接地电阻不合格危害
浅谈接地电阻高的危害
![浅谈接地电阻高的危害](https://img.taocdn.com/s3/m/5bf048fd0975f46527d3e172.png)
浅谈接地电阻高的危害摘要:随着工业的发展和自动化水平的提高,供配电和控制系统中,需要接地的设备越来越多,接地的类型也很复杂,既有工作接地又有保护接地,同时,对接地电阻的要求率很高,在一般情况下,要达到要求具有一定难度,而在土壤电阻率很高、环境狭窄的条件下,要达到要求更是非常困难。
接地网是一个大型的接地系统,连接着全部的高低压电气设备的接地线。
接地电阻对接地网的安全起着非常重要的作用,接地电阻的大小是安全接地的重要技术指标。
如果接地电阻阻值过大或发生接地线断线故障,将会由于供电异常造成设备烧毁,甚至会对人身安全造成危险。
为此,我们必须了解接地电阻阻值过大的危害。
关键词接地电阻接地电阻的危害Pick to: with the development of the industry and raise the level of automation, power supply and control system, need grounding equipment more and more, the grounding types are very complex, both working grounding and grounding protection, at the same time, the requirements for earth resistance rate is very high, in general, to meet the requirements of a certain degree of difficulty, and in the soil resistivity is high, narrow environment conditions, to meet the requirement is very difficult. Grounding grid is a large grounding system, connecting all the high and low voltage electrical equipment grounding. Grounding resistance of grounding grid security plays a very important role, the grounding resistance is the size of the safety grounding important technical indexes. If the grounding resistance value is too large or the occurrence of grounding wire break fault, will be due to power supply abnormality caused by burning equipment, and even to the personal safety of dangerous. Therefore, we must understand the grounding resistance value too much harm.Key words: grounding resistance of grounding resistance hazards引言随着电力系统改造的进一步深入,变配电变压器已经分布各地点的负荷中心,使电网达到了结构合理、供电可靠。
关于接地电阻的常见问题详细解答
![关于接地电阻的常见问题详细解答](https://img.taocdn.com/s3/m/aca20d4467ec102de3bd896a.png)
关于接地电阻的常见问题详细解答接地技术的引入初是为了防止电力或电子等设备遭雷击而采取的保护性措施,目的是把雷电产生的雷击电流通过避雷针引入到大地,从而起到保护建筑物的作用。
同时,接地也是保护人身安全的一种有效手段,当某种原因引起的相线(如电线绝缘不良,线路老化等)和设备外壳碰触时,设备的外壳就会有危险电压产生,由此生成的电流就会经保护地线到大地,从而起到人身安全保护作用。
下面小编将接地电阻常见的一些问题及答案进行编辑整理,为正确测量接地电阻值提供参考依据。
问题一:电气接地电阻测试有哪些接地类型?接地的作用总的步说可以分为有两个:保护人员和设备不受损害叫保护接地;保障设备的正常运行的叫工作接地。
1、保护接地:(1)防雷接地是防止受到雷电袭击;(2)机壳安全接地是将系统中平时不带电的金属部分(机柜外壳,操作台外壳等)与地之间形成良好的导电连接,以保护设备和人身安全.保护接地还可以防止静电的积聚.2、工作接地:工作接地是为了使系统以及与之相连的仪表均能可靠运行并保证测量和控制精度而设的接地.它分为机器逻辑地、信号回路接地、屏蔽接地,在石化和其它防爆系统中还有本安接地。
问题二:接地装置的接地电阻由哪4部分组成?接地电阻就是电流由接地装置流入大地再经大地流向另一接地体或向远处扩散所遇到的电阻,它包括接地线和接地体本身的电阻、接地体与大地的电阻之间的接触电阻以及两接地体之间大地的电阻或接地体到无限远处的大地电阻。
问题三:接地电阻的计算公式?串联: R=R1+R2+...+Rn并联:1/R=1/R1+1/R2+...+1/Rn 两个电阻并联式也可表示为R=R1·R2/(R1+R2)定义式:R=U/I决定式:R=ρL/S(ρ表示电阻的电阻率,是由其本身性质决定,L表示电阻的长度,S表示电阻的横截面积)问题四:接地电阻的测量方法有哪些?常用的接地电阻测量方法有四种:接地电阻器测量法、电流电压法(三极法)、变频法、四极法。
接地电阻检测标准
![接地电阻检测标准](https://img.taocdn.com/s3/m/9ecc3a3476232f60ddccda38376baf1ffd4fe35a.png)
接地电阻检测标准《接地电阻检测标准》前言嘿,朋友们!在我们的电气世界里啊,接地可是个相当重要的事儿呢。
你想啊,就像我们人得有个踏实的立足之地一样,电气设备也得有个可靠的接地。
为啥呢?这接地啊,就像是给电找了个安全的出口,能防止设备漏电的时候电到人,还能保护设备自身呢。
接地电阻检测标准就是为了确保这个接地的有效性而存在的。
这就好比给电气设备的安全上了一道保险锁,让我们能放心地使用各种电器设备。
今天呢,咱们就好好唠唠这个接地电阻检测标准。
一、适用范围(一)建筑电气系统在咱们的高楼大厦里,各种电气设备可不少,像电梯啦、照明系统啦、空调系统之类的。
这些设备都得接地良好才行。
比如说吧,你家住在高层,电梯要是接地电阻不合格,万一漏电了,那可就危险得很。
