WSD-电梯自动应急疏散装置安装指导说明书
应急照明及智能疏散安装及调试方案
智能型火灾信息显示及智能疏散批示系统安装及调试方案目录1、规定及布线 ...................................................................................................................................................... - 3 -1.1、施工前准备 .......................................................................................................................................... - 3 -1.2、钢管内穿线、布线、校线................................................................................................................... - 3 -1.3、线槽内配线施工措施 .......................................................................................................................... - 4 -1.4、外接线预留长度 .................................................................................................................................. - 5 -1.5、线路电阻测量 ...................................................................................................................................... - 5 -2、系统设备安装 .................................................................................................................................................. - 5 -2.1、主机安装 .............................................................................................................................................. - 5 -2.2、系统式电源安装 .................................................................................................................................. - 6 -2.3、疏散批示灯安装 .................................................................................................................................. - 7 -3、智能疏散系统设备调试 .................................................................................................................................. - 8 -3.1、调试前准备 .......................................................................................................................................... - 8 -3.2、系统检查 .............................................................................................................................................. - 8 -3.3、设备单机调试 ...................................................................................................................................... - 9 -3.4、系统设备联动调试 .............................................................................................................................. - 9 -4、智能疏散系统竣工验收 ................................................................................................................................ - 10 -4.1、所需文献 ............................................................................................................................................ - 10 -4.2、系统验收重要涉及如下装置............................................................................................................. - 10 -1.规定及布线1.1、施工前准备1.1.1、在施工前应认真并熟悉设备安装平面图、接线图、系统图。
中川电气智能疏散-工程安装指导书V14.3.14
消防应急照明和疏散指示系统产品
中川智能疏散指示系统 工程安装指导书
Ver14.3.14
中川电气科技有限公司
工程部
中川电气科技有限公司
目录
一.智能疏散系统系列设备箱体表、地址码说明............................................................. 1 1.1 设备箱体表说明 ........................................................................................................1 1.2 产品地址码说明 ........................................................................................................1
电源和通讯四总线采用穿 SC20 钢
管同管铺设,在每个消防应急灯处
设 86 接线盒。若为嵌墙灯具、地
埋灯具应提前放置灯具预埋盒,具
体预埋方案可联系我司。
线材型号样图 WDZN-RYJSP-2*1.5mm2
WDZN-BYJ-3*Nmm2
WDZN-BYJ-2*2.5mm2 WDZ-RYJS-2*1.5mm2
A、火灾报警系统的第三方通讯协议接口卡及火警输出协议; B、烟感或温感探测器的地址竣工图; C、最终版智能疏散施工图 CAD 电子档(含各主要设备部件、应急灯具的安装位置、连线方式及布线走向等)。
6
四.智能疏散系统产品安装、接线说明 4.1 应急照明控制器安装、接线说明:
中川电气科技有限公司
1 安装说明;
消防电梯使用手册(3篇)
第1篇一、前言为确保火灾发生时人员的安全疏散和救援工作的顺利进行,本手册旨在详细说明消防电梯的使用方法和注意事项。
请使用者务必仔细阅读并严格遵守以下规定。
二、消防电梯概述消防电梯是专门为火灾时紧急疏散和救援而设计的电梯,具有以下特点:1. 独立供电:消防电梯配备独立电源,在火灾发生时,即使主电源中断,消防电梯仍能正常运行。
2. 紧急照明和报警:消防电梯内部配备紧急照明和报警装置,确保在火灾情况下能正常使用。
3. 自动运行:消防电梯在火灾发生时,可自动运行至最近的楼层或指定楼层,便于人员快速疏散。
4. 安全可靠:消防电梯具有多重安全保护措施,如超载保护、紧急停止按钮等。
三、消防电梯使用方法1. 启动电梯:- 按下电梯门口的呼叫按钮,启动电梯。
- 等待电梯到达所在楼层。
2. 进入电梯:- 检查电梯门是否关闭严密,确保安全。
- 按下对应楼层的按钮,选择目标楼层。
3. 使用紧急按钮:- 如遇火灾等紧急情况,按下电梯内的紧急停止按钮,使电梯停止运行。
- 紧急情况下,可使用电梯内的对讲系统与外界联系,寻求救援。
4. 使用对讲系统:- 消防电梯内部配备对讲系统,可随时与外界联系。
- 如遇火灾,可通过对讲系统告知救援人员所在楼层和情况。
5. 紧急情况下撤离:- 如遇火灾,请立即按下紧急停止按钮,使电梯停止运行。
- 按照指示标志和紧急疏散路线,有序撤离至安全区域。
四、消防电梯注意事项1. 禁止乘坐非消防电梯:- 消防电梯仅供火灾时紧急疏散和救援使用,禁止在正常情况下乘坐。
2. 禁止随意操作:- 消防电梯的操作按钮和设备不得随意操作,以免影响电梯的正常运行。
3. 禁止在电梯内吸烟:- 消防电梯内禁止吸烟,以防火灾发生。
4. 禁止携带易燃易爆物品:- 消防电梯内禁止携带易燃易爆物品,确保电梯运行安全。
5. 禁止在电梯内嬉戏打闹:- 请保持电梯内的秩序,禁止在电梯内嬉戏打闹,以免影响他人使用。
五、消防电梯维护保养1. 定期检查:- 定期对消防电梯进行维护保养,确保其正常运行。
应急停电平层装置使用说明书
电梯停电应急装置说明书一.概述本公司根据《电梯制造与安全规范》(GB758-2003,EQUEN81-1:1998)的部分内容设计出SWD-EPS系列电梯应急救援设备,能迅速准确解救出被困人员。
SWD-EPS系列电梯应急救援装置能与国内外各种电梯配套使用,是宾馆、饭店、办公楼、医院、住宅等高层建筑必不可少的安全装置。
主要技术参数(1)输入电压:三相380V;(2)蓄电池组:12V17AH/24AH×4;(3)可驱动电梯的功率:≤38KW(特殊规格或>38KW另予注明)。
(4)空气中不得含有爆炸、腐蚀性等有害气体或尘埃。
二.工作原理SWD-EPS系列电梯应急装置工作原理如图1所示:1)电源检测当三相交流电源正常供电时,电梯应急装置内的电源检测回路给出交流输入电源正常的信号,该装置的蓄电池组通过充电回路自动浮充,使之保持额定工作电平状态。
充电回路具有过充、短路和过流等保护功能。
2)应急运行当电梯突遇停电或电梯控制系统发生故障而停止运行时,应急装置的应急控制系统会立即检测电梯状态,自动投入应急救援。
首先电源接触器KP断开,从而断开三相电源YG2、YG4、YG6与电梯控制柜主变压器输入电源YG1、YG3、YG5的连接,接着检查安全回路及门锁回路是否正常,若正常则启动直流变换器给门机控制系统和门区传感器供电,继电器JN,PZ的常开接点闭合。
应急装置检测到平层信号,继电器D0吸合,其常开接点闭合,门机系统得到所需要的电压及开门信号而起动,将轿门和厅门同时打开;如果轿厢不在平层位置,则接触器KDP常开触点闭合,由直流变换器给抱闸回路供电,打开抱闸,三相逆变回路输出的电压经KR给曳引机供电,使之起动,牵引轿厢向一定方向运行,轿厢运行至平层位置停下。
三相逆变电压停止输出,合上抱闸。
轿门、厅门打开后,应急装置上述接触器的触头和继电器的触点全部恢复到应急运行前的状态。
三相交流电源恢复与电梯控制系统的连接,结束应急运行,自动关断应急装置电源。
IDD门机安装调试说明
5.充电模块功能指示
蓄电池充电单元装有电源、欠压、充电、浮充四只指示灯和复位键,如下图所示:
注:1、充电电源为AC220V(波动范围:190V-250V)。
2、充电板接通充电电源(AC220V)后带有高压,严禁触摸,以防触电!
