阀门三位定位器 说明
电动阀门智能定位器使用说明书概要
电动阀门智能定位器使用说明书Intelligent Electric Valve Locator Instruction Manual一、简介Introduction二、面板说明Panel Description1、按键功能说明The Key Function Description(1) A/M 键:A/M KeyA.手 /自动模式切换;Manual/Auto mode switchingB.手动模式下按 2 秒进入标定模式、In Manual mode, press it for 2 seconds to enter calibration modeC.标定模式下标定结果的储存和确认等;In calibration mode the verification and storage of the calibration results and soon(2)▲键:▲KeyB.手动模式下控制电机正转;In Manual mode control the motor forwardB.标定模式下做累加键使用;In calibration mode as the use of cumulative( 3)▼键:▼KeyA. 手动模式下控制电机反转;In Manual mode control the motor reversalB.标定模式下做递减键使用;In calibration mode as the use of decreaseC.自动模式下按 2 秒进入初始化模式In Auto mode, press it for 2 seconds to enter the initialization mode2、数码管显示说明(参照表1)LED display description (Table 1)( 1)手动模式下,显示阀门相应开度,显示范围不受0.00~ 100.0 的限制;In Manual mode, display the corresponding valve opening, the display range is notlimited from 0.00 to100.0( 2)自动模式下,正常状态显示目前阀门开度,显示范围不受0.00~ 100.0 的限制;In Auto mode, display the current valve opening, the display range is not limitedfrom 0.00 to100.0( 3)标定模式下,各显示详细含义见标定功能说明;In calibration mode the specific meaning refer to the function description.3、状态 LED 显示说明Status LED display description( 1)OPEN:电动履行器控制输出电路“开”输出有效;Electric actuator control output circuit “opening ”output is effective ( 2)SHUT :电动履行器控制输出电路“闭”输出有效;Electric actuator control output circuit “ closing output” is effective ( 3)MANU :定位器处于手动模式;Locator is in manual mode( 4)AUTO :定位器处于自动模式;Locator is in Auto mode4、用户标定LED 显示说明User calibration LED display description( 1)DRTA :正相标定,即4mA 对应阀门全闭,20mA 对应阀门全开;Normal phase calibration, 4mA corresponds to the valve fully closed,20mAcorresponds to the valve fully open( 2)RVSA :反相标定,即4mA 对应阀门全开,20mA 对应阀门全闭;RP Calibration, 4mA corresponds to the valve fully closed, 20mA corresponds tothe valve fully open( 3)OPEN:无输入信号时,阀门自动调至全开;No input signal, the valve automatically transferred to full open ( 4)STOP:无输入信号时,阀门自动停在目前地点;No input signal, the valve automatically stops at the current location ( 5)SHUT :无输入信号时,阀门自动调至全闭;No input signal, the valve automatically transferred to full closed.三、性能参数 ( Performance parameters)1、控制精度: 0.1% ~ 1.0% (可设置)Control precision: 0.1% ~ 1.0% (can be set)2、工作功耗: <10WWorking Power3、工作电压:沟通100~ 240VOperating Voltage: AC 100 ~ 240V4、电动履行器反应电位器:500 欧姆~ 10K 欧姆Electric actuator feedback potentiometer5、输入信号: 4~ 20mAInput signal6、输入阻抗: 250 欧姆Input impedance7、输出信号: 4~ 20mAOutput signal8、输出信号负载:≤450 欧姆Output Load9、环境温度: -20 ° C~ 70 ° CThe ambient temperature10、环境湿度:≤80% RHThe ambient humidity四、接线说明 ( wiring instructions)五、标定操作 ( calibration operation)在手动状态下,按住A/M 键 5 秒进入参数标定状态按A/M 键按▼键显示 F1-2 显示 F.1.-.2.按 A/M 键按 A/M 键最后确认相位按▼键显示 F2A1 自动标定按 A/M 键按A/M 键按▼键显示 F2H1 最小转角标定按 A/M 键按 A/M 键按▼键显示 F2H2 最大转角标定按 A/M 键按 A/M 键按▼键显示 F3-2 显示 F.3.-.2.按 A/M 键按 A/M 键最后确认模式按▼键显示 --05 显示 -.-.0.5.按 A/M 键按 A/M 键最后确认精度退出标定状态,答复到正常运转状态按▼键选择相位模式按A/M 键显示 F2A1按A/M显示 F2A1按A/M显示 F2A1按▼键无信号模式按A/M 键按▼键改变精度按A/M 键In manual mode, hold down the A / M button for 5 seconds to enter calibration statusPress A / Mpress ▼press ▼Display F1-2Display F.1.-.2. Select Phase Mode Press A/M keyFinal phase confirmationPress A/MPress A/Mpress ▼Display Press A/MDisplay Press A/MF2A1F2H1Automatic calibrationDisplay F2A1Press A/Mpress ▼Press A/MMinimum angle calibration Display F2A1Press A/MPress ▼Press A/MDisplay F2H2Minimum angle calibration Display F2A1Press A/MPress A/Mpress ▼press ▼Display F3-2Display F.3.-.2.No signal mode Press A/MPress A/MPress A/MFinal confirmation modePress ▼Press ▼Display --05Display -.-.0.5.Change the precisionPress A/MFinal accuracy confirmationPress A/MPress A/MOut of calibration status, return to normal operating state1、标定模式进入:手动模式下,按A/M 键并保持 2 秒,将进入标定模式;Enter the calibration mode: in manual mode, press A / M key and keep 2 seconds, will enterthe calibration mode2、相位标定:Phase calibration:(1)显示目前实质相位设置,如是正相模式则显示“F1- 2”,反相模式则显示“ F1- 1”,相应标定 LED 也会被点亮。
智能机械6种阀门定位器操作方法及故障说明
智能机械6种阀门定位器操作方法及故障说明阀门定位器是一种用于控制和调节管道中阀门开度的装置。
根据不同的工作原理和功能特点,可以分为智能阀门定位器和机械阀门定位器。
下面将介绍智能和机械阀门定位器的六种操作方法及可能出现的故障。
一、智能阀门定位器的操作方法及故障说明:1.手动操作:当智能阀门定位器处于手动模式时,可以使用手动操作杆使阀门开度达到所需的位置。
此时,智能阀门定位器将不会自动调节阀门开度。
故障说明:如果智能阀门定位器出现故障,无法切换到手动模式,可能导致阀门无法正确操作,需要进行修理或更换定位器。
2.远程操作:智能阀门定位器可以通过无线通信技术与监控系统连接,实现远程操作和监控。
通过监控系统,可以实时了解阀门的开度情况,并进行远程控制。
故障说明:如果智能阀门定位器无法与监控系统连接,可能导致无法进行远程操作和监控,需要检查通信连接或修复故障。
3.自动调节:智能阀门定位器可以根据预设的控制策略,自动调节阀门开度,以保持管道中流体的稳定流量或压力。
故障说明:如果智能阀门定位器无法进行自动调节,可能导致管道中的流体无法得到合理的控制,需要检查定位器的控制算法或传感器的准确性。
4.位置反馈:智能阀门定位器可以通过回传信号,实时反馈阀门的开度位置。
这些反馈信号可以用于监控系统的数据采集和状态诊断。
