受弯、偏压构件计算例题
偏心受压构件承载力计算例题
![偏心受压构件承载力计算例题](https://img.taocdn.com/s3/m/61c3c24367ec102de3bd8913.png)
13
6.验算垂直于弯矩作用平面的承载力
l0/b=2500/300=8.33>8
1
1 0.002 (l0 / b 8)2
1
1 0.002(8.33 8)2
=0.999 Nu =0.9[(As+As′)fy′+Afc]
=0.9×0.999[(1375+1375) ×300+300×500×11.9]
40)
198
为大偏心受压。
4
(4)求As=Asˊ
e
ei
h 2
as
(1.024 59
400 2
40)mm
771mm
x
=90.3mm
>2a
' s
=80mm,
则有
Asˊ=As=
Ne
1
f cbx h0
x 2
f
y
h0
as
260 103
460
0.55
(0.8 0.55)(460 40)
=0.652
12
x h0
=0.652×460=299.9mm
5.求纵筋截面面积As、As′
As=As′=
Ne 1 fcbx(h x / 2)
f
' y
(h0
as'
)
1600 103 342.5 1.0 11.9 300 299.9(500 299.9 / 2) 300 (460 40)
=2346651N>N=1600kN
偏心受压构件承载力计算例题
![偏心受压构件承载力计算例题](https://img.taocdn.com/s3/m/583317ac915f804d2a16c173.png)
【解】fc=11.9N/mm2,fy=
1 =1.0, 1 =0.8
1.求初始偏心距ei
f
= 300N/mm2,
y
b=0.55,
M e0= N
180103 112.5 1600
ea=(20,
h 30
)= max (20, 500
30
)=20mm
ei=e0+ea=112.5+20=132.5mm
3 0 0 (4 6 0 4 0 ) =1375mm2
6.验算垂直于弯矩作用平面的承载力
l0/b=2500/300=8.33>8
1
10.00(l20/b8)2源自10.002(18.338)2
=0.999 Nu =0.9[(As+As′)fy′+Afc]
=0.9×0.999[(1375+1375) ×300+300×500×11.9]
=1235mm2
(5)验算配筋率
As=Asˊ=1235mm2> 0.2%bh=02% ×300×400=240mm2, 故配筋满足要求。
(6)验算垂直弯矩作用平面的承载力
lo/ b=3000/300=10>8
1
10.00(l20/b8)2
10.0021(108)2
=0.992
Nu =0.9φ[fc A + fyˊ(As +Asˊ)] =0.9×0.992[9.6×300×400+300(1235+1235)]
eo=M/N=150×106/260×103=577mm ea=max(20,h/30)= max(20,400/30)=20mm ei=eo+ea = 577+20=597mm
圆形截面偏心受压(受弯)构件均匀配筋计算
![圆形截面偏心受压(受弯)构件均匀配筋计算](https://img.taocdn.com/s3/m/29b74cdc5022aaea998f0f02.png)
一、计算参数注:后缀s表示砼材料性质按水(海)工规范取值注:本表格只适用于热轧钢筋二、配筋计算均匀配筋圆形截面偏心受压(受弯)构件的配筋根据《混凝土结构设计规范》(GB 50010-2002)7.3.8 条计算轴向力偏心距 e 0=M / N 14250mm 附加偏心距 e a 40mm初始偏心距 e i =e 0+e a 14290mm 截面曲率修正系数 ζ1 1.0长细比对截面曲率影响系数 ζ2 1.0偏心距增大系数 η 1.006解上面的联立方程可得:全部纵向钢筋截面面积 As =22022受压区砼截面圆心角与2π的比值 α =0.287受拉纵筋与全部纵筋面积的比值 αt =0.676实际选用40根直径d=32mm 的钢筋实际配筋面积32170mm 2三、裂缝计算圆形截面偏心受压(受弯)构件最大裂缝宽度根据《港口工程灌注桩设计与施工规程》(JTJ 248-2001)附录B 计算最大裂缝宽度限值[W max ] =0.25mm构件受力特征系数α1=0.9钢筋表面形状影响系数α2= 1.0荷载长期效应组合影响系数α3= 1.5桩身截面配筋率ρ= 2.84%受压区砼截面圆心角之半φ= 1.33受拉区边缘纵向钢筋应力σsl =304.4最大裂缝宽度0.226mm 圆形截面偏心受压(受弯)构件均匀配筋计算)()()(38.3.7225.128.3.7sin sin sin 3218.3.7)(22sin 1311--=-++≤--+⎪⎭⎫⎝⎛-≤ααππαπαππααηααπαπαααt ts s y c i s y t c r A f Ar f e N A f A f N =⎪⎪⎭⎫⎝⎛++=ρσααα1028.030321max s s sl d E W。
钢结构计算例题(轴压、受弯、拉弯与压弯)
![钢结构计算例题(轴压、受弯、拉弯与压弯)](https://img.taocdn.com/s3/m/a7fcc39b0722192e4436f6ad.png)
Cl4轴压构件例题例1:下图所示为一轴心受压柱的工字形截面,该柱承受轴心压力设计值N=4500kN 计算长度为 l ox =7m,l oy =3.5m,钢材为 Q235BF f =205N / mm 2,验算 该柱的刚度和整体稳定性。
A = 27500mm 2, I x = 1.5089咒109mm 4, I y =4.1667x108mm 4,[X ] =150。