三、装置与电梯连接
1.连接原理a.疏散装置与电梯的安全回路、门回路、检修回路、门区传感器、门机的连接采用串接法:
b.疏散装置与电梯曳引电动机的连接采用并接法。
2.疏散装置自检查(在没有与电梯联机前)
1).将FU10、FU7、FU4空气开关推上,置于闭合状态,接通蓄电池电源。
2).启动检测:
用短接线短接接线端子E4-9和E4-10(模拟相序继电器常闭触点启动信号),E4-2和E4-3(模拟电梯此段安全回路信号闭合状态),E5-11和E5-12(模拟测速盒已连接),并仔细检查。QKS9门机还需要短接E4-7和E4-8(模拟轿顶接线盒已连接),将“S”开关由检修拨向工作,启动装置。应能立即听到“吱………”变压器的工作声,IDD门机E6-11和E6-12之间应有AC240V左右的电压,关闭“S”开关。如无声或声音异常,迅速将“S”开关拨回检修位置,检查各线路板接插件、蓄电池连线有否松动、脱落等。
3.输入
a).停电信号
b).编码器信号
c).平层信号
d).安全回路、厅门轿门回路状态信号,电梯检修信号
e).蓄电池充电电源
4.输出
a).三相曳引机驱动电源
b).曳引机制动器电源
c).门电动机驱动电源
d).安抚语音
二、原理
1.结 构
装置由微电脑控制器、功率模块(IGBT)SPWM逆变器、小功率UPS、继电器隔离与接口电路、编码器检测电路及48伏的免维护蓄电池五大部分组成,其结构框图如下。
电梯应急平层装置安装说明书
LT—5000系列电梯应急装置安装使用指南VER: V5.05-LPC932广州联梯电子设备有限公司LT-5000系列电梯应急装置安装使用指南一、说明1.本指南随机配备,其中接口图部分只对同种电梯有效。
2.电梯应急装置柜内的接线在产品出厂前已装配好,用户不需再装配。
3.安装人员须对电梯电路比较熟悉,有一定的电气基础。
4.注意:电梯检修时,请先将本应急装置内的“S1”、“S2”开关关闭。
二、安装1.安装前要切断电梯的总电源,轿厢照明及井道照明等电源开关。
2.确保应急装置内部的断路器及面板上的急停开关在关闭状态。
3.用三条1―2(mm)2的铜芯导线把本装置的TR,TS,TT接到外电网380V市电的输入端。
4.用三条4(mm)2的铜芯导线把本装置的U,V,W接至电梯曳引机的三个输出端。
5.应急装置与电梯之间应有连接良好的接地线。
6.移动接线的线号应用标号标明,以免混乱。
7.详细的接线方法参照安装接线图。
三、调试1.检查接线是否正确、良好、不应有松动、脱离等现象。
2.合上应急装置内部的S1、S2断路器。
3.合上外电网,本装置控制板上的XJ发光管应亮,若不亮,则检查380V电源线接线有否正确。
4.本装置的电池在市电正常的情况会自动充电,当电池电压不足时,控制板上的CD发光管发亮,当电池电压充足时,CD灯灭。
5.当合上市电,电梯将正常的运行,此时应测量电梯与应急装置之间的抱闸电压、安全信号、门锁、平层信号等电压是否与要求的一致,确保万无一失。
6.在应急装置运行前,首先须要作称重测试,否则将无法正常工作。
执行键盘设置的PF菜单即可自动完成此项操作。
此时应急装置自动进入数据写入状态,此过程大约需要20秒钟,当此过程完成后,应急装置自动停止工作。
7.经过上述参数设置后,应急装置会自动判断电梯的运行方向,让电梯处于平层位置,且关好门的状态下人为模拟外电网停电,应急装置立即投入运行,此时数码管应显示为PC,且送出开门电压使厅门和轿门同时打开。
电梯操作及应急作业指导书
1适用范围适用于合肥京东方光电科技有限公司2目的为保证公司电梯设备安全可靠运行,减小事故造成的影响和避免人身伤害事故的发生,特制定本预案。
3用语的定义无4责任与权限4.1电梯管理人员守则4.1.1热爱本职工作,钻研专业知识和有关国家对电梯管理的有关法规、标准、条例;4.1.2熟悉本单位有关电梯管理和规章制度,并组织有关人员实施和组织检查;4.1.3督促有关部门及维修保养单位进行电梯正常运行的巡视和检查;4.1.4以身作则、坚持原则、始终贯彻“安全第一”的工作方针;4.1.5定期组织不同人员的专业培训及安全教育。
4.2电梯安全管理人员职责4.2.1坚持“安全第一”的原则,督促各部门及有关人员正确使用防护用品;4.2.2对在工作中不按操作规程操作的人员或不能正确使用防护用品的人员有指正、批评、处罚的权利;4.2.3安全员应以身作则,工作期间严禁喝酒;4.2.4定期检查电梯运行状况,预防困人、伤人事故的发生,杜绝火灾和安全事故的发生;4.2.5不定期检查电梯维修人员、司机操作人员执行安全操作规程的情况,并有相应的违章或处罚记录。
4.3电梯管理部门负责人岗位职责4.3.1电梯管理部门负责人,对本单位电梯的管理、运行及大修、改造项目、工程进度和施工安全负计划、组织、实施检验和监督责任,执行本单位与维保单位签订的电梯维保、运行协议,对电梯管理工作进行全面管理,以保证电梯的正常运行;4.3.2在电梯正常运行中,按照有关标准和规范进行质量检查及时对运行中发生的故障组织进行修理或采取具体的预防措施;4.3.3对在维修工程中及司机操作时的各种不安全因素和违章提出警告批评或经济处罚;4.3.4对定期检验验收后技术监督局检验人员提出的“整改意见书”具体内容经整改后进行检查,并监督执行;4.6.3当电梯发生漏水、火灾或地震事故时,组员最迟应在30分钟赶到现场,组织维修或抢救;4.6.4每年至少组织一次《电梯应急救援》演习;4.6.5定期巡视检查应急救援物品,如易燃易爆物品的单独保存消防器材应放在机房固定部位并应保证在合格有效期内;4.6.6一旦发生事故,组织人员打电话报警,救援小组成员救助伤员,保护好事故现场,并及时上报单位领导,事故后要认真分析发生原因,制定防护措施并应写出事故报告;4.6.7定期进行电梯故障“应急救援”措施及有关专业知识的培训,组织单位相关人员现场演习培训及逃生方法等等;4.6.8各电梯使用科室管理人员对电梯的正常运行负责;5 应急操作措施5.1因停电造成电梯停梯时的措施运行中的电梯将会因供电线路的故障或限电等原因造成突然停梯,将乘客困在轿箱内,则应该采取如下方法处理:5.1.1、如果有司机操作,司机应对乘客说明原因,使乘客保持镇静并与维修人员联系,进行断电(拉闸)盘车放人操作;5.1.2、如无司机操作,维修人员到达现场后应与轿厢内被困人员取得联系,说明原因,使乘客保持镇静等待,有备用电源的应及时启用备用电源;5.1.3、若恢复送电需要较长时间,对于无平层功能的电梯。
