某机械厂10kv降压变电所的电气设计毕业设计
某厂10kV降压变电所电气设计 精品
目录设计任务说明书·························4页一、负荷计算和无功功率计算及补偿················5页1.1 机械厂负荷统计资料····················5页1.2负荷计算和无功功率计算·················5页1.3无功功率补偿·······················7页1.4年耗电量的估算·····················8页二、变电所位置和形式的选择···················9页三、变电所主变压器台数和容量及主接线方案的选择·········9页3.1变电所主变压器台数的选择················9页 3.2变电所主变压器容量选择·················9页3.3变电所主接线方案的选择················ 10页四、短路电流的计算······················ 11页4.1确定基准值························· 11页4.2计算短路电路中各主要元件的电抗标么值:··········· 11页4.3计算k-1点的短路电路总电抗标么值及三相短路电流和短路容量·· 12页4.4计算k-2点短路电路总电抗标么值及三相短路电流和短路容量·· 12页五、变电所一次设备的选择与校验················ 13页5.1变电所高压一次设备的选择·················· 13页5.2变电所高压一次设备的校验················· 13页5.3变电所低压一次设备的选择················· 15页5.4变电所低压一次设备的校验················· 15页六、变电所高、低压线路的选择················· 16页6.1高压线路导线的选择···················· 17页6.2低压线路导线的选择···················· 17页七、变电所二次回路方案选择及继电保护的整定·········· 18页7.1二次回路方案选择····················· 18页7.2继电保护的整定······················ 19页八、心得和体会························ 22页附录参考文献························· 23页附图····························· 23页设计任务说明书一.设计题目某厂10kV降压变电所电气设计二.设计要求1.工厂的负荷计算及无功补偿(要求列表)。
某机械厂降压变电所电气设计
某机械厂降压变电所电气设计一、设计要求:1.变电所的功率6000KVA,负荷主要为机械厂的设备;2.变电所的主要电气设备包括主变压器、低压开关柜、配电室等;3.变电所应具备稳定可靠的供电能力,满足机械厂的用电需求;4.设计应符合相关电气安全规范和标准。
二、设计方案:1.主变压器:根据题设条件,主变压器的额定功率为6000KVA。
选用三相油浸式变压器,额定电压为10kV/0.4kV。
变压器的绕组应选用C级绝缘材料,以保证变压器的可靠性和耐久性。
变压器还应配备绝缘油温控制装置、油温表、避雷器等保护设备,以确保变压器的安全运行。
2.低压开关柜:低压开关柜是变电所的重要组成部分,主要用于供电和配电控制。
选用三相交流380V低压开关柜,额定电流根据机械厂的负荷需求确定。
低压开关柜的主要配电设备包括断路器、接触器、过载保护器等。
开关柜还应配备漏电保护器、短路保护装置等安全设备,以确保供电过程中的安全性。
3.配电室:配电室是变电所的重要组成部分,主要用于对电力进行配电控制。
配电室的主要设备包括配电柜、电流互感器、电能仪表等。
配电室的电缆布线应合理,防火性能要符合相关标准要求,以确保供电过程中的安全性。
配电室还应配备消防器材,以确保供电过程中的安全性。
4.接地系统:接地系统是变电所电气设计的重要组成部分,用于确保供电过程中的安全性。
设计中应设置地网以确保设备和人员的安全。
地网的设计应根据地质条件和相关规范确定,地网的接地电阻要符合相关标准要求。
地网还应与设备的金属外壳、框架等导电部分连接,以确保设备的安全运行。
5.照明系统:变电所的照明系统是为了提供工作环境的照明,确保工作人员的安全。
设计中应选用高效节能的照明设备,并合理设置灯具位置,保证照明光线的均匀性和良好的照明效果。
照明系统还应具备防爆、防水等安全特性,以确保供电过程中的安全性。
三、安全措施:为确保供电过程中的安全,设计中应采取以下安全措施:1.设备选择应符合相关国家标准和规范;2.电气设备布局合理,各设备之间保持安全距离;3.设备的维护保养应定期进行,确保设备的正常运行;4.设置明显的安全警示标志,提醒人员注意安全;5.加强人员的电气安全培训,提高人员的安全意识。
某10KV机械厂降压变电所的电气设计
工厂供电课程设计报告题目:某机械厂降压变电所的电气设计姓名:学号:班级:导师:时间:某机械厂降压变电所的电气设计前言在工厂里,电能虽然是工业生产的主要能和动力,但是它在产品成本中所占的比重很小(除电化工业外)。
电能在工业生产中的重要性,并不在于它在产品成本中或投资总额所占的比重多少,而在于工业生产实现电气以后可以大大增加产量,提高产品质量,提劳动生产率,降低生产成本,减轻工人的劳动强度,改善工人的劳动条件,有利于实现生过程自动化。
从另一方面来说,如果工厂的能供应突然中断,则对工业生产可能造成严的后果。
因此,做好工厂供电工作对于发展工业生,实现工业现代化,具有十分重要的意义。
能源节约是工厂供电工作的一个重要方面,能源节约对于国家经济建设具有十分重要战略意义,因此做好工厂供电工作,对于节约能源、支援国家经济建设,也具有重大的作用。
课程设计是检验我们这学期学习情况的一项综合测试,它要求我们把所学的知识全部适用,融会贯通的一项训练,是对我们能力的一项综合评定,它要求我们充分发掘自身的潜力,开拓思路设计出合理适用的供配电系统。
众所周知,电能是现代工业生产的主要能源。
电能即易于由其他形式的能量转换而来,又易于转换为其他形式的能量以供应用。
电能的输送和分配既简单经济,又便于控制、调节、测量。
有利于实现生产过程自动化。
而工厂供电就是指工厂所需要电能的供应和分配。
工厂供电设计要达到为工业生产服务,保障工厂生产和生活用电的需要,并做好节能工作,就必须做到:安全、可靠、优质、经济。
同时课程设计也是教学过程中的一个重要环节,通过设计可以巩固各课程理论知识,了解工厂供电设计的基本方法,了解工厂供电电能分配等各种实际问题,培养独立分析和解决实际工程技术问题的能力,同时对电力工业的有关政策、方针、技术规程有一定的了解,在计算绘图、编号、设计说明书等方面得到训练,为以后工作奠定基础。