z 15 20 25 30 35 40 45 <p0.9830.9700.9530.9360.9180.8990.8781 hg iiay 誘i1y Lrt1 xi20 J :500Iso=_ =192.3N / mm 2 < f =205N / mm0.93^27500例 2:右图示轴心受压构件,l x = 2.54>M04cm 4 , I y = 1.25咒 lO 'cm 4 , A = 8760 cm 2, I =5.2m ,Q235钢,截面无削弱,翼缘为轧制边。
问:(1)此柱的最大承载力设 计值N?( 2)此柱绕y 轴失稳的形式?( 3)局部稳定是否满足要求?n解: i x " xV A =234.2mm ,i yb =l23.1mm A刚度验算:几1oxi x= 2000=29.9234.2loyi y型0=28.4 123.1r'■max= 29.9 <[X ] =150整体稳定算:当A =29.9时,护=0.936A解:(1)整体稳定承载力计算对x轴:l ox =l =5.2mi X = j I x/A = J2.54x 10 /87.6 = 17cm 殘=l0x/i x = 520/17 = 30.6 兰[几]=150 翼缘轧制边,对x轴为b类截面,查表有:护x=0.934N x=q\Af =0.934X8760X215X10」=1759kN 对y 轴:l0y=1 /2 =2.6mi y= JQ^ = J1.25x10787.6 = 3.78cm A y = l0y/i y=520/3.78 =68.8 <[A] = 150翼缘轧制边,对y轴为c类截面,查表有: 护y =0.650N y Ny Af =0.65X8760X215X10」=1224kN于稳定承载力,故构件的最大承载力为:由于无截面削弱,强度承载力高N max =N y =1224kN (2)绕y轴为弯扭失稳(3)局部稳定验算/■max —max{k x'iu y} —68.8,30 兰'"max —100 1)较大翼缘的局部稳定d/t =95/14 =6.79 <(10+0.1A max)j235f y= (10+ 0.1 咒68.8)J235/235 = 16.88 , 可2)腹板的局部稳定h o/t w =400/10 =40 <(25 +0.5几max)j235f y =(25 +0.5咒68.8)J235/235 = 59.4 ,可例3:下图所示轴心受压格构柱承受轴力设计值N=800kN计算长度l ox=l oy=10m 分肢采用 2 [25a:A=2X 34.91 = 69.82cm2, i y=9.81cm,l 1=175.9cm4, i1=2.24cm, y1=2.07cm,钢材为Q235BF缀条用L45X 4, A=3.49cm2。
偏心受压构件承载力计算例题[详细]
![偏心受压构件承载力计算例题[详细]](https://img.taocdn.com/s3/m/5f83d565195f312b3069a557.png)
【解】fc=11.9N/mm2,fy=
1=1.0, 1 =0.8
1.求初始偏心距ei
f
= 300N/mm2,
y
b=0.55,
M e0= N
180103 112.5 1600
ea=(20,
h 30
)= max (20,
500 30
)=20mm
ei=e0+ea=112.5+20=132.5mm
2.求偏心距增大系数η
=0.652
x h0
=0.652×460=299.9mm
5.求纵筋截面面积As、As′
As=As′=
Ne 1 fcbx(h x / 2)
f
' y
(h0
as'
)
1600 103 342.5 1.0 11.9 300 299.9(500 299.9 / 2) 300 (460 40)
l0/h=
2500 500
=5≤5,故η=1.0
3.判别大小偏心受压
h0=h-40=500-40=460mm
x=
N
1600103
1 fcb 1.011.9 300
=448.2 mm>ξbh0=0.55×460=253 mm
属于小偏心受压构件。
4.重新计算x e=ηei+-as=1.0×132.5+-40=342.5mm
x 2
f y h0 as
260 103
7711.09.6300 90.3360
90.3 2
300360 40
=1235mm2
(5)验算配筋率
As=Asˊ=1235mm2> 0.2%bh=02% ×300×400=240mm2, 故配筋满足要求。
混凝土结构-偏压构件计算练习
![混凝土结构-偏压构件计算练习](https://img.taocdn.com/s3/m/13d93b024a7302768e993938.png)
4
C = − Ne′ − f y As
′) β1 (h0 − as β1 − ξb 360 × 804 × 0.8 × (750 − 50) = −1335.5 × 106 0.8 − 0.518
= −4180 × 103 × 182 − x=
− B ± B 2 − 4 AC −600457 ± 600457 2 + 4 × 3575 × 1335.5 × 106 = = 533mm 2A 2 × 3575 x = 533mm < (2 β1 − ξb )h0 = (2 × 0.8 − 0.518) × 750 = 811.5mm e = ei + 800 h − as = 168 + − 50 = 518mm 2 2
h 800 − ei − as' = − 168 − 50 = 182mm ( (注:此处计算不能错, ei = e0 + ea ) 2 2
