩调整系数)内力按塑性理论计算(适用于大偏心受压):跨中弯矩(kN-m/m):Ma = 0.00 Mb = 76.87垂直板边弯矩(kN-m/m):下右上左 -136.66 0.00 0.00 0.00 [配筋结果]轴压比: N/(A*fc)= 0.0000竖直方向配筋(mm^2/m):[注意: 配筋小于0表示超筋, 荷载作用面为外侧]上截面:非荷载侧= 1200 荷载侧= 1200(mm^2/m)中截面:非荷载侧= 1200 荷载侧= 800(mm^2/m)下截面:非荷载侧= 800 荷载侧= 1200(mm^2/m) 水平方向配筋(mm^2/m):[注意: 配筋小于0表示超筋]左中右荷载侧 1200 1200 1200非荷载侧 1200 1200 1200------------------------------------------------------------------- 计算项目: 人防临空墙 1------------------------------------------------------------------- [ 计算条件 ]墙长 = 7.65(m) 墙宽 = 2.90 (m) 墙厚 = 300 (mm)墙面均布荷载: 130.00 (kN/m^2)竖向均布荷载: 0.00 (kN/m)砼强度等级: C40纵筋级别: HRB400配筋计算as (mm):: 15 (mm)跨中弯矩调整系数: 1.00支座弯矩调整系数: 1.00支承条件:**** 下边右边上边左边固接固接简支固接[内力结果] (已乘弯矩调整系数)内力按塑性理论计算(适用于大偏心受压):跨中弯矩(kN-m/m):Ma = 0.00 Mb = 76.87垂直板边弯矩(kN-m/m):下右上左 -136.66 0.00 0.00 0.00 [配筋结果]轴压比: N/(A*fc)= 0.0000竖直方向配筋(mm^2/m):[注意: 配筋小于0表示超筋, 荷载作用面为外侧]上截面:非荷载侧= 900 荷载侧= 900(mm^2/m)中截面:非荷载侧= 900 荷载侧= 600(mm^2/m)下截面:非荷载侧= 600 荷载侧= 1172(mm^2/m) 水平方向配筋(mm^2/m):[注意: 配筋小于0表示超筋]左中右荷载侧 900 900 900非荷载侧 900 900 900------------------------------------------------------------------- 计算项目: 人防临空墙 1------------------------------------------------------------------- [ 计算条件 ]墙长 = 8.40(m) 墙宽 = 2.90 (m) 墙厚 = 300 (mm)墙面均布荷载: 130.00 (kN/m^2)竖向均布荷载: 0.00 (kN/m)砼强度等级: C40纵筋级别: HRB400配筋计算as (mm):: 15 (mm)跨中弯矩调整系数: 1.00支座弯矩调整系数: 1.00支承条件:**** 下边右边上边左边固接固接简支固接[内力结果] (已乘弯矩调整系数)内力按塑性理论计算(适用于大偏心受压):跨中弯矩(kN-m/m):Ma = 0.00 Mb = 76.87垂直板边弯矩(kN-m/m):下右上左-136.66 0.00 0.00 0.00 [配筋结果]轴压比: N/(A*fc)= 0.0000竖直方向配筋(mm^2/m):[注意: 配筋小于0表示超筋, 荷载作用面为外侧]上截面:非荷载侧= 900 荷载侧= 900(mm^2/m)中截面:非荷载侧= 900 荷载侧= 600(mm^2/m)下截面:非荷载侧= 600 荷载侧= 1172(mm^2/m) 水平方向配筋(mm^2/m):[注意: 配筋小于0表示超筋]左中右荷载侧 900 900 900非荷载侧 900 900 900------------------------------------------------------------------- 计算项目: 人防单元隔墙 1------------------------------------------------------------------- [ 计算条件 ]墙长 = 6.25(m) 墙宽 = 2.90 (m) 墙厚 = 300 (mm)墙面均布荷载: 50.00 (kN/m^2)竖向均布荷载: 2000.00 (kN/m)砼强度等级: C40纵筋级别: HRB400配筋计算as (mm):: 15 (mm)跨中弯矩调整系数: 1.00支座弯矩调整系数: 1.00支承条件:**** 下边右边上边左边固接固接简支固接[内力结果] (已乘弯矩调整系数)内力按塑性理论计算(适用于大偏心受压):跨中弯矩(kN-m/m):Ma = 0.00 Mb = 29.57垂直板边弯矩(kN-m/m):下右上左-52.56 0.00 0.00 0.00[配筋结果]轴压比: N/(A*fc)= 0.2909竖直方向配筋(mm^2/m):[注意: 配筋小于0表示超筋, 荷载作用面为外侧]上截面:非荷载侧= 600 荷载侧= 900(mm^2/m)中截面:非荷载侧= 900 荷载侧= 600(mm^2/m)下截面:非荷载侧= 600 荷载侧= 900(mm^2/m)水平方向配筋(mm^2/m):[注意: 配筋小于0表示超筋]左中右荷载侧 900 900 900非荷载侧 900 900 90011。

