数据采集器采集各种设备和仪表的配置说明(doc 79页)DED-BA-E7101数据采集器设备和仪表配置说明(内部使用,未完待续)重庆德易安科技发展有限公司Chongqing EHS Technology Development Co.,Ltd.目录界面概述 (20)1.沈阳航发热能表 (23)1.1.航发超声波表配置231.2.航发机械表配置242.德易安温控器 (29)3.江阴众和电表(645-2007) (30)4.埃美柯水表 (32)5.TTD温度传感器 (33)6.深圳北电电表(645-1997) (35)7.长沙索拓温控器 (36)8.宁波甬港热能表 (37)17.浙江立新DDS238-4单相电子式电能表 .. 5917.1.采集端口配置:5917.2.配置温控器地址:6017.3.采集数据配置:6017.4.采集数据显示:6017.5.解析:6018.浙江立新DDS238-7三相电子式电能表 .. 6018.1.采集端口配置:6018.2.配置温控器地址:6118.3.采集数据配置:6118.4.采集数据显示:6118.5.解析:6219.深圳北电电表三相四线电子式有功电能表(645-1997) (62)19.1.采集端口配置:6219.2.配置表地址:6219.3.采集数据配置:6219.4.采集数据显示:6320.浙江立新DTS238-7 ZN/S型三相四线电子式电能表ModBus (63)20.1.采集端口配置:6320.2.配置表地址:6320.3.采集数据配置:6420.4.采集数据显示:6720.5.解析:6721.21.德易安温湿度传感器 (67)21.1.采集端口配置:6821.2.配置表地址:6821.3.采集数据配置:6821.4.解析:6822.浙江立新DTS238-7 ZN/S型三相四线电子式电能表T645-2007 (68)22.1.采集端口配置:6822.2.配置表地址:6922.3.采集数据配置:6922.4.采集数据显示:7322.5.解析:7323.华控信业室外温湿度传感器 (73)7323.2.配置表地址:7423.3.采集数据配置:7423.4.采集数据显示:7523.5.解析:7524.光照度传感器 (75)24.1.采集端口配置:7524.2.配置表地址:7524.3.采集数据配置:7624.4.采集数据显示:7624.5.解析:7725.中力格林配置方法 (77)7725.2.配置表地址:7725.3.采集数据配置:7825.4.采集数据显示:7825.5.解析:7826.浙江立新DTS238型三相四线有功电能表(645-1997) (79)26.1.采集端口配置:7926.2.配置表地址:7926.3.采集数据配置:7926.4.采集数据显示:8027.深圳北电单相电子式电能表(645-2007)808027.2.配置表地址:8027.3.采集数据配置:8027.4.采集数据显示:8127.5.解析:8128.F2000TSM-VOC系列变送器 (81)28.1.采集端口配置:8128.2.配置表地址:8128.3.采集数据配置:8228.4.采集数据显示:8228.5.解析:8229.EDA9033F三相电参数 (82)8229.2.配置表地址:8329.3.采集数据配置:8329.4.采集数据显示:8329.5.解析:8330.RS485压力变送器 (84)30.1.采集端口配置:8430.2.配置表地址:8430.3.采集数据配置:8430.4.采集数据显示:8430.5.解析:8431.EX8-214 三相电子式电能表(力创97—645协议) (85)31.1.采集端口配置:8531.2.配置表地址:8531.3.采集数据配置:8531.4.采集数据显示:8531.5.解析:8532.EX8-214 三相电子式电能表(力创07—645协议) (86)32.1.采集端口配置:8632.2.配置表地址:8632.3.采集数据配置:8632.4.采集数据显示:8632.5.解析:33.EX8 +三相电子式电能表(力创ModBus 通信协议) (87)33.1.采集端口配置:8733.2.配置表地址:8733.3.采集数据配置:8733.4.采集数据显示:8733.5.解析:8734.山东DDSD—113型电能表(力创97—645协议) (88)34.1.采集端口配置:8834.2.配置表地址:8834.3.采集数据配置:8834.4.采集数据显示:34.5.解析:8835.建恒热能表 (88)35.1.采集器端口配置(功能码:3 命令码:8080)(采集器程序2.84a) (89)35.2.配置表地址8936.上海安特瑞三相四线表 (89)36.1.采集器端口配置8936.2.一次侧有功电能8936.3.相电压9036.4.频率9037.江阴华诺HN530E三相四线有功电能表. 9137.1.(测试时烧写的程序是das_multi_FMGS_v2.82a01_20150924.hex) 9138.照明模块 (92)38.1.采集器端口的配置9338.2.配置表地址9338.3.采集数据配置9338.4.采集数据显示9339.机电模块 (94)39.1.采集端口配置9439.2.配置表地址9439.3.采集数据配置9439.4.采集数据显示9440.华邦三相四线电子式有功电能表(97-645)9540.1.采集器端口配置9540.2.配置表地址9540.3.采集器数据显示9541.大连道盛热量表 (96)41.1.端口配置9641.2.通道配置9642.威胜电表DTSY341电子式预付费614-2007 (96)42.1.端口配置9642.2.配置表地址9642.3.数据格式9743.上海广合DDS850Y-BK 电子式预付费 (97)43.1.端口配置9743.2.地址配置9743.3.数据格式9843.4.串口修改地址9844.常州驰高电表CG194E-9S4/9S7/9S9/9S9A9844.1.端口配置9844.2.地址配置9844.3.数据格式9945. (99)45.1.端口配置9945.2.地址配置9946.数据格式 (100)界面概述A: 根据采集器下连接的设备选择相应的协议和参数,选择好后单击“下载采集器端口配置”都配好需要保存配置时,单击上方的“保存配置”。
E6803 数据采集传输仪 说明书

数采仪概述
型号 控制器
CPU
内存 数据 数据掉电保存时间 平均无故障时间
I/O 配置
模拟量输入(AI) 数字量输入(DI) 数字量输出(DO)
通信
RS-232 传输方式 通信速率 通信协议 协议模式 连接方式
RS-485 传输方式 通信速率 通信协议 协议模式
E6803
32 位处理器、运算速度 30MPIS、内部实时时钟日期、集成 看门狗、32 个定时器、32 路 PID 64M 程序 128M 数据 FLASH 10 年 100,000h
其中第一个 485 的通道对应数采仪的 COM2, 第二个 485 的通道与 COM1 共用,连接时只能选择一种方式。 如果数采仪没有配置内置的 GPRS 模块,COM0 可以提供使用,
-9-
否则不行。
3、“本机 IP”配置
E6803 数Biblioteka 采集传输仪“本机 IP”配置界面,用于设置网络连接的参数,包括数采仪本机 IP 地址、掩码、网关、MAC 地址。以十进制格式输入,点击“确定”写 入设置,“返回”取消设置。
现场安装注意事项 数采仪是一个电子仪器,现场安装的环境直接影响到数采仪的使用,可靠
性,以及使用寿命。为保证数据数采仪正常可靠运行,安装环境应注意: 应安装在室内,不要安装在走廊、屋檐下等地方 远离灰尘、粉尘 无腐蚀性气体 远离热源 电源接入线应选无大动力设备的相线 避免太阳光直射
-6-
2、等比例采样仪控制
E6803 数据采集传输仪
点击“等比例采样仪控制”按钮可以进入以上相应界面,如果需要即时 采样,点击后进入界面,必须输入其中的瓶号和采样量,然后点击“即时采 样”按钮。如果没有安装等比例采样仪,本项操作都将无效。
福禄克 190 Series III 范围测量仪 MDA-550 产品技术指标 说明书