这个标准就适用于整个建筑电气系统的接地电阻检测,不管是新建的大楼,还是老旧建筑的电气改造,都得按照这个标准来。
(二)工业电气设备工厂里更是电气设备的集中地,那些大型的机床、电机、配电柜等设备。
这些设备工作起来电流可大了,如果接地不好,不仅会损坏设备,还可能引发火灾或者危害工人的安全。
这个接地电阻检测标准在工业领域那是必须遵循的,就像工人师傅们必须遵守操作规程一样重要。
(三)通信基站现在大家都离不开手机,通信基站到处都是。
这些基站里的电气设备要是接地电阻有问题,信号传输可能会受到干扰,还可能因为雷击等原因损坏设备。
所以啊,通信基站的接地电阻检测也得符合这个标准。
这就好比是给基站的稳定运行打个基础,基础打不好,上面的“楼”(通信服务)就可能晃悠。
二、术语定义(一)接地电阻接地电阻呢,说白了就是电流从接地电极流入大地所遇到的电阻。
你可以想象一下,电就像水流,大地是一个巨大的水库,接地电极是水管,接地电阻就是水管里的一些小阻碍,这个阻碍越小,电就能越顺畅地流入大地,接地也就越安全有效。
(二)接地电极这就是和大地直接接触的部分啦,像咱们常见的接地棒、接地网之类的东西。
它的作用就是把电气设备上的电传导到大地里去。
接地电阻测试仪的阻值过大有什么危害
![接地电阻测试仪的阻值过大有什么危害](https://img.taocdn.com/s3/m/62cb47703b3567ec102d8aab.png)
接地电阻测试仪的阻值过大有什么危害数字接地电阻测试仪,接地电阻表,接地表用于电力、通信、铁路及工矿企业等部门各种装置接地电阻值的测量。
同时,数字接地电阻测试仪可测量土壤电阻率及地电压。
数字接地电阻测试仪摒弃传统的人工手摇发电工作方式,接地电阻测试仪采用先进的中大规模集成电路,数字接地电阻测试仪应用DC/AC变换技术将三端钮、四端钮测量方式合并为一种机型的新型接地电阻测量仪。
接地电阻测试仪阻值的大小影响着供电质量,如果阻值过大或发生接地线断线故障,将会由于供电异常造成设备烧毁,甚至会对人身安全造成危险。
所以,我们必须了解接地电阻测试仪阻值过大的危害及防范措施。
接地电阻测试仪的阻值过大有什么危害,具体请看下面:阻值过大的危害1、接地电阻测试仪阻值过大,如同时伴有低压相线绝缘损坏而接地,这时接地线中将有电流流过,L1相电压加在大地和接地电阻上,接地电阻阻值越大,接地电阻上的分压就越大。
这时,如果有人误触变压器接地线或中性线以及变压器外壳,人体将和接地电阻形成并联,那么加在人体上的电压就会导致人身触电。
2、当三相四线中的中性线接地电阻阻值过大或中性线断线时,此时由于三相负载的不平衡,变压器中性点将发生偏移,接地点电位不为零,使得有的相电压升高而烧毁用电设备。
3、当接地电阻阻值过大,同时变压器批避雷器不能正常对地放电,致使避雷器或变压器烧毁。
阻值过大的原因分析1、接地装置所用的材料不合格。
由于接地体埋设不规范,安装工艺不合格,接地体与接地线接头连接松动,大地过于干燥等原因,均有可能造成接地电阻阻值过大。
2、由于对接地线作用的重要性认识不足,中性线截面积选择过小,或由于外力的破坏、接地线被盗等原因,都有可能导致接地线断线或接地电阻阻值过大。
防范措施 接地装置一般由钢管、角钢、扁钢及钢绞线等材料制成。
埋设深度应不小于0.5~0.8m。
接地装置的施工一般应和基础施工同时进行,具体要求如下。
1、接地槽的深度应符合设计要求,一般为0.5~0.8m,可耕地应敷设在耕作深度以下。
接地电阻不合格危害
![接地电阻不合格危害](https://img.taocdn.com/s3/m/98103de4f111f18582d05a79.png)
配电变压器接地电阻过大的危害与预防发布者:admin 发布时间:2011-9-17 阅读:79次配电变压器(以下称变压器)接地电阻阻值的大小影响供电质量,如果接地电阻阻值过大或发生接地线断线故障,将会由于供电异常造成设备烧毁,甚至会对人身安全造成危险。
为此,我们必须了解接地电阻阻值过大的危害及防范措施。
1、接地电阻阻值过大的危害(1)变压器接地线接地电阻阻值过大,如同时伴有低压相线绝缘损坏而接地(例如L1相线接地),这时变压器接地线中将有电流流过,L1相电压加在大地和接地电阻上,接地电阻阻值越大,接地电阻上的分压就越大。
这时,如果有人误触变压器接地线或中性线以及变压器外壳,人体将和接地电阻形成并联,那么加在人体上的电压就会导致人身触电。
(2)当变压器三相四线中的中性线接地电阻阻值过大或中性线断线时,此时由于三相负载的不平衡,变压器中性点将发生偏移,接地点电位不为零,使得有的相电压升高而烧毁用电设备。
(3)当接地电阻阻值过大,同时变压器批避雷器不能正常对地放电,致使避雷器或变压器烧毁。
2、变压器接地电阻阻值过大的原因(1)接地装置的材料不合格。
由于接地体埋设不规范,安装工艺不合格,接地体与接地线接头连接松动,大地过于干燥等原因,均有可能造成接地电阻阻值过大。
(2)由于对变压器接地线作用的重要性认识不足,中性线截面积选择过小,或由于外力的破坏、接地线被盗等原因,都有可能导致接地线断线或接地电阻阻值过大。
3、预防措施(1)严格施工工艺,规范接地体的埋设。
接地装置一般由钢管、角钢、扁钢及钢绞线等材料制成。
埋设深度应不小于0.5~0.8m。
接地装置的施工一般应和基础施工同时进行,具体要求如下。
①接地槽的深度应符合设计要求,一般为0.5~0.8m,可耕地应敷设在耕作深度以下。
接地槽的宽度一般为0.3~0.4m,并应清除槽中一切影响接地体与土壤接触的杂物。
②钢管的规格及打入土壤中的深度应符合设计要求,接地体应垂直打入地中且固定,以免增加街道电阻阻值。
论述配电变压器接地电阻阻值过大的危害
![论述配电变压器接地电阻阻值过大的危害](https://img.taocdn.com/s3/m/2826d69bddccda38366baf04.png)
论述配电变压器接地电阻阻值过大的危害当配电变压器接地电阻阻值过大的时候会影响供电设备的正常运行,严重的情况下还会威胁到人员的人身安全。
如果配电变压器的电阻阻值较大的时候,此时配电变压器的避雷器接地电阻值也会增大,如果遇到雷雨天气,此时不能通过避雷器将电流传送到大地,否则会危害到避雷器或者供电设备。
要想预防配电变压接地电阻阻值过大所带来的危害,就要分析导致配电变压器接地电阻阻值较大的具体原因,并根据具体情况探究其中存在的危害,及时采取措施加以解决。
1 配电变压器接地电阻阻值过大带来的危害第一,配电变压器接地线接地电阻的阻值过大时会伴随着低压相线绝缘损坏而接地。
比如:当LI相接地的时候,此时会有电流流经配电变压器接地线,然后在大地以及接地电阻上加入L1相电压,当前的接地电阻阻值与接地电阻上的分压成正比,也就是说接地电阻的阻值越大,接地电阻上的分压也会越大。
如果有人不小心碰触到配电变压器接地线或者中性线、配电变压器的外壳时,人体与接地电阻形成了并联关系,流经人体的电压就会变得非常高,最终导致了触电现象的发生。