电梯安装作业指导书
电梯安装作业指导书1.1必须牢记“安全第一”的生产观念,从思想上保持警惕。
1.2进入施工现场,必须头戴安全帽,工作时穿上合适的工作服和安全鞋,不可戴手镯、戒指等其它装饰品,严禁在工作时玩耍、打逗、饮酒。
1.3在井道脚手架上工作,上、下爬行时要注意站稳抓实,每层脚手架中间须搭一根钢管铺两层脚手片,除非已提供某些防护措施,当工作高度超过2米而有坠落危险时,必须戴上安全带,并紧系在牢固的物体上。
当拆除脚手架时,必须把附在木板上的钉子除去或弄弯。
1.4在每个井道顶部挂两根生命线,用足够强度的支架固定。
1.5在厅门未安装前,必须在预留洞处设置防护栏,其高度不低于1米,并且张贴醒目的危险标记。
防护栏底部用约150mm的踢脚板固定。
1.6应避免在井道内的不同楼层进行两项或多项工作。
1.7工作区域及周围地区必须保持清洁,任何时间均应防止绊倒,或其他损伤,保持安全的环境。
在留有预留孔的机房内,须用木板固定或重物覆盖预留孔移动,使物体坠入井道。
机房内承重吊钩须有用户单位出具的承重载荷保证书。
1.8井道内要有足够的照明,严禁使用明火或者220V电源作照明,必须使用36V以下的电源作照明。
1.9当使用易燃、易爆及有害液体时,必须要有足够的空气流通,并有保护措施和设置消防器材。
在现场严禁吸烟和引入火种。
如在密封场所,也无通风设施,则必须戴上许可的口罩,防止溶液接触到皮肤。
切勿将氧气、氯气等和这些溶液混合,以免发生爆炸。
1.10在使用电动工具时,必须保证有可靠而有效的接地,并配有漏电保护器,电动工具不得在潮湿或水中使用,切不可将电动工具当作其它用途使用。
2.气割设备应放置妥善地方,并有《禁止吸烟》标志、消防措施和灭火工具。
氧气瓶和乙炔瓶存放距离不得小于7米,且远离火源至少10米。
持有操作证方可动火,动火必须有监护人并配备灭火器。
2.2防止溶液溅到衣服。
2.3当放在棕绳、钢丝绳、电缆时,人不可钻其中间。
2.4严禁在电缆、电线、导轨、补偿链上爬行或滑下。
电梯应急救援说明书
电梯应急救援说明书一、电梯停电关人放人预案1、在突然停电或电梯因意外故障不能运行时,应确认电梯里有无乘客;2、在确认电梯轿厢里有乘客之后,值班人员应及时与电梯中的乘客保持联系,使乘客务必保持镇静;同时,至少3人,其中至少有1名持证人员尽可能迅速赶到机房。
3、在机房内,首先应关闭电梯总电源,然后根据平层标识判断电梯轿厢所处的位置;4、在机房内手动盘车放人前,应确认电梯的主电源开关已关闭,参照紧急救援装置操作说明在电机尾端装上盘车轮,至少一人用手扶住盘车轮,然后再用松闸扳手松开抱闸,手动缓慢盘车,根据平层标识使电梯轿厢缓慢升(降)到就近的平层位置后,松开松闸扳手。
5、在电梯轿厢平层的楼层,救援人员用三角钥匙打开厅门,拉开轿门,放出轿厢里的乘客。
6、若是因故障停机,保持电梯主电源关闭,待电梯维保公司的维修作业人员到现场后在处理。
二、机房失火救援方案1、在发现电梯机房失火后,救援人员应迅速赶到机房,关闭机房内所有电气开关;2、用干粉灭火器或电气专用灭火器,禁止使用其它类型的灭火设施,以免损害电气元件;3、在灭火之后,应调查起火原因;4、电梯公司持证维修人员对控制屏内进行清理,检查电气元件,确认所有元件正常后,再启动电梯进行调试运行。
三、井道底坑进水1、在发现井道(底坑)进水后,应及时关闭电梯主电源开关,使电梯停止运行,待持证维修人员到现场后处理。
2、若可能,电梯使用单位应及时排除底坑积水,打开最底层的厅门并做好危险防护措施,使井道能及时得到通风。
3、维修人员到现场后,首先到轿顶,清理轿顶积水,吹干轿顶控制柜及其它电气元个,检查轿顶线路,若有损坏,应修复。
4、再到底坑,检查底坑中各种电气开关及操作盒的完好性,若有进水或打湿,应吹干之后再检查,如有损坏应修复。
5、电梯使用单位应调查出事原因,采取相应措施,以防止发生类似的事件。
四、电梯机房钥匙(三角钥匙)保管制度1、电梯机房钥匙及三角钥匙应由持证人员专人负责保管。
紧急照明和疏散指引系统的安装与调试
紧急照明和疏散指引系统的安装与调试1. 简介紧急照明和疏散指引系统在建筑物中起着至关重要的作用。
该系统通过在紧急情况下提供适当的照明和指引,帮助人们安全、迅速地疏散。
本文档将介绍紧急照明和疏散指引系统的安装和调试过程。
2. 系统安装2.1 安装位置选择在安装紧急照明和疏散指引系统时,需要考虑以下几个因素:- 建筑物的布局和结构- 紧急疏散通道的位置和长度- 人员密集区域和重要设施的位置根据这些因素,选择合适的位置安装紧急照明和疏散指引系统。
2.2 系统组成部分紧急照明和疏散指引系统主要由以下几个组成部分构成:- 紧急照明灯具:用于在停电或灾难发生时提供照明。
- 疏散指示灯:用于指示疏散方向和紧急出口。
- 疏散指示标识:用于标识疏散通道和紧急出口。
- 控制面板:用于监控和控制整个系统的运行。
2.3 安装步骤以下是紧急照明和疏散指引系统的安装步骤:1. 根据需要,选择合适的位置安装紧急照明灯具、疏散指示灯和疏散指示标识。
2. 安装控制面板,并将其与其他组件连接起来。
3. 进行电气接线,确保系统能够正常供电。
4. 对每个组件进行必要的测试,确保其正常工作。
5. 进行系统的整体测试,确保所有照明和指引功能正常。
3. 系统调试系统安装完成后,需要进行调试以确保其正常运行。
下面是一些调试步骤:1. 检查所有组件的连接和电气接线是否正确。
2. 打开控制面板,确认其工作状态和显示信息是否正常。
3. 逐一测试每个紧急照明灯具和疏散指示灯,确保其能够正常亮起。
4. 检查疏散指示标识是否清晰可见,能够正确指示疏散方向和紧急出口。
5. 进行系统整体测试,模拟紧急情况,确保系统的照明和指引功能能够可靠地工作。
4. 定期维护与检修为确保紧急照明和疏散指引系统的长期稳定运行,定期维护与检修是必要的。
建议按照以下步骤进行维护与检修:1. 定期检查控制面板和所有组件的工作状态,如有需要,尽早更换损坏或老化的部件。
2. 定期清洁照明灯具和疏散指示灯,确保其发光效果良好。
电梯安装说明书.