一般技术指标
保修 ............................................................................3 年 (不包括电池和附件) 校准周期 ..................................................................... 技术指标基于 1 年校准间隔 尺寸 ............................................................................265 mm x 192 mm x 70 mm (10.5 in x 7.6 in x 2.8 in) 重量
电磁兼容性 (EMC) 国际 .........................................................................IEC 61326-1:工业 CISPR 11: 第 1 组, A 类 第 1 组:设备内部产生和 / 或使用与传导相关的无线电频率能量,该能量对于设备自身的内部功能必不可少。 A 类:设备适用于非家庭使用以及未直接连接到为住宅建筑物供电的低电压网络的任意设备中。由于传导干扰和 辐射干扰,在其他环境中可能难以保证电磁兼容性。 此设备连接至测试对象后,产生的发射可能会超过 CISPR 11 规定的水平。 韩国 (KCC)...............................................................A 类设备 (工业广播和通讯设备) A 类:本产品符合工业电磁波设备的要求,销售商或用户应注意这一点。本设备旨在用于商业环境中,而非家庭 环境。 USA (FCC)...............................................................47 CFR 第 15 章 C 小节。
Omega OM-EL-DATAPAD 数据记录仪数据收集与存储平台说明书

Operation: Single front-panel push-button used for power-switch. Single press = ON, press and hold for 3 sec = OFFData Logger Connection:1x USB Type A socket (top of unit) for connection of data loggers.PC Connection:1x micro-USB (bottom of unit) for connection of unit to PC via 1 m (3.3') USB cable (included).Dimensions:107 H x 68 W x 19 mm D(4.2 x 2.7 x 0.7")Weight: 110 g (3.9 oz)of compatible OM-EL-USB Seriesdata loggers to configure theirunits and download data and viewlogging results on-the spot ratherthan removing the logger from theenvironment being measured andtaking it to their PC.This allows continual logging withshorter breaks in data collection,less travel for the user, on-site datacollection in graph, legend andsummary format and the ability forusers to reconfigure loggers in “thefield”. The logger is connected to theOM-EL-DATAPAD via a standardUSB port at the top of the viewer.Once connected, the user is guidedthrough a simple touchscreen menuwith options to set-up logger, stoplogger and download and view data.On-screen instructions follow the samestructure as the OM-EL-WIN-USBsoftware for PC currently providedwith each data logger.Ordering Example: OM-EL-DATAPAD handheld programmer and data collector for theOM-EL-USB Series data loggers and OCW-1OMEGACARE SM 1-year extended warrantyadds 1-year to standard 1-year warranty, and OM-EL-BOOT protective rubber boot for OM-EL-DATAPAD.OMEGACARE SM extendedwarranty program is available formodels shown on this page. Askyour sales representative for fulldetails when placing an order.OMEGACARE SM covers parts,labor and equivalent loaners.OM-EL-USB Series dataloggers plug directly intothe OM-EL-DATAPADeliminating the need foran on-site PC.connection (included)LCD: 240 x 320, 2.8" TFTwith touch-screenMemory: Internal flashData Recording Capacity:>8.5 million readings typicalOperating Time(On SingleCharge): 8 hours typical(5 hours continuous use)Operating Temperature:0 to 50°C (32 to 122°F)。
4G 无线直流电压电流采集器器产品说明书

【上海数采物联网科技有限公司】无线电压电流采集器产品说明书版本:V1.1目录1产品概述 (1)2服务理念 (2)3产品特性参数 (3)3.1采集特性 (3)3.2电气特性 (3)3.3通信特性 (3)3.4结构特性 (3)3.5工作环境 (3)4产品核心优势 (4)5数据上报通信协议 (5)5.1协议解析说明 (5)5.2协议接收测试 (5)5.3协议定制 (5)6平台对接 (6)6.1默认平台 (6)6.2用户指定平台 (6)7注意事项 (7)1产品概述SC-GP-VC4G无线直流电压电流采集器,是上海数采物联网科技有限公司推出的一款基于4G网络通讯,将电压电流信号转化为数字信号,由无线模块传送到服务器的工业监测设备,电压电流传感器采用进口隔离霍尔元件,采集精度高,稳定性好,采集精度达0.1%,广泛应用于多种工业与民用场景,例如直流屏、光伏产业、测试及检测设备、消费品、汽车、地铁、自动控制、数据记录器、气象站、家电、医疗、电力及其他相关工业检测控制。
2服务理念我司郑重承诺:您购买的不仅仅是产品,还有细致、周到的技术支持服务(=^_^=)本产品,现场只需普通工人接电安装即可!无需调试!我们免费提供远程指导,远程配置调试服务,将数据发送至用户指定的云平台。
免费提供物联网方案咨询服务!3产品特性参数3.1采集特性●电压精度0.01V/±0.1%,电流0.01A/±0.5%●电压范围0-200V,电流范围0-100A●电流采集非侵入式,电压采集并联采集3.2电气特性●供电方式:12V直流供电(电源接口:DC5.5*2.1mm母头插座,内正外负)●工作功耗:小于5W3.3通信特性无线传输方式:4G/GPRS通信协议:MQTT/TCP/UDP/HTTP/SSL/ModBus RTU,可定制其他协议数据转发:任意公网服务器服务器中心数量:最多可支持同时向7个云服务器同时上报数据。
心跳包:支持自定义心跳包,可设置为信号强度。
ESJ680操作手册v1.4.1_General_ Chinese

喷码机操作及维修手册目录⏹技术参数 (5)✧电气规格 (5)✧重量 (5)✧尺寸 (5)✧环境规格 (6)✧墨水的用量 (6)✧喷码机耗材容量 (6)⏹喷码原理 (7)✧喷码机的应用特点 (7)✧喷印字符的形成 (7)✧工作原理简述 (8)喷墨打印原理 (8)墨路工作原理 (10)✧影响喷印质量及稳定性的因素 (11)✧主要组成部件及功能 (11)⏹喷码机描述 (12)✧外观及主要部件 (12)✧墨路系统组件 (13)✧喷头 (13)✧外部连接 (14)✧操作面板描述 (15)✧液晶屏 (16)⏹喷码机操作 (17)✧操作界面架构图 (18)✧新机器开机流程 (19)✧正常开机 (22)✧正常关机 (22)✧停机流程表 (23)✧快速关机 (25)✧整机清洗流程 (25)✧查看喷码机状态参数 (26)✧编辑信息 (27)清除屏幕 (27)选择字体 (27)字符间距 (28)字符方向 (28)字符加粗 (28)插入项目 (28)●插入时钟 (29)●插入序列号 (30)●插入班次: (31)●插入信息: (32)●插入二维码: (33)●插入条形码: (35)●插入串口随机号 (36)●插入磁盘字符串 (38)打印信息 (40)保存信息 (40)另存信息 (40)显示模式 (40)✧选择信息 (41)✧喷印设置 (42)喷印延时 (42)喷印速度 (42)喷印高度 (43)信息方向 (43)粗体喷印 (45)电眼控制 (45)●有效状态 (45)●滤波间隔 (45)●响应方式 (46)速度模式 (46)●内同步 (46)●外同步 (47)重复喷印 (48)充电算法 (49)计米喷印 (49)✧序列号 (50)✧功能限制 (51)✧系统设置 (52)时钟设置 (53)密码设置 (54)计数器 (55)外部接口 (56)事件记录 (56)系统恢复 (56)软件升级 (56)配置信息 (57)通讯设置 (57)特殊设置 (58)✧墨路维护 (59)喷头维护 (59)喷头结构图 (60)黏度标定 (61)手动控制 (61)墨路系统原理图 (63)墨路引灌 (64)墨路排空 (64)飞行时间校准 (64)自动清洗 (64)帮助 (64)✧系统维护 (65)墨线开关 (65)高压开关 (65)喷印测试 (66)喷嘴调制 (67)相位测试 (67)高压监测 (68)黏度监测 (68)压力设置 (68)转速设置 (68)运行时间 (68)✧更多功能 (69)⏹技术参数✧电气规格✧重量喷码机净重量为30Kg。
数据采集设备操作使用说明书

