110kv-10kv变电所电气设计(工程、毕业设计参考)要点
(完整版)110kV变电站设计毕业设计(论文)
![(完整版)110kV变电站设计毕业设计(论文)](https://img.taocdn.com/s3/m/6d30d81ab52acfc788ebc917.png)
110kV变电站设计摘要本次毕业设计以110kV 变电站为主要设计对象,该110kV变电站是地区重要变电站,是电力系统110kV电压等级的重要部分。
该变电站设有2 台主变压器,站内主接线分为110kV、35 kV、和10 kV 三个电压等级。
本设计的第一章为绪论,主要阐述了变电站在电力系统中的地位。
设计变电站的原则和目的以及变电站的基本情况。
第二章是负荷计算及变压器的选择,根据已知变电站的负荷资料对变电站进行负荷计算。
通过得出的负荷确定了主变的容量和台数、主变的型式及主变阻抗。
第三章是变电站电气主接线的设计,分别通过对110kV、35kV、10kV侧电气主接线的拟定,选择出最稳定可靠的接线方式。
第四章是短流计算,首先确定短路点,计算各元件的电抗,然后对各短路点分别进行计算,得出各短路点的短路电流。
第五章是电气设备的选择,电气设备包括母线、断路器、隔离开关、电流和电压互感器、熔断器。
第六章是配电装置,主要对变电站的配电装置进行设计。
通过对110kV变电站设计,使我对电气工程及其自动化专业的主干课程有一个较为全面,系统的掌握,增强了理论联系实际的能力,提高了工程意识,锻炼了我独立分析和解决电力工程设计问题的能力。
关键词:电气主接线短路计算电气设备AbstractThis graduation project take the 110kV transformer substation as the main design object, this 110kV transformer substation is the local important transformer substation, is the electrical power system 110kV voltage rank important part. This transformer substation is equipped with 2 main transformers, in the station the first chapter is an introduction, mainly elaborated the transformer substation in electrical power system status. Designs the transformer substation the principle and the goal as well as the transformer substation basic situation. Second chapter is shoulders the computation and the transformer choice, carries on the load computation according to the known transformer substation load material to the transformer substation. Through the load which obtains , the winding wiring way, the accent press the way and the electricity , separately through to 110kV, 35kV, 10kV side electricity , first determined short-circuits the spot, calculates various parts reactance, then to respectively short-circuits separately to carry on the computation, obtains respectively short-circuits the short-circuit current. Fifthchapter is the electrical equipment choice, the electrical equipment including the generatrix, the circuit breaker, the isolator, the electric current and the voltage transformer, the fuse. Sixth chapter is the power distribution equipment, mainly carries on the design to the transformer substation power distribution equipment. Seventh chapter is anti-radar with the earth, this chapter the choice to the arrester, as well as design, causes me electric power project design question ability.Key words: The electrical Electrical equipment目录1 绪论 (3)1.1变电站设计的原因和目的以及原则 (3)1.2变电站的基本情况 (3)1.2.1 原始资料 (3)1.2.2 所选地址及环境 (4)2 负荷计算及变压器选择 (5)2.1负荷计算 (5)2.1.1 负荷资料 (5)2.1.2 负荷计算 (5)2.2主变的选择 (7)2.2.1 主变压器容量和台数的确定: (7)2.2.2 主变压器型式的确定: (7)2.2.3 主变压器阻抗的选择: (8)2.3站用变压器的选择 (9)2.3.1 站用变台数的确定: (9)2.3.2 站用变的容量确定: (9)2.4无功补偿 (10)2.4.1 补偿作用 (10)2.4.2 无功补偿容量及电容器接线方式 (10)3 变电站主接线形式 (12)3.1变电站主接线的要求及原则 (12)3.1.1 设计要求 (12)3.1.2 设计原则 (13)3.2变电站主接线形式的选取 (14)3.2.1 110kV 侧主接线方案选取 (14)3.2.2 35kV侧主接线方案选取 (17)3.2.3 10kV 侧主接线方案选取 (18)4 短路电流的计算 (21)4.1短路电流计算的目的 (21)4.2短路电流计算 (21)4.2.1 各元件电抗计算及等值电路图 (21)4.2.2 110kV母线侧短路电流的计算: (23)4.2.3 35kV母线侧短路电流的计算 (24)4.2.4 10kV母线侧短路电流的计算 (25)5 电气设备的选择 (27)5.1电气设备选择的一般原则 (27)5.2载流导体的选择 (27)5.3断路器和隔离开关的选择 (30)5.4电流互感器的选择 (35)5.5电压互感器的选择 (38)5.6高压熔断器选择 (39)6 配电装置 (41)6.1配电装置概述 (41)6.2变电站各电压等级采用的配电装置 (41)6.2.1 110kV配电装置 (41)6.2.2 35kV~10kV配电装置 (42)总结 (43)致谢 (44)参考资料 (45)1 绪论变电站是电力系统的重要组成部分,它直接影响整个电力系统的安全与经济运行,是联系发电厂和用户的中间环节,起着变换和分配电能的作用。
110KV电气变电所设计
![110KV电气变电所设计](https://img.taocdn.com/s3/m/387e255026284b73f242336c1eb91a37f11132d5.png)
110KV电气变电所设计110KV电气变电所设计110KV电气变电所是给整个地区提供电力的主要供电设备,在设计生产110KV变电所时,应符合以下基本原则:(1)以安全高效的水平确保有效的电能输送、利用和分配;(2)结构合理、结构安全可靠;(3)保障可靠的变电所性能,使变电所的投产运行可靠;(4)变电所的设计要结合当地及周遭环境条件,协调变电所使用和环境保护要求;(5)有利于维修保养,通过拆装时可以方便、快捷地进行;(6)结构精致美观,外观尽量同化当地环境;(7)减少施工和设备承载性能的影响,作用最大的节能器。