采用参数方程 Ax 2 + Bx + C = 0 A = 0.5 × α1 f c b = 0.5 ×1.0 × 14.3 × 500 = 3575 ′ as h0 ′ + f y As B = −α1 f cbas β1 − ξb 1− = −1×14.3 × 500 × 50 + 360 × 804 × (1 − 50 ) 750 = 600457 0.8 − 0.518
' 即 x < 2as' , 说明破坏时 AS 不能达到屈服强度,近似取 x = 2as' 计算 As
h 500 e' = ei − + as' = 407 − + 40 = 197mm 2 2 Ne' 324 × 103 × 197 As = = = 422mm 2 ' f y (h0 − as ) 360 × (460 − 40) > As ,min (= ρ min bh = 0.002 × 400 × 500 = 400mm2 ) (注:此处验算最小配筋率计算不能少) (5).配筋 选3 16 ( AS = 603mm 2 )
第六章受弯构件典型例题_钢结构
![第六章受弯构件典型例题_钢结构](https://img.taocdn.com/s3/m/79055c35f111f18583d05abb.png)
360
3m
3m
3m
3m 10
M图(KN·m) 1396 1446 483 468.3 V 图 ( KN) 474 465.3 163.8 155.1 1861.2 1915.8 1396 1446
155.1 155.1 163.8 465.3 474
155.1
468.3 483
【解答】 分析: (1)选择工字形焊接组合梁截面的步骤是先确定腹板高度和厚度,即 h0 和 t w ; 再确定翼缘板的宽度和厚度,即 b 和 t 。确定腹板高度时,除考虑经济要求外,还应注意满 足刚度要求;满足局部稳定要求外,还应注意满足抗剪强度要求。 (2)选择截面后,应进行强度、刚度和整体稳定的验算。强度验算时,应注意在集中 力作用的跨中截面除进行抗弯强度验算外,还应进行腹板高度处折算应力的验算。抗剪强度 和刚度,因在选择截面时已满足要求,可不再进行验算。整体稳定验算时应考虑梁跨中有侧 向支承后,受压翼缘的自由长度是实际侧向支承点的距离。 1.内力计算 跨中截面:
(200 − 8) b 96 2 (1) 翼缘: 1 = =截面满足局部稳定要求。
h0 800 = = 100 tw 8
80<
受弯构件——例题
![受弯构件——例题](https://img.taocdn.com/s3/m/7a9bd10ebb68a98271fefa69.png)
梁支座截面中性轴以上(或以下)毛截面对中和轴的面积矩:
S x = 15 × 12.5 = 632.5mm 3
Steel Structure
梁支座截面中性轴处剪应力:
τ max
Vmax S x 198 ×103 × 632.5 ×103 = = =56.2N/mm 2 < f v = 180N/mm 2 27843 ×104 × 8 I xtw
抗剪强度 满足要求
(3)腹板局部承压强度 由于在支座反力作用处设置了支承加劲肋,因而不必验算腹板局部承压强度。 (4)刚度计算 正常使用极限状态下钢梁上的荷载效应组合: qk = σ GK + σ Q1K = 20 + 30 = 50kN/m 梁跨中的最大挠度:
5 qk l 4 5 × 50 × 60004 l ⋅ = = 14.7mm< [ν T ] = = 24mm υT = 384 EI x 384 × 206 ×103 × 27843 ×104 250 5 qk l 4 5 × 30 × 60004 l υQ = ⋅ = = 8.8mm< ν Q = 3 4 300 = 20mm 384 EI x 384 × 206 ×10 × 27843 ×10
永久荷载效应控制的组合:
q = γ Gσ GK + ∑ γ Qiψ ciσ QiK = 1.35 × 20 + 1.4 × 0.7 × 30 = 56.4kN/m
i =1
n
故取可变荷载效应控制的组合: q = 66kN/m 1 1 M x max = ql 2 = × 66 × 62 = 297kN ⋅ m 梁的跨中最大弯矩为: 8 8
l ν Q = 300
钢材的弹性模量: E = 206 × 103 N/mm 2 (1)抗弯强度计算-验算跨中截面受拉或受压边缘纤维处 承载能力极限状态下钢梁上的荷载效应组合: 可变荷载效应控制的组合:
受弯构件例题
![受弯构件例题](https://img.taocdn.com/s3/m/2d919465561252d380eb6e82.png)
受弯构件一.强度计算(抗弯、抗剪、局部承压、复杂应力)1.已知简支轨道梁承受动力荷载,其最大弯矩设计值Mx=440KNm,采用热轧H 型钢H600×200×11×17制作,Ix=78500×104mm4,W nx=W x=2610×103mm3,钢材为Q235。
验算受弯承载力。
2.抗剪强度计算例题:某焊接工字形等截面简支楼盖梁,截面尺寸如图所示,无削弱,为Q345钢。
梁的剪力设计值:支座截面V max=224.22KN,跨中截面处V=214.5KN。
要求验算该梁的抗剪强度。
3.局部承压强度计算例题:某热轧普通工字钢简支梁如图所示,型号为I36a,跨度为5m,梁上翼缘作用有均布荷载其设计值为q=36KN/m(包括自重),该梁为支承于主梁顶上的次梁,未设加劲肋。
支承长度a=100mm,t w=10mm,h y=t+r,此处t=15.8mm,r=12.0mm,钢材为Q235,f=215N/mm2。
验算此梁的局部承压强度。
4.复杂(折算)应力强度的计算例题:如图所示一焊接组合截面吊车梁,钢梁截面尺寸如图所示。
