洁净空调日维护保养记录-诺华制药
空气净化机组日常维护记录本

空气净化机组日常维护记录本
净化机组日常维护记录本
空气净化系统的维护要求
1、空气处理机组、新风机组应定期检查,保持清洁。
2.新风机组粗滤网每两天清洗一次;粗效过滤器应在1月至2月更换一次;中效过滤
器每周检查一次,每三个月更换一次;亚高效过滤器应每年更换一次。
如有污染和堵塞,
应及时更换。
3、末端高效过滤器宜每年检查一次,当阻力超过设计初阻力160pa或已经使用3年
以上时宜更换。
4、排风机组中的中效过滤器宜每年更换,发现污染和堵塞及时更换。
5.定期检查回风口滤网,每周清洗一次,每年更换一次。
如有特殊污染,应及时更换,并用消毒剂擦拭回风口内表面。
6、设专门维护管理人员,遵循设备的使用说明进行保养与维护;并制定运行手册,
有检查和记录。
日期
名称新风机组粗效过滤网新风机组中效过滤网新风机组亚高效过滤网新风机组末端高
效过滤网回风口过滤网排风机组中效过滤器空气处理机组签名清洁检查维修更换执行者科
室备注。
洁净空调停机维护保养记录-诺华制药

Check ball bearing for abnormal noise and vibration NB. This should be checked before the unit is stopped and from the entries in the Log Books. 检查轴承,是否有杂音和震动
HVAC System No.: Operator’s Namnnel No.:
Date: Started on:
Work Order No.: Finished at:
Fine-dust filter replacement ( A3 or dP reaches limit whatever comes first)
SOP reference : SOP-000217
Preventive Maintenance Record for HVAC System (When AHU Shut Down) 空调系统的预防性维护记录(空调机组停机)
FRM-000388 Version : 01 Effective from : 14.07.2008
Name 姓名: Author 作者:
Date 日期:
Signature 签名:
Approvers 批准人:
Final Approver 最终批准人:
Applicability : document applies for Beijing Novartis Pharma Ltd. 适用性:文件适用于北京诺华制药有限公司
某制药企业三十万级空气净化系统标准操作维护保养规程

标准操作规程目的:建立三十万级空气净化系统的标准操作维护保养规程,使其操作有据可依。
适用范围:适用于三十万级空气净化系统操作岗位。
责任人:工程部、三十万级空气净化系统操作人。
一、标准操作程序:1.三十万级空气净化系统岗位操作人必须经过岗位培训考核合格后才能上岗操作。
2.准备工作:检查新风阀,确保打开。
新风、回风混合比例一般为30%:70%。
根据所需运行工况,检查相应的设备(包括:组合式空调器、加湿器、风冷热泵机组、臭氧发生器、除尘器、排风机等)的机械等部分完好情况,并将相应阀门等调整到相应状态,确保连接正常,加湿器、风冷热泵水源供给正常。
打开空调控制箱,开启总电源,根据所需运行工况,开启相应设备(包括:组合式空调器、回风机、加湿器、冷冻水泵、变风量机组、吊顶空调、臭氧发生器、除尘器、排风机、通风器、轴流风机等)电源开关。
风冷热泵机组电源从低压配电室直接供给,平时一般保持通电状态。
3.开机运行:空调系统应在使用前三十分钟提前开机运行,以使净化区通过自净达到相应净化级别。
空调系统开机顺序为:空调送风机→回风机→(根据生产要求)排风箱、除尘机组(避免系统形成负压)。
并正确悬挂设备状态标志牌(正在运行)。
在空调控制箱面板上按(空调送风机)启动按钮,再按墙上组合式空调器送风机变频器控制面板上(RUN)键,送风机从0Hz上升至设定频率(一般设定频率≤50Hz),正常运行。
按(回风机)启动按钮,启动回风机。
观察初、中效压差表显示情况。
制冷时,首先选择冷冻水泵1或2,并将相应冷冻水阀打开,在空调控制箱面板上按(冷冻水泵1)或(冷冻水泵2)启动按钮,启动冷冻水系统,并观察压力表情况。
冷冻水系统运行正常后,再按组合式空调器加湿段处风冷热泵远程微电脑控制面板上(F2)(此时为制冷模式1)启动风冷热泵,开始制冷。
观察冷冻水送、回水温度。
观察送、回风及净化区温度变化(正常温度范围:18℃~26℃),及时调整制冷系统。
制热时,首先选择冷冻水泵1或2,并将相应冷冻水阀打开,在空调控制箱面板上按(冷冻水泵1)或(冷冻水泵2)启动按钮,启动冷冻水系统,并观察压力表情况。
洁净空调维护保养操作规程-诺华制药

Replaces No.: SOP-000217 version 02Reason for Change:1. All EPCP AHUs added and are in service as shown to the table of chapter 31 Regulatory Basis and Reference DocumentsThe Group Quality Manual:QM N 6.1: Facility and Equipment - Qualification and CommissioningQM N 6.2: Cleanliness ZoningIGs N6.2.2: Cleanliness Zoning Policy for The Manufacture of Non-Sterile Drug Products and the Respective Drug SubstanceBNP SOPs:SOP-000052: Work Order Management ProcessSOP-000066: Filter Replacement for HVAC InstallationSOP-000074: Cleaning of HVAC installation semi solid dosage form AHU 2.2, 2.3SOP-000117: Safety GuidelinesSOP-000124: Safety Lock Off ProcedureSOP-000214: Cleaning of HVAC Installation for Room-airSOP-000309: HVAC System Operational ProcedureSOP-000328: General Operating Procedures in case of HVAC Shut DownSOP-000390: Cleanliness ZoningSOP-000407: Replacement, Cleaning and Maintenance Return Air Filter in ProductionNB. Upon approval of the RMS SOP these SOPs will be referenced to this SOP.2 PurposeThis SOP describes the procedures for the preventive maintenance on HVAC units.The preventive maintenance program has to be established in