SiC灭磁电阻型式试验报告

合集下载
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

Type Test Report

for SiC Non-Linear Resistor M & I Materials - METROSIL

CONTENT:

1.Introduction (3)

2.Test Set-up (4)

3.Test No. 1: 2’200 A; 620 V; 0,5 seconds (5)

4.Test No. 2: 6’000 A; 0,1 seconds (6)

5.Records of the Test No. 1 (7)

6.Records of the Test No. 2 (13)

1. Introduction

The test was performed on a set of the SiC non-linear resistors of type 600A /US16/ p / Spec. 6298. The purpose of the test was to investigate the loading capability of the SiC non-linear resistor for two cases:

No. 1: Intermittent load with current of approximately 2’200 A and duty cycle:

- Loading period was 0,5 seconds

- Cooling period was 30 minutes

- Repetition of duty cycle was ten (10) times

No. 2: 6’000 A in duration of 0,1 second.

Testing results are shown in Item 3 & 4

Records are shown in Item 5 & 6

2. Test Set-up

L a s t e l e m e n t - l e f t s i d e

F r I n s MEASURIN

G POINTS

3. Test No. 1: 2’200 A; 620 V; 0,5 seconds

I: 2’200 A DC (according to diagram)

Uout: ~ 690 V DC (according to diagram)

Uc: 6,0 V DC (Gate Control)

Uac: 700 V AC (Supply of thyristor converter)

Ambient temperature: 23 °C

Temperatures on measuring elements:

Measuring Point: Before: After the test:

(1) 26 °C 92 °C

(2) 25 °C 106 °C

(3) 36 °C 130 °C

Measuring points are indicated on Figure 1.

Maximum over temperature rise: 107 °K < 145 °K

Conclusion:

- Temperature rise is below the specified temperature limit for the given loading conditions. - Dissipated energy per cycle: 770 kJ

4. Test No. 2: 6’000 A; 0,1 seconds

I: 6’000 A DC (according to diagram)

Uout: ~ 1’000 V DC (according to diagram)

Uc: 6,0 V DC (Gate Control)

Uac: 1’180 V AC (Supply of thyristor converter)

Ambient temperature: 24 °C

Temperatures on measuring elements:

Measuring Point: Before: After the test:

(1) 25 °C 90 °C

(2) 25 °C 85 °C

(3) 35 °C 120 °C

Measuring points are indicated on Figure 1.

Maximum over temperature rise: 96 °K < 145 °K

Conclusion:

- Temperature rise is below the specified temperature limit for the given loading conditions. - Dissipated energy: 600 kJ

5. Records of the Test No. 1

Duty Cycle 1

Duty Cycle 2

Duty Cycle 3

Duty Cycle 4

Duty Cycle 5

Duty Cycle 6

Duty Cycle 7

Duty Cycle 8

Duty Cycle 9

Duty Cycle 10

6. Records of the Test No. 2