第二,如果配电变压器三相四线中的中性线接地电阻的阻值较大或者出现断线的时候,此时的三相负载具有不平衡性,导致配电变压器中性点发生了偏移,接地点电位的值超过了零,这就提升了有的相的电压,致使一些正在用电的设备被烧毁。
第三,如果接地电阻阻值较大的时候,这就直接增加了配电变压器避雷器的接地电阻阻值。
当雷击电压时,避雷器不能够将电压完全释放出来,这就直接引发烧毁避雷器或者配电变压器的现象。
2 配电变压器接地电阻阻值较大的具体原因2.1 接地装置的材料与规定的要求不相符由于埋设接地体过程中存在着不规范的行为,并且安装工艺不够精确,这就导致接地体与接地线之间的连接存在着松动。
同时由于大地较为干燥,这就会增加接地电阻的阻值。
2.2 配电变压器安装设计不合理在设计以及安装配电变压器的时候,如果所选择的中性截面积较小,那么外力的破坏、接地线被盗等相关原因都会影响到接地线,最终会增加接地电阻的阻值。
配电变压器接地电阻过大的危害与预防范本
![配电变压器接地电阻过大的危害与预防范本](https://img.taocdn.com/s3/m/bc2688d2112de2bd960590c69ec3d5bbfd0ada03.png)
配电变压器接地电阻过大的危害与预防范本当配电变压器的接地电阻过大时,可能会导致以下几个方面的危害:1. 电器设备损坏:接地电阻过大会导致接地电流增大,如果变压器内部存在故障电流,就会通过接地电阻引流到地面,从而影响到其他的电气设备,甚至损坏它们。
这对于一些敏感的电气设备,如计算机、医疗设备等,可能会造成严重的影响,甚至使它们无法正常工作。
2. 电击危险:接地电阻过大会导致接地电流增大,当人接触带有故障电流的设备时,可能会导致电击事故。
特别是在湿润的环境下,电流更容易通过人体流动,增加了电击的危险性。
3. 火灾风险:接地电阻过大会使得接地电流无法及时传导到地面,从而使电压梯度产生偏差。
这样会使电力设备产生过热,引发火灾的可能性增加。
一旦发生火灾,将会造成巨大的财产损失,并可能危及人员安全。
为了预防配电变压器接地电阻过大的危害,可以采取以下几个措施:1. 定期检测:定期对配电变压器的接地电阻进行检测,了解其变化情况,发现问题及时修复。
通常建议每年进行一次检测,或者在使用环境变化较大的情况下,视情况增加检测频率。
2. 规范施工:在进行变压器配电系统的施工过程中,必须严格按照相关标准和规范进行操作,确保电气设备的接地电阻符合要求。
施工人员应具备专业知识和操作技能,并严格按照规定的步骤和要求进行操作。
3. 保持干燥清洁:保持变压器周围环境干燥、清洁,避免沉积物和湿气对接地系统的影响。
湿润的环境会降低接地电阻,增加电流流动的可能性,因此应保持周围环境的干燥。
4. 定期维护:定期对变压器进行维护,清洁和紧固接地系统。
及时发现并处理可能存在的问题,确保接地电阻不会因为腐蚀、松动等原因增大。
5. 安全教育培训:为相关人员提供相关的安全教育培训,加强他们对于电气设备安全的认识和意识。
教育他们正确使用电气设备,遵循相关的操作规程,以减少电击事故和火灾的发生。
综上所述,配电变压器接地电阻过大会带来严重的危害,涉及设备损坏、电击危险和火灾风险等。
塔吊接地电阻摇测不合格
![塔吊接地电阻摇测不合格](https://img.taocdn.com/s3/m/a1ba66f8f424ccbff121dd36a32d7375a517c650.png)
塔吊接地电阻摇测不合格1. 前言大家好,今天咱们来聊聊一个非常重要但又容易被忽视的话题,那就是塔吊的接地电阻摇测。
哎呀,听起来是不是有点儿枯燥?其实不然,接地电阻可是保障工地安全的重要一环,真是“万里长征,第一步”嘛!如果这一步没做好,后面的工程可就危险了。
2. 接地电阻的意义2.1 什么是接地电阻首先,接地电阻简单来说就是塔吊与地面之间的电阻。
你想啊,塔吊这么高大威猛,要是它的电流不顺利排到地里,那可就麻烦了!就像人掉进水里却找不到出口,真的是“进退两难”呀。
接地电阻越小,说明导电性越好,自然就越安全。
2.2 为什么要摇测摇测的目的就是为了确保这个电阻值在安全范围内。
你要是想想,万一塔吊在运作的时候突然放电,那简直就是“山雨欲来风满楼”的节奏,后果不堪设想!定期的摇测就像给塔吊做健康检查,及时发现问题,才能“未雨绸缪”。
3. 常见问题与解决方案3.1 测试不合格的原因可是,话说回来,测试结果不合格也是常有的事。
像我以前就遇到过这样的情况,摇测的时候电阻值居然高得离谱。
你要知道,这可能是因为接地系统老化、连接不良或者土壤湿度不足。
就像一棵树根如果没扎稳,再大风也抗不住,真是“树大根深”的道理!3.2 应对措施如果发现接地电阻不合格,别慌!首先得排查接地线和连接点,看有没有松动的地方。
然后,可以考虑重新加装接地装置,或者加深接地体的埋设深度。
像我朋友那样,遇到问题总是“临阵磨枪”,其实不如“早做准备”,这样才能稳妥应对各种突发情况。
4. 结尾总之,塔吊的接地电阻摇测虽然听起来简单,但可马虎不得。
它关乎着工地的安全,关乎着每一位工人的生命。
我们应该以“滴水穿石”的精神,做好每一次的摇测,让安全成为工地的“第一保障”。
这样一来,大家都能安心工作,不用担心“青天霹雳”式的事故发生。
希望今天的分享能让大家对塔吊接地电阻有更深入的了解,毕竟“安全第一,预防为主”是我们永远不能忘记的信念!再见啦,朋友们,祝你们工地顺利,平安无事!。
配电变压器接地电阻过大的危害与预防(三篇)
![配电变压器接地电阻过大的危害与预防(三篇)](https://img.taocdn.com/s3/m/52c9b316777f5acfa1c7aa00b52acfc788eb9f69.png)
配电变压器接地电阻过大的危害与预防配电变压器接地电阻过大是指变压器接地系统中的接地电阻数值超过了额定标准值。
这种情况可能会造成电流无法顺利通过接地系统,导致系统故障和安全隐患的出现。
接下来,本文将详细探讨配电变压器接地电阻过大的危害以及如何预防这种情况的发生。
首先,让我们了解一下配电变压器接地系统是什么。
配电变压器接地系统是用于将电气设备的金属外壳与地面建立连接的系统,以便将故障电流引导到地。
这样做的目的是为了保护人身安全、防止设备损坏,并提高系统的可靠性。
接地电阻是描述接地系统性能的一个重要参数。
接地电阻过大可能会引起以下危害:1. 安全隐患:当接地电阻过大时,当设备出现漏电、绝缘击穿等故障时,无法及时将故障电流引流到地,导致电压累积和电气火灾风险增加。
以人身安全来说,过大的接地电阻会增加人体触电的危险性。
2. 设备损坏:过大的接地电阻会导致设备共模电压上升,在设备之间形成电荷不平衡,使设备出现毁坏、断电等故障。
另外,在过大的接地电阻下,设备的绝缘强度会大幅下降,易发生绝缘击穿,导致设备损毁。