accordance with Novartis Quality Module 6.1.This maintenance program is implemented to ensure that the equipment remains in a qualified or commissioned state after handover to the User.3 ScopeThis SOP covers the preventive maintenance of all HVAC units. The following table gives an overview of the current status of HVAC units which are operational at the moment.No. Function Servicing areas Cleaning Zone1.1 Production areaDispensing A-308, Day storage Room A-310, Blending Room A-313,Intermediate Storage A-504, Granulation Room A-506, Compressing Rooms A-508.1, Compressing ante-room A-510, Capsule filling room A-508.2,Coating Room A-514, Coating drying room A-516, Corridors 300 and 500etc.Zone 22.1 Capsule filling Encapsulating A-511, Printing A-509 and locker 507 Zone 22.2 Emugel filling Cream/Ointments Filling A-505 and Personnel Lockers 505.1, 505.2, 505.3,501.1Zone 22.3EmugelprocessingCream/Ointments Processing A-503 and locker 501, Storage room 503.1 Zone 23.0 Packaging Secondary packaging A-405,Air locker 405.1 etc. Zone 24.0 N/A N/A Zone 35.0 Lockers Offices and Production Lockers Zone 26.0 QC QC Laboratories Zone 48.0 Alu-Alu packaging Alu-Alu Blister Packing A-302, Compressing Room A-304 Zone 29.0 Sampling Sampling Cabin A-907 with Personnel Lockers 905, 906 Zone 210.0 Material lockMaterial Entry A-910Material Air-Lock A-306Zone 4Zone 313.0 Washing Washing Area A-314.1, Equipment storage room A-314, PW Plant Room A-316Zone 220 New Warehouse Receiving/Dispatch Area A-804, High Rack Storage Area A-806 Zone 421New ConditionedStorage AreaNew Conditioned Storage Area 932 Zone 4PCU1 Inlet to AHU Central fresh-air pre-conditioning unit N/A AIC 1 Air Inlet Fresh-air Inlet Chamber 1 N/A PCU2 Inlet to AHU Central fresh-air pre-conditioning unit N/A AIC 2 Air Inlet Fresh-air Inlet Chamber 2 N/A ------ Canteen Canteen N/AAHU11 Dispensary A-320 Airlock, A-322 Clean store, ,A-324 Dirty Equipment,A-326 Washing,A-328 Drying,A-330 Breached material store, A-332 Emergency Shower,A-334Change room, A-918 Dispensed batch store, A-921 Dispensing room 1, A-922 Dispensing room 2,A-924 Dispensary material store,A-928 Pallettransfer.Zone 2AHU12 Clean corridor New HVAC system is used for production area step by step Zone 2AHU14 Granulation Suite A-602 Blending room,A-604Storage,Zone 2AHU15 Compression suite Covers Corridor A-612 Compression corridor,A-608 Compression room 1,A-610 Compression room A-616 , Compression room A-618Zone 2AHU16 Coating, Covers A-628 Coating, A-628.1 PersonalAirlock, A-630 Control room, A-632Printing, A-634 Bulk storage.Zone 2 Clean Stair1 A-238, Clean Stair 2 A-240 : operated zone 2Shoe Change A-238 : operated zone 2Clean Change A-232 : operated zone 4*Rooms A-230, A-234 : operated zone 4*Rooms A-222, A-226 : operated none zone**Rooms A-224, A-228, A-228.1 : operated none zoneNote:*: AHU17 is designed for Zone 2(A-232, A-234, A-230), the operation mode of the rooms are defined as listed above.