目录第一章设计任务书 (1)1.1 设计题目 (1)1.2 设计要求 (1)1.3 设计依据 (1)1.3.1 工厂总平面图 (1)1.3.2 工厂负荷情况 (1)1.3.3 供电电源情况 (2)1.3.4 气象资料 (3)1.3.5 地质水文资料 (3)1.3.6 电费制度 (3)第二章负荷计算和无功功率补偿 (4)2.1负荷计算 (4)2.1.1单组用电设备计算负荷的计算公式 (4)2.1.2多组用电设备计算负荷的计算公式 (4)2.2无功功率补偿 (6)2.2.1有关功率的名词解释 (6)2.2.2提高功率因数的意义 (7)2.2.3提高功率因数方法 (7)2.2.4电容器的选择、补偿方式和联接方式 (8)2.2.4无功补偿的计算 (11)第三章变电所位置和型式选择 (13)3.1变配电所所址选择的一般原则 (13)3.2型式与布置 (14)3.3负荷中心的确定方法 (14)3.2.1负荷指示图 (14)3.2.2负荷电能矩 (14)3.2.3负荷功率矩 (14)第四章变电所主变压器台数和容量、类型的选择 (17)4.1台数 (17)4.2容量 (17)4.3台数、容量、类型的选择 (17)第五章变电所主接线方案的设计 (18)5.1装设一台主变压器的主接线方案: (18)5.2装设两台主变压器的主接线方案 (19)5.3主接线方案的技术经济比较 (20)第六章短路电流的计算 (21)6.1绘制计算电路 (21)6.2确定短路计算基准值 (21)6.3计算短路电路中个元件的电抗标幺值 (21)6.4 k-1点(10.5kV侧)的相关计算 (22)6.5 k-2点(0.4kV侧)的相关计算 (22)第七章变电所一次设备的选择和校验 (23)7.1 10kV侧一次设备的选择校验 (24)7.1.1按工作电压选择 (24)7.1.2 隔离开关、负荷开关和断路器的短路稳定度校验 (25)7.2 380V侧一次设备的选择校验 (26)7.3 高低压母线的选择 (27)第八章变电所进出线的选择和校验 (28)8.1 10kV高压进线和引入电缆的选择 (28)8.1.1 10kV高压进线的选择校验 (28)8.1.2 高压配电室至主变的一段引入电缆的选择校验 (28)8.2 380低压出线的选择 (29)8.2.1铸造车间 (29)8.2.2锻压车间 (30)8.2.3金工车间 (30)8.2.4 热处理车间 (31)8.2.5 电镀车间 (32)8.2.6 仓库 (32)8.2.7装配车间 (33)8.2.8机修车间 (33)8.2.9锅炉房 (34)8.2.10工具车间 (35)8.2.11 生活区 (35)8.3 作为备用电源的高压联络线的选择校验 (36)8.3.1按发热条件选择 (36)8.3.2校验电压损耗 (36)8.3.3短路热稳定校验 (37)第九章变电所二次回路方案的选择及继电保护的整定 (38)9.1变电所二次回路方案的选择 (38)9.2 变电所的保护装置 (38)9.2.1主变压器的继电保护装置 (38)9.2.2装设电流速断保护 (39)9.3作为备用电源的高压联络线的继电保护装置 (40)9.4变电所低压侧的保护装置 (40)第十章防雷保护与接地装置的设计 (41)10.1变电所的防雷保护 (41)10.1.1 直接防雷保护 (41)10.1.2 雷电侵入波的防护 (41)10.2变电所公共接地装置的设计 (41)10.2.1接地电阻的要求 (41)10.2.2接地装置的设计 (42)参考文献 (43)附录 (44)第一章设计任务书1.1 设计题目某机械厂降压变电所的电气设计1.2 设计要求要求根据本厂所能取得的电源及本厂用电负荷的实际情况,并适当考虑到工厂生产的发展,按照安全可靠、技术先进、经济合理的要求,确定变电所的位置与型式,确定变电所主变压器的台数与容量、类型,选择变电所主接线方案及高低压设备和进出线,确定二次回路方案,选择整定继电保护装置,确定防雷和接地装置,最后按要求写出设计说明书,绘出设计图纸。
某机械厂10KV降压变电所电气设计
毕业设计(论文)说明书题目某机械厂10KV降压变电所电气设计助学单位:专业:班级:准考证号:设计人:指导教师:毕业设计(论文)任务书注:此表与该生毕业设计(论文)一路装订。
某机械厂10KV降压变电所电气设计摘要按照我国能源利用情形,供电设计的原则要求,依照设计任务书的详细要求,对该厂进行整体分析,然后着手对该机械厂高压供配电系统进行设计。
在指导老师的悉心指导下、在同组成员尽心帮忙下,同时借助参考文献,完成该次设计。
第一,对全厂的负荷进行系统计算,为肯定供电系统的电力变压器、各类开关电器的容量、电力线路的截面和变电所的所址等提供依据。
而且对其进行无功补偿,以减少变压器、电力线路、开关设备的功率损耗,从而减少电器元件的规格,降低它的功率损耗和电压损耗,减少投资。
第二,按照本厂的实际情形和经济技术比较电力变压器,肯定变电所的地址、类型和其主接线方案,其中包括变压器容量和台数的肯定,全厂配电系统的设计。
然后,按负荷情形系统地对厂区进行设计,为了校验一次设备的短路稳固度,开关电器的断流能力及电流保护装置的灵敏度,整定电流速断保护装置的动作电流,进行短路电流的计算,进而选择了电力线路和高低压电气设备。
最后,肯定全厂配电系统的防雷接地系统设计。
关键词:电力变压器、无功补偿、负荷计算、电缆敷设、接地与防雷。
AbstractAccording to China's energy utilization, power supply in accordance with the principle of design, the design plan descriptions of the factory, the detailed requirements for overall analysis of the factory, and then set high power supply system design. In the guidance, take in your group members, and help with many references to finish the design.First of all, the load calculation system, to determine the power supply system of switch power transformer, electric capacity, power lines and the substation of address, etc. And on the reactive power compensation, to reduce the transformer, electric circuit, the power switch equipment, thereby reducing the loss of electrical components, reduce its specification and voltage loss of power consumption, reducing