智能电表计量箱
智能电表计量箱智能电表计量箱E2型计量箱技术规范二○一一年五月四日智能电能表的计量箱技术规范1.1本技术规范适用于(以下简称“公司”)城、农网户外单相计量箱它包括技术指标、机械性能、适应环境、功能要求、电气性能、抗干扰及可靠性等方面的技术要求。
1.2 本技术规范主要的技术依据为以下规范,生产产品应满足下述规GB 4208-1993 《外壳防护等级的分类》 GB 132-1996 《材料产烟毒性分级》GB 7251.1-97 《低压成套开关设备和控制设备》GB 7251.3-97 对非专业人员可进入场地的低压成套开关设备和控制设备-配电板的特殊要求GB 7251.5-1998 《低压成套开关设备和控制设备》第五部分:对户外公共场所的成套设备--动力配电网用电缆分线箱(CDCs )的特殊要求GB 7251.3-1997《低压成套装置》GBJ63-1990 《电力装置的电测量仪表装置设计规范》 GB191-1990 《包装储运图示标志》 GB /T-16934 《电能计量柜》GB50254 《电气安装工程低压电器施工及验收规范》 GB191 《包装储运图示标志》GB/T 23641-20 《电气用纤维增强不饱和聚酯模塑料(SMC/BMC)》 GB/T 22470-2021 《电气用环保型模塑料通用要求》 GB2681 《电工成套装置中的导线颜色》 GB2682 《电工成套装置中的指示灯和按钮颜色》 GB7251 《低压成套开关设备》GB1048-89 《固体绝缘材料工频电气强度的试验方法》 GB50054-95 《低压配电设计规范》GB1408.2 《低压断路器》 IEC255-21-1 《振动试验标准》 IEC255-21-1 《冲击和碰撞实验标准》 DL447-91 《电能计量柜》DL/T448-2000 《电能计量装置技术管理规范》 Q/GDW 347-2021 《电能计量装置通用设计规范》 Q/GDW 355-2021 《单相智能计量箱型式规范》 JB/T 2930-1991 《低压电器产品型号编制办法》JB5777.2-1991 《电力系统二次电路用控制及机电保护屏(柜、台)通用技术条件》JB5777.3-1991 《电力系统二次电路用控制及机电保护屏(柜、台)基本技术条件》JB/T2930-1991 《低压电器产品型号编制办法》2 计量箱材质及基本参数2.1材质与工艺2.1.1计量箱材质为SMC (不饱和聚酯玻璃纤维增强型片状模塑料)SMC 片材由上下二层薄膜夹芯片材,中玻纤含量为25%,玻纤为均匀1英寸(25.4mm )长度。
电能计量柜基本试验方法
DL/T 549—94
中华人民共和国电力工业部 1994-06-15 批准
1994-11-01 实施
1 总则 1.1 适用范围
本标准适用于交流频率为 50Hz、额定电压为 0.38~35kV、额定电流为 20~1000A 的户 内金属封闭整体式电能计量柜。对分体式电能计量柜和其他类型的电能计量用金属封闭设备 可参照执行。 1.2 主要目的
的能力以及耐受其额定绝缘水平的电压值,并应满足下列全部要求。
a.试验中不应发生拒合、拒分以及影响电能计量柜正常运行的异常现象和故 障。
b.固定式电能计量柜的回路电阻应满足本标准第 4 条的要求。移开式电能计量柜机械寿
命试验前、后应测量手车与骨架之间的接触电阻,其值应不大于 1000μΩ;测量位置为工
插入各 25 次,其操作应良好。
6.1.2 连锁:连锁装置处于防止断路器、隔离开关操动和防止手车抽出、插入的闭锁位置,
对断路器、隔离开关进行 50 次试操作,对手车进行 25 次抽出和 25 次插入的试操作。如能
满足下列条件,则认为连锁是可靠的:
a.断路器、隔离开关不能被操作。
b.手车的抽出与插入被阻止。
c.机械寿命试验前所做的机械操作试验,若试验后未经调整,其次数可计入机械寿命试
验次数中。
6.2.3 试验中的规定:试验中只允许按技术文件的规定进行润滑,不允许作机械调整或进行
其他方式的维护。若不符合标准要求进行调整,则调整后应重新进行试 验。
6.2.4 试验判据:试验中及试验后,试品应能正常地操作,具有承载其额定电流、短路电流
制订本标准的主要目的在于规定电能计量柜基本试验方法和检验标准,应包括下列内 容:
电能计量柜检验规范
中能电气股份电能计量柜检验规编号:ZTJ-B-002-02 REV.a1、主题容与适用围本规适用于交流50Hz、额定电压(0.38-35)kV、额定电流(20~1000)A与电力用户供电线路配合使用的金属封闭式高、低压电能计量柜的产品出厂检验项目、检验方法、检验规则。
2、产品检验原则电能计量柜出厂检验采取全检方式。
3、参考标准GB 17201-1997(eqv. IEC 44-3:1980) 组合互感器GB 1207-2006(eqv. IEC 186:1987) 电压互感器GB 1208-2006 (eqv. IEC 185:1987) 电流互感器GB/T 16934-1997 电能计量柜GB/T 12706.4-2002 额定电压1kV到35kV挤包绝缘电力(eqv. IEC 60502-4:1997) 电缆及其附件第四部分GB 311.6-1983 高电压试验技术GB/T 7354-1987 局部放电测量GB 4208-1993 外壳防护等级(IP代码)DL/T 448-2000 电能计量装置技术管理规程DL/T 825-2002 电能计量装置安装接线规则GB/T 5582-1993 高电压设备外绝缘的污秽等级闽电营[2003]634号省电力电能计量柜技术条件4、检验项目4.1 一般检查4.1.1柜体检查4.1.1.1 外型尺寸和安装尺寸符合图纸要求,柜体的高、深、宽尺寸的偏差不应超过±5mm;前后、左右侧面、底面对角线尺寸偏差的绝对值不应超过5mm。