MDR-8.07 移动数据记录器操作使用说明书北京京南航天数据技术有限公司目录1简介 (4)1.1用途 (4)1.2主要特点 (4)1.3 主要技术指标 (4)1.4设备组成 (4)1.4.1电源适配器 (5)1.4.2 MDR采集器 (5)2MDR软件安装 (7)2.1 硬件驱动安装 (7)2.2 MDR控制软件安装 (8)2.2.1软件安装条件 (8)2.2.2软件安装 (8)3MDR列表配置 (12)4MDR系统连接 (15)4.1 USB连接 (16)4.2网络连接 (16)4.3串口(RS422)连接 (17)5控制软件主界面 (17)5.1 菜单项 (19)5.1.1 系统配置 (19)5.1.2 数据操作 (19)5.1.3 数据显示 (21)5.1.4 应变调整 (21)5.1.5 标定 (22)5.1.6 其他菜单 (22)5.2 工具栏 (23)5.3 控制面板 (23)5.4 显示窗口 (24)6参数设置 (25)6.1 参数设置界面 (26)6.2 统一参数 (28)6.3 滑动平均 (28)6.4 触发类型设定 (29)7数据传输 (29)7.1 通道选择 (32)7.2 数据传输 (32)7.3 图形显示开关和显示图形延时 (32)7.4 图形操作 (33)8传感器标定 (33)9MDR数据采集步骤 (36)9.1 MDR连接 (36)9.2 MDR列表配置 (36)9.3 参数设置 (38)9.4 数据实时显示 (38)9.5 数据采集 (39)9.6 数据传输 (40)1简介1.1用途移动数据记录器 (Moving Data Recorder) 简称MDR,是北京京南航天数据技术有限公司自主研制具有国际领先水平的高技术产品;能够记录冲击、噪声、振动、速度、位移、过载、应变、陀螺、温度、压力、数字等多种信号,适用于恶劣环境下的动态、静态数据采集记录;广泛应用于桥梁、铁路、风能、教学、煤炭机械、特种设备、汽车碰撞、运输实验、分离实验、爆炸试验、摩拖车颠簸、飞行试验中的系统测量和设备检测等领域。
智能采集终端产品介绍说明书

产品介绍说明书(智能采集终端)山东智慧燃气物联网技术有限公司目录1 市场现状分析 (1)2 公司介绍 (2)2 产品简介 (3)3基本参数 (3)4 产品特点 (4)5 显示屏代码说明 (5)6接线图 (6)智能采集终端产品需求说明书(山东智慧燃气物联网技术有限公司)随着社会能源配套的基础设施逐渐完善,燃气作为一种高能能源广泛应用于工商业,对燃气公司来说,大用户(包括工业生产、公共服务、采暖制冷企业等)的用气量比较大,然而在使用过程中,出现了各种各样的问题,部分工商业用户现场流量计的数值波动很大,存在严重的跳数现象,由此造成很多贸易计量纠纷,也给燃气用户带来了诸多困扰。
1.1燃气公司现状根据我们的初步了解,我们认为目前燃气公司大客户管理存在下列问题:很多燃气用户都在使用大功率耗电及变频设备,这些设备的启停,会产生电磁脉冲干扰现场的设备及流量计。
部分燃气流量计和燃气设备不能提供相关的计算机数据和接口。
根据燃气公司的发展设想,要逐步淘汰掉这些设备。
某些燃气流量计和燃气设备提供标准RS232/RS485接口,可以提供表或设备的相关信息,但是需要人工用台式计算机或手提电脑现场采集。
这种情况存在下列局限性:1、人工成本较高;2、人员素质影响数据采集工作;3、不能随时和长期动态的了解设备运行状况和用户用气情况;4、不能及时掌握用户的用气量,导致发生欠费现象;5、现场人工采集可能影响到用户的正常业务。
1.2燃气公司大客户的特点:公服用户一般都是生产和服务行业的公司,耗气量大;公服用户一般使用较大型的燃气设备;公服用户可能拥有多个燃气设备,并进行统一结算;对燃气的依赖程度高,能否正常供给对经营活动影响比较大。
为提高计量设备管理水平,减少供销差率都具合理分配燃气资源,而且可以随时掌握用户的用气量,避免欠费,我公司研究出针对性解决方案,推出智能采集终端硬件产品,通过对所有公服用户用气情况进行及时准确的分析,为整个燃气网的合理分析供、调配提供基础数据;这也是提高公司对大客户提高服务质量的一种有效手段。
奥姆格达数据采集系统产品说明书

