菲尼克斯防雷器、电涌防护器使用说明书

合集下载

菲尼克斯防雷

菲尼克斯防雷

1. Ignition due to triggervoltage -> 0.9 or 1.5 or 2.5 kV 2. Arc bridges the distance between electrodes 3. Arc is driven outwards… 4. sprayed over the crash plate form the electrode tips 5. Arc is distributed... 6. moves across the arc transfer plates 7. Arc transfer plates feed the arc in between the eraser plates 8. Between the eraser plates single arcs are created and
雷击电流放电器
过电压放电器
L1
L2
kWh
L3
Z
PEN
设备保护器
主配电 6 kV 二次配电 4 kV
绝缘材料的最大冲击耐压
2,5 kV 用电器 1,5 kV
有效的保护圈:
接收、发送馈线
数字电讯 以太网,5类电缆 RS485 视频信号 ....
TT 362 18.02.98
电源线路 24 / 230 / 400 / 690 V
电源第三级保护 PT2-PE/S-230AC
插拔式防雷保护单元 适用单相电源的保护 插头含有失效指示窗口 基座含有远程报警接口FM 额定浪涌放电电流(每相)
Imax = 10KA (8/20)µs
紧凑设计: 仅 17.5mm宽 (1TE)
TN-C-S-System
电力公司
主配电
二次配电

雷击浪涌设备操作规程

雷击浪涌设备操作规程

雷击浪涌设备操作规程一、前言为确保雷击浪涌设备的正常运行和安全使用,保护设备和人身安全,制定本操作规程。

本规程适用于雷击浪涌设备的操作和维护人员。

二、操作前准备1.了解设备操作人员应熟悉雷击浪涌设备的使用方法、工作原理和相关技术要求,熟悉设备的构造和各部件的功能。

2.安全检查操作人员应检查设备的电源和接地是否正常,设备是否完好无损,各连接线是否松动或破损。

3.个人防护操作人员应穿戴符合要求的防静电服、绝缘鞋等个人防护装备,避免静电引起的危险事故。

三、操作流程1.启动设备a.检查电源开关和设备状态指示灯,确保设备处于关闭状态。

b.打开电源开关,设备状态指示灯亮起。

c.按操作要求设置设备参数,如雷击电流、浪涌电压等。

d.按下启动按钮,设备开始工作。

2.使用设备a.避免操作人员接近设备或触摸设备,防止意外触电或受伤。

b.根据需要调整设备参数,保证设备工作的稳定性和有效性。

c.监测设备的运行状态和工作指示灯,及时发现异常情况并进行处理。

d.严禁私自修改设备参数或操作设备未经许可的功能。

3.关闭设备a.按下停止按钮,设备停止工作。

b.关闭电源开关,设备状态指示灯熄灭。

c.检查设备的各连接线是否松动或破损,必要时进行修复或更换。

d.清理设备及操作区域,保持设备的清洁整洁。

四、维护保养1.定期检查a.按照设备的使用说明书和维护手册,定期进行设备的检查和维护。

b.检查设备的电源线、接地线是否正常,设备各部件是否运转灵活可靠。

c.清洁设备外壳和内部零部件,避免灰尘和杂物对设备的影响。

2.日常维护a.根据设备运行情况,定期检查设备的软件系统,更新或升级系统版本。

b.根据设备厂家的要求,更换设备的易损件,保证设备的正常使用寿命。

3.故障处理a.在设备出现故障时,应立即停机,并进行初步排查。

b.对于能够修复的故障,操作人员应按照维修要求进行修复。

c.对于无法修复的故障,操作人员应及时向设备经销商或厂家报修,并按照要求进行后续处理。

rg菲尼克斯说明书

rg菲尼克斯说明书

rg菲尼克斯说明书菲尼克斯稳压电源l品牌:PHOENI-菲尼克斯l名称:菲尼克斯稳压电源l型号:QUINT-PS-100-240AC、24DC、10l产品简介:l可将不稳定的或非24V等级直流电压变换成可调节的24V电压。

输入和输出完全隔离,适用于直流高隔离要求场合。

预警监视功能通过继电器触点和晶体管有源输出及时地将电源故障信号输出。

l产品详细:l可将不稳定的或非24V等级直流电压变换成可调节的24V电压。

输入和输出完全隔离,适用于直流高隔离要求场合。

预警监视功能通过继电器触点和晶体管有源输出及时地将电源故障信号输出。

基本参数:1、输入数据:标称输入电压100伏交流。

240伏交流AC输入电压范围85V交流。

264V交流直流输入电压范围90V直流电。

350V直流电交流频率范围45HZ。

65HZ直流频率范围0HZ电流消耗约:2、4A(120伏交流电)1、3A(230伏交流电)标称功率消耗240W瞬间冲击电流“15”(典型值)电力故障旁路“50毫秒”(120伏交流电)“50毫秒”(230伏交流电)输入保险丝6。

3A备用保险丝推荐10A(16A)2、输出数据:额定输出电压:24伏直流±1%设置输出的电压范围:22、5V直流电。

28。

5V直流电输出电流:10A(最多至60°C),15A(电力升压时)并联:是,当有剩余且增加负载的时候串联:是剩余波值:“30mVPP”峰值开关电压额定负载:“50mVPP(20MHZ)空转最大功耗:4W标称功率损耗最大负荷:33W3、普通参数:宽度85mm高度130mm深度130mm重量1、3kg工作电压显示方式:绿屏LED效率:88%输入、输出绝缘电压值:2kv(常规测试)4kv(模范试验)保护程度:IP20保护等级:1级。

用PE连接时平均无故障工作时间:> 500 000 h in acc。

with IEC 61709 (SN 29500)操作环境温度:-25℃。

M-SYSTEM CO,LTD MD7FB电子设备专用避雷器 说明书

M-SYSTEM CO,LTD MD7FB电子设备专用避雷器 说明书

电子设备专用避雷器 M-RESTER 系列FOUNDATION Fieldbus用避雷器机型: MD7FB-①② ①、②在下列代码中选择。

(例如: MD7FB-FF0)选择防爆认证代码2时,必须在订购表格 (No.ESU-8057)上指定使用国家。

①屏蔽端子 (对地)FF: 浮空FG: 接地②防爆认证0: 无2: CENELEC本质安全型(ATEX)通讯总线注)总线的电源必须限制在400mA以内保护等级: IP20连接方式: 欧式端子连接 (螺丝的许容扭矩为0.3N·m)端子适用电线: 0.2~2.5mm2接地方式: DIN导轨接地机壳材质: 黑色耐燃性树脂・无防爆认证: -25~+85℃・有防爆认证: 参照防爆规格之项使用湿度范围: 30~90%RH (无冷凝)安装: DIN导轨安装 (TH35-7.5 厚度1mm)(铝制导轨的表面氧化现象将会影响本机器与接地之间的导电性。

请使用铁制或铜制的导轨。

)重量: 约70gSHLD-接地间为短路。

最大工作电压 (Uc)・线间: ±32V・线-接地间: ±160V・SHLD-接地间: ±160V电压保护水平 (Up) (@4kV (1.2/50μs) )・线间: ±60V・线-接地间: ±800V・SHLD-接地间: ±800V响应时间・线间: 4ns以下・线-接地间: 20ns以下・SHLD-接地间: 20ns以下漏电流 (@最大工作电压)・线间: 5μA以下・线-接地间: 5μA以下・SHLD-接地间: 5μA以下放电容量 (Imax) : 20kA (8/20μs)、1.0kA (10/350μs)最大负载电流 (I N) : 400mA内部串联电阻: 1.5Ω±10% (每条导线)静电容量 (@10kHz)・线间: 约1500pF・线-接地间: 约100pF・SHLD-接地间: 约100pFATEX指令(94/9/EC) Ex ia EN 60079-11:2007 Category 1G EN 60079-26:2007电磁兼容指令(EMC指令)(2004/108/EC) EMI EN 61000-6-4:2007 EMS EN 61000-6-2:2005认证:CENELEC 本质安全型防爆(ATEX) II 1G,Ex ia IIC,T4,T5 EN 60079-0:2006 EN 60079-11:2007 EN 60079-26:2007 EN 60079-27:2008浪涌保护性能: IEC 61643-21: 2000 (类别C1、C2、D1)安全保持器FISCO 电源Ui(Vmax)32V 17.5V Ii(Imax)any 400mA Ci 5nF 5nF Li0μH0μHPi 温度等级环境温度5.4WT4-25~+40℃1.3W -25~+60℃1.2W -25~+80℃1.0W T5-25~+40℃1.0W8-M3欧式端子约20°(插入电缆线的角度)※1、选择接地 (FG) 时为短路。

CDYN电涌保护器 使用说明书

CDYN电涌保护器 使用说明书

CDYN电涌保护器使用说明书安装、使用产品前,请仔细阅读使用说明书并妥善保管、备用安全告知在安装、操作、运行、维护、检查之前,请务必认真阅读本说明书,并按照说明书上的内容准确安装、使用本产品。

危险:●严禁湿手操作电涌保护器;●使用中,严禁触摸导电部位;●维护与保养时,必须确保产品不带电;注意:●安装、维护与保养时,应由具有专业资格的人员操作;●使用前请确认产品可持续工作电压、标称放电电流、电压保护水平是否符合工作要求;●指示窗口显示红色表示产品已经损坏,需要更换。

●火线支路上应串联后备保护用的保险丝或断路器,接地系统要有良好的连接。

●产品报废时,请做好废弃物处理,谢谢您的合作。

目录1主要用途及适用范围 (1)2产品面板介绍 (1)3正常使用、安装及运输条件 (3)3.1正常使用、安装条件 (3)3.2正常贮存和运输条件 (3)4技术特性 (3)4.1主要技术参数 (3)5外形及安装尺寸 (4)6安装和使用(维护) (6)6.1安装 (6)6.2维护与保养 (7)7开箱检查 (7)8公司承诺 (7)1主要用途及适用范围CDYN系列电涌保护器主要用于交流50Hz/60Hz、额定电压230V/400V的单相/三相配电系统,用于抑制瞬态过电压,泄放电涌能量,防止或减轻因雷击或操作引起的瞬态过电压对设备造成的损害。

2产品面板介绍CDYN-IIICDYN-II/20、CDYN-II/40、CDYN-II/65CDYN-II/80、CDYN-II/120CDYN-II/160、CDYN-I+II/12.5、CDYN-I+II/15说明:1接线符号 2进线端子 3德力西品牌 4产品型号5主要技术参数:In-标称放电电流,Imax-最大放电电流,Up-电压保护水平,Uc-最大持续工作电压,Uoc-开路电压,Iimp-冲击电流6出线端子 7遥信端子接线图 8遥信端子工作状态指示窗口:A:绿灯亮表示防雷功能正常,绿灯灭表示防雷功能失效。