4.1.1.2 计量柜箱体外壳表面防腐处理,烘户外烤漆,且箱体表面涂层平整均匀应无流挂、裂纹、起泡、脱落、划伤及无坍塌、变形等现象,柜门、面板的凹凸度,在每1000mm 围不应超过3mm且相邻两个平行边尺寸的偏差绝对值不应超过3mm。
吊攀焊接牢固。
4.1.1.3 门框架结构为嵌入式,仪表室和互感器室必须配备带铅封孔的专用门锁。
户计量柜每扇门应分别设有两对铅封柱或铅封眼。
DLT549-94电能计量柜基本试验方法(doc 13页)
DLT549-94电能计量柜基本试验方法(doc 13页)中华人民共和国电力行业标准DL/T 549—94 电能计量柜基本试验方法中华人民共和国电力工业部1994-06-15批准1994-11-01实施1 总则1.1 适用范围本标准适用于交流频率为50Hz、额定电压为0.38~35kV、额定电流为20 ~1000A 的户内金属封闭整体式电能计量柜。
对分体式电能计量柜和其他类型的电能计量用金属封闭设备可参照执行。
1.2 主要目的制订本标准的主要目的在于规定电能计量柜基本试验方法和检验标准,应包括下列内容:a.一般检查试验。
b.主回路电阻测量。
c.温升试验。
GB 763交流高压电器在长期工作时的发热GB 3309高压开关设备常温下的机械试验GB 2706交流高压电器动热稳定试验方法GB 1207电压互感器GB 1208电流互感器GB 11022高压开关设备通用技术条件 DL 447电能计量柜JB 616电力系统二次电路用屏(台)通用技术条件SD 109电能计量装置检验规程2 名词术语2.1 基本试验方法在规定的工作条件下进行具有通用性的试验方法,不包括装置的某些专门和特定试验。
2.2 环境温度在规定条件下测定的围绕整个电能计量柜壳外的平均温度。
2.3 主回路电能计量柜中,用来传送电能的回路内的所有导电部分。
注:电压互感器的连线不属于主回路。
2.4 计量回路在电能计量柜中,用以完成电能计量功能的回路内的导电部分。
2.5 辅助回路在电能计量柜中,所有监控、信号、防误、调试检查回路内的导电部分。
2.6 破坏性放电在电场作用下绝缘损坏而引起的放电。
此时,放电跨接绝缘介质,使电极之间的电压降到零或接近于零。
注:破坏性放电使固体介质永远丧失绝缘强度(非自恢复绝缘),而在气体介质中绝缘强度的丧失仅是暂时的(自恢复绝缘)。
2.7 短时耐受电流在规定的试验条件下,主电路在规定的时间内能够耐受的电流有效值。
2.8 峰值耐受电流在规定的试验条件下,主电路能够耐受的峰值电流值。
电测计量监督标准规程目录(2016)
电测、计量监督标准规程目录(2016)1.《中华人民共和国计量法》2.《中华人民共和国计量法实施细则》3.《中华人民共和国电力法》4.水利、电力部门电测、热工计量仪表和装置检定、管理的规定(国务院国函[1986]59号)5.《计量标准考核办法》(2005年1月14日国家质量监督检验检疫总局令第72号发布)6.《计量检定人员管理办法》(2007年12月29日国家质量监督检验检疫总局令第105号发布)7.四川省电力公司技术监督条例(试行版)8.国家电网公司电测监督条例9.JJF 1001-2011 通用计量术语及定义10.JJF 1033-2008 计量标准考核规范11.JJF 1059-1999 测量不确定度评定与表示12.JJF 1094-2002 测量仪器特性评定13.JJF 1022-2014 计量标准命名规范14.JJF 1075-2001 钳形电流表校准规范15.JJG 01-1994 电测量变送器检定规程16.JJG 124-2005 电流表、电压表、功率表及电阻表检定规程17.JJG 126-1995 交流电量变换为直流电量电工测量变送器检定规程18.JJG 307-2006 机电式交流电能表19.JJG 366-2004 接地电阻表检定规程20.JJG 596-2012 电子式电能表检定规程21.JJG 597-2005 交流电能表检定装置检定规程22.JJG 622-1997 绝缘电阻表(兆欧表)检定规程23.JJG 1005-2005 电子式绝缘电阻表检定规程24.JJG 1021-2007 电力互感器检定规程25.JJG 724-1991 直流数字式欧姆表检定规程26.JJG 982-2003 直流电阻箱27.JJG 569-2014 最大需量电能表(电度表)试行检定规程28.JJG 691-2014 分时计度(多费率)电能表检定规程29.JJG 314-2010 测量用电压互感器检定规程30.JJG 313-2010 测量用电流互感器检定规程31.JJG 1036-2008 交流电能表检定装置试验规范32.JJG 125-2004 直流电桥检定规程33.JJG 440-1986 工频单相相位表检定规程34.JJG 603-2006 频率表35.JJG 315-1983 直流数字电压表试行检定规程36.JJG 598-1989 直流数字电流表试行检定规程37.JJG 1001-1998 通用计量术语及定义38.JJG 780-1992 交流数字功率表检定规程39.JJG 690-2003 高绝缘电阻测量仪(高阻计)40.JJG 531-2003 直流电阻分压箱41.JJG 505-2004 