C-69Type T -25 to 500°C Millivolt -5 to 45 millivolt Thermocouple Accuracy:1.0°C @25°CThermocouple Resolution:0.1°C Millivolt Accuracy:0.5% livolt Resolution:0.01 mV Voltage InputsNumber of Analog Inputs:6single-ended or 3 differential Resolution:12 bitsAnalog Input Range:0 V to 4 V Hardware Conversion Time:Dependent on speed of hostcomputer, 22µs minimum, 35µs on a 486-Dx266,160µs on a 386-Dx33Digital I/ONumber of Digital I/O Lines:2Max. Current (Sinking):4 mA Max. Current (Sourcing):0.5 mA Overvoltage Protection:+5/-0.5 Vdc OMK-TDA8Number of Thermocouple Inputs:8Ranges:Type J -50 to 800°C;Type K -50 to 1000°C; Type T -25 to 500°C Accuracy:1°C Resolution:0.1°CThroughput:1 sample on all channels every 20 mSPHYSICAL(OMK-TDA4 and OMK-TDA8)Operating Temperature Range:0to 70°C (-18 to 158°F)Dimensions:(2.3 x 2.2 x 0.6")58.4mmH x 55.8mmW x 15.2mmD Power Consumption:50 mWOMEGAdata ™SeriesData Acquisition SystemsOMK-TDA Series Low Cost Parallel Port Data AcquisitionThe OMK-TDA series are parallel port interfaces for readingthermocouples and other process signals. There are two modelsavailable, the OMK-TDA4 and the OMK-TDA8. The OMK-TDA4 has four inputs which can be used to read thermocouples or millivolt signals and six analog inputs that can accept voltage signals in the range of 0-4 volts. Two digitalinput/output lines are also provided.The OMK-TDA8 is a dedicated thermocouple measurement device that can read up to 8 thermocouples.Both OMK-TDA series products plug into the parallel port of a standard IBM PC or compatible computer and derive all power from that port making them ideally suited for portable applications.The OMK-TDA series comes with a standard software package. The software is a Microsoft Windows compatible display and loggingprogram. A Data Plotter is included that allows the analog input values to be plotted versus time. Datamay also be logged at user specified intervals in a format which iscompatible with most spread sheet programs.Windows Active X controls (OCX)are included for use with develop-ment languages such as Microsoft Visual Basic, Visual C++, Borland C++ and Borland Delphi.SpecificationsOMK-TDA4Thermocouple/millivolt Inputs Number of inputs:4 (J, K, T or millivolt)Ranges: Type J -50 to 800°C;Type K -50 to 1000°C;user’s manual on CD rom.Ordering Example: OMK-TDA4, OMEGACARE SM 1 year extended warranty for theOMK-TDA4(adds 1 year to standard 1 year warranty), and OMK-STP25A terminal panel,$199 + 25 + 35 = $259.OMK-TDA8 withSTP-25A terminal panelOMK-TDA4$199ߜ Direct Thermocouple Input, 4 Channel and 8Channel Models ߜ Millivolt and Voltage Inputs ߜ Compatible with Windows95/98/NT4/2000/MEMOST POPULARCANADA www.omega.ca Laval(Quebec) 1-800-TC-OMEGA UNITED KINGDOM www. Manchester, England0800-488-488GERMANY www.omega.deDeckenpfronn, Germany************FRANCE www.omega.frGuyancourt, France088-466-342BENELUX www.omega.nl Amstelveen, NL 0800-099-33-44UNITED STATES 1-800-TC-OMEGA Stamford, CT.CZECH REPUBLIC www.omegaeng.cz Karviná, Czech Republic596-311-899TemperatureCalibrators, Connectors, General Test and MeasurementInstruments, Glass Bulb Thermometers, Handheld Instruments for Temperature Measurement, Ice Point References,Indicating Labels, Crayons, Cements and Lacquers, Infrared Temperature Measurement Instruments, Recorders Relative Humidity Measurement Instruments, RTD Probes, Elements and Assemblies, Temperature & Process Meters, Timers and Counters, Temperature and Process Controllers and Power Switching Devices, Thermistor Elements, Probes andAssemblies,Thermocouples Thermowells and Head and Well Assemblies, Transmitters, WirePressure, Strain and ForceDisplacement Transducers, Dynamic Measurement Force Sensors, Instrumentation for Pressure and Strain Measurements, Load Cells, Pressure Gauges, PressureReference Section, Pressure Switches, Pressure Transducers, Proximity Transducers, Regulators,Strain Gages, Torque Transducers, ValvespH and ConductivityConductivity Instrumentation, Dissolved OxygenInstrumentation, Environmental Instrumentation, pH Electrodes and Instruments, Water and Soil Analysis InstrumentationHeatersBand Heaters, Cartridge Heaters, Circulation Heaters, Comfort Heaters, Controllers, Meters and SwitchingDevices, Flexible Heaters, General Test and Measurement Instruments, Heater Hook-up Wire, Heating Cable Systems, Immersion Heaters, Process Air and Duct, Heaters, Radiant Heaters, Strip Heaters, Tubular HeatersFlow and LevelAir Velocity Indicators, Doppler Flowmeters, LevelMeasurement, Magnetic Flowmeters, Mass Flowmeters,Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area Flowmeters, Vortex Shedding FlowmetersData AcquisitionAuto-Dialers and Alarm Monitoring Systems, Communication Products and Converters, Data Acquisition and Analysis Software, Data LoggersPlug-in Cards, Signal Conditioners, USB, RS232, RS485 and Parallel Port Data Acquisition Systems, Wireless Transmitters and Receivers。
胜利仪器 VICTOR 9000E无线高低压叉形电流表 说明书

DAM-E3000数据采集模块用户手册说明书

DAM-E3070D说明书★端子分布图★主要指标2路计数器/频率模块量通道:2路独立的32位计数器输入类型:隔离或非隔离隔离通道:输入电平:逻辑电平0:+1V(最大)逻辑电平1:+3.5V~+30V隔离电压:3750V非隔离通道:可编程阈值输入电平:逻辑电平0:0~+5V(默认0.8V)逻辑电平1:0~+5V(默认2.4V)最大计数:4,294,967,295(32位)可编程数字滤波器:2~65ms报警门槛值:2路计数器都有计数预调整值:可编程频率测量:范围:1Hz~100KHz内置可编程阈值时间:1.0/0.1秒开关量输出:通道:2集电极开路30V(30mA最大负载)功耗:300mW显示(仅DAM-E3070D)LED显示:5位,通道0或通道1可编程支持10/100Mbps以太网提供默认网页或可定制网页支持双看门狗电源:未调理+10~+30VDC功耗:2.0W@24VDC★端子定义表表1端子名称说明1DO0/LO开关量0输出端2DO1/H1开关量1输出端3IN0非隔离计数0输入端4GATE0非隔离门控0输入端5GND参考地(同直流电源输入地)6IN1非隔离计数1输入端7GATE1非隔离门控1输入端8GND参考地(同直流电源输入地)9-11未连接12INIT*恢复出厂设置端,与(B)GND脚短接后上电使复位13(R)+Vs直流正电源输入,+10~+30VDC14(B)GND直流电源输入地15IN0+隔离计数0输入正端16IN0-隔离计数0输入负端17GATE0+隔离门控0输入正端18GATE0-隔离门控0输入负端19IN1+隔离计数1输入正端20IN1-隔离计数1输入负端21GATE1+隔离门控1输入正端22GATE1-隔离门控1输入负端★代码配置表■显示格式代码表代码00010203显示格式二进制码工程单位欧姆值百分比■数码管显示数字配置代码表通信协议1MODBUS简介工业控制已从单机控制走向集中监控、集散控制,如今已进入网络时代,工业控制器连网也为网络管理提供了方便。
Omega OM-HL-SH Series 单通道温度和湿度数据记录仪手持智能数据记录器产品说明书