3. 系统故障:过大的接地电阻会导致电气设备无法正常工作,甚至变压器过载、变压器温升过高等故障,从而引发电力系统的故障,并影响供电可靠性。
为了避免接地电阻过大带来的危害,我们应该采取以下预防措施:1. 定期检测维护:配电变压器的接地系统应进行定期检测与维护,包括测量和记录接地电阻值,及时发现和排除接地故障,保持接地电阻在合理范围内。
2. 合理设计接地系统:在设计阶段,应根据工程实际情况合理规划接地系统,选择适当的接地电阻标准和材料。
对于重要设备,可以采用双重或多重接地方式,以提高接地系统的可靠性。
3. 加强培训与管理:加强员工的培训与管理,提高他们对接地系统重要性和维护措施的认识。
定期组织培训,提高员工对配电变压器接地系统检测与维护工作的技能水平。
4. 引入检测设备:引入适当的检测设备,如接地电阻测试仪等,在日常维护中进行定期检测,及时发现接地电阻过大的情况,并采取相应的措施进行修复。
接地电阻国家标准
![接地电阻国家标准](https://img.taocdn.com/s3/m/e079e975ce84b9d528ea81c758f5f61fb73628ce.png)
接地电阻国家标准接地电阻是衡量接地设施的质量和安全性能的重要指标之一。
接地电阻不合格不仅会影响设备的正常运行,还会带来安全隐患。
为了保障人身和财产安全,我国制定了一系列关于接地电阻的国家标准,本文将对这些标准进行介绍和解读。
GB/T 50309-2018 《建筑物电气安装工程施工质量验收规范》该标准是我国建筑业关于电气安装工程施工质量验收的统一规范,它对于接地电阻的检测和验收也进行了明确规定。
根据GB/T 50309-2018标准,建筑物的接地电阻应符合以下规定:•构筑物总层数≤7层,接地电阻值不大于4.0Ω;•构筑物总层数>7层,接地电阻值不大于2.0Ω。
同时,该标准还规定了接地电阻的检测方法和仪器要求,包括使用金属电极或钢管电极进行测试,仪器应具有多次反复测试的功能、测试精度不大于0.1%等。
GB 50057-2010 《电气设计规范》该标准是我国电气工程领域的重要规范之一,其中第五部分“电气接地设计规范”详细规定了接地电阻的要求和检测方法。
在GB 50057-2010标准中,接地电阻要符合以下规定:•构筑物总层数不大于6层,接地电阻值不大于4.0Ω;•构筑物总层数>6层,接地电阻值不大于2.0Ω。
该标准还规定了接地电阻测量仪器的技术指标、检测方法的详细步骤和注意事项等,以确保接地电阻值的准确可靠。
GB 14706-2010 《电气安装工程施工质量评定标准》该标准是针对电气安装工程施工质量评定制定的全国性标准,其中第11部分“接地设施施工质量评定标准”对接地电阻也进行了制定。
根据GB 14706-2010标准,接地电阻要满足以下要求:•构筑物总层数不大于2层,接地电阻值不大于4.0Ω;•构筑物总层数>2层,接地电阻值不大于2.0Ω。
同时,该标准还要求进行接地电阻测试时,应对测试点进行清理和封闭,以保证测试的准确性。
总结接地电阻是保障电气设备安全运行的核心指标之一,我国制定的国家标准为保证接地电阻的质量和安全性能提供了有力的保障。
接地电阻过大的预防与危害
![接地电阻过大的预防与危害](https://img.taocdn.com/s3/m/574e620c964bcf84b9d57b12.png)
/400接地电阻过大的预防与危害接地电阻阻值的大小影响供电质量,如果接地电阻阻值过大或发生接地线断线故障,将会由于供电异常造成设备烧毁,甚至会对人身安全造成危险。
为此,我们必须了解接地电阻阻值过大的危害及防范措施。
1、接地电阻阻值过大的危害(1)变压器接地线接地电阻阻值过大,如同时伴有低压相线绝缘损坏而接地(例如L1相线接地),这时变压器接地线中将有电流流过,L1相电压加在大地和接地电阻上,接地电阻阻值越大,接地电阻上的分压就越大。
这时,如果有人误触变压器接地线或中性线以及变压器外壳,人体将和接地电阻形成并联,那么加在人体上的电压就会导致人身触电。
(2)当变压器三相四线中的中性线接地电阻阻值过大或中性线断线时,此时由于三相负载的不平衡,变压器中性点将发生偏移,接地点电位不为零,使得有的相电压升高而烧毁用电设备。
(3)当接地电阻阻值过大,同时变压器批避雷器不能正常对地放电,致使避雷器或变压器烧毁。
2、变压器接地电阻阻值过大的原因(1)接地装置的材料不合格。
由于接地体埋设不规范,安装工艺不合格,接地体与接地线接头连接松动,大地过于干燥等原因,均有可能造成接地电阻阻值过大。
(2)由于对变压器接地线作用的重要性认识不足,中性线截面积选择过小,或由于外力的破坏、接地线被盗等原因,都有可能导致接地线断线或接地电阻阻值过大。
3、预防措施(1)严格施工工艺,规范接地体的埋设。
接地装置一般由钢管、角钢、扁钢及钢绞线等材/400料制成。
埋设深度应不小于0.5~0.8m。
接地装置的施工一般应和基础施工同时进行,具体要求如下。
①接地槽的深度应符合设计要求,一般为0.5~0.8m,可耕地应敷设在耕作深度以下。
接地槽的宽度一般为0.3~0.4m,并应清除槽中一切影响接地体与土壤接触的杂物。
②钢管的规格及打入土壤中的深度应符合设计要求,接地体应垂直打入地中且固定,以免增加街道电阻阻值。
在山区及土壤电阻率较高的地区,尽量少用管形接地装置,而采用表面埋入方式的接地装置。
配电变压器接地电阻过大的危害与预防范本(2篇)
![配电变压器接地电阻过大的危害与预防范本(2篇)](https://img.taocdn.com/s3/m/e77b497966ec102de2bd960590c69ec3d5bbdb22.png)
配电变压器接地电阻过大的危害与预防范本配电变压器接地电阻过大可能会导致以下危害:供电质量下降、电器设备损坏、人身安全受到威胁等。
为了预防此类问题的发生,应采取一系列措施,如检查接地电阻、保持设备正常运行、定期维护和检修等。
配电变压器接地电阻过大会导致供电质量下降。
接地电阻过大会使得接地电流难以顺利通过接地体,导致接地电位升高,进而影响供电质量。
高接地电阻会增加电流回路的阻抗,导致电流的不稳定和变压器内部的电压波动。
这将对供电区域内的设备和用户产生负面影响,如设备运行不稳定、设备故障增多、耗能增加等。
配电变压器接地电阻过大还会导致电器设备损坏。
接地电阻过大会导致接地故障电流沿着设备的金属外壳流动,从而引起设备的外壳电位升高。
当外壳电位升高到一定程度时,可能会对人体构成电击风险。
同时,外壳电位的升高也会导致电器设备内部的电压增大,超过设备设计的额定电压范围,从而使设备损坏。
此外,电器设备损坏还可能导致火灾等严重后果。
为了预防配电变压器接地电阻过大所带来的危害,可以考虑以下预防范本。
1. 定期检查接地电阻。
要定期对配电变压器的接地电阻进行检查和测量。
根据国家标准,一般来说,配电变压器接地电阻应小于4欧姆。