直流比较电位差计42.JJG 494-2005 高压静电电压表43.JJG 166-1993 直流电阻器检定装置44.JJG 1027-1991 测量误差及数据处理45.GB 1208-2006 电流互感器46.GB 1207-2006 电磁式电压互感器47.GB 17215-2008 0.2S级和0.5S级静止式交流有功电能表48.GB 17442-1998 1级和2级直接接入或交流有功电度表验收检验49.GB 15282-1994 无功电能表50.GB 15283-1994 0.5、1和2级交流有功电度表51.GB 4703-2001 电容式电压互感器52.GB 17201-2007 组合互感器53.GB 17215-2008 1级和2级静止式交流有功电度表54.GB 17882-1999 2级和3级静止式交流有功电度表55.GB 16934-2013 电能计量柜56.GB 50063-2008 电力装置的电测量仪表装置设计规范57.GB 8170-2008 数值修约规则58.DL/T 410-1991 电工测量变送器运行管理规程59.DL/T 447-1991 电能计量柜60.DL/T 448-2000 电能计量装置技术管理规程61.DL/T 460-2005 交流电能表检验装置检定规程62.DL/T 549-1994 电能计量柜基本试验方法63.DL/T 566-1995 电压失压计时器技术条件64.DL/T 585-1995 电子式电能表技术条件65.DL/T 606-1996 火力发电厂能量平衡导则66.DL 614-2007 多功能电能表67.DL/T 630-1997 交流采样远动终端技术条件68.DL/T 645-2007 多功能电能表通信协议69.DL/T 686-1999 电力网电能损耗计算导则70.DL/T 698-1999 低压电力用户集抄系统技术条件71.DL/T 731-2000 电能表测量用误差计算器72.DL/T 732-2000 电能表测量用光电采样器73.DL/T 725-2013 电力用电流互感器使用技术规范74.DL/T 726-2013 电力用电磁式电压互感器使用技术规范75.DL/T 825-2002 电能计量装置安装接线规则76.DL/T 829-2002 单相感应式交流有功电能表使用导则77.DL/T 830-2002 静止式单相交流有功电能表使用导则78.DL/T 838-2003 发电企业设备检修导则79.DL/T 866-2004 电流互感器和电压互器选择及计算导则80.DL/T 973-2005 数字高压表检定规程81.DL/T 979-2005 直流高压高阻箱检定规程82.DL/T 980-2005 数字多用表检定规程83.DL/T 1051-2007 电力技术监督导则84.DL/T 1066-2007 水电站设备检修管理导则85.DL/T 1075-2007 数字式保护测控装置通用技术条件86.DL/T 1112-2009 直流仪表检验装置检定规程87.DL/T 1199-2013 电测技术监督规程88.DL/T 5043-1995 火力发电厂电气试验室设计标准89.DL/T 5136-2012 火力发电厂、变电所二次接线设计技术规程90.DL/T 5137-2001 电测量及电能计量装置设计技术规程91.DLT 5413-2009 水力发电厂测量装置配置设计规范92.国家电网营销[2005]347号《交流采样测量装置校验规范》及《交流采样测量装置校验作业指导书》更新规程:1、JJF 1001-2011 通用计量术语及定义(JJF 1001-1998)2、JJF 1022-2014 计量标准命名规范(JJF 1022-1991)3、JJG 596-2012 电子式电能表检定规程(JG 596-1999)4、JJG 314-2010 测量用电压互感器检定规程(JJG 314-1994)5、JJG 313-2010 测量用电流互感器检定规程(JJG 313-1994)6、JJG 1036-2008 交流电能表检定装置试验规范(JJG 1036-1993)7、GB 16934-2013 电能计量柜(GB/T 16934-1997)8、GB 8170-2008 数值修约规则(GB 8170-1987)9、DL 614-2007 多功能电能表(DLT 614-1997)10、DL/T 645-2007 多功能电能表通信协议(DLT 645-1997)11、DL/T 725-2013 电力用电流互感器使用技术规范(DL/T 725-2000)12、DL/T 726-2013 电力用电磁式电压互感器使用技术规范(DL/T 726-2000)13、DL/T 5136-2012 火力发电厂、变电所二次接线设计技术规程(DL/T 5136-2001)新增加规程:1、DL/T 866-2004 电流互感器和电压互器选择及计算导则2、DL/T 1199-2013 电测技术监督规程3、DLT 5413-2009 水力发电厂测量装置配置设计规范。
电能计量装置现场检验 154页PPT
A
B
C
图5-4-5 电流互感器不完全星形接法几种可能接线图 (a)A、B相电流
A B
C
图5-4-5 电流互感器不完全星形接法几种可能接线图 (b)B、C相电流
A
B
C
图5-4-5 电流互感器不完全星形接法几种可能接线图 (c)极性端接地(A、B相电流)
2.电压交叉法
