220KV变电站设计毕业论文
毕业设计(论文)-220KV枢纽降压变电所设计
摘要本次设计的220KV枢纽降压变电所,将从经济性、可靠性以及灵活性几方面予以选择主变压器、主接线方式、短路电流的计算及电气设备的选择,并将安全性作为继电保护规划、配电装置的规划及防雷规划设计的基本准则,同时还须兼顾经济性方面的考虑。
主接线的可靠性、经济性、灵活性较好。
由于所设计的变电站是枢纽变电站,全站停电后,将影响整个地区的供电,所以此变电站在设计时,采用两台OSFPSL-120000/2200型变压器,满足了灵活性和可靠性。
220KV侧2回架空线路,出于经济性和灵活性的考虑,采用双母线接线形式;110KV侧4回架空线路,为了满足供电的可靠性,采用了双母线带旁路母线的接线形式;10KV侧重要负荷较多,为14回电缆线路,出于可靠性和经济性的考虑,则采用了单母线分段的接线形式。
设备选择后,对设备进行校验。
关键词:变电所;电气主接线;短路电流计算;设备选择校验;AbstractShould design the some problem that discussed in design first 220 KV change to give or get an electric shock, include an electricity lord that changing and giving or get an electric shock the choice, short-circuit electric current calculation connects the line design, electricity equipments and press protection etc. problem with the research that conduct electricity after the electricity protection programming.The reliability、economic and flexibility of the bus arrangement is well. This is a local electric substation. If the electric substation power cut, it will influence the whole area. So in the design of this electric substation use two transformers which model number is OSFPSL-120000/2200. So it can satisfy the flexibility and reliability. It doesn’t take load in the side of 220KV, so it uses double bus bar cord form in order to satisfy economy and reliability .There is much load in the side of 110KV. In order to satisfy the reliability of power supply, it uses double bus bars which have bypass bus bar cord form. There are much important load and it take the load of this electric substation in the side of 10KV, considering the reliability and economy, it use single bus bar section card form .After the equipment be selected, it should be checked.Key words:substation ;the electrical bus arrangement ;the calculation of short circuit;equipment selection and check。
220KV降压变电站电气部分设计本科毕业论文
220KV降压变电站电气部分设计本科毕业论文第一篇说明书前言电力工业是国民经济的重要部门之一,它是负责把自然界提供的能源转换为供人们直接使用的电能的产业。
它即为现代工业、现代农业、现代科学技术和现代国防提供不可少的动力,又和广大人民群众的日常生活有着密切的关系。
电力是工业的先行。
电力工业的发展必须优先于其他的工业部门,整个国民经济才能不断前进。
我国具有极其丰富的能源。
这些优越的自然条件为我国电力工业的发展提供了良好的物质基础。
但是,旧中国的电力工业落后,无法将其利用。
不过,随着改革开放的深入发展,我国电力工业的发展很快。
到2000年,我国电力工业已跃升世界第2位,电力工业的发展为我国的国民经济的高速发展做出了巨大的贡献。
不仅如此,目前我国的电力工业已开始进入“大电网”、“大机组”、“超高压交、直流输电”等新技术发展的新阶段,一些世界水平的先进的高新技术,已在我国电力系统中得到了相应的应用。
但是,随着近年来我国国民经济的高速发展与人民生活用电的急剧增长,电力工业的发展仍不能满足整个社会发展的需要,未能很好起到先行的作用,仅以2004年夏季的供电负荷高峰期为例,全国预计总共缺电3000万KW左右,有24个省区都先后出现拉闸限电的情况,这样的局面预期还要过2~3年才可能得到较好的解决。
另外,由于我国人口众多,由此在按人口平均用电方面,迄今不仅仍远远落后于一些发达国家,即使在发展中国家中,也只处于中等水平,尚不及全世界平均人口用电量的一半。
因而,要实现在21世纪初全面建设小康社会的要求,我国的电力工业必须持续、稳步地大力发展,一方面是要大力加强电源建设,搞好“西电东送”,以确保电力先行,另一方面,要继续深化电力体制改革,实施厂网分开、竞价上网,并建立起符合社会主义市场经济法则的、规范的电力市场。
展望未来,我们坚信,在新的世纪,中国的电力工业必须持续、高速地发展,取得更加辉煌的成就。
第一章原始资料分析1.1 变电站的类型本次设计的为220kv降压变电站,建成后与110kv和220kv电网相连,并供给近区用户。
220kv变电站设计毕业论文
摘要随着我国可以发展,特别是计算机的进步,电力系统对变电站的要求越来越高。
本设计讨论的是220kV变电站电气部分的设计。
首先对原资料进行分析,选择主变压器,在此基础上进行主接线设计,在进行短路计算,选择设备,然后进行防雷接地以及保护,配电装置设计。
关键词:设备选择;短路计算;防雷接地;主接线;电气平面布置;互感器;隔离开关;ABSTRACTAlong with our country can be developed, especially the progress of computer, more and more high to the requirement of transformer substation in power systems.Is discussed in this design 220 kV transformer substation electrical part of the design.First analyze the original data, choose the main transformer, on the basis of the main wiring design, the short circuit calculation, equipment choice, then grounding and protection, power distribution equipment design.Key words: equipment selection;Short circuit calculation.The main grounding, wiring;The electrical layout;Transformer;Isolating switch目录摘要 (I)关键词: (I)ABSTRACT ......................................................................................................................................................... I I 诚信声明............................................................................................................................................................. I II 第一章、引言................................................................................................................................................ - 1 - (一)原始资料分析............................................................................................................................ - 1 -1.设计原始资料.............................................................................................................................. - 1 - 第二章、电气主接线设计............................................................................................................................ - 2 - (一)电气主接线的概念及要求 ........................................................................................................ - 3 -1. 电气主接线的概念.................................................................................................................... - 3 -2. 电气主接线的要求.................................................................................................................... - 3 -(二)变压器的选择.............................................................................................................................. - 3 - (三)电气主接线的形式...................................................................................................................... - 4 -1. 单母线接线................................................................................................................................ - 4 -2. 双母线接线................................................................................................................................ - 5 -3. 3/2断路器接线....................................................................................................................... - 6 -(四)电气主接线的技术比较.............................................................................................................. - 7 -1. 方案一........................................................................................................................................ - 7 -2. 方案二........................................................................................................................................ - 7 -3. 两方案经济比较........................................................................................................................ - 8 -4. 所用电设计................................................................................................................................ - 9 - 第三章、短路电流计算................................................................................................................................ - 9 - (一)短路概述.................................................................................................................................. - 10 - (二)短路参数计算.......................................................................................................................... - 10 -1. 变压器参数计算...................................................................................................................... - 10 -2. 系统等效阻抗图...................................................................................................................... - 12 -3. 短路点的确定及各点短路电流的计算 .................................................................................. - 12 -4. 10kV馈线侧限流电抗器的选择与校验 ................................................................................. - 15 -5. 重新计算10kV并列运行时短路电流 .................................................................................... - 16 -(三)短路电流计算数据表.............................................................................................................. - 17 - 第四章、主要电气设备的选择.................................................................................................................. - 18 - (一)电气设备选择及校验原则 ...................................................................................................... - 18 - (二) 220kV电压等级电气设备选择 ............................................................................................... - 19 -1. 对220kV侧的分析计算 .......................................................................................................... - 19 -2. 220kV侧断路器的选择与校验 ............................................................................................... - 19 -3. 