吊车为重级工作制(A7),吊车轨道型号为QU100,轨道高度为150mm,吊车最大轮压F=355KN,吊车竖向荷载动力系数为1.1,可变荷载分项系数为1.4,车轮作用处最大弯矩设计值为M=4932KNm,对应的剪力设计值为316KN,吊车梁采用Q345-B钢,I nx=2.433×1010mm4。
求车轮作用处钢梁的折算应力。
二.整体稳定计算1.轧制工字钢梁的整体稳定计算例题:某轧制工字钢简支梁,型号为I50a,Wx=1860cm3,跨度为6m,梁上翼缘作用均布永久荷载g k=10KN/m(标准值,含自重)和可变荷载q k=2510KN/m (标准值),跨中无侧向支承。
钢材为Q235。
验算此梁的整体稳定。
例题:一焊接工字形截面简支主梁如图所示,截面无扣孔,跨度为12.75m。
大小偏压构件算例
![大小偏压构件算例](https://img.taocdn.com/s3/m/2492f790e53a580216fcfea4.png)
[例 5.11] 钢筋混凝土偏心受压柱,截面尺寸b =500mm ,h =500mm ,40mm s sa a '==。
柱承受轴向压力设计值N =210kN ,柱两端截面弯矩设计值1280kN mM =⋅,2310kN m M =⋅。
柱挠曲变形为单曲率。
弯矩作用平面内柱上下两端的支撑长度为4.4m ;弯矩作用平面外柱的计算长度l 0=5.5m 。
混凝土强度等级为C35,纵筋采用HRB400级钢筋。
采用对称配筋,求受拉和受压钢筋。
解:2360N /mm y y f f '==;216.7N /mm c f =。
(1) 二阶效应的考虑122800.9030.9310M M ==> 所以应考虑二阶效应的影响。
120.70.30.70.30.9030.971m M C M =+=+⨯= 50016.7mm<20mm 3030h ==,取=20mm a e 30.50.516.75005009.9421010c c f A N ξ⨯⨯⨯===⨯,取 1.0c ξ= 220111300c ns c a l M h e N h ηξ⎛⎫=+ ⎪⎛⎫⎝⎭+ ⎪⎝⎭ 231440011 1.01850031010130020210460⎛⎫=+⨯= ⎪⎛⎫⨯⎝⎭+ ⎪⎝⎭0.971 1.0180.989 1.0m ns C η=⨯=<,取 1.0m ns C η=2310kN m M M ==⋅(2) 判别偏心受压类型30121010mm=25mm<238mm 116.7500b c N x h a f b ξ⨯===⨯⨯ 判定为大偏心受压,但<280mm sx a '= (3) 计算钢筋面积60331010201496mm 21010i a a M e e e e N ⨯=+=+=+=⨯50050014961496401286mm 222i s s h e e a a '''=-+=-+=-+= ()()3220210101286mm 1748mm 36046040s s y sNe A A f h a '⨯⨯'===='-⨯- 选用5根直径22mm 的HRB400级钢筋,截面总配筋率为:190120.01520.005500500s s A A bh ρ'+⨯===>⨯,满足要求。
受压构件承载力计算例题
![受压构件承载力计算例题](https://img.taocdn.com/s3/m/2b0b1d24240c844768eaee63.png)
受压构件承载力计算1、某现浇框架柱,截面尺寸为 300X 300,轴向压力设计值 N = 1400 kN ,计算 长度3.57 m ,采用C30混凝土、U 级(HRB335)钢筋。
求所需纵筋面积。
解:I 。
., b =3570 300 二“.9,查得书=0.9515, A' 1159 3:'亠= =0.01288 > fin =0.006A 300 汇3002、已知某正方形截面轴心受压柱,计算长度 7.5 m ,承受轴向压力设计值 N = 1800 kN ,混凝土强度等级为 C20,采用U (HRB335)级钢筋。
试确定构件截面 尺寸及纵向钢筋截面面积。
3、 已知一偏心受压柱,b X h = 450 X 450,a = a' = 4,0C30, HRB335 钢筋, E b = 0.55,承受纵向力 N = 350 kN ,计算弯距 M = 220 kN • m 。
柱计算长度 为10= 3.0m ,受压区钢筋 A's = 402 (2#16),求受拉区钢筋面积。
解:(1) 设计参数:1=1.0, a =a ' = 40 h 0=410 ,f c =14.3 N/mm 2 , f y =300N/mm 2e 0= 630,取 c a =20,e i = e 0 + e a = e 0+20=648&.5fcA _0.514.3江450 汉450 _4.[取匸 1=11N3500002 =1.15-0.01b=1.15-0.01 3000=1.08,取 Z 2=1 h 450=1 -- 1(_3000)2 1 1=1.026484501400 - 450 (2) 受压区高度 n e i = 661> 0.3 h 0 按大偏压计算e =661+(450/2- 40)= 846,X ' ' 'Ne 二:1 f c bx(h °) f y A s (h ° -a ) 2*1400咒103l0.9 汉 0.962 -14.3 300 3002=1159.5m解:A'sdb = 7500 400 =18.75,查得书=0.7875 2— 9.6 汇 400 汉 400 = 3345.6mm ,=0.021>;-min-0.006匚=1 --1400eh °1300 1800X03^0.^ 0.7875A'sA 3345.6 400 400350000 846 =1 14.3 450x(410 -x2)300 402(410 -40)x 二110mm::: X b 二b h0二0.55 410 二225.5mm2a = 80mm(3) 求钢筋面积N = :r f c bx f y A s - f y A sA s =1594mm2,取 4 # 22, A s = 1520mm2(4) 验算配筋率A s _ bh1520450 450= 0.75%」min0.2%垂直于弯矩作用方向的承载力验算l0/b=6.6 , 可得,=1.0N =°.9 [f c bh f y(A s A s)] =3125kN>350kN 满足要求。