investment.Secondly, according to the actual situation of our economy and technology power transformer substation, and determine the address, types and its main connection scheme, including transformer capacity and the number of plant distribution system, the design.Then, according to the situation of factory with systematic design, in order to check the equipment, switch short-circuit stability of electric current flow capacity and the sensitivity of protection device, the velocity of electric current protection device, the calculation of short-circuit current, and then choose the power line and high-low voltage electrical equipment.Finally, make sure all distribution system of lightning proof grounding system design.Keywords:Power transformer, reactive power compensation, load calculation, and lightning protection and grounding cables.目录摘要 (I)ABSTRACT (II)第1章绪言 (1)原始资料 (2)设计内容及要求 (4)设计任务 (4)第2章负荷计算及无功功率补偿计算 (5)负荷计算 (5)无功功率补偿计算 (10)第3章变电所主接线及变压器的选择 (12)变电所位置和形式选择 (12)主接线选择 (12)变电所主变压器台数和容量 (14)第4章短路电流的计算 (15)第5章变电所一次设备的选择和与校验 (17)变电所高压一次设备的选择 (17)变电所高压一次设备的校验 (17)第6章变电所高低压电路设计 (21)高压线路导线的选择 (21)低压线路导线的选择 (22)第7章变电所二次回路设计及继电保护的整定 (25)二次回路方案选择 (25)继电保护的大体要求 (25)继电保护的整定 (26)第8章防雷和接地装置的肯定 (30)总结 (31)参考文献 (32)附录 (33)谢辞 (36)第1章绪言电能是现代人们生产和生活的重要能源。
某机械厂降压变电所电气设计
某机械厂降压变电所电气设计1. 引言本文档是关于某机械厂降压变电所电气设计的详细说明。
降压变电所是机械厂电力系统的重要组成部分,负责将高压电流转换为适用于机械设备使用的低压电流。
本文档将介绍降压变电所的电气设计要求、设计流程、主要设备及其选型等内容。
2. 设计要求2.1 电源接入方式降压变电所的电源接入方式一般分为两种:直接接入变电站和通过配电变压器接入变电站。
根据某机械厂的实际情况,选择适合的电源接入方式,确保供电的可靠性和稳定性。
2.2 降压变电设备容量根据某机械厂的用电负荷需求,确定降压变电所的设备容量。
考虑到未来的扩展需求,建议留有一定的余量,以便后续增加负荷时不需更换或增加设备。
2.3 电气设备安装布局根据厂区的实际布局和安全要求,确定降压变电所的电气设备的安装布局。
保证设备之间的合理距离,便于运行和维护。
3. 设计流程3.1 方案设计根据电源接入方式和设备容量要求,设计降压变电所的初步方案。
考虑到降压变电所的安全性和可靠性,建议采用双路供电方案,以确保在一路电源故障时仍能正常供电。
3.2 设备选型根据初步方案确定的设备容量,选择合适的降压变电设备。
要考虑设备的质量和性能,确保其稳定运行和长寿命。
3.3 系统设计根据设备选型结果,进行降压变电所的系统设计。
设计系统的电缆和配电线路,确保其满足负荷需求,并且具备合适的安全保护机制。
3.4 施工图纸根据系统设计结果,绘制降压变电所的施工图纸。
图纸应包括设备布局、电缆线路、接地系统等详细信息,以便施工人员进行准确的安装和调试。
4. 主要设备及其选型4.1 变压器降压变电所的核心设备为变压器,用于将高压电流降压为适用于机械设备使用的低压电流。
变压器的选型应考虑负载容量、绝缘等级、效率等因素。
4.2 开关柜开关柜用于控制和保护降压变电所的电路。
根据需求选择合适的开关柜,应考虑其负载容量、保护功能、操作方式等因素。
4.3 电缆和配电线路电缆和配电线路是降压变电所的输电通道,负责将电能传输到各个用电设备。
电气工程及其自动化专业毕业论文某机械厂降压变电所电气设计
电气工程及其自动化专业毕业论文某机械厂降压变电所电气设计一、绪论随着工业技术的不断进步与发展,电气工程及其自动化专业在各个领域的应用越来越广泛。
特别是在机械制造业中,电气系统的设计与优化对于提高生产效率、保障设备安全运行具有重要意义。
降压变电所作为机械厂电气系统的重要组成部分,其电气设计的质量直接关系到整个机械厂的运行效率和安全性。
本研究旨在深入探讨某机械厂降压变电所的电气设计,为相关领域提供有益的参考与借鉴。
本研究背景基于当前机械厂电气设备升级与改造的需求,通过对某机械厂降压变电所电气设计的探讨,为机械厂提供科学、合理、高效的电气设计方案。
研究的意义在于,不仅能够提高机械厂电气系统的运行效率,而且有助于保障设备的安全运行,减少因电气故障导致的生产事故。
本研究还可为类似机械厂的电气设计提供借鉴,推动电气工程及其自动化专业的发展。
在文献综述方面,本研究通过对前人关于降压变电所电气设计的研究进行梳理与分析,发现目前研究主要集中在电气主接线设计、电气设备选择、防雷保护措施等方面。
针对特定机械厂降压变电所的电气设计研究相对较少。
本研究旨在填补这一空白,为某机械厂降压变电所的电气设计提供具体的解决方案。
本研究将详细介绍某机械厂降压变电所的电气设计过程,包括设计原则、设计方案、关键技术等。
通过实证分析,验证设计的可行性与有效性。
研究方法主要包括文献调研、现场勘查、设计实践等。
研究的预期成果将为某机械厂降压变电所的电气设计提供科学依据,为类似项目的电气设计提供借鉴。
本研究旨在深入探讨某机械厂降压变电所的电气设计,为提高机械厂运行效率和保障设备安全运行提供科学依据。
研究的开展具有重要的理论意义与实际应用价值。
1. 背景介绍:简要阐述电气工程的重要性和在某机械厂的应用场景。
电气工程作为现代工业发展的重要支柱,在现代社会科技进步和工业升级的大背景下具有举足轻重的地位。