220kV隔离开关的选择和校验 ............................................................................................... - 21 -4. 互感器的作用与特点.............................................................................................................. - 22 -5. 电流互感器选择与校验 .......................................................................................................... - 23 -6. 电压互感器选择...................................................................................................................... - 24 -7. 母线的选择与校验.................................................................................................................. - 24 -(三) 110kV电压等级电气设备选择 ............................................................................................... - 26 -1. 对110kV侧的分析计算 .......................................................................................................... - 26 -2. 110kV母线侧断路器的选择与校验 ....................................................................................... - 26 -3. 110kV母线隔离开关的选择和校验 ....................................................................................... - 28 -4. 电流互感器选择与校验 .......................................................................................................... - 29 -5. 电压互感器选择...................................................................................................................... - 30 -6. 母线的选择与校验.................................................................................................................. - 30 -7.110kV馈线侧断路器的选择与校验 ......................................................................................... - 31 -8.110kV馈线侧隔离开关的选择与校验 ..................................................................................... - 33 -9. 110kV馈线侧线路导线的选择与校验 ................................................................................... - 34 -(四)10kV电压等级电气设备选择 ................................................................................................... - 35 -1. 10kV出线电缆的选择与校验 ................................................................................................. - 35 -2. 10kV高压开关柜选择............................................................................................................. - 35 -3. 10kV电流互感器选择与校验 ................................................................................................. - 36 -4. 10kV电压互感器选择............................................................................................................. - 37 -5. 10kV馈线无功补偿设备的选择 ............................................................................................. - 37 -(五)设备清单.................................................................................................................................. - 37 - 第五章、电气总平面布置.......................................................................................................................... - 38 - (一)概述............................................................................................................................................ - 38 -1. 配电装置特点.......................................................................................................................... - 39 -2. 配电装置类型及应用.............................................................................................................. - 39 -(二)配电装置的确定...................................................................................................................... - 40 - (三)电气总平面布置...................................................................................................................... - 43 -1.电气总平面布置的要求............................................................................................................ - 43 -2.电气总平面布置........................................................................................................................ - 43 - 参考文献........................................................................................................................................................ - 45 -第1章 引言1.1 原始资料分析1.1.1设计原始资料由于经济的发展,闽西地区电力需求增加,单由于闽西地区电力网络早期规范欠缺的原因,造成龙岩一带变电站电力负荷过重,急需修建一个3⨯120MVA 220 的变电站,以缓解这一地区的电力压力。
220KV变电站设计 毕业论文
220KV变电站设计毕业论文
简介
本文档旨在探讨和研究220KV变电站的设计要点和技术考虑
因素。
变电站作为电力系统的重要组成部分,其设计对于电力传输
和配电具有重要影响。
本文将重点讨论变电站的整体设计、设备选
择和布局优化等方面。
设计要点
1. 变电站规模与载能力的匹配:根据实际需求和负荷预测,确
定变电站的规模和容量,确保其能够满足供电要求。
2. 电力设备的选择与配置:选择合适的变压器、开关设备、保
护装置等,确保设备的可靠性和稳定性。
3. 控制系统和自动化技术:采用先进的控制系统和自动化技术,提高变电站的运行效率和安全性。
4. 安全与环保考虑:考虑火灾、爆炸和电磁辐射等安全因素,
同时注重变电站的环保设计和能源利用效率。
技术考虑因素
1. 电气设计:包括电压等级、电流容量、电缆布置、接地系统等。
2. 建筑结构设计:确保变电站建筑的稳定性和安全性。
3. 通信系统设计:实现变电站的远程监控和通信功能。
4. 维护和运维考虑:考虑到变电站的长期运行和维护,设计应方便检修和维护。
结论
通过对220KV变电站设计的研究和探讨,可以更好地理解其设计要点和技术考虑因素。
合理的变电站设计能够提高供电质量,增强电力系统的稳定性和可靠性。
因此,在进行220KV变电站设计时,需要充分考虑以上要点和因素,以满足供电需求并确保变电站的安全和可持续发展。
220KV变电站电气部分设计毕业论文
设计课题:220KV变电站电气部分设计随着经济的发展和现代工业建设的迅速崛起,供电系统的设计越来越全面、系统,工厂用电量迅速增长,对电能质量、技术经济状况、供电的可靠性指标也日益提高,因此对供电设计也有了更高、更完善的要求。
设计是否合理, 不仅直接影响基建建投资、运行费用和有色金属的消耗量,也会反映在供电的可靠性和安全生产方面,它和企业的经济效益、设备人身安全密切相关。
本设计讨论的是220KV变电站电气部分的设计。
首先对原始资料进行分析,选择主变压器,在此基础上进行主接线设计,再进行电气总平面的布置及配电装置的设计,变压器的选择,然后进行短路计算,导体电气设备的选择,继电保护的设计和配备,最后进行防雷接地以及保护设计。
关键字:变电站;短路计算;设备选择;继电保护;防雷接地;ABSTRACTWith the development of economy and the rapid rise of the modern industrial construction, the design of the power supply system is more and more comprehensive, system, plant power consumption growing rapidly, the power quality, technical and economic conditions, the power supply reliability index also is increasing day by day, therefore also has a bigger, better for power supply design requirements. Design is reasonable, not only directly affect the capital construction investment, operation cost and the consumption of non-ferrous metal, also reflected in the power supply reliability and safety production, and it is closely related to the enterprise's economic benefits, equipment safety.The design is refer to the part of 220kV electrical substation design. First of all, analyze the original data ,based on it, design the main wiring and then the design of the electrical general layout of the arrangement and distribution equipment and choose the main transformer, then the short circuit calculation ,the choice of conductor electrical equipment, the design of relay protection and are equippedwith,at last, Lightning protection grounding and protection design .Key Words: Substation; Short Circuit Calculation; Equipment Selection; Relay protection; Lightning protection grounding;.IZ .A —刖日 ......1电气主接线的设计.・・・. 1. 1主接线概述 ........ 1.2主接线设计原则.・・・・ 1. 3主接线选择 ........2电气总平面布置及配电装置的选择 4 220KV 变电站电气部分短路计算・. 1.1 变压器的各绕组电抗标幺值计算..................................... 19 1.2 10KV 侧短路计算 .................................................. 90 1.3 3 220KV 侧短路计算 ............................................... 103 4.4 110KV 侧短路计算 ................................................. 114 5导体和电气设备的选择 .............................................. 136 5.1断路器和隔离开关的选择 ........................................... 137 5. 1. 1 220KV 出线、主变侧 ............................................ 27 5. 1.2 主变 110KV 侧 .................................................. 31 5.1.3 10KV 限流电抗器、断路器隔离开关的选择 .......................... 204 5. 2电流互感器的选择 ................................................. 39 5. 2. 1 220KV 侧电流互感器的选择 ..................................... 260 5. 2.2 110KV 侧的电流互感器的选择 .................................... 281 5. 2. 3 10KV 侧电流互感器的选择 ...................................... 292 5. 3电压互感器的选择 ................................................ 313 5. 3. 1 220KV 侧母线电压互感器的选择 ................................. 325 5. 3. 2 110KV 母线设备PT 的选择 (325)目录.8 10 102. 1概述 .................. 2. 1. 1配电装置特点 ....... 2. 1.2配电装置类型及应用..3. 2配电装置的确定 ........4. 3电气总平面布置 ........5. 3. 1电气总平面布置的要求6. 3. 2电气总平面布置 ..... 3主变压器的选择73. 1. 1 3. 1.2 3. 1.3 主变压器台数的选择 ..... 主变压器容量的选择 ..... 主变压器型式的选择 .....绕组数量和连接形式的选择 7. 2主变压器选择结果 .....错误!未定义书签。
(完整版)220KV变电站毕业设计
8.1概述53
8.1.1配电装置特点53
8.1.2配电装置类型及应用53
8.2配电装置的确定54
8.3电气总平面布置56
8.3.1电气总平面布置的要求56
8.3.2电气总平面布置56
8.3.3给排水、消防及其他57
8.3.4环境保护与绿化57
第9章 电气二次部分说明58
Key words: Substation;Short circuit calculation;Equipment selection;Protect.
