Eaton 198885
Eaton Moeller® series Rapid Link - Speed controllers, 4.3 A, 1.5 kW, Sensor input 4, Actuator output 2, 180/207 V DC, Ethernet IP, HAN Q4/2, with manual override switch
Allgemeine spezifikation
Eaton Moeller® series Rapid Link Speed controller
198885157 mm
270 mm 220 mm 3.59 kg
RoHS
IEC/EN 61800-5-1 UL approval CE UL 61800-5-1
4015081969432RASP5-4421EIP-412R000S1
Product Name
Catalog Number
Product Length/Depth Product Height Product Width Product Weight Certifications Catalog Notes EAN
Model Code
3 fixed speeds and 1 potentiometer speed
can be switched over from U/f to (vector) speed control Connection of supply voltage via adapter cable on round or flexible busbar junction
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus
Parameterization: Keypad
Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation
Selector switch (Positions: REV - OFF - FWD)
Thermo-click with safe isolation
Key switch position AUTO
Key switch position OFF/RESET
Key switch position HAND
IGBT inverter
PTC thermistor monitoring
Control unit
Internal DC link
PC connection
Manual override switch
2 Actuator outputs
1 potentiometer speed
For actuation of motors with mechanical brake
3 fixed speeds NEMA 12
IP65
1st and 2nd environments (according to EN 61800-3)
III
Speed controller
EtherNet/IP
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: for conducted emissions only
2000 V
AC voltage
Center-point earthed star network (TN-S network)
Phase-earthed AC supply systems are not permitted.
Vertical
15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms, Half-sinusoidal shock 11 ms, 1000 shocks per shaft
Resistance: 6 Hz, Amplitude 0.15 mm
Resistance: 10 - 150 Hz, Oscillation frequency
Resistance: According to IEC/EN 60068-2-6
Resistance: 57 Hz, Amplitude transition frequency on acceleration Max. 2000 m
Above 1000 m with 1 % performance reduction per 100 m -10 °C
40 °C
-40 °C
70 °C
Features Fitted with:
Functions Degree of protection
Electromagnetic compatibility Overvoltage category
Product category
Protocol
Radio interference class
Rated impulse withstand voltage (Uimp) System configuration type
Mounting position Shock resistance Vibration Altitude
Ambient operating temperature - min Ambient operating temperature - max Ambient storage temperature - min Ambient storage temperature - max Climatic proofing
< 95 %, no condensation
In accordance with IEC/EN 50178
Current limitation
0.4 - 4.3 A, motor, main circuit
Adjustable, motor, main circuit
Delay time
< 10 ms, On-delay
< 10 ms, Off-delay
Efficiency
98 % (η)
Input current ILN at 150% overload
4.1 