第七章拉弯和压弯构件典型例题_钢结构精选全文
![第七章拉弯和压弯构件典型例题_钢结构精选全文](https://img.taocdn.com/s3/m/69cead45974bcf84b9d528ea81c758f5f61f29b1.png)
【例题1】某两端铰接压弯杆,如图所示,选用型钢2∠100×70×6,钢材Q235,m 2.4=l ,受轴向压力kN 42=N (设计值)和横向均布荷载m /kN 63.3=q (设计值),试验算截面是否满足要求。
【解答】m 2.4===l l l oy ox查表得,2∠110×70×6的截面数据:[]322.015014688.2/420/442.011954.3/420/cm 88.2cm 54.3cm 267cm 27.2142==<===========y y oy y x x ox x y x x i l i l i i I A ϕλλϕλ,,,,,(1)验算弯矩作用平面内的稳定32312322222cm 7.3547.7/cm 6.7553.3/N 277636.4119/212710206/mkN 82.463.38181=====×××==⋅=××==x x x x x Ex x I W I W EA N'ql M πλπ 查表得,20.105.121==x x γγ,按无端弯矩但有均布横向荷载作用时,取0.1=mx β,1.1/1.1(b 类截面)(b 类截面))6.277/428.01106.7505.110812127442.01042)8.01(36311×−××××+××=−+(Exx x xmx x N'N W M ANγβϕ 215N/mm 159.4114.77.442=<=+=f (满足))6.277/4225.11107.352.1108121271042)25.11(36322×−××××−×=−−(Exxx x mx N'N W M A N γβ 215N/mm 210.3230.3202=<=−=f (满足)(2)验算弯矩作用平面外的稳定7518.01460017.01235/0017.01=×−=−=y y b f λϕ3631106.757518.010*********.01042××××+××=+x b x tx y W M A N ϕβϕ 215N/mm 202141612=<=+=f (满足)实腹式截面无削弱,强度无需计算;因截面是角钢(型钢),局部稳定不用验算。
受弯构件计算例题
![受弯构件计算例题](https://img.taocdn.com/s3/m/9286f2136137ee06eef9185b.png)
1.单筋矩形截面例4-1 已知矩形截面简支梁(见图4-19),混凝土保护层厚为20mm(一类环境),梁计算跨度l0=5m,梁上作用均布永久荷载(已包括梁自重)标准值g k=6kN/m,均布可变荷载标准值q k=15kN/m。
选用混凝土强度等级C20,钢筋HRB335级。
试确定该梁的截面尺寸b×h及配筋面积A s。
图4-18 例题4-1图解:(1)设计参数由附表2和附表6查得材料强度设计值,C20混凝土f c=9.6N/mm2,f t=1.1N/mm2,HRB335级钢筋f y=300N/mm2,等效矩形图形系数1=1.0。
设该梁的箍筋选用直径为φ8的HPB300钢筋。
(2)计算跨中截面最大弯矩设计值(3)估计截面尺寸b h⨯由跨度选择梁截面高度 450h mm =(111l ),截面宽度 b =200mm (12.25h ), 取简支梁截面尺寸 200450b h mm mm ⨯=⨯ (4)计算截面有效高度0h先按单排钢筋布置,取受拉钢筋形心到受拉混凝土边缘的距离a s = c+d v +d /2≈40mm ,取a s =40mm ,则梁有效高度 h 0=h -a s =450-40=410mm 。
(5)计算配筋6,max 221088.125100.2730.3991.09.6200410s s c M f bh ααα⨯===<=⨯⨯⨯ 满足适筋梁的要求。
112)1120.2730.326s ξα=--=--⨯=200.3262004109.6855300c s y f A bh mm f ξ⨯⨯⨯=== 由附表16,选用320钢筋,A s =942mm 2。
(6)验算最小配筋率min min 0.450.001659410.010*******0.002ts yf A f bh ρρρ>=====⨯>=满足要求。
(7)验算配筋构造要求 钢筋净间距为 200282203425mmd 20m 2m2mm-⨯-⨯>>==满足构造要求。
第三章 受弯构件例题
![第三章 受弯构件例题](https://img.taocdn.com/s3/m/e4dcd2a7f524ccbff12184c3.png)
M
u
4 16 200
= α
1
f c bh
2 0
ξ (1 − 0 .5 ξ )