地下室人防外墙计算

地下室人防外墙计算

1.2*qd*9/128
a). =
2937 mm2 Ф20@100 As=
3142 mm2
66.74 kN.m
钢筋计算
fc= α s=M/(fc*h02 )*1000
29.6 N/mm2
0.036
b).
平时使用 状态下 裂缝宽度 验算:
γ =1/2+1/2*SQ RT(1-2*α s)=
0.982
平时状态 a). 下计算
M=1.2*qtl2/15 +1.2*qsl2/15+ 1.2*qsl2/8=
钢筋计算
fc=
16.7 N/mm2
钢筋保护层
厚度
as
ho=h-
有效高度 as-10
α
s=M/(fc*h02 )*1000
γ
=1/2+1/2*SQ
RT(1-2*α
s)=
40 mm 250 mm 0.139
钢筋计算
fc=
21.1 N/mm2
14.3x1
调整后fc= .5=
α
s=M/(fc*h02 )*1000
γ
=1/2+1/2*SQ
RT(1-2*α
s)=
31.65 N/mm2 0.164 0.910
AS=M/(γ
*fy*h0)=
实际配
筋为:








计 平时状态下
算 M=1计.2*算(qt+qs )*l2*0.0298+
室外地坪标

-0.45 m
地下水位标

-
h1
0.15 m
顶板至地下

应急中心人防计算书

应急中心人防计算书

附二综合楼挡土墙&人防墙计算书本工程防空地下室为甲类核5级防空地下室,设置一个防护单元(包括抗爆单元一、二)。

人防设在地下一层。

1、构件截面选型与荷载确定1)人防顶板厚度及顶板等效静荷载q e1根据《人民防空地下室设计规范》(GB50038-2005)4.8.2条规定,顶板覆土厚度≤0.5m,不考虑上部建筑影响的情况下,核武器地面爆炸时产生的顶板等效静荷载q e1取120KN/m2。

根据GB50038-2005 3.2.2条及4.11.3条规定,该工程人防顶板厚度不小于360mm。

人防顶板所处环境类别为一类。

2)人防外墙厚度及外墙等效静荷载q e2该工程地下二层的地下室底板板顶绝对标高60.0m根据湖南省勘察设计院于2008年5月提供的《岩土工程详细勘察报告》,人防地下室基本位于地下水位以下,因此应按饱和土计算。

根据GB50038-2005第4.6.2条规定,钢筋砼结构构件的允许延性比[β]取2.0;根据GB50038-2005第4.8.3条规定,饱和土中钢筋砼外墙等效静荷载标准值为115KN/m2。