根据以上要求,制定110KV变电所的设计方案应包括以下内容:1.确定110KV变电所的型式和类型,详细制定和设计其现场布置、结构、功能,及调节要求等;2.设计变电所采用的冷却设备(如变压器、运行器、变压器底板等)及其冷却系统。
采用市电供应能否满足变电所需要,需要采用发电机供电的,还需设计发电机及其配套设备;3.设计高压隔离开关、绝缘母线变压器、电容器及仪表等构配件;4.安排变电所供电设备的排列和布置,综合考虑管理、操作安全、可靠运行、维修保养、电工调试、安装工艺特点和节能等技术要求;5.设计变电所接地系统及连接当地联络线路,确保变电所的安全接地;6.设计监测管理的软件系统,满足变电所和远动操控调度的要求;7.根据变电所上电前、上电期间、上电后测试的实际情况,研究并表明变电所的安全开关应具备的技术性能及其防护措施;8.完善方案及根据场地条件设定高压接地网及穿越中压线路的防护要求;9.根据当地电网环境和现场情况,设计设备的安装支架、支架围墙及土建工程;10.根据变电所软件管理、操作及控制要求,搭建变电所现场控制及监测系统;11.不断完善110KV变电所的各项安全措施及预防措施,以确保变电所的安全性和可靠性。
220 110 10KV变电站电气设计说明书 毕业设计论文
![220 110 10KV变电站电气设计说明书 毕业设计论文](https://img.taocdn.com/s3/m/b64aeae049649b6648d747fa.png)
摘要变电站是电力生产与分配的重要环节,变电站的作用是变换电压等级,汇集电流,分配电能,控制电能的流向,调整电压。
电力生产过程有别于其他工业生产的一个重要特点,就是它的生产,输送,变换,分配,消费的几个环节是在同一个时间内同步瞬间完成。
电力生产过程要求供需严格动态平衡,一旦失去平衡生产过程就要受到破坏,甚至造成系统瓦解,无法维持生产。
因而电力生产与分配是关系国民生计的重要环节,而变电站也起到了举足轻重的作用。
电力工业在国民经济中占有十分重要的地位,建国以来,我国的电力工业发展迅速。
电力也成为工农业不可缺少的动力,并广泛应用到一切生产部门和日常生活方面。
电力工业自动化水平正在逐步提高许多变电站以装设微机综合自动化,有些以实现无人值班,电力系统已实现调度自动化。
本文主要是变电站一次部分设计。
首先,根据任务书上所给系统、线路所给负荷情况,通过对负荷的分析计算及供电范围确定主变压器的台数、容量及型号,同时也确定站用变压器的容量及型号;其次,根据原始资料,通过对电力系统的安全、可靠、灵活、经济运行等方面的考虑,确定了220KV、110KV及10KV侧的电气主接线;最后根据最大工作电流及短路电流的计算结果表,对断路器、隔离开关、电压互感器、电流互感器、避雷器、导体等电气设备进行选型、,从而完成220KV变电站电气一次部分的设计。
关键字:220KV变电站、电气一次部分设计、变压器、主接线、电气设备选择。
目录上篇220/110/10KV变电站电气设计说明书目录 (1)第一章概述 (3)1.1 原始资料分析 (4)1.2 主要工作 (5)第二章主变压器和站用变压器的选择 (5)2.1 主变的选择 (5)2.2 站用变的选择 (7)第三章电气主接线方案的确定 (8)3.1 电气主接线的基本要求 (8)3.2 电气主接线的设计方案 (9)3.3 电气主接线图 (12)第四章短路电流的计算 (13)4.1 短路计算的一般规定 (13)4.2 短路类型 (13)4.3 短路点的选择 (13)4.4 短路计算方法 (13)4.5三相短路电流计算的运算曲线法 (14)4.6 等值网络 (14)第五章主要电气设备的选择 (15)5.1高压电气设备选择的一般规则 (15)5.2 断路器和隔离开关的选择 (15)5.3 互感器的选择 (18)5.4 避雷器的选择 (20)5.5 导体的选择 (20)5.6 支持绝缘子的选择 (22)5.7 高压熔断器的选择 (22)第六章电气布置及配电装置 (23)6.1 电气设备布置 (23)6.2 配电装置布置 (23)下篇220/110/10KV变电站电气设计计算书第七章变压器容量的确定 (25)第八章短路电流计算 (25)8.1 系统等值网络图及参数计算 (25)8.2 系统在K1点短路 (28)8.3 系统在K2点短路 (30)8.4 系统在K3点短路 (31)第九章电气设备的选择和校验 (33)9.1 断路器和隔离开关的选择和校验 (33)9.2 互感器的选择 (37)上篇说明书第一章概述一、设计题目:220/110/10kV变电站电气部分设计二、设计原始资料:1.变电站性质:地区重要变电站,连接两个水火系统,并向地方负荷供电2.地理位置:位于某较大城市近郊3.自然条件:站区地势平坦,海拔(300)m,交通方便,有铁路、公路从本站附近经过;年最高气温(34)℃,年最低气温(-24 )℃,最热月平均最高气温(28 )℃,最大风速(5 )m/s,覆冰厚度(10 )mm,地震烈度( 5 )级;周围环境基本无污染。
毕业设计---110kV变电站电气部分设计
![毕业设计---110kV变电站电气部分设计](https://img.taocdn.com/s3/m/8fb21363168884868762d6c3.png)
分类号编号毕业设计题目 ghk110kV变电站电气部分设计2010年5月31日本科生毕业设计任务书一、毕业设计的目的毕业设计是本科生培养方案中的重要环节。
毕业设计是在完成本专业全部课程的基础上,学生综合性地运用几年内所学知识去分析、解决一个问题,使学生得到一次综合运用所学基本理论,基本知识和技能,进行工程设计或科学研究的初步训练,进一步培养学生分析、解决问题的能力。
能够让学生在作完毕业设计后,感到自己的实践动手、动笔能力得到锻炼,增强了即将跨入社会去竞争,去创造的自信心。
通过毕业设计应使学生达到下列要求:1、提高学生关于电力工业建设的政策观念和经济技术观点,以及对工程技术中的技术与经济问题能够进行较全面的综合分析能力。
2、学习变电站工程设计程序和方法,使学生进一步获得查阅文献,搜集资料,调查研究,综合分析,计算比较,设计制图和编写说明等多方面的训练。
3、使学生巩固和提高以往学习的理论和知识,进一步补充某些新的知识和基本技能,从而获得综合应用各种知识解决实际问题的锻炼,提高理论联系实际的能力。
二、主要设计内容(一)电气一次部分1、电气主接线设计;2、短路电流计算及主要电气设备选择;3、配电装置设计。
(二)电气二次部分1、变压器的保护配置设计;2、变压器保护设计;3、变压器保护整定计算;三、重点研究问题1、电气主接线方案设计,包括方案论证(变压器选择、技术论证和经济比较);2、短路电流计算(包括三相短路电流计算与不对称短路电流计算);3、电气设备选择计算;4、变压器保护整定计算。
四、主要技术指标或主要设计参数设计的原始资料为满足乡镇负荷日益增长的需要,提高对用户供电的可靠性和电能质量,根据系统发展规划,拟建设一座110/35/10kV的区域性降压变电所,设计原始资料要求如下:1、电压等级:110/35/10kV2、设计容量:拟设计安装两台主变压器。
3、进出线及负荷情况:(1)、110kV侧,110kV侧进出线4回,其中两回为电源进线,每回最大负荷50000KVA,功率因数为0.85,一回停运后,另一回最大可输送100000KVA负荷;另2回为出线,本期拟建设一回,留一回作为备用出线间隔,出线正常时每回最大功率为35000kVA,最小为25000kVA,功率因数为0.85,最大负荷利用时间为4200h。
110kV变电站电气部分设计毕业论文设计
![110kV变电站电气部分设计毕业论文设计](https://img.taocdn.com/s3/m/dda96314be23482fb4da4cba.png)
110kV变电站电气部分设计第一篇:毕业设计说明书第一章变电站总体分析第一节变电站的基本知识一.变电站的定义变电站是联系发电厂和用户的中间环节,起着变换和分配电能的作用,是进行电压变换以及电能接受和分配的场所。
二.变电站的分类1、根据变电站的性质可分为升压和降压变电站(1)升压变电站是将发电厂发出的电能进行升压处理,便于大功率和远距离输送。
(2)降压变电站是对电力系统的高电压进行降压处理,以便电气设备的使用。
2、变电所根据变电站在系统中的地位,可分为枢纽变电站、区域变电站和用户变电站(1)枢纽变电所。
位于电力系统的枢纽点,连接电力系统高压和中压的几个部分,汇集多个电源,电压为330~500KV的变电所,称为枢纽变电所。