其重要性不仅体现在为社会经济发展提供持续稳定的电力供应上,更表现在优化能源结构、提升能源利用效率、推动技术创新等多个方面。
工厂供电某工厂10kV降压变电所系统设计课程设计
沈阳工程学院课程设计任务书课程设计题目:某工厂10kV降压变电所系统设计系别班级学生姓名学号指导教师职称课程设计进行地点:任务下达时间:年月日起止日期:年月日起——至年月日止教研室主任年月日批准1、基础资料该工厂0.4KV计算负荷S30=980KV A,COSφ=0.7。
10KV线路5km,上一级电网短路容量500MV A,基准容量100MV A。
工厂全部为Ⅲ级负荷,该工厂有5个车间,其中1 个车间计算负荷P30=80,COSφ=0.7。
距离工厂变电所200m,采用铝芯塑料电力电缆供电,线芯温度按60℃考虑。
2、设计要求2.1 变电所主接线设计(0.4KV侧从简)。
2.2 选择变压器容量。
2.3 短路电流计算。
计算10KV侧变压器一次短路和变压器低压(0.4KV)侧短路电流。
2.4 按主接线方案选择设备,包括隔离开关,高压断路器,高压电流互感器,低压断路器(变压器低压侧出口)。
2.5 变压器继电保护及整定计算。
2.6 从变电所到1车间的供电电缆选择(按发热条件选择),电压降计算。
2.7 无功补偿。
要求采用低压侧补偿,补偿后10KV侧功率因数大于0.9.3 对设计说明书撰写内容、字数的要求;3.1 设计题目、目录、原始数据及技术要求等。
3.2 设计目的、有必要的计算及表格。
字数不少于3000字。
3.3 设计图纸3.3.1 变电所主接线单线图3.3.2 变压继电保护原理图3.4 设计总结。
3.5 参考文献。
4 时间进度安排;5、主要参考资料(文献)。
(1)《工厂供电》刘介才机械工业出版社2009.12(2)《电力工程设计手册》(第一、二、三、四册)西北、东北电力设计院编上海科学技术出版社1.1(3)《电力系统计电保护原理与新技术》李佑光林东华科学出版社2005.71、基础资料该工厂0.4KV计算负荷S30=980KV A,COSφ=0.7。
10KV线路5km,上一级电网短路容量500MV A,基准容量100MV A。
毕业设计--10KV变电所电气部分初步设计
毕业设计说明书题目:10KV变电所电气部分初步设计专业:发电厂及电力系统班级:电力904班学号:姓名:指导老师:2011年11月18日前言毕业设计是高等工程教育最重要的实践性教学环节,它是由我们独立完成的一项综合性、创造性、设计性的大型作业。
开展毕业设计课题至关重要并具有深远的意义,不仅培养我们分析和解决各种实际问题的能力,也进一步巩固、深化和扩展所学的理论知识。
我们这次设计的主要内容是对某110kV降压变电站的电气部分进行初步设计,包括了:负荷统计分析、主变的选择、电气主接线方案选择、短路电流的计算、电气设备的选择和校验、防雷设施以及继电保护的选择等内容。
经过五个星期的努力,我终于完成了这次毕业设计。
在此过程中,我从对变电站的生疏,到了解,再到深入研究,我有了不少的收获:巩固了以前学的专业知识,并在以前的基础上理解的更加透彻,掌握的更加熟练;锻炼了自己的实际应用能力,将课本上学到的理论知识和实际生产联系了起来;增强了自己独立解决问题的能力以及团队合作精神,培养实事求是、全面科学、严肃认真的工作作风,为今后从事本专业工作打下坚实牢固的基础。
但由于时间和水平的局限,设计中难免会有不妥之处,敬请老师多批评指导。
2011年11月18日目录前言第1章原始材料 (6)1.1变电站基本资料................................................................ 错误!未定义书签。
1.2变电站负荷情况................................................................ 错误!未定义书签。
2.1负荷的概述 (1)2.1.1负荷分类..................................................................... 错误!未定义书签。
第2章主变压器的选择 (8)2.1概述 (8)2.2主变压器台数的原则及选择 (8)2.3主变压器容量的选择 (8)2.3主变压器形式的选择 (9)第3章电气主接线选择 (11)3.1概述 (11)3.2电气主接线的基本要求 (11)3.3变电站主接线基本接线方式 (11)3.4变电站主接线选择 (13)3.4.1 110kV侧主接线选择方案 (13)3.4.2 35kV侧主接线方案选择 (14)3.4.3 10kV侧主接线方案选择 (15)3.4.4 变电站主接线图 (15)3.4.5 变电站的站用电......................................................... 错误!未定义书签。
10kV降压变电所电气设计
哈尔滨某机械厂降压变电所电气设计目录一、负荷计算和无功功率计算及补偿 (2)二、变电所主变压器台数和容量选择 (6)三、变电所位置和形式的选择 (8)四、短路电流的计算 (8)五、变电所高、低压线路的选择 (9)六、变电所一次设备的选择与校验 (11)七、变电所二次回路方案选择及继电保护的整定 (14)八、防雷和接地装置的确定 (18)九、附录参考文献 (18)一负荷计算和无功功率计算及补偿哈尔滨某机械厂负荷统计资料厂房编号用电单位名称负荷性质设备容量/kw需要系数tanϕ功率因数cosϕ1 仓库动力88 0.25 1.17 0.65照明 2 0.80 1.0 2 铸造车间动力338 0.35 1.02 0.70照明10 0.80 1.0 3 锻压车间动力338 0.25 1.17 0.65照明10 0.80 1.0 4 金工车间动力338 0.25 1.33 0.60照明10 0.80 1.0 5 工具车间动力338 0.25 1.17 0.65照明10 0.80 1.0 6 电镀车间动力338 0.50 0.88 0.75照明10 0.80 1.07 热处理车间动力138 0.50 1.33 0.60 照明10 0.80 1.08 装配车间动力138 0.35 1.02 0.70照明10 0.80 1.0 9 机修车间动力138 0.25 1.17 0.65(一)负荷计算和无功功率计算在负荷计算时,采用需要系数法对各个车间进行计算,并将照明和动力部分分开计算,照明部分最后和宿舍区照明一起计算。
具体步骤如下。