电子设备的防雷浪涌保护实用指南说明书

电子设备的防雷浪涌保护实用指南说明书

CONTENTS PAGE (1)I ONI NTRODUCT11.1 Voltage surges and lightning strikes (1)1.2 Lightning protection — standards, devices and dangers (1)1.3 Guide to protection (1)2 LIGHTNING ACTIVITY AND VOLTAGE SURGES (1)2.1 General (1)2.2 Resistive coupling (1)2.3 Inductive coupling (2)2.4 Capacitive coupling (2)3 SURGE PROTECTION DEVICES — THE PRINCIPLES (2)3.1 Magnitude of lightning-induced surges (2)3.2 Surge protection components (3)4 SPDs FOR MAINS POWER SYSTEMS (3)4.1 General (3)4.2 ‘Ideal’ specification for a mains power SPD (4)5 SPDs FOR DATA/TELECOMMUNICATIONS SYSTEMS (4)5.1 General (4)5.2 ‘Ideal’ specification for a data/telecommunications SPD (4)6 INSTALLATION PRACTICE (5)6.1 Mains power SPDs (5)6.2 Data/telecommunications SPDs (5)7 LIGHTNING PROTECTION SYSTEMS — CHECKLIST (5)7.1 I ntroduction (5)7.2 Structural lightning protection (5)7.3 Protection for internal equipment (5)1I NTRODUCTI ON1.1 Voltage surges and lightning strikesVoltage surges are momentary increases in the normal working voltage of a system. Sometimes referred to as ‘spikes’, ‘overvoltages’ or ‘transients’, these surges can affect power cables, data/telephone cables and instrumentation wiring, causing anything from data loss to the total destruction of equipment. Typical causes include fluorescent light switching, blown fuses and nearby lightning activity — the last of these being potentially the most dangerous.Lightning storms are on the increase globally — including the UK where more than 420,000 lightning strikes to ground were recorded in 1994. Also on the increase is industry’s reliance on sensitive electronic instrumentation, com-puters and communication networks. These make uneasy bedfellows as light-ning-induced voltage surges damage or destroy delicate equipment with all the consequent costs associated with repairs, replacements and downtime.1.2 Lightning protection — standards,devices and dangersThe current Electrical Wiring Regulations (BS7671) refer to the British Stan-dard for Lightning Protection BS6651. This identifies two distinctive forms of lightning protection, i.e. one designed to protect the building structure and fabric and a second to protect sensitive equipment inside the building.The traditional mesh of copper tapes on roofs and walls and their associated earth rods, properly installed, protect the bricks and mortar but not, except to a very limited degree, electronic equipment within the building. T he latter need protecting with ‘surge protection devices’ (SPDs).SPDs do not (indeed cannot) protect equipment against direct lightning strikes. Their concern is to neutralise voltage surges on cables caused by inductive or resistive coupling from nearby lightning strikes. In particular, SPDs should be fitted on the mains power supply lines and incoming data/signal cables to/ from all critical sensitive equipment. Cables such as these — and consequently any equipment associated with them — are particularly at risk as they are partly installed outside the building where they are more vulnerable to the effects of nearby lightning strikes. A strike within 100m of cables or buildings can induce surges up to 5kV and 1.25kA.Also at great risk are sites powered from overhead cables. Any direct lightning strikes to the power network will travel along the cables to the detriment of any equipment powered by these since surges on mains power cables can rise to a level of more than 6kV and 3kA.1.3 Guide to protectionThis p ublication p rovides a n e asy-to-read g uide t o t he d angers i nduced b y l ight-ning strikes and cost-effective ways to combat these with surge protection devices.2 LIGHTNING ACTIVITY AND VOLTAGE SURGES2.1 GeneralA direct lightning strike can cause an enormous amount of physical damage. However, the indirect effects from a nearby strike can also cause damage by inducing voltage surges onto mains and data cables.Lightning-induced voltage surges are often described as a ‘secondary effect’ of lightning and there are three recognized means by which these surges are induced in mains or data/telecommunications cables:-a) Resistive coupling (see section 2.2)b) Inductive coupling (see section 2.3)c) Capacitive coupling (see section 2.4)2.2 Resistive couplingWhen lightning strikes the ground near a building it causes a massive rise in ground voltage in the vicinity. This rise in ground voltage affects electrical earthing systems (earthed pipework, etc.) and is conducted back through these into the building where it can travel through the electrical system — cre-ating havoc along its path. Additionally, any data or telecommunications cables connecting the affected building to a second building provide a path for the currents to infect that building also. See figure 1.2.3 Inductive couplingA lightning strike onto a lightning conductor forming part of the structural protective system of a building generates a large electromagnetic pulse of energy which can be picked up by nearby cables in the form of a destructive voltage surge. See figure 2.2.4 Capacitive couplingOverhead high-voltage power distribution cables are naturally prone to direct Figure 1 Resistive coupling from a lightning strike near one buildinglightning strikes. While much of the lightning energy is dissipated by integral high voltage surge protection devices, a large proportion will travel along the distribution system and, due to its high frequency nature, will capacitively cou-ple through HV/LV power transformers into the power systems of individual buildings, devastating any electronic equipment it feeds. See figure 3.3 SURGE PROTECTION DEVICES — THE PRINCIPLES3.1Magnitude of lightning induced surgesVoltage surges on cabling systems, however they may be caused, are limited in magnitude by the insulation of the cable and any electrical or electronic equipment connected to it. In other words, if a rising voltage is applied to a cabling system, a point will come when the insulation of either the cable or the associated equipment breaks down and the voltage ‘flashes over’, thuspreventing it rising any further.IEC 60664 defines practical limits for the breakdown voltage of cable insula-tion within a building. The British Standard for lightning protection, BS6651, defers to IEEE C62.41 (in which measurements of induced voltage surges on cabling systems are discussed) to determine the maximum voltage surge that is likely to travel along a cable and, hence, the maximum voltage surge that a surge protection device (SPD) must divert successfully to protect the equip-ment connected to the cable.IEEE C62.41 tells us that the largest surge that is likely to appear on the bus-bars of the main power distribution board for a building is 6kV and 3kA, de-fined as ‘Category B’ (figure 4). Hence, an SPD fitted to the board must be able to divert safely a surge of this magnitude. IEEE C62.41 also explains that the maximum surge current caused by lightning is limited by the impedance of the cabling system, which, in turn, is related to the current rating of the circuit. A low impedance 1kA busbar distribution board could possibly pass 3kA of lightning induced current, whereas a higher impedance 30A twin and earth branch circuit, some distance away from the main incoming distribution board, could pass only 200A due to its higher impedance.Figure 2 Inductive coupling from a lightning strike on a lightning conductorFigure 3 Capacitive coupling from a direct lightning strike on overhead cablesFigure 4 BS6651 and IEEE C62.41 location categoriesData/telecommunications cables linking buildings are generally considered to be in Category C, as the slower surge voltages seen on these systems (10/700µs) are not attenuated in the same way as those on mains power cabling.Further details on the nature of these surges is provided in TAN 1002.3.2 Surge protection componentsWhen selecting components for use in a surge protection device, designers are compelled, by the current state of technology, to choose between high cur-rent handling capability and high speed operation. Some possible components are strong in one of these parameters and others in the other. In practice, therefore, SPDs often make use of a combination of components, known as a ‘hybrid circuit,’ for effective protection.Lightning induced voltage surges can rise from zero to up to 6kV in about 1µs. Surge diverting components must therefore operate quickly. Fuses and circuit breakers do not provide protection as they simply cannot work quickly enough.Voltage-limiting components used in modern SPDs are usually selected from three main types:—a) Gas discharge tubes (GDTs)b) Metal oxide varistors (MOVs)c) High-speed clamping diodesGas discharge tubes can handle very high surge currents, but are relatively slow to start and can thus let through a lot of the surge before they operate (figure 5a).Metal oxide varistors can handle fairly high surge currents, but their clamping voltage rises the more surge current that passes through (figure 5b).High-speed suppression diodes can only handle relatively small surge cur-rents, but they do have very accurate and rapid voltage clamping performance (figure 5c).4 SPDs FOR MAINS POWER SYSTEMS4.1 GeneralWhen considering surge protection for a mains power system, the ability of the whole system to withstand voltage surges should be considered, i.e. the surge protection device (SPD) must be capable of limiting any surge voltages to a level considered safe for the most vulnerable piece of equipment served by the system. It must also be able to divert safely the maximum surge cur-rent likely to be experienced by the system it is protecting, i.e. the IEEE defined location category (A, B or C — see section 3.1) should be borne in mind. Generally, most low voltage power systems (240/415V) and the electronic and electrical equipment with which they are associated, can withstand volt-age surges of two to three times their normal peak operating voltage, i.e. around 1kV for 240V (rms) systems, (8/20µs, 3kA waveshape, according toBS6651, Appendix C).Figure 5 Performance of surge protection components4.2 ‘Ideal’ specification for a mains power SPDTable 1 lists the specification parameters that should be considered when selecting SPDs for mains supply applications.Table 1 Specification parameters for a mains power SPD ParameterRequired performance Limiting voltage:* <1kV(often known as ‘let-through’ voltage) Modes of operation: Phase to neutral Phase to earthNeutral to earth Peak surge current: † Category A >1kA Category B >3kACategory C >10kA Leakage current: <0.5mA (phase to earth)Indication:Visual indication of statusVolt-free contact: This should be provided for high risk applications, where remote indication of reduced protection isrequiredIP protection rating: IP40 for internal applicationsIP65 for outdoor applications Temperature/humidity: Suitable for environmentSystem impairment: The SPD should not interfere with the normal operation of the system into which it is connectedNote: Gas discharge tubes should not be connected directly across mains cables as they can shortcircuit the supplyNotes* As tested on the connection terminals of the complete SPD, when tested with the 1.2/50µs voltage and 8/20µs current waveforms appropriate to their location, e.g. 6kV/3kA for Category B, as defined in BS6651, Appendix C.† Peak surge current is an indication of the lifetime of the complete SPD, e.g. a device in which the surge protection elements will handle a peak surge of 20kA will withstand many lightning induced currents of 3kA, asdefined in BS6651, Appendix C.5 SPDs FOR DATA/TELECOMMUNICATIONSSYSTEMS 5.1GeneralWhen considering surge protection for a data /telecommunications system, the ability of the whole system to withstand voltage surges should be consid-ered, i.e. the surge protection device (SPD) must be capable of limiting any surge voltages to a level considered safe for the most vulnerable piece of equipment served by the system. It must also be able to divert safely the maxi-mum surge current likely to be experienced by the system it is protecting, i.e.the appropriate IEEE defined location categories (A, B or C — see section 3.1) should be borne in mind. As an example, cables outside buildings are‘Category C’.Generally, most data/telecommunication cabling systems and the equip-ment with which they are associated, can safely withstand voltage surges of twice their normal peak operating voltage, e.g. around 48V for 24V systems (8/20µs).Some manufacturers specify a reaction time of ’10ns’ for their devices. This figure relates to the performance of individual components within the circuit.It cannot relate to the performance of the complete SPD as the impedance ofeven short connections between the device terminals and the internal com-ponents makes such a performance impossible. I t is also misleading since the fastest voltage surge the SPD will experience is the 10/700µs waveform used to define its limiting performance. If the device was slow to operate, this would be reflected by its performance and the limiting voltage would be too high.5.2 ‘Ideal’ specification for a data/telecommunications SPDTable 2 lists the specification parameters that should be considered when selecting SPDs for data/telecommunications applications.Table 2 Specification parameters for a data/telecommunications SPDParameter Required performanceLimiting voltage:* Twice the peak operating voltage of (often known asthe circuit with which the SPD is‘let-through’voltage) usedPeak surge current: † Category C (low) 2.5kA Category C (high) 10kASystem impairment: The SPD should not interfere with the normal operation of the systemwith which it is usedInsertion loss: Expressed as an equivalent cablerun lengthBandwidth: Normally expressed at the 3dBpoint in a 50ž systemIn-line resistance: Note: If the value for in-line resistance is 0, then it is possible the SPD will not operate undersome conditions, leaving the system unprotectedVoltage standing wave An indication of the effect the SPDratio:will have on the networkShunt capacitance:This affects the bandwidthTemperature/humidity: Minimum and maximum values should be quoted Notes* As tested on the connection terminals of the complete SPD, when tested with the 10/700µs current waveforms appropriate to their location.† Peak surge current is an indication of the lifetime of the complete SPD, e.g. a device that will handle a peak surge of 10kA will withstand many lightning induced currents of 125A.Figure 6 Typical shunt SPD connection details6 INSTALLATION PRACTICE 6.1 Mains power SPDs 6.1.1Shunt connecting SPDsLong connecting leads impair the effectiveness of an SPD installation (1m of 16mm2 earthing cable can generate more than 300V along it’s length when a surge of 6kV/3kA is applied to it). Hence, the SPD should be mounted and connected as close to the electrical system it is to protect as possible. See figure 6 for three ways in which this might be done.6.1.2 In-line connecting SPDsTo reduce the risk of picking up voltage surges in cable runs caused by induc-tive and capacitive coupling, in-line connecting SPDs should be connected as close to the protected equipment as possible. See figure 7.6.2 Data/telecommunications system SPDsGenerally, all SPDs designed for protecting data and telecommunications sys-tems connect in-line. These should be located as close to either the protected equipment or to the main power earth for the protected equipment as pos-sible. The length of the SPD connections to the electrical earth of the equip-ment should be no longer than 1m in length.Connection of this earth cable can be made to either the earth terminal of the equipment itself, or to the earth bar of the electrical power supply feeding the equipment. See figure 8 for illustrations of both these forms of connection.7 LIGHTNING PROTECTION SYSTEMS —CHECKL I ST7.1 I ntroductionThis checklist is designed to help guide users through a brief visual check toestablish whether a site is effectively protected against the effects of lightning (according to BS6651, including Appendix C) both with respect to structure and electronic computer networks, telecommunications, and process and control equipment. If the answers to the questions include doubts, a special-ist should be consulted to offer advice. Eaton operates a lightning protection consultancy service staffed by experts qualified to provide sound advice from design to implementation. For details, contact your local sales representativevia: /support/distribution/index.htm.Figure 7 In-line SPD connection detailsFigure 8 Connections of data/telecommunications SPD earths7.2 Structural lightning protectionTick boxQ1 Does the building have an intact roof conductor network? (Wherever an observer stands on the roof, a lightning conductor should be visible no more than 10m away)Q2 Does the building have an intact system of down-conductors?(There should be an intact down-conductor located at least every 20m around the perimeter of the building)Q3 Does each down-conductor connect to an intact earth pit and earth rod? (Check that the down-conductor issecurely fastened to the earth rod)7.3 Protection for internal equipmentTick boxQ4 Is there a lightning surge protection device (SPD) installed on the main power distribution board/incomingpower board?(Check for the correct installation — see section 6.1.1)Q5 Is an SPD installed on the telecommunication linesfeeding modems and telemetry equipment?(Check for the correct installation — see section 6.2)Q6 If the controls section of switchgear cubicles contain sensitive electronic equipment (e.g. flowmeters, PLCs, computers, etc.) is the power feed into this section protected by a locally connected (i.e. within 1m) in-line SPD?(Check for the correct installation — see section 6.1.2)Q7 Are data/signal/network cables installed outside the building over distances of more than 10m (either underground or overhead) equipped with SPDs at the controlssection end of the cables?(Check for the correct installation — see section 6.2)Q8 Is any field-mounted equipment that is critical for the process or expensive (e.g. magflows, ultrasonic instrumentation, etc.) provided with locally-mounted(less than 1m distance) SPDs?EUROPE (EMEA): +44 (0)1582 723633 ********************THE AMERICAS: +1 800 835 7075*********************ASIA-PACIFIC: +65 6 645 9888***********************The given data is only intended as a productdescription and should not be regarded as a legal warranty of properties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.Eaton Electric Limited,Great Marlings, Butterfield, Luton Beds, LU2 8DL, UK.Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283E-mail:********************© 2016 EatonAll Rights ReservedPublication No. AN904-1001 Rev G 211016 October 2016AUSTRALIAMTL Instruments Pty Ltd,10 Kent Road, Mascot, New South Wales, 2020, Australia Tel: +61 1300 308 374 Fax: +61 1300 308 463E-mail:*********************BeNeLuxMTL Instruments BVAmbacht 6, 5301 KW Zaltbommel The NetherlandsTel: +31 (0)418 570290 Fax: +31 (0)418 541044E-mail:*********************CHINACooper Electric (Shanghai) Co. Ltd955 Shengli Road, Heqing Industrial Park Pudong New Area, Shanghai 201201Tel: +86 21 2899 3817 Fax: +86 21 2899 3992E-mail:****************FRANCEMTL Instruments sarl,7 rue des Rosiéristes, 69410 Champagne au Mont d’Or FranceTel: +33 (0)4 37 46 16 53 Fax: +33 (0)4 37 46 17 20E-mail:*******************GERMANYMTL Instruments GmbH,Heinrich-Hertz-Str. 12, 50170 Kerpen, GermanyTel: +49 (0)22 73 98 12 - 0 Fax: +49 (0)22 73 98 12 - 2 00E-mail:*******************INDIAMTL India,No.36, Nehru Street, Off Old Mahabalipuram Road Sholinganallur, Chennai - 600 119, IndiaTel: +91 (0) 44 24501660 /24501857 Fax: +91 (0) 44 24501463E-mail:***********************ITAL YMTL Italia srl,Via San Bovio, 3, 20090 Segrate, Milano, Italy Tel: +39 02 959501 Fax: +39 02 95950759E-mail:******************JAPANCooper Crouse-Hinds Japan KK, MT Building 3F , 2-7-5 Shiba Daimon, Minato-ku,Tokyo, Japan 105-0012Tel: +81 (0)3 6430 3128 Fax: +81 (0)3 6430 3129E-mail:****************NORWA Y Norex ASFekjan 7c, Postboks 147, N-1378 Nesbru, NorwayTel: +47 66 77 43 80 Fax: +47 66 84 55 33E-mail:*************RUSSIACooper Industries Russia LLC Elektrozavodskaya Str 33Building 4Moscow 107076, RussiaTel: +7 (495) 981 3770 Fax: +7 (495) 981 3771E-mail:*******************SINGAPORECooper Crouse-Hinds Pte LtdNo 2 Serangoon North Avenue 5, #06-01 Fu Yu Building Singapore 554911Tel: +65 6 645 9864 / 5 Fax: +65 6 487 7997E-mail:***********************SOUTH KOREACooper Crouse-Hinds Korea 7F . Parkland Building 237-11 Nonhyun-dong Gangnam-gu,Seoul 135-546, South Korea.Tel: +82 6380 4805 Fax: +82 6380 4839E-mail:*******************UNITED ARAB EMIRATESCooper Industries/Eaton CorporationOffice 205/206, 2nd Floor SJ Towers, off. Old Airport Road, Abu Dhabi, United Arab EmiratesTel: +971 2 44 66 840 Fax: +971 2 44 66 841E-mail:*****************UNITED KINGDOM Eaton Electric Ltd,Great Marlings, Butterfield, Luton Beds LU2 8DLTel: +44 (0)1582 723633 Fax: +44 (0)1582 422283E-mail:********************AMERICASCooper Crouse-Hinds MTL Inc. 3413 N. Sam Houston Parkway W.Suite 200, Houston TX 77086, USA Tel: +1 281-571-8065 Fax: +1 281-571-8069E-mail:*********************。