e-mail:**************For latest product manuals:Shop online at User’s GuideOM-HL-SH SeriesSingle Channel Temperature and Humidity Data Logger, HandhelderMode l: OM -HL-S H-TH LOG***********************Servicing North America:U.S.A. Omega Engineering, Inc.Headquarters:Toll-Free: 1-800-826-6342 (USA & Canada only)Customer Service: 1-800-622-2378 (USA & Canada only)Engineering Service: 1-800-872-9436 (USA & Canada only)Tel: (203) 359-1660 Fax: (203) 359-7700e-mail:**************For Other Locations Visit /worldwideThe information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.Table of ContentsSection ...................................................................................... PageSection 1Introduction (1)1.1 Introduction (1)1.2 Features (1)1.3 Applications (1)1.4 Series Data Logger Model (1)1.5 Temperature Data Logger Appearance (2)1.6 Temperature Data Logger Screen (2)1.7 Temperature and Humidity Data Logger Appearance (3)1.8 Temperature and Humidity Data Logger Screen (3)1.9 Button function instructions (3)Section 2 Installation and Instruction (4)2.1 Software Installation (4)2.1.1 The Requirement of the Computer Hardware (4)2.1.2 Install Driver & Software (4)2.2 How to Read and Configure the Logger (5)2.2.1 Read and Configure the Logger's Settings (5)2.2.2 Setting Parameters Description (6)2.3 Turn On/Off Logger & Start/Stop Logging (7)2.4 Download the Logging Data (9)2.5 View Data Sheet (10)2.6 Exporting Logs from LogPro (10)2.7 Delete Records in the Logger (11)2.8 Check the Save File in File List (11)Section 3 Attention (12)Section 4 FAQ (12)4.1 LCD Screen Dim (12)4.2 Data & Time Error (12)4.3 Software "Runtime Error" (12)4.4 Check COM Port Number (12)Section 1 - IntroductionOM-HL-SH temperature humidity data logger, developed by OMEGA, isfeatured with LCD display, elegant appearance, low energy consumption, andexcellent consistency. All the sensors are manufactured in Switzerl and, whichassures quality and stability.Section 1.2 - Features• Appearance is small and exquisite, cigarette packet size, easy to use.• The sensor was produced by Switzerland, high accuracy.• 2 x AAA Battery can be working 6 months with 25 ℃ environment.(sampling interval is 60 secs, logging interval is 300 secs).• Host Size(L x H x D): 57mm x 92mm x 20mm.• LCD Screen Size: 37mm x 17mm.• Temperature & Humidity External Probe Diameter: 16mm.• Temperature External Probe Diameter: 6mm.Section 1.3 - Application• Transportation.• Supermarkets.unit may void your warranty.Section 1.4 - Data Logger Model1Section 1.5 - Temperature Data Logger Appearance (OM-HL-SH-T )25.6.7.8.Hanger LabelBattery Cover USB Port1.2.3.4.LCD ScreenLOG/STD ButtonMAX/MIN Button Sensor1.2.3.4.Temperature ValueDisplay the Maximum Value in the MemoryDisplay the Minimum Value in the MemoryBattery Symbol: Please replace the battery when show only one bar.5. LOG Symbol6. USB Communication Symbol7. Display years, month/day, hour/ minute recurrently8. Fahrenheit Unit9. Centigrade UnitSection 1.6 - Temperature Data Logger Screen (OM-HL-SH-T )Section 1.7 - Temperature and Humidity Data Logger Appearance(OM-HL-SH-TH)1.2.3.4.Temperature & Humidity Value Display the Maximum Value in the MemoryDisplay the Minimum Value in the MemoryBattery Symbol: Please replace the battery when show only one bar.5.6.7.8.Hanger LabelBattery Cover USB Port1.2.3.4.LCD ScreenLOG/STD Button MAX/MIN Button Sensor 5.6.7.8.9.10LOG SymbolUSB Communication Symbol Display years, month/day, hour/minute recurrently Humidity Unit Fahrenheit Unit Centigrade UnitSection 1.8 - Temperature and Humidity Data Logger Screen(OM-HL-SH-TH)3Section 1.9 - Button function instructions:Switching the read maximum and minimum value.:When device is off, press 5S to enter standby mode and press 3S to enter recording mode. When device is recording, press 3S can enter standby mode (only enter standby mode), in standby model, press 5S to turn the device off.2.1.1 - The Requirement of the Computer HardwareSection 2.1 - Software InstallationSection 2 - Installation and Instruction1. OS: Windows XP/Vista/8/10 (32/64bit).2. CPU: 1.6GHz.3. Physical Memory: 512MB.4. Hard-drive Space: 4 GB.5. USB Port: 1.This section will explain how to use the software to upload, read, configure and synchronize the settings, how to turn on/off the logger & enter/exist the logging mode, and how to delete and download the logging data.42.1.2 - Install Driver & SoftwareNote: "If need to install Driver separately, please install 64 bit driver for Windows 64 bit computer & 32 bit driver for Windows 32 bit computer".1. Install LogPro Software and Driver together(Default Path: C:\OM-HL Logger).2. Installation Steps: When enter the software, click the ‘Install LogPro and Driver’(as below Pic ), and then click the ‘Next ’(5 times), click the ‘Install’, click the ‘Finish’. When entering the LogPro software interface, the installation driver softwarewindow will pop up. Click 'Install', and the success of installation will be displayed.Install driverThe successful installed Default installation folderLogPro installation page2.2.1 - Read and Configure the Logger's Settings1. Turn on and Insert the data logger to the computer ¹.2. Start LogPro software on the PC.3. From the toolbar select Connect.4. Load & Read the logger’s current settings.5. Configure the new settings.6. Sync the settings & time. (The PC time will be synchronized to the logger as well.) .7. From the toolbar select disconnect.8. Sync the Computer's Data & Time to the Data Logger.9. Unplug the logger from the computer, and then the logger is in Standby mode.7453861. The windows operating system cannot handle USB devices being unplugged and plugged back too fast. When unplugging the logger, wait for about 5 seconds before plugging it in again. If you unplug and plug back a device too quickly, the computer may stop recognizing any USB devices on that port. If this happens you will have to restart the computer. This is a windows USB problem and is not related to LogPro.5Section 2.2 - How to Read and Configure the Logger2.2.2 -Setting Parameters DescriptionCalibrate the logger: The logger is factory calibrated to an accuracy given in the device specifications. However, there may be times when you wish to adjust the calibration of your logger. Logpro provides you with the ability to perform a single point offset calibration. This calibration can be used to increase the accuracy of the logger for a restricted data range.67Section 2.3 - Turn On/Off Logger & Start/Stop Logging Under Button to Start ModeStart Logging - When the Logger is on and on stand-by(LCD does not have “LOG” logo display), press "LOG/STD" for 3 seconds, LCD display time, loosen "LOG/STD" button when the LCD display "3.0", now the logger start logging and storing data(LCD has “LOG” logo display).Turn On the Logger - Push “LOG/STD” Button for 5 Secs then LCD display is on.Stop Logging - When the logger is on logging, press "LOG/STD" for 3 seconds, LCD display time, loosen "LOG/STD" button when the LCD display "3.0",LCD does not have LOG logo display ,then the logger will be on stand-by.8Turn Off the Logger - Push the“LOG/STD” Button for 5 Secs then LCD display is off.LOG Full - The device won't record data while the memory is full, that you have todownload the data and delete it by Logpro software, then device can record again. OM-HL-SH-T LOG Full OM-HL-SH-TH LOG FullOM-HL-SH-TH LCD Display- Display temperature and humidity recurrently, eachdisplay time is 5S.Section 2.4 - Download the Logging Data10. Insert the data logger to the computer.11. Start LogPro software on the PC.12. From the toolbar select Connect.13. From the toolbar select Download.1213Once the data is downloaded from the logger to the PC, the log graph will be displayed.Tips: Press and hold the left mouse button to drag a box, when the left mouse buttonis released, the graph will be redraw with the data in the selected rectangle area. Click right button, then the graph will be redrawing with all the data in the logs file.9Section 2.5 - View Data SheetClick “Data List” button on the toolbar, and then the data listing windowis shown below. Channel 3 unit is Dew Point. The Value is calculated fromtemperature & humidity.The data pane lists the data samples collected by the logging device.The column width of each column is adjustable by using the left mouse buttonand dragging the column the desired width.Section 2.6 - Exporting Logs from LogPro• Export data list to an Excel file.• Export data list to a PDF file.• Export graph to a BMP file.10Section 2.7- Delete Records in the Logger 14. From the toolbar select Delete.14Section 2.8 - Check the Save File in File list15. From the toolbar select File List.16. Click to open the file.• Double click left mouse button, then the selected file is opened.• Click right mouse button, a popup menu is shown as below, you can rename or delete or log file.• The save file is saved in the LogPro software’s installation path in the PC’s hard driver.151611• Plastic shell is ABS, flame retartdant, not resistant to acid andalkali.• If repair is needed, only authorized technician can do the repair.• The instrument configuration by 2 x AAA Battery (1.5V) is not rechargeable.• USB power supply (2.7V) cannot let the Data Logger work.Section 4.1 - LCD Screen DimInsufficient battery or the environment tmeperature is too low or too high.Solution: In the case of insufficient battery, please replace the battery. If resultsfrom environment temperature, please immediately take the logger out of theenvironment.Section 4.2 - Data & Time ErrorReason:• The Battery level is low.• The Data Logger is not synchronous properties, before start recording.Solution:• Replace the battery.• Please sync the properties, before start recording.Section 4.3 - Software “Runtime Error”Reason:• OS forbid software creating files.Solution:• Run the program (software) as an administrator.• Install software in D or E drive if available.• A data logger name cannot contain any of the following characters: \ / :* ? “ < > |• Software’s installation path cannot include Chinese character or garbagecharacter.Section 4.4 - Check COM Port NumberPress “Win” + “R” in keyboard -> Run “devmgmt.msc” to Open “DeviceManager” in Windows-> Expand “Ports (COM & LPT)” -> “USB-serial CH340(COM No.)” is the Data Logger.12OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.OMEGA is a trademark of OMEGA ENGINEERING, INC.© Copyright 2018 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:1. Purchase Order number under which the product was PURCHASED,2. Model and serial number of the product under warranty, and3. Repair instructions and/or specific problems relative to the product.FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:1. Purchase Order number to cover the COST of the repair,2. Model and serial number of the product, and 3. Repair instructions and/or specific problems relative to the product.RETURN REQUESTS/INQUIRIESDirect all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.The purchaser is responsible for shipping charges, freight, insurance and proper packaging to preventbreakage in transit.WARRANTY/DISCLAIMEROMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the c om pone nt u po n w hich liability is b a se d. I n no event s hal l O MEG A be liable for consequential, incidental or special damages.CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of theProduct(s) in such a manner.Where Do I F ind Everything I Need fo rP r oce ss Me a s urement and Cont r ol?OME GA…Of Cours e!Shop online at TEMPERATUREThermocouple, RTD & Thermistor Probes, Connectors,Panels & AssembliesWire: Thermocouple, RTD & ThermistorCalibrators & Ice Point ReferencesRecorders, Controllers & Process MonitorsInfrared PyrometersPRESS U RE, STRAIN AND FO RC ETransducers & Strain GagesLoad Cells & Pressure GagesDisplacement TransducersInstrumentation & AccessoriesFLOW/LEVELRotameters, Gas Mass Flowmeters & Flow ComputersAir Velocity IndicatorsTurbine/Paddlewheel SystemsTotalizers & Batch ControllerspH/CONDUCTIVITYpH Electrodes, Testers & AccessoriesBenchtop/Laboratory MetersControllers, Calibrators, Simulators & PumpsIndustrial pH & Conductivity EquipmentDATA ACQUISITIONCommunications-Based Acquisition SystemsData Logging SystemsWireless Sensors, Transmitters, & ReceiversSignal ConditionersData Acquisition SoftwareHEATERSHeating CableCartridge & Strip HeatersImmersion & Band HeatersFlexible HeatersLaboratory HeatersENVIRONMENTALMONITORING AND CONTROLMetering & Control InstrumentationRefractometersPumps & TubingAir, Soil & Water MonitorsIndustrial Water & Wastewater TreatmentpH, Conductivity & Dissolved Oxygen InstrumentsM5706/1018。
NB-IOT无线红外抄表终端产品说明书