摘 要I
ABSTRACTII
第1章引言1
第2章电气主接线的设计2
2.1主接线概述2
2.2主接线设计原则2
2.3电气主接线方案的选择2
第3章主变压器的选择5
该设计包括以下任务:1、选择主变压器的台数、容量及型号 2、主接线选择3、确定无功补偿方式 4、选择所用变压器的容量、台数及接线方式 5、确定主变压器中性点的运行方式。若需装设消弧线圈,应选择消弧线圈的容量、台数及型号 6、配电装置的规划 7、短路电流计算 8、主要电气设备的选择 9、变电所的防雷规划,并配置主接线中常规避雷器 10、配置继电保护及自动装置 11、任选一条低压侧架空出线的继电保护整定计算 12、自选题的设计。
6.4.5变压器110kV侧引接线的选择与校验44
6.4.6变压器10kV侧引接线的选择与校验45
6.5电容补偿装置的选择46
第7章防雷接地设计47
7.1防雷设计47
7.1.1防雷设计原则47
7.1.2避Biblioteka 器的选择477.1.3避雷针的配置50
7.2接地设计51
7.2.1接地设计的原则51
220KV变电站设计毕业设计论文
毕业设计(论文)题目发电厂220kV变电站设计毕业设计(论文)原创性声明和使用授权说明原创性声明本人郑重承诺:所呈交的毕业设计(论文),是我个人在指导教师的指导下进行的研究工作及取得的成果。
尽我所知,除文中特别加以标注和致谢的地方外,不包含其他人或组织已经发表或公布过的研究成果,也不包含我为获得及其它教育机构的学位或学历而使用过的材料。
对本研究提供过帮助和做出过贡献的个人或集体,均已在文中作了明确的说明并表示了谢意。
作者签名:日期:指导教师签名:日期:使用授权说明本人完全了解大学关于收集、保存、使用毕业设计(论文)的规定,即:按照学校要求提交毕业设计(论文)的印刷本和电子版本;学校有权保存毕业设计(论文)的印刷本和电子版,并提供目录检索与阅览服务;学校可以采用影印、缩印、数字化或其它复制手段保存论文;在不以赢利为目的前提下,学校可以公布论文的部分或全部内容。
作者签名:日期:学位论文原创性声明本人郑重声明:所呈交的论文是本人在导师的指导下独立进行研究所取得的研究成果。
除了文中特别加以标注引用的内容外,本论文不包含任何其他个人或集体已经发表或撰写的成果作品。
对本文的研究做出重要贡献的个人和集体,均已在文中以明确方式标明。
本人完全意识到本声明的法律后果由本人承担。
作者签名:日期:年月日学位论文版权使用授权书本学位论文作者完全了解学校有关保留、使用学位论文的规定,同意学校保留并向国家有关部门或机构送交论文的复印件和电子版,允许论文被查阅和借阅。
本人授权大学可以将本学位论文的全部或部分内容编入有关数据库进行检索,可以采用影印、缩印或扫描等复制手段保存和汇编本学位论文。
涉密论文按学校规定处理。
作者签名:日期:年月日导师签名:日期:年月日注意事项1.设计(论文)的内容包括:1)封面(按教务处制定的标准封面格式制作)2)原创性声明3)中文摘要(300字左右)、关键词4)外文摘要、关键词5)目次页(附件不统一编入)6)论文主体部分:引言(或绪论)、正文、结论7)参考文献8)致谢9)附录(对论文支持必要时)2.论文字数要求:理工类设计(论文)正文字数不少于1万字(不包括图纸、程序清单等),文科类论文正文字数不少于1.2万字。
220KV变电站设计毕业论文
引言随着经济的腾飞,电力系统的发展和负荷的增长,电力网容量的增大,电压等级和综合自动化水平也不断提高,科学技术突飞猛进,新技术、新电力设备日新月异,该地原有变电所设备陈旧,占地较大,自动化程度不高,为满足该地区经济的持续发展和人民生活的需要,电网正在进行大规模的改造,对变电所的设计提出了更高、更新的要求。
建设新的变电所,采用先进的设备,使其与世界先进变电所接轨,这对提高电力网的供电可靠性,降低线路损耗,改善电能质量,增加电力企业的经济效益有很大的现实意义。
1、绪论由于经济社会和现代科学技术的发展,电力网容量的增大,电压等级的提高,综合自动化水平的需求,使变电所设计问题变得越来越复杂。
除了常规变电所之外,还出现了微机变电所、综合自动化变电所和无人值班变电所等。
目前,随着我国城乡电网建设与改革工作的开展,对变电所设计也提出了更高、更新的要求。
1.1 我国变电所发展现状变电技术的发展与电网的发展和设备的制造水平密切相关。
近年来,为了满足经济快速增长对电力的需求,我国电力工业也在高速发展,电网规模不断扩大。
目前我国建成的500kV变电所有近200座,220kV变电所有几千座;500kV电网已成为主要的输电网络,大经济区之间实现了联网,最终将实现全国联网。
电气设备的制造水平也在不断提高,产品的性能和质量都有了较大的改进。
除空气绝缘的高压电气设备外,GIS、组合化、智能化、数字化的高压配电装置也有了新的发展;计算机监控微机保护已经在电力系统中全面推广采用;代表现代输变电技术最高水平的750kV直流输电,500kV交流可控串联补偿也已经投入商业运行。
我国电网供电的可靠性近年来也有了较大的提高,在发达国家连续发生严重的电网事故的同时,我国电网的运行比较稳定,保证了经济的高速发展。
1.2 变电所未来发展需要解决的问题在未来,随着经济的增长,变电技术还将有新的发展,同时也给电力工程技术人员提出了一些需要解决的问题,例如:高压、大容量变电所深入负荷中心进入市区所带来的如何减少变电所占地问题、环境兼容问题;电网联系越来越紧密,如何解决在事故时快速切除隔离故障点,保证电力系统安全稳定问题;系统短路电流水平不断提高,如何限制短路电流问题;在保证供电可靠性的前提下,如何恰当的选择主接线和电气设备、降低工程造价问题等。
220kv变电站一次部分设计毕业论文
河南理工大学毕业设计(论文)说明书摘要随着经济的发展和现代工业建设的迅速崛起,供电系统的设计越来越全面、系统,工厂用电量迅速增长,对电能质量、技术经济状况、供电的可靠性指标也日益提高,因此对供电设计也有了更高、更完善的要求.本设计主要介绍了220kV变电站一次部分的设计。
首先通过对原始资料进行分析,设计主接线形式,综合比较各种接线方式的特点、优缺点,根据电气主接线设计的基本要求选择两种较其它方案可靠的主接线方案;再对两种方案进行全面的可靠性、灵活性和经济性比较,确定最优的主接线方案;然后根据题目要求选择主变压器的台数以及容量,再进行短路电流计算,为设计中需要的高压电气设备的选择、整定、校验等方面做准备;继而进行主要电气设备的选择与校验,最后进行防雷保护设计。
关键词:变电站;主变压器;短路计算;电气设备选择。
ABSTRACTWith the development of economy and the rapid rise of the modern industrial construction, design of power supply system is more and more comprehensive,system,factory power consumption increased rapidly,the power quality, technical and economic conditions, power supply reliability index is increasing, so the design of power supply also has a higher, better.This design mainly introduces the design of 220 kv substation a part。
Through analyze the raw data first, design main wiring forms, comprehensive comparison of various characteristics of wiring method,advantages and disadvantages,choose according to the basic requirement of the main electrical wiring design two kinds of main wiring scheme than other solutions and reliable;Again to the reliability of the two plans to conduct a comprehensive,flexible and economical comparison,to determine the optimal main wiring scheme; Then the sets and the capacity of main transformer according to the request of topic selection, short-circuit current calculation again, needed for the design of high voltage electrical equipment choice preparation, setting,calibration, etc;And then to the main electrical equipment selection and calibration, finally carries on the lightning protection design。
220kv变电站系统毕业设计论文