全所停电后,将引起系统解列,甚至出现瘫痪。
(2)中间变电所。
高压侧以交换潮流为主,起系统交换功率的作用,或使长距离输电线路分段,一般汇集2~3个电源,电压为220~330KV,同时又降压供当地用电,这样的变电所起中间环节的作用,所以叫中间变电所。
全所停电后,将引起区域电网解列。
(3)地区变电所。
高压侧一般为110~220KV,向地区用户供电为主的变电所,这是一个地区或城市的主要变电所。
全所停电后,仅使该地区中供电停电。
(4)终端变电所。
在输电线路的终端,接近负荷点,高压侧电压为110KV,经降压后直接向用户供电的变电所,即为终端变电所。
全所停电后,只是用户受到损失。
第二节所设计变电站的总体分析变电站电气一次部分的设计主要包含:负荷的分析计算、变压器的选型、主接线的设计、无功补偿、短路电流的计算、电气设备的选型和校验、母线的选择和校验等有关知识。
因此,变电站的总体分析也应该从这几个方面着手。
1、由待设计变电站的建设性质和规模可知,所设计变电站主要是为了满足某铁矿生产生活的发展需要,是一个110/10kv降压变电站,也是一个地区性变电站,并且只有两个电压等级,因此,主变压器可选用双绕组型的。
毕业设计110千伏变电站电气部分的设计
![毕业设计110千伏变电站电气部分的设计](https://img.taocdn.com/s3/m/f83bf725915f804d2a16c102.png)
摘要电力配电站是由一系列设备组成的电力系统,电能在其中转换、分配、联络、变压、转换。
一个配电站包括各类设备:变压器、断路器、负荷开关、母线、电流互感器、电压互感器等。
配电站是一种综合设施,它可以从分支输电网到初级配电网对电压进行切换和调节。
最重要的是,由于配电站的存在,一部分配电站设备的损坏,或一条通向配电站的电缆切断,都不会引起全局的供电故障。
本文是对10千伏变电站电气部分的设计。
在设计中,我们运用经济及技术比较的方法来确定变电站的电气主接线,运用短路电流实用计算法来进行短路电流计算。
通过查阅设计手册和技术规程对主要设备和导体以及电气总平面布置和高压配电装置进行了设计和选择。
该变压室设有2台主变压器,采用单母线结构及单母线分段的结构。
进行了电气主接线图形式的论证、短路电流计算、主要电气设备选择及校验(包括断路器、负荷开关、隔离开关、电流互感器、电压互感器),同时介绍了继电保护的设计整定等相关方面的知识。
关键词:10KV变配电站短路电流变压器继电保护ABSTRACTThe electric power substation is an assembly of equipment in an electric power system through which electrical energy is passed for transmission, distribution, interconnection, transformation, or switching. A substation includes a variety of equipment: transformers, circuit breakers, load break switch, bus-bars, current transformers, potential transformers, and so on.The distribution substation is an assemblage of equipment for purpose of switching, changing, and regulating the voltage from subtranmission to distribution. More important substations are designed so that the failure of a piece of equipment in the substation or one of the subtranmission lines to the substation will not cause an interruption of power to the load.This paper introduces the design of main electricity system about the 10KV substation,and return fish-eye an electricity lord to connect the line diagram to take into the elucidation at the same time. We utilize the means of economy and technology comparing to select main electricity connect of the 10KV substation, and compute short current by the means of practical short current’s compute in the design . We design and select main equipment and conductor、plant network、plan of site and high voltage distribution equipment through checking designing handbook and technical code .That transformer substation has two main transformer of sets,choose single bus-bar structure.And return fish-eye an electricity lord、short current、choice and check of main equipment(include circuit breaker、load break switch、disconnect switch、current transformer、potential transformer ),introduce the relay protection and so on .Key words: 10KVdistribution substation; short current; transformers; relay protection给定条件1.电源和环境条件:由西王集团热电厂10KV双回路供电,正常情况下,一路工作,一路备用。
110kv变电所电气部分的设计--毕业设计
![110kv变电所电气部分的设计--毕业设计](https://img.taocdn.com/s3/m/f9e86fd327284b73f342506a.png)
110kv变电所电气部分的设计--毕业设计摘要本设计为建平变电所电气部分的设计(110 kV/10kV)。
本次设计的变电所是在当前建平县概况的前提下进行的,设计负荷充分的考虑到建平地区的工业及非工业情况,明确在变电所所有供电负荷中,哪些是一级负荷,哪些是二、三级负荷,并对相应的负荷采取不同的供电措施,以保证供电质量和供电的可靠性。
因本次设计的110KV变电所属于高压网络,该地区变电站所涉及方面多,考虑问题也多,在分析变电所担负的任务及用户负荷等情况下,慎重的进行选择所址。
充分利用用户数据进行负荷的统计和计算,确定对进行用户无功功率补偿装置,同时进行变电所主变压器的选择,使变电所在能满足当前供电负荷的情况下,同时能满足未来5-10年该地区的供电负荷。
考虑安全、可靠、灵活和经济,确定变电所的电气主接线的接线方式。
再进行短路电流计算,以便选择设计变电所的高低压电气设备和导线,同时对它们进行校验。
本变电站的初步设计包括了:(1)总体方案的确定(2)负荷计算(3)主变压器的选择(4)电气主接线的确定(5)高低压配电系统设计(6)继电保护(7)防雷与接地保护等内容。
随着电力技术高新化、复杂化的迅速发展,电力系统在从发电到供电的所有领域中,通过新技术的使用,都在不断的发生变化。
变电站作为电力系统中一个关键的环节也同样在新的技术领域得到了充分的发展。