电梯安装说明书Elevator Installation Manual本安装说明书适用于电力拖动,曳引驱动,额定载重量3000Kg以下,额定速度不大于2.5m/s的各类电梯的安装。
电梯安装标准按额定速度分为三类:A类电梯:电梯的额定速度为>2.0m/s~2.5m/s(简称高速梯)B类电梯:电梯的额定速度为 1.0m/s~2.0m/s(简称中速梯)C类电梯:电梯的额定速度为<1.0m/s (简称低速梯)注:随着技术进步,内容如有改动,恕不另行通知。
第一章安装前的准备工作 (1)第二章缓冲器底座的安装 (5)第三章导轨支架及导轨的安装 (5)第四章曳引机承重梁的安装 (9)第五章轿厢架、轿厢安全钳及导靴的安装 (10)第六章门动系统的安装 (12)第七章曳引机支架、减震器装置、曳引机、导向轮的安装 (17)第八章缓冲器的安装 (20)第九章对重装置的安装 (21)第十章钢丝绳锥套和曳引绳的安装 (21)第十一章限速器装置的安装 (27)第十二章补偿链的安装 (28)第十三章平层装置、极限、限位、强换开关的安装、调整 (28)第十四章电梯层门、指示器和召唤箱的安装 (29)第十五章机房电器装置的安装 (34)第十六章随行电缆的安装 (35)第十七章配线、接地线及绝缘 (36)第十八章电梯调试 (37)第一章安装前的准备工作1.1安装队伍的组成1.1.1根据电梯的种类、技术要求、规格参数、层站数和安装设备自动化程度等因素来确定所需劳动力及技术工人。
1.1.2所有安装人员必须持有经当地质量技术监督局培训考核并取得电梯安装特种作业证。
1.1.3电梯安装负责人必须向安装成员介绍有关电梯井道、机房、库房、电梯安装材料、堆货场地、施工现场、施工办公室、电话、厕所、电源、灭火器、火警、警报处、医疗站、附近医院及工作周期等事项的介绍,并应进行安全交底和技术交底。
并且作好记录。
1.1.4安装人员应熟知电梯安装、验收的国家标准,地方法规、企业产品标准,熟悉所装电梯的土建资料、电梯部件及整机安装图、安装说明书、电梯使用维护说明书、电气控制原理图、电气接线图、结构、控制方式等,并作出具体的进度计划和安装工艺。
最强悍电梯应急平层装置安装说明书
ARD电梯应急平层装置接线说明安装智能人性化,国际最好使用最易安装的电梯应急平层装置,只接八根线,初中生即可看图安装一、电梯有门锁继电器或楼层继电器安装接线图;二、电梯无门锁继电器或楼层继电器,平层信号为高电平安装接线图;三、电梯无门锁继电器或楼层继电器,平层信号为低电平安装接线图;※电池输入的端子台端子BAT+BAT-只有外接电池式ARD才使用,内建电池式ARD 则否。
四、安装步骤:1、关闭电梯控制柜总开关电源;2、将变频器控制柜上R/S/T 3根电源线拆下;对应接在停电柜R/S/T输入端;3、停电柜R/S/T输出端引出三根电源线对应接到控制柜上R/S/T接线端,线径≥6mm ²;4、变频器有门锁继电器,V+与SD接门锁继电器NC点,SD1与V-短接,线径≥0.75mm²;5、变频器没有门锁接触器时,将SD+/SD-接控制柜平层信号及控制柜COM端;6、开、关机时间延迟时间由主板上SW1设定,请参阅附表,6.1、如变频器停电后放电慢,可以延长停电平层装置开机供电时间,最长等待时间30秒;如放电快,则缩短开机等待时间,最短时间5秒;6.2、如需要电梯平层后延迟关机,可以延长停电平层装置关机时间,最长关机延迟时间45秒;为了避免平层后立即停电部分电梯强制关门夹人或损坏电梯,关机延迟时间最短10秒。
7、完成以上步骤可以合上墙壁电源总开关,电梯开到顶楼,控制柜打到检修位置,让电梯低速运行到顶楼和下一楼层中间靠下停止,然后断开总电源开关,检修拨回正常位置,打开电梯应急平层装置绿色开关,等待5秒后,测试电梯是否能顺利抵达下一楼层,并在设定时间内关机。
空载下行时电梯负荷最大,上行最小,顶楼最大,底楼最小。
一般电梯停电后更靠近某一层则来电时返向某一层。
下行没有问题,上行也没有问题;上行没有问题,下行可能会有问题导致停电困人。
试验中可能会出现电梯停靠位置偏上导致反复几次上行到最近平层,多试验几次观察电梯停靠位置即可。
电梯安装安全操作手册
电梯安装安全操作手册一、前言电梯作为现代建筑中不可或缺的垂直运输工具,为人们的生活和工作带来了极大的便利。
然而,电梯安装是一项复杂且危险的工作,如果操作不当,可能会导致严重的安全事故,给安装人员和使用者带来生命和财产的威胁。
因此,为了确保电梯安装工作的安全进行,制定本安全操作手册,希望所有参与电梯安装的人员都能严格遵守。
二、安装前的准备工作(一)人员要求安装人员应具备相关的专业知识和技能,经过专门的培训并取得相应的资格证书。
同时,安装人员应身体健康,无妨碍从事高处作业的疾病和生理缺陷。
(二)技术资料准备在安装前,应仔细查阅电梯的设计图纸、安装说明书、质量检验报告等技术资料,了解电梯的结构、性能和安装要求。
(三)现场勘查安装人员应到安装现场进行勘查,了解现场的环境条件,包括建筑物的结构、层高、井道尺寸、机房位置等,确定是否符合电梯安装的要求。
如果发现现场条件与设计图纸不符,应及时与建设单位和设计单位沟通,协商解决方案。
(四)工具和设备准备根据安装工作的需要,准备好所需的工具和设备,如电动工具、起重设备、量具、安全防护用品等。
所有工具和设备应完好无损,性能可靠,并经过检验合格。
(五)材料准备按照设计要求,准备好所需的安装材料,如导轨、支架、轿厢、对重、钢丝绳等。
材料的质量应符合国家标准和设计要求,并有合格证明文件。
三、井道施工安全(一)井道搭建在进行井道施工时,应搭建牢固的脚手架,脚手架的搭建应符合相关标准和规范的要求。
脚手架的横杆和立杆间距应均匀,脚手板应铺满、铺平,并绑扎牢固。
(二)井道防护在井道入口处应设置防护门,并悬挂警示标志,防止无关人员进入井道。
在井道内,每隔一定距离应设置一道水平防护网,防止人员和物体坠落。
(三)照明和通风井道内应有足够的照明和良好的通风条件,照明灯具应采用安全电压,并固定牢固。
通风设备应运行正常,确保井道内空气清新。
(四)高处作业安全在井道内进行高处作业时,安装人员应系好安全带,安全带应挂在牢固可靠的地方。
EVACTRON SD系列疏散装置安装手册说明书
EVACTRONSD Series Evacuation UnitsInstallation Manual ver3.2Models SD20-120The EVACTRON SD series amplifier units are a new range of Building Occupant Warning System (BOWS) which provide Automatic and Manual control of Alert and Evacuation tones.The SD series units are available in a variety of sizes- 20, 40, 60,120 and 250 watt.NEW KEY FEATURES INCLUDE∙High efficiency, class D amplifiers.∙Removable SD Card with voice-over messages for Alert and Evacuation tones.∙ A library of messages and tones easily changed to suit individual customer’s requirements.∙ 4 x Inputs to play custom tones and messages e.g. school bell, lock-down, chemical alarm etc ∙Test and False Alarm messages using on-board push buttons.∙ 2 wire Monitored Strobe Output, up to 3amps to directly drive strobe indicators.∙Local microphone connection including a socket for a plug-in mic using EVACTRON MIC-SD.∙Local microphone output, for simple looping of microphone, no balancing transformers required.∙Balanced AUX input for paging/music with 3.5mm socket for speaker testing with IPOD etc.∙T.G. 1V audio output with RCA connection to drive additional slave amplifiers if required.∙All models have plug-in terminal connectors.∙Test Tone for 100V speaker output calibration.OTHER FEATURES INCLUDED∙22-30vdc power input with reverse-polarity protection.∙Onboard LED indication for fault and function status.∙ALERT and EVACUATE tones (Evac ISO T3-default or Evac2220 selectable via DIP switch) ∙Alarm input with ALERT to EVAC change-over timer 0-8 minute.∙Chime feature available for both M1 and M2 if required, upon activation.∙Monitored 100v speaker output with open and short protection.∙Fault output contacts selectable N.O. or N.C. with remote common-fault input and output.∙Fault condition after 10 minutes if no action or left in ISOLATE.∙Connections for standard wired in 003 KEY SWITCH or SELECTOR SWITCH.∙IDC socket for connection to EVACTRON KEYPAD.∙LMU4 compatible. Multiple EVACTRON LMU4 cards can be connected.∙Easy access from above for all controls and connections.