1. 仓库:动力部分 ,30(11)880.2522P kW kW =⨯=;30(11)22 1.1725.74var Q kW k =⨯=30(11)33.86S k VA ==; 30(11)33.8651.451.7320.38k VAI A kV==⨯照明部分,30(12)20.81.6P kW kW =⨯=;30(11)0Q = 2. 铸造车间:动力部分,30(21)3380.35118.3P kW kW =⨯=;30(21)118.3 1.02120.666var Q kW k =⨯=30(21)168.98S k VA ==30(21)168.98256.751.7320.38k VAI A kV==⨯照明部分,30(22)100.88P kW kW =⨯=;30(22)0Q = 3. 锻压车间:动力部分,30(31)3380.2584.5P kW kW =⨯=;30(31)84.5 1.1798.865var Q kW k =⨯=30(31)130.06S k VA == 30(31)130.06197.611.7320.38k VAI A kV==⨯照明部分,30(32)100.88P kW kW =⨯=;30(32)0Q = 4. 金工车间:动力部分,30(41)3380.2584.5P kW kW =⨯=;30(41)84.5 1.33112.385var Q kW k =⨯=30(41)140.61S k VA ==30(41)140.61213.641.7320.38k VAI A kV==⨯照明部分,30(42)100.88P kW kW =⨯=;30(42)0Q =30(51)3380.2584.5P kW kW =⨯=;30(51)84.5 1.1798.865var Q kW k =⨯=30(51)130.06S k VA == 30(51)130.06197.611.7320.38k VAI A kV==⨯照明部分,30(52)100.88P kW kW =⨯=;30(52)0Q = 6. 电镀车间:动力部分,30(61)3380.5169P kW kW =⨯=;30(61)1690.88148.72var Q kW k =⨯=30(61)225.12S k VA == 30(61)225.12342.041.7320.38k VAI A kV==⨯照明部分,30(62)100.88P kW kW =⨯=;30(62)0Q = 7. 热处理车间:动力部分,30(71)1380.569P kW kW =⨯=;30(71)69 1.3391.77var Q kW k =⨯=30(71)114.82S k VA == 30(71)114.82174.461.7320.38k VAI A kV==⨯照明部分,30(72)100.88P kW kW =⨯=;30(72)0Q = 8. 装配车间:动力部分,30(81)1380.3548.3P kW kW =⨯=;30(81)48.3 1.0249.266var Q kW k =⨯=30(81)68.99S k VA == 30(81)68.99104.821.7320.38k VAI A kV==⨯照明部分,30(82)100.88P kW kW =⨯=;30(82)0Q = 9. 机修车间:动力部分,30(91)1380.2534.5P kW kW =⨯=;30(91)34.5 1.1740.365var Q kW k =⨯=30(91)53.10S k VA == 30(91)53.1080.681.7320.38k VAI A kV==⨯照明部分,30(92)50.84P kW kW =⨯=;30(92)0Q =30(101)1380.569P kW kW =⨯=;30(101)69 1.1780.73var Q kW k =⨯=30(101)106.2S k VA == 30(101)106.2161.361.7320.38k VAI A kV==⨯照明部分,30(102)20.8 1.6P kW kW =⨯=;30(102)0Q = 11.宿舍区照明,30(11)4000.7280P kW kW =⨯=。
某10KV机械厂降压变电所设计
湖南工程学院课程设计任务书课程名称:供电工程题目:某机械厂10/0.4kV降压变电所设计专业班级:电气工程及其自动化学生姓名: ** 学号: %%%%%%%%%%%% 指导老师: ###任务书下达日期:2012年2月27日设计完成日期:2012年6月 1日设计内容与设计要求一、设计内容(一)原始数据1、工厂总平面图2、工厂负荷情况负荷统计资料见表,本厂多数车间为两班制,年最大负荷利用小时4600h,日最大负荷持续时间为6h,该厂除铸造车间、电镀车间和锅炉房属二级负荷外,其余属三级负荷。
厂房编号厂房名称负荷类别设备容量/KW需要系数功率因数1 铸造车间动力360 0.3 0.70 照明 6 0.8 1.02 锻压车间动力350 0.3 0.65 照明8 0.7 1.03 金工车间动力400 0.3 0.05 照明10 0.8 0.84 工具车间动力300 0.3 1.0 照明7 0.9 0.55 锅炉房动力50 0.7 0.8 照明 1 0.8 1.06 热处理车间动力150 0.3 0.5照明 5 0.8 1.07 装配车间动力160 0.3 0.7 照明 6 0.8 1.0目录第1章负荷计算和无功功率补偿 (6)1.1负荷计算 (6)1.2无功功率补偿 (9)1.3变电所主变压器的选择 (10)第2章变电所主接线方案的选择 (11)2.1电气主接线的基本要求 (12)2.2主接线形式 (12)第3章短路电流计算 (13)3.1短路电流计算的目的 (13)3.2短路电流计算 (14)第4章变电所进出线的选择及校验 (16)4.1导线选择的原则 (16)4.2变电所导线的选择 (17)第5章变电所继电保护的整定 (20)第6张防雷保护 (21)6.1变电所遭受雷击的主要原因 (21)6.2变电所防雷的具体措施 (22)总结 (25)第1章 负荷计算和无功功率补偿1.1 负荷计算(1)单组用电设备负荷的计算①有功计算负荷(单位为KW ) ②无功计算负荷(单位为kvar )30P =e d P K ,d K 为系数 ϕtan 3030P Q =③视在计算负荷(单位为KVA )30S =ϕcos 30P ④计算电流(单位为A ) 30I =NU S 330, N U 为用电设备的额定电压(单位为KV )(2)多组用电设备负荷的计算 ①有功计算负荷(单位为KW )30P =i p P K ⋅⋅∑∑30式中i P ⋅∑30是所有设备组有功计算负荷30P 之和,p K ⋅∑是有功负荷同时系数,可取0.85~0.95②无功计算负荷(单位为kvar )30Q =i q Q K ⋅⋅∑∑30,i Q ⋅∑30是所有设备无功30Q 之和;q K ⋅∑是无功负荷同时系数,可取0.9~0.97③视在计算负荷(单位为kvA )30S =230230Q P + ④计算电流(单位为A ) 30I =NU S 330经过计算,得到各厂房和生活区的负荷计算表,如表1-1所示(额定电压取380V )1.2无功功率补偿无功补偿的主要作用无功补偿的主要作用就是提高功率因数以减少设备容量和功率耗损、稳定电压和提高供电质量,在长距离输电中提高系统输电稳定性和输电能力以及平衡三相负载的有功和无功功率。
「某机械厂降压变电所的电气设计」
「某机械厂降压变电所的电气设计」机械厂的降压变电所是该厂电力系统的重要组成部分,其电气设计需要满足工艺流程需求和相关电力设备的要求。
本文将对该降压变电所的电气设计进行详细介绍。