中文摘要本文主要对国泰220kV一次降压变电所电气部分进行设计,根据任务书的要求,设计的主要内容包括主变选择、电气主接线的拟定、短路计算、电气设备选择、配电装置的规划、继电保护和自动装置的规划以及防雷保护的规划等主要工作。
本文中对主变的选择、电气主接线的拟定、配电装置的规划、继电保护和自动装置的规划进行了详细的说明,特别是对主变继电保护的规划、动作原理等内容进行了深入的研究和思考。
本文重点的计算部分包括短路计算、设备的选择校验计算、和避雷针的保护范围计算等部分。
其中短路计算包括对称短路计算和不对称短路计算两部分,分别应用了计算曲线和正序等效原则;防雷计算中采用了等针高的计算方式。
本次设计既满足了电力系统的安全、经济、可靠、环保的基本要求,又重视了电力系统的长期规划长远的发展,注重了解和应用电力系统的新技术新设备,变电所进行设计,是一次较为综合性的实践过程。
是对以往所学专业知识的系统总结和提高。
本设计属于变电所电气部分初步设计,能够基本满足任务书和毕业论文的总体要求。
关键词变电所,电气系统,短路计算,电气设备- I -AbstractIn this paper The professional graduate in system in electric power design is once more synthesize of training, it is we will during the period of school a profession for learning knowledge proceed theories and practice very good combination, make use of the theories knowledge proceeds with a profession for learning technical ability engineering design with science study. This graduate design thesis is a 220 kV declining to press to change to give or get an electric shock an electricity parts of first steps design. For the sake of dependable that guarantee the power supply with a request that contented long-term burthen, carries according to the forward the programming proceeding design developments, from but guarantee to change to give or get an electric shock can long-term dependable power supply.This design not only meets the power system security, economic, reliable, basic requirements of environmental protection, but also to the long-term power system planning long-term development, focusing on understanding and application of new technologies and new power system equipment, substation design, is a more integrated practice. Is the knowledge learned in the past and upgrade the system. This design is part of the preliminary design of electrical substations and can basically meet the overall mission statement and these- II -requirements.Key Word substation,electric power system,short computing,electricity equipment目录中文摘要 (I)Abstract (II)目录............................................................................................................................................... I II 第一部分说明书 (1)1 主变压器的选择 (1)1.1 主变选择的有关规定 (1)- III -1.2 主变选择的原则 (1)1.2.1 主变台数的确定 (2)1.2.2 变压器形式的选择 (2)1.2.3 主变容量的确定 (2)2 电气主接线的选择 (3)2.1 概述 (3)2.2 主接线的设计原则 (4)2.2.1 考虑变电所在电力系统中的地位和作用 (4)2.2.2考虑近期和远期的发展规模 (4)2.2.3考虑负荷的重要性分级和出线回路数多少对主接线的影响 (4)2.2.4考虑主变台数对主接线的影响 (5)2.2.5考虑备用容量的有无和大小对主接线的影响 (5)2.3 主接线设计的基本要求 (5)2.3.1 可靠性 (5)2.3.2 灵活性 (6)2.3.3 经济性 (6)2.4 主接线的确定 (6)2.4.1 对原始资料的分析 (6)2.4.2 主接线方案的拟定 (7)3 短路计算 (10)3.1 概述 (10)3.2短路电流计算的主要目的 (10)3.3短路计算中的一般规定 (11)3.4电路元件参数的计算 (11)3.4.1基准值 (11)3.4.2各元件参数标么值计算 (12)3.4.3标么值表示的等值网络 (12)3.5 三相短路电流周期分量计算 (12)3.5.1影响短路电流变化规律的主要因素 (12)- IV -3.5.2应用计算曲线的具体步骤如下: (13)4 电气设备的选择 (14)4.1 概述 (14)4.1.1 一般原则 (14)4.1.2 选择的一般问题 (14)4.1.3 选择项目的说明 (15)4.2 高压断路器的选择 (16)4.3 高压隔离开关的选择 (16)4.4 母线选择 (17)4.4.1软导线介绍 (17)4.4.2一般要求 (18)4.4.3导体截面积的选择与校验 (18)4.5 电流互感器 (19)4.5.1参数选择 (19)4.5.2一次额定电流选择 (19)4.5.3电流互感器准确级 (19)4.5.4热稳定和动稳定校验 (20)4.6 电压互感器 (21)4.6.1 电压选择 (21)4.6.2 准确度选择 (21)4.7 避雷器 (22)4.7.1 避雷器的参数 (22)4.7.2 避雷器的配置 (23)5 配电装置 (24)5.1 屋内外配电装置的安全净距 (24)5.1.1 概述 (25)5.1.2 分类及特点 (25)5.1.3 屋内外配电装置的安全净距 (26)5.2 屋外配电装置 (27)- V -5.3 设计原则 (28)5.4 设计要求 (29)5.4.1 满足安全净距的要求 (29)5.4.2 施工、运行和检修的要求 (29)5.5 配电装置形式的选择 (30)6 继电保护及自动化装置规划设计 (31)6.1 继电保护在电力系统中的作用 (31)6.2 继电保护的基本要求 (32)6.3 选择保护配置及构成方案时的基本要求 (32)6.4 主要设备继电保护配置 (33)6.4.1 变压器保护 (33)6.4.2 母线保护 (34)6.4.3 线路保护 (34)6.5 自动化装置配置 (35)6.5.1 自动重合闸 (35)6.5.2 备用电源自动投入装置 (36)7 过电压保护 (36)7.1 概述 (36)7.2 配电装置的防雷保护 (37)7.3 防雷设计要求和所需资料 (37)第二部分计算书 (39)1 主变压器的容量计算 (39)1.1变电所60kV的用户总容量 (39)1.2变压器的容量 (40)1.3主变压器容量的选择 (40)2 短路电流计算 (42)2.1 系统等值网络 (42)2.1.1 系统等值电路图 (42)2.1.2 各元件电抗标幺值的计算 (42)- VI -2.2K点短路电流计算 (43)12.2.1 网络化简 (43)2.2.2 短路电流计算 (46)2.3K点短路电流计算 (47)22.3.1 网络化简 (47)2.3.2短路电流计算 (49)2.3.3短路电流计算结果 (50)3 设备的选择计算 (51)3.1 断路器的选择 (51)3.1.1 220 kV侧断路器的选择 (51)3.1.2 60kV侧断路器的选择 (54)3.2 隔离开关选择 (56)3.2.1 220kV侧隔离开关的选择 (56)3.2.2 60kV侧隔离开关选择 (58)3.3 电压互感器选择 (60)3.4 电流互感器的选择 (61)3.4.1 220 kV侧电流互感器选择 (61)3.4.2 60kV侧电流互感器选择 (63)3.5 母线的选择 (64)3.5.1 220 kV侧母线的选择 (64)3.5.2 60 kV侧母线的选择 (66)3.6 避雷器的选择 (67)4 避雷针的保护范围计算 (69)4.1 避雷针的定位及针距 (69)4.2 变电所避雷针布置图 (70)4.3 保护范围计算 (70)总结 (72)致谢 (73)- VII -参考文献 (75)附录 (76)A1.变电所电气主接线图 (76)A2.变电所配电装置平面图 (76)A3.变电所高压配电装置断面图 (76)A4.全所防雷保护图 (76)- VIII -。