关键词:变电站;负荷;主变压器;电气主接线;高低压电气设备AbstractThis design is a part of Jianping electrical substations excogitation(110 kV/10kV).The substation was designed on the basis of Jianping electrical power situation, think over the industry and non-industrial of Jianping district to design, according to thinking about what is the first class load ,the second class load and the third class load explicit about the load of the substation in Jianping. Using the different measures in line with the relevant the load situation to ensure the quality of power supply and service reliability of customers.Because of this design are high-voltage network 110KV substation, substation in the area in more involved, consider the problem more, substation in the analysis tasks and user load such circumstances, careful to choose the site. Make full use of user data for statistical and computing load, determine for reactive power compensation device users, at the same time the choice of main transformer substation, to meet the current electricity substation in the case of load, at the same time the next 5-10 years to meet the region's electricity load. Consider safety, reliability, flexibility and economy, to determine the electrical substation main connection of wiring. Further short-circuit current calculation, in order to choose the design of high voltage electrical substation equipment and wires, check them at the same time.The preliminary design of the substation including:(1)the overall scheme determined (2) load calculation (3) the choice of main transformer (4)Determination of Main Electrical Wiring (5)High and low voltage power distribution system design (6) lightning protection and grounding (7)Lightning protection and grounding .Key words:transformer substation; load; transformer; main electrical connection;high and low voltage electrical equipment目录第1章绪论 (1)1.1 概述 (1)1.2 课题来源及设计背景 (2)第2章变电站负荷计算和无功补偿计算 (4)2.1 变电站的负荷计算 (4)2.2 变电站无功补偿计算 (8)第3章主变压器台数和容量的选择 (10)3.1 变压器选择原则 (10)3.2 主变压器台数的选择 (10)第4章电气主接线的确定 (13)4.1 主接线方案比较 (13)4.2 电气主接线设计方案 (15)第5章短路计算 (19)5.1 短路电流的概述 (19)5.2 计算短路电流的目的 (19)5.3 短路电流计算的步骤 (20)第6章电气设备的选择与校验 (27)6.1 电气设备选择和校验的原则 (27)6.2 高压断路器的选择 (28)6.2.1 110kV电压级断路器 (28)6.2.2 10kV电压级断路器 (30)6.3 隔离开关的选择 (32)6.3.1 110kV侧隔离开关的选择 (32)6.3.2 10kV侧隔离开关的选择 (33)6.4 互感器的选择 (35)6.4.1 电流互感器的选择 (35)6.4.2 电压互感器的选择 (37)6.5 母线的选择 (38)6.6 各电气设备选择结果表 (40)第7章主变压器的继电保护设计 (41)7.1 继电保护的目的 (41)7.2 继电保护设计 (41)第8章防雷和接地保护设计 (49)8.1 变电所防雷设计 (49)8.2 变电所接地保护设计 (52)第9章结论 (54)参考文献 (55)致谢 (57)附录 (58)第1章绪论1.1概述能源是社会生产力的重要基础,随着社会生产的不断发展,人类使用能源不仅在数量上越来越多,在品种及构成上也发生了很大的变化。
110kV变电站设计(毕业设计,毕业论文)
![110kV变电站设计(毕业设计,毕业论文)](https://img.taocdn.com/s3/m/68804649a0116c175e0e481a.png)
题目:110kV变电站设计专业班级l 学生姓名学号摘要随着经济的发展和现代工业建设的迅速崛起,供电系统的设计越来越全面、系统,工厂用电量迅速增长,对电能质量、技术经济状况、供电的可靠性指标也日益提高,因此对供电设计也有了更高、更完善的要求。
设计是否合理,不仅直接影响基建投资、运行费用和有色金属的消耗量,也会反映在供电的可靠性和安全生产方面,它和企业的经济效益、设备人身安全密切相关。
变电站是电力系统的一个重要组成部分,由电器设备及配电网络按一定的接线方式所构成,他从电力系统取得电能,通过其变换、分配、输送与保护等功能,然后将电能安全、可靠、经济的输送到每一个用电设备的转设场所。
作为电能传输与控制的枢纽,变电站必须改变传统的设计和控制模式,才能适应现代电力系统、现代化工业生产和社会生活的发展趋势。
随着计算机技术、现代通讯和网络技术的发展,为目前变电站的监视、控制、保护和计量装置及系统分隔的状态提供了优化组合和系统集成的技术基础。
随着电力技术高新化、复杂化的迅速发展,电力系统在从发电到供电的所有领域中,通过新技术的使用,都在不断的发生变化。
变电所作为电力系统中一个关键的环节也同样在新技术领域得到了充分的发展。