如果接地电阻超过了允许范围,应及时采取措施进行修复和改进。
2. 保持设备正常运行。
定期检查变压器的工作状态,确保所有设备处于正常运行状态。
注意电缆、绝缘子、开关等设备的磨损和老化情况,及时进行维护和更换。
保证设备正常运行,可以减少接地电阻过大的风险。
3. 加强设备检修和维护。
定期检修和维护变压器设备,保持设备的良好状态。
检查设备的接地装置是否存在松动、腐蚀等问题,及时修复和更换。
还可通过测量接地电阻来确定接地装置的状态。
这些措施有助于减少接地电阻过大的风险。
4. 加强员工培训和安全意识教育。
培训员工有关电气安全和配电系统的知识,提高员工对电气事故的防范意识和安全意识。
教育员工遵守操作规程,正确使用电器设备,避免因误操作而导致接地电阻过大的风险。
变电站避雷针接地电阻不合格的危害及处理方案
![变电站避雷针接地电阻不合格的危害及处理方案](https://img.taocdn.com/s3/m/d3c15d71cdbff121dd36a32d7375a417866fc1ec.png)
变电站避雷针接地电阻不合格的危害及处理方案下载提示:该文档是本店铺精心编制而成的,希望大家下载后,能够帮助大家解决实际问题。
文档下载后可定制修改,请根据实际需要进行调整和使用,谢谢!本店铺为大家提供各种类型的实用资料,如教育随笔、日记赏析、句子摘抄、古诗大全、经典美文、话题作文、工作总结、词语解析、文案摘录、其他资料等等,想了解不同资料格式和写法,敬请关注!Download tips: This document is carefully compiled by this editor. I hope that after you download it, it can help you solve practical problems. The document can be customized and modified after downloading, please adjust and use it according to actual needs, thank you! In addition, this shop provides you with various types of practical materials, such as educational essays, diary appreciation, sentence excerpts, ancient poems, classic articles, topic composition, work summary, word parsing, copy excerpts, other materials and so on, want to know different data formats and writing methods, please pay attention!变电站避雷针接地电阻不合格的危害及处理方案在变电站的运行中,避雷针的接地电阻合格与否直接关系到设备和人员的安全以及电网的可靠性。
[全]值班电工安全知识学习-全考点
![[全]值班电工安全知识学习-全考点](https://img.taocdn.com/s3/m/1594dc10bb4cf7ec4bfed079.png)
值班电工安全知识学习-全考点一、单选题(每题1分,共30题)22. 变压器的分接头一般放在()。
(1分)A. 高压侧B. 中压侧C. 低压侧D. 均可以(A)129. 紧急救护时,发现伤员意识不清、瞳孔扩大无反应、呼吸、心跳停止时,应立即在现场就地抢救,用()支持呼吸和循环,对脑、心重要脏器供氧。
(1分)A. 心脏按压法B. 口对口呼吸法C. 口对鼻呼吸法D. 心肺复苏法(D)127. 接地线、接地刀闸与检修设备之间不得连有()。
(1分)A. 断路器(开关)或熔断器B. 断路器(开关)或隔离开关(刀闸)C. 任何设备D. 隔离开关(刀闸)或熔断器(A)185. 因故间断电气工作()者,应重新学习安规,并经考试合格后,方能恢复工作。
(1分)A. 3个月以上B. 连续3个月以上C. 6个月以上D. 连续6个月以上(B)86. 电系设备都应有命名,并应装有固定牢靠的(),以便运行操作时识别。
(1分)A. 指示牌B. 铭牌C. 警告牌D. (B)4. ()是反映电网设备运行情况、状态监测及调度员对这类信息进行确认的信息总称。
该类信息需定期巡视。
(1分)A. 操作信息B. 异常信息C. 告知信息D. 事故信息(C)173. 新设备投运前,有关调度机构应确定、批准新设备的命名与()。
(1分)A. 号码B. 编号C. 铭牌D. (B)239. 电流互感器的作用是()。
A. 升压B. 降压C. 变压D. 变流(D) 63. 倒闸操作的接发令要求发令人和受令人应先互报()和()。
(1分)A. 姓名和年龄B. 单位和姓名C. 时间和姓名D. 单位和职务(B)124. 建立调度关系的有人值班用户变电站内涉及电业的设备,由()担任工作许可人。
(1分)A. 用电监察指派专人B. 电业职工C. 用户变电站值班D. 调度员(C)66. 低压故障主要包括()。
(1分)A. 客户内部故障B. 供电电压、频率等方面问题导致低压用户设备故障C. 路灯等非供电产权的低压线路故障D. 低压线路、进户装置、低压公共设备、低压计量设备故障(D)5. “检修状态”是指设备的开关在()位置、小车在试验或检修位置。
配电变压器接地电阻阻值过大的危害及防范
![配电变压器接地电阻阻值过大的危害及防范](https://img.taocdn.com/s3/m/182f7618a21614791711281e.png)
运 行 基 本 情 况
许 昌 县 椹 涧 变 电 站 自动 化 改 造 后 实 现 了 无 人 值
守 , 2 0 于 0 6年 6 月 初 投 运 。 该 站 投 运 至 今 运 行 情 况 基 本 良好 , 视 监 控 系 统 能 长 期 、 续 、 靠 工 作 。 有 效 遥 连 可 能
转 弯 部 分 为 101 。 . 1 1
④ 接 地 引 下 线 除 为 测 量 接 地 电 阻 而 预 留 的 断 开 处 外不得 另有接 头 。 地装 置的连 接应保证 接触 可靠 。 接 接
地 引 下 线 与 接 地 体 的 连 接 以 及 接 地 体 本 身 之 间 的 连 接 . 采 用 焊 接 。 地 引 下 线 与 为 测 量 接 地 电 阻 而 预 留 均 接
《 村 电 ̄ } 0 0年第 7期 农 21
栏 目主持 张敬 安
( 2) 接 地 装 置 一 般 应 和 基
础 同时 进 行 施 工 。 要 求 如 下 。 其
① 接 地 槽 的 深 度 应 符 合 设
鱼 夏霍 葡
( 16 0 广 东 电网公 司汕尾供 电局 陈孝 建 560 )
33 .