220kV变电站一次部分初步设计毕业论文
220kV变电站一次部分初步设计毕业论文目录摘要.................................. 错误!未定义书签。
ABSTRACT ................................ 错误!未定义书签。
第1章引言. (3)1.1 国内外现状和发展趋势 (3)第2章电气主接线的设计 (5)2.1 电气主接线设计概述 (5)2.2 主接线的基本接线形式及其特点 (7)2.3 电气主接线的选择 (9)第3章主变压器的选择 (11)3.1 主变压器台数和容量的确定 (11)3.2 主变压器型式的选择 (11)3.3主变压器的选择结果 (12)第4章短路电流计算 (14)4.1 电路各元件参数标幺值的计算 (14)4.2 三相短路电流计算 (15)第5章导体和电气设备的选择 (26)5.1 断路器和隔离开关的选择 (23)5.2 电流互感器的选择 (38)5.3 电压互感器的选择 (48)5.4导体的选择与校验 (50)5.5互感器在主接线中的配置 (57)第6章高压配电系统及配电装置设计 (58)6.1 配电装置的要求 (58)6.2 配电装置的分类 (59)6.3 配电装置的应用 (59)6.4 配电装置的设计要求及步骤 (59)6.5 屋内配电装置的布置原则 (61)6.6 本设计中配电装置的确定 (62)第7章所用电的设计 (64)7.1 所用电源数量及容量 (64)7.2 所用电源引接方式 (65)第8章防雷和接地设计 (66)8.1 防雷设计 (66)8.2 接地设计 (73)第9章保护配置 (74)9.1 变压器的保护配置 (74)9.2 母线的保护配置 (75)第10章总结 (76)参考文献 (77)第1章 引言1.1 国内外现状和发展趋势数字化变电站技术发展现状和趋势以往制约数字化变电站发展的主要是IEC61850的应用不成熟,智能化一次设备技术不成熟,网络安全性存在一定隐患。
220kV变电站电气设计与建设毕业论文
220kV变电站电气设计与建设毕业论文目录容摘要 (I)Summary (II)第一部分设计说明书1 原始资料 (1)1.1 建站的必要性 (1)1.2 系统接入方式 (1)1.3 变电工程规模 (2)1.4变电站站址选择 (2)1.5系统短路阻抗及本期出线潮流估计 (2)2 变压器选择 (5)2.1 主变压器选择 (5)3 电气主接线设计 (9)3.1 主接线设计的原则和要求 (9)3.2 主接线基本接线方式 (9)3.3 主接线设计步骤 (10)3.4 本站主接线设计方案 (11)4 短路电流计算说明 (18)4.1 短路电流计算概述 (18)4.2 常见短路电流计算 (19)4.3 短路电流计算结果 (21)5 高压电器设备选择 (23)5.1 电气设备选择一般条件 (23)5.2 高压断路器的选择 (24)5.3 隔离开关的选择 (26)5.4 互感器的选择 (27)5.5 母线的选择 (28)6 配电装置设计 (29)6.1配电装置应满足以下基本要求 (29)6.2配电装置设计的基本步骤 (29)6.3配电装置的种类及应用 (29)6.4本变电站配电装置设计 (29)7 防雷保护设计 (31)7.1变电站防雷保护的特点 (31)7.2防雷防护类型 (31)第二部分设计计算书8 短路电流计算 (33)8.1 等值电路计算 (33)8.2 对称短路电流计算 (34)8.2 不对称短路电流计算 (43)9 电气设备选择及校验计算 (51)9.1 高压断路器选择及校验计算 (51)9.2 隔离开关选择及校验计算 (53)9.3 互感器选择及校验计算 (54)9.4 母线选择及校验计算 (55)10 防雷保护计算 (58)总结 (59)参考文献 (60)致谢 (62)第一部分设计说明书1 原始资料1.1 建站的必要性考虑到目前花垣县供电现状及将来的网络发展格局,提高了电源外送和用户供电的可靠性,加强了地区220KV电网,新建花垣220KV变电站主要为地区中间变电站,给花垣县供电并为保靖、水顺、龙山4县水电外送提供接入点。
220kV智能变电站的设计论文【范本模板】
四川理工学院毕业设计(论文)220kV智能变电站的初步设计学生:赵波学号:11021043625专业:电气工程及其自动化班级:2011.6指导教师:周爱华四川理工学院自动化与电子信息系二O一五年五月摘要伴随着工业的发展,世界上正面临着能源短缺与经济发展的矛盾。
怎样高效、节约的使用这些不可再生能源?成为当今社会所面临的巨大问题与挑战。
我们居住的地球正面临着气候变暖带来的巨大威胁,低碳经济是人类得以延续和生存的必经之路。
21世纪80年代末,世界发达国家相继开展了智能变电站的研究与探索,国内外智能电网和智能变电站的成为当今社会的必然趋势,IEC 61850协议的制定对为今智能变电站奠定了坚实的基础。
智能变电站的建设与发展不仅仅大大的降低了能源的损耗,而且也使得成本得到了大大的降低,本文将从220kV智能变电的一次电气部分设计。
首先对原始资料的分析,主变压器的选择,在此基础上提出主接线的设计方案,再进行短路计算和设备的选择。
关键词:智能变电站,IEC 61850,主接线方案,设备选择AbstractWith the development of industry, the world is facing the contradiction between the shortage of energy and economic development. How efficient, economical use of these non renewable energy? Become enormous problems and challenges facing society today. The earth on which we live is facing a huge threat of climate warming, the low-carbon economy is the only way which must be passed to the continuation of human survival.In twenty-first Century 80 at the end of the 1970s, the developed countries in the world have carried out the research and exploration of intelligent substation has become an inevitable trend in today's society, the domestic smart grid and intelligent substation, IEC 61850 protocol has laid a solid foundation for the smart substation. The construction and development of Smart Substation is not only greatly reduces the energy consumption, but also makes the cost of greatly reduced, an electrical part of the design in this paper from the 220kV intelligent substation。
220kV变电站一次系统设计毕业论文
220kV变电站一次系统设计毕业论文本科毕业设计(论文)题目名称: 220kV变电站一次系统设计220kV变电站一次系统设计摘要变电站作为电力系统的重要组成部分,对电能的传输和分配起着举足轻重的作用。
变电站设计是否合理,不仅影响投资和运行费用,还会影响供电可靠性和安全生产,它和企业经济效益、设备及人身安全等密切相关。
本次设计主要介绍了220kV变电站的一次系统设计。
首先根据原始资料,对可靠性、灵活性和经济性进行综合考虑,确定了220kV、110kV 和10kV侧的电气主接线形式;然后根据负荷情况等对主变压器和站用变压器的容量和型号进行选择,并对主变压器的选择结果进行校验;之后绘制系统等值网络并根据各短路点进行网络化简,得出计算电抗后根据短路电流运算曲线表得到短路电流;然后再计算最大持续工作电流,并根据最大持续工作电流和短路电流值对断路器、隔离开关、电压互感器、电流互感器、导体等电气设备进行选择并校验热稳定和动稳定;最后对配电装置、继电保护和防雷接地设计等内容进行简单论述,最终完成了本次设计。