[关键词]变电站输电系统配电系统高压网络补偿装置AbstractAlong with the economic development and the modern industry developments of quick rising, the design of the power supply system become more and more completely and system. Because the quickly increase electricity of factories, it also increases seriously to the dependable index of the economic condition, power supply in quantity. Therefore they need the higher and more perfect request to the power supply. Whether Design reasonable, not only affect directly the base investment and circulate the expenses with have the metal depletion in colour metal, but also will reflect the dependable in power supply and the safe in many facts. In a word, it is close with the economic performance and the safety of the people.The substation is an importance part of the electric power system, it is consisted of the electric appliances equipments and the Transmission and the Distribution. It obtains the electric power from the electric power system, through its function of transformation and assign, transport and safety. Then transport the power to every place with safe, dependable, and economical. As an important part of power’s transport and control, the transformer substation must change the mode of the traditional design and control, then can adapt to the modern electric power system, the development of modern industry and the of trend of the society life.Along with the high and quick development of electric power technique, electric power system then can change from the generate of the electricity to the supply the power.[key words] substation transmission system distributionhigh voltage network correction equipment.目录第1章原始资料及其分析 (3)1原始资料 (3)2原始资料分析 (4)第2章负荷分析 (5)第3章变压器的选择 (8)第4章电气主接线 (10)第5章短路电流的计算 (13)1短路电流计算的目的和条件 (13)2短路电流的计算步骤和计算结果 (14)第6章配电装置及电气设备的配置与选择 (17)1 导体和电气设备选择的一般条件 (17)2 设备的选择 (17)3 高压配电装置的配置 (18)第7章二次回路部分 (21)1 测量仪表的配置 (21)2 继电保护的配置 (21)第8章所用电的设计 (27)第9章防雷保护 (39)结束语 (41)致谢 (42)参考文献 (43)附录一:一次接线图附录二:10KV配电装置接线图绪论电力工业是国民经济的一项基础工业和国民经济发展的先行工业,它是一种将煤、石油、天然气、水能、核能、风能等一次能源转换成电能这个二次能源的工业,它为国民经济的其他各部门快速、稳定发展提供足够的动力,其发展水平是反映国家经济发展水平的重要标志。
毕业设计--10KV变电所电气部分初步设计
![毕业设计--10KV变电所电气部分初步设计](https://img.taocdn.com/s3/m/360c64ca33d4b14e85246898.png)
毕业设计说明书题目:10KV变电所电气部分初步设计专业:发电厂及电力系统班级:电力904班学号:姓名:指导老师:2011年11月18日前言毕业设计是高等工程教育最重要的实践性教学环节,它是由我们独立完成的一项综合性、创造性、设计性的大型作业。
开展毕业设计课题至关重要并具有深远的意义,不仅培养我们分析和解决各种实际问题的能力,也进一步巩固、深化和扩展所学的理论知识。
我们这次设计的主要内容是对某110kV降压变电站的电气部分进行初步设计,包括了:负荷统计分析、主变的选择、电气主接线方案选择、短路电流的计算、电气设备的选择和校验、防雷设施以及继电保护的选择等内容。
经过五个星期的努力,我终于完成了这次毕业设计。
在此过程中,我从对变电站的生疏,到了解,再到深入研究,我有了不少的收获:巩固了以前学的专业知识,并在以前的基础上理解的更加透彻,掌握的更加熟练;锻炼了自己的实际应用能力,将课本上学到的理论知识和实际生产联系了起来;增强了自己独立解决问题的能力以及团队合作精神,培养实事求是、全面科学、严肃认真的工作作风,为今后从事本专业工作打下坚实牢固的基础。
但由于时间和水平的局限,设计中难免会有不妥之处,敬请老师多批评指导。
2011年11月18日目录前言第1章原始材料 (6)1.1变电站基本资料................................................................ 错误!未定义书签。
1.2变电站负荷情况................................................................ 错误!未定义书签。
2.1负荷的概述 (1)2.1.1负荷分类..................................................................... 错误!未定义书签。
第2章主变压器的选择 (8)2.1概述 (8)2.2主变压器台数的原则及选择 (8)2.3主变压器容量的选择 (8)2.3主变压器形式的选择 (9)第3章电气主接线选择 (11)3.1概述 (11)3.2电气主接线的基本要求 (11)3.3变电站主接线基本接线方式 (11)3.4变电站主接线选择 (13)3.4.1 110kV侧主接线选择方案 (13)3.4.2 35kV侧主接线方案选择 (14)3.4.3 10kV侧主接线方案选择 (15)3.4.4 变电站主接线图 (15)3.4.5 变电站的站用电......................................................... 错误!未定义书签。
110kV变电站电气部分设计毕业设计
![110kV变电站电气部分设计毕业设计](https://img.taocdn.com/s3/m/e08f7ea64431b90d6d85c748.png)
毕业设计题目110kV变电站电气部分设计学院电力学院专业电气工程及其自动化姓名学号指导教师2010年5月31日水利水电学院本科生毕业设计任务书一、毕业设计的目的毕业设计是本科生培养方案中的重要环节。
毕业设计是在完成本专业全部课程的基础上,学生综合性地运用几年所学知识去分析、解决一个问题,使学生得到一次综合运用所学基本理论,基本知识和技能,进行工程设计或科学研究的初步训练,进一步培养学生分析、解决问题的能力。
能够让学生在作完毕业设计后,感到自己的实践动手、动笔能力得到锻炼,增强了即将跨入社会去竞争,去创造的自信心。
通过毕业设计应使学生达到下列要求:1、提高学生关于电力工业建设的政策观念和经济技术观点,以及对工程技术中的技术与经济问题能够进行较全面的综合分析能力。
2、学习变电站工程设计程序和方法,使学生进一步获得查阅文献,搜集资料,调查研究,综合分析,计算比较,设计制图和编写说明等多方面的训练。
3、使学生巩固和提高以往学习的理论和知识,进一步补充某些新的知识和基本技能,从而获得综合应用各种知识解决实际问题的锻炼,提高理论联系实际的能力。
二、主要设计容(一)电气一次部分1、电气主接线设计;2、短路电流计算及主要电气设备选择;3、配电装置设计。
(二)电气二次部分1、变压器的保护配置设计;2、变压器保护设计;3、变压器保护整定计算;三、重点研究问题1、电气主接线方案设计,包括方案论证(变压器选择、技术论证和经济比较);2、短路电流计算(包括三相短路电流计算与不对称短路电流计算);3、电气设备选择计算;4、变压器保护整定计算。