不少筋
解:(1)确定材料 确定材料 选 砼:C15 钢筋: 级 钢筋:I级 (2)选择截面 选择截面
h = l0 12 = 1200 12 = 100 ( 根部 )
⇒ f cm = 8 .5 N
y
mm
2
⇒
f
= 210
N
mm
2
自由端: 自由端:60mm
(3)荷载计算 荷载计算 恒载标准值 20防水砂浆: 防水砂浆: 防水砂浆 板重(平均厚 平均厚80): 板重 平均厚 : 20水泥砂浆: 水泥砂浆: 水泥砂浆
0 . 02 × 20 0 . 08 × 25
0 . 02 × 20
= 0 . 4 kN = 2 . 0 kN
= 0 . 4 kN
= 2 . 8 kN
m m
m
m
2
2 2
2
∑
板计算单元为1m, 板计算单元为 ,则
g
k
= 2 . 8 kN
m
2
× 1 m = 2 . 8 kN
m
活载标准值: 活载标准值:Fk=1kN/m
Q
q
k
]l0
2
2
]×
6
(3)配筋计算 配筋计算 先设钢筋为一排, 先设钢筋为一排, h 0 = h − a
受弯、压弯构件
![受弯、压弯构件](https://img.taocdn.com/s3/m/8894d6e6551810a6f52486a2.png)
Z
T f y As
h0
1 m ( n 2)( 2 1) 2 ' x m 1 m n 1
2
x0
4 受弯和受压构件的承载力计算
简化后的合力及作用位置
C a1 f cbx a1 f cbb1 xc x 1 1 ' x b1 xc b1mx0 2 2 2
4 受弯和受压构件的承载力计算
(2)物理关系
距截面中心轴 yci混凝土的应力
ci c(e ci ) c ( , , yci )
距截面中心轴 ysi钢筋的应力
si s(e si ) s ( , , ysi )
(3)平衡方程
N c (e c )dAc s (e s )dAs ci Aci si Asi M c (e c ) yc dAc s (e s ) y s dAs ci yci Aci si ysi Asi
n
0 e s e y , s e s Es
e e 0 , 常数
0
e s e y , s y
4 受弯和受压构件的承载力计算
4.1.3 受压混凝土应力图形简化
a1fc
fc
Mu
xc
C
yc
Mu
h0
x=b1xc
C yc
Z
T f y As
美国规范 压应力图形的应力取0.85fc’
0.8 f cuk 50 MPa b1 0.8 0.002( f cuk 50 ) 50 MPa f cuk 80 MPa
4 受弯和受压构件的承载力计算
溷凝土受弯、偏压构件计算步骤
![溷凝土受弯、偏压构件计算步骤](https://img.taocdn.com/s3/m/86f7a66587c24028915fc3d7.png)
进行承载力校核时,由于钢筋面积 已知,可用式(a)判定。
2 承载力计算
已知 截面尺寸b、h及 、 ,材料强度 、 及 。求
(1)判别类型:当 时,属第一类T形截面,可按
的单筋矩形截面梁方法计算。若 属第二类T形。
(2)第二类T形:首先,求出x及 , ,
当 或 时,
,当 时,取 ,则
3 配筋计算
(1)首先判定截面类型, ,属第一类T形截面,按 的单筋矩形截面梁方法计算;否则属第二类T形截面
(2) 第二类T形截面计算: 先求 ,
,求 , ,当 时,
三、受弯构件的斜截面受剪承载力(P67页)
(一)、无腹筋板的受剪承载力计算
,其中 , 是截面高度影响系数,当
<800mm;取 mm;当 >2000mm时,取 mm。
(二)、箍筋梁的斜截面受剪承载力
计算步骤:
(1)、承载力计算
已知 截面尺寸和材料强度、箍筋直径、肢数和间距,计算斜受剪的最大承载力。
4)求 :一纵纵向钢筋的最小限值
当 时,取
5)求混凝土受压区高度x
根据 求得x
6)求 :当 时,
当 时,则 此处
当 时,按小偏心受压计算。
7)验算 : 时,取
(3)大偏心受压柱的配筋计算,(求 、 )
计算步骤:1)~4)和已知 ,求 的步骤1)~4)相同。
5) 求 :取 ,
6) 验算 :当 时,取 ,按已知 求
一矩形截面构件的受弯承载力(图形见规范P45页)
(一)、单筋梁的正截面受弯承载力
计算步骤
(1)承载力计算
求出 ,若 ,则
当 时,
当 时,取 ,此时
当 时,截面承载力满足要求。
新规范偏心受压构件例题
![新规范偏心受压构件例题](https://img.taocdn.com/s3/m/42e1687ea88271fe910ef12d2af90242a995ab53.png)
[ 例6-1 ] 某矩形截面钢筋混凝土柱,构件环境类别为一类。
600m 600mm m m m 400==h b ,,柱的计算长度.m 2.70=l 。
承受轴向压力设计值.kN 1000=N ,柱两端弯矩设计值分别为m kN 450.m kN 40021×=×=M M ,。
该柱采用HRB400级钢筋(2N/mm 360=¢=y y f f )混凝土强度等级为C25(2t 2c N/mm 27.1N/mm 9.11==f f ,)。
若采用非对称配筋,试求纵向钢筋截面面积并绘截面配筋图。
纵向钢筋截面面积并绘截面配筋图。
[解] 1.材料强度和几何参数材料强度和几何参数C25混凝土,2c N/mm 9.11=fHRB400级钢筋2N/mm 360=¢=y yf f HRB400级钢筋,C25混凝土,8.00.1518.011b ===b a x ,,由构件的环境类别为一类,柱类构件及设计使用年限按50年考虑,构件最外层钢筋的保护层厚度为20mm ,对混凝土强度等级不超过C25的构件要多加5mm ,初步确定受压柱箍筋直径采用8mm ,柱受力纵筋为20~25mm ,则取mm 45128520s =+++=¢=s a a 。