在 用 户 电 能 表 后 装 设 剩 余 电 流 动 作 保 护 器
地 过 于 干 燥 等 原 因 , 有 可 能 造 成 接 地 电阻 阻 值 过 大 。 均
( )配 电 变 压 器 设 计 安 装 时 对 中 性 线 截 面 积 选 择 2
当用 户 装 设 了剩 余 电流 动 作 保 护 器 后 ,此 时 如 果
② 钢 管 的 规 格 及 打 人 土 壤
中 的深 度 应 符 合设 计 要 求 , 接
地 体 应 垂 直 打 人 地 中 且 同 定 。 免 增 加 接 地 电 阻 。 山 以 在 区及 土壤 电阻率较 高的地 区 , 量 少用管ห้องสมุดไป่ตู้形接 地装 置 , 尽
配电变压器接地电阻过大的危害与预防
![配电变压器接地电阻过大的危害与预防](https://img.taocdn.com/s3/m/57b2e90e2a160b4e767f5acfa1c7aa00b42a9d60.png)
配电变压器接地电阻过大的危害与预防配电变压器接地电阻过大是一种常见的电力设备故障,可能导致电力系统安全隐患和设备损坏。
本文将从危害和预防两个方面进行详细介绍。
一、危害:1. 触电危险:配电变压器接地电阻过大,可能会导致设备的接地失效,增加人员触电的风险。
当外壳或设备出现漏电时,如果变压器接地电阻过大,漏电电流无法通过接地系统及时排除,有可能导致人员触电事故发生。
2. 设备损坏:配电变压器接地电阻过大也可能导致设备内部绝缘失效,进而损坏设备。
当设备内部出现短路或其他故障时,高接地电阻会导致故障电流无法及时得到排除,加剧了设备的损坏程度。
3. 供电质量下降:配电变压器接地电阻过大会导致电力系统的接地电位升高,进而影响供电质量。
在电力系统中,接地电位过高会对设备正常运行造成干扰,导致设备故障频繁发生,甚至造成电力系统供电不稳定。
二、预防:1. 定期检测:为了及时发现和解决配电变压器接地电阻过大的问题,需要定期进行接地电阻测试。
根据电力设备的使用情况和要求,制定适当的测试周期,进行定期检测。
一般建议每年进行一次接地电阻测试,或者在设备更换、维修后进行测试。
2. 接地系统设计:在配电系统设计中,应根据实际情况合理设计接地系统。
接地电阻合理的设计可以降低接地电阻过大的风险。
在设计中,需要考虑地质条件、土壤导电性能和设备容量等因素,确定合适的接地电极材料、型式和布置方式。
3. 接地设施维护:为了保持接地设施的良好状态,减小接地电阻的值,需要定期进行设施的检查和维护。
包括对接地电极、接地线路、接地装置等进行清洁、修复和更新;对接地电极周围土壤进行湿润处理,以提高接地效果。
4. 提高操作技能:提高操作技能和意识可以有效预防配电变压器接地电阻过大的问题。
操作人员应经过专业培训,了解接地电阻测试方法和要求,能够正确操作测试仪器,并熟悉故障排除程序。
5. 及时处理故障:一旦发现配电变压器接地电阻过大的问题,应及时处理。
接地电阻过大的危害,原因及预防
![接地电阻过大的危害,原因及预防](https://img.taocdn.com/s3/m/567a2d45dd36a32d7275812f.png)
接地电阻过大的危害,原因及预防接地电阻的危害(1)变压器接地线的接地电阻太大。
如果伴有低压相线绝缘损坏和接地(例如,L1相线接地),则电流将在变压器的接地线中流动,并且L1相电压将接地。
而接地电阻,则接地电阻的电阻越大,则接地电阻上的分压越大。
此时,如果有人不小心触摸了变压器的接地线或中性线与变压器的外壳,则人体将与接地电阻并联,施加到人体上的电压会引起人身触电。
(2)当三相四线变压器中的中性点接地电阻的电阻太大或中性线断开时,由于三相负载的不平衡,会使变压器的中性点偏移。
不为零,导致某些相电压升高并烧毁电气设备。
(3)当接地电阻的电阻太大时,互感器避雷器不能正常接地,导致避雷器或变压器烧毁。
接地电阻过大的原因(1)接地设备的材料不合格,由于接地体结构不规范,安装过程不合格,接地体与接地线之间的连接松动,接地过于干燥,可能导致接地电阻过大大。
(2)由于对变压器接地线的重要性认识不足,中性线截面积过小,或者由于外力损坏,接地线被盗等原因。
可能导致接地线断裂或接地抵抗性太大了防止接地电阻过大的注意事项(1)严格的施工工艺和规范的掩埋体。
接地装置通常由钢,角钢,扁钢和钢绞线制成,埋深不小于0.5〜0.8m,接地设备的施工通常应与基础施工同时进行。
具体要求如下。
1.接地沟的深度应满足设计要求,一般为0.5〜0.8m,耕地应在耕作深度以下,接地槽的宽度一般为0.3〜0.4m,应清除槽内影响接地体与土壤接触的所有物体。
2.钢管的规格和进入土壤的深度应符合设计要求。
接地体应垂直打入地面并固定,以避免增加街道电阻,在山区和土壤电阻率较高的地区,请尽量减少使用管状接地装置,并使用表面埋入的接地装置。
3.接地导体应沿着电线杆放置,并保持尽可能短和笔直,以减少其电抗。
接地导体与支撑部件固定在塔上。
支撑件之间的直线距离通常为1.0〜1.5m,转弯部分为0.1m。
建筑电气工程电缆敷设前接地电阻测试应合格
![建筑电气工程电缆敷设前接地电阻测试应合格](https://img.taocdn.com/s3/m/ca9538eb29ea81c758f5f61fb7360b4c2e3f2a1e.png)
建筑电气工程电缆敷设前接地电阻测试应合格(实用版)目录1.建筑电气工程电缆敷设前接地电阻测试的重要性2.接地电阻测试的标准和要求3.接地电阻测试的方法和步骤4.接地电阻测试不合格的影响和处理方法5.结论:建筑电气工程电缆敷设前接地电阻测试应合格正文一、建筑电气工程电缆敷设前接地电阻测试的重要性在建筑电气工程中,电缆敷设是一项重要的工作。
而在进行电缆敷设之前,接地电阻测试则是必不可少的一个环节。
接地电阻测试的目的是为了确保电气设备的安全运行,防止因接地不良而引发的触电、火灾等事故。
因此,建筑电气工程电缆敷设前的接地电阻测试应合格。
二、接地电阻测试的标准和要求根据国家标准《建筑电气设计规范》GB 50057-2010 的规定,接地电阻应符合以下要求:1.接地电阻值应小于等于 4 欧姆;2.接地电阻测试点应设置在接地网的各个角落和连接点;3.测试时应使用合格的接地电阻测试仪,并在标准条件下进行测试。
三、接地电阻测试的方法和步骤1.准备工作:检查接地电阻测试仪是否完好,准备测试导线、夹具等工具;2.设置测试点:根据设计要求,在地网地极工程完成后,设置测试点,确保测试点不被外墙饰面遮蔽,并有明显标识;3.连接测试仪:将测试导线一端连接到接地体,另一端连接到测试仪;4.开始测试:启动测试仪,进行接地电阻测试;5.记录测试结果:记录测试仪显示的接地电阻值,并与设计要求进行对比。
四、接地电阻测试不合格的影响和处理方法1.影响:接地电阻测试不合格可能导致电气设备运行不稳定,存在安全隐患,甚至引发触电、火灾等事故。
2.处理方法:(1)查找原因:分析接地电阻不合格的原因,可能是接地网设计不合理、施工质量差等原因;(2)整改:根据原因进行整改,如调整接地网结构、更换接地材料等;(3)重新测试:整改完成后,重新进行接地电阻测试,直至测试合格。
五、结论建筑电气工程电缆敷设前接地电阻测试应合格,以确保电气设备的安全运行。