关键词:220kV,变电站,变压器,主接线,短路计算220 KV PRIMARY SUBSTATION SYSTEM DESIGNABSTRACTAs an important part of the electric power system, the transformer substation plays an important role in the transmission and distribution of electricity. If the design of substation is reasonable, not only affects the investment and operation cost, and also affects the power supply reliability and safety in production.And it is closely related to the economic benefits, equipment and safety of the enterprise..This design introduces a system design of 220kV substation. Firstly, according to the original data, the reliability, flexibility and economy are considered, and 220kV, 110kV and 10kV are determined. The main transformerand the station are selected according to the load condition, and the selection results of the main transformer are verified. Then the network of the system is plotted and the network is based on the short circuit points, and then the calculation of the electrical resistance is obtained by the short circuit current operation curve. And then calculate the maximum continuous working current, and according to the maximum continuous working current and short-circuit current value of circuit breaker, isolating switch, current transformer, voltage transformer, conductor and other electrical equipment selection and calibration thermal stability and dynamic stability; Finally, the design of power distribution device, relay protection and ear-proof grounding design was discussed briefly.Key words:220kV, substation, transformer, main connection, short circuit calculation目录第一章绪论------------------------------------------- 11.1 引言 ------------------------------------------ 11.2 原始资料分析 ------------------------------ 21.2.1 课题内容 ------------------------------ 21.2.2 原始资料 ------------------------------ 21.3 本文主要工作 ------------------------------ 4第二章电气主接线设计---------------------------- 52.1 电气主接线概述 --------------------------- 52.2 电气主接线的基本要求 ------------------ 62.3 电气主接线设计与选择 ----------------- 102.3.1 220kV侧接线形式 ------------------ 102.3.2 110kV侧接线形式 ------------------ 162.3.3 10kV侧接线形式-------------------- 202.4 电气主接线形式图 ----------------------- 23第三章主变压器与站用变压器的选择--------- 243.1主变压器的选择--------------------------- 243.1.1 主变压器台数的选择--------------- 243.1.2 主变压器容量的选择--------------- 253.1.3 主变压器型式的选择--------------- 263.2 主变压器的校验 -------------------------- 313.3 站用变压器的选择 ----------------------- 333.3.1 站用电源数量 ----------------------- 333.3.2 站用电源容量 ----------------------- 34第四章站用电设计--------------------------------- 364.1 站用电源引接方式 ----------------------- 364.2 站用变压器低压侧接线 ----------------- 37第五章短路电流计算------------------------------ 395.1 短路计算的目的 -------------------------- 395.2 短路计算的一般规定 -------------------- 405.3 短路计算步骤 ----------------------------- 415.4 短路电流计算 ----------------------------- 415.4.1 电路各元件电抗标幺值计算------ 415.4.2 系统等值网络及短路点的选取--- 435.4.3 短路电流的计算--------------------- 44第六章电气设备的选择与校验------------------ 496.1 一般原则 ----------------------------------- 496.2 电气设备选择的一般条件 -------------- 506.2.1 按正常工作条件选择额定电压和额定电流---------------------------------------------- 506.2.2 按短路条件校验热稳定和动稳定516.3 断路器的选择及校验 -------------------- 536.3.1 各回路最大持续工作电流、额定电压及次暂态短路电流 ---------------------------- 546.3.2 220kV侧断路器选择 --------------- 556.3.3 110kV侧断路器选择 --------------- 576.3.4 10kV侧断路器选择----------------- 606.4隔离开关的选择--------------------------- 626.4.1 220kV侧隔离开关选择 ------------ 626.4.2 110kV侧隔离开关选择 ------------ 636.4.3 10kV侧隔离开关选择-------------- 656.5 电流互感器的选择 ----------------------- 666.5.1 电流互感器的选择条件------------ 666.5.2 220kV侧电流互感器选择 --------- 696.5.3 110kV侧电流互感器选择 --------- 706.5.4 10kV侧电流互感器选择----------- 726.6 电压互感器的选择 ----------------------- 746.6.1 电压互感器的选择条件------------ 746.6.2 电压互感器的选择结果------------ 756.7 导体的选择 -------------------------------- 766.7.1 导体的选择原则--------------------- 766.7.2 220kV侧导体选择 ------------------ 796.7.3 110kV侧导体选择 ------------------ 816.7.4 10kV侧导体选择-------------------- 83第七章配电装置------------------------------------ 897.1 配电装置的类型 -------------------------- 897.2 配电装置设计原则及要求 -------------- 927. 3 配电装置的确定 ------------------------- 93第八章继电保护的配置--------------------------- 948.1 电力变压器保护 -------------------------- 948.2 母线保护 ----------------------------------- 98第九章防雷与接地------------------------------- 1019.1 防雷设计 --------------------------------- 1019.1.1 变电站的直击雷保护------------- 1019.1.2 变电站的雷电侵入波保护------- 1039.1.3 变电站的进线段保护------------- 1099.2 接地设计 --------------------------------- 1109.2.1 接地概述 --------------------------- 1109.2.2 防雷接地 --------------------------- 110第十章结论---------------------------------------- 113参考文献 -------------------------------------------- 115谢辞 -------------------------------------------------- 118第一章绪论1.1 引言电能在当今世界是一种不可或缺的二次能源,可方便地由自然界中的煤、石油、天然气、水力等一次能源转化而来,同时电能也可方便地转化为光能、机械能等形式以供人们的生活需要,为各行各业的发展带来巨大的贡献。