600m 600mm m m m 400==h b ,,2.求弯矩设计值(考虑二阶效应后)求弯矩设计值(考虑二阶效应后)由于889.0450/400/21==M M ,mm 2.173600121121====h A Ii 102M/7200/173.241.5734-1223.33M l i ==>=。
应考虑附加弯矩的影响。
应考虑附加弯矩的影响。
根据式(6-1 )~式()~式( 6-3)有:)有: 0.1428.11010006004009.115.05.03c>=´´´´==N A fc z ,取0.1c =z 9667.04504003.07.03.07.021m =+=+=M M C mm 203060030a ===he 13.10.1)6007200(555/)20101000/10450(130011/)/(1300112362002ns =´+´´+=÷øöçèæ++=c a h l h e N M z h 考虑纵向挠曲影响后的弯矩设计值为:考虑纵向挠曲影响后的弯矩设计值为: m kN 57.49145013.19667.02×=´´==M C M ns m h3.求i e ,判别大小偏心受压,判别大小偏心受压mm 57.4911010001057.491360=´´==N Me m m 57.5112057.4910=+=+=a i e e e m m 5.1665553.03.00=´=>h e i 可先按大偏心受压计算。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
αs =
α1 fc bh2 0
ξ = 1 − 1 − 2α s = 0.101<2as′/h0 = 0.174
说明受压钢筋 As′ 过多,破坏时不能达 f y′ (但不得减少), 对受压钢筋合力作用点取矩可得 M 290 × 106 = = 1918mm 2 As = f y ( h0 − as′ ) 360 × ( 460 − 40 )
矩形截面钢筋混凝土梁,截面尺寸 b × h = 250mm × 500mm ,混凝土采用C25 2 ( fc=11.9N/mm2,ft=1.27N/mm2 ),纵向钢筋采用HRB400级( f y = f y′ = 360N / mm ), 一类使用环境(混凝土保护层最小厚度为25mm)。若弯矩设计值M=150kN· m。试确定梁内 纵筋数量。 解:由于受拉钢筋未知,故属于截面设计问题。
20 = 35mm , h0 =h − as = 465mm 2 ⎧ ⎫ ft ⎪ ⎪ , 0.2%⎬ = 0.2% , As,min = ρ min bh = 250mm 2 ρ min = max ⎨ 0.45 fy ⎪ ⎪ ⎩ ⎭ 按单筋截面计算(两个未知量 ξ 、As ) as = c + 150 × 106 = = 0.233 αs = 2 2 bh0 α1 fc 250 × 465 × 1 × 11.9 M
设计问题:特点是受拉钢筋未知。
单筋截面,当不满足计算公式的下限 时,应减小截面高度h ;当不满足计算公式 的上限时,可改为双筋截面计算。 双筋截面,当受压钢筋未知时(三个 未知数),可由用钢量最省且满足公式上 限先确定ξ,再由两个平衡方程求钢筋面 积,适用条件满足。 双筋截面,当受压钢筋已知时(两个 未知数) ,先由基本计算公式求出ξ ,当 不满足计算公式的下限 ξ ≥2as′ / h 0 时,说 明已有受压钢筋过多(但不可减少)不能 达屈服,可对受压钢筋合力作用点取矩近 似计算Mu ;当不满足计算公式的上限时, 说明已有受压钢筋不足,应按受压钢筋未 知情形计算受压和受拉钢筋面积。
取 as =as′ = 40mm, 0 =h − as = 460mm h 双筋截面有两个未知数,则由基本计算公式得 M − As′ f y′ ( h0 − as′ ) 290 × 106 − 1140 × 360 × ( 460 − 40 ) 1 × 11.9 × 250 × 460
2
αs =
α1 fc bh
As = 1256mm 2>As,min = ρ min bh = 250mm 2
ξ=
bh0α1 fc
=
M u = ξ ( 1 − 0.5ξ ) bh2α1 fc 0 = 0.3269 × ( 1 − 0.5 × 0.3269 ) × 250 × 4652 × 11.9 = 176 × 106 N ⋅ mm = 176kN ⋅ m Mu = 1 2 pl , 8 p= 8M u 8 × 176 = = 39.1kN/m 2 2 l 6
2
αs =
α1 fc bh
2 0
=
= 0.4064
ξ = 1 − 1 − 2α s = 0.5673>ξ b = 0.518
说明已有受压钢筋不足,应按 As′ 未知(三个未知数)重新计算 受压、受拉钢筋数量,计算结果同例2。
目录
【例5】:受弯构件正截面承载力设计问题:双筋,下限不满足。
条件同例1。但弯矩设计值M=290kN· m ,已有受压钢筋4 22( As′ = 1520mm 2)。 试确定梁内纵向受拉钢筋数量。 解:属于截面设计问题。
取 as =as′ = 40mm, 0 =h − as = 460mm h 双筋截面有两个未知数,则由基本计算公式得 M − As′ f y′ ( h0 − as′ ) 290 × 106 − 1520 × 360 × ( 460 − 40 ) = = 0.096 1 × 11.9 × 250 × 4602
as = c +
ρ min