四、主要技术指标或主要设计参数设计的原始资料为满足乡镇负荷日益增长的需要,提高对用户供电的可靠性和电能质量,根据系统发展规划,拟建设一座110/35/10kV的区域性降压变电所,设计原始资料要求如下:1、电压等级:110/35/10kV2、设计容量:拟设计安装两台主变压器。
3、进出线及负荷情况:(1)、110kV侧,110kV侧进出线4回,其中两回为电源进线,每回最大负荷50000KVA,功率因数为0.85,一回停运后,另一回最大可输送100000KVA负荷;另2回为出线,本期拟建设一回,留一回作为备用出线间隔,出线正常时每回最大功率为35000kVA,最小为25000kVA,功率因数为0.85,最大负荷利用时间为4200h。
110kv-10kv变电所电气设计(工程、毕业设计参考)要点
![110kv-10kv变电所电气设计(工程、毕业设计参考)要点](https://img.taocdn.com/s3/m/d48b2b0402768e9951e738f8.png)
110kv/10kv变电所电气设计摘要:本文首先根据任务书上所给系统与线路及所有负荷的参数,分析负荷发展趋势。
从负荷增长方面阐明了建站的必要性,然后通过对拟建变电站的概括以及出线方向来考虑,并通过对负荷资料的分析,安全,经济及可靠性方面考虑,确定了110kV,10kV以及站用电的主接线,然后又通过负荷计算及供电范围确定了主变压器台数,容量及型号,同时也确定了站用变压器的容量及型号,最后,根据最大持续工作电流及短路计算的计算结果,对高压熔断器,隔离开关,母线,绝缘子和穿墙套管,电压互感器,电流互感器进行了选型,从而完成了110kV电气一次部分的设计一.变电所的地位和作用变电所是电力系统中变换电压、接受和分配电能、控制电力的流向和调整电压的电力设施,它通过其变压器将各级电压的电网联系起来。
变电所的主要作用是进行高底压的变换,一些变电站是将发电站发出的电升压,这样一方面便于远距离输电,第二是为了降低输电时电线上的损耗;还有一些变电站是将高压电降压,经过降压后的电才可接入用户。
对于不同的情况,升压和降压的幅度是不同的,所以变电站是很多的,比入说远距离输电时,电压为11千伏,甚至更高,近距离时为1000伏吧,这个电压经变压器后,变为220伏的生活用电,或变为380伏的工业用电。
本次设计的变电所属110kV、10kv负荷型变电所,主要满足该地区工业和居民用电。
二.变电所主变的选择主要考虑变压器的台数,容量;变压器的型式等。
(1)负荷分析机械厂和加工厂:他们的生产过程与电联系不是非常紧密,若中止供电,不会带来太大的损失,所以应属于二级负荷。
纺织厂1、2:若中断纺织厂的电力供应,就会引起跳线,打结,从而使产品不合格,所以应属于二级负荷。
药棉厂:药棉厂的生产过程伴随着许多化学反应过程,一旦电力供应中止了就会造成产品报废,造成极大的经济损失,所以应属于一级负荷。
10KV侧负荷大小S10KV=0.85[(1.5×2+1.2×2+1×2+2.5×2)/0.8] ×(1+5%)=11.6025 MVA在考虑15%的负荷发展余地,则有S10KV=11.6025×(1+15%)=13.343 MVA(2)变压器的容量和台数的选择根据变电站的实际情况,应根据以下的原则进行选择1)主变得容量一般按变电站建成后5~10年的规划负荷选择2)根据电压网络的结构和变电站所带的负荷的性质来确定主变的容量,对于有重要用户的变电站应考虑当一台主变停运时其余变压器在计及过负荷能力后的允许时间内,应。
110KV10KV变电所电气部分设计
![110KV10KV变电所电气部分设计](https://img.taocdn.com/s3/m/51c8834f59eef8c75fbfb3fa.png)
发电厂电气部分课程设计题目110/10KV变电所电气部分设计日期:2015.9.21目录●课程设计任务书----------------------------------------------------●110/10KV变电所设计说明书------------------------------------------❖1、简要说明所设计变电所在电力系统中的地位(终端);❖❖2、变电所主变压器的台数、容量、具体的型号;❖❖3、采用的主接线的形式[单母线分段(B所);❖❖4、其他高压电器:断路器、隔离开关、电流互感器、电压互感器的规格型号;●110/10KV变电所设计计算书------------------------------------------变电所选取110kv、10kv两个短路点,计算短路电流●110/10KV变电所设计主接线图●参考文献●感谢课程设计任务书1.课程设计应达到的目的通过本次课程设计,对所学课程的知识进行强化,提高学生分析问题和解决问题的能力,拉近课堂与工程设计的距离,使学生完全掌握变电所一次部分的设计过程、主接线和配电装置的初步设计、变电所主设备的选择方法等。
2.课程设计题目及要求110/10kV变电所电气部分设计一、设计内容1. 对待设计变电所在系统中的地位和作用及所供用户的分析。
2. 选择待设计变电所主变的台数、容量及型式。
3. 分析确定高低压主接线及配电装置型式4. 分析确定所用电接线型式。
5. 进行互感器的配置。
6. 进行选择设备和导体所必须的短路电流计算。
7. 选择变电所高、低压侧的断路器、隔离开关。
8. 设计10kV硬母线系统。
二、有关原始数据1.变电所有关资料(110/10kV)L1 20 km,L2 22 km,L3 19 km,L4 15 km。
2.环境温度年最高温度40℃,最热月最高平均气温32℃3.变电所10kV侧过电流保护动作时间为1秒4.110kV输电线路电抗按0.4Ω/km计5.发电厂变电所地理位置图(附图一)6.典型日负荷曲线(附图二)附图一发电厂变电所地理位置图G:汽轮机 QFQ-50-2,50MW COSφ=0.8,X〃d=0.124T:变压器SF7-40000/121±2×2.5%P o = 46kW PK= 174kW Io% = 0.8U K % = 10.5附图二典型日负荷曲线3、课程设计任务及工作量的要求〔包括课程设计计算说明书、图纸、实物样品等要求〕成品提交的设计文件和图纸要求:1.设计说明书1份2.设计计算书1份3.图纸1张:变电所主接线图110/10KV变电所设计说明书(1B)第一章所设计变电所在电力系统中的地位电力系统是由发电机、变压器、输电线路和用电设备(负荷)组成的网络,它包括通过电的或机械的方式连接在网络中的所有设备。
毕业设计:10kV变电所电气部分设计
![毕业设计:10kV变电所电气部分设计](https://img.taocdn.com/s3/m/41b69a300912a216147929e4.png)
目录摘要 (I)Abstract (II)1绪论 (1)1.1我国电力行业发展概况 (1)1.2变电所的类型概述 (1)1.3变电所电气设备概述 (2)1.4本次设计主要内容 (3)2负荷计算 (4)2.1负荷计算的目的和方法 (4)2.2负荷计算 (5)2.3无功功率补偿计算 (8)2.4电源进线方式设计 (12)2.5变电站主变压器的台数、容量及类型的设计 (12)2.6变电所形式的设计 (13)3电气主接线的设计 (15)3.1对电气主接线的基本要求 (15)3.2电气主接线的基本形式 (16)3.3主接线方案设计 (21)4短路电流计算和设备选择与校验 (22)4.1概述 (22)4.2短路电流计算 (22)4.3高低压电气设备的选择与校验 (31)5总结 (42)谢辞 ................................................................................................. 错误!未定义书签。
参考文献 . (43)附录1:外文资料翻译 (45)Ⅲ1绪论1.1我国电力行业发展概况我国电源建设发展迅速,我国电力行业持续快速发展。
近些年来,我国总发电装机容量和发电量已经连续十年位居世界第二位,随着总发电装机容量增长,增长率有所平缓,但仍保持了较高增长水平。
我国电网建设持续增长,长期以来,我国电力工业“重发轻供”,电网发展严重滞后于电源发展,表现为输变电建设严重滞后于电源建设,配电网建设滞后于主网建设,负荷中心受端电网建设滞后于送端电网建设,电网累计投资占电力投资的比例约30%左右,远低于发达国家50%以上的水平。
为解决此问题,国家今后将重点持续促进电网建设,以适应我国工业化及城市化建设的需要。