根据GB50038-2005 4.11.3条规定,该工程人防外墙厚度不小于250mm,根据实际情况该工程人防外墙厚度取为400mm。

人防外墙所处环境类别为二a类。

3)人防底板厚度及底板等效静荷载q e3根据GB50038-2005第4.8.15条规定,q e3取50KN/m2。

参考GB50038-2005 4.11.3条规定,根据实际情况该工程人防底板厚度取为400mm。

人防底板所处环境类别为二a类。

4)不同抗暴单元间隔墙、门框墙厚度及等效静荷载q e根据GB50038-2005第4.8.9条规定,防护单元内不同抗暴单元间隔墙q e取100KN/m2,防护单元与普通地下室之间隔墙q e取180KN/m2,门框墙q e取320KN/m2。

参考GB50038-2005 4.11.3条规定,根据实际情况该人防工程防护单元与普通地下室之间隔墙、门框墙厚度取为400mm。

地下室外墙、人防外墙计算

地下室外墙、人防外墙计算

地下室侧墙计算1:单层地下室外墙(土、水在顶板下)2:单层地下室外墙-(土、水在顶板上)3:单层地下室外墙-(土在顶板上,水在下)4:单层悬臂地下室外墙5:水池侧壁 (1)6:水池侧壁 (2)悬臂模式7:双层地下室外墙(土水顶板上)8:双层地下室外墙(土在顶板上水在-1层)9:双层地下室外墙(土在顶板上水在-2层)10:双层地下室外墙(土水均在-1层)11:双层地下室外墙(土在-1层水在-2层)12:悬臂双层地下室外墙=(土水在悬臂)修改记录一:R2版第一次修改为新规范更改:计算改进及新规范修改说明1:根据新规范,计算裂缝采用准永久组合,对挡土墙地面活荷载采用了消防车的准永久组合系数0.62:根据新规范,裂缝公式修改A,构件受力特征系数2.1改为1.9;B,当外墙水平筋在外侧时,裂缝计算公式中c考虑了水平筋3:水、土与顶板关系相同情况下的人防与非人防计算表格统一为一个表格,所以表格增加可选项确定人防还是非人防墙4:表格增加可选项确定墙体水平筋与竖向筋之间关系,计算时予以考虑5:单层地下室计算模型为下部固端,上部简支的单跨梁;悬臂墙为悬臂梁模型6:表格仅考虑弹性工作状态,不考虑塑性工作状态,即不考虑弯矩调幅7:跨中内侧弯矩为各种图形荷载弯矩最大值的简单叠加,实际情况中最大弯矩并非出现在同一位置,因此本表格对跨中弯矩8:本次表格调整了计算高度的考虑,不再简化地认为实配竖向筋直径为20,相对精确地考虑实配钢筋的最大直径,即拉通筋二:2011.11.4 修改了新版边缘构件中剪力墙配箍率中fc取值问题,小于C35时将按照C35取值-高规6.4.7及7.2.15三:2011.12.10~12.24 柱、边缘构件中L形及T字形增加了外箍和内箍直径的选项,外箍分为X向和Y向,内箍取统一数值,箍四:2011.12.111:删除抗浮验算中1.05F浮单元格批注,系数1.05引自2009年版全国民用建筑工程技术措施/结构/地基与基础》中7.1.22:增加人防封堵面顶板梁及封堵面侧边柱抗扭验算3:增加底板人防封堵翻边受力计算4:对人防门框墙as的计算中fc疏漏混凝土人防调整系数修改五:2011.12.12 根据北京市建筑设计标准化办公室2008六:2012.3.6 增加悬臂双层地下室外墙七:1:2012.3.20修改边柱与角柱抗冲切计算,当满足规范要求时角柱可按边、中柱计算,边柱可按中柱计算2:增加基础承台及无梁楼盖大分项八:2012.4.2修正人防封堵梁、柱中的梁宽错误,梁宽由1000改为梁宽b九: 2012.4.18底板倒无梁楼盖考虑集水井影响十:2012.4.20增加普通灌注桩抗裂验算。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