**: AHU17 is designed for Zone 3(A-222, A-226), the operation mode of the rooms are defined as listed above.Clean Stair1 A-140 : operated zone 2Shoe Change A-136 : operated zone 2AHU17 Clean ChangeClean Change A-132 : operated zone 4*Zone 2No. Function Servicing areas Cleaning Zone1.1 Production areaDispensing A-308, Day storage Room A-310, Blending Room A-313,Intermediate Storage A-504, Granulation Room A-506, Compressing Rooms A-508.1, Compressing ante-room A-510, Capsule filling room A-508.2,Coating Room A-514, Coating drying room A-516, Corridors 300 and 500etc.Zone 22.1 Capsule filling Encapsulating A-511, Printing A-509 and locker 507 Zone 22.2 Emugel filling Cream/Ointments Filling A-505 and Personnel Lockers 505.1, 505.2, 505.3,501.1Zone 22.3EmugelprocessingCream/Ointments Processing A-503 and locker 501, Storage room 503.1 Zone 23.0 Packaging Secondary packaging A-405,Air locker 405.1 etc. Zone 24.0 N/A N/A Zone 35.0 Lockers Offices and Production Lockers Zone 26.0 QC QC Laboratories Zone 48.0 Alu-Alu packaging Alu-Alu Blister Packing A-302, Compressing Room A-304 Zone 29.0 Sampling Sampling Cabin A-907 with Personnel Lockers 905, 906 Zone 210.0 Material lockMaterial Entry A-910Material Air-Lock A-306Zone 4Zone 313.0 Washing Washing Area A-314.1, Equipment storage room A-314, PW Plant Room A-316Zone 220 New Warehouse Receiving/Dispatch Area A-804, High Rack Storage Area A-806 Zone 421New ConditionedStorage AreaNew Conditioned Storage Area 932 Zone 4PCU1 Inlet to AHU Central fresh-air pre-conditioning unit N/A AIC 1 Air Inlet Fresh-air Inlet Chamber 1 N/A PCU2 Inlet to AHU Central fresh-air pre-conditioning unit N/A AIC 2 Air Inlet Fresh-air Inlet Chamber 2 N/A ------ Canteen Canteen N/AAHU11 Dispensary A-320 Airlock, A-322 Clean store, ,A-324 Dirty Equipment,A-326 Washing,A-328 Drying,A-330 Breached material store, A-332 Emergency Shower,A-334Change room, A-918 Dispensed batch store, A-921 Dispensing room 1, A-922 Dispensing room 2,A-924 Dispensary material store,A-928 Pallettransfer.Zone 2AHU12 Clean corridor New HVAC system is used for production area step by step Zone 2AHU14 Granulation Suite A-602 Blending room,A-604Storage,Zone 2AHU15 Compression suite Covers Corridor A-612 Compression corridor,A-608 Compression room 1,A-610 Compression room A-616 , Compression room A-618Zone 2AHU16 Coating, Covers A-628 Coating, A-628.1 PersonalAirlock, A-630 Control room, A-632Printing, A-634 Bulk storage.Zone 2 Rooms A-130, A-134 : operated zone 4*Rooms A-122, A-126 : operated none zone**Rooms A-124, A-128, A-128.1 : operated none zoneNote:*: AHU17 is designed for Zone 2(A-132, A-134, A-130), the operation mode of the rooms are defined as listed above.**: AHU17 is designed for Zone 3(A-122, A-126), the operation mode of the rooms are defined as listed above.AHU18Primarypackaging areaPrimary packaging room A-710, A-720, A-730, A-740. Zone 2AHU19Secondarypackaging areaPackaging Area, A-407, Packaging Waste Air Lock, A-409. Zone 3AHU20WarehouseWarehouse Receiving Area, A-804 and the High Rack Storage Area, A-806.Zone 4AHU21Warehouse Conditioned Storage, A-932. Zone 4AHU22Process area New wash bay, Rooms A-624 Equipment drying room, A-620 Dirtyequipment room. Zone 2No. Function Servicing areas Cleaning Zone1.1 Production areaDispensing A-308, Day storage Room A-310, Blending Room A-313, Intermediate Storage A-504, Granulation Room A-506, Compressing Rooms A-508.1, Compressing ante-room A-510, Capsule filling room A-508.2,Coating Room