特高压电网建设及坚强智能电网规划促进我国电力系统高质量发展,1)特高压电网建设,按照国家电网公司的规划,未来将建成以特高压电网为骨干网架、各级电网协调发展的坚强国家电网。
110kV变电站一次部分电气设计电气工程及其自动化专业毕业设计论文
![110kV变电站一次部分电气设计电气工程及其自动化专业毕业设计论文](https://img.taocdn.com/s3/m/f364aa99680203d8ce2f2496.png)
毕业设计说明书110kV变电站一次部分电气设计毕业设计(论文)任务书姓名专业班级毕业设计(论文)题目110kV变电站一次部分电气设计毕业设计(论文)工作起止时间地点毕业设计(论文)的内容:1.分析原始资料,选择电气主接线选择主变压器的台数及容量,对初选2-4种电气主接线进行技术比较,淘汰较差的方案,保留较好的方案;2.计算短路电流;3.主要电气设备选择及校验;毕业设计(论文)的要求:1、完成设计内容,要求方案设计论证充分,设备选择合理,计算准确。
2、撰写毕业论文1份,正文字数在12000左右,要求有规范的目录和参考文献,其它参照成教学院的文件要求。
3、绘制电气主接线图1张。
毕业设计(论文)工作进度计划:2010年6月17日~ 2010年9月25日:收集资料,形成论文总体框架,完成中期审查。
2010年9月26日~ 2010年11月5 日:完成论文最终稿。
本任务书于 2010 年 6月 17 日发出,毕业设计(论文)应于 2010 年11月 5 日前完成,由指导老师审阅后,提交毕业设计(论文)指导小组进行答辩。
指导教师制定年月日毕业设计(论文)指导小组组长制定年月日办学单位负责人制定年月日毕业设计(论文)评语1、指导教师评语:本论文根据某地区的用电需求及电力系统的可靠性、经济性要求,按照给出的原始资料和供应电能的相关情况,设计出能够满足负荷增长需要的运行灵活、检修维护安全方便、接线简单清晰、操作方便、投资少、运行费用低和有扩建可能性的变电站主接线方案,并通过短路电流计算,选择和校验其他电气设备。
该论文选题符合电力系统工程实际需要,结构合理,数据资料充分,写作进度安排合理,文字表达较流畅,已达到毕业设计(论文)水平。
指导教师签名年月日2、评阅教师评语:随着对电力系统电能质量、发供电可靠性、技术经济指标等的相关要求的日益提高,变电站的规划设计成为电网发展的关键一环,并将进一步影响到整个社会的稳定和国民经济的发展。
毕业设计说明书-110kV变电站电气部分设计
![毕业设计说明书-110kV变电站电气部分设计](https://img.taocdn.com/s3/m/03701abacaaedd3382c4d3ca.png)
110kV变电站电气部分设计第一篇:毕业设计说明书第一章变电站总体分析第一节变电站的基本知识一.变电站的定义变电站是联系发电厂和用户的中间环节,起着变换和分配电能的作用,是进行电压变换以及电能接受和分配的场所。
二.变电站的分类1、根据变电站的性质可分为升压和降压变电站(1)升压变电站是将发电厂发出的电能进行升压处理,便于大功率和远距离输送。
(2)降压变电站是对电力系统的高电压进行降压处理,以便电气设备的使用。
2、变电所根据变电站在系统中的地位,可分为枢纽变电站、区域变电站和用户变电站(1)枢纽变电所。
位于电力系统的枢纽点,连接电力系统高压和中压的几个部分,汇集多个电源,电压为330~500KV的变电所,称为枢纽变电所。
全所停电后,将引起系统解列,甚至出现瘫痪。
(2)中间变电所。
高压侧以交换潮流为主,起系统交换功率的作用,或使长距离输电线路分段,一般汇集2~3个电源,电压为220~330KV,同时又降压供当地用电,这样的变电所起中间环节的作用,所以叫中间变电所。
全所停电后,将引起区域电网解列。
(3)地区变电所。
高压侧一般为110~220KV,向地区用户供电为主的变电所,这是一个地区或城市的主要变电所。
全所停电后,仅使该地区中供电停电。
(4)终端变电所。
在输电线路的终端,接近负荷点,高压侧电压为110KV,经降压后直接向用户供电的变电所,即为终端变电所。
全所停电后,只是用户受到损失。
第二节所设计变电站的总体分析变电站电气一次部分的设计主要包含:负荷的分析计算、变压器的选型、主接线的设计、无功补偿、短路电流的计算、电气设备的选型和校验、母线的选择和校验等有关知识。
因此,变电站的总体分析也应该从这几个方面着手。
1、由待设计变电站的建设性质和规模可知,所设计变电站主要是为了满足某铁矿生产生活的发展需要,是一个110/10kv降压变电站,也是一个地区性变电站,并且只有两个电压等级,因此,主变压器可选用双绕组型的。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
110kv/10kv变电所电气设计摘要:本文首先根据任务书上所给系统与线路及所有负荷的参数,分析负荷发展趋势。
从负荷增长方面阐明了建站的必要性,然后通过对拟建变电站的概括以及出线方向来考虑,并通过对负荷资料的分析,安全,经济及可靠性方面考虑,确定了110kV,10kV以及站用电的主接线,然后又通过负荷计算及供电范围确定了主变压器台数,容量及型号,同时也确定了站用变压器的容量及型号,最后,根据最大持续工作电流及短路计算的计算结果,对高压熔断器,隔离开关,母线,绝缘子和穿墙套管,电压互感器,电流互感器进行了选型,从而完成了110kV电气一次部分的设计一.变电所的地位和作用变电所是电力系统中变换电压、接受和分配电能、控制电力的流向和调整电压的电力设施,它通过其变压器将各级电压的电网联系起来。
变电所的主要作用是进行高底压的变换,一些变电站是将发电站发出的电升压,这样一方面便于远距离输电,第二是为了降低输电时电线上的损耗;还有一些变电站是将高压电降压,经过降压后的电才可接入用户。
对于不同的情况,升压和降压的幅度是不同的,所以变电站是很多的,比入说远距离输电时,电压为11千伏,甚至更高,近距离时为1000伏吧,这个电压经变压器后,变为220伏的生活用电,或变为380伏的工业用电。
本次设计的变电所属110kV、10kv负荷型变电所,主要满足该地区工业和居民用电。
二.变电所主变的选择主要考虑变压器的台数,容量;变压器的型式等。
(1)负荷分析机械厂和加工厂:他们的生产过程与电联系不是非常紧密,若中止供电,不会带来太大的损失,所以应属于二级负荷。
纺织厂1、2:若中断纺织厂的电力供应,就会引起跳线,打结,从而使产品不合格,所以应属于二级负荷。
药棉厂:药棉厂的生产过程伴随着许多化学反应过程,一旦电力供应中止了就会造成产品报废,造成极大的经济损失,所以应属于一级负荷。
10KV侧负荷大小S10KV=0.85[(1.5×2+1.2×2+1×2+2.5×2)/0.8] ×(1+5%)=11.6025 MVA在考虑15%的负荷发展余地,则有S10KV=11.6025×(1+15%)=13.343 MVA(2)变压器的容量和台数的选择根据变电站的实际情况,应根据以下的原则进行选择1)主变得容量一般按变电站建成后5~10年的规划负荷选择2)根据电压网络的结构和变电站所带的负荷的性质来确定主变的容量,对于有重要用户的变电站应考虑当一台主变停运时其余变压器在计及过负荷能力后的允许时间内,应保证用户的一级和二级的负荷,对一般性变电站,一台机停用时,应使其余变压器保证全部负荷的70%~80%3)同级电压的降压变压器容量的级别不宜过多,应系列化,标准化4)对于大城市市郊的一次变电站,在中低压侧已构成环网的基础上,变电所以装设两台变压器为宜有以上原则可知,此变电所单台主变的容量为:S=ΣS2*0.8=13.343 ×0.8=10.6744 MVA所以应选容量为20000KVA的主变压器SFPSL—20000/110(S 三相 FP 强迫油循环风冷)(3)变压器绕组形式选择根据:不受运输条件限制时,在330kv及其以下的发电厂和变电所中,均采用三相变压器(4)变压器绕组数量的选择根据:在具有三种电压的变电站中,如通过主变各侧的功率均达到该主变容量的15%及以上,或低压侧虽无负荷,但在变电所内需装设无功功率补偿设备时,主变宜采用三绕组变压器(5)绕组连接方式根据:我国110kv及以上的电压级别,变压器绕组均用y0的接法,35kv用y连接,其中性点过消弧线圈接地。
三.主接线形式现代电力系统是一个巨大的、严密的整体。
各类发电厂、变电站分工完成整个电力系统的发电、变电和配电的任务。
其主接线的好坏不仅影响到发电厂、变电站和电力系统本身,同时也影响到工农业生产和人民日常生活。
因此,发电厂、变电站主接线必须满足以下基本要求。