1. 本工程地下二层为甲类防空地下室,人防等级为核6级. 一、人防临空墙计算1、室内出入口等效静荷载为q Q =200k N /㎡ 人防临空墙厚度为300㎜材料强度综合调整系数γl =1.35 混凝土采用C35受力钢筋采用HRB400临空墙短跨方向(主要受力方向)为3.00m 考虑上、下端人防顶板和基础的约束作用 取M =101ql 2 现取宽度1.0m 板带进行计算,保护层厚度为20㎜ M =10200×3.02=180 k N •m 按建筑结构常用数据:A S = 1.35h 3601018006⨯⨯⨯= 1.35270360102.5206⨯⨯⨯=1371.74㎜ 2取C18@150,A S =1696㎜2 人防临空墙配筋:水平分布筋为D14@150 垂直分布筋为D18@150 均满足承载力计算要求。

二、门框墙计算本工程门框墙处均设有暗柱,无端柱门框墙按最大悬挑长度:l 0=700㎜ 防护密闭门门框墙:270k N /㎡,取宽度1.0m 板带进行计算 M =Pl l q 21212+⨯⨯=7.05.02.12702170.0270212⨯÷⨯⨯+⨯⨯=122.85 k N •m A S = 1.35h 3600⨯⨯M = 1.352703601085.1226⨯⨯⨯=936.21㎜2门框墙暗柱箍筋水平筋取:D14@150,满足承载力计算要求。