毕业论文220KV变电站设计
变电站是电力输配变的重要环节,它是将发电厂和用电负荷连接起来的纽带,对电能的分配和变换起着决定性的作用。
因此,变电站设计的好坏将直接影响供电的稳定性和安全性。
在中国经济快速发展的现状下,为了满足区域经济的发展也为了顺应时代发展的潮流,大容量变电站因为其对土地资源的利用率高、对周边环境影响小等优点成为变电站发展所趋。
关于220KV变电站的设计本着经济、节能、可靠的原则,主要从两个方面展开:第一是变电站主要设备即变压器型号的确定,根据电站的电压等级和负荷大小对变压器的容量进行比较计算,变压器型号关系着系统供电的可靠性和稳定性。
第二是变电站一次供电线路的短路计算,短路计算的目的是为了确定电站一次设备,例如断路器,隔离开关,互感器等的型号选择。
此外,电站的防雷保护在文中也进行了相关的计算和介绍。
最后,根据设计结果,给出该电站的一次接线图。
关键字: 220KV变电站;变压器;主接线;一次设备ABSTRACTSubstation is an important of the power transmission and distribution and transmission, it is the glue link which conncts power plant with power load. And it plays a decisive role in power distribution and transformaton. Therefore,the design of the substain will directly impact the stability and safety of power supply.under the current situation of chinas rapid economill development.It is also in order to meet the development of regional economy and keep up with the trend of the times. Large capacity substaion have becom the trend of the trend of substation deveplment.Because of its high utilization of land resources,and the advantages of small impact on the surrounding envicnment.The design of 220KV substation is based on the principles of economic energy saving and reliable.This paper will start form two aspect. The first one is the determination of the transformers model.The transform is the capacity of transformer acoording to the size of voltage grade and the load of power station.For transformer model has closely related with the reliability and stability of the power supply system. The second one is a subtation power smeupply circuit of short circuit calution is to determine the devivices at a time in the in the snbbtion.such as circuit breakers isolation switches,transformer model selectoion. In addtion, this paper has also carried out the calcucation and introdution about the lightning pratection. Finally, acording to the design results, a wiring diagran of the power substation is presentd.Key words:220KV Substation;Transformer;Main wiring;Primary equipment 目录1 绪论01.1 设计的目的意义01.2 本文的主要工作02 主变压器的选择02.1 概述02.2 主变压器台数的选择02.3 主变压器容量的选择02.4 主变压器型号的选择12.5 所用变压器的选择13 电气主接线选择23.1 概述23.2 主接线的选择24 短路电流计算34.1 短路计算的目的及假设34.2 短路电流计算的步骤45 母线和电气设备的选择15.1 概述15.2 断路器和隔离开关的选择25.3 电流互感器的选择55.4 电压互感器的选择65.5 母线的选择 (6)6 防雷保护76.1 概述76.2 防雷设备87 总结错误!未定义书签。
220KV变电站电气部分优秀毕业设计论文
毕业设计是我们在校期间最后一次综合训练,它将从思维、理论以及动手能力方面给予我们严格的要求。使我们综合能力有一个整体的提高。它不但使我们巩固了本专业所学的专业知识,还使我们了解、熟悉了国家能源开发策略和有关的技术规程、规定、导则以及各种图形、符号。它将为我们以后的学习、工作打下良好的基础。
能源是社会生产力的重要基础,随着社会生产的不断发展,人类使用能源不仅在数量上越来越多,在品种及构成上也发生了很大的变化。人类对能源质量也要求越来越高。电力是能源工业、基础工业,在国家建设和国民经济发展中占据十分重要的地位,是实现国家现代化的战略重点。电能也是发展国民经济的基础,是一种无形的、不能大量存储的二次能源。电能的发、变、送、配和用电,几乎是在同时瞬间完成的,须随时保持功率平衡。要满足国民经济发展的要求,电力工业必须超前发展,这是世界发展规律。因此,做好电力规划,加强电网建设,就尤为重要。而变电站在改变或调整电压等方面在电力系统中起着重要的作用。它承担着变换电压、接受和分配电能、控制电力的流向和调整电压的责任。220KV变电站电气部分设计使其对变电站有了一个整体的了解。该设计包括以下任务:1、主接线的设计 2、主变压器的选择 3、短路计算 4、导体和电气设备的选择 5、所用电设计 6、防雷接地设计 7、配电装置设计 8、继电保护的配置等。
摘
随着我国科学技术的发展,特别是计算机技术的进步,电力系统对变电站的更要求也越来越高。
本设计讨论的是220KV变电站电气部分的设计。首先对原始资料进行分析,选择主变压器,在此基础上进行主接线设计,再进行短路计算,选择设备,然后进行防雷接地以及保护、配电装置设计。
关键字:变电站;短路计算;设备选择。
2、双母线分段接线
为了缩小母线故障的停电范围,可采用双母分段接线,用分段断路器将工作母线分为两段,每段工作母线用各自的母联断路器与备用பைடு நூலகம்线相连,电源和出线回路均匀地分布在两段工作母线上。双母接线分段接线比双母接线的可靠性更高,当一段工作母线发生故障后,在继电保护作用下,分段断路器先自动跳开,而后将故障段母线所连的电源回路的断路器跳开,该段母线所连的出线回路停电;随后,将故障段母线所连的电源回路和出线回路切换到备用母线上,即可恢复供电。这样,只是部分短时停电,而不必短期停电[6]。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
引言随着经济的腾飞,电力系统的发展和负荷的增长,电力网容量的增大,电压等级和综合自动化水平也不断提高,科学技术突飞猛进,新技术、新电力设备日新月异,该地原有变电所设备旧,占地较大,自动化程度不高,为满足该地区经济的持续发展和人民生活的需要,电网正在进行大规模的改造,对变电所的设计提出了更高、更新的要求。
建设新的变电所,采用先进的设备,使其与世界先进变电所接轨,这对提高电力网的供电可靠性,降低线路损耗,改善电能质量,增加电力企业的经济效益有很大的现实意义。
1、绪论由于经济社会和现代科学技术的发展,电力网容量的增大,电压等级的提高,综合自动化水平的需求,使变电所设计问题变得越来越复杂。
除了常规变电所之外,还出现了微机变电所、综合自动化变电所和无人值班变电所等。
目前,随着我国城乡电网建设与改革工作的开展,对变电所设计也提出了更高、更新的要求。