A-514, Coating drying room A-516, Corridors 300 and 500etc.Zone 22.1 Capsule filling Encapsulating A-511, Printing A-509 and locker 507 Zone 22.2 Emugel fillingCream/Ointments Filling A-505 and Personnel Lockers 505.1, 505.2, 505.3,501.1Zone 22.3EmugelprocessingCream/Ointments Processing A-503 and locker 501, Storage room 503.1 Zone 23.0 Packaging Secondary packaging A-405,Air locker 405.1 etc. Zone 24.0 N/A N/A Zone 35.0 Lockers Offices and Production Lockers Zone 26.0 QC QC Laboratories Zone 48.0 Alu-Alu packaging Alu-Alu Blister Packing A-302, Compressing Room A-304 Zone 29.0 Sampling Sampling Cabin A-907 with Personnel Lockers 905, 906 Zone 210.0 Material lockMaterial Entry A-910Material Air-Lock A-306Zone 4Zone 3 13.0 WashingWashing Area A-314.1, Equipment storage room A-314, PW Plant Room A-316Zone 220 New Warehouse Receiving/Dispatch Area A-804, High Rack Storage Area A-806 Zone 421New ConditionedStorage AreaNew Conditioned Storage Area 932 Zone 4 PCU1 Inlet to AHU Central fresh-air pre-conditioning unit N/AAIC 1 Air Inlet Fresh-air Inlet Chamber 1 N/APCU2 Inlet to AHU Central fresh-air pre-conditioning unit N/AAIC 2 Air Inlet Fresh-air Inlet Chamber 2 N/A------ Canteen Canteen N/AAHU11 DispensaryA-320 Airlock, A-322 Clean store, ,A-324 Dirty Equipment,A-326 Washing,A-328 Drying,A-330 Breached material store, A-332 Emergency Shower,A-334Change room, A-918 Dispensed batch store, A-921 Dispensing room 1, A-922 Dispensing room 2,A-924 Dispensary material store,A-928 Pallettransfer.Zone 2 AHU12 Clean corridor New HVAC system is used for production area step by step Zone 2 AHU14 Granulation SuiteA-602 Blending room,A-604Storage,Zone 2 AHU15 Compression suiteCovers Corridor A-612 Compression corridor,A-608 Compression room 1,A-610 Compression room A-616 , Compression room A-618Zone 2 AHU16 Coating,Covers A-628 Coating, A-628.1 PersonalAirlock, A-630 Control room, A-632Printing, A-634 Bulk storage.Zone 2AHU24Process areaGranulation, Covers A-638 Material Airlock, A-640 Personal Airlock, A-636 Granulation room, A-642 Emergency Shower. Zone 2 AHU 25 Sampling Rooms A 820, A 821, A 822, A823, A 8244 Procedures4.1 GeneralAll maintenance activities in Production, Packaging and warehouse areas can only be performed after fulfillment of the cleanliness Zone conditions required. If it is necessary to shut down the HVAC during the preventive maintenance, the steps described in the SOP-000328 must be followed strictly.Preventive Maintenance on HVAC units will be performed on all HVAC units which are in operation and usage. For each HVAC unit, a unique maintenance manual (activity list) must be available, to ensure that specific preventive maintenance activities (e.g. measurements) are carried out appropriately. The PM works (Tasks) are stated in FRM-000363 / FRM-000386 / FRM-000387 / FRM-000388 / FRM-000392 (Related FRM to this SOP) and manufacturer recommendations.4.2 Start preventive maintenanceThe PM (Head of Utilities) Engineering Department informs the Head ofProduction and/or Production Supervisors, if possible 3 working days in advance (only AHU need to be shut down), about the preventive maintenance activities currently managed on a excel base task tracking. The schedule and work