三、人防外墙计算地下室外墙按单向板计算 取1m 宽进行计算 1、基本资料: 截面宽度b = 1000 (mm) 截面高度h = 250 (mm) 混凝土强度等级 C45 钢筋 III 级 fy= 360 N/mm2计算长度L0= 3.000 m 计算模型为一端固接,一端铰接顶板标高-3 m室外地坪标高-0.45 m地下水位标高-1.85 m底板标高-6 m顶板至室外地坪h1 2.55 m顶板至地下水距离h2 -1.15 m水位至底板h3 4.15 m填土容重γ18 KN/m3浮容重γ’8 KN/m3地面堆载q地面10 KN/m3土内摩擦角φ19.3 °主动土压力系数K0 0.502、荷载计算:a). 土对外墙的侧压力: qt=K0(γ(h1+h2)+γ’h3)=29.3855967 kN/mb). 地下水压力: qs=γ水x h3=41.5 kN/mc). 核爆炸等效静荷载: qe= 60 kN/md). 堆载侧压力qd=K0*q地面=5.0 kN/m3、弯矩及配筋计算:取最大受力点进行计算,故取固端支座B点计算a). 平时状态下计算M=1.2*qtl2/15+1.2*qsl2/15+1.2*qsl2/8=57.83 kN.m钢筋计算fc= 21.1 N/mm2钢筋保护层厚度as 40 mm有效高度ho=h-as-10 =200mmαs=M/(fc*h02)*1000=0.069γ=1/2+1/2*SQRT(1-2*αs)=0.964AS=M/(γ*fy*h0)= 833mm2实际配筋为:Ф16@150 As= 2680 mm2b). 核爆炸作用下计算fy= 486 N/mm2M=1.2*qtl2/15+1.2*qsl2/15+1.2*qsl2/8+1.0*qel2/8= 125.330533 kN.m钢筋计算fc= 21.1 N/mm2调整后fc= 14.3x1.5=31.65N/mm2αs=M/(fc*h02)*1000=0.099γ=1/2+1/2*SQRT(1-2*αs)=0.948AS=M/(γ*fy*h0)=1360 mm2实际配筋为:Ф16@150 As= 2680 mm2跨中最大弯矩近似计算平时状态下计算a). M=1.2*(qt+qs)*l2*0.0298+1.2*qd*9/128= 26.63 kN.m钢筋计算fc= 29.6 N/mm2αs=M/(fc*h02)*1000=0.022γ=1/2+1/2*SQRT(1-2*αs)=0.989AS=M/(γ*fy*h0)=374 mm2实际配筋为:Ф16@150 As= 2680 mm2核爆炸作用下计算fy= 486 N/mm2b). M=1.2*(qt+qs)l2*0.0298+1.0*qel2*9/128+1.2*qd*9/128M= 64.60357857 kN.m钢筋计算fc= 29.6 N/mm2调整后fc= 14.3x1.5= 44.4N/mm2αs=M/(fc*h02)*1000=0.036γ=1/2+1/2*SQRT(1-2*αs)=0.981AS=M/(γ*fy*h0)==677mm2实际配筋为:Ф16@150 As= 2680 mm2三、人防顶板计算LB-1矩形板计算项目名称_____________日期_____________设计者_____________校对者_____________一、构件编号: LB-1二、示意图三、依据规范《建筑结构荷载规范》 GB50009-2001《混凝土结构设计规范》 GB50010-2010四、计算信息1.几何参数计算跨度: Lx = 4500 mm; Ly = 3800 mm板厚: h = 250 mm2.材料信息混凝土等级: C40 fc=19.1N/mm2 ft=1.71N/mm2 ftk=2.39N/mm2 Ec=3.25×104N/mm2钢筋种类: HRB400 fy = 360 N/mm2 Es = 2.0×105 N/mm2最小配筋率: ρ= 0.214%纵向受拉钢筋合力点至近边距离: as = 20mm保护层厚度: c = 10mm3.荷载信息(均布荷载)永久荷载分项系数: γG = 1.200可变荷载分项系数: γQ = 1.000准永久值系数: ψq = 1.350永久荷载标准值: qgk = 12.000kN/m2可变荷载标准值: qqk = 60.000kN/m24.计算方法:弹性板5.边界条件(上端/下端/左端/右端):固定/固定/固定/固定6.设计参数结构重要性系数: γo = 1.00泊松比:μ = 0.200五、计算参数:1.计算板的跨度: Lo = 3800 mm2.计算板的有效高度: ho = h-as=250-20=230 mm六、配筋计算(lx/ly=4500/3800=1.184<2.000 所以按双向板计算):1.X向底板钢筋1) 确定X向板底弯矩Mx = 表中系数(γG*qgk+γQ*qqk)*Lo2= (0.0155+0.0249*0.200)*(1.200*12.000+1.000*60.000)*3.82 = 21.962 kN*m2) 确定计算系数αs = γo*Mx/(α1*fc*b*ho*ho)= 1.00*21.962×106/(1.00*19.1*1000*230*230)= 0.0223) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.022) = 0.0224) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.022/360= 268mm25) 验算最小配筋率ρ = As/(b*h) = 268/(1000*250) = 0.107%ρ<ρmin = 0.214% 不满足最小配筋要求所以取面积为As = ρmin*b*h = 0.214%*1000*250 = 535 mm2采取方案12@180, 实配面积628 mm22.Y向底板钢筋1) 确定Y向板底弯矩My = 表中系数(γG*qgk+γQ*qqk)*Lo2= (0.0249+0.0155*0.200)*(1.200*12.000+1.000*60.000)*3.82 = 30.050 kN*m2) 确定计算系数αs = γo*My/(α1*fc*b*ho*ho)= 1.00*30.050×106/(1.00*19.1*1000*230*230)= 