∙Supplied on powder coated base plate (same footprint mount for model SD20, 40, 60 &120) ∙19” 3U rack versions are available also in various wattages.TERMINAL CONNECTIONSTB1-1 COM Common 0vTB1-2 AUTO0v to activate.TB1-3 EVAC0v to activate.TB1-4 ALERT0v to activate.TB1-5 SD-C0v to activate. SD Card input, DSW1-3 ON = latched, OFF = un-latched (default)TB1-6 SD-D0v to activate. SD Card input, DSW1-3 ON = latched, OFF = un-latched (default)TB1-7 SD-E0v to activate. SD Card input, DSW1-3 ON = latched, OFF = un-latched (default)TB1-8 SD-F0v to activate. SD Card input, DSW1-3 ON = latched, OFF = un-latched (default)TB2-1 M1/1V Mic1 audio out, to loop hand mic to multiple SD1’s. Matching transformers not required.TB2-2 PA10v to activate M1 audio inputTB2-3 M1+Mic1+ balanced audio in, 1mV (default) for hand microphoneTB2-4 M1-Mic1- balanced audio in, 1mV (default) for hand microphoneTB2-5 0v Audio ground, 0VTB2-6 M2-Mic2- balanced audio in, 1v (default) for line level (music etc)TB2-7 M2+Mic2+ balanced audio in, 1v (default) for line level (music etc)TB2-8 PA20v to activate M2 audio input (must be in AUTO-NON ALARM)TB3-1 24VDC OUT Output fused 1amp max (+24vdc, power for control relays, paging mics pre-amp etc)TB3-2 CON OUT Control output, 0v, 300mA max (0v out for LMU4 all call, speaker relays etc, if required)TB3-3 ALM+24vdc in to activate, reverse polarity protected. See connection diagram for optionsTB3-4 ALM-0V in to activate, reverse polarity protected. See connection diagram for optionsTB3-5 N.O/N.C.Selectable common fault relay contacts. N.O. closes in fault, N.C (default) opens in fault.TB3-6 COM FAULT COM contact for common fault relay.TB3-7 R.FLT OUT Remote common fault contact out, 0v output up to 1amp max, in fault conditionTB3-8 R.FLT IN Remote common fault in, 0V in to activate, used for fault connection to LMU4/s, SRB1’s etcTB4-1 STR A+Monitored strobe output, 4k7 E.O.L. A+ = +24vdc in ALERT A+ = 0vdc in EVACUATE TB4-1 STR E+ Monitored strobe output, 3amp max E+ = 0vdc in ALERT E+ = +24vdc in EVACUATE TB5-1 +24V BATT Battery/PSU input +22-30vdcTB5-2 0V BATT Battery/PSU input 0vTB6-1 100V SPK Monitored, 100V speaker output 22k E.O.L supplied on speaker output terminals,TB6-2 100V SPK Monitored, 100V speaker output. relocate to end of speaker circuit to monitor.TB7-1 4R Amplifier output 4 ohm to step-up transformerTB7-2 C Amplifier Common to step-up transformerTB7-3 A1 100V IN100v from step-up transformer, Loop to A1 input on LMU4 if installed.TB7-4 A2 100V IN100v from step-up transformer, Loop to A2 input on LMU4 if installed.CONNECTORS3.5mm M2 SOCKET A 3.5mm socket has been provided for connection to an IPOD etc for speaker testing.To activate input, place M2 jumper from CTRL to LOCK and select AUTO.Note input is looped from M2 in, so only one source can be used at once.Un-plug TB2 if BGM/paging mic connected whilst using 3.5mm input.M2 GAIN jumper should be in the 1V position (default) adjust M2 to required level.4 PIN MIC1 SOCKET 4 Pin socket for connection to plug-in hand microphone EVACTRON model MIC-SDAUD-OUT RCA 1v common audio out to drive slave amplifier/s.IDC CONNECTOR 16 way IDC- connection for keypad control, EVACTRON model KEYPAD-SD.FUNCTION SETTINGSDIP SWITCH1-Evacuate T3/2220 OFF (default) = T3 temporal EVAC tone. ON = old 2220 EVAC tone2-Messages in manual OFF (default) = ALERT and EVACUATE messages in AUTO only ON = ALERT and EVACUATE messages in MANUAL and AUTO.3-SD-Latching OFF (default) = Non-latching- SD Card inputs C, D, E & F only play whilst input is low. ON = Latched - 0v momentary to trigger, will play full file whilst in AUTO. 4-100V Test ToneOFF = Test tone off (default)ON = 100v test tone active. Adjust TONE VOL to 100vac MAX on SPK output.TIMER ALERT to EVACUATE change-over time in AUTO-ALARM mode.BLACK 0=min straight to EVAC (Vertical) 1=1min ALERT then EVAC 2=2min ALERT then EVAC3=3min ALERT then EVAC 4=4min ALERT then EVAC5=5min ALERT then EVAC 6=6min ALERT then EVAC 7=7min ALERT then EVAC 8=8min ALERT then EVAC 9= stay in ALERT VOLUME CONTROLSMIC1 VOL Adjusts level of MIC1 input, see M1 GAIN jumper links below MIC2 VOL Adjusts level of MIC2 input, see M2 GAIN jumper links below TONE VOL Adjusts ALERT, EVACUATE & TEST TONE level MESS VOL Adjusts TONE and MESSAGE files (loaded on SD Card)JUMPER LINKSM1 GAIN 1mV (default) microphone level, 1V line level (music/PABX) & 3V if removed. M2 GAIN 1mV microphone level, 1V (default) line level (music/PABX) & 3V if removed.FUNC1 SPK Monitoring Disable ON speaker monitoring is disabled (used when no speaker caps fitted)OFF (default) speaker monitoring is enabled (22k E.O.L required)FUNC2 Strobe Monitoring Disable ON strobe monitoring is disabled (used when connecting multiple SRB1’s) OFF (default) strobe monitoring is enabled (4k7 E.O.L. required)PA1 STD/SEL STD (default) for all connections other than selector switch.SEL link when connecting a selector switch.PA2 CTRL/LOCK CTRL (default) control output 0v is active with any function other than PA2. LOCK PA2 locked on (0V) and Control output active. REMOVED all functions activate control output, including PA2.COM-FLT Common Fault Contacts N.C. (default) Closed under normal conditions, opens on com fault or loss of power.N.O. Remains open under normal conditions, closes on com fault or loss of power.PUSH BUTTONSF FALSE ALARM MESSAGE Press button “F ” to play False Alarm message.T TEST MESSAGE Press button “T ” to play Test Message.TEST MESSSD CARDThe SD1 units have been supplied with a removable SD card, this stores a library of messages and tones for you to choose from if required. Also loaded onto the card are various data sheets and installation notes.To view files simply remove the SD Card, located under the left hand corner of the PCB (next to IDC) then insert into a SD slot on your computer. Copy files from the library into the required trigger folder, replacing existing ones.NOTE removing SD Card will not stop ALERT and EVAC tones from functioning.Multiple files can be loaded into trigger folders. These will play in alphabetical or numerical order, re-name if required.e.g. 1bell.wav 2bellmessage.wav 3bellmessage.wav (bell tone will play once followed by bell message twice)Note a file with the same name can not be loaded into a trigger folder as it will try to over-write the file.1 Tone Library contains various tones files to choose from.2 Message Library contains various messages to choose from.TRIGGER FOLDERSALERT and EVAC default tones are loaded on to the EEPROM.If different tones are required, load the new files into the“Alternate” folders and they will override the default tones,once the SD Card is re-inserted. If ALERT or EVAC messagesare not required, remove files from the folder.Note if the old 2220 Evac tone is required, set DSW1-1 to ON.