orders of HVAC AHUs maintenance is followed by SAP-PM system (SOP-000052: Work Order Management Process).In case of full or partial shut-down of HVAC system, please refer to SOP-000328in its current revision.Production notifies PM (Head of Utilities) in writing (e.g. e-mail) about "ProductionReadiness" for HVAC preventive maintenance.PM engineering starts PM works as soon as the written release for PM works fromproduction is received based on the specific maintenance manual for each unit. 4.3 Execution of preventive maintenancePM Engineering personnel or external vendor’s personnel execute the preventive maintenance based on the specific maintenance manual (activity lists) for each unit or a specific SOP and following the work order (SOP-000052: Work Order Management Process).The maintenance personnel (internal or external) must be well trained, skilled andexperienced in terms of execution of preventive maintenance and cGMP.If the maintenance personnel observe abnormalities on HVAC units, theresponsible HVAC Engineer has to be informed in order to define suitable remedies or repair work. The abnormalities have to be documented in the logbook FRM-000289 and assessed in view of GMP impact by the HVAC Engineer.PM Engineering HVAC Engineer is responsible for evaluating the preventive maintenance results. If a part of equipment is requiring repair or servicing, an assessment will be made as to whether the needed repair is minor or major. The assessment needs to be documented in the logbook FRM-000289 and corresponding maintenance work orders will be initiated to purchase the required spare parts. The assessment also includes a statement whether GMP compliant HVAC operations can be continued before having carried out the repair. In case the assessment result reveals that a continued operation might impact a GMP compliant operation of the HVAC unit, the Production Head and QA Head have to be informed in writing (e.g. e-mail).Minor repairs (e.g. belts, dumper, actuator, sensors) will be performed during the preventive maintenance. Major repairs (e.g. fans, coils) will be planned separately depending on the availability of the spare parts.4.4 Completion of preventive maintenanceAll preventive maintenance activities (e.g. measurements, etc.), after finishing,have to be recorded in the specific HVAC logbook FRM-000289 for each HVAC unit.PM Engineering notifies Production in writing (e.g. e-mail) about "Finishingpreventive maintenance” for HVAC units.After completion of all activities, including deficiencies, a scheduling for the next execution of preventive maintenance is to be defined in accordance to the periodicity recommended on FRM-000363 / FRM-000386 / FRM-000387 / FRM-000388 / FRM-000392, separately for each HVAC unit. Re: SOP-000052: Work Order Management Process (SAP-PM)The preventive maintenance activities and records have to be documentedproperly (i.e. log-books). The Preventive Maintenance activities must be periodically reviewed by the engineering management.5 ResponsibilitiesPreventive Maintenance is performed by PM Engineering or by external vendors based on written procedures within the valid BNP SOPs and supervised by BNP personnel.The evaluation of the results