如其他条件均同上法,仅负载不够稳定,可用 “电压交叉法”检查接线。为此,将与电能表的电 压端钮A和C连接的两根电压线互换位置(其实任何 两根电压线互换位置都可以),电能表如不转动或 向其一侧微动,就能肯定电能表原来的接线是正确 的。因为把电压线交叉以后,没有误接的电能表所 测定的功率为零,即
功和无功电能表不一定都正转或反转。例如在联络 线路内或同步电动机过励磁运行时,就容易发生两 者转向不一致的情况。
当无功表接线端子电源侧为正相序而负载为容 性,或电源侧为逆相序而负载为感性时,常用的无 功电能表都会反转,现以附加电流线圈型及内相角 60°型无功电能表为例来说明。
根据图5-4-2(a)、(b)所示相量图,附加电流 线圈型无功电能表在上述两种情况下所测得无功功 率都是负值。
如不能判断电压线圈公共端是否B相或有无B相
电流通过电流线圈,则不能应用以上两法。因为只 要电压对称,接入表内两相电流相等且相位互差 120°,则原来转动的电能表在A、C相电压线互换后 均会停转。此时用“B相电压法”检查,断B相电压 后转向均与原转向一致,转速均较原转速慢一半。
此外,若接线正确,而负载不平衡时,如三相 三线电能表测量单相负载(如冶炼感应炉用电等), 设负载接在B、C相,此时电能表计量的电量是正常 的。但将A、C相电压线对调后,电能表仍将顺转, 且有可能转得比原接法快(当cosφ <0.866时)。当然 “B相电压法”也不适用,故应用上述两法前一定要 确认使用条件是否符合。
国网电能计量装置现场检验作业指导书
电能计量装置现场检验作业指导书国家电网公司生产运营部目录一、总则 ·········································································1. 适应范围······································································2. 引用的标准和规程··························································3. 名词和术语···································································二、安全工作的一般要求 ····················································1. 基本要求······································································2. 保证安全的组织措施·······················································三、电能表现场实负荷(在线)检验 ·····································1. 安全工作要求································································2. 检验项目······································································3. 检验条件······································································4. 检验方法······································································5. 检验结果的处理·····························································四、计量用互感器现场测试前的准备工作 ·······························1. 现场测试工作的注意事项·················································2. 现场测试工作的技术要求(措施)·····································五、计量用电流互感器现场测试 ···········································1. 安全工作要求································································2. 测试项目······································································3. 测试用设备和供电电源····················································4. 测试方法······································································5. 测试结果的处理·····························································六、计量用电压互感器现场测试 ···········································1. 安全工作要求································································2. 测试项目································································3. 