0.0303) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.030) = 0.0304) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.030/360 = 368mm25) 验算最小配筋率ρ = As/(b*h) = 368/(1000*250) = 0.147%ρ<ρmin = 0.214% 不满足最小配筋要求所以取面积为As = ρmin*b*h = 0.214%*1000*250 = 535 mm2采取方案12@180, 实配面积628 mm23.X向支座左边钢筋1) 确定左边支座弯矩M o x = 表中系数(γG*qgk+γQ*qqk)*Lo2= 0.0552*(1.200*12.000+1.000*60.000)*3.82= 59.291 kN*m2) 确定计算系数αs = γo*M o x/(α1*fc*b*ho*ho)= 1.00*59.291×106/(1.00*19.1*1000*230*230)= 0.0593) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.059) = 0.0614) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.061/360 = 738mm25) 验算最小配筋率ρ = As/(b*h) = 738/(1000*250) = 0.295%ρ≥ρmin = 0.214% 满足最小配筋要求采取方案12@180, 实配面积628 mm24.X向支座右边钢筋1) 确定右边支座弯矩M o x = 表中系数(γG*qgk+γQ*qqk)*Lo2= 0.0552*(1.200*12.000+1.000*60.000)*3.82= 59.291 kN*m2) 确定计算系数αs = γo*M o x/(α1*fc*b*ho*ho)= 1.00*59.291×106/(1.00*19.1*1000*230*230)= 0.0593) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.059) = 0.0614) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.061/360 = 738mm25) 验算最小配筋率ρ = As/(b*h) = 738/(1000*250) = 0.295%ρ≥ρmin = 0.214% 满足最小配筋要求采取方案12@180, 实配面积628 mm25.Y向上边支座钢筋1) 确定上边支座弯矩M o y = 表中系数(γG*qgk+γQ*qqk)*Lo2= 0.0630*(1.200*12.000+1.000*60.000)*3.82= 67.707 kN*m2) 确定计算系数αs = γo*M o y/(α1*fc*b*ho*ho)= 1.00*67.707×106/(1.00*19.1*1000*230*230)= 0.0673) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.067) = 0.0694) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.069/360 = 847mm25) 验算最小配筋率ρ = As/(b*h) = 847/(1000*250) = 0.339%ρ≥ρmin = 0.214% 满足最小配筋要求采取方案12@180, 实配面积628 mm26.Y向下边支座钢筋1) 确定下边支座弯矩M o y = 表中系数(γG*qgk+γQ*qqk)*Lo2= 0.0630*(1.200*12.000+1.000*60.000)*3.82= 67.707 kN*m2) 确定计算系数αs = γo*M o y/(α1*fc*b*ho*ho)= 1.00*67.707×106/(1.00*19.1*1000*230*230)= 0.0673) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.067) = 0.0694) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.069/360 = 847mm25) 验算最小配筋率ρ = As/(b*h) = 847/(1000*250) = 0.339%ρ≥ρmin = 0.214% 满足最小配筋要求采取方案12@180, 实配面积628 mm2三、人防底板计算LB-1矩形板计算项目名称_____________日期_____________设计者_____________校对者_____________一、构件编号: LB-1二、示意图三、依据规范《建筑结构荷载规范》 GB50009-2001《混凝土结构设计规范》 GB50010-2010四、计算信息1.几何参数计算跨度: Lx = 4500 mm; Ly = 3800 mm板厚: h = 250 mm2.材料信息混凝土等级: C40 fc=19.1N/mm2 ft=1.71N/mm2 ftk=2.39N/mm2 Ec=3.25×104N/mm2钢筋种类: HRB400 fy = 360 N/mm2 Es = 2.0×105 N/mm2最小配筋率: ρ= 0.214%纵向受拉钢筋合力点至近边距离: as = 20mm保护层厚度: c = 10mm3.荷载信息(均布荷载)永久荷载分项系数: γG = 1.200可变荷载分项系数: γQ = 1.000准永久值系数: ψq = 1.350永久荷载标准值: qgk = 12.000kN/m2可变荷载标准值: qqk = 45.000kN/m24.计算方法:弹性板5.边界条件(上端/下端/左端/右端):固定/固定/固定/固定6.设计参数结构重要性系数: γo = 1.00泊松比:μ = 0.200五、计算参数:1.计算板的跨度: Lo = 3800 mm2.