20 = 35mm , h0 =h − as = 465mm 2 ⎧ ⎫ ft ⎪ ⎪ = max ⎨ 0.45 , 0.2%⎬ = 0.2% fy ⎪ ⎪ ⎩ ⎭ As f y 1256 × 360 = 0.3269 <ξ b = 0.518 250 × 465 × 1 × 11.9
目录
f y′ ,近似取 ξ = 2as′ / h 0(此时受压钢
s
筋与受压区混凝土的合力作用线重 ′ 合) ,并对As 合力作用点取矩求Mu 。 单筋截面一般极少出现不满足计算公 式下限情形(出现少筋梁的破坏、承载力 很低)。 (备注)
【例1】:受弯构件正截面承载力设计问题:单筋,上、下限均满足。
选用受拉钢筋4
28 (As=2463mm2),受压钢筋3 12( As′ = 603mm 2 )。
(备注)
目录
【例3】:受弯构件正截面承载力设计问题:双筋,上、下限均满足。
条件同例1。但弯矩设计值M=290kN· m ,已有受压钢筋3 22( As′ = 1140mm )。
2
试确定梁内纵向受拉钢筋数量。 解:属于截面设计问题。
目录
一、受弯构件正截面受弯承载力计算
1. 正截面计算应力图形
α1 fc α1 fc
Mu h0 as'
ξ h0
Mu
ξ h0
As' fy '
h0
As fy
as
As fy
as
单筋矩形截面
双筋矩形截面
目录
2. 矩形截面受弯构件正截面受弯承载力 计算公式及适用条件
⎧ ⎧ As f y =ξ bh0α 1 f c ⎪计算公式: ⎪ ⎨ ⎪ 2 ⎪ M ≤M u =α s bh0α 1 f c ⎪ ⎩ 单筋矩形截面 ⎨ ⎪ : ⎧下限(保证不发生少筋梁的破坏) As≥As,min =ρ min bh ⎪ 适用条件: ⎪ ⎨ ⎪上限(保证破坏时纵向受拉钢筋达到屈服):ξ ≤ξ b ⎪ ⎩ ⎩ ⎧ ⎧ As f y =ξ bh0α 1 f c + As′ f y′ ⎪ ⎪计算公式: ⎨ 2 ⎪ ⎪ M ≤M u =α s bh0α1 f c + As′ f y′ ( h0 − as′ ) ⎩ 双筋矩形截面 ⎨ : ⎧下限(保证破坏时纵向受压钢筋达到屈服) ξ ≥2as′ / h0 ⎪ ⎪ ⎨ ⎪适用条件: ⎪上限(保证破坏时纵向受拉钢筋达到屈服):ξ ≤ξ b ⎩ ⎩ x 式中,相对受压区高度ξ = ,内力臂系数 α s = ξ ( 1 − 0.5ξ ) ,同时有 ξ =1 − 1 − 2α s h0
条件同例1。但弯矩设计值M=290kN· m。试确定梁内纵筋数量。 解:属于截面设计问题。
h0 =h − as = 465mm 290 × 106 按单筋截面计算 α s = 2 = = 0.451 bh0 α1 fc 250 ×4652 × 1 × 11.9 M
ξ = 1 − 1 − 2α s = 0.687>ξ b = 0.518 ,单筋不行,可改用双筋。
选用受拉钢筋4
25 (As=1964mm2)。
目录
【例6】:正截面受弯单筋截面复核问题:上、下限均满足。
条件同例1。纵向受拉钢筋4 20 (As=1256mm2),求梁截面所能承受的弯矩设计值Mu=?若该
梁为计算跨度 l=6m 的简支梁,求梁上所能承受的均布荷载设计值(包括自重)。 解:属于单筋梁截面复核问题(两个未知量ξ、Mu )。
目录
【例7】:正截面受弯单筋截面复核问题:上限不满足。
条件同例1。纵向受拉钢筋4 28 (As=2463mm2),求梁截面所能承受的弯矩设计值Mu=?若该
梁为计算跨度 l=7.2m 的简支梁,求梁上所能承受的均布荷载设计值(不包括自重)。
解:属于单筋梁截面复核问题(两个未知量ξ、Mu)。
28 = 39mm , h0 =h − as = 461mm 2 ⎧ ⎫ ft ⎪ ⎪ ρ min = max ⎨ 0.45 , 0.2%⎬ = 0.2% ,As = 1256mm 2>As,min = ρ min bh = 250mm 2 fy ⎪ ⎪ ⎩ ⎭ As f y 2463 × 360 = = 0.6465 >ξ b = 0.518 , 为超筋梁 ξ= bh0α1 f c 250 × 461 × 1 × 11.9 as = c + M u = ξ b ( 1 − 0.5ξ b ) bh2α1 f c 0 = 0.518 × ( 1 − 0.5 × 0.518 ) × 250 × 4612 × 11.9 = 242.7 × 106 N ⋅ mm = 242.7kN ⋅ m 8M 1 8 × 242.7 M u = pl 2 , p = 2 u = = 37.45kN/m (包括自重) 2 8 l 7.2 扣除自重得 p′ =p − 1.2 × 25bh = 37.45 − 1.2 × 25 × 0.25 × 0.5 = 33.7kN/m
目录
不满足适用条件情形
复核问题:特点是配筋为已知(均为 两个未知数ξ 和Mu )。
直接解联立方程求出ξ。 无论单筋或双筋截面,当不满足计算 公式的上限ξ≤ξb时,说明破坏时As达 不到 fy,近似取ξ=ξb,并对As合力作用 点取矩求Mu 。 双筋截面 当 不满足计算公式的下限 ξ ≥2as′ / h 0 时,说明破坏时 A′ 达不 到
25 (As=1964mm2)。
目录
【例4】:受弯构件正截面承载力设计问题:双筋,上限不满足。
条件同例1。但弯矩设计值M=290kN· m ,已有受压钢筋2 12( As′ = 226mm 2 )。 试确定梁内纵向受拉钢筋数量。 解:属于截面设计问题。
取 as =as′ = 40mm, 0 =h − as = 460mm h 双筋截面有两个未知数,则由基本计算公式得 M − As′ f y′ ( h0 − as′ ) 290 × 106 − 226 × 360 × ( 460 − 40 ) 1 × 11.9 × 250 × 460