has to be done by the Head of Utility and engineering management based on agreed written procedures as indicated in previous chapters.The production Head has to provide a maintenance slot for the HVAC unit for execution of preventive maintenance after request by the Site Engineering.6 Additional Instructions6.1 Safety instructionsDuring the maintenance of any air system, the supply air and exhaust air fans must be switched off and applied as regulated by the SOP-000117 and SOP-000124. Steam heated units also require the steam supply to be shut off and the Safety Lock off Procedure applied during any cleaning procedure.7 Definitions & AbbreviationsBNP Beijing Novartis PlantHVAC Heating Ventilation Air ConditioningPM Preventive MaintenanceQA Quality Assurance8 Annexes/Related FormsFRM-000363: Preventive Maintenance Record for HVAC System (Three Months)FRM-000386: Preventive Maintenance Record for HVAC System (Six Months)FRM-000387: Preventive Maintenance Record for HVAC System (Annually)FRM-000388: Preventive Maintenance Record for HVAC System (When AHU shut down)FRM-000392: Working Activities Preventive Maintenance for HVAC System (Daily)。
空调卫生维护记录单(示例)

空调卫生维护记录单(示例)日期:______________
维护人员:______________
空调维护情况
1. 清洁过滤器
- 检查过滤器是否干净,如有需要,请清洁或更换过滤器。
- 清洁过滤器的方法:______________
2. 清洁冷凝器和蒸发器
- 检查冷凝器和蒸发器是否有积尘或污垢,如有需要,请进行清洁。
- 清洁冷凝器和蒸发器的方法:______________
3. 清洁排水口
- 检查排水口是否通畅,如有需要,请进行清洁。
- 清洁排水口的方法:______________
4. 检查制冷剂压力
- 使用压力计检查制冷剂的压力,确保制冷剂处于正常范围内。
- 正常制冷剂压力范围:______________
5. 检查电气连接
- 检查空调的电气连接是否松动或损坏,如有需要,请进行修复。
- 修复电气连接的方法:______________
维护记录
备注
- 在备注中记录维护过程中的任何特殊情况或需要注意的事项。
注意:以上维护项目仅为示例,实际维护应根据具体空调型号
和使用情况进行调整。
请确保维护人员具备相关专业知识和技能,
并遵守相关安全操作规程。
洁净空调维护及保养记录【范本模板】

净化空调维护及保养记录月份
日
期
初效过滤器
中效过滤器
高效过滤器
双签名
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
广元市第一人民医院
净化空调维护及保养记录月份
日
期
初效过滤器
末端高效过滤器
每年检查(测阻力)一次、当阻力超过设计初阻力160kpa或已使用3年更换
回风口过滤网
清洁:每周一次、更换:每年一次、如遇特殊污染随时更换
中效过滤器
高效过滤器
双签名
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
21
22
23
24
25
26
27
28
29
30
31
注明:“√”表示清洁/检查、“△”表示更换
维护
保养
要求
新风/循环机组
初效过滤器:每月清洁1次、每3—6月(或阻力超过额定初阻力60Pa)更换一次、中效过滤器每月清洁1次每6—12月(或额定初阻力80Pa)换一次。
空调净化系统检查维护保养、清洗记录

填表人/日期: 生效日期:2016年05月18日
KANGGU
项目
嘉兴康谷医用材料有限公司
空气净化系统检查维护保养、清洗记录
检查结果
保养清洗内容
HWR-001-00
日期
送风管道
初效过滤
中效过滤
高效过滤
送风、回风口
风机
空调冷凝液、 润滑油
备注:初效过滤器每月清洁一次,中效过滤器每三个月清洁一次,先从过滤器上小心拆下
过滤布,放入桶中用饮用水清洗两次,每次30分钟;在布上放洗衣粉,用毛刷刷去污垢,用饮用水 清洗3次,每次15分钟;用纯化水清洗过滤布2次,每次15分钟,自然晾干。高效过滤器一般情况下 每年更换一次,每月检漏一次,以保证达到洁净度要求。
洁净空调维护及保养记录

净化空调维护及保养记录月份
日
期
初效过滤器
中效过滤器
高效过滤器
双签名
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
Hale Waihona Puke 1﹟2﹟3﹟4﹟
5﹟
6﹟
7﹟
8﹟
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
广元市第一人民医院
净化空调维护及保养记录月份
日
期
初效过滤器
中效过滤器
高效过滤器
双签名
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
1﹟
2﹟
3﹟
4﹟
5﹟
6﹟
7﹟
8﹟
21
22
23
24
25
26
27
28
29
30
31
注明:“√”表示清洁/检查、“△”表示更换
维护
保养
要求
新风/循环机组
初效过滤器:每月清洁1次、每3-6月(或阻力超过额定初阻力60Pa)更换一次、中效过滤器每月清洁1次每6-12月(或额定初阻力80Pa)更换一次。
末端高效过滤器
每年检查(测阻力)一次、当阻力超过设计初阻力160kpa或已使用3年更换
精密空调维护保养记录模板

结论:
单位:
年月日
3.接线缎子(正常)|(不正常)
三、室内过滤网:
1、室内过滤网(过脏)|(正常)
四、空调温湿度加热测试
1、加热(正常)|(不正常)|(关闭)
2、加湿(正常)|(不正常)|(关闭)
3、制冷(正常)|(不正常)|(关闭)
五、室外机检查:
1、电源供电:(正常)|(不正常)|(关闭)
2、室外风机:(正常)|(不正常)|(关闭)
空调维护保养记录模板
设备位置___吉林国文医院1.监控面板按键操作功能(正常)|(不正常)
2.面板指示灯及蜂鸣器的功能(正常)|(不正常)
3.系统事件及历史记录(正常)|(不正常)