测试用设备···································································4. 使用标准电压互感器的检验方法········································5. 使用电容式电压比例标准器的检验方法·······························6. 电压互感器实际二次负荷的测量········································7. 测量数据处理································································七、电压互感器二次回路压降测试 ········································1. 安全工作要求································································2. 测试用设备···································································3. 测试方法······································································4. 测试结果处理································································附录A 电能计量装置现场检测原始记录格式··························附录B 电能计量装置合成误差的计算···································附录C 电压互感器的负荷误差换算······································前言本作业指导书主要针对电网关口和大的电力用户的电能计量装置,包括电能表、计量用电流、电压互感器以及电压互感器二次回路压降的现场检验的方法、操作程序和安全要求予以科学合理的规范。
DLT540-1994气体继电器检验规程(doc 8页)
DLT540-1994气体继电器检验规程(doc 8页)中华人民共和国电力行业标准DL/T 540—94805025-QJ 型气体继电器检验规程中华人民共和国电力工业部1994-04-11批准1994-10-01实施1 主题内容与适用范围本标准规定了气体继电器的机械性能、动作可靠性、主要特性、整组保护的检验和试验要求及方法等内容。
本标准适用于QJ-25、50、80型气体继电器(以下简称继电器),作为现场安装和运行中对继电器进行检验的规则和依据。
2 继电器结构与外观检查2.1 继电器壳体、玻璃窗、出线端子、探针和波纹管等应完好。
2.2 继电器内部零件应完好,各螺丝应有弹簧垫并拧紧,固定支架牢固可靠,各焊缝处应焊接良好无漏焊。
2.3 放气阀、探针操作应灵活,探针头与挡板挡舌间保持1.5~2.5mm 的间隙。
2.4 开口杯转动应灵活,轴向活动范围为0.3~0.5mm ,开口杯转动过程中与出线端子最近距离不小于3mm 。
2.5 干簧触点固定牢固,玻璃管应完好,根部引出线焊接可靠,引出硬柱不能弯曲并套软塑料管排列固定,永久磁铁在框架内固定牢固。
2.6弹簧与调节螺杆连接平稳可靠,并与挡板静止位置垂直。
2.7挡板转动应灵活,轴向活动范围为0.3~0.5mm。
干簧触点可动片面向永久磁铁并保持平行,尽可能调整两个触点同时断合。
2.8开口杯的干簧触点应接在动作于“信号”的出线端子上,挡板的两个干簧触点应串接在动作于“跳闸”的回路中。
检查接线盒漏水孔是否畅通。
3继电器动作可靠性检查3.1检查动作于跳闸的干簧触点动作可靠性转动挡板至干簧触点刚开始动作处,永久磁铁面距干簧触点玻璃管面的间隙应保持在 2.5~4.0mm范围内。
继续转动挡板到终止位置,干簧触点应可靠吸合,并保持其间隙在0.5~1.0mm范围内,否则应进行调整。
3.2检查动作于信号的干簧触点动作可靠性转动开口杯,自干簧触点刚开始动作处至动作终止位置,干簧触点应可靠吸合,并保持其滑行距离不小于1.5mm,否则应进行调整。
电能计量装置的现场检查方法
e) 对于非中性点绝缘系统的电压互感器,应采用Y0/y0的连接方式。对于中性点绝缘系统的电压互感器,35kV与以上的应采用Y/y的连接方式;35kV以下的 宜采用V/V的连接方式。
f) 贸易结算用的计量点设置在统调上网电厂侧的,在出线侧与主变高压侧均应安装计量装置。
γ=(t0-t)/t×100% (2)
其中γ为电表误差,为电表转n0圈秒表实测时间
2.4 用电能表现场校验仪检验电表误差。用现场校验仪可以直观的测出电能表的各相电压、电流、功率、误差。更重要的可以通过向量图判断电表的接线是否正确。当发现电能表误差较大时,应将其拆回校验。
4 三相三线表的检查
4.1 测量线电压法:三相三线表一般都是安装在高压计量箱中使用,属于高供高计方式,高压计量箱的电压线圈最易受雷击开路,所以测量电能表的电压显得十分重要。用万用表测电能表各电压端钮间的线电压,正常时Uab=Ubc=Uca=100V,如果测出的结果是Uab=0,Ubc=Uca=100V,则说明A相电压断开,Uab=Ubc=50V,Uca=100V,则说明B相电压断开,Uab= Uca=100V, Ubc=0,则说明C相电压断开。失压的原因可能是电压线圈损坏或电压回路接触不好等。