首先,根据工艺流程及设备要求,确定了变电所的容量和电压等级。
经过综合考虑,确定了该工地的降压变电所的容量为1000KVA,中压侧额定电压为10KV,低压侧额定电压为0.4KV。
根据变电所的负荷需求及工艺流程,设计了变电所的主要电气系统和设备,包括高压侧进线柜、10KV主变压器、低压配电柜等。
其中,高压侧进线柜采用了固定式进线柜,能够对10KV进线的电能进行安全的接入和切断。
主变压器选择了适当容量的变压器,可以进行中压侧到低压侧的电能变压。
低压配电柜则用于对变压器输出的低压电能进行分配和控制。
根据电气安装规范和设备使用要求,进行了降压变电所的布置设计。
根据设备的尺寸和安全距离要求,合理安排了高低压设备的布置位置,并保证了设备之间的安全间距。
此外,在设备的周围还设置了足够的通道和未来的扩容空间。
为了保证降压变电所的安全可靠运行,进行了相应的电气保护和接地设计。
电气保护方面,采用了过电流保护、短路保护、过载保护等安全措施,能够对系统的异常情况进行及时切断和保护。
接地设计方面,根据电气设备的接地要求,设计了合适规模的接地装置,确保电气设备和工人的安全。
此外,还进行了低压配电系统的设计。
根据工艺流程和设备需求,设计了适当容量的低压配电柜,并设置了合适的断路器、接触器和保护装置,以实现对电能的分配和控制。
同时,根据设备的耗电量、负载需求等因素,合理划分了不同区域的配电线路和断路器。
最后,对降压变电所的接线和布线进行了详细设计。
根据设备的电气连接要求,进行了线缆的选择和敷设方案的设计。
在敷设时,考虑了线缆长度、散热、敷设通道等因素,避免了电缆拥挤、短路等问题。
总之,机械厂降压变电所的电气设计充分考虑了工艺流程需求和设备要求,通过合理选择设备、布置设计、保护装置和接线布线等措施,确保了系统的安全可靠运行。
某冶金机械厂降压变电所的电气设计(1)知识分享
某冶金机械厂降压变电所的电气设计(1)某冶金机械厂降压变电所的电气设计1.设计资料1.1工厂总平面图工厂总平面图如图1所示图1 工厂总平面图1.2工厂负荷情况该厂多数车间为两班制,年最大负荷小时数为4600h,日最大负荷持续时间为6h。
该厂除铸造车间、电镀车间和锅炉房属二级负荷处,其余为三级负荷。
该厂的负荷统计资料如下表1。
表1 工厂各车间负荷情况厂房编厂房名负荷类设备容量需要系数功率因数tan1 铸造车间动力520 0.4 0.7 1.02照明10 0.9 1.0 02 锻压车间动力240 0.3 0.65 1.17照明10 0.9 1.0 03 金工动力390 0.32 0.65 1.12车间照明10 0.9 1.0 04 工具车间动力290 0.35 0.65 1.33照明10 0.9 1.0 0续表1厂房编厂房名负荷类设备容量需要系数功率因数tan5 电镀车间动力450 0.6 0.80 0.75照明10 0.9 1.0 06 热处理车间动力260 0.62 0.82 0.82照明10 0.9 1.0 07 装配车间动力170 0.4 0.75 1.02照明10 0.9 1.0 08 机修车间动力100 0.3 0.7 1.17照明 5 0.9 1.0 09锅炉车间动力115 0.8 0.8 1.05 照明 3 0.9 1.0 010仓库动力50 0.4 0.9 0.75照明 2 0.9 1.0 0 11生活区照明400 0.8 1.0 0.481.3供电电源情况按照工厂与当地供电部门登定的供用电协议规定,本厂可由附近一条10kV的公用电源干线取得工作电源。
该干线的走向参看工厂总平面图。
该干线的导线牌号为LGT-150(0.36 Ω/km),干线首端距离本厂约8km。
干线首端所装设的高压断路器断流容量为500MVA。
为满足工厂二级负荷的要求,可采用高压联络线由邻近的单位取得备用电源。
1.4气象资料本地区的年最高气温为38℃,年平均气温为23℃,年最低气温为-8℃,年最热月平均气温为33℃,年最热月平均气温为26℃,年最热月地下0.8m处平均温度为25℃。
某机械厂降压变电所电气设计_毕业设计论文
某机械厂降压变电所电气设计说明书目录摘要 (1)第1章绪论 (2)1.1 (2)1.2 工厂总平面图 (2)1.3 工厂内部和周边情况 (2)第2章负荷计算和无功功率补偿 (4)2.1 负荷计算 (4)2.1.1 单组用电设备计算负荷的计算公式 (4)2.1.2 多组用电设备计算负荷的计算公式 (4)2.2 无功功率补偿 (5)第3章变电所位置和接线方案的选择 (8)3.1 变配电所的位置选择 (8)3.2 变电所主接线方案 (9)3.3变压器型号的选择 (10)3.4变电所进出线与临近单位联络线的选择 (13)第4章短路电流的计算 (14)4.1 短路电流 (14)4.2 绘制计算电路 (15)4.3 确定短路计算基准值 (15)4.4 计算短路电路中各个元件的电抗标幺值 (16)第5章降压变电所防雷与接地装置的设计 (17)5.1 变电所的防雷保护 (17)5.1.1 直接防雷保护 (17)5.1.2 雷电侵入波的防护 (17)5.2 变电所公共接地装置的设计 (17)5.2.1 接地电阻的要求 (17)5.2.2 接地装置的设计 (18)结论 (19)参考文献 (21)致谢 (20)摘要为保障工业生产安全进行,保证电能合理分配、输送,灵活改变运行方式。
特进行本次设计。
本设计主要阐述了对机械厂总降压变电所的电气设计方案。
在设计中进行了对工厂负荷的统计计算;变电所位置与型式的选择;变电所主变压器及主接线方案的选择;短路电流的计算;变电所进出线与邻近单位联络线的选择;降压变电所防雷与接地装置的设计等。
本机械厂降压变电所电气设计为毕业设计,其目的是通过设计实践,综合运用所学知识,理论联系实际,锻炼独立分析和解决建筑电气设计问题的能力,为未来的工作奠定坚实的基础。
关键词:工厂供电,变电所,无功功率补偿,变压器,短路电流计算,一次设备,避雷器。
第一章 前言 1.1 设计背景本次设计要求根据本厂所能取得的电源及本厂用电负荷情况,并适当考虑工厂生产的发展,按照安全可靠、技术先进、经济合理的要求,确定变电所的位置和型式,确定变电所主变压器的台数、容量与类型,选择变电所主接线方案、一次设备的选择、高低压设备和进出线,确定防雷和接地装置。
毕业设计:10kV变电所电气部分设计
目录摘要 (I)Abstract (II)1绪论 (1)1.1我国电力行业发展概况 (1)1.2变电所的类型概述 (1)1.3变电所电气设备概述 (2)1.4本次设计主要内容 (3)2负荷计算 (4)2.1负荷计算的目的和方法 (4)2.2负荷计算 (5)2.3无功功率补偿计算 (8)2.4电源进线方式设计 (12)2.5变电站主变压器的台数、容量及类型的设计 (12)2.6变电所形式的设计 (13)3电气主接线的设计 (15)3.1对电气主接线的基本要求 (15)3.2电气主接线的基本形式 (16)3.3主接线方案设计 (21)4短路电流计算和设备选择与校验 (22)4.1概述 (22)4.2短路电流计算 (22)4.3高低压电气设备的选择与校验 (31)5总结 (42)谢辞 ................................................................................................. 错误!未定义书签。