故障说明:如果智能阀门定位器无法准确反馈阀门位置,可能导致数据采集和状态诊断的错误,需要检查位置传感器或信号传输的连通性。
二、机械阀门定位器的操作方法及故障说明:1.手动操作:机械阀门定位器通过手动操作杆调节阀门开度。
这种操作方法适用于一些简单的管道系统,但需要人工监控和调整阀门开度。
故障说明:如果机械阀门定位器的手动操作杆损坏或无法正常运动,可能导致无法手动控制阀门开度,需要修理或更换机械定位器。
2.自动控制:机械阀门定位器可以通过自动控制系统,根据流量或压力信号实现自动调节阀门开度。
这种操作方法适用于一些较复杂的管道系统,可以实现自动控制和调节。
智能阀门定位器说明书 ppt课件
3.2.1在潮湿环境下使用的注意事项
为了防止定位器在潮湿的环境下进水,使电路发生故障或显示不清 晰等故障的发生,请按图示安装,带有X的图是不适宜的安装方位。
PPT课件
12
3.2.2阀门定位器安装附件
阀门定位器安装所用的附件(见图3-2-2.1)
序号 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 数量 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 名称 安装底板 六角螺栓 弹簧垫圈 平垫圈 连接板 六角螺栓 弹簧垫圈 弹簧垫圈 六角螺栓 弹簧垫圈 平垫圈 销 六角螺母 导向杆 内六角螺钉 弹簧垫圈 平垫圈 方螺母 备注
本产品为本质安全仪表,可以应用在具有爆炸性气体环境中。 DLA1011E 可以接受二线制、4—20mA 标准输入信号。也可以接受 3 线/4 线制输入信号。 DLA1011E 可以用于控制气动直行程阀、角行程阀。可以控制单作用阀 和双作用阀,可以用于防爆和非防爆场合。
PPT课件 3
DLA1011E型智能阀门定位器是具有丰富功能、可通讯的新一代阀门定 位器。 DLA1011E 具有精巧的外观设计,模块化的内部结构,无可比拟的 性能价格比。与传统的阀门定位器相比,它的机械运动部件大大减少, 从而大大降低了故障率,提高了可靠性。
2.1.2 液晶显示器及操作键盘
液晶显示有两行:第一行显示项目数值;第二行显示分项项目号 和项目内容。 :功能键; :下降键; :上升键
PPT课件
7
2.1.3 位置变送电流输出模块报警及限位传感器模块
定位器当前位置通过2线制4~20mA输出反馈。一个数字输出表示一 组故障信息,这两个报警输出电路与其他电路是隔离的。两个可调 整限位位置的数字量输出通道。
西门子阀门定位器中文说明书
西门子阀门定位器中文说明书一、概述西门子阀门定位器是一种用于控制工业阀门开度的高精度设备。
它能够接收来自控制系统的信号,并将其转化为准确的阀门动作,以实现对工艺过程中流体流量、压力等参数的精确控制。
二、工作原理西门子阀门定位器通过检测阀门的实际位置,并将其与控制系统给定的目标位置进行比较,然后根据偏差信号驱动阀门执行机构,使阀门移动到目标位置。
其工作原理基于电气转换和反馈控制技术。
定位器内部包含传感器、放大器、控制器等部件。
传感器用于检测阀门的行程或转角,并将其转换为电信号。
放大器将微弱的电信号放大,以驱动执行机构。
控制器则根据输入信号和反馈信号的差异,计算出控制输出,确保阀门准确地定位在所需的位置上。
三、产品特点1、高精度定位能够实现精确到毫米级的阀门定位,满足各种严格的工艺控制要求。
2、快速响应对控制信号的变化能够迅速做出反应,使阀门动作及时、准确。
3、多种通信接口支持多种工业通信协议,方便与不同的控制系统集成。
4、自诊断功能可实时监测自身的工作状态,及时发现并报告故障,便于维护和维修。
5、适应性强能够适应不同类型的阀门和执行机构,具有广泛的应用范围。
四、安装与调试1、安装前的准备检查阀门和执行机构的状态,确保其完好无损。
准备好安装所需的工具和附件。
2、安装步骤将定位器安装在阀门执行机构上,并确保安装牢固。
连接气源和电气信号线路,注意连接的正确性和密封性。
3、调试步骤打开气源和电源,使定位器处于工作状态。
通过操作控制系统,给定不同的阀门开度信号,观察定位器的响应和阀门的动作。
调整定位器的参数,如增益、死区等,以获得最佳的控制性能。
五、操作与使用1、操作界面定位器通常配备有显示屏和操作按键,用于显示工作状态和参数设置。
2、常用操作手动操作:可以通过手动按键或旋钮,临时控制阀门的开度。
自动操作:在正常工作状态下,由控制系统自动控制阀门的开度。
六、参数设置1、基本参数包括阀门行程范围、控制信号类型、气源压力等。
智能阀门定位器YT-3300系列使用说明书
智能阀门定位器YT-3300,YT-3350系列使 用 说 明 书YTC V.1.05- 目 录(硬件)-说明书概要3安全注意事项和产品保证内容及保证期限3产品简介4主要特征和功能4铭牌内容和说明5型号标记方法6主要参数7内部结构8防爆认证9安装10注意事项10直行程产品外形尺寸图10角行程产品外形尺寸图11 YT-3300L的安装12 YT-3300L的安装例图 12利用支架安装YT-3300L12 YT-3300L无管路连接型的安装15 YT-3300R的安装16利用支架安装YT-3300R16气管连接17注意事项17使用的空压条件17接管的条件17执行机构和气管的连接17电源连接18注意事项18输入信号以及输出信号端子的连接18限位开关端子的连接19自动/手动开关20 PTM, HART选项模块的安装20- 目 录 (软件)-自动设定和基本操作方法22按钮说明22正常运行模式(RUN模式)的说明23自动设定 (AUTO CAL)23自动设定1 (AUTO 1) 24自动设定2 (AUTO 2)24自动设定HF (AUTO HF) 24手动模式(MANUAL)24参数模式 (PARAM)25死区(dEAdZONE)设定25 P 值设定(KP)25I 值设定(KI)25D 值设定(KD)25P_ 值设定(KP_)26 I_ 值设定(KI_)26 D_值设定(KD_)26 BIAS值设定26 KF值设定26手动设定模式 (HAND CAL)26手动设定模式的种类26阀门的零点和量程的设定26阀位反馈信号的零点和量程设定27按行程百分比降低阀门量程(PE TRIM)27设定反馈信号的正/反输出信号(TR_NORM/REV)28 HART通讯的正/反输出设定( HT NORM / REVS )28阀门模式(VALVE)28动作模式的变更 (ACT)28流量特性的变更 (CHAR)29用户自定义流量特性的设定 (USER SET)29正作用阀门紧密关闭功能的设定 (TSHUT OP)29反作用阀门紧密关闭功能的设定 (TSHUT CL)29分程控制 (SPLIT)30用户自定义零点信号设定(CST ZERO)30用户自定义量程信号设定(CST ENd)30角度补偿模式 (ITP OFF/ON)30查看模式(VIEW)31错误警告代码32主程序软件导航图33智 能 阀 门 定 位 器 YT-3300,YT-3350系列说明书概要感谢选用我公司产品。
山武 SVP3000 Alphaplus 智能阀门定位器 AVP100 102 使用说明书
株式会社山武SVP3000 Alphaplus智能阀门定位器型号:AVP100/102使用说明书CM4-AVP100-20011版:2005年8月参考英文CM2-AVP100-2001 2版型号AVP100/102-SVP3000 Alphaplus智能阀门定位器i前言ii型号AVP100/102-SVP3000 Alphaplus智能阀门定位器前言型号AVP100/102-SVP3000 Alphaplus智能阀门定位器iii目录第一章:前言1-1 : SVP型号.......................................................................................................................................1-1 1-2 : 通信..............................................................................................................................................1-2 1-2-1: 手动通信...............................................................................................................................1-2 1-2-2: 使用现场智能通信装置(SFC)............................................................................................1-2 1-2-3: 使用HART通信装置.............................................................................................................1-2 1-2-4: HART通信装置(用于AVP102型).....................................................................................1-3 1-3 : SVP示意图....................................................................................................................................1-4第二章:安装2-1 : SVP装配.......................................................................................................................................2-3 2-1-1: 安装SVP反馈杆...................................................................................................................2-3 2-2 : SVP安装步骤................................................................................................................................2-5 2-3 : 气源..............................................................................................................................................2-7 2-4 : SVP初始调整................................................................................................................................2-8 2-5 : 电气接线.......................................................................................................................................2-9 2-5-1: 接线原则...............................................................................................................................2-10 2-5-2: 接线步骤...............................................................................................................................2-10 2-6 : 用于无弹簧双作用执行机构的SVP(双作用放大器)...................................................................2-11 2-6-1: 将双作用放大器安装到SVP上..............................................................................................2-12 2-6-2: 不带过滤减压阀直接安装的双作用SVP................................................................................2-13 2-6-3: 将双作用SVP安装到薄膜执行机构上...................................................................................2-14 2-6-4: 将双作用SVP安装到角行程执行机构上...............................................................................2-14 2-6-5: 自动设定...............................................................................................................................2-15第三章:调整3-1 : 自动设定.......................................................................................................................................3-1 3-1-1: 用开度开关进行自动设定....................................................................................................3-2 3-2 : 零点-量程调整.............................................................................................................................3-3 3-3 : 现场智能通信装置.........................................................................................................................3-5 3-4 : SFC键盘操作................................................................................................................................3-6 3-5 : SFC出错.......................................................................................................................................3-6 3-6 : SFC开始通信................................................................................................................................3-6 3-7 : 用现场智能通信装置进行自动设定和零点-量程调整...................................................................3-7 3-8 : 手动SVP设定...............................................................................................................................3-11 3-9 : 用SFC设定控制信号/阀门开度之间的关系.................................................................................3-14 3-9-1: 示例......................................................................................................................................3-15 3-10 : 确认SVP输入信号、EPM输出和阀门开度输出..........................................................................3-18目录第四章:使用HART 通信装置进行配置4-1 : HART 通信装置的功能...................................................................................................................4-24-2 : 启动通信......................................................................................................................................4-44-3 : 确认和修改一般信息.....................................................................................................................4-64-3-1: 设备信息..............................................................................................................................4-64-3-2: 厂商.....................................................................................................................................4-74-4 : 设备条件.......................................................................................................................................4-84-4-1: 电流输入值 (单位:mA )..................................................................................................4-84-4-2: 输入信号% (百分比) 值 (单位:%)...........................................................................4-84-4-3: 阀门开度 (单位:%).......................................................................................................4-84-4-4: 驱动信号(EPM (电-气转换器模块) 驱动信号) (单位:%)......................................4-84-4-5: 温度 (设备内部温度) (单位:℃)...............................................................................4-84-4-6: 