The Piston-type Steam pressure reducing valve

Instruction manual Configurations:

Main performance and uses:

Y43H is principally used in steam pipe, it can reduce the inlet pressure to a certain outlet pressure you need by adjusting the spring, when the flow and the pressure of the inlet varies, the outlet pressure can also remain within a certain range by the strength of the medium itself, but the differential pressure of the inlet and outlet must be equal or greater than 0.2MPa. Technical parameter:

Working principal:

When the pressure reducing valve leaves the factory, the adjusting spring is in uncompressed state, the main valve disc and secondary valve disc is in close position. When you want to use it, you can turn the adjusting screw clockwise; this can compress the adjusting spring, move the diaphragm down and then open the secondary valve disc, the medium also enters above the main valve seat through “a”hole to “b”hole, make the main valve disc open and then enters under the diaphragm through “c” hole. But when the downstream pressure is exceed the set pressure, the medium moves the diaphragm up and compresses adjusting spring, and then the secondary valve disc closes slowly, because the flow reduces, the downstream pressure get a new balance, on the other hand, when the downstream pressure is less than the set pressure, the gap between the main valve disc and the main valve seat increases and then the flow increases too and then make the downstream pressure get a new balance.

Installation and maintenance:

1.Clean the valve and the pipe line and remove the dirt before

installation, at the same time the valve must be installed in horizontal direction, bracket is needed when the valve deadweight is heavy or vibration exists at the site.

2.While installing, make sure the flow direction and the

direction marked on valve body is consistent, and a bypass pipe is usually required. When the valve size and the pipe size differ, reducer should be adopted. The installing site should have sufficient space for a convenient usage and maintenance.

3.When the valve is put into use, the bypass globe valve must

be opened, remove the condensate and the water vapor mixture in order to avoid the water hammer occurred by opening the valve. If there is no unusual phenomenon appears, you can turn the adjusting screw clockwise till getting the outlet pressure we need, then lock the nut and cover the top cap.

4.A filter must be installed before the pressure reducing valve

which prevents the impurities from getting into the valve. 5.There must be a straight pipe at least 600mm and 1000mm

seperately before and after the pressure reducing valve.

6.A water-vapor separator and a steam trap should be installed

before the pressure reducing valve, atfter which a steam trap should also be installed.

7.Pressure reducing valve should be kept in a dry room, both of

which should be blocked with blind plates. Do not keep in piles.