一起因接地电阻超标引发的事故
![一起因接地电阻超标引发的事故](https://img.taocdn.com/s3/m/c3f2caf7fab069dc502201ac.png)
腐 蚀 性 的 产 物 , 对 设 备 造 成 严 重 的 行 抽 真 空 约 2 h, 使 真 空 度 小 于 5 周 期 性 普 测 工 作 是 很 有 必 要 的 。 在
破 坏 。 P a 。充 入 高纯 度 氮气 至 0 . 4 MP a ( 表 发 现 超 标 缺 陷 时 , 要 及 时 地 进 行 换
分 测试 及超 声局 放等 。
S 气 体 进 行 回 收 。工 作 班 成 员 应 使 合 格 的 S F 气 体 ,静 置 2 4 h后 进 行 测得 的 S 气体 微水 数据 为 6 9 . 3 l L / L, 符合 运行 标准 。
注 意 事 项
近 期 。 在 某 变 电 站 进 行 GI S变 用 良好 、 合格的 S 专 用 安 全 防 护 用 检 漏 、 微水 试 验 。如 此 干燥 处 理后 ,
等 缺陷 , 而其 他检测 未 发现异 常 。
2
发 现 零 部 件 绝 缘 不 合 格 ,否 则 要 及
( 3) 工作中 , 应 保 持 工 作 现 场 通
完 好 的 劳动 防 护 用 品 ,用 过 的2 1 2 器
通 过 检 测 的 结 果 分 析 。 该 气 室 时 更 换 。并 对 拆 开 部 位 的 密 封 件 进 风 、 干燥 、 无尘 , 工 作人 员 使 用合 格 、
主持 : 师
帅 2 0 1 3 . 1 1
1 i 1 0 k V变 ຫໍສະໝຸດ 站 G I S 翟蕈每晕豫基靼耨舶
( 4 7 3 0 0 9 ) 河 南省 电力公 司技 能培训 中心 张 涛 丁旭峰
( 4 7 3 2 0 0 ) 河 南 省 方 城 县 电 业 局 余 勇
处 理
柴发接地电阻
![柴发接地电阻](https://img.taocdn.com/s3/m/b2065b2da66e58fafab069dc5022aaea988f4160.png)
柴发接地电阻
柴发接地电阻是指柴油发电机组的接地电阻,它是保证电气设备安全运行的重要组成部分。
在柴油发电机组的运行过程中,如果接地电阻不合格,会导致电气设备的故障和安全事故的发生。
我们需要了解什么是接地电阻。
接地电阻是指电气设备的接地电路中,接地电极与地之间的电阻。
在电气设备的接地电路中,接地电极是连接设备与地之间的桥梁,它能够将设备的电荷释放到地面上,从而保证设备的安全运行。
而接地电阻则是衡量接地电极与地之间电阻大小的指标,它越小,说明接地电路越好,设备的安全性就越高。
柴发接地电阻的合格标准是多少呢?根据国家标准,柴发接地电阻应该小于4欧姆。
如果接地电阻大于4欧姆,就会导致电气设备的漏电流过大,从而引起设备的故障和安全事故的发生。
因此,对于柴油发电机组的接地电阻,我们必须要进行定期检测和维护,确保其合格。
那么,如何检测柴发接地电阻呢?一般来说,我们可以使用接地电阻测试仪进行检测。
测试时,需要将测试仪的两个电极分别连接到柴油发电机组的接地电极和地面上,然后进行测试。
如果测试结果小于4欧姆,说明接地电阻合格;如果测试结果大于4欧姆,就需要进行维护和修理。
维护柴发接地电阻的方法也很简单。
首先,要保持接地电极的清洁,避免积尘和氧化。
其次,要定期检查接地电极和接地线路的连接情况,确保连接牢固。
最后,要定期进行接地电阻测试,确保其合格。
柴发接地电阻是保证电气设备安全运行的重要组成部分。
我们必须要重视柴发接地电阻的检测和维护,确保其合格,从而保障电气设备的安全性。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
配电变压器接地电阻过大的危害与预防发布者:admin 发布时间:2011-9-17 阅读:79次配电变压器(以下称变压器)接地电阻阻值的大小影响供电质量,如果接地电阻阻值过大或发生接地线断线故障,将会由于供电异常造成设备烧毁,甚至会对人身安全造成危险。
为此,我们必须了解接地电阻阻值过大的危害及防范措施。
1、接地电阻阻值过大的危害(1)变压器接地线接地电阻阻值过大,如同时伴有低压相线绝缘损坏而接地(例如L1相线接地),这时变压器接地线中将有电流流过,L1相电压加在大地和接地电阻上,接地电阻阻值越大,接地电阻上的分压就越大。
这时,如果有人误触变压器接地线或中性线以及变压器外壳,人体将和接地电阻形成并联,那么加在人体上的电压就会导致人身触电。
(2)当变压器三相四线中的中性线接地电阻阻值过大或中性线断线时,此时由于三相负载的不平衡,变压器中性点将发生偏移,接地点电位不为零,使得有的相电压升高而烧毁用电设备。
(3)当接地电阻阻值过大,同时变压器批避雷器不能正常对地放电,致使避雷器或变压器烧毁。
2、变压器接地电阻阻值过大的原因(1)接地装置的材料不合格。
由于接地体埋设不规范,安装工艺不合格,接地体与接地线接头连接松动,大地过于干燥等原因,均有可能造成接地电阻阻值过大。
(2)由于对变压器接地线作用的重要性认识不足,中性线截面积选择过小,或由于外力的破坏、接地线被盗等原因,都有可能导致接地线断线或接地电阻阻值过大。
3、预防措施(1)严格施工工艺,规范接地体的埋设。
接地装置一般由钢管、角钢、扁钢及钢绞线等材料制成。
埋设深度应不小于~。
接地装置的施工一般应和基础施工同时进行,具体要求如下。
①接地槽的深度应符合设计要求,一般为~,可耕地应敷设在耕作深度以下。
接地槽的宽度一般为~,并应清除槽中一切影响接地体与土壤接触的杂物。
②钢管的规格及打入土壤中的深度应符合设计要求,接地体应垂直打入地中且固定,以免增加街道电阻阻值。
在山区及土壤电阻率较高的地区,尽量少用管形接地装置,而采用表面埋入方式的接地装置。
③接地引下线应沿电杆敷设引下,并尽可能短而且直,以减少其冲击电抗。
接地引下线以支持件固定在杆塔上,支持件之间的直线距离通常为~,转弯部分为。
④接地引下线除为测量接地电阻阻值而预留的断开处外不得另有接头,接地装置的连接应保证接触间的连接,均采用焊接。
接地引下线与为测量接地电阻阻值而预留的断开处连接均应采用螺栓连接,连接螺栓应镀锌防锈。
⑤接地体敷设完毕,应回填土,不得将石块等影响接地体与土壤接触的杂物埋入。
(2)在变压器的中性线上选取适当的位置,将变压器的中性线多点重复接地。
这样当变压器中性线在某点断线时,由于多点接地,中性线电流仍可经大地回到变压器中性点,中性线的电位始终为零,每相负载的电压始终为正常的相电压。
(3)在用户电能表后装设剩余电流动作保护器。
当用户装设了保护器后,此时如果变压器接地点接地电阻阻值过大,大地电位将不再为零,这时将有一个电流经保护器、大地流入变压器接地点,此电流将使保护器动作而将接地点切除,防止了大地电位的升高。
另外,加装保护器后,当人接触相线时,保护器也会动作,从而保障人身安全。
《美国国家电气法规》NEC第100节对“接地”一词定义如下:电气回路或设备与大地,或与代替大地的导体之间的导电的连接,可以是有意的连接,也可以是无意的连接。
在配电回路或分支回路里,所有的回路和设备都通过导电连接来互相连通,从而减少它们之间的电位差,或将电位差限制到最小值。