二、空调内部检查:
1.断路器(正常)|(不正常)
2.接触器(正常)|(不正常)
空调日常维护保养记录

空调日常维护保养记录概述本文档旨在记录空调设备的日常维护保养情况,以确保空调设备的正常运行,提高其使用寿命和性能。
日期- 维护日期:[日期]- 下次维护日期:[日期]维护人员- 维护人员:[姓名]- 联系方式:[联系方式]维护内容清洁过滤器- 检查过滤器的状况,如有污垢或损坏,及时更换或清洁。
- 使用清洁剂和软刷清洁过滤器。
注意避免使用过热水或化学溶剂进行清洗。
- 清洁后将过滤器晾干或用干净的布擦干。
清洁内外机- 使用湿布或软刷清洁内外机的表面。
注意避免使用过热水或化学溶剂进行清洗。
- 清洁时应断电,并注意避免水渗入电器部分。
检查制冷剂- 检查制冷剂的压力和液位,确保在正常范围内。
- 如发现制冷剂泄漏或液位异常,需及时联系维修人员进行处理。
检查排水系统- 检查排水管道是否畅通,如有堵塞应清洁或疏通管道。
- 检查排水桶或盘的放置情况,确保能够有效收集冷凝水。
检查电气连接- 检查电气线路连接是否松脱或腐蚀,如有问题应及时修复或更换。
检查控制器- 检查空调控制器的功能是否正常,如有异常应及时修复或更换。
其他维护事项- 记录空调运行时的异常情况,并及时联系维修人员进行排查和处理。
- 如有其他维护保养需要,应根据实际情况进行记录和处理。
维护结果- 维护情况:[维护情况描述]- 是否存在问题:[是/否]- 如有问题,请描述问题的具体情况:下次维护计划- 下次维护计划:[日期或具体时间段]- 预期维护内容:[维护内容描述]以上是本次空调日常维护保养记录,谢谢!。
诺华制药压缩空气系统维护保养记录

FRM-000305 Version : 02Effective from : 29.10.2008SOP reference: SOP-000347Preventive Maintenance Record for Compressed Air System压缩空气系统维护保养记录Approvals 批准人:Applicability : document applies for Beijing Novartis Pharma Ltd.All Plant QC QA HR/Admin. ProductionProcessingPackagingSemi SolidEngineering SCM BPAother :Replaces No: FRM-000305 Version 01 Reason for Change:Detailed …How to do it ‟ was added. 6 items was added. Translate to Chinese. Reference SOP : SOP-000347Preventive Maintenance Record for Compressed Air System压缩空气系统维护保养记录NB. for daily routine maintenance refer to FRM-000306: Monitoring Logbook for Compressed Air System被注:日维修记录在FRM-000306。
1 Quarterly季度维护保养Quarterly PM Checklist WO No.:Responsible Technician: Scheduled Date:SOP reference: SOP-000347 Page: 1/4压缩空气系统维护保养日志SOP reference: SOP-000347 Page: 2/4压缩空气系统维护保养日志Describe repair and maintenance if applicable during Preventive Maintenance briefly: 如果在预防性维护保养其间有其它维修工作被执行,详细记录如下:Reviewed by Clean Utility:Comments:SOP reference: SOP-000347 Page: 3/4压缩空气系统维护保养日志2 Annually年度维护保养Annually PM Checklist WO. No.:Responsible Technician: Scheduled Date Window:Describe repair and maintenance if applicable during Preventive Maintenance briefly如果在预防性维护保养其间有其它维修工作被执行,详细记录如下:SOP reference: SOP-000347 Page: 4/4压缩空气系统维护保养日志Reviewed by Clean Utility:Comments:SOP reference: SOP-000347 Page: 5/4。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
FRM-000392 Version : 01
Effective from : 23.06.2008
SOP reference : SOP-000217
Working Activities Preventive Maintenance for HVAC System (Daily)
空调系统的日预防性维护保养项目
Approvals 批准: Name 姓名: Date 日期: Signature 签名
:
Author 作者:
Approvers 批准人:
Final Approver 最终批准人:
Applicability : document applies for Beijing Novartis Pharma Ltd. 适用性:文件适用于北京诺华制药有限公司
All Plant QC QA HR/Admin. Production Processing Packaging Semi Solid
Engineering SCM
BPA
other :
Replaces No. 替代: N/A Reason for Change 更改原因: New form
Reference SOP 参考SOP: SOP-000217
SOP reference : SOP-000217 Page:1/1
空调系统的日预防性维护保养项目 Item
Content 内容
Acceptance Criteria
接受标准
Performed by
执行人
000 Normally check 常规检查
010 Daily record of temperature, relative humidity, pressure drop of filters and fans, room pressure difference; 日记录温度,相对湿度,压差
Reference: FRM-000222, FRM-000346 完成表格: FRM-000222, FRM-000346
Morning and Evening Shift 大夜, 小夜
011 Check if leakage from hot water and chilled water; 检查热水,冷冻水是否漏水
No leakage 无泄漏 Day Shift 白班 012
Check temperature of hot water and chilled water; 检查热水,冷冻水的温度
The temperature of supply hot water is 60℃.