参考文献 . (43)附录1:外文资料翻译 (45)Ⅲ1绪论1.1我国电力行业发展概况我国电源建设发展迅速,我国电力行业持续快速发展。
近些年来,我国总发电装机容量和发电量已经连续十年位居世界第二位,随着总发电装机容量增长,增长率有所平缓,但仍保持了较高增长水平。
我国电网建设持续增长,长期以来,我国电力工业“重发轻供”,电网发展严重滞后于电源发展,表现为输变电建设严重滞后于电源建设,配电网建设滞后于主网建设,负荷中心受端电网建设滞后于送端电网建设,电网累计投资占电力投资的比例约30%左右,远低于发达国家50%以上的水平。
为解决此问题,国家今后将重点持续促进电网建设,以适应我国工业化及城市化建设的需要。
特高压电网建设及坚强智能电网规划促进我国电力系统高质量发展,1)特高压电网建设,按照国家电网公司的规划,未来将建成以特高压电网为骨干网架、各级电网协调发展的坚强国家电网。
某机械厂降压变电所的电气设计
某机械厂降压变电所的电气设计1. 引言本文档旨在对某机械厂降压变电所的电气设计进行详细介绍和说明。
该变电所是为了满足机械厂正常运营所需的电能供应而建设的。
电气设计是变电所建设的关键环节,包括供电系统、变压器选型、保护设备等方面的设计。
2. 变电所概述2.1 变电所位置和规模该变电所位于某机械厂占地面积内,距离主生产区较近,方便供电。
变电所设计容量为XXX kW,以满足全厂的电能需求。
2.2 变电所布置图变电所布置图如下所示:变电所布置图变电所布置图3. 供电系统设计供电系统设计是变电所电气设计的核心之一,包括主要设备的选型和系统的配置。
3.1 主变压器选型根据机械厂的电能需求以及电网情况,我们选择了一台XXX kVA的主变压器作为供电系统的核心设备。
主变压器的选型需要考虑负载容量、变比、温升等因素,以确保电能的稳定供应。
3.2 主开关柜设计主开关柜作为供电系统的控制中心,选用合适的开关设备和保护装置非常重要。
我们选择了XXX型号的主开关柜,配备了过电流保护装置、欠压保护装置等功能,以保证供电系统的可靠性和安全性。
3.3 配电柜设计变电所配电柜的设计需要考虑供电负荷的分配和系统的可靠性。
根据实际需求,我们设计了多台配电柜,分别连接到不同的设备和区域。
配电柜配备了相应的断路器、接触器、电能表等设备,以实现对不同电路的控制和计量。
4. 保护系统设计为了确保供电系统的安全运行,我们设计了完善的保护系统,包括过电流保护、短路保护、接地保护等。
4.1 过电流保护过电流保护是变电所保护系统的重要组成部分。
我们选用了电流互感器配合继电器,实现对供电系统中过电流的及时检测和保护。
4.2 短路保护短路保护是变电所保护系统的另一个关键方面。
我们选择了短路保护器件,实现对供电系统中短路故障的迅速切断和保护,以避免设备损坏和人员安全事故的发生。
4.3 接地保护为确保供电系统的安全接地,我们设计了接地系统。
接地系统包括接地装置和接地线,通过对设备和设施的接地,降低了电气设备的绝缘电阻,减少了触电危险。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
毕业设计(论文)题目:永济机械厂10kv降压变电所的电气设计年级专业:机电1072班学生姓名:指导教师:2010年5 月20日摘要电能是现代人们生产和生活的重要能源。
电能可由其他形式的能转换而来,也可简便地转换成其他形式的能。
电能的输送,分配,调试,控制和测试等简单易行,有利于实现生产过程的自动化,因此,在工矿企业,交通运输,人民生活中得到广泛应用。
电力工业是国民经济重要的部门,是现代化建设的基础。
本次设计主要是有关工厂降压变电所设计方面的内容,本说明书中主要叙述了工厂降压变电所设计方法、和其他要求的确定供电系统的主要电气设备,供电系统的接线和结构,负荷计算和断路计算,电线和导线的选择及校正,断电保护装置及二次系统,防雷;接地及电气安全,电气照明技术,工厂供电系统的经济运行,工厂供电系统的运行维护和检修,实验与实践等。
本次工厂降压变电所的设计,它从多方面体现出了工厂供电的重要性工厂总降压变电所的位置和形式选择参考电源进线方向,综合考虑设置总降压变电所的有关因素,确定变压器的台数和容量.工厂总降压变电所主结线方案设计根据变电所配电回路数,,确定变电所高,低接线方式,系统短路电流计算由系统不同运行方式下的短路参数,求出不同运行方式下各点的三相及两相短路电流.负荷计算及无功功率补偿负荷计算的方法有需要系数法,利用系数法及二项式等几种.本设计采用需要系数法确定.【关键词】电气设计功率补偿负荷计算防雷与接地主变压器一次设备的选择与校验二次回路方案的选择目录前言 (1)第一章电气设计的一般原则.设计内容及步骤 (2)1.1、电气设计设计的一般原则 (2)1.2、设计内容及步骤 (2)第二章负荷计算的内容和目的 (5)2.1负荷计算的内容和目的 (5)2.2负荷分级及供电要求 (5)2.3电源及供电系统 (6)2.4电压选择和电能质量 (6)2.5无功补偿 (6)2.6低压配电 (7)2.7变电所进出线选择和校验 (7)第三章负荷计算和无功功率计算及补偿 (8)3.1负荷计算及无功功率补偿 (8)3.2无功功率补偿计算 (11)3.3年耗电量的估算 (11)第四章变电所主变压器台数和容量及主接线方案的选择 (13)4.1变电所主变压器台数的选择 (13)4.2变电所主变压器容量选择 (13)4.3变电所主接线方案的选择 (13)第五章变电所一次设备的选择与校验- (15)5.1变电所高压一次设备的选择 (15)5.2变电所高压一次设备的校验 (15)5.3.高压设备的热稳定性校验 (16)5.4变电所低压一次设备的选择 (17)5.5变电所低压一次设备的校验 (17)第六章变电所高、低压线路的选择 (19)6.1高压线路导线的选择 (19)6.2低压线路导线的选择 (19)第七章变电所二次回路方案选择及继电保护的整定 (21)7.1二次回路方案选择 (21)7.2继电保护的整定 (21)第八章防雷保护与接地装置设计 (24)8.1防雷设备 (24)8.2.接地与接地装置 (24)第九章总结 (26)参考文献 (27)致谢 (28)附录 (29)前言电能是现代工业生产的主要能源和动力。
电能既易于由其它形式的能量转换而来,又易于转换为其它形式的能量以供应用;电能的输送的分配既简单经济,又便于控制、调节和测量,有利于实现生产过程自动化。
因此,电能在现代工业生产及整个国民经济生活中应用极为广泛。
在工厂里,电能虽然是工业生产的主要能源和动力,但是它在产品成本中所占的比重一般很小(除电化工业外)。