4.4.1确定电压相序和相别
为了确定各相电压与电流的相位的关系,在测得电压正确结果后,与进行电表电压端子排电压相序测量,用相序表测定三相电压相序,根据测得的相序和找出的B相电压,确定其余两个电压端钮连接的电压线所属相别。
4.4.2 画出向量图
把两只单相标准表电流线圈分别与被测表的两个电流线圈串联电压对应并联,读取标准表数据Pa-ab、Pc-bc,接着将接到两只标准表的电压线互换位置,读取数据Pa-bc、Pc-ab,最后两只标准表都加电压Uca读取Pa-ca、Pc-ca,若某只标准表反转,应将连接的两根电压线互换位置,使其正转,但读数要记为负值。验算应满足:Pa-ab+Pa-bc+Pa-ca≈0, Pc-ab+Pc-bc+Pc-ca≈0, Pa-ab,Pa-bc,Pa-ca, Pc-ab,Pc-bc,Pc-ca可看作是Ia、Ic在Uab 、Ubc、Uca上的投影,因此可根据a-ab,Pa-bc,Pa-ca, Pc-ab,Pc-bc,Pc-ca用一样的比例画出Ia、Ic在Uab 、Ubc、Uca上的投影,如Pa-ab为正值,则在Uab上截取,如Pa-ab为负值,则在Uba上截取,由各投影末端引垂线所得交点与原点O的连线,就确定了A相电流的相位和相对值。用同样的方法可画出C相电流,如下图:
DLT549-94电能计量柜基本试验方法
DLT 549-94 电能计量柜基本试验方法DL/T 549—94电能计量柜基本试验方法中华人民共和国电力工业部1994-06-15批准1994-11-01实施1 总则1.1 适用范围本标准适用于交流频率为50Hz、额定电压为0.38~35kV、额定电流为20 ~1000A的户内金属封闭整体式电能计量柜。
对分体式电能计量柜和其他类型的电能计量用金属封闭设备可参照执行。
1.2 主要目的制订本标准的主要目的在于规定电能计量柜基本试验方法和检验标准,应包括下列内容:a.一般检查试验。
b.主回路电阻测量。
c.温升试验。
d.机械试验。
e.保护电路有效性试验。
f.电气距离的测量。
g.绝缘电阻测量和绝缘耐受试验。
h.短时耐受电流和峰值耐受电流试验。
i.计量单元准确度试验。
j.操作震动试验。
k.局部放电试验。
1.3 与其他标准的关系1.3.1 本标准是DL447《电能计量柜》规定试验项目的基本试验方法和检验标准。
电能计量柜的试验除应符合本标准所规定的试验方法和检验标准外,还应符合DL 447中的其他规定。
1.3.2 引用标准GB 3906 3~35kV交流金属封闭开关设备GB 7251低压成套开关设备GB 9466低压成套开关设备基本试验方法GB 311.1高压输变电设备的绝缘配合GB 311.2~311.4高电压试验技术GB 763交流高压电器在长期工作时的发热GB 3309高压开关设备常温下的机械试验GB 2706交流高压电器动热稳定试验方法GB 1207电压互感器GB 1208电流互感器GB 11022高压开关设备通用技术条件DL 447电能计量柜JB 616电力系统二次电路用屏(台)通用技术条件SD 109电能计量装置检验规程2 名词术语2.1 基本试验方法在规定的工作条件下进行具有通用性的试验方法,不包括装置的某些专门和特定试验。
2.2 环境温度在规定条件下测定的围绕整个电能计量柜壳外的平均温度。
2.3 主回路电能计量柜中,用来传送电能的回路内的所有导电部分。
电能计量装置检验规程
电能计量装置检验规程SD 109—1983中华人民共和国水利电力部关于颁发《电能计量装置检验规程》等四种规程的通知(83)水电技字第94号我部1962年颁发的《电气测量仪表检验规程(试行)》,已委托西北电管局电力试验研究所等单位进行了修订。
根据各方面的意见,现将原规程分订成《电能计量装置检验规程》和《电测量指示仪表检验规程》两本规程,并委托华北电管局电力试验研究所和华东电管局电力试验研究所等单位编写了《交流仪表检验装置检定方法》和《直流仪表检验装置检定方法》两本规程。
经过两年来的试验、验证和讨论修改,现正式颁发,其名称及编号如下:1.电能计量装置检验规程SD109—19832.电测量指示仪表检验规程SD110—19833.交流仪表检验装置检定方法SD111—19834.直流仪表检验装置检定方法SD112—1983以上规程从1984年7月1日开始执行。
在执行中,如遇到问题,可随时函告我部。
自执行之日起,原水利电力部1962年颁发的《电气测量仪表检验规程(试行)》作废。
1983年12月31日目次1 电能计量装置的分类办法和检验周期1.1 分类办法1.2 检验周期2 电能表的检验项目3 电能表的技术要求及检验方法3.1 直观检查3.2 绝缘强度试验3.3 起动试验3.4 潜动试验3.5 基本误差的测定3.6 需量指示器的试验3.7 走字试验3.8 检验结果的处理4 电能表的现场检验4.1 检验项目4.2 误差测定4.3 接线检查4.4 计量差错与不合理计量方式的检查5 测量用互感器的检验5.1 检验项目及检验设备5.2 一般项目的技术要求及试验方法5.3 误差测定5.4 三相电压互感器的误差测定5.5 电压互感器二次回路电压降引起的误差的测量5.6 检验结果的处理6 电能计量装置的综合误差的计算6.1 互感器合成误差的计算6.2 电压互感器二次回路电压降引起的误差6.3 综合误差的计算附录A(补充件)按原第一机械工业部标准《交流电能表》电(D)28-61生产的(包括1965年以前进口的)电能表,其基本误差和起动电流的规定附录B(补充件)交流电能的典型计量方式本规程适用于电力系统中考核经济技术指标和计收电费的新装及运行中的电能计量装置(包括安装式感应系有功、无功电能表,最大需量表,以及与它们连用的电流、电压互感器及二次回路)和携带型精密电能表的检验。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