【上海数采物联网科技有限公司】无线红外抄表终端产品说明书版本:V 1.1修订记录目录1 概述 (2)2 产品特性 (4)3 微功耗工作模式 (5)3.1间隔时间模式: (5)3.2整点模式 (5)4 产品核心优势 (5)5 产品使用 (5)6 应用案例 (6)7 注意事项 (6)8 联系方式.................................................................................................. 错误!未定义书签。
1概述数采物联SC-LP-IR05无线红外抄表终端是上海数采物联网科技有限公司一款基于红外通讯,电池或太阳能电池板自供电或有线供电的通用电表燃气表抄表终端,可采集国网电表的电能数据、电压、电流、功率因数等电参数数据。
无线红外抄表终端采用GPRS / NB-IOT/LoRa通信方式,克服现场特殊环境导致的无线通信遮挡,大大简化现场部署时间和降低施工费用。
设备工作状态分为休眠、采集存储、激活上报三种状态。
可在采集数据后,自动进入低功耗状态,降低电源消耗,延长工作时间。
本终端支持各种具备红外通信接口的电表、燃气表等仪表的抄表场景,适用于电能表数据采集、智慧城市数据采集、电力监控数据采集、节能减排数据监控系统数据采集、能耗监控系统数据采集、光伏系统数据采集、智能监控数据采集、机器人数据采集、智慧安防系统数据采集、云平台系统数据采集;电能表校验检验测试台;特别适合供电局国网电表总表铅封完全封闭状态,不可开启任何封印的情况的抄表。
2产品特性采集特性●红外载波频率:38 kHz●通信波特率:1200~115200 bps,根据电能表通信参数自适应●通信距离:≤10米●通信角度:≤15度●通信角度:≤15度●红外通信协议:符合IEC62056-21(IEC1107)和DL/645标准电气特性●供电方式:电池供电/外部电源供电●可选外部供电电压:12V DC●电池容量:3.6V*38Ah●待机功耗:小于*********●工作功耗:5~*********●发射功耗:50~*********通信特性●天线类型:外置吸盘天线或胶棒天线(可选内置天线)●传输方式:GPRS/NB-IOT/LoRa可选●通信协议:默认电表数据透传,UDP通信方式,可定制其他协议●数据转发:任意公网服务器结构特性●材质:ABS塑料(外壳)●主体防护等级:IP65●主体尺寸:130mm×95mm×60mm●主体安装方式:壁挂或螺丝紧固工作环境●温度-30°C~75°C,湿度0~95%(非冷凝)存储环境●温度-40°C~90°C,湿度0~95%(非冷凝)3微功耗工作模式无线红外抄表终端通过间歇工作的方式实现省电的效果,设备大部分时间处于待机状态,仅有极小一部分电路继续工作以保持在微功耗的状态。
AT682 AT683绝缘电阻测试仪用户手册说明书

用户手册User’s GuideRev.E4固件说明:适用于主程序RevH及以上的版本AT682/AT683绝缘电阻测试仪@Instruments常州安柏精密仪器有限公司.全国免费服务热线:400-600-1217电话:*************销售服务电子邮件:*****************技术支持电子邮件:****************©2005-2020 Applent Instruments Ltd..2 AT682 683 用户手册安全须知当你发现有以下不正常情形发生,请立即终止操作并断开电源线。
立刻与安柏精密仪器销售部联系维修。
否则将会引起火灾或对操作者有潜在的触电危险。
●仪器操作异常。
●操作中仪器产生反常噪音、异味、烟或闪光。
●操作过程中,仪器产生高温或电击。
●电源线、电源开关或电源插座损坏。
●杂质或液体流入仪器。
安全信息为避免可能的电击和人身安全,请遵循以下指南进行操作。
免责声明用户在开始使用仪器前请仔细阅读以下安全信息,对于用户由于未遵守下列条款而造成的人身安全和财产损失,安柏精密仪器将不承担任何责任。
仪器接地为防止电击危险,请连接好电源地线。
不可在爆炸性气体环境使用仪器不可在易燃易爆气体、蒸汽或多灰尘的环境下使用仪器。
在此类环境使用任何电子设备,都是对人身安全的冒险。
不可打开仪器外壳非专业维护人员不可打开仪器外壳,以试图维修仪器。
仪器在关机后一段时间内仍存在未释放干净的电荷,这可能对人身造成电击危险。
不要使用已经损坏的仪器如果仪器已经损害,其危险将不可预知。
请断开电源线,不可再使用,也不要试图自行维修。
不要使用工作异常的仪器如果仪器工作不正常,其危险不可预知,请断开电源线,不可再使用,也不要试图自行维修。
不要超出本说明书指定的方式使用仪器超出范围,仪器所提供的保护措施将失效。
3有限担保和责任范围有限担保和责任范围常州安柏精密仪器有限公司(以下简称Applent)保证您购买的每一台AT682/683在质量和计量上都是完全合格的。
伯乐酶标仪680使用说明操作规程生物化工公司