上次配置数据......................................................................................................................4-94-5 : 配置和标定(设备设定和标定)..................................................................................................4-104-5-1: Mode (切换SVP 模式)......................................................................................................4-104-5-2: Input signal range (设定电流输入值)................................................................................4-104-5-3: Valve sys config (阀门系统配置)......................................................................................4-114-5-4: Dynamic chara (动态特性)................................................................................................4-124-5-5: Valve chara (阀门特性)....................................................................................................4-144-5-6: Tvl cut off (开度截止).......................................................................................................4-154-5-7: Calibrate (标定)................................................................................................................4-164-5-8: Diag parameters (诊断参数)............................................................................................4-184-5-9: Burst mode (触发模式)......................................................................................................4-254-6 : 初始设定.......................................................................................................................................4-264-7 : Maintenance (维修)..................................................................................................................4-274-7-1: Dummy input sig (仿真输入信号).....................................................................................4-274-7-2: Dummy drive sig (仿真驱动信号)......................................................................................4-274-7-3: User data save (用户数据保存).........................................................................................4-284-7-4: Correct reset (修正复原)....................................................................................................4-284-8 : Device status (设备状态)............................................................................................................4-294-8-1: Failures (故障)...................................................................................................................4-294-8-2: Notices (提示)...................................................................................................................4-294-8-3: Valve diagnostics (阀门诊断).............................................................................................4-30目录第五章:维修5-1 : 自动/手动选择开关......................................................................................................................5-1 5-1-1: A/M开关的结构..................................................................................................................5-1 5-1-2: 操作步骤...............................................................................................................................5-2 5-2 : 滤网更换和节气喷嘴维修..............................................................................................................5-3 5-3 : 清洁挡板.......................................................................................................................................5-4 5-4 : EPM (电-气转换器模块)平衡调整..........................................................................................5-5 5-5 : 绝缘电阻测试................................................................................................................................5-6 5-5-1: 测试步骤...............................................................................................................................5-6 5-5-2: 判定标准...............................................................................................................................5-6 5-6 : 使用带增幅器的SVP时的调整步骤...............................................................................................5-7 5-7 : 默认内部数据值表.........................................................................................................................5-8 5-8 : SVP 内部方框图和SVP I/O流程图.................................................................................................5-9第六章:故障排除6-1 : 故障排除.......................................................................................................................................6-1 6-1-1: 