中华人民国电力行业标准DL/T 549—94电能计量柜基本试验方法中华人民国电力工业部1994-06-15批准 1994-11-01实施1 总则1.1 适用围本标准适用于交流频率为50Hz、额定电压为0.38~35kV、额定电流为20 ~1000A的户金属封闭整体式电能计量柜。
对分体式电能计量柜和其他类型的电能计量用金属封闭设备可参照执行。
1.2 主要目的制订本标准的主要目的在于规定电能计量柜基本试验方法和检验标准,应包括下列容:a.一般检查试验。
b.主回路电阻测量。
c.温升试验。
d.机械试验。
e.保护电路有效性试验。
f.电气距离的测量。
g.绝缘电阻测量和绝缘耐受试验。
h.短时耐受电流和峰值耐受电流试验。
i.计量单元准确度试验。
j.操作震动试验。
k.局部放电试验。
1.3 与其他标准的关系1.3.1 本标准是DL447《电能计量柜》规定试验项目的基本试验方法和检验标准。
电能计量柜的试验除应符合本标准所规定的试验方法和检验标准外,还应符合 DL 447中的其他规定。
1.3.2 引用标准GB 3906 3~35kV交流金属封闭开关设备GB 7251低压成套开关设备GB 9466低压成套开关设备基本试验方法GB 311.1高压输变电设备的绝缘配合GB 311.2~311.4高电压试验技术GB 763交流高压电器在长期工作时的发热GB 3309高压开关设备常温下的机械试验GB 2706交流高压电器动热稳定试验方法GB 1207电压互感器GB 1208电流互感器GB 11022高压开关设备通用技术条件DL 447电能计量柜616电力系统二次电路用屏(台)通用技术条件SD 109电能计量装置检验规程2 名词术语2.1 基本试验方法在规定的工作条件下进行具有通用性的试验方法,不包括装置的某些专门和特定试验。
2.2 环境温度在规定条件下测定的围绕整个电能计量柜壳外的平均温度。
2.3 主回路电能计量柜中,用来传送电能的回路的所有导电部分。
注:电压互感器的连线不属于主回路。
2.4 计量回路在电能计量柜中,用以完成电能计量功能的回路的导电部分。
2.5 辅助回路在电能计量柜中,所有监控、信号、防误、调试检查回路的导电部分。
2.6 破坏性放电在电场作用下绝缘损坏而引起的放电。
此时,放电跨接绝缘介质,使电极之间的电压降到零或接近于零。
注:破坏性放电使固体介质永远丧失绝缘强度(非自恢复绝缘),而在气体介质中绝缘强度的丧失仅是暂时的(自恢复绝缘)。
2.7 短时耐受电流在规定的试验条件下,主电路在规定的时间能够耐受的电流有效值。
2.8 峰值耐受电流在规定的试验条件下,主电路能够耐受的峰值电流值。
2.9 互感器合成误差互感器的合成误差是与电能表以不同的接线方式连接的电流互感器和电压互感器角差、比差的综合。
2.10 综合误差电能计量装置的综合误差是电能表误差、互感器的合成误差和二次回路压降误差的代数和。
3 一般检查主要检查电能计量柜的外观质量、装配质量,通常用目测、平台和直尺进行检查。
检查结果应符合下列规定。
3.1 柜所安装的电气设备及元器件应是经鉴定的合格品,应具有产品检验合格证;应符合电能计量柜设计、制造工艺和设备明细表的要求。
3.2 距柜体1m处目测,柜体表面的漆膜应均匀平整,不得有明显流痕起缝、透底漆、刷痕、擦伤及明显的机械杂物;焊缝不得有夹渣、焊裂、焊穿现象。
3.3 柜体结构应无松动、无变形;标准紧固件及其他零部件应无松动脱落现象。
3.4 柜体外形尺寸公差与偏差及平面度:柜体高、深尺寸公差为±3mm;宽尺寸公差为+0mm、-3mm;前后、左右侧面和底面对角线绝对差值小于4mm。
门及面板每米围的凸凹不平度不得大于3mm,相邻两平行边间的尺寸差的绝对值不得大于3mm。
3.5 母线:电气一次母线和支持绝缘件应无裂纹锤痕和破损,母线颜色标志及相序排列布置应符合表1的规定。
主电路母线截面应满足主回路载流量短时耐受电流、峰值耐受电流和温升要求。
3.6 计量回路和辅助回路:计量回路和辅助回路应采用单股或多股铜质绝缘导线。
其截面规定为:电压回路不小于2.5mm2;电流回路不小于4.0mm2。
其额定电压不低于500V。
计量回路和辅助回路导线应采用不同颜色的绝缘层:A相,黄色;B相,绿色;C相,红色;零线,黑色;接地线,黄绿混合色。
表 1 电气一次母线颜色标志及相序排列布置注:从电能计量柜正面看。
电路接线应正确无误,导线两端应有回路编号,连接线的捆扎及敷设应符合规定。
3.7 计量柜应有防护措施,供电与用户部分应区分、隔离,柜门锁及铅封装置和防误操作闭锁装置应完备好用。
3.8 电能计量柜观察窗密封性应良好,玻璃采用无色透明材料,厚度不小于4mm。
观察窗的大小应满足监视及抄表的要求。
固定玻璃用的边框,应采用铝合金或有足够强度的工程塑料组成。
4 主回路电阻的测量4.1 对6~35kV电能计量柜,按GB763规定在温升试验前后应分别进行隔离开关、触头和整个主回路电阻测量。
0.38kV电能计量柜可不做主回路电阻测量。
4.2 电阻的测量应采用直流电压降法。
测量应在载流导体温度与周围空气温度相同的条件下进行。
测量电流推荐选用100A。