伯乐酶标仪680使用说明操作规程检验数据管理(通用模式)是整个系统中最重要的作业,实验几乎有90%以上的工作都在这里完成,它可以录入样本的基本信息,标本相关信息,检验相关信息,同时可新增删除标本,项目检验结果,打印报告单(批次和非批次),这些功能正是检验的日常工作,故系统尽量使此项作业做到便捷、快速。
a.画面说明:如右图画面左边为样本资料、标本资料、检验环境记录资料等的录入区;画面左下方为仪器通讯消息区和收费情况显示区域,显示仪器通讯消息,包括接收到每一笔标本或检验项目或错误信息和收费明细等等;画面右边为检验结果区,显示当前标本的所有检验项目和结果以及项目数。
b.样本等资料录入:在左边区域内录入样本等信息,对于当前标本样本类型、性别、收费类型、标本类型、科室、医生、备注等信息的录入,可在该字段上鼠标双击即可弹出窗口列出所有资料用户选择,若输入错误系统也会自动弹出列表窗口;切换输入字段可以通过回车键、TAB键、上下键,也可以通过鼠标点击直接切换;对应输入法的切换,如果系统设置中设置输入法自动切换那么在光标落入备注和样本姓名字段时,系统自动切换为中文输入法,其他字段自动切换为英文输入法;至于有些字段不需要录入或设定默认值在“设置”->“输入字段设置” 中已经提过;c.[打印]:打印当前标本的报告单只需要按下打印按钮或F6快捷键即可,若要批次打印某一天的标本可以选择菜单:“日常作业”->“检验结果批次打印”。
d.检验结果查看:画面右边显示当前标本的检验结果,单列显示时包括项目代号、结果和参考值,一屏可显示约24行,对于阳性或超过参考上限的结果,系统用红色表示,反之小于参考下限的结果,系统用蓝色表示,正常结果一律黑色表示。
e.[新增项目]、[修改项目]:修改某项目的检验结果或新增某一检验项目结果.f.[删除项目]:删除一检验项目结果g.切换日期:进入日常作业后,系统显示的是当天的标本资料,若想查看其它日期资料,需要按下标本日期后?按钮,弹出日历窗口由用户选择日期,确定后切换到那一天的工作状态,不过当日常作业上标本为非今日标本时,日常作业画面的底色变为绿色(本来为灰色),以提示这不是今天的标本,防止用户操作错误。
数据采集传输仪

485-信号线。RS232 采用 9 针接口,2 针和 3 针交叉连接,5 针直连。
注意:连接之前务必关闭各仪器电源。
电源连接
使用电源线连接数采仪的电源输入口( )和交流电源插座。
开机与关机
使用数采仪前面板上的电源开关按钮( ),按动一次开机,再次按动则 关机,当可能受到干扰或危险的情况下,请不要开机。
概要
模拟量输入 数字量输入 数字量输出 A/D 分辨率
操作方式 供电方式
功耗 外形尺寸 工作温度 工作湿度 储存温度
接线端子 1路 全双工 10~100Mbit/s HJ/T 212、Modbus TCP/IP RJ45
0/4~20mA 电平信号 触点信号、 16 位 本地/远程操作 220VAC 15W(最小) 450×430×175(mm) -40~70℃ 5~95%RH -50~80℃
-1-
在潮湿、霉菌滋生地安装 接地良好,要求接地电阻小于 4 欧姆
E6803 数据采集传输仪
与其他被采集数据仪器的连接要求 不正常的仪器会影响数据数采仪的正常工作,确保被采集仪器工作正常 如确认被采集仪器干扰或损坏数采仪,则选配 232 隔离器 现场有的配有流量计,因流量计的探头线较长,容易引入干扰,必须把 流量计探头线屏蔽层接地,要求接地良好,有条件可穿铁管,铁管接地, 接地同样要求良好
E6803 数据采集传输仪 使用说明书
目录
使用入门 .......................................................................................................................1 数采仪概述 ...................................................................................................................2 操作说明 .......................................................................................................................3
Omega 数据记录仪产品说明书

To Order, Call
or Shop Online at SM
1
OM-CP-IFC200, Windows® software displays data in graphical or tabular format.
Real Time Recording: The device may be used with PC to monitor and record data in real-time
Memory: 1,000,000 readings; software configurable memory wrap; 330,000 readings in multiple start/stop
Wrap Around: Yes
Start Modes: • Immediate start • Delay start up to 24 months • Multiple pushbutton start/stop
Specifications
DATA LOGGER
Measurement Range:
Dry: 266 mV typical 100% Saturated: 833 mV typical
Resolution: 50 µV
Accuracy: ±0.1 mV
Specified Accuracy: Nominal range @ 25ºC
LED Functionality: Green LED Blinks: 10 second
rate to indicate logging, 15 second rate to indicate delay start mode
Red LED Blinks: 10 second rate to indicate low battery and/or full memory, 1 second rate to indicate an alarm condition
奥米科技 USB温度 电压输入数据采集模块产品说明书

languages, and other languages, including DASYLab®, and ULx for NI LabVIEW® (comprehensive library of
Eight independent, TTL-compatible digital I/O channels are provided to monitor TTL-level inputs, communicate with external devices and to generate alarms. The digital I/O channels are software programmable for input or output.
The OM-USB-TEMP and OM-USB-5203 provide eight differential temperature input channels. The OM-USB-TEMP-AI provides eight analog input channels that are configured as four differential temperature inputs and four differential or single-ended voltage inputs.
Software Triggering
No Yes
Hardware Triggering
No Yes
Time-of-Day Triggering
No Yes
Linear Scaling No Yes
2021年型数据采集系统使用说明 图文

2021年型数据采集系统使用说明图文____型数据采集系统使用说明书长沙军麟仪器设备有限公司1目录第一章软件使用说明 ................................................................... ....................................................... 1 1.1. 传感器率定 ................................................................... .......................................................... 1 1.1.1 1.1.2 1.1.3 1.1.4 1.1.5 1.1.6 1.2.1 1.2.2 1.2.3 1.2.4 1.2.5 1.2.6 1.2.7 1.2.8 1.2.9 1.2.10 1.2.11 1.3.1 1.3.2 1.3.3 1.3.4类型选择 ................................................................... ...................................................... 1 配置传感器 ................................................................... .................................................. 1 打开设备 ................................................................... ...................................................... 2 读入数据 ................................................................... ...................................................... 2 率定 ................................................................... .............................................................. 3 性能测试 ................................................................... ...................................................... 3 配置传感器 ................................................................... .................................................. 4 采样设置 ................................................................... ...................................................... 6 输入文件名 ................................................................... .................................................. 6 打开设备 ................................................................... ...................................................... 6 更换显示通道 ................................................................... .............................................. 7 数据采集 ................................................................... ...................................................... 7 立即采集 ................................................................... ...................................................... 7 分开与合并显示 ................................................................... .......................................... 8 定零与定位 ................................................................... .................................................. 8 更改量程 ................................................................... .................................................. 8 针对传感器温漂的解决方案 ................................................................... .................. 9 压力传感器数据 ................................................................... ........................................ 10 波高传感器数据 ................................................................... ........................................ 13 总力传感器数据 ........................................................................................................... 18 位移传感器数据 ................................................................... . (18)1.2. 数据采集模块 ................................................................... (4)1.3. 数据处理 ................................................................... (10)第二章系统必备、驱动安装及注意事项 ................................................................... ................... 18 2.1. 2.2.软件安装必备 ................................................................... .................................................... 18 硬件必备 ................................................................... (19)2.3. 采集仪驱动安装 ................................................................... ................................................ 19 2.4. 传感器安装 ................................................................... ........................................................ 24 2.5. 使用注意事项 ................................................................... .................................................... 25 2.6. 技术支持 ................................................................... (25)2第一章软件使用说明____型数据采集系统包括传感器率定、数据采集和数据处理三个部分,其中传感器率定模块支持对传感器精度的验证、数据采集模块可对接入本系统的传感器进行图形监视和数据采集,数据处理模块则是针对采集到的数据进行统计分析等。
A4300 VA3 Pro Ex 三通道振动分析仪数据收集器与平衡仪说明书