菲尼克斯防雷选型

菲尼克斯防雷选型

4、产品选型设计根据IEC1024-1:1993的表3规定,雷击电流的电荷在实践中应采用(10/350μS)的波形作为雷击电流的测试脉冲,10/350μS波形雷电流的能量相当于8/20 μS波形的17.5倍,另外,两种雷击波形电流存在这样的转换关系:1KA10/350μS的雷击电流相当于4.7KA8/20μS波形。

本次设计选择德国菲尼克斯防雷及浪涌保护产品。

该产品无论在品牌还是质量上都属世界一流。

根据IEC 61643关于SPD电源浪涌保护器的要求及贵方招标文件对电源SPD的技术参数要求做如下选型:4.1电源一级防雷器电源一级防雷器选择菲尼克斯FLT 35/3+1,适用于220V/380V AC系统,并联安装,可承受100KA雷电流,保护水平Up低于1.5KV,是目前防雷领域保护水平Up最低、体积最小的过电压保护器。

FLT 35 CTR系列是德国菲尼克斯公司在全球获得形状、结构、材料设计专利保护的新一代产品。

它具有独特的圆柱状放电间隙,它由负膨胀系数的钛合金材料制作而成,具有能够耐受7000℃的高温高压下不变形的特点(寿命长);动作更加灵敏、可靠、节省更多的安装空间。

FLT 35 是代表当今最领先技术的防雷产品,保证在飞速发展的防雷技术领域不会落后,具有选型的前瞻性。

该类型防雷产品具有如下优势:能直接泄放直击雷电流;具有全摸式保护方式:L-N,N-G(干线),L-L,L-G,N-G(设备)。

残压低,相对地分别降到1500V以下,而且具备截断高达100KA的工频续流能力。

具有特有的“电流闸”特性,使得额定电流值很小的保险装置也不会因此而动作。

具有热容和过流保护功能,通过远程报警接口可提供远程监控。

紧凑设计,节省安装空间。

不受工作电流限制。

需要说明的问题:根据上述对雷电流波形的分析比较,35KA10/350μS的雷电流转换成8/20μS波形为164.5KA,大大满足了电源一级防雷器对雷击电流泄流量的相关要求。