4.3 温升试验、机械寿命试验前后,测得的电阻的差值不得超过试验初始所测值的20%。
5 温升试验5.1 试验目的通过温升试验验证电能计量柜各部分温升是否符合本标准5.7条的规定。
5.2 电能计量柜的放置电能计量柜应按正常使用情况放置,其外壳、隔板、活门都应装好,试验时应将盖板和门关闭。
电能计量柜应置于不受照射或其他热辐射影响,且无外来气流的房间,试验室空气的流速不应大于0.15m/s,该房间应有一定的空间,至少应按本标准5.6条的规定测定周围空气温度。
5.3 试验电流考虑了额定的分散系数后,应选择一个或几个有代表性的并能获得最高温升的电路。
给这些电路通以三相额定工作电流值,其最大偏差为+2%;电流波形应为正弦波,波形失真度不大于5%;电流频率为50Hz,其允差围为+2%~-5%。
5.4 试验的次数电能计量柜进行寿命试验时,对于有涂、镀触头接触表面裸露的,应在做完机械试验后加做一次温升试验。
5.5 回路导体试验时,电能计量柜两端的连接线不应明显地对其传入或导出热量,连接导体长度应不小于2m。
母线导体规格、材质和尺寸应记入试验报告中。
5.6 测量条件5.6.1 试验应在周围空气温度不低于+10℃及不高于+40℃的情况下进行。
若试验时的周围空气温度低于10℃,则温升读数可用气温每降低1K增加4‰的近似线性关系对试验结果进行修正,但试验不得在0℃以下或+40℃以上周围空气温度下进行。
周围空气温度应在试验周期的最后1/4期间测量,用不少于三支的温度计或热电偶均匀地布置在电能计量柜周围1m远的地方,其布置高度约等于电能计量柜高度的一半。
5.6.2 电能计量柜的发热温度,应采用热电偶进行测量。
温度测量宜在各零件的温度最高或裕度最小的部位进行。
5.6.3 为加速试验,在不影响试验结果和电能计量柜结构强度的情况下,可用大于规定的试验电流将试品进行预热。
预热可进行到全部测试点中任何一点首先达到预期温升的80%左右为止。
5.6.4 电能计量柜在试验电流保持不变的情况下,如各部分的温升在3h以的变化不超过2K,则电能计量柜的温升可认为已稳定。
试验进行到温升稳定时为止。
5.7 试验结果温升稳定后所测值不超过表2规定的数值,在电能计量柜部的温度条件下并在其规定的电压围能正常工作,即认为温升试验通过。
6 机械试验6.1 机械操作试验表 2 温升允许值注:括号中的数值仅用于手柄为绝缘材料的电能计量柜。
机械操作试验是检查电能计量柜在规定操作条件下的操作性能及合闸、分闸、合分操作的可靠性。
试验时,施加正常的操作力,且不允许对断路器、隔离开关、手车及联锁装置进行调整。
6.1.1 断路器、隔离开关及手车:电能计量柜开关应操作50次,移开式柜手车应抽出和插入各25次,其操作应良好。
6.1.2 连锁:连锁装置处于防止断路器、隔离开关操动和防止手车抽出、插入的闭锁位置,对断路器、隔离开关进行50次试操作,对手车进行25次抽出和25次插入的试操作。
如能满足下列条件,则认为连锁是可靠的:a.断路器、隔离开关不能被操作。
b.手车的抽出与插入被阻止。
c.断路器、隔离开关、手车及柜门连锁装置具有正常的工作程序,并且试验前后的操作力基本相同。
6.2 机械寿命试验6.2.1 机械寿命试验是验证6~35kV高压电能计量柜在规定的机械特性及不更换零部件的条件下,能否承受规定的分、合闸空载操作的试验,并考核其机械操作的稳定性。
6.2.2 试验次数和分配:a.对固定式高压电能计量柜主回路中的隔离开关及其防误操作连锁装置,应能经受2000次分、合闸操作。
b.对移开式高压电能计量柜主回路中的隔离触头、触头罩,随手车动作的辅助隔离插头和手车,以及防误操作连锁装置,均应能经受从工作位置到移出位置及从移出位置到工作位置,抽出和推进各500次的机械寿命操作。
c.机械寿命试验前所做的机械操作试验,若试验后未经调整,其次数可计入机械寿命试验次数中。
6.2.3 试验中的规定:试验中只允许按技术文件的规定进行润滑,不允许作机械调整或进行其他方式的维护。
若不符合标准要求进行调整,则调整后应重新进行试验。
6.2.4 试验判据:试验中及试验后,试品应能正常地操作,具有承载其额定电流、短路电流的能力以及耐受其额定绝缘水平的电压值,并应满足下列全部要求。
a.试验中不应发生拒合、拒分以及影响电能计量柜正常运行的异常现象和故障。
b.固定式电能计量柜的回路电阻应满足本标准第4条的要求。
移开式电能计量柜机械寿命试验前、后应测量手车与骨架之间的接触电阻,其值应不大于1000 μΩ;测量位置为工作位置、断开位置、试验位置;测量点在手车与固定部分的总接地螺栓之间。
c.试验后,不出现零部件过度磨损、脱落、损坏或永久性变形。
7 接地保护电路有效性试验7.1 对装有超过安全电压元件的各活动门、板及操作把手,应测量其对主接地点的直流电阻,移开式电能计量柜的固定部分与手车移动部件之间的接地连接也应进行试验,以检查保护电路各部分的有效连接情况。
其测量值不得大于1000μΩ,可用直流电压降法或电桥测量。
7.2 对于0.38kV电能计量柜,如其中性母线与三相母线并排放置,则应对中性母线与它最近的一个母线之间进行短路强度试验,以验证保护电路耐受短路电流的能力。
如其中性母线与三相母线分开放置,可免做此项试验。
试验电流值为电能计量柜的相—相短路强度试验电流值的60%。
7.3 试验结果:若保护电路符合本标准第7.1条的要求,短路试验没有使其连续性受到损坏,则认为试验通过。
7.4 测量电阻值的部位和短路试验结果均应载入试验报告。