使用SFC...............................................................................................................................6-1 6-1-2: 使用HART通信装置.............................................................................................................6-2 6-1-3: 一般故障排除方法................................................................................................................6-2插图列表图 1-1概况.............................................................................................................................1-1图 1-2山武现场智能通信装置.................................................................................................1-2图 1-3HART 通信结构.............................................................................................................1-3图 1-4SVP 示意图...................................................................................................................1-4图 2-1SVP 反馈杆...................................................................................................................2-3图 2-2SVP 最大动作范围........................................................................................................2-4图 2-3....................................................................................................................................2-4图 2-4....................................................................................................................................2-5图 2-5....................................................................................................................................2-6图 2-6....................................................................................................................................2-7图 2-7....................................................................................................................................2-8图 2-8....................................................................................................................................2-9图 2-9....................................................................................................................................2-11图 2-10双作用放大器已安装到SVP 上.....................................................................................2-12图 2-11不带过滤减压阀直接安装的双作用SVP........................................................................2-13图 3-1....................................................................................................................................3-3图 3-2....................................................................................................................................3-4图 3-3....................................................................................................................................3-14图 3-4....................................................................................................................................3-14图 3-5....................................................................................................................................3-15图 3-6流量特性概况...............................................................................................................3-16图 4-1HART 通信装置.............................................................................................................4-1图 4-2HART 通信结构.............................................................................................................4-5图 4-3.....................................................................................................................................4-15图 4-4强制全开值和强制全关值.............................................................................................4-15图 5-1A/M 开关的结构...........................................................................................................5-1图 5-2从自动(正常)操作状态切换到手动操作状态...........................................................5-2图 5-3从手动操作状态切换到自动操作状态...........................................................................5-2图 5-4A/M 开关......................................................................................................................5-3图 5-5EPM 平衡调整..............................................................................................................5-4图 5-6EPM 平衡调整..............................................................................................................5-5图 5-7SVP 方框图...................................................................................................................5-9图 5-8SVP I/O 流程图.............................................................................................................5-10插图列表各部分说明1-2 :通信有三种与SVP 通信的方法:手动;使用现场智能通信装置(SFC );或使用HART 通信装置。