∙Alert Message -plays after every 5 tone pulses.∙Alert Tone Ramp Alternative -insert a different file if required.∙Alert Tone Steady Alternative -insert a different file if required.∙Evac 2220 Message -plays after every 4 tone pulses.∙Evac 2220 Tone Alternative -insert a different file if required.∙Evac T3 Message1 -plays after every 3 tone pulses.∙Evac T3 Message2 -insert for alternating messages in EVACIf loaded, message 1 & 2 will alternate after each 3 tone pulses.∙Evac T3 Tone Alternative -insert different file if required.∙Mic1 Chime -insert chime file, will play when mic1 is activated.∙Mic2 Chime -insert chime file if required, when mic2 is activated.∙PB F False Alarm Message-default message loaded.Press push button 1 “F” to activate.∙PB T Test Message-default message loaded.Press push button 2 “T” to activate.∙SD A Input- activated via KEYPAD-SD.Test message (default) insert different file if required.∙SD B Input- activated via KEYPAD-SD.False Alarm message (default) insert a different file if required.∙SD C Input- default file loaded, change if required.∙SD D Input- default file loaded, change if required.∙SD E Input- default file loaded, change if required.∙SD F Input- default file loaded, change if required.Inputs C-F can only be activated in AUTO NON-ALARMLOADING YOU OWN FILESYou may choose to record or supply your own CUSTOM files to load onto SD Card, they must be in the following format. FILE TYPES SUPPORTEDUncompressed PCM WAVE files with the file extension “.wav”. Files must only contain a single audio channel (Mono audio) MP3 files will not work and need to be converted. Save as WAV PCM signed 16 bit, mono.Many free programs are available to convert files to required format. A free program commonly used is called Gold Wave to edit files. Otherwise send file to *****************.au and we can have it converted.EVACTRON SD SERIES EVACUATION UNITS SPECIFICATIONSSupply Voltage22-30vdcCurrent Draw MaxStandby 120mASD20 20W output- 1.1 FLASD40 40W output- 2.0 FLASD60 60W output- 2.8 FLASD120 120W output- 5.5 FL AAdd loading of strobes if connected.Speaker Impedance Max using Impedance meter SD20 20W500 ohms ACSD40 40W250 ohms ACSD60 60W 166 ohms ACSD120 120W 83 ohms ACSpeaker Output22k end of line resistor (E.O.L.)Recovery Time from S/C 13 secondsRecovery Time from O/C 20 secondsStrobe Output4k7 end of line (E.O.L)3amp maximum (can drive strobes directly) Control OutputOpen collector transistor 0v switch,300mA max (to drive relay or multiple LMU4 all call) Common Fault Contacts1amp rating, selectable N.O or N.C Output LevelsM1 Output 1V (for mic looping)RCA audio out 1VInput LevelsM1 Gain JumperInput Level M1 Top -1mV (mic level)Input Level M1 Bottom -1V (line level)Input Level M1 Removed 3V (3V line level)M2 Gain JumperInput Level M2 Top -1mV (mic level)Input Level M2 Bottom -1V (line level)Input Level M2 Removed 3V (3V line level)Frequency ResponseFrequency response any channel (-3dB) 50Hz - 15 kHz DimensionsSD20-120221mmL x 115mmD x 90mmH(Mounted on hat section including transformer)PCB only 200mmL x 115mmD x 40mmH (no stand-offs) Individual Transformers20watt 65mmR x 30mmH,40watt 95mmR x 35mmH,60watt 95mmR 35mmH,120watt 110mmR x 40mmHAll specifications are for supply voltage of 24VDC and ambient temperature of 26C unless otherwise statedEVACTRON SD SERIES EVACUATION UNITS TYPICAL AMPLIFIER CONFIGURATIONSINGLE SD UNITSingle control/mic, single speaker circuitSingle control/mic, multiple slavese.g 2 x SD120=240wSingle mic, multiple controls, multiple SD1 units RECOMMENDED TEST PROCEDURE1. Make sure the PSU is capable of the full load current draw of the installed SD1 unit and ancillaries.2. Connect all controls and microphone if required. Leave speaker circuit disconnected for now.3. Connect 24vdc to BATT input, all LEDS except ALARM will momentarily light up on power-up.AMP POWER and STR POWER green leds should remain on at all times whilst power connected.SPK S/C led should stay on for 13 seconds and then clear after power-up,SPK O/C led will come on, if 22K E.O.L. is not across the speaker output terminals.4. With the speaker circuit disconnected, place an AC meter across the speaker output and turn DSW1-4 to the ON position(TEST TONE) the meter should read 100VAC, adjust TONE VOL if required, return DSW1-4 to OFF.5. Connect a test speaker to speaker output (this allows local testing without disrupting the building occupants)6. Press on-board push button “T” (TEST MESSAGE) the green P.A. led should flash. Adjust MESS VOL if required.7. If a microphone is connected. Select P.A; speak into the microphone, green led P.A. should be steady.Adjust M1 VOL to required level. (If key switch fitted, hand microphone will work in AUTO or override EVAC)8. Set timer ALERT to EVAC change-over time see time instructions (0 min = straight to EVAC)Select AUTO and activate a FIP ALARM, the red ALARM led should light. (ALM