计算板的有效高度: ho = h-as=250-20=230 mm六、配筋计算(lx/ly=4500/3800=1.184<2.000 所以按双向板计算):1.X向底板钢筋1) 确定X向板底弯矩Mx = 表中系数(γG*qgk+γQ*qqk)*Lo2= (0.0155+0.0249*0.200)*(1.200*12.000+1.000*45.000)*3.82 = 17.534 kN*m2) 确定计算系数αs = γo*Mx/(α1*fc*b*ho*ho)= 1.00*17.534×106/(1.00*19.1*1000*230*230)= 0.0173) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.017) = 0.0184) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.018/360= 214mm25) 验算最小配筋率ρ = As/(b*h) = 214/(1000*250) = 0.085%ρ<ρmin = 0.214% 不满足最小配筋要求所以取面积为As = ρmin*b*h = 0.214%*1000*250 = 535 mm2采取方案10@140, 实配面积560 mm22.Y向底板钢筋1) 确定Y向板底弯矩My = 表中系数(γG*qgk+γQ*qqk)*Lo2= (0.0249+0.0155*0.200)*(1.200*12.000+1.000*45.000)*3.82 = 23.992 kN*m2) 确定计算系数αs = γo*My/(α1*fc*b*ho*ho)= 1.00*23.992×106/(1.00*19.1*1000*230*230)= 0.0243) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.024) = 0.0244) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.024/360= 293mm25) 验算最小配筋率ρ = As/(b*h) = 293/(1000*250) = 0.117%ρ<ρmin = 0.214% 不满足最小配筋要求所以取面积为As = ρmin*b*h = 0.214%*1000*250 = 535 mm2采取方案10@140, 实配面积560 mm23.X向支座左边钢筋1) 确定左边支座弯矩M o x = 表中系数(γG*qgk+γQ*qqk)*Lo2= 0.0552*(1.200*12.000+1.000*45.000)*3.82= 47.337 kN*m2) 确定计算系数αs = γo*M o x/(α1*fc*b*ho*ho)= 1.00*47.337×106/(1.00*19.1*1000*230*230)= 0.0473) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.047) = 0.0484) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.048/360 = 586mm25) 验算最小配筋率ρ = As/(b*h) = 586/(1000*250) = 0.234%ρ≥ρmin = 0.214% 满足最小配筋要求采取方案10@130, 实配面积603 mm24.X向支座右边钢筋1) 确定右边支座弯矩M o x = 表中系数(γG*qgk+γQ*qqk)*Lo2= 0.0552*(1.200*12.000+1.000*45.000)*3.82= 47.337 kN*m2) 确定计算系数αs = γo*M o x/(α1*fc*b*ho*ho)= 1.00*47.337×106/(1.00*19.1*1000*230*230)= 0.0473) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.047) = 0.0484) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.048/360 = 586mm25) 验算最小配筋率ρ = As/(b*h) = 586/(1000*250) = 0.234%ρ≥ρmin = 0.214% 满足最小配筋要求采取方案10@130, 实配面积603 mm25.Y向上边支座钢筋1) 确定上边支座弯矩M o y = 表中系数(γG*qgk+γQ*qqk)*Lo2= 0.0630*(1.200*12.000+1.000*45.000)*3.82= 54.056 kN*m2) 确定计算系数αs = γo*M o y/(α1*fc*b*ho*ho)= 1.00*54.056×106/(1.00*19.1*1000*230*230)= 0.0543) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.054) = 0.0554) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.055/360 = 671mm25) 验算最小配筋率ρ = As/(b*h) = 671/(1000*250) = 0.269%ρ≥ρmin = 0.214% 满足最小配筋要求采取方案12@160, 实配面积706 mm26.Y向下边支座钢筋1) 确定下边支座弯矩M o y = 表中系数(γG*qgk+γQ*qqk)*Lo2= 0.0630*(1.200*12.000+1.000*45.000)*3.82= 54.056 kN*m2) 确定计算系数αs = γo*M o y/(α1*fc*b*ho*ho)= 1.00*54.056×106/(1.00*19.1*1000*230*230) = 0.0543) 计算相对受压区高度ξ = 1-sqrt(1-2*αs) = 1-sqrt(1-2*0.054) = 0.0554) 计算受拉钢筋面积As = α1*fc*b*ho*ξ/fy = 1.000*19.1*1000*230*0.055/360 = 671mm25) 验算最小配筋率ρ = As/(b*h) = 671/(1000*250) = 0.269%ρ≥ρmi n = 0.214% 满足最小配筋要求采取方案12@160, 实配面积706 mm2。