智能机械6种阀门定位器操作方法及故障说明
智能机械6种阀门定位器操作方法及故障说明智能机械阀门定位器是一种先进的控制设备,可用于对阀门的开关进行自动定位和控制。
以下是关于智能机械阀门定位器的六种操作方法以及常见故障的说明。
操作方法一:定位模式1.将定位模式选择开关设定为“定位”模式。
2.通过操作控制系统或按下设备上的按钮,启动阀门动作。
3.定位器会对阀门进行自动定位,并将准确的位置信息反馈给控制系统。
操作方法二:手动操作1.将定位模式选择开关设定为“手动”模式。
2.手动旋转定位器上的手轮,可以直接控制阀门的开关。
3.手动操作通常用于紧急情况或设备维护。
操作方法三:旁路操作1.将定位模式选择开关设定为“旁路”模式。
2.在该模式下,阀门可以完全绕过定位器,实现手动操作。
3.这种操作方法适用于设备维护或维修期间,需要暂时关闭定位器。
操作方法四:反馈检测1.将定位模式选择开关设定为“反馈”模式。
2.反馈模式下,定位器会检测阀门位置,并将实际位置信息反馈给控制系统。
3.这种操作方法可用于验证阀门位置是否正确,以及对定位器进行校准。
操作方法五:自学习1.将定位模式选择开关设定为“自学习”模式。
2.自学习模式下,定位器会通过对阀门进行多次操作,自动学习并记录阀门的动作曲线和位置信息。
3.这种操作方法可以提高定位器的准确性,并使其能够自动适应不同的阀门特性。
操作方法六:故障排除1.当定位器发生故障时,首先检查供电是否正常,并检查与控制系统之间的连接是否良好。
2.检查阀门是否受阻或损坏,以及定位器的传感器是否正常工作。
3.如果以上排除故障方法无效,可以尝试重启定位器或进行其他维护和修复操作。
智能机械阀门定位器的常见故障包括:1.供电故障,如电源线松动或断开。
2.控制系统故障,如信号传输错误或控制器故障。
3.传感器故障,如位置传感器损坏或失效。
4.阀门受阻,阀门卡死或被异物阻塞。
5.定位器内部机械零件损坏,如齿轮断裂或传动带脱落。
6.环境因素导致的故障,如温度过高或湿度过高导致部件损坏。
positioner阀门定位器说明书
positioner阀门定位器说明书positioner阀门定位器说明书阀门定位器,按结构分气动阀门定位器、电-气阀门定位器及智能阀门定位器,是调节阀的主要附件,通常与气动调节阀配套使用,它接受调节器的输出信号,然后以它的输出气压信号去控制气动调节阀,当调节阀动作后,阀杆的位移又通过机械装置或位置信号反馈到阀门定位器,阀位状况通过电信号传给上位系统。
阀门定位器按其结构形式和工作原理可以分成气动阀门定位器、电-气阀门定位器,阀门定位器和智能式阀门定位器。
阀门定位器能够增大调节阀的输出功率,减少调节信号的传递滞后的情况发生,加快阀杆的移动速度,能够提高阀门的线性度,克服阀杆的摩擦力并消除不平衡力的影响,从而保证调节阀的正确定位。
阀门定位器按输入信号分为气动阀门定位器、电-气阀门定位器和智能阀门定位器。
气动阀门定位器的输入信号是标准气信号,例如,20~100kPa气信号,其输出信号也是标准的气信号。
电气阀门定位器的输入信号是标准电流或电压信号,例如,4~20mA电流信号或1~5V电压信号等,在电气阀门定位器内部将电信号转换为电磁力,然后输出气信号到拨动控制阀。
智能电气阀门定位器它将控制室输出的电流信号转换成驱动调节阀的气信号,根据调节阀工作时阀杆摩擦力,抵消介质压力波动而产生的不平衡力,使阀门开度对应于控制室输出的电流信号,并且可以进行智能组态设置相应的参数,达到改善控制阀性能的目的。
按动作的方向可分为单向阀门定位器和双向阀门定位器。
单向阀门定位器用于活塞式执行机构时,阀门定位器只有一个方向起作用,双向阀门定位器作用在活塞式执行机构气缸的两侧,从两个方向起作用。
按阀门定位器输出和输入信号的增益符号分为正作用阀门定位器和反作用阀门定位器。
正作用阀门定位器的输入信号增加时,输出信号也增加,因此,增益为正。
反作用阀门定位器的输入信号增加时,输出信号减小,因此,增益为负。
按阀门定位器输入信号是模拟信号或数字信号,可分为普通阀门定位器和现场总线电气阀门定位器。
阀门定位器说明书
—1—
图 1 智能阀门定位器原理框图
2.1 功能介绍
自适应功能:自动寻找阀门零点和满度,优化阀门控制参数, 提高控制精度 组态功能: 可设置阀门特性曲线、动作方式、死区、行程范围、关断值、事件输出 自诊断功能:能显示输入电流值、上/下行程时间、死区、预判值等 故障模式:故障时定位器可选择 全开、全关、保持、手动等模式 通讯功能:HART 协议的通讯功能 电流反馈功能:输出 4~20mADC 阀位反馈信号
3 技术参数
气指标 输入输出
气源压力 阀泄漏量 稳态耗气量 适应执行机构 行程范围 电流输入 反馈输出
0.14~0.7 Mpa < 0.6L / H < 36L / H
单作用、双作用 直行程 10~100mm;角行程 30~120º 4~20mA DC,最小输入电流>3.6mA;可设定分程控制起点和终点
1 用户须知
1.1 安全指示
定位器先上电,后供气源; 产品使用过程中,不要随意的触摸反馈连接装置; 产品必须正确安装、正确操作和正确维护。
1.2 开箱清单
智能阀门定位器; 安装配件; 用户手册; 另外订制附件,详见装箱清单。
1.3 重要信息提示
为了您能更好地应用这份说明,以及保障你在调试,运行和维修这台仪器时的安全,请注意下列符
智能电气阀门定位器
用户手册
1 用户须知 ...................................................................................................................................................... 1
智能阀门定位器说明书
图 3.5.2.2.2
显示界面(见图3.5.2.2.2)。在未初始化状 态中,按 用于充气,按 用于放气。
2.参数设定、初始化状态 不论在未初始化状态界面,还是在正常运营界面,顾客只需同步按下:
+ + 三个键3秒钟就能够进入到参数设定和初始化状态。
3.正常运营状态 参数设定、初始化成功后,定位器系统自动进入运营状态。
6.调整阀门定位器位置,使阀门定位器到达最高点和最低点时,反馈连杆 摆动角度不超出允许范围。
7.阀门定位器旳进一步调整见3.5节“初始化及投入使用”。
3.3 电气连接
图3-2-2 安装图
阐明:在进行电气连接前确 保全部旳可选择模块已安 装好。
注意:在进行电气安装时, 请参见有关原则,尤其在 危险旳环境中更要根据危 险
智能阀门定位器阐明书
安全注意事项
1.智能阀门定位器简介
2.定位器旳构造
2.1 定位器旳单元构成
3.操作阐明
3.1 外型连接尺寸 3.2 安装 3.3 电气连接 3.4 气动连接 3.5 初始化及投入使用
4. 主要技术参数
5.维护注意事项
6.故障诊疗
返回
安全注意事项
在使用本定位器之前,请务必仔细阅读下面旳安全 注意事项。
2.执行器正/反作用设定。默以为正作用 设定措施与定位器类型设定相同。项号11为
正作用/反作用设定界面。按功能+向上键,系 统退出执行器正/反作用设定,进入阀门气开气 关设定界面。按功能 +向下键 进入10号菜单。 下列全部菜单旳转化以此类推,不再反复阐明。
正作用表达4—20mA相应于0—100%行程。 反作用表达4—20mA相应于100—0%行程。
单作用定位器压力测量模块涉及两个压力表,能够显示输入、输出 气体旳压力。
阀门定位器.模块使用说明书
ZXQ系列电动阀门智能定位器/阀门操作器(电子式伺服控制器)使用说明书DOC NO:201109ZXQ2003ZXQ2004BZXQ2004ZXQ2004C目录一、概述 (2)二、主要技术指标 (2)三、定位器面板 (3)四、接线方式 (5)五、设定操作方法 (6)六、错误代码列表 (9)附录:其它标定操作(出厂后如需此项操作,请在厂家指导下使用) (9)如顾客所购买的是本公司Z型(机电一体)执行器,部定位器无需对执行器转角标定,接线无误即可正常使用。
ZXQ系列电动阀门智能定位器是以工业单片机为核心的智能信号采集控制系统,体积小巧,可选择安装在电动执行器的接线盒或以DIN导轨方式固定在外,能直接接收工业仪表或计算机等输出的4~20mA DC信号(其它输入信号类型可在出厂前定制),与电位器反馈的电动执行器配套对各种阀门或装置进行精确定位操作,能对电动执行器的转角(或位移)进行自由标定,同时输出4~20mA DC的执行器转角位置(或位移)反馈转换信号,可精确设定执行器转角位置的下限限位值和上限限位值,定位器采用3个按键操作,9个LED灯可直接显示定位器模态,4位数码LED通过按键切换显示阀位实际开度值、阀位设定开度值、定位器壳温度,操作方便。
●控制精度:0.1%~3.0%(通过U4参数可调)●可接电动执行器反馈信号:电位器500Ω~10KΩ●可接收外部控制信号(DC):4~20mA (1~5V、0~10V、开关量等出厂前定制)●输入阻抗:250Ω;●通过修改U1参数可设定:①DRTA/正动作,RVSA/逆动作模态②输入信号中断时“中断”模态—OPEN(开)、STOP(停)、SHUT(闭) ●可选:可控硅输出(AC,1000V,25A)●输出执行器位置信号:低漂移输出4~20mA DC对应执行器全闭至全开,信号完全与输入隔离(光电隔离),输出负载≤500Ω●环境温度:0~80℃,相对湿度:≤90%RH●有超温保护功能: 定位器壳温度≥70℃时,定位器停止对执行器的开闭控制●外形尺寸:ZXQ2003→77mm(底面长)×76mm(底面宽)×51mm(高/厚);ZXQ2004→74 mm(底面长)×57mm(底面宽)×45mm(高/厚)ZXQ2004B→119mm(底面长)×76mm(底面宽)×26mm(高/厚)ZXQ2004C→62mm(底面长)×48mm(底面宽)×26mm(高/厚)●可通过按键自由标定输入信号所对应执行器的动作区间(一般标定为电动执行器全闭、全开位置)●可设定最大阀位限制值与最小阀位限制值●密码锁,防止误操作●防执行器频繁启动功能●带故障报警代码指示功能(E-0X)●按输入信号和执行器转角位置进行智能步距调整精确定位■参照下图定位器接线端子和定位器外壳上的接线图连接好电动执行器和电源连线,注意连接时的极性,为减少电机干扰,应将电动执行器的电机控制线和反馈信号线分开走线;定位器的弱电信号线应尽量短些,若必须使用较长的连线时,应采用屏蔽信号线,外屏蔽与控制柜外壳妥善接地。