The temperature of supply chilled water is 7℃. 热水温度为60℃,冷冻水温度为7℃
Day Shift 白班 013 Check if abnormal noise from equipment; 检查所有设备是否有杂音
There is no abnormal noise from equipment,
check the supply air fan, return air fan. pump.
检查送风机,回风机,水泵,没有异常声音. Morning and Evening Shift
大夜, 小夜各一次
014 Check status of each equipment; 检查所有设备运行状态
Running 运行正常 Morning and Evening Shift 大夜, 小夜各一次 020 Check the four chillers on the roof 检查屋顶的4台制冷机
021 Check the compressor, hear the noise. 检查压缩机,听声音 There is no abnormal noise from compressor 无奇怪声音 Day Shift 白班 022 Check the Fan 检查风扇
Running 全部运行
Day Shift 白班 023 Check the Condenser 检查冷凝器
Clean, otherwise Clean them using dust collector on Thursday
干净,否则安排星期四小夜清洁,使用吸尘器。
Day Shift 白班
216 Check the pressure gauges in the chillers 检查制冷机的压力表
No damaged, no leakage. 无损坏,无泄漏
Day Shift 白班 217 Check the temperature gauge in the inlet and outlet pipe 检查制冷机的进出口管道的温度表
No damaged, no leakage. 无损坏,无泄漏
Day Shift 白班 030 Check the Seven chilled water pumps on the technology floor
检查技术夹层的7台冷冻水循环泵
031
Check the chiller water pumps. Touch them by hand, hand can keep on
Morning and Evening Shift
SOP reference : SOP-000217 Page:2/1
空调系统的日预防性维护保养项目 Item
Content 内容 Acceptance Criteria
接受标准
Performed by
执行人
检查冷冻水泵
them.( first quickly touch them using hand back to confirm there is no power in the pump body) 用手摸水泵壳体,手可停留(先用手背迅速摸,确认是否带电)
大夜, 小夜各一次
032
Check the motor of the chiller water pumps 检查水泵电机
Touch them by hand, hand can keep on them. ( first quickly touch them using hand back to confirm there is no power in the motor body) 用手摸电机壳体,手可停留(先用手背迅速摸,确认是否带电)
Morning and Evening Shift 大夜, 小夜各一次
033 Check the mechanical seal 检查机械密封
There is no water leakage. 无水泄漏
Morning and Evening Shift 大夜, 小夜各一次
034 Hearing the pump and motor 听声音
There is no abnormal noise from equipment 无杂音
Morning and Evening Shift 大夜, 小夜各一次
040 Check hot water tank 检查热水分水缸 No damage, no leakage 无损坏,无泄漏
Morning and Evening Shift 大夜, 小夜各一次
050 Check chilled water tank 检查冷水分水缸
No damage, no leakage 无损坏,无泄漏
Morning and Evening Shift 大夜, 小夜各一次
060 Check the existing chilled water system pressure 检查老的冷冻水系统压力
2.0~ 2.5 bar on chilled water supply tank 冷冻水供水分水缸压力在2.0~2.5公斤
Morning and Evening Shift 大夜, 小夜各一次
070
Check the extension chilled water system pressure 检查新的冷冻水系统压力
2.0~2.5 bar on outlet pipe of chilled water tank 冷冻水供水泵出口压力在2.0~2.5公斤
Morning and Evening Shift 大夜, 小夜各一次
Note: These are daily working activities of preventive maintenance for HAVC System, hot water system. Chilled water system. The purpose of the form to describe the working activities detail and acceptance criteria. So it can guide the daily operation. Because these working activities aren’t GMP critical items, so no record for these activities.
如果一切正常,在房间的ROOM Logbook 上记录”日检查,一切正常”; 如果有特殊情况备注说明.。