MASTER THE LANGUAGE OF YOUR MACHINERYA4300 VA3 P RO E XI NTRINSICALLY S AFE3-CHANNEL VIBRATION ANALYZERDATA COLLECTOR, BALANCER AND MUCH MORE...MASTER THE LANGUAGE OF YOUR MACHINERY2A4300 VA3 Pro Ex3-CHANNEL ANALYZERThe A4300 VA3 Pro Ex is the newest addition to our range of portable devices for vibration diagnostics and machine balancing.There are 2 signal inputs and 1 tacho/trigger input. Input 2 offers connectivity to a triaxialsensor, therefore all 3 channels can be measured simultaneously. The expert system developed by Adash can automatically detect machine faults such as unbalance, looseness, misalignment and bearing faults.There is a non-contact IR temperature sensor(forimmediate bearing temperature measurement) and a LED stroboscope/torch.The A4300 VA3Pro Ex is designed forone- handed operation. With aweight of just 760g and a battery life of more than 6 hours of operation, the unit is suitable forlong route measurements. The A4300 VA3 Pro Ex instrument can be confi gured according to your requirements by choosing optional modules: analyzer, route,balancer, recorder, run up or ultrasound. Optional modules can be purchased also additionally anddownloaded to the instrument without the need of sending it back to the factory.>Low weight 760 g >Long lasting battery >Ideal for route measurement >Machine balancingIncludes stroboscope and temperature sensorAnalyzer Route Stroboscope FASIT Balancer Meter Recorder Run Up UltrasoundII 3G ex ic op is IIC T3 Gc3TOP PANELA/D CONVERSIONIDEAL FOR ROUTE MEASUREMENTDATA PROCESSING›ACC ICP ® - sensor input›Input IN2 is ready for triaxial sensor (3 simultaneous channels)›Input for tacho/trigger›IR non-contact temperature sensor ›LED stroboscope/torch ›Mini USB for data transfer›24 Bit A/D conversion ›64 Bit signal processing ›120 dB dynamic range›AutoGain function is not necessary›Heavy-Duty aluminium case ›Li-Ion battery pack›More than 6 hours of operation ›Colour display 240 x 320 px ›FFT resolution: 25 600 lines ›Route memory: 8 G B›Real time FFT›DEMOD - ENVELOPE analysis ›ACMT - low speed bearing analysis ›Order analysis›User band pass analysis ›RPM measurement ›DC measurement ›Orbit measurementMEASUREMENTSAnalyzer BalancerExpert system Time signalMASTER THE LANGUAGE OF YOUR MACHINERYAdash, spol. s r.o.Hlubinska 1379/32702 00 Ostrava Czech Republic e-mail:**************© Adash 2023Input channels:3 AC, ICP ® power supply on/off 3 DC for process values 1 TACHO for external trigger Input range:AC +/- 12 V peak-peak DC +/- 24VAD conversion:24 bit, 64 bit internal signal processing AutoGain function is not necessary!Dynamic range S/N:120 dBFrequency ranges (-3 dB):Maximum range: 0.5 Hz - 25 kHz (64 kHz sampling)Minimum range: 0.5 Hz - 25 Hz (64 Hz sampling)Sampling mode:Fully simultaneous for 3 channels FFT resolution:Min. 25 linesMax. 25 600 linesUnit modes:Analyzer - analytic measurement Data collector - route measurement Balancer Recorder Run Up UltrasoundLED stroboscope, LED torchFASIT - Expert system for fault detection Vibration meterData processing:Real time FFTDEMOD - ENVELOPE analysis ACMT - low speed bearing analysis Order analysisUser band pass analysis RPM measurement DC measurement Orbit measurementIR temperature measurement:Range -70˚C to +380˚C (-94˚F to +716˚F)Trigger:Manual, External, Amplitude, T acho - Ex ia op is IIC T4 Ga Display:Colour 240 x 320 pixels, TFT Communication:USBOperating temperature range:-10˚C to +50˚C (with tacho probe +40˚C)Power:Battery 6 hours of operation, AC 100 V - 230 V Case:Aluminium heavy duty Weight:760 gDimensions:230 x 82 x 32 mmTECHNICAL SPECIFICATIONS:II 3G ex ic op is IIC T3 Gc。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
卓越品质
★ 满足HJ477-2009标准,通过中国环境监测总站适用性测试, 获得国家环境保护产品认证★ “5S ”生产管理,全过程的品质控制★ EMC 测试,达到电子产品标准3级以上
★ 优选元器件供货商,严格控制每个元器件的采购★
“三防”测试、防雷测试、振动测试、软件压力测试★ 高低温测试,达到工业级标准-10℃~+60℃★ 稳定的ARM 技术、嵌入式Linux 操作系统
易操作、易维护
★ 触摸屏完成所有配置工作
★ 标准工业信号端口,具备良好的兼容性★ 组态界面,配置简易灵活
★ 软、硬件模块化设计,方便二次开发
★ 内置WEB ,远程升级、远程操作、远程维护
★ 支持增值业务开发,可实现运维管理的考勤、考核、统计、 分析、诊断功能
卓越品质 源于更高要求
E6803型数据采集传输仪是北京安控科技股份有限公司为环境在线监测系统定制的专业数据采集和传输设备,拥有完整的软、硬件自主知识产权,兼容国内主流厂商的系统平台和监测仪器,并已在环境在线监测行业得到大规模应用。
安控科技根据多年工业现场控制工程实施的经验,将恶劣工业环境下的数据采集设备引入到环境在线监测领域,为环保行业提供性能卓越的数据采集传输产品。
E6803
数据采集传输仪
数采仪第一品牌
技术参数
专业的研发队伍,支持的内容涵盖标准研究、软硬
件设计、工业过程控制
专业的服务队伍,包括售前支持、过程支持、售后服务
拥有完善的备品备件供货体系,保障设备的正常运行提供技术开发服务、OEM 合作
可编程控制器采用32位高速ARM9微处理器、嵌入Linux 操作系统
支持污染源传输标准HJ/T212-2005及 Modbus 协议,内置主流仪器厂商和平台系统传输协议,屏幕设置即可使用
支持IEC61131-3的5种标准的编程语言,方便用户的二次开发。
包括梯形图(LD )、功能块图(FBD )、顺序功能图(SFC )、指令表(IL)和结构化文本 (ST)
64M 程序空间、128M FLASH 存储器(可扩展2G )
、USB 接口可导出历史数据
8-12路AI (4~20mA ,1~5V ,16位分辨率)
、8路DI (0~5V )
、4路DO (AC250V1A 触点信号)、5个RS232(或RS485)
,1个以太网口可选通讯模式包括RS232/485、Ethernet ,选配无线传输模块,支持GPRS/CDMA
支持一点多传,满足多平台接收数据需求支持采集数据视频图像叠加功能
支持IE 浏览器远程查询现场仪表数据、参数和工作状态
企业工况数据信息的采集、监控和管理
抗外界干扰能力强,防止电磁干扰、雷击等外界环境因素对设备的损坏
具有断电保护功能,数据存储保留时间大于10年软/硬件看门狗功能,保证系统运行稳定可靠