阀门定位器.模块使用说明书
ZXQ系列电动阀门智能定位器/阀门操作器(电子式伺服控制器)使用说明书DOC NO : 201109(接线前请检查执行器在外部切换开关控制下能否在动作区域内工作, 有^/|\ 无异常现象,能否达到开度的零位与满位,确保限位开关能正常工作。
13 ______________________ J接线前请检查执行器中电位器有无强电,用万用表分别测量电位器三接线端子,确保电位器在执行器运转过程中的阻值变化正常,排除断点等[厶f 异常现象。
定位器与执行器间连线要一致,仔细检查两者端子的对应关系;特别注意定位器电源、输入信号与输出信号接线,切莫把电源接至弱电信号端, 同时用仪表测量控制输入信号在定位器接受信号范围内。
. 如与执行器配套使用,在严寒、酷热、高温的环境下开箱时,仪表应于现场存放3小时以上方可进行标定校验。
目录概述.......主要技术指标三、定位器面板................ ・・. ............ . (3)四、接线方式 (5)五、设定操作方法.......................... ・・・・6六、错误代码列表 (9)附录:其它标定操作(出厂后如需此项操作,请在厂家指导下使用) (9)如顾客所购买的是本公司Z型(机电一体)执行器,内部定位器无需对执行器转角标定,接线无误即可正常使用。
~、概述ZXQ系列电动阀门智能定位器是以工业单片机为核心的智能信号采集控制系统,体积小巧,可选择安装在电动执行器的接线盒内或以DIN导轨方式固定在外,能直接接收工业仪表或计算机等输出的4~20mA DC信号(其它输入信号类型可在出厂前定制),与电位器反馈的电动执行器配套对各种阀门或装置进行精确定位操作,能对电动执行器的转角(或位移)进行自由标定,同时输出4~20mA DC的执行器转角位置(或位移)反馈转换信号,可精确设定执行器转角位置的下限限位值和上限限位值,定位器采用3个按键操作,9个LED灯可直接显示定位器模态,4位数码LED通过按键切换显示阀位实际开度值、阀位设定开度值、定位器壳内温度,操作方便。
定位器操作说明
(三)注意事项
• 压缩空气气源要保持洁净,干燥 • 电气接口接线后密封可靠,无松动 • 定位器调试完成后,外壳盖紧 • 如果个别位置无法排除外界杂质进入定位
内部,可参考做如下图处理
谢谢!
A. 基础菜单与完整菜单之间的切换 基础菜单(basic menu)只有 5 项,完整菜单 (full menu)有 9 项。在 shift menu 里面完 成基础与完整菜单之间的切换。
B. 切换中文菜单 出厂默认是英文菜单,可以在设定(setup) 里面找到外观(Appearance),再找到语言 (language),从中选择中文(chinese)。 按 OK 键确认选择。界面瞬时换成中文。
自动调试
• 首先切换到离线状态,此时屏幕左上角有竖条光标在闪烁,
表示定位器处于已处于离线状态,此时不接受 DCS 信号 控制。同时按住上,下两键 5 秒钟,此时三个灯交替闪烁, 松手,此时已开始自动校验。校验结束会停留在黄灯闪烁 (阀门处于开或者关的位置)或者绿灯闪烁(阀门处于中 间位置)。
• 或者进入校验(calibrate)菜单,选择自动校验(
• 方法如下: • 依次输入4,8,12,16,20mA,检查阀门位置是否一
一对应,连续按3次黄色按键,此时正反作用已切 换,重新输入4,8,12,16,20mA检验。
恢复出厂设置
• 在断电(也就是不接入信号)情况下,按 住黄色按钮,然后按照正负极接入信号 (直到三个灯被点亮,然后黄-红交替闪 烁),此时松开按钮,这时就完成了恢复 出厂设置。
4-20mA 输出信号校验
• 进入校验(calibrate)菜单,选择专业校验 (expert cal),进入传送(transm)。校 验传送低值(transm low)调整到 4mA 按 OK 键确认;校验传送高值(transm hi)调 整到 20mA 按 OK键确认。前提是需要给输 入接线柱 4mA 供电,同时输出接线柱串联 24V 电源和万用表测量输出。
(推荐)电气阀门定位器YT1000系列使用说明书
电气阀门定位器YT-1000系列使用说明书YT-1000系列使用说明书目录结构 (1)动作原理 (2)调节 (3)零点调节 (9)量程调节 (9)自动/手动开关(旁路开关) (10)底座调节 (11)节流孔调节 (12)产品维护和检查 (12)故障诊断和措施 (14)结构动作原理为了打开阀门增加电流信号,力矩马达(①)产生电磁场,挡板(②)受电磁场力远离喷嘴(③)。
喷嘴(③)和挡板(②)间距变大,排出先导阀(④)内部的线轴(⑤)上方气压。
受其影响线轴(⑤)向右边移动,推动挡住底座(⑦)的阀芯(⑧),气压通过底座(⑦)输入到执行机构(⑩)。
随着执行机构气室(⑪)内部压力增加,执行机构推杆(⑫下降,通过反馈杆(⑬)把执行机构推杆(⑫)的位移变化传达到滑板(⑭)。
这个位移变化又传达到量程反馈杆(⑮),拉动量程弹簧⒃。
当量程弹簧⒃和力矩马达(①) 的力保持平衡时,挡板(②)回到原位,减小与喷嘴(③)间距,随着通过喷嘴(③)排出空气量的减小,线轴(⑤)上方气压增加,线轴(⑤)回到原位,阀芯(⑧)重新堵住底座(⑦),停止气压输入到执行机构(⑩)。
当执行机构(⑩)的运动停止时,定位器保持稳定状态。
安装注意事项产品安装时请遵守如下事项:z安装前必须完全切断阀门执行机构和其他周边附件的所有输入信号和气源信号,。
z为了防止系统停机要通过旁通阀或类似装置把控制阀从系统中隔离,。
z执行机构内部不能留有空压。
安装时必要的工具安装时必要的工具和螺丝如下:①内六角扳手(按必要尺寸)②十字螺丝刀③一字螺丝刀④六角螺栓头用扳手(按必要尺寸)YT-1000L的安装YT-1000L使用在直行程(直线运动形)阀门。
如弹簧复位型隔膜式执行机构或活塞式执行机构的直通阀,闸阀等执行机构推杆上下直线型运动的阀门。
YT-1000L的部件如下。
安装YT‐1000L前请确认如下部件。
①YT-1000L本体。
②反馈杆和固定弹簧。
③(YT-1000L)固定螺母安装在本体主轴下方。
智能阀门定位器YT-3300系列使用说明书
智能阀门定位器YT-3300,YT-3350系列使 用 说 明 书YTC V.1.05- 目 录(硬件)-说明书概要3安全注意事项和产品保证内容及保证期限3产品简介4主要特征和功能4铭牌内容和说明5型号标记方法6主要参数7内部结构8防爆认证9安装10注意事项10直行程产品外形尺寸图10角行程产品外形尺寸图11 YT-3300L的安装12 YT-3300L的安装例图 12利用支架安装YT-3300L12 YT-3300L无管路连接型的安装15 YT-3300R的安装16利用支架安装YT-3300R16气管连接17注意事项17使用的空压条件17接管的条件17执行机构和气管的连接17电源连接18注意事项18输入信号以及输出信号端子的连接18限位开关端子的连接19自动/手动开关20 PTM, HART选项模块的安装20- 目 录 (软件)-自动设定和基本操作方法22按钮说明22正常运行模式(RUN模式)的说明23自动设定 (AUTO CAL)23自动设定1 (AUTO 1) 24自动设定2 (AUTO 2)24自动设定HF (AUTO HF) 24手动模式(MANUAL)24参数模式 (PARAM)25死区(dEAdZONE)设定25 P 值设定(KP)25I 值设定(KI)25D 值设定(KD)25P_ 值设定(KP_)26 I_ 值设定(KI_)26 D_值设定(KD_)26 BIAS值设定26 KF值设定26手动设定模式 (HAND CAL)26手动设定模式的种类26阀门的零点和量程的设定26阀位反馈信号的零点和量程设定27按行程百分比降低阀门量程(PE TRIM)27设定反馈信号的正/反输出信号(TR_NORM/REV)28 HART通讯的正/反输出设定( HT NORM / REVS )28阀门模式(VALVE)28动作模式的变更 (ACT)28流量特性的变更 (CHAR)29用户自定义流量特性的设定 (USER SET)29正作用阀门紧密关闭功能的设定 (TSHUT OP)29反作用阀门紧密关闭功能的设定 (TSHUT CL)29分程控制 (SPLIT)30用户自定义零点信号设定(CST ZERO)30用户自定义量程信号设定(CST ENd)30角度补偿模式 (ITP OFF/ON)30查看模式(VIEW)31错误警告代码32主程序软件导航图33智 能 阀 门 定 位 器 YT-3300,YT-3350系列说明书概要感谢选用我公司产品。
ABB阀门定位器操作说明
ABB阀门定位器操作说明一、产品概述二、产品组成1.定位器本体:负责接收控制信号,通过内置电机或气动装置驱动阀门转动。
2.阀门连接装置:用于与阀门连接,将定位器的运动传递给阀门。
3.控制电路:负责处理输入信号,驱动定位器运动,并将执行情况反馈给控制系统。
4.参数调节装置:用于调节定位器的灵敏度、行程等参数。
三、产品使用方法1.链接阀门:首先将阀门连接装置安装到阀门上,确保连接牢固。
2.连接电源:将定位器的电源连接到适配的电源插座中,确保电源正常供应。
3.设置参数:按照实际需求,通过参数调节装置,调节定位器的灵敏度、行程等参数。
参数调节具体方法见附带说明书。
4.输入控制信号:将控制信号输入到定位器的控制电路中,可以通过电流信号或者空气信号进行控制。
具体信号类型和输入方法,请参考附带说明书。
5.操作阀门:通过控制信号,定位器会根据输入信号的变化,控制阀门的开关和调节。
根据实际需求,可以通过控制信号调整阀门的位置。
四、注意事项1.在安装和操作前,请先阅读附带的产品说明书,并确保根据说明进行正确操作。
2.在连接和调节过程中,请确保电源已经关闭,以免发生电击危险。
3.在操作过程中,请注意防止水、油、灰尘等杂质进入定位器内部,以免影响正常使用和降低使用寿命。
5.定位器内部的维修和保养应由专业人员进行,切勿私自拆卸或进行其他操作,以免造成损坏或安全事故。
6.长期不使用时,请及时切断电源,并进行适当的保养,以确保产品的正常使用和延长使用寿命。
五、产品维护保养1.定期检查定位器连接部分和阀门连接部分,确保连接牢固,如发现松动情况,请及时进行紧固。
2.定期清洁定位器内部,可以使用吹扫或者清洗的方法,清除内部的杂质,防止影响正常使用。
3.定期检查电源和控制电路的连接,确保连接正常,电路不松动。