电能在工业生产中的重要性,并不在于它在产品成本中或投资总额中所占的比重多少,而在于工业生产实现电气化以后可以大大增加产量,提高产品质量,提高劳动生产率,降低生产成本,减轻工人的劳动强度,改善工人的劳动条件,有利于实现生产过程自动化。
从另一方面来说,如果工厂的电能供应突然中断,则对工业生产可能造成严重的后果。
因此,做好工厂供电工作对于发展工业生产,实现工业现代化,具有十分重要的意义。
由于能源节约是工厂供电工作的一个重要方面,而能源节约对于国家经济建设具有十分重要的战略意义,因此做好工厂供电工作,对于节约能源、支援国家经济建设,也具有重大的作用。
工厂供电工作要很好地为工业生产服务,切实保证工厂生产和生活用电的需要,并做好节能工作,就必须达到以下基本要求:(1)安全在电能的供应、分配和使用中,不应发生人身事故和设备事故。
(2)可靠应满足电能用户对供电可靠性的要求。
(3)优质应满足电能用户对电压和频率等质量的要求(4)经济供电系统的投资要少,运行费用要低,并尽可能地节约电能和减少有色金属的消耗量。
此外,在供电工作中,应合理地处理局部和全局、当前和长远等关系,既要照顾局部的当前的利益,又要有全局观点,能顾全大局,适应发展。
【关键词】电气设计功率补偿负荷计算工厂供电防雷主变压器一次设备的选择与校验第一章电气设计的一般原则.设计内容及步骤1.1、电气设计设计的一般原则按照国家标准GB50052-95 《供配电系统设计规范》、GB50053-94 《10kv及以下设计规范》、GB50054-95 《低压配电设计规范》等的规定,进行工厂供电设计必须遵循以下原则:(1)遵守规程、执行政策;必须遵守国家的有关规定及标准,执行国家的有关方针政策,包括节约能源,节约有色金属等技术经济政策。
(2)安全可靠、先进合理;应做到保障人身和设备的安全,供电可靠,电能质量合格,技术先进和经济合理,采用效率高、能耗低和性能先进的电气产品。
(3)近期为主、考虑发展;应根据工作特点、规模和发展规划,正确处理近期建设与远期发展的关系,做到远近结合,适当考虑扩建的可能性。
(4)全局出发、统筹兼顾。
按负荷性质、用电容量、工程特点和地区供电条件等,合理确定设计方案。
工厂供电设计是整个工厂设计中的重要组成部分。
工厂供电设计的质量直接影响到工厂的生产及发展。
作为从事工厂供电工作的人员,有必要了解和掌握工厂供电设计的有关知识,以便适应设计工作的需要。
1.2、设计内容及步骤全厂总降压变电所及配电系统设计,是根据各个车间的负荷数量和性质,生产工艺对负荷的要求,以及负荷布局,结合国家供电情况。
解决对各部门的安全可靠,经济的分配电能问题。
其基本内容有以下几方面。
1、负荷计算全厂总降压变电所的负荷计算,是在车间负荷计算的基础上进行的。
考虑车间变电所变压器的功率损耗,从而求出全厂总降压变电所高压侧计算负荷及总功率因数。
列出负荷计算表、表达计算成果。
2、工厂总降压变电所的位置和主变压器的台数及容量选择参考电源进线方向,综合考虑设置总降压变电所的有关因素,结合全厂计算负荷以及扩建和备用的需要,确定变压器的台数和容量。
3、工厂总降压变电所主结线设计根据变电所配电回路数,负荷要求的可靠性级别和计算负荷数综合主变压器台数,确定变电所高、低接线方式。
对它的基本要求,即要安全可靠又要灵活经济,安装容易维修方便。
4、厂区高压配电系统设计根据厂内负荷情况,从技术和经济合理性确定厂区配电电压。
参考负荷布局及总降压变电所位置,比较几种可行的高压配电网布置放案,计算出导线截面及电压损失,由不同放案的可靠性,电压损失,基建投资,年运行费用,有色金属消耗量等综合技术经济条件列表比值,择优选用。
按选定配电系统作线路结构与敷设方式设计。
用厂区高压线路平面布置图,敷设要求和架空线路杆位明细表以及工程预算书表达设计成果。
5、工厂供、配电系统短路电流计算工厂用电,通常为国家电网的末端负荷,其容量运行小于电网容量,皆可按无限容量系统供电进行短路计算。
由系统不同运行方式下的短路参数,求出不同运行方式下各点的三相及两相短路电流。
6、改善功率因数装置设计按负荷计算求出总降压变电所的功率因数,通过查表或计算求出达到供电部门要求数值所需补偿的无功率。
由手册或厂品样本选用所需移相电容器的规格和数量,并选用合适的电容器柜或放电装置。
如工厂有大型同步电动机还可以采用控制电机励磁电流方式提供无功功率,改善功率因数。
7、变电所高、低压侧设备选择参照短路电流计算数据和各回路计算负荷以及对应的额定值,选择变电所高、低压侧电器设备,如隔离开关、断路器、母线、电缆、绝缘子、避雷器、互感器、开关柜等设备。
并根据需要进行热稳定和力稳定检验。
用总降压变电所主结线图,设备材料表和投资概算表达设计成果。
8、继电保护及二次结线设计为了监视,控制和保证安全可靠运行,变压器、高压配电线路移相电容器、高压电动机、母线分段断路器及联络线断路器,皆需要设置相应的控制、信号、检测和继电器保护装置。
并对保护装置做出整定计算和检验其灵敏系数。
设计包括继电器保护装置、监视及测量仪表,控制和信号装置,操作电源和控制电缆组成的变电所二次结线系统,用二次回路原理接线图或二次回路展开图以及元件材料表达设计成果。
35kv及以上系统尚需给出二次回路的保护屏和控制屏屏面布置图。
9、变电所防雷装置设计参考本地区气象地质材料,设计防雷装置。
进行防直击的避雷针保护范围计算,避免产生反击现象的空间距离计算,按避雷器的基本参数选择防雷电冲击波的避雷器的规格型号,并确定其接线部位。
进行避雷灭弧电压,频放电电压和最大允许安装距离检验以及冲击接地电阻计算。
10软母线制作安装1)、所用的导线及避雷线,其结构及规格应与工程设计相符,并符合国家标准的各项规定。
2)、使用液压设备前,要认真检查其完好程度,以保证正常操作。
对耐张线夹应使用精度为0.02mm的游标卡尺测量受压部分的内外径。
3)、对使用的各种规格的耐张线夹,应用汽油清洗管内壁的油垢,并清除影响穿管的锌疤及焊渣。
4)、对铝绞线的外层铝股用棉纱蘸少量汽油擦净表面油垢;并涂电力复合脂,将外层铝股覆盖住。
然后进行液压压接。
11硬母线安装1)、母线安装前应检查支架安装面水平偏差不大于3mm,同一平面内绝缘子顶面偏差户内不大于2mm、户外不大于3mm,直线段内各绝缘子中心线偏差不大于2mm,支柱瓷瓶无损伤掉瓷,母线表面应光洁平整,不应有裂纹、变形和扭曲现象。
如需整校时,应在直木板上进行,严禁用铁锤进行打击。
2)、母线需制作立弯、平弯时应予先进行放样,弯曲立弯、平弯时应使用专用弯曲机进行。
弯曲部分外观无断裂无明显抓皱。
3)、各处接连接时所有接触面应用水磨砂纸打磨光洁,并涂抹适量的电力复合脂。
第二章负荷计算的内容和目的2.1负荷计算的内容和目的1 计算负荷又称需要负荷或最大负荷。
计算负荷是一个假想的持续性的负荷,其热效应与同一时间内实际变动负荷所产生的最大热效应相等。
在配电设计中,通常采用30分钟的最大平均负荷作为按发热条件选择电器或导体的依据。
2 尖峰电流指单台或多台用电设备持续1秒左右的最大负荷电流。
一般取启动电流上午周期分量作为计算电压损失、电压波动和电压下降以及选择电器和保护元件的依据。