避雷器说明书

避雷器说明书

避雷器说明书一、产品概述避雷器是一种用于保护电力设备和电气设备的重要装置。

它可以有效地避免因雷电等电气突击而引起的设备损坏或人身伤害。

本说明书将详细介绍避雷器的结构、工作原理、安装要求和维护保养等内容,为用户提供全面的使用指南。

二、结构组成1. 外壳:避雷器外壳采用高强度、耐腐蚀的材料制成,在遭受雷电冲击时能够有效地保护内部结构。

2. 电极:避雷器的电极由高导电性材料制成,能够迅速将雷电冲击的电流引至地下,防止电流通过设备及导线进入电气设备内部。

3. 引线:避雷器引线采用特殊材料制成,具有较高的绝缘性能和电导率。

4. 接地装置:避雷器的接地装置是确保它能有效地将电流引至地下的重要组成部分。

请用户根据安装说明正确安装接地装置,确保其接地电阻符合标准要求。

三、工作原理当雷电冲击避雷器时,其电极将迅速产生放电现象,将大部分电流引至地下。

避雷器的外壳和引线能够有效地阻挡残余电流进一步穿过设备,从而起到保护作用。

四、安装要求1. 安装位置:避雷器应安装在电源输入端,确保其离电气设备的正负极距离适当,一般建议距离设备1米左右。

2. 接地:安装避雷器时,务必正确连接接地装置,确保接地电阻符合标准要求。

3. 防护:在避雷器附近应设置有效的防护装置,防止避雷器受到物理损坏。

五、维护保养1. 定期检查:用户应定期检查避雷器的外观和接地系统,确保其完好无损。

2. 清洁保养:避雷器表面应保持清洁,避免积尘和污垢影响其工作效果。

3. 更换周期:根据实际使用情况和制造商的建议,定期更换避雷器,以确保其性能始终处于良好状态。

六、注意事项1. DIY禁止:用户不得自行拆解或修复避雷器。

2. 过载保护:使用过程中,应根据设备的额定电流和额定电压选择合适的避雷器。

3. 温度限制:避雷器的工作温度应在指定范围内,避免过高温度影响其性能。

4. 存储条件:避雷器在长时间不使用时,应存放在干燥、通风的环境中,避免受潮。

七、常见问题解答1. 避雷器损坏怎么办?如果避雷器损坏,请立即停止使用,并联系售后服务人员进行维修或更换。

菲尼克斯电气过程行业SPD解决方案

菲尼克斯电气过程行业SPD解决方案

新产品发布PT 3-24DC
24V两线制、模拟量/开关量通用 认证:CE、SIL 2、UL认证、SPD型式试验、中国石化 应用:大连新港油码头项目超过1000片 符合石化行业防雷标准SH/T 3164-2012参数
石油化工仪表系统防雷工程设计规范
Uc≥36V Ic≥600mA PT 1×2-24DC 28V 450mA PT 3-24DC 36V 600mA
IEC 61663-1; E 06.97 采用金属芯线的电缆
IEC 61024-1-1; E 09.93 应用准则 A: 避雷装置的 防雷级别的选择 IEC 61024-1-2; E 1996 应用准则 B: 避雷装置的 设计,安装,维护及检测
Legend:图例 D = Draft草案 C = CDV (Committee draft for vote)委员会投票草案 F = FDIS (Final draft international standard)最终草案 TR= Technical report技术报告 TS= Technical specification技术规范(说明)
2
10 28 10 61 26 13 23 23 24
Yamal Europe Gas Pipeline 亚马尔欧洲天然气管道
中航油广州新白云机场油料库
防雷系统通过国家民航总局验收
上海高桥石化炼油厂罐区
石油化工仪表系统防雷工程设计规范 (SH/T 3164-2012)
8.4 信号线路电涌防护器的参数 8.4.1最大持续运行电压Uc 最大持续运行电压Uc即最大工作信号电压(Working Voltage) ,是电涌防护器长期工作的最大信号电压有效值或直流电压。这也 是在额定漏电流条件的线间或线与地之间的不影响其所在电路正常 工作的最大电压。 对于24V直流供电仪表,由于直流电源电压波动及负载变化等因 素影响,最大信号电压的数值为:30~36V DC,因此,最大持续运 行电压为:Uc≥36 V。 8.4.2最大信号电流Ic 最大信号电流(Working Current)是电涌防护器所在线路的最 大工作信号电流。 对于两线制、三线制、四线制的4~20mA信号仪表(包括HART 通信信号),最大信号电流的数值为:Ic≥150mA。 对于24V直流供电线路,如电磁阀、超声波仪表、可燃气体检测 器等仪表,最大信号电流的数值为:Ic≥600mA

菲尼克斯电源说明书

菲尼克斯电源说明书

菲尼克斯稳压电源∙品牌:PHOENIX-菲尼克斯∙名称:菲尼克斯稳压电源∙可将不稳定的或非24V等级直流电压变换成可调节的24V电压.输入和输出完全隔离, 适用于直流高隔离要求场合.预警监视功能通过继电器触点和晶体管有源输出及时地将电源故障信号输出.∙产品详细:∙可将不稳定的或非24V等级直流电压变换成可调节的24V电压.输入和输出完全隔离, 适用于直流高隔离要求场合.预警监视功能通过继电器触点和晶体管有源输出及时地将电源故障信号输出.基本参数:1.输入数据:标称输入电压100伏交流... 240伏交流AC输入电压范围85 V交流... 264 V交流直流输入电压范围90V直流电... 350V直流电交流频率范围45HZ... 65HZ直流频率范围0HZ电流消耗约:2.4 A( 120伏交流电)1.3A( 230伏交流电)标称功率消耗240 W瞬间冲击电流“ 15 ”(典型值)电力故障旁路“ 50毫秒”( 120伏交流电)“ 50毫秒”( 230伏交流电)输入保险丝6.3 A备用保险丝推荐10A(16A)2.输出数据:额定输出电压:24伏直流± 1 %设置输出的电压范围:22.5V直流电... 28.5V直流电输出电流:10 A (最多至60 ° C ),15 A(电力升压时)并联:是,当有剩余且增加负载的时候串联:是剩余波值:“ 30 mVPP ”峰值开关电压额定负载:“ 50 mVPP ( 20MHZ)空转最大功耗:4W标称功率损耗最大负荷: 33 W3.普通参数:宽度85mm高度130mm深度130mm重量1.3kg工作电压显示方式:绿屏LED效率:88 %输入/输出绝缘电压值:2kv(常规测试)4kv(模范试验)保护程度:IP20保护等级:1级.用PE连接时平均无故障工作时间:> 500 000 h in acc. wi th IEC 61709 (SN 29500)操作环境温度:-25 ℃ ... 70 ℃(>60 ℃降额值)环境温度(储存/运输):-40 ℃ ... 85 ℃操作环境可允许的最大湿度值:100 %(允许冷凝)组装说明:水平0c m,垂直5c m。

菲尼克斯电子断路器说明书

菲尼克斯电子断路器说明书

菲尼克斯电子断路器说明书
1.商品名称:菲尼克斯电子断路器。

2.商品毛重:1.0kg。

3.安装类型:安装在基座上。

4.颜色:黑色。

5.位数:1。

6.过电压类别GRP:II。

7.绝缘材料:PA66/6。

8.阻燃等级,符合UL94:V0。

9.保险丝:电子。

10.保险丝类型:自动设备。

11.额定过电压:0.5kV。

12.标称工作电压:24VDC。

13.工作电压:18VDC—32VDC。

14.额定电流IN:4A。

15.要求的备用保险丝:不需要,内置本安元件。

16.介电强度:大32VDC(负载电路)。

17.污染等级:2。

18.过电压类别GRP:II。

19.绝缘材料组:I。

20.开关容量ICN:主动电流限制。

21.闭路电流范围I0:典型值25mA±5mA(接通时)。

22.高度:60mm。

23.宽度:12.5mm。

24.深度:70mm。

25.完整模块高度:115mm。

26.完整模块宽度:38mm。

27.完整模块深度:112.5mm。

28.菲尼克斯电子断路器安装说明:当成排安装且无对流冷却时,由
于热影响,在持续操作中,额定设备电流通常大只能达到80%(操作系数)。

为元器件的重新启动,或机械中应采取特殊的措施(如使用安全PLC)。

不允许并行连接多个断路器。

雷电浪涌防护器培训资料

雷电浪涌防护器培训资料

雷电浪涌防护器培训资料第一部分:雷电浪涌的危害雷电是一种自然现象,它产生的能量极大,能够造成严重的危害。

雷电对设备和设施的影响主要表现在以下几个方面:1. 烧毁设备:雷电的高能量会导致设备的烧毁,使得设备无法正常工作。

2. 数据丢失:雷电对数据存储设备也会造成损坏,导致重要数据丢失。

3. 安全隐患:雷电的冲击可能会引发火灾等安全隐患。

为了有效减少雷电对设备和设施的危害,需要使用雷电浪涌防护器进行防护。

接下来我们将详细介绍雷电浪涌防护器的功能和使用方法。

第二部分:雷电浪涌防护器的功能雷电浪涌防护器是一种电子设备,主要用于抵御雷电产生的浪涌电压,保护设备和设施不受雷电的影响。

雷电浪涌防护器的功能主要包括以下几个方面:1. 吸收浪涌电压:雷电浪涌防护器能够迅速吸收雷电产生的浪涌电压,避免其传导到设备和设施上。

2. 分流浪涌电流:当雷电产生浪涌电流时,雷电浪涌防护器能够将其分流到地线或其他安全通道上,避免浪涌电流对设备造成损害。

3. 快速响应:雷电浪涌防护器能够在很短的时间内响应雷电产生的浪涌电压和浪涌电流,有效保护设备和设施。

综上所述,雷电浪涌防护器的功能主要是在雷电产生浪涌电压和浪涌电流时,迅速吸收和分流,保护设备和设施不受损害。

第三部分:雷电浪涌防护器的使用方法雷电浪涌防护器的使用方法主要包括以下几个步骤:1. 安装位置选择:雷电浪涌防护器应该安装在设备和设施的电源输入端,以最大限度地降低雷电浪涌对设备和设施的影响。

2. 接地保护:雷电浪涌防护器必须接地使用,确保浪涌电压和浪涌电流能够迅速传导到地线上,避免对设备造成危害。

3. 定期检查:雷电浪涌防护器应该定期进行检查和维护,确保其正常工作。

4. 经常测试:在雷电季节或频繁雷电的环境中,应该经常对雷电浪涌防护器进行测试,确保其能够有效工作。

通过正确的安装和使用方法,雷电浪涌防护器能够有效防护设备和设施不受雷电的影响。

结语雷电浪涌防护器是一种非常重要的设备,它能够有效防护设备和设施不受雷电的危害。

大班pg菲尼克斯说明书

大班pg菲尼克斯说明书

大班pg菲尼克斯说明书宽度70mm高度130mm深度125mm备用端子宽度122mm备用端子高度130mm备用装配视图73mm左侧/右侧安装距离5mm/5mm顶部/底部安装距离50mm/50mm环境条件保护等级IP20阻燃等级(外壳/端子)符合UL94标准V0环境温度(运行)-25°C...70°C(>60°C衰减:2.5%/K) 环境温度(调试类型测试)-40°C环境温度(存放/运输)-40°C...85°C允许的相对湿度(操作)≤95%(25°C时,无冷凝) 气候等级3K3(符合EN60721标准)污染等级2安装高度≤5000m(>2000m,注意降低值)输入数据额定输入电压范围100VAC...240VAC110VDC...250VDC输入电压范围100VAC...240VAC-15% (10)110VDC...250VDC-18% (40)介电强度300VAC60sAC频率范围50Hz...60Hz-10% (10)频率范围(fN)50Hz...60Hz-10% (10)16.7Hz(符合EN50163标准)PE放电电流<3.5mA电耗量6.8A(100VAC)5.5A(120VAC)2.8A(230VAC)2.7A(240VAC)额定功耗520VA冲击电涌电流典型值11A(25°C时)电网缓冲时间典型值28ms(120VAC)典型值29ms(230VAC)输入熔断器12A(慢熔断,内部)使用的输入保护断路器10A...16A(特性B、C、D、K或类似) 功率因数(cosphi)0.98保护瞬态电涌保护保护电路/组件压敏电阻,气体放电管额定输出电压24VDC输出电压(USet)的设置范围24VDC...29.5VDC(恒定容量)额定输出电流(IN)20A StaticBoost(IStat.Boost)25A DynamicBoost(IDyn.Boost)30A(5s)选择性熔断(ISFB)120A(15ms)衰减>60°C...70°C(2.5%/K)并连是,用于冗余和增加容量串连是反馈电压电阻≤35VDC典型响应时间300ms(来自SLEEPMODE) 空转功耗<5W(120VAC)<5W(230VAC)额定负载功率损耗<40W(120VAC)<32W(230VAC)。