1 运行的可靠断路器检修时是否影响供电;设备和线路故障检修时,停电数目的多少和停电时间的长短,以及能否保证对重要用户的供电。
2 具有一定的灵活性主接线正常运行时可以根据调度的要求灵活的改变运行方式,达到调度的目的,而且在各种事故或设备检修时,能尽快地退出设备。
切除故障停电时间最短、影响范围最小,并且再检修在检修时可以保证检修人员的安全。
3 操作应尽可能简单、方便主接线应简单清晰、操作方便,尽可能使操作步骤简单,便于运行人员掌握。
复杂的接线不仅不便于操作,还往往会造成运行人员的误操作而发生事故。
但接线过于简单,可能又不能满足运行方式的需要,而且也会给运行造成不便或造成不必要的停电。
4 经济上合理主接线在保证安全可靠、操作灵活方便的基础上,还应使投资和年运行费用小,占地面积最少,使其尽地发挥经济效益。
5应具有扩建的可能性由于我国工农业的高速发展,电力负荷增加很快。
因此,在选择主接线时还要考虑到具有扩建的可能性。
变电站电气主接线的选择,主要决定于变电站在电力系统中的地位、环境、负荷的性质、出线数目的多少、电网的结构等。
110kv接线的选择方案一单母线分段接线优点:1、母线发生故障时仅故障母线停止供电非故障母线仍可继续工作,缩小母线故障影响范围。
2、对双回路供电的重要用户,可将双回路接于不同的母线段上,保证对重要用户的供电。
缺点:当一段母线故障或检修时,必须断开在该段上的全部电源和引出线,这样减少了系统的供电量,并使该回路供电的用户停电。
方案二桥行接线110kv侧以双回路与系统相连,而变电站最常操作的是切换变压器,而与系统连接的线路不易发生故障或频繁切换,因此可采用内桥接线,这也有利于以后变电站的扩建。
优点:高压电器少,布置简单,造价低,经适当布置可较容易地过渡成单母线分段或双母线分段。
缺点:可靠性不是太高,切换操作比较麻烦。
方案三双母线接线优点:1、供电可靠,通过两组母线隔离开关得到换操作,可以轮流检修一组母线而不至于供电中断,一组母线故障后能迅速恢复供电,检修任一组的母线隔离开关时只停该回路。
2、扩建方便,可向双母线的左右任何一个方向扩建,均不影响两组母线的电源和负荷的平均分配,不会引起原有回路的停电,以至连接不同的母线段,不会如单母线分段那样导致交叉跨越。
3、便于试验,当个别回路需要时单独进行试验时可将该架路分开,单独接至一组母线上。
缺点:1,增加一组母线和每回路需增加一组母线隔离开关,投资大。
2,当母线故障或检修时,隔离开关作为倒换操作电气容易误操作,为了避免隔离开关误操作须在隔离开关和断路器之间装设连锁装置。
对于110kv侧来说,因为它邀功给较多的一类,二类负荷,因此其要求有较高的可靠性。
对此以上三种方案,从经济上,可靠性等多方面因素考虑,最佳设计方案为方案二,具有一定的可靠性和扩展性,而且比双母线投资小。
10kv侧接线选择方案一单母线接线优点:接线简单、清晰,采用设备少,操作方便,便于扩建。
缺点:运行不够灵活、可靠,任一元件故障、检修都要使整个配电装置停电。
方案二单母线分段接线接线简单、操作方便、运行经济等优点,在一定程度上克服了单母线的缺点,提高了系统供电可靠性。
是目前中间变电所最常用的主接线方式。
方案三单母线分段带旁路接线是在单母线分段基础上增加旁路母线和旁路闸刀。
其主要作用是减少母线故障或断路器检修时停电范围,提高系统供电可靠性。
在正常运行方式下,旁路母线不带电,类似于单母线分段运行方式。
当需要检修断路器时,可合上旁路断路器和相应的旁路闸刀,然后断开需要检修的断路器和二侧闸刀。
优点:其操作方式简单,也不影响相应电气设备正常运行对以上三种方案,单母线接线可靠性低,当母线故障时,各出线需全部停电,不能满足1,2类负荷供电性的需求,故不采用,将1,2类负荷的双回电源线不同的分段母线上,当其中一段母线故障时,有另一段母线提供电源,从而保证供电可靠性,虽然分段断路器兼做旁路断路器的单母线分段也能满足要求,但其投资大,经济性能差,故采用方案二单母线分段接线。
主接线图如下所示四.互感器的配置1、电压互感器的配置(1)电压互感器的数量和配置与主接线方式有关,并应满足测量、保护、同期和自动装置的要求。
电压互感器的配置应能保证在运行方式改变时,保护装置不得失压,同期点的两侧都能提取到电压。
(2)6—220KV电压等级的每组母线的三相上应装设电压互感器。
旁路母线上是否需要装设电压互感器,应视各回出线外侧装设电压互感器的情况和需要确定。
(3)当需要监视和检测线路侧有无电压时,出线侧的一相上应装设电压互感器。
(4)当需要在330KV及以下主变压器回路中提取电压时,可尽量利用变压器电容式套管上的电压抽取装置。
(5)发电机出口一般装设两组电压互感器,供测量、保护和自动电压调整装置需要。
当发电机配有双套自动电压调整装置,且采用零序电压式匝间保护时,可再增设一组电压互感器。
2、电流互感器的配置(1)凡装有断路器的回路均应装设电流互感器其数量应满足测量仪表、保护和自动装置要求。
(2)在未设断路器的下列地点也应装设电流互感器:发电机和变压器的中性点、发电机和变压器的出口、桥形接线的跨条上等。
(3)对直接接地系统,一般按三相配置。
对非直接接地系统,依具体要求按两相或三相配置。
(4)一台半断路器接线中,线路—线路串可装设四组电流互感器,在能满足保护和测量要求的条件下也可装设三组电流互感器。
线路—变压器串,当变压器的套管电流互感器可以利用时,可装设三组电流互感器。
五.短路电流的计算设BS=100MV A,BV=Vav,则等值网络中的各电抗的标幺值如下:525.020100105.064.02510016.04321=⨯===⨯==xxxx263.0201001005.1021151.01151004.050121.01151004.040181.01151004.060212.01151004.070067.0115100401.022210928272625=⨯⨯==⨯⨯===⨯⨯==⨯⨯==⨯⨯==⨯⨯=Txxxxxxx076.02/151.02/067.0)2121//(91331514====+=xxxxxx110KV侧短路计算:(1)三角型-----星型043.0121.0181.0212.0121.0181.0050.0121.0181.0212.0121.0212.0075.0121.0181.0212.0181.0212.0876871787686168767615=++⨯=++==++⨯=++==++⨯=++=xxxxxxxxxxxxxxxxxx(2)星型-----三角型052.0100252104.025229.1283.428.1283.41153100104.01104.0207.0208.0207.0208.0//207.0)()(208.0)()(""191819181918151417161317161319161317151417151418=⨯⨯=⨯==⨯⨯===⨯⨯===+⨯=+===+++++==+++++=∑∑∑BfjhimishBffSxXKAIKIKAIxEIxxxxxxxxxxxxxxxxxxxxxxxxx计算电抗:冲击电流:起始次暂态电流:则有10KV侧短路计算:(1) 三角型-----星型043.0121.0181.0212.0121.0181.0050.0121.0181.0212.0121.0212.0075.0121.0181.0212.0181.0212.0876871787686168767615=++⨯=++==++⨯=++==++⨯=++=xxxxxxxxxxxxxxxxxx(2)串联合并306.0263.0043.0126.0050.0076.0142.0075.0067.01720161319151418=+=+==+=+==+=+=Txxxxxxxxx(3)星型-----三角型474.3142.0306.0126.0306.0126.0004.4126.0306.0142.03063.0142.0182019201922192018201821=+++=+++==+++=+++=xxxxxxxxxxxx860.1004.4474.3004.4474.3//2221=+⨯==∑xxxf93.0100502860.1252524.7956.228.12956.205.13100860.11""=⨯⨯=⨯==⨯⨯===⨯⨯==∑∑BfjsimishBfSxXKAIKIKAIxEI计算阻抗:冲击电流为:则起始电流为:六.主要电气设备选择由于电气设备和载流导体得用途及工作条件各异,因此它们的选择校验项目和方法也都完全不相同。