requires 24vdc supply to activate) ALERT or EVAC tones will activate with corresponding led.Messages should interrupt the tones and P.A. led will flash whilst messages are playing.9. Test all other functions as required.10. Once initial local is complete, disconnect test speaker and connect building speaker circuit.The 22K E.O.L. resistor will need to be moved to the end of the speaker circuit for monitoring to be complete.Test levels and adjust as required, if adjusting TONE VOL again use DS1-4 TEST TONE function to set up to 100V.Exceeding 100v could result damage to speakers. Check speaker supplier’s specifications if required.NOTE POWERING DOWN THE UNIT CAN BE SIMPLY DONE BY UN-PLUGGING 2 WAY “BATT 24V” TERMINAL.EVACTRON SD SERIES EVACUATION UNITSTROUBLE SHOOTINGFAULT CONDITION CHECKLISTNo leds on but power connected Check Battery/PSU polarity and voltage 22-30VDC.AMP POWER green led - off Check blade fuse (amplifier fuse only) and replace fuse with same rating.STR POWER green led - off Overload on strobe circuit, max 3 amps at one time. Self re-setting poly-fuse. Alarm input no action ALM input requires both 0V & +24VDC to activate and in AUTO mode (AUT low) SPK S/C red led stays on after 13sec Speaker Short Circuit, disconnect circuit, E.O.L. it should be 22K.SPK O/C yellow led - on Open Circuit in speaker line, disconnect circuit, E.O.L. it should be 22K.No SPK S/C or O/C fault function Check FUNC1 jumper, should be in OFF position (SPK monitoring enabled)STR S/C red led on Strobe Short Circuit, disconnect circuit, E.O.L. should be 4K7.STR O/C yellow led on Open Circuit in strobe circuit, disconnect circuit, E.O.L. should be 4K7.No Strobe S/C or O/C fault function Check FUNC2 jumper, it should be in the OFF position (STR monitoring enabled) AMP CLIP blue led on/flashing Amplifier close to maximum gain, indicator only.AMP FAULT-yellow led - on Amplifier shut down due to over-load or over temperature, check loading.AMP FAULT-yellow led flashing Amplifier High Temperature condition, fan should come on.Fan on Fan will cycle on as heat sink requires, depending on temp/load.COM FAULT yellow led on Fault condition O/C or S/C, Amp fault, remote fault in, supply voltage under 22VDC. COM FAULT yellow led flashing Fault condition after 10min with no input activated e.g. left in OFF position.No audio out of speakers Check for speaker fault condition. Use tone test (DSW1-4) for 100v test tone.No SD tones/messages working Check the SD Card is inserted underneath (pins to top) re-insert.SD C-F not working SD1 must be in AUTO with no ALARM to operate as SD C-F inputs.SD C-F not staying on If momentary trigger is required, set DSW1-3 to ON (latched), file should play fully. SD C-F stays on Set DSW1-3 to OFF, file will only play whist C-F input is low.Adjust M1/M2 VOL to suit (1mV=hi gain, 3V= low gain)Press either on-board push buttons to test. If P.A led flashes check MESS VOL. Custom message not playing Check format of loaded files, try one from library. See SD Card file type instructions Multiple tones/messages playing Check input folder for more than one file loaded in folder. Leave required one.M1 level too low /high M1 GAIN - 1mV=mic level (default) 1V=line level & 3V if removed. Adjust M1 VOL. M2 level too low/high M2 GAIN - 1mV=mic level 1V=line level (default) & 3V if removed. Adjust M2 VOL. Alert to EVAC Timer issues BLUE timer switches with clear power relay, use the following settings-0=EVAC, 1=2min, 2=1, 3=3, 4=8, 5=10, 6=ALERT stays on, 7=11, 8=4, 9=6min. LMU4/s connection problem Check 100V to LMU4, it must come from A1 & A2 of step up transformer on SD1, toA1 & A2 on LMU4, matching polarity. SD1 should have 22K across SPKSee LMU4 connection drawing for details.SRB1’s connection problem If using SRB1’s on STR output, check FUNC2 jumper, it should be in the ONposition (STR monitoring disabled) to allow 0V switching to strobe relays.See SRB1 connection drawing for details.E V A C T R O N K E Y P A D S D。
DK-4型电梯应急救援装置使用说明书改版
电梯应急救援装置使用说明书目录一、简介 0二、功能特点 (1)三、主要技术指标 (1)四、装置主要部件说明 (2)1、外显板 (2)2、中控板 (2)3、充电板 (3)4、故障板 (4)5、驱动板 (4)6、接口板 (4)7、功率模块 (4)8、强电板 (4)9、电池组 (4)五、使用及维护注意事项 (5)六、使用方法 (5)1、开机 (5)2、模拟应急运行 (5)3、关机 (6)4、救援情况记录 (6)七、救援工作流程 (6)八、常见故障分析与处理 (7)一、简介电梯在运行过程中,有可能因为意外事故而导致突然停止运行,例如电梯供电中断(如停电、缺相等),或电梯自身出现故障(非电梯安全回路或门锁回路故障),这给被困在轿厢内的乘客带来不便,甚至会危及生命安全。
DK系列电梯应急救援装置就是专为电梯解决此问题而研制生产的电梯安全装置。
它能够在上述情况发生时自动投入应急救援:将电梯轿厢慢速运行到就近层站停靠,打开轿门和厅门,放出受困的乘客。
DK-4型系列电梯应急救援装置是最新一代产品。
它采用微机控制技术和先进的交流变频调速技术,科学的优化设计和功能模块化设计,因而具有完善的自我保护功能和灵活多变的对外接口。
它可配套各种型号的交流电梯,是宾馆、饭店、办公楼、医院、住宅以及各类高层建筑的电梯配套应急救援装置的理想选择。
DK-4型电梯应急救援装置因应急救援功能不同而有多种型号,命名方法如下:第3部分:表示同时处理电梯的数目,S表示一拖一,Q表示一拖二。
第2部分:表示产品功能,A仅有停电救援功能,B具有停电救援和电梯故障救援双功能。
第1部分:表示产品系列号。
二、功能特点1.全自动运行,无需人工干预:电梯正常运行时,装置处于守侯状态。
当电网发生故障或电梯自身发生故障(仅限带电梯故障救援型)时,装置自动投入工作,切断电梯控制回路进入应急救援工作,在救援过程中外电网恢复不影响装置的正常工作。
对于故障救援型,当应急救援工作完成后,若原故障未排除,装置不会再次启动,除非电梯重新走梯。
梯控安装应急预案和操作流程
梯控安装应急预案和操作流程下载温馨提示:该文档是我店铺精心编制而成,希望大家下载以后,能够帮助大家解决实际的问题。
文档下载后可定制随意修改,请根据实际需要进行相应的调整和使用,谢谢!并且,本店铺为大家提供各种各样类型的实用资料,如教育随笔、日记赏析、句子摘抄、古诗大全、经典美文、话题作文、工作总结、词语解析、文案摘录、其他资料等等,如想了解不同资料格式和写法,敬请关注!Download tips: This document is carefully compiled by theeditor. I hope that after you download them,they can help yousolve practical problems. The document can be customized andmodified after downloading,please adjust and use it according toactual needs, thank you!In addition, our shop provides you with various types ofpractical materials,such as educational essays, diaryappreciation,sentence excerpts,ancient poems,classic articles,topic composition,work summary,word parsing,copy excerpts,other materials and so on,want to know different data formats andwriting methods,please pay attention!梯控安装应急预案一、应急响应级别1. 一级响应:电梯发生故障或紧急情况,可能导致人员伤亡或重大财产损失。