电涌保护器 说明书

电涌保护器 说明书

SDX系列电涌保护器使用说明书江苏斯菲尔电气股份有限公司JIANGSU SFERE ELECTRIC CO.,LTD目录1.用途 (1)2.使用条件 (1)3.常用名词定义 (1)4产品命名意义 (2)5主要技术参数 (2)6主要结构特点 (2)7外形尺寸 (3)8安装与使用 (3)9运输和保管 (4)10保修 (4)11订货须知 (4)12附表一 (5)1.用途感谢您选用SDX系列电涌保护器!本产品适用对间接雷电和直接雷电或其他瞬时过电压的电涌进行保护。

这些产品被组装后连接到交流额定电压不超过1000V(有效值)、50/60Hz或直流电压不超过1500V的电路和设备。

其中Ⅰ级产品(符合Ⅰ级分类试验)用于从室外引来的线路上(在LPZ0区与LPZ1区分界处,一般为总配电箱)使系统或设备免遭雷电击中输配电线路或户外避雷器而引起的浪涌电流的损害;Ⅱ级产品(符合Ⅱ级分类试验)用于室内线路(LPZ1区与LPZ2区分界处或以后雷电防护分界处,一般为楼层配电箱、电表箱或终端箱)防止由于间接雷击或开关操作引起的瞬态浪涌电压;Ⅲ级产品(符合Ⅲ级分类试验)适用于线路末端(一般为插座箱)的用电设备进一步保护,使其不受过电压损坏。

2.使用条件2.1正常工作条件2.1.1频率:电源的交流频率在48Hz至62Hz之间。

2.1.2电压:持续施加在SDX系列电涌保护器的接线端子间的电压不应超过其最大持续工作的电压。

2.1.3海拔:海拔不应超过2000m。

2.1.4使用和储存温度:──正常范围:-5℃至+40℃──极限范围:-40℃至+60℃2.1.5相对湿度:在室温下应不大于95%RH。

2.1.6污染等级:保护器适用于污染等级为2的场合。

2.2异常使用条件对置于异常使用条件下的SDX系列电涌保护器,在设计和使用中需作特殊考虑,请在订货时与我公司市场部联系。

3.常用名词定义3.1SDX系列电涌保护器用于限制瞬时过电压和泄放电涌电流的电器,它至少包含一非线性元件。

电涌保护器仪操作规程

电涌保护器仪操作规程

电涌保护器仪操作规程1. 引言电涌保护器仪是一种用于保护电气设备免受电涌损害的仪器。

本文档旨在详细介绍电涌保护器仪的操作规程,以确保安全、正确地使用该仪器。

2. 适用范围本操作规程适用于使用电涌保护器仪进行电涌保护的相关工作人员。

3. 仪器概述电涌保护器仪是一种便携式仪器,用于测量和监测电路中的电涌。

它能够对电流、电压和频率等指标进行测量,并能提供报警功能。

4. 仪器结构电涌保护器仪通常由以下部分组成: - 显示屏:用于显示电涌保护器仪的测量结果和相关信息。

- 按键:用于设置电涌保护器仪的参数和进行操作。

- 连接口:用于连接电涌保护器仪与被测电路。

- 电源:用于为电涌保护器仪提供电力供应。

5. 操作步骤5.1 准备工作在进行操作之前,需要准备好以下工作: 1. 确保电涌保护器仪的电源充足,并将其连接到可靠的电源。

2. 检查电涌保护器仪的显示屏和按键是否正常工作。

3. 确保所需测量接线正确连接,并确保测量线路没有短路或断路。

5.2 设置仪器参数1.打开电涌保护器仪的电源,等待其启动。

2.根据需要,使用仪器的按键设置测量参数,如测量范围、样本率等。

5.3 连接被测电路1.将电涌保护器仪的连接口与被测电路正确连接,确保连接牢固。

2.检查连接线路的安全性,确保没有松动或接触不良。

5.4 进行测量1.确认仪器已正确设置并与被测电路连接。

2.按下仪器的开始测量按键,使其开始测量电涌。

3.观察仪器的显示屏,记录测量结果。

5.5 分析测量结果1.将仪器的测量结果与规定的标准进行比较,以判断电涌保护器是否正常工作。

2.分析测量结果,查找电涌发生的原因,并采取相应的措施进行修复或改进。

5.6 关闭电涌保护器仪1.当测量完成后,按下仪器的停止测量按键,停止测量过程。

2.关闭电涌保护器仪的电源。

6. 安全注意事项在操作电涌保护器仪时,需要注意以下事项以确保安全: 1. 只有经过培训和授权的人员才能操作电涌保护器仪。

菲尼克斯二合一 三合一电涌保护器产品说明书

菲尼克斯二合一 三合一电涌保护器产品说明书

公 司 通 知
Notice / Information
市场部 2010 第(021 )号
Subject : 二合一、三合一电涌保护器正式供货
为了完善产品系列,更好的贴近中国市场,TRABTECH 监控系统用二合一、三合一电涌保护器从2010年6月30日开始正式供货。

1、 产品描述
▪ 交/直流供电监控摄像机电涌保护器
▪ 三个最大持续工作电压等级供选择:24V 、220V 、
320V ▪ 多功能一体化电涌保护器,可同时保护摄像机的电
源、视频、和控制回路 ▪ 有二合一、三合一两种系列产品供选择 ▪ 带状态指示灯 2、 产品的命名原则
3、 安装方式
4、 产品技术参数
BXT - CVP - 24VAC BXT - VP - 24VAC
三合一监控系统防雷器
BOXTRAB 系列 电涌保护器
V-Video 表示视频线路保护 P-power 表示电源线路保护
二合一监控系统防雷器
5、 产品尺寸图
如需获得该产品的更多信息请与防雷项目部Ms.胡倩(8367)或Ms.景婷(8307)联系
市场部 2010-07-08。

菲尼克斯SEC系列电涌保护产品手册

菲尼克斯SEC系列电涌保护产品手册

栿╓ヽ䝚∾㚆䘋㹢₳㍺✾ⱟ∾凓报㑽⌌㍖㠅Safe Energy Control Technology2PHOENIX CONTACT哈ⴒ∡㚅䘋㳪ÿÿ 核ⓧ∾Ử䘢ⱸ㌍╢ⓞ′` ἐⱸ㌍㒦ⁱἀヽ⏬㟣⍷䝚∾䓙ヽῗỰ咇ⳑ⇠㙄䗊㲩柳⻍扢婛ᾖắ㣍じ䭳἞⌰┡Ẩắ㌕㟄䜙㑥⏜喝䢩⑦慽晽Ả㙂⾕⑦⊏⊰㙅䜙Ἴ╖┡䎁䌎䜙婸≈㙎㣝喏ὺ㽶幈ⰷ㋌㙺䝟⤳昔䜙枕㳗Ƞ∁⒍㋕㍺㞞䜙ᾬ⦯Ẩ⊾Ⳇ㛄㊦ᾁ䭳἞⌰䜙㞕⨒屖㚣Ƞ咇ⳑ⇠㙄䗊㲩㛄䗊㲩恳㐺ȟ䗊⯥㐺⑸ὺ⑟剿⌽⎫椛⡴䜙ẫ䗡⺗⟏椛ⲑ傚Ƞ∁⒍㛄⊰䭠ἣ1923⼉䜙ⱋ㙤⾤ᾖắ喏䞃⋢➽⇽䒘㍺㞞14,000⒢⓭⹺Ƞ咇ⳑ⇠㙄䗊㲩➽⇽䒘⾏䭠ἛⰡ☙䜙斕◃俦佱ȟ㍺㞞帚恜50ⱋ斕◃∁⒍⑟30⦯ế斕◃ὸ䒛喏㙎⁔ả㊦ᾁ䜙ⰷ㋌恰壡⑟㚋ȟⳆ恦⟅㴴悯Ƞ咇ⳑ⇠㙄䗊㲩㑥‰歭╖嶽䜙Ἴ╖┡㞢⌶喏⼔㵰⼩䖽ἣ⒙ế椛⡴ȠἼ╖厘➉⎚㎁⼩䖽ἣ屓⦜⋋悵◛⑟㟏㥅⋋悵䜙恳㐺㌕㟄喏⼩䖽ἣ䑅ὸ⎫㐼⋋㡱䜙恳㐺⛽ᾋȠ⒡㚋Ⲏἣ⒙䩢⼩䖽椛⡴喏咇ⳑ⇠㙄㑥‰䞍⼩䜙Ἴ╖婸≈㙎㣝喏恮ἰ椛⡴⎚㎁喝剿⌽⎫壡ắȟ楣⌰⑦䗊ȟ⇞ᾤȟ恜䪠壡ắ喏ὺ⑟㳉⦙䒛ȟ‰懢䗊ȟἹ悯⢏䣕屓㙒䯞Ƞ4 / 56 / 78 / 910 / 11FLASHTRAB-SEC-HYBRID12 / 13FLASHTRAB-SEC-PLUS-440 14 / 15FLASHTRAB-SEC-PLUS-350 16 / 17FLASHTRAB-SEC-T1+T218 / 19VALVETRAB-SEC 20 / 21PLUGTRAB-SEC22 / 2324 / 2526 / 27PHOENIX CONTACT 3ἐ戣䘋䷑侵㒦ⁱⱟ∾䝚柍䘋╢䘋㹢₳㍺枌䗊⑟䗊㸡⟜ᾯ㏴⟤屓⦜,㞕ㄋ⌸䜙ㅚ≊䖯劈ᾯ㏴⟤㘉ế䶐佴。