4.定期进行性能检测,根据需要调整参数,以保证定位器的精度和可靠性。
5.对于长期不使用的定位器,将电源切断,并在干燥通风的环境中储存,以避免湿气和污染物的腐蚀。
ft800定位器fct说明书
ft800定位器fct说明书
1、将阀门定位器与安装联板固定在一起,方法是将阀门定位器上表壳打开,用三只M520螺钉穿过壳内三孔与安装联板连接。
2、将阀门定位器的反馈部件与执行机构连接,将调节阀上的阀杆螺帽松开,将反馈部件中支板插在指示器与连接螺母之间紧固。
3、将装有阀门定位器的安装联板与执行机构支架两螺孔有
M1015螺钉按所需位置固定好。
4、将反馈部件中的反馈连接板上的连接销插入阀门定位器凸轮反馈干开口槽中。
5、不同型式的执行机构都应该保证当阀位在50%时,凸轮反馈杆应该在水平位置。
6、将安装连接的各部位调整好后,固定锁紧。
电动阀门智能定位器使用说明书概要
电动阀门智能定位器使用说明书Intelligent Electric Valve Locator Instruction Manual一、简介Introduction二、面板说明Panel Description1、按键功能说明The Key Function Description(1)A/M键:A/M KeyA.手/自动模式切换;Manual/Auto mode switchingB.手动模式下按2秒进入标定模式、In Manual mode, press it for 2 seconds to enter calibration modeC.标定模式下标定结果的存储和确认等;In calibration mode the verification and storage of the calibration results and soon(2)▲键:▲KeyA.手动模式下控制电机正转;In Manual mode control the motor forwardB.标定模式下做累加键使用;In calibration mode as the use of cumulative(3)▼键:▼KeyA.手动模式下控制电机反转;In Manual mode control the motor reversalB.标定模式下做递减键使用;In calibration mode as the use of decreaseC.自动模式下按2秒进入初始化模式In Auto mode, press it for 2 seconds to enter the initialization mode2、数码管显示说明(参考表1)LED display description (Table 1)(1)手动模式下,显示阀门相应开度,显示范围不受0.00~100.0的限制;In Manual mode, display the corresponding valve opening, the display range is notlimited from 0.00 to100.0(2)自动模式下,正常状态显示当前阀门开度,显示范围不受0.00~100.0的限制;In Auto mode, display the current valve opening, the display range is not limitedfrom 0.00 to100.0(3)标定模式下,各显示具体含义见标定功能说明;In calibration mode the specific meaning refer to the function description.3、状态LED显示说明Status LED display description(1)OPEN:电动执行器控制输出电路“开”输出有效;Electric actuator control output circuit “opening” output is effective (2)SHUT:电动执行器控制输出电路“闭”输出有效;Electric actuator control output circuit “closing” output is effective (3)MANU:定位器处于手动模式;Locator is in manual mode(4)AUTO:定位器处于自动模式;Locator is in Auto mode4、用户标定LED显示说明User calibration LED display description(1)DRTA:正相标定,即4mA对应阀门全闭,20mA对应阀门全开;Normal phase calibration, 4mA corresponds to the valve fully closed, 20mAcorresponds to the valve fully open(2)RVSA:反相标定,即4mA对应阀门全开,20mA对应阀门全闭;RP Calibration, 4mA corresponds to the valve fully closed, 20mAcorresponds to the valve fully open(3)OPEN:无输入信号时,阀门自动调至全开;No input signal, the valve automatically transferred to full open (4)STOP:无输入信号时,阀门自动停在当前位置;No input signal, the valve automatically stops at the current location (5)SHUT:无输入信号时,阀门自动调至全闭;No input signal, the valve automatically transferred to full closed.三、性能参数( Performance parameters)1、控制精度:0.1%~1.0% (可设置)Control precision: 0.1% ~ 1.0% (can be set)2、工作功耗:<10WWorking Power3、工作电压:交流100~240VOperating Voltage: AC 100 ~ 240V4、电动执行器反馈电位器:500欧姆~10K欧姆Electric actuator feedback potentiometer5、输入信号:4~20mAInput signal6、输入阻抗:250欧姆Input impedance7、输出信号:4~20mAOutput signal8、输出信号负载:≤450欧姆Output Load9、环境温度:-20 °C~70 °CThe ambient temperature10、环境湿度:≤80%RHThe ambient humidity四、接线说明(wiring instructions)五、标定操作(calibration operation)1、标定模式进入:手动模式下,按A/M键并保持2秒,将进入标定模式;Enter the calibration mode: in manual mode, press A / M key and keep 2 seconds, will enter the calibration mode2、相位标定:Phase calibration:(1)显示当前实际相位设置,如是正相模式则显示“F1-2”,反相模式则显示“F1-1”,相应标定LED也会被点亮。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
阀门三位控制器说明
本定位器可根据控制室的指令,控制阀门处在:关位置、中间某个位置(可任意设定)、开位置;为了方便现场调试,具有手动控制功能、模拟控制室指令进行现场调试的功能,同时具有断电自动保存最后一次指令功能。
还可对阀门设定的某个中间位置进行顺时和逆时的延时控制(出厂延时设定为3秒)。
输入、输出安排:
◆电源:+24V、-GND
◆电位器信号:P1、P2、P3
◆输入信号:(来自控制室指令:低电平脉冲有效、GND为公共端)
1、CLOSE(要求阀门关闭)
2、MID(要求阀门处于中间位置)
3、OPEN(要求阀门打开)(说明:系统以最后接收到的控制指令作相应动作)
◆输出信号:(输出到控制室的状态信号:24V、GND为公共端)
OUTC:阀门处在关闭位置OUTM:阀门处在中间位置OUTO:阀门处在打开位置
◆电磁阀信号:(控制双电控电磁阀)
1、关闭阀门信号(VC+、VC-)
2、打开阀门信号(VO+、VO-)
◆手动控制按键:(3个)
1、调试按键:3个(手动控制功能/模拟控制室指令----根据SW1:ON/OFF区分功能)
K_C:手动关闭阀门/ 要求阀门关闭;
K_M:设置功能键/ 要求阀门处在中间位置;
K_O:手动打开阀门/ 要求阀门打开;
2、设置功能:K_M键(当SW1=ON时有用,用于设定关闭位置、中间位置、打开位置)
操作步骤:(进入设置状态后,可通过K_C、K_O键手动调整阀门位置)
a)长按K_M键,LED黄灯闪烁几下,此时,松开此按钮,系统进入设置状态;
b)按K_C键使阀门处于关闭位置,短按一下K_M键,LED黄灯闪一下,进入下一设置状态;
c)按K_C或K_O键使阀门处于需设定的中间位置,短按一下K_M键,LED黄灯闪一下,进入
下一设置状态;
d)按K_O键使阀门处于打开位置,短按一下K_M键,LED黄灯闪烁几下,设置完毕,将SW1
拨到OFF位置,系统自动进入正常工作状态。
(若黄灯不断闪烁,则表示位置有重叠或电位器
在盲区,需调整电位器起始位置后重新设定)
◆LED灯:(3个)(根据SW1:ON/OFF 区分功能)
1、LED_C(红灯):“关阀门电磁阀”线圈得电指示灯/ 阀门处在“关闭状态”指示灯
2、LED_M(黄灯):设置时,设置过程状态指示灯/ 阀门处在“中间状态”指示灯
3、LED_O(绿灯):“开阀门电磁阀”线圈得电指示灯/ 阀门处在“打开状态”指示灯
◆跳线开关:(4位)
1、SW1:ON/OFF-----手动设置功能/ (模拟)控制室指令
2、SW2:ON/OFF--- --关闭阀门时延时/ 不延时(3秒)
3、SW3:ON/OFF-----打开阀门时延时/ 不延时(3秒)
4、SW4:ON/OFF----- 误差±3% / 误差±2%
操作简要说明:
1、SW1拨到ON位置,用3个按键进行先设定关闭位置、其次设定中间位置、最后打开位置的设定,确
保设置准确;
2、SW1拨到OFF位置,即可。
(此时可用3个按键模拟控制室命令进行试验,看功能是否准确)
3、如中间位置来回漂移无法整定可通过节流阀调整进气。
阀门三位控制器示意图:
注;本产品旋转角度<1620度,按装产品起始位应调整至中间位800度左右。