在上述定义里,术语“地”是个关键。
接地的主要目的就是保证电气安全。
在电击防护和为接地故障电流提供返回电源通路方面接地是很重要的。
这两个问题都可将回路和地之间加以连接来解决。
通常将一接地棒打入地内就算与大地相连接了。
对于一个建筑物的配电系统,可在靠近电源进线处打一接地棒来接地。
将回路导线与地连接(Ground)或将设备接地(Grounding)可起到如下作用:(1) 提供设备与近处金属物体间的低阻抗连接,以减少人身电击危险;(2) 给接地故障电流提供返回电源的低阻抗通路,使熔断器或断路器得以动作;(3) 给雷电感应电流提供低阻抗的对地泄放通路;(4) 给静电电荷提供对地泄放通路,以防产生电火花或电弧。
变电站的接地装置是接地体(埋入地中并与大地直接接触的一组金属导体)和接地引下线(电气设备接地部分与接地体连接的金属导体)的总称。
其作用是通过降低接地电阻,加速接地电流的扩散,减少地电位的升高。
接地装置长期处在地下或阴暗、潮湿的环境中,则最容易发生腐蚀。
由于接地装置的腐蚀会极大的影响装置的使用寿命,造成接地网局部断裂,接地线与接地网脱离,形成严重的接地隐患或构成事故,因此要加强运行维护和巡视检查,及时进行缺陷处理,定期进行接地电阻和回路电阻测量,以保证接地一直处于良好的状态。
一、接地装置的正常巡视检查项目由于变电站接地装置的特殊性,主要从以下几个方面进行检查:(1)设备的接地引下线有无损伤、断裂、锈蚀,连接处是否接触良好。
(2)接地网与接地引下线连接线夹或螺栓是否完好、牢固。
(3)接地网的接地圆钢、扁钢有无露出、被盗、浅埋等现象。
(4)接地装置在引入建筑物的入口处要有明显的标志,明敷的接地引下线表面的涂漆标志是否完好。
(5)用导通法定期检查接地引下线的通断情况。
(6)定期测试接地电阻值是否合格,并分析所测量的接地电阻变化情况,是否符合规程要求。
(7)对含有重酸、碱、盐或金属矿研等化学成分的土壤地带,定期对接地装置的地下部分挖开地面进行检查,观察接地体腐蚀情况。
(8)设备每次检查后,应检查其接地是否牢固。
二、接地装置的定期维护及试验项目在运行期间,对接地装置的连接情况检查和接地电阻的测量,主要按下列周期进行:(1)连接情况检查至少每一年一次。
(2)接地电阻的测量至少每五年一次。
(3)必要时,选点挖土检查接地体和接地线连接是否完好。
(4)接地装置设记录本,将检查结果载入备查。
(5)当进行设备扩建时和根据当地雷击率,应重新评估接地引下线截面的过流容量。
(6)各防雷装置的接地线每年(雷雨季节前)检查一次。
三、接地装置经长周期运行后,普遍存在的问题。
有些接地装置在投运初期是合格的,但经一定的运行周期后,接地电阻就会变大,以下一些问题值得注意:一是由于接地体的腐蚀,使接地体与周围土壤的接触电阻变大,特别足在山区酸性土壤中,接地体的腐蚀速度相当快,会造成一部分接地体脱离接地装置;二是在接地引下线与接地装置的连接部分因锈蚀而使电阻变大或形成开路;三是接地引下线接地极受外力破坏时误损坏等。
四、接地装置的接地电阻不合格,会造成的危害。
接地装置起着工作接地和保护接地的作用,《电力设备接地设计技术规程》(SDJ8—79)中对接地电阻值有具体的规定,一般不大于Ω,如果接地电阻过大,则:(1)发生接地故障时,使中性点电压偏移增大,可能使健全相和中性点电压过高,超过绝缘要求的水平而造成设备损坏。
(2)在雷击或雷电波袭击时,由于电流很大,会产生很高的残压,使附近的设备遭受到反击的威胁,并降低接地装置本身保护设备(变电站电气设备)带电导体的耐类水平,使设备达不到设计的要求而损坏。
总之,变电站的接地装置,对于整个电网安全运行起着非常重要的作用,它能提高电力系统安全运行的可靠性,因此,要加强接地装置的运行维护和定期试验,以保证它健康运行。
变电所防雷接地电阻允许值的分析计算变电所防雷接地电阻不能满足对地电位允许电阻值的要求,满足接地电势、跨步电势和暂态电压允许电阻值的要求。
对于变电站,周围没有低土壤电阻率地区或水源,不具备采取引外接地措施降低接地电阻的条件;采用人工降阻、电解接地、爆破接地等其他降阻费用很大且影响变电站的正常运行,有必要对地电位接地电阻允许值进行分析计算,合理选择确定接地电阻允许值。
接地装置的对地电位,是指发生接地故障时,接地装置与大地零电位之间的电位差。
对地电位要求R≤2000/I,规定对地电位为2000V,对于大部分110~500KV变电所,入地短路电流很大,要求接地电阻很小。
对接地电阻大于对地电位要求值时,接地装置的对地电位超过2000V,例如某站接地电阻允许值为欧姆,对地电位达到55800×=5306V,因此,有必要分析对地电位升高对人体和设备的影响。
1)对设备的影响:当接地网采用均压措施后,所区各处的地电位基本相同,在共用接地系统中,所以设备均以接地装置的电位作为等电位。
当接地装置对地电位升高时,在设备接地线良好的情况下,设备的零电位和设备外壳的电位随之升高。
采取均压措施,通过共用接地系统,可以防止地电位升高对低压设备绝缘的危害影响。
2)对人体的影响:虽然接地网采取均压措施可以使得所区各处的对地电位基本相同,但是接地网并非密实的金属板,均压带直接以及接地网边缘仍然存在电位差,因此接地电阻需要满足接触电势和跨步电势的规定要求。
3)对电缆的影响:采取沿电缆沟两侧敷设接地线的屏蔽措施,可以限制电缆绝缘层的感应电流和电位。
根据国内实验测量结果,当接地网网格为10×12m时,网格内最大电位梯度为m,对于一点接地的控制电缆,其绝缘水平为3500V时允许敷设长度可达450M以上。
采取均压措施,通过减小均压带间距限制接地网电位梯度,可以防止电位升高对电缆绝缘的危害影响。
4)对雷击的分析:事实上,雷击电流对低压设备的危害远大于短路电流,这是因为雷击次数较多和雷击电流较大,雷击时的对地电位远大于短路时的对地电位。
然而,国内接地技术表对对防雷接地并未要求很低的接地电阻,一般要求1~10欧姆以内,注意通过采取防护措施防止雷击危害。
例如设置放电管限压防止高电位通过电缆进入低压设备,设置均压接地系统减少设备之间的电位差和防止跨步电势危害,要求避雷针与建筑物和设备保持足够距离等。
通过短路电流与雷击电流的比较分析可知,降低接地电阻并非保证接地安全的根本措施,应该积极采取防护措施和加强运行维护才能保证接地安全。
5)对分流分析:流经变电所接地网的入地短路电流,不等于接地短路点的全部短路电流。
当接地短路发生在接地网内时,一部分短路电流与接地网连接的架空线的“地线杆塔”接地系统分流;另一部分短路电流,经由接地网直接流回变电所变压器接地的中性点;剩下的一部分短路电流,才经过接地网入地中,经大地流回系统变压器接地中性点。
最后的这部分电流,称为计算用的流经接地装置的入接短路电流。
例如,某站最大单相接地短路电流发生在110KA母线侧为,经主变中性点和线路避雷线分流后,最大入地短路电流为。
如果不考虑分流,某站对地电位要求的接地电阻值为R≤2000/10830=欧姆,对这样小的接地电阻,不仅与理论和实践不相符合,而且在技术上难以实现。
6)加强防护措施:为了防止设备接地引线烧断产生高电位对低压设备构成危害,设备应采取两根接地引线并适当增加截面。