䶐佴䜙⃱㟏ả₃⦢恰ẕ㯺⤳⌵Ἓ㊥㟁枕㳗。

咇ⳑ⇠㙄䗊㲩ỏㄽ⺻㟺⒄柵䜙Ἴ╖婸≈㙎㣝:⇽㙅䶐⊬䗊㸡⁲㌹⛽。

䟄〫哈ⴒ∡㚅䘋㳪䘋㹢₳㍺✾ⱟ∾凓报㑽⌌㍖㠅ⱟ∾
止SEC ώ▗ⓅΆ⽕㶱⽪䗾ὤ῭⧰楜⢵Ɫ♚䝚㙊
ώ▗㚏㤞ώ▗惟⡡4PHOENIX CONTACT㍖㠅楜∞䝚䘋㹢₳㍺ώ▗㠻勀哈ⴒ∡㚅䘋㳪㸡岫䒅単䶔䞠㴘䶔ὣἼ╖⾕⑦䜙⊲㞴曋㱊喏咇ⳑ⇠㙄䗊㲩䜙ⰳ次ⰹⳆ㌔㍚Ἓ㋕㞞Ἴ╖䜙㷠屪⹺῱Ƞⰳ次ⰹὺDIN EN ISO/IEC 17025尹屖ỏ⢏䣕喏⳪䧏Ἓ∋➽Ẩắ㌕㟄椛⡴䜙Ẩắゼȟ䎁䭠ゼ喏⑟ⰷ婗ゼȠỏ㽶幈⺗⟏枕㳗喏咇ⳑ⇠㙄䗊㲩ỏẢ㙂⑦⳪䜙㙅㌕㟄㌪⇺Ἓ⦼扤巙扦Ƞ恮ἰ巙扦Ố娖䖽ἣả㌕㟄曷㢶䜙ⱛ⊜⒝῱ỂȠ∋Ểẕếᾭ䩕㣝†Ⳇ㛄⺻㞞Ⱎ⇽冒扤㐼⋋㌕㟄䜙⇽㙅㗓䗊暉朮ȠẨắ䜙⾕⑦ὺ⑟屓尶喏⒡㚋悯恜Ẻ㣑䜙㢜≛㷠屪喏㟺剿ἣ咇ⳑ⇠㙄䗊㲩䜙䗊㸡⁲㌹⛽喏ỏ懢䗊䶐佴㑥‰Ⱑ☙䜙䗊㸡曇㌹ȠứỰ岔屷⋱㚆㍖㠅PHOENIX CONTACT5殮ヽ凓㸡岫媚叙⏬㸡岫屺岗㸡岫6PHOENIX CONTACTⱟ∾凓报㑽⌌㍖㠅喝㚶促㸗ȟ㚶柖ⓤ⧝₳㍺䝚䘋㹢₳㍺✾㚶柖ⓤ⧝₳㍺䉪㚃✾⨗㠱Ố❳庄䈩㙂⛽Ⲥἣ315A 喏SEC 䶐⊬䗊㸡⁲㌹⛽㙵枕∢懢倃⒣⦜⁲㌹䈩㙂⛽Ƞ⨗㠱Ố❳庄䈩㙂⛽椲Ⱟ䗊㷖怘歭喏ㄽỴ⒄ὺ悞㍾FLT -SEC-HYBRID Ἴ╖喏屺Ἴ╖√慽杛㊥Ἓ㗓䗊暉朮┡⒣⦜⁲㌹䈩㙂⛽ȠⰞ⇽冒扤㐼⋋㌕㟄喋Safe Energy Control 喌,䰕䪅SEC 喏⒄ὺ῱ỏ枌䗊⁲㌹┡䗊㸡⁲㌹椛⡴ゼ冒䫈Ⱟȟ⌴冒⿏⦼䜙ὸ⒢屢Ƞ⊰㙅䜙㗓䗊暉朮㌕㟄冒⦴愔⇢ᾐῪ⿷⾤䜙侂㷖Ƞ恮➽㞕⦼䪠⼻ẟ曢ΰἛ㘉ế䶐佴䜙␠⌰喏⒡㚋Ỵ屖㚣Ἓ䗊㸡⁲㌹⛽䜙䫈ⰯゼȠ䗊㸡⁲㌹⛽ỏㄽ䶐佴䜙㯸⻍恥壡⁲欓㌹势Ƞ➽Ả⒡⼩䖽⟏⒝喏⟜⒄㑥‰㙵枕⒣⦜⁲㌹䈩㙂⛽䜙Ἴ╖㙎㣝ȠPHOENIX CONTACT7促㸗䝚Ɒ἟侂㷖㛄䗊㷖䜙ẕ慽⊛Ƞ⿨㗓䗊暉朮ⲛ‰䗊俦佱Ể䜙䗊㸡䗊㷖㵙㗓⒣喏㷖佤㗓䗊暉朮䜙䗊㷖⒄䪅ỏ侂㷖Ƞ恮䩢侂㷖ᾯ㎖侂ms似喏恦ῑἣ䢂庄䗊㷖Ƞ侂㷖ᾯⲎ㘉ế䶐佴悵㊥␠⌰Ƞ侂㷖ᾯ⾪希䗊␠⑭⎫喏䖯劈䶐佴㗚朱Ƞ㯹⦫喏➽㡥ἰㅚ≊Ạ喏⋢似䜙恜怒⁲㌹屓⦜⒄冒ᾯ奀婻⑦ȠSEC䶐⊬䜙I䴐䗊㸡⁲㌹⛽㛄樫㯓㙵侂㷖䜙㗓䗊暉朮Ἴ╖Ƞ恮➽䞴㯸ㆤỞẟῨ䑅Ἓ歭ゼ冒⟅⁲㌹䶐佴屓⦜䜙䒛りȠ㙵侂㷖䜙㗓䗊暉朮杛㊥⾤䜙⒣⦜⁲㌹䈩㙂⛽8PHOENIX CONTACTⱟ∾
止喝SEC ䷑⋭ώ▗∾䓙屺岗∌㞞Ⱎ⇽冒扤㐼⋋㌕㟄䜙䗊㸡⁲㌹⛽⺇佤悯恜⦯䩢㟏㠙尹屖喏⎚㎁喝KEMA,UL ┡GL Ƞ㞉⦯尹屖⁶㄄岌⑗婖27椊SEC 䶐⊬Ἴ╖冒⦴Ⱑ☙曇㌹枌䗊䗊㷖⑟䗊㸡䗊␠Ƞ⇽㙅䜙㗓䗊暉朮喏佨⒝II 䴐⑟III 䴐䗊㸡⁲㌹⛽喏ỏ懢䗊䶐佴㑥‰Ⱑ☙䜙䗊㸡⁲㌹㙎㣝Ƞ佴ẕ䜙䶼≦⠠佨㠙喏Ⱑ☙䜙⒄㑧㍩屓尶喏⁔ἣ䑅⟏Ⱎ奚ȠSEC 䶐⊬Ἴ╖ỏㄽ䜙䶐佴㑥‰⇽柷䜙䗊㸡⁲㌹Ƞ愻₷㍻尼媼䆏⧽核䫅㣝岆‣ₕὤ㒨㎪PHOENIX CONTACT9I+II 䴐䗊㸡⁲㌹⛽II 䴐䗊㸡⁲㌹⛽III 䴐屓⦜⁲㌹⛽I 䴐枌䗊㷖⁲㌹⛽I 䴐枌䗊㷖⁲㌹⛽√慽杛㊥⒣⦜⁲㌹䈩㙂⛽180⽼㚡恂ⱟ妛㻛㝆䝚㠐㦆䎌プ㏝䨐㌖㟟㒨⨊⠝⻼㟟月旯㒨㎪俬䣗䒅10PHOENIX CONTACTSEC ䷑⋭ώ▗喝惘䗾ὤợⓢ䝚戣䘋䷑侵戣䘋傥䖽⒄柵䜙䗊㸡⁲㌹⛽冒⦴䤃⁲⹺ắȟ◛ắὺ⑟㲦䖽ῤⰚ䫈Ⱟ䜙䗊⌰‰⼩Ƞ⿐䰧◛ắ┡ῤⰚ㨑Ⱌ悯䖽䜙䗊㸡Ἴ╖婸≈㙎㣝Ƞ惰₷ỏ㋕㞞悯⁶俦佱㑥‰㙵⼇㌅䜙䗊㸡⁲㌹⛽喏⒡㚋䗊㸡⁲㌹屓⦜⟜悯恜䞍∈尹屖Ƞ㠐㦆⌌惶⼩䖽ἣ㐼⋋㡱䜙䗊㸡⁲㌹⛽喏Ἴ╖佨㠙䶼≦喏北䞖䬏暉喏Ả〆╢䶐佴㯸⻍恥壡Ƞ榤䘋␈—➽楣⟏䜙ㄋ⌸㟶ᾋẠ喏䗊㸡⁲㌹⛽Ỵ冒㑥‰⿏⦼䜙⁲㌹⌴冒Ƞ⣐䤖岔㚓歭ゼ冒䜙䗊㸡⁲㌹⛽ỏẢ暉㙂䗊⌰‰⼩ȟ恥怨ȟἹ悯㑥‰⁲㌹Ƞ㱤ế壡ắ憒⺡㞰䶐佴䫈Ⱟ⒄柵喏冒⦴昔Ớ恥壡Ƞ咇ⳑ⇠㙄䗊㲩㑥‰㌕㟄椛⇝䜙䗊㸡⁲㌹⛽Ἴ╖喏攝ⲎẢ⒡⼩䖽⟏⒝⟜冒㑥‰Ẩắ⎫䜙Ἴ╖婸≈㙎㣝ȠFLASHTRAB-SEC-HYBRID:㘔䘋曊杯+䉪㚃✾侚ⓞ⿥Ⓟ㒨㎪ώ▗ώ▗䍏䆏• ΰ䗊␠⁲㌹㳉⼈• 㙵枕⦫慽⒣⦜⁲㌹䈩㙂⛽• 北䞖㡱Ῠ䬏暉• 䤃⁲䗊㲩䶐佴䜙—䖽Ⲕ┒• 㞕⦼䪠⼻㑥歭䶐佴䜙⒄柵ゼ• 䑅⟏㞉㏷䰕⁔• ⒄悯恜CHECKMASTER 2恰壡㥕㷠FLASHTRAB-SEC-HYBRID 㛄樫㯓杛㊥⾤䜙I䴐䗊㸡⁲㌹⛽喏屺㪶⟬ⲛ㙵侂㷖ȟ歭ゼ冒䜙㗓䗊暉朮ả⒣⦜⁲㌹䈩㙂⛽杛㊥➽⒡ẕế㑧⧉ỂȠ杛㊥⾤䈩㙂⛽䜙佨㠙屓尶喏—䗊㸡⁲㌹⛽䜙Ⱎ奚㞉⌵㙎⁔ȟ䄊㷐ȠỴ恰ẕ㯺北䞖Ἓ㡱Ῠ䬏暉ὺ⑟㐺佔⹺῱ȠFLASHTRAB-SEC-HYBRID悗䖽ἣ230/400V䜙懢䗊䶐佴Ƞ⒄㑧㍩䜙佨㠙屓尶⁔ἣ䗊㸡⁲㌹⛽➽䑅⟏䜙㥕㷠⑟㞉㏷Ƞ㺚㜅䜙㟏㥅䬬⑸㎜䧏䝦㐼䈩㙂⛽┡㗓䗊暉朮㙵侂㷖䜙㗓䗊暉朮FLASHTRAB-SEC-HYBRID䒆⠐⽪䗾⟔․②戣䘋T135.6 mm恱䪠惺⁶㌺寻婻䅎杛㊥⾤⒣⦜⁲㌹䈩㙂⛽㐽㍞⾤⿎䲼斖㋸䤃⁲㑧⧉䫈➏喏⒡㚋⁔ἣ㑧㍩FLASHTRAB-SEC-PLUS-440:惘䗾ὤ400/690V戣䘋䷑侵ώ▗䍏䆏• ΰ䗊␠⁲㌹㳉⼈• Ⲥἣ400 A䜙ㅚ≊Ạ喏⒄㙵枕⦫慽⒣⦜⁲㌹䈩㙂⛽• 䤃⁲䗊㲩䶐佴䜙—䖽Ⲕ┒• 