1.1 我国变电所发展现状变电技术的发展与电网的发展和设备的制造水平密切相关。
近年来,为了满足经济快速增长对电力的需求,我国电力工业也在高速发展,电网规模不断扩大。
目前我国建成的500kV变电所有近200座,220kV变电所有几千座;500kV电网已成为主要的输电网络,大经济区之间实现了联网,最终将实现全国联网。
电气设备的制造水平也在不断提高,产品的性能和质量都有了较大的改进。
除空气绝缘的高压电气设备外,GIS、组合化、智能化、数字化的高压配电装置也有了新的发展;计算机监控微机保护已经在电力系统中全面推广采用;代表现代输变电技术最高水平的750kV直流输电,500kV交流可控串联补偿也已经投入商业运行。
我国电网供电的可靠性近年来也有了较大的提高,在发达国家连续发生严重的电网事故的同时,我国电网的运行比较稳定,保证了经济的高速发展。
1.2 变电所未来发展需要解决的问题在未来,随着经济的增长,变电技术还将有新的发展,同时也给电力工程技术人员提出了一些需要解决的问题,例如:高压、大容量变电所深入负荷中心进入市区所带来的如何减少变电所占地问题、环境兼容问题;电网联系越来越紧密,如何解决在事故时快速切除隔离故障点,保证电力系统安全稳定问题;系统短路电流水平不断提高,如何限制短路电流问题;在保证供电可靠性的前提下,如何恰当的选择主接线和电气设备、降低工程造价问题等。
1.3 地区变电所的未来发展变电所实现无人值班是一项涉及面广、技术含量高、要求技术和管理工作相互配套的系统工程。
它包括:电网一、二次部分、变电所装备水平、通信通道建设、调度自动化系统的建立以及无人值班变电所的运行管理工作等。
所以要实现变电所的无人值班,必须满足一定的条件,主要有以下几个方面:⑴变电所的基础设施要符合要求。
如:主接线力求简单,运行方式改变易实现,变压器要具有调压能力(可以是有载调压变压器或由调压器与无载调压变压器相配合来实现调压),主开断设备要具有较高的健康水平,操作机构要能满足远方拉合要求等。
另外,所还要具备一定的基础自动化水平,用以完成对一些辅助性设备实现控制(如主变风扇的开停、电容器的投切等),以减轻调度端的工作量。
⑵调度自动化系统在达到部颁发的《县级电网电力调度自动化规》中所要求的功能的基础上,通过扩展“遥控”、“遥调”,实现“四遥”功能,达到实用化要求。
同时还要满足RTU功能先进、通道畅通可靠等条件。
⑶企业要有一支高素质的人才队伍。
这既是变电所实现无人值班建设的需要,更是变电所无人值班建成后运行和管理的需要,也是变电所能否真正实现无人化运行,发挥出应有效益的要求。
⑷对企业必须产生明显的效益。
因为变电所要实现无人值班,无论是设备升级,还是上自动化系统,需要有大量的资金投入。
对企业来说,要搞无人值班变电所,首先要作好投入产出评价。
一般来说,当运行的无人值班变电所低于3~4座时,总体经济效益是不明显的。
这主要是因为一方面县调自动化功能由于覆盖率低而得不到充分发挥;另一方面企业又要为无人值班变电所的运行、操作和管理工作配备一支队伍,而从变电所减下来的人员由于数量少,达不到减人增效的目的。
所以说,要搞无人值班变电所,就必须要形成规模。
实践证明:一个县级供电部门,在无人值班变电所数量达到50%以上时,才可能受到良好的经济效益。
实现无人值班的几点意见:⑴坚持积极稳妥的建设原则,要统筹规划,作好可行性论证,因地制宜,量力而行,以点带面,逐步展开。
目前国家在无人值班变电所设计、建设到管理等方面还没有制定出一个统一的技术导则或运行管理办法,各供电部门只能边干,边摸索,边总结,为国家形成相应的文件提供参考依据。
⑵要防止“为无人而无人”的观念。
在县级电网的规划建设时,建议在非枢纽所和用户所可先行实现无人值班,而对电网影响大的枢纽所可考虑上综合自动化系统。
⑶要坚持新建与改造并重的原则。
对于新建变电所,有条件、有实力的县局可以按照原电力部提出的小型化远景模式方案,一次到位实现变电所无人值班;对于条件尚不成熟的县局,可通过对变电所进行改造这条途径,先从设备改造入手,提高基础自动化水平,分步骤实施,最终达到无人值班的要求。
2、电气主接线2.1 电气主接线的设计原则和要求变电所电气主接线是指变电所的变压器、输电线路怎样与电力系统相连接,从而完成输配电任务。
变电所的主接线是电力系统接线组成中的一个重要组成部分。
主接线的确定,对电力系统的安全、稳定、灵活、经济运行以及变电所电气设备的选择、配电装置的布置、继电保护和控制方法的拟定将会产生直接的影响。
2.1.1 主接线的设计原则⑴考虑变电所在电力系统中的地位和作用。
变电所在电力系统中的地位和作用事决定主接线的主要因素。
变电所不管是枢纽变电所、地区变电所、终端变电所、企业变电所还是分支变电所,由于它们在电力系统中的地位和作用不同,对主接线的可靠性、灵活性、经济性的要求也不同。
⑵考虑近期和远期的发展规模。
变电所主接线设计应根据5~10年电力系统发展规划进行。
应根据负荷的大小和分布,负荷增长速度以及地区网络情况和潮流分布,并分析各种可能的运行方式,来确定主接线的形式以及所连接电源和出线回数。
⑶考虑负荷的重要性分级和出线回数多少对主接线的影响。
对一级负荷,必须有两个独立电源供电,且当一个电源失去后,应保证全部一级负荷不间断供电;对二级负荷,一般要有两个电源供电,且当一个电源失去后,能保证大部分二级负荷供电。
三级负荷一般只需一个电源供电。
⑷考虑主变压器台数对主接线的影响。
变电所主变的容量和台数,对变电所主接线的选择将产生直接的影响。
通常对大型变电所,由于其传输容量大,对供电可靠性要求高,因此,其对主接线的可靠性、灵活性的要求也高。
而容量小的变电所,其传输容量小,对主接线的可靠性、灵活性要求低。
⑸考虑备用容量的有无和大小对主接线的影响。
发、送、变的备用容量是为了保证可靠的供电,适应负荷突增、设备检修、故障停运情况下的应急要求。
电气主接线的设计要根据备用容量的有无而有所不同,例如,当断路器或母线检修时,是否允许线路、变压器停运;当线路故障时允许切除线路、变压器的数量等,都直接影响主接线的形式。
2.1.2 主接线设计的基本要求根据我国原能源部关于《220~500kV变电所设计技术规程》SDJ2—88规定:“变电所的电气主接线应根据该变电所在电力系统中的地位,变电所的规划容量、负荷性质、线路、变压器连接元件总数、设备特点等条件确定。
并应综合考虑供电可靠、运行灵活、操作检修方便、投资节约和便于过渡或扩建等要求。
主接线应满足可靠性、灵活性和经济性三项基本要求。
⑴可靠性所谓可靠性是指主接线能可靠的工作,以保证对用户不间断的供电。
衡量可靠性的客观标准是运行实践,经过长期运行实践的考验,对以往所采用的主接线经过优选,现今采用主接线的类型并不多。
主接线的可靠性是它的各组成元件,包括一、二次部分在运行中可靠性的综合。
因此,不仅要考虑一次设备对供电可靠性的影响,还要考虑继电保护二次设备的故障对供电可靠性的影响。
同时可靠性不是绝对的,而是相对的。
一种主接线可靠性的标志:①断路器检修时是否影响供电;②线路、断路器、母线故障和检修时,停运线路的回数和停运时间的长短,以及能否保证对重要用户的供电;③变电所全部停电的可能性。
⑵灵活性主接线的灵活性有以下几方面要求:①调度要求。
可以灵活的投入和切除变压器、线路,调配电源和负荷;能够满足系统在事故运行方式下、检修方式下以及特殊运行方式下的调度要求。
②检修要求。
可以方便的停运断路器、母线及其继电保护设备,进行安全检修,且不致影响对用户的供电。
③扩建要求。
可以容易的从初期过渡到终期接线,使在扩建时,无论一次和二次设备改造量最小。
⑶经济性经济性主要是投资省、占地面积小、能量损失小。
2.2 主接线方案比较及确定根据对原始资料的分析,现将各电压等级可能采用的较佳方案列出。
进而,以优化组合的方式,组成最佳可比方案。
表2.1 方案拟定表电压等级方案Ⅰ方案Ⅱ220kV 双母线接线双母带旁路接线110kV 双母线接线双母带旁路接线10kV 单母线接线单母分段接线2.2.1 220kV和110kV主接线方案确定⑴方案Ⅰ:图2.1 双母线接线①线路故障断路器拒动或母线故障只停一条母线及所连接的元件,将非永久性故障元件切换到无故障母线,可迅速恢复供电。
②检修任一元件的母线隔离开关,只停该元件和一条母线,其他元件切换到另一母线,不影响其他元件供电。
③可在任何元件不停电的情况下轮流检修母线,只需将要检修的母线上的全部元件切换到另一母线即可。
④断路器检修可加临时跨条,将被检修断路器旁路,用母联断路器代替被检修断路器,减少停电时间。
⑤运行和调度灵活,根据系统运行的需要,各元件可灵活地连接到任一母线上,实现系统的合理接线。
⑥扩建方便,一般情况下,双母线接线配电装置在一期工程中就将母线构架一次建成,近期扩建间隔的母线也安装好,在扩建新元件施工时,对原有元件没有影响。
⑵方案Ⅱ:图2.2 双母带旁路接线加旁路母线虽然解决了断路器和保护装置检修不停电的问题,但是旁路母线也带来了如下的负面影响:①旁路母线、旁路断路器及在各回路的旁路隔离开关,增加了配电装置的设备,增加了土地,也增加了工程投资。
②旁路断路器代替各回路断路器的倒闸操作复杂,容易产生误操作,酿成事故。
③保护及二次回路接线复杂。
④用旁路代替各回路断路器的倒闸操作,需要人来完成,因此带旁路母线的接线不利于实现变电所的无人值班。
近年来,系统地发展,系统接线可靠性的提高,新技术、新设备的采用,使得采用旁路母线的环境发生了较大的变化,主要有以下几个方面:⑴由于设备制造水平的提高,高质量的断路器不断出现,例如现在广泛采断路器、真空断路器,运行可靠性大幅度提高。
连续不检修运行的时间用的SF6不断增长,SF断路器制造厂可保证20年不检修。