货梯紧急疏散方案
货梯紧急疏散方案简介货梯紧急疏散方案是为应对发生紧急情况时,确保货梯上的人员能够迅速、安全地疏散而制定的计划。
本文档旨在提供一份简洁明了的紧急疏散方案。
紧急疏散步骤1. 发现紧急情况后,立即按下货梯上的紧急停止按钮。
停止按钮通常位于货梯内部的显眼位置,便于人员迅速操作。
2. 在货梯停止后,人员应保持冷静并按照以下步骤进行疏散:- 如果紧急情况仍然存在,人员应立即使用货梯内部的紧急通信设备与外界联系,向有关人员汇报情况并请求救援。
- 如果紧急情况已解除,人员可以通过货梯内部的疏散指示器判断疏散方向。
通常,指示器会标示出最近的安全出口。
- 沿着疏散指示器的指示方向,有序地排队等待疏散。
在人员较多的情况下,可以按照楼层进行分批疏散,以避免拥堵。
- 到达安全出口后,人员应迅速离开货梯区域,通往安全地点集合,并等待救援人员的指导和安排。
预防措施为了减少货梯紧急疏散的发生概率,以下是一些预防措施的建议:- 定期检查货梯设备,确保其运行正常,包括紧急停止按钮和疏散指示器等设备的灵敏度和可靠性。
- 安装并定期维护货梯内部的紧急通信设备,以便人员能够及时与外界联系。
- 提供员工紧急疏散培训,使其了解货梯的紧急疏散程序和操作方法,并能够应对紧急情况。
- 在货梯内部显眼位置设置紧急疏散指示器,方便人员快速找到疏散出口。
总结货梯紧急疏散方案是确保货梯上的人员在紧急情况下能够安全疏散的重要计划。
通过按下紧急停止按钮、利用紧急通信设备、遵循疏散指示器等步骤,人员能够有序地进行疏散。
同时,定期检查设备、提供员工培训等预防措施也能减少紧急疏散的发生概率。
以此方案为基础,可以进一步制定和优化货梯安全管理措施。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
WSD-电梯自动应急疏散装置安装指导说明书————————————————————————————————作者:————————————————————————————————日期:2WSD-818电梯自动应急疏散装置安装指导说明书西子奥的斯电梯有限公司文件编号:原始会签记录编制钱敏燕校对审核批准部门PDC 部门部门部门日期2006.12.13 日期日期日期授权AUTH. PC-LS0026-2006适配型号OH5000适配电梯型号适配门机型DO2000号更改记录序号更改PC 更改内容描述更改日期签名1234567891011121314151617181920This work and the information it contains are the property of Xizi Otis Elevator Company (“XOEC”). It is delivered to others on the express condition that it will be used only for, or on behalf of, XOEC; that neither it nor the information it contains will be reported or disclosed, in whole or in part, without the prior written consent of XOEC, and that on demand it and any copies will be promptly returned to XOEC.目录安装前注意事项一、概述 (5)二、原理 (6)三、装置与电梯连接 (9)四、调试 (15)五、异常情况处理 (19)六、验收事项 (20)七、使用注意事项 (20)附图一(装置与电梯接口端子图)附图二(装置与电梯门机系统接线图)附图三(装置与电梯连接图)附图四(装置端子位置图)附图五(装置壁挂示意图)安装前注意事项1.为了正确安装、调试和使用WSD-818电梯应急装置,请您务必先认真阅读此使用说明书。
2.为了避免造成人员及设备事故,本产品的安装、调试及维修等必须采取以下安全措施:1)在进行本产品的安装、连接工作之前,必须切断电梯总电源。
地良好。
3)在接通电源调试之前,必须确保电梯应急装置与电梯电气系统之间连接正确。
4)本产品要求专业人员参照说明书中提示操作,以防造成人员伤害,同时避免损害电梯设备。
一、概述电梯应急装置是专为现代电梯的优化使用而设计的电梯安全装置。
正在运行中的电梯,如遇到供电系统故障(停电、缺相、火警)或电梯系统电气设备故障时,将会使运行的轿厢立即停止运行。
此时,乘客将被困在轿厢中无法离开。
应急自动疏散装置能在电梯失电时自动投入工作,将电梯轿厢曳引到就近的楼层,并自动平层及开门放客,以避免因电梯困人而造成的不良后果。
在电梯上配备一台应急自动疏散装置,不仅可以确保电梯乘客的安全疏散,而且相应地增强了电梯的整体安全性能。
1.使用条件:a).环境温度-10℃~+60℃b).相对湿度≤90% 无凝露c). 无腐蚀性和易燃易爆性气体及导电尘埃。
2.功能a). 装置在电梯失电后,3秒钟内自动启动,切换电梯控制回路进入应急运行状态。
在救援过程中外电网供电系统不影响装置的正常工作。
b). 装置投入应急运行后,若电梯在门区位置,装置仅开门放客。
若电梯不在门区位置,且满足安全运行条件,装置将驱动曳引机使轿厢向上(或向下)移动,当轿厢运行到门区位置后即停止驱动并开门放客。
c). 装置完成疏散后,将自动停止工作,并自动恢复原始待机工作状态,以便再次投入工作。
d). 装置选用4只12V全密封免维护蓄电池疏散工作。
(建议用户:免维护蓄电池每使用3年更换一次)e). 装置设置拖动电梯轿厢运行的最大距离为7M(电梯有盲层时可做非标处理)。
f). 装置应急运行的平层精度为≤3CM 。
g).WSD-818型电梯应急自动疏散装置适配于永磁同步无齿轮传动曳引电动机电梯。
3.输入a). 停电信号b). 编码器信号c). 平层信号d). 安全回路、厅门轿门回路状态信号,电梯检修信号e). 蓄电池充电电源4.输出a). 三相曳引机驱动电源b). 曳引机制动器电源c). 门电动机驱动电源d). 平层光电传感器电源e). 安抚语音二、原理1.电气结构装置由微电脑控制器、功率模块(IGBT)SPWM逆变器、小功率UPS、编码器检测电路、继电器隔离与接口电路、及48伏的免维护蓄电池六大部分组成,其结构框图如下。
UPS电源SPWM逆变器220V 输入充电和保护48VLTKM驱动电路微电脑控制器隔离与接口电路M3~KMKMUVW疏散装置内部结构电梯系统断电检测电路速度位置编码器测速电路2、装置布置及器件对照表3.电源检测应急疏散装置与电梯的连接方式:装置中启动检测触点E3-3 ,E3-4与电梯三相保护继电器J 长闭触点相连接。
当电梯处于正常运行时,三相保护继电器J 长闭触点处在断开状态,疏散装置处于待命状态,对电梯电气系统不发生任何影响。
当电梯失电时,此继电器常闭触点因失电而闭合,连通疏散装置的检测触点E3-3 ,E3-4,此时疏散装置由此得到电梯断电信号,自动转接入疏散装置电气控制系统中,装置投入工作。
4. 工作流程5.充电模块功能指示` 蓄电池充电单元装有电源、欠压、充电、浮充四只指示灯和复位键,如下图所示:速度很慢 或不动到层了吗平层、抱闸 停止曳引开门放客启动逆变器 拖动轿厢到层了吗调整速度否结束是否是到层了吗是继续运行否进入电动制动运行安全、门回路通吗在门区吗电梯在检修吗启动工作速度较慢否是否是是否停电速度正常输出关门力矩三、装置与电梯连接1.连接原理a. 疏散装置与电梯的安全回路、门回路、检修回路、门区传感器、门机的连接采用串接法:b. 疏散装置与电梯曳引电动机的连接采用并接法。
2. 疏散装置自检查(未与电梯联机前)1). 将FU10、FU7空气开关推上,置于闭合状态,接通蓄电池电源。
2). 启动检测:用短接线将接线端子E3-3和E3-4短接(模拟相序继电器 J 长闭触点启动信号),短接E2-11和E4-2(模拟电梯检修开关闭合),短接E5-11和E5-12(模拟测速回路正常),并仔细检查。
将 “S” 开关由检修拨向工作,启动装置。
应能立即听到“吱………”变压器的工作声,关闭“S” 开关。
如无声或声音异常,迅速将“S”开关拨回检F1LED1J3J1J2LED4BT1LED3LED212+12J414保险丝 2A充电模块指示功能图电源充电浮充欠压复位电源――指示已接通充电电源充电――指示电池充电器充电状态 (亮为充电,灭为不充电)浮充――指示电池电量已充满 (亮为充满)欠压――指示电池欠压状态(亮为欠压,不亮则不欠压)复位――当蓄电池欠压后,重新恢复到45V以上时,按此键欠压灯灭, 装置可以再次工作,按此键时 装置开关必须在"检修"位置。
CDQ48VBE2-11E2-12E1-12E1-7E1-11E1-12E1-9E1-10疏散装置E1-5E1-6E4-1E4-2检修回路ERO TCIPESTESEEC 电梯控制柜安全回路SAFE LOOPGS(轿门)门回路DS (底层)DS (顶层)串接 示意图OFF空气开关ONON 空气开关闭合状态断开状态OFF修位置,检查UPS 连线有否松动、脱落等。
3)工作过程检测:短接接线端子E1-6和E1-7(模拟厅门轿门回路闭合),再短接E1-10和E1-11(模拟安全回路闭合),重新启动装置,按以下顺序操作,参照右图并观察装置的工作状态:: a. 装置工作 3S 后接触器 KM1 吸合,E4的8、9、10之间输出 AC35V 左右三相交流关门电源。
b. 再3秒后接触器KM3吸合,此时接线端子E1-2和E1-3之间会输出制动器工作电压DC110V 或DC24V ,E1-3为正极。
c. 约2秒钟后,接触器KM3释放。
d. 再1秒钟后接触器KM2吸合,此时接线端子E1-2、 E1-3之间有制动器工作电压DC110V 或DC24V 输出。
接线端子EB2的U 、V 、W 端应有平衡的交流三相输出,电压在AC28~35之间晃动。
e. 约2秒钟后,接触器KM1和KM2释放。
再次关闭 “S” 开关。
4)到层试验:短接E2-5和E2-7(模拟 1LV 上门区信号),或短接E2-5和E2-9 (模拟 2LV 下门区信号),启动疏散装置,在 3 秒钟之后端子E4的8、9、10之间输出三相AC80V 左右(供电梯门机开门电压),约 15 秒之后结束。
5)自检完毕请拆除所有短接线及蓄电池,以确保装置安全。
3. 固定疏散装置有机房固定将疏散装置安置于靠近电梯控制柜并能在调试疏散装置时能方便观察电梯曳引电动机的位置。
无机房固定参照《疏散装置壁挂示意图》用Φ8膨胀螺钉将疏散装置挂置于靠近电梯控制柜处,注意疏散装置在井道内与轿厢等运动部件的安全距离达到规定的标准距离。
4、装置与电梯的详细连接步骤注意:A.联机前请确认疏散装置与电梯是否匹配,否则可能造成设备损坏。
B.安全回路、厅门轿门回路必须全部并分别接入疏散装置E1-6、E1-7和E1-10、E1-11,以确保疏散安全。
C.曳引机制动器、平层光电传感器的连接,必须注意极性。
D.装置充电AC220V 电源必须从电梯控制柜中取得,保证充电可靠。
第一步:关闭电梯总电源,有机房电梯将电测速回路2L V 信号1L V 信号检修回路启动信号厅门、轿门回路安全回路634125912107811118710129521436634125912107811118710129521436634125912107811E 5E 4E 3E 2E 1FU7、FU10OFF ON 工作检修蓄电池断开状态主板TB1主板厅外紧急检修操纵盘主开关OFF 有机房电梯OFF 主开关电源配电箱源配电箱内主开关拉下,无机房电梯将厅外紧急检修操纵盘内主空气开关拉下,并将疏散装置检修开关 “S” 处于检修位置。
第二步:将疏散装置FU7、FU10空气开关拨下,处在断开状态,以保证装置安全。
第三步:连接曳引机,参照下图,用电梯随配的曳引机连接电缆将电梯 TB2、疏散装置 EB2、曳引电动机连接好。
疏散装置 EB2 处的接线需用疏散装置随配的接线鼻与黄蜡绝缘套管按照下图制作接线端子。
第四步:参照疏散装置布置图与电梯控制柜布置图,将疏散装置随配标有E1、E2、E3的电缆按标示对应插接在疏散装置端子内,另一端对应插入电梯控制柜内E1、E2、E3插座。
将电梯标有E4的随行电缆E4插头插入疏散装置E4插座。