冒⦴㽶幈IT䶐佴䜙TOV枕㳗• 悯恜≇⊐┡㏄⌽㷠屪• 㞕⦼䪠⼻㑥歭䶐佴䜙⒄柵ゼ• 北䞖㡱Ῠ䬏暉• 䑅⟏㞉㏷䰕⁔• ⒄悯恜CHECKMASTER 2恰壡㥕㷠FLASHTRAB-SEC-PLUS-440 悗䖽ἣ怘歭䗊␠䜙⟏⒝Ƞ䶼≦䜙⦫⿷佨㠙ὺ⑟Ⱑ☙䜙⒄㑧㍩屓尶喏㞞⊾ἣ北䞖㡱Ῠ䬏暉ὺ⑟䄊㷐Ⱎ奚ȠFLASHTRAB-SEC-PLUS-440 ㌕㟄ゼ冒ᾭ帟喏悗䖽ἣ400/690V TN ┡400V IT懢䗊䶐佴ỂȠFLASHTRAB-SEC-PLUS-440䜙㞕⦼㎖侂⹺῱䗊␠ỏ440V喏ⲹ∋悗⒝⼩䖽➽⹺ắὺ⑟楣䗊䶐佴Ể喏⒡㚋冒⦴㌔⑬⿏䅝䜙≇⊐┡㏄⌽Ƞ㙵侂㷖䜙㗓䗊暉朮FLASHTRAB-SEC-PLUS-440䒆⠐⽪䗾⟔․②戣䘋T1106.8 mm㋕㞞⁲㌹㑧⧉⟜⺻㞞㺚㜅䜙䍋ゖ㎜䧏㘉Ῠ⼪⼼喏㙵枕㣺㐺ᾋ恱䪠惺⁶㌺寻婻䅎㗄㎖䆂㑧㍩佨㠙䶼≦ȟゼ冒⿏⦼FLASHTRAB-SEC-PLUS-350:惘䗾ὤ230/400V戣䘋䷑侵侩㡚䷽⊧ȟ⍵凓【⧽ώ▗䍏䆏• 悗䖽ἣ㋕㞞懢䗊䶐佴• ΰ䗊␠⁲㌹㳉⼈• F1Ⲥἣ315A䜙ㅚ≊Ạ喏⒄㙵枕⦫慽⒣⦜⁲㌹䈩㙂⛽• 㙵侂㷖㗓䗊暉朮• 䤃⁲䗊㲩䶐佴䜙—䖽Ⲕ┒• 㞕⦼䪠⼻㑥歭䶐佴䜙⒄柵ゼ• 䑅⟏㞉㏷䰕⁔• ⒄悯恜CHECKMASTER 2恰壡㥕㷠FLASHTRAB-SEC-PLUS-350㛄懢䗊䶐佴ὺ⑟⹺ắ⼩䖽䒛ㆈ䜙䗊㸡⁲㌹Ἴ╖ȠFLASHTRAB-SEC-PLUS-350䶐⊬Ἴ╖⌴冒⿏⦼喏ỏ䗊㲩䶐佴㑥‰㎖Ớ䜙䗊㸡⁲㌹喏⦼⻚⼻㑥歭Ἓ䶐佴䜙—䖽Ⲕ┒ȠFLASHTRAB-SEC-PLUS-350Ἴ╖冒⦴怐㠓⼩Ⲏ䗊␠㵷⌽ὺ⑟⿏⦼䜙枌䗊㷖Ƞ㙵侂㷖䜙㗓䗊暉朮FLASHTRAB-SEC-PLUS䒆⠐⽪䗾⟔․②戣䘋142.4 mmT1㋕㞞⁲㌹㑧⧉⟜⺻㞞㺚㜅䜙䍋ゖ㎜䧏恱䪠惺⁶㌺寻婻䅎㗄㎖䆂㑧㍩FLASHTRAB-SEC-T1+T2:䟵㰹䝚I+II䵑侚ⓞ⿥䘋㹢₳㍺✾ώ▗䍏䆏• Ⱎ奚䰕⁔• ΰ䗊␠⁲㌹㳉⼈• F1Ⲥἣ315A䜙ㅚ≊Ạ喏⒄㙵枕⦫慽⒣⦜⁲㌹䈩㙂⛽• 冒⦴⼩Ⲏ怘ΰ䜙䗊㸡䗊␠• 䤃⁲䗊㲩䶐佴䜙—䖽Ⲕ┒• 㞕⦼䪠⼻㑥歭䶐佴䜙⒄柵ゼ• 北䞖㡱Ῠ䬏暉• 䑅⟏㞉㏷䰕⁔• ⒄悯恜CHECKMASTER 2恰壡㥕㷠FLASHTRAB-SEC-T1+T2㛄枌䗊㷖⁲㌹⛽┡䗊㸡⁲㌹⛽䜙余⒝⾤Ἴ╖Ƞ屺䶐⊬Ἴ╖ⲹ∋悗䖽ἣ⾕∈⌽῱椦他䜙⹺㐼⟏⒝Ƞ⿏⦼䜙㗓䗊暉朮冒⦴⒄柵⟅㵙㗓枌䗊㷖喏傡II䴐␠㗤䗊曐㪶⟬⒄ὺ㞞㗝效⋋䗊␠喏⁲屖Ἓ㘉ế䗊㸡⁲㌹⛽䜙ΰ㰠␠Ƞ恮㯓Ἴ╖㛄㗓䗊暉朮ả␠㗤䗊曐䜙㞕 余⒝Ƞ余⒝⾤䜙䗊㸡⁲㌹⛽㛓哬曢ΰⰞ奚ả侉㌹㊥㟁Ƞ⒡㚋恮㯓䗊㸡⁲㌹⛽Ể䜙⇘⛽ᾋỏ㙵侂㷖㗓䗊暉朮┡⊰㙅屓尶䜙II䴐␠㗤䗊曐Ƞ㙵侂㷖䜙㗓䗊暉朮FLASHTRAB-SEC-T1+T2䒆⠐⽪䗾⟔․②戣䘋T1T2+142.4 mm㋕㞞⁲㌹㑧⧉⟜⺻㞞㺚㜅䜙䍋ゖ㎜䧏恱䪠惺⁶㌺寻婻䅎㗄㎖䆂㑧㍩VAL VETRAB-SEC:∾䓙㟖⳥Ⓟ㒨㎪䘋㹢₳㍺㫷⠭ώ▗䍏䆏• ΰ䗊␠⁲㌹㳉⼈• ⿏⦼䜙䆂准㋸奚倃• F1Ⲥἣ315A㚋喏㙵枕⒣⦜⁲㌹䈩㙂⛽• 歭恓50kA䜙䢂庄䗊㷖傥⑬冒⌰• 北䞖㡱Ῠ䬏暉• 䑅⟏㞉㏷䰕⁔• ⒄悯恜CHECKMASTER 2恰壡㥕㷠• ⒡㚋㑥‰175V䗊␠䯞似Ἴ╖὚὚12mmⱒ⼻䜙䶼≦⠠䗊㸡⁲㌹⛽喏冒⦴ỏ䶐佴㑥‰⿏㞞⌰䜙䗊㸡⁲㌹Ƞ❵㯹喏␈—㛄ぃ⠠懢䗊㡱喏VALVETRAB SEC䶐⊬Ἴ╖Ỵ⒄ὺ怐㠓Ⱎ奚Ƞ⒡㚋喏⿨Ố❳庄䈩㙂⛽Ⲥἣ315A㚋喏䗊㸡⁲㌹⛽㙵枕⌵奚⒣⦜⁲㌹䈩㙂⛽ȠVALVETRAB SEC䶐⊬Ἴ╖㍺㞞歭悯㷖冒⌰ȟ䶼≦䵓⹼䜙䌎䅎喏悗䖽ἣ⒙䩢懢䗊䶐佴ỂȠ㗄㎖䆂㑧㍩㋕㞞⁲㌹㑧⧉⟜⺻㞞㺚㜅䜙䍋ゖ㎜䧏V AL VETRAB-SEC䒆⠐⽪䗾⟔⋜戣䘋㢲T249.2 mmPHOENIX CONTACT21恱䪠惺⁶㌺寻婻䅎歭䢂庄䗊㷖傥⑬冒⌰22PHOENIX CONTACTPLUGTRAB-SEC:惘䗾ὤAC ὺ㸗ỤDC 䟊㸗䷑侵䝚岔⧝₳㍺✾ώ▗䍏䆏• 恜怒╢⼩冒⌰恰ẕ㯺㑥歭• 䑅⟏㞉㏷䰕⁔• Ἱ䞉㷖悯䖽• 悗䖽ἣ⹺椦䗊㷖26A ὺẠ䜙⟏⒝• 㙵枕⒣⦜⁲㌹䈩㙂⛽• ⒄柵䜙惺⁶㌺寻⌴冒• ⒄悯恜CHECKMASTER 2恰壡㥕㷠PLUGTRAB-SEC 㛄⼩䖽ἣ佝䮄屓⦜⁲㌹䜙III 䴐䗊㸡⁲㌹⛽Ƞ⇽㙅屓尶ȟ√倃准㋸奚倃䜙䗊㸡⁲㌹⛽㙵枕⋢倃䈩㙂⛽喏➽恜怒ㅚ≊Ạ冒⦴Ⱎ⇽ȟ㞞㗝㙂⾕ȠPLUGTRAB-SEC 䶐⊬Ἴ╖⒄ὺỏἹ䞉㷖䶐佴䜙佝䮄屓⦜㑥‰⒄柵䜙䗊㸡⁲㌹Ƞ䘋㽦₳㍺⋜戣䘋㢲T317.7 mm35 mmPHOENIX CONTACT23恱䪠惺⁶㌺寻婻䅎曇岄㑧㍩侫䢖䑄⿏⦼䜙√慽准㋸奚倃Plugtrab SEC-3S悗䖽ἣ230/400ẞ䞍懢䗊䶐佴24PHOENIX CONTACT哈ⴒ∡㚅䘋㳪ἐㅾ㒦ⁱ∾核、Ɫ♚䝚䘋㹢₳㍺✾ώ▗㋧ῂ奍゙⻢㟱SEC ䷑⋭ώ▗凓⧵ἐㅾ㒦ⁱ5⽊ΆỠ䝚䘋㹢₳㍺SEC 䶐⊬Ἴ╖Ả㚨⌸⎫,ㄽ劈ⲦἩ⼉√㙵枕㍚じ㪶⟬㏴⟤、㞉㏷䜙暃椭。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

VAL-MS230 ST 和F-MS 12 ST 德国菲尼克斯浪涌保护器防雷器防雷器的工作原理:防雷器内部结构其实就是巨功率电压敏感器件,当雷击进入电源进户线路时:防雷器将过高的电压吸收和泄放到大地上,所以地线是很重要的,没有地线就没有防雷效果,只能吸收浪涌效果,当遇到过于强大的雷击时需要空气开关或熔断器(保险丝)来保护,所以空气开关和熔断器的电流要选择合适,不然烧了防雷器还与电网未断开,在空气开关后面再接熔断器是为了更保险,因为空气开关是机械动作的,不会100%可靠。

防雷器的使用必须与空气开关和熔断器配合,理论上讲:空气开关或保险丝电流越小越好,防雷器的并联只数越多效果越好,对雷电的吸收功率越大,但如果选用过大电流的空气开关是不利的,当防雷器达到极限功率时间后,如果空气开关或保险丝未断开是不行的。

使用漏电开关要接在防雷线路之后,漏电开关里面有电子线路,接在防雷线路后面可以保护漏电开关被雷击损坏。

本防雷器属于快速更换结构,当过强雷击被击穿后可以快速更换防雷器芯,不用任何工具,只从防雷器座上拔下和插上,购买时也以多买几个防雷器芯备用,防雷器芯购买请看:德国菲尼克斯 PHOENIX CONTACT VAL-MS230 防雷器芯下图是:简单的浪涌保护接线图,本图不能实现防雷保护,只有浪涌保护,空气开关和溶断器大于32A时用两只防雷器并联。

下图是:简单型的防雷和浪涌保护(成本低,效果一般)。

下图是:32A典型防雷浪涌保护接线图(效果最好)。

下图是:63A以下大电流防雷浪涌保护接线图(对线路电流大的也有很好效果)。

下图是: 三相五线防雷浪涌保护接线图,电流大的要用多只并联。

VALVETRAB -MS是一个单通道、导轨安装式的Ⅱ类(C级)电涌保护器。

为了对多路导线进行电涌保护,可以将多个VALVETRAB并联在一起安装,并在接地侧桥接。

VAL MS...VF产品在保护插头中特殊设计了压敏电阻和气体放电管,可以有效限制漏电流。

VALVETRAB产品由保护插头和基座两部分组成,这种构造的优点是,在进行绝缘检测的整个过程中,可以拔出保护插头或者在超负荷情况下无需中断供电便可调换保护插头。

保护插头的基座的编码在首次插入保护插头时即行完成。

这样就排除了将不合适的保护插头插入已编码的基座中的可能。

VAL-MS产品特性:—可插拔—热脱离装置—机械式状态显示—遥信接点(浮地干接点)—VALVETRAB产品在两侧都有双接线端子。

这样,每个接头可以同时可靠地夹紧一根导线和桥接件的一个分叉触头。

桥接件MPB18系列产品可以为单相或多相供电系统中的电涌保护器这间的布线提供方便,在电涌保护器接有小型断路器和漏电保护器时也不例外。

F-MS12和F-MS40安装在N和PE线之间,与应用在L和N线之间的VAL-MS...电涌保护器组合使用。

F-MS40适用于工业环境。

1、VAL -MS 60(插拔式C级电源浪涌保护器)技术参数:额定工作电压UN:60V最大持续工作电压UC :DC/AC 100V /75V额定放电电流In(8/20)µs:15kA最大放电电流Imax(8/20)µs:40kAIn时的保护电平:≤500V5kA时的残压:300V无前置熔断器时的截断后续短路电流:-前置熔断器:125A gL响应时间tA:≤25ns漏电流:≤0.3mA2、VAL -MS 120(插拔式C级电源浪涌保护器)技术参数:额定工作电压UN:120V最大持续工作电压UC :DC/AC 200V/150V额定放电电流In(8/20)µs:20kA最大放电电流Imax(8/20)µs:40kAIn时的保护电平:≤800V5kA时的残压:550V无前置熔断器时的截断后续短路电流:-前置熔断器:125A gL响应时间tA:≤25ns漏电流:≤0.3mA3、VAL -MS 230(插拔式C级电源浪涌保护器)技术参数:额定工作电压UN:230V最大持续工作电压UC :DC/AC 350V /275V额定放电电流In(8/20)µs:20kA最大放电电流Imax(8/20)µs:40kAIn时的保护电平:≤1.35kV5kA时的残压:1kV无前置熔断器时的截断后续短路电流:-前置熔断器:125A gL响应时间tA:≤25ns漏电流:≤0.3mA4、VAL -MS 230IT(插拔式C级电源浪涌保护器)技术参数:额定工作电压UN:230V最大持续工作电压UC :DC/AC 500V /385V额定放电电流In(8/20)µs:20kA最大放电电流Imax(8/20)µs:40kAIn时的保护电平:≤1.8kV5kA时的残压:1.35kV无前置熔断器时的截断后续短路电流:-前置熔断器:125A gL响应时间tA:≤25ns漏电流:≤0.3mA5、VAL -MS 320(插拔式C级电源浪涌保护器)技术参数:额定工作电压UN:320V最大持续工作电压UC :DC/AC 420V /335V额定放电电流In(8/20)µs:20kA最大放电电流Imax(8/20)µs:40kAIn时的保护电平:≤1.5kV5kA时的残压:≤1.2kV无前置熔断器时的截断后续短路电流:-前置熔断器:125A gL响应时间tA:≤25ns漏电流:≤0.3mA6、VAL -MS 400(插拔式C级电源浪涌保护器)技术参数:额定工作电压UN:400V最大持续工作电压UC :DC/AC 585V /440V额定放电电流In(8/20)µs:20kA最大放电电流Imax(8/20)µs:40kAIn时的保护电平:≤2.2kV5kA时的残压:≤1.5kV无前置熔断器时的截断后续短路电流:-前置熔断器:125A gL响应时间tA:≤25ns漏电流:≤0.3mA7、VAL -MS 500(插拔式C级电源浪涌保护器)技术参数:额定工作电压UN:500V最大持续工作电压UC :DC/AC 600V /600V额定放电电流In(8/20)µs:15kA最大放电电流Imax(8/20)µs:30kAIn时的保护电平:≤2.8kV5kA时的残压:≤2.3kV无前置熔断器时的截断后续短路电流:-前置熔断器:125A gL响应时间tA:≤25ns漏电流:≤0.3mA8、F-MS 12(插拔式N-PE电源浪涌保护器)技术参数:额定工作电压UN:230V (N-PE)最大持续工作电压UC :DC/AC - /260V额定放电电流In(8/20)µs:20kA最大放电电流Imax(8/20)µs:40kAIn时的保护电平:≤1kV5kA时的残压:≤150V无前置熔断器时的截断后续短路电流:25kA前置熔断器:125A gL响应时间tA:≤100ns漏电流:≤1µA9、F-MS 40(插拔式N-PE电源浪涌保护器)技术参数:额定工作电压UN:230V (N-PE)最大持续工作电压UC :DC/AC - /260V额定放电电流In(8/20)µs:20kA最大放电电流Imax(8/20)µs:40kAIn时的保护电平:≤1.5kV5kA时的残压:≤1kV无前置熔断器时的截断后续短路电流:-前置熔断器:-响应时间tA:≤100ns漏电流:-10、VAL -MS 230VF/FM(插拔式C级电源浪涌保护器)技术参数:额定工作电压UN:230V最大持续工作电压UC :DC/AC 260V AC/-额定放电电流In(8/20)µs:10kA最大放电电流Imax(8/20)µs:20kAIn时的保护电平:≤1kV5kA时的残压:≤550V无前置熔断器时的截断后续短路电流:25kA前置熔断器:63A gL响应时间tA:≤100ns漏电流:≤1µA11、VAL -MS 350VF/FM(插拔式C级电源浪涌保护器)技术参数:额定工作电压UN:230V最大持续工作电压UC :DC/AC 350V AC/-额定放电电流In(8/20)µs:10kA最大放电电流Imax(8/20)µs:20kAIn时的保护电平:≤1.2kV5kA时的残压:≤1kV无前置熔断器时的截断后续短路电流:25kA前置熔断器:125A gL响应时间tA:≤100ns漏电流:≤1µA12、VAL -MS 230/3+1 FM(三相五线C级电源浪涌保护器)技术参数:标称工作电压UN:230V最大持续工作电压UC :L-N/N-PE/L-NPE 275VAC/260VAC/-额定放电电流In(8/20)µs:L-N/N-PE/L-NPE 20kA/20kA/-最大放电电流Imax(8/20)µs:L-N/N-PE/L-NPE 40kA/40kA/-5kA时的残压:L-N/N-PE/L-NPE ≤1.1kV/≤0.15kV/-电压保护水平Up:L-N/N-PE/L-NPE ≤1.4kV/≤1kV/-响应时间tA:L-N/N-PE/L-NPE ≤25ns/≤100ns/-13、VAL -MS 320/3+1 FM(三相五线C级电源浪涌保护器)技术参数:标称工作电压UN:320V最大持续工作电压UC :L-N/N-PE/L-NPE 335VAC/260VAC/-额定放电电流In(8/20)µs:L-N/N-PE/L-NPE 20kA/20kA/-最大放电电流Imax(8/20)µs:L-N/N-PE/L-NPE 40kA/40kA/-5kA时的残压:L-N/N-PE/L-NPE ≤1.25kV/≤0.15kV/-电压保护水平Up:L-N/N-PE/L-NPE ≤1.6kV/≤1kV/-响应时间tA:L-N/N-PE/L-NPE ≤25ns/≤100ns/-14、VAL -MS 230/3 FM(三相四线C级电源浪涌保护器)技术参数:标称工作电压UN:230V最大持续工作电压UC :L-N/N-PE/L-NPE -/-/275V AC额定放电电流In(8/20)µs:L-N/N-PE/L-NPE -/-/60kA(全通道)最大放电电流Imax(8/20)µs:L-N/N-PE/L-NPE -/-/120kA(全通道)5kA时的残压:L-N/N-PE/L-NPE -/-/1kV电压保护水平Up:L-N/N-PE/L-NPE -/-/1.35kV响应时间tA:L-N/N-PE/L-NPE - /-/25ns15、VAL -MS 320/3 FM(三相四线C级电源浪涌保护器)技术参数:标称工作电压UN:320V最大持续工作电压UC :L-N/N-PE/L-NPE -/-/335V AC额定放电电流In(8/20)µs:L-N/N-PE/L-NPE -/-/60kA(全通道)最大放电电流Imax(8/20)µs:L-N/N-PE/L-NPE -/-/120kA(全通道)5kA时的残压:L-N/N-PE/L-NPE -/-/1.2kV电压保护水平Up:L-N/N-PE/L-NPE -/-/1.5kV响应时间tA:L-N/N-PE/L-NPE - /-/25ns16、VAL -MS 120/3+1 FM-UD(三相五线C级电源浪涌保护器)技术参数:标称工作电压UN:120V最大持续工作电压UC :L-N/N-PE/L-NPE 150VAC/260VAC/-额定放电电流In(8/20)µs:L-N/N-PE/L-NPE 20kA/20kA/-最大放电电流Imax(8/20)µs:L-N/N-PE/L-NPE 40kA/40kA/-5kA时的残压:L-N/N-PE/L-NPE ≤700V/≤0.15kV/-电压保护水平Up:L-N/N-PE/L-NPE ≤0.85kV/≤1kV/-17、VAL -MS 320/3+1 FM-UD(三相五线C级电源浪涌保护器)技术参数:标称工作电压UN:320V最大持续工作电压UC :L-N/N-PE/L-NPE 335VAC/260VAC/-额定放电电流In(8/20)µs:L-N/N-PE/L-NPE 20kA/20kA/-最大放电电流Imax(8/20)µs:L-N/N-PE/L-NPE 40kA/40kA/-5kA时的残压:L-N/N-PE/L-NPE ≤1.25kV/≤0.15kV/-电压保护水平Up:L-N/N-PE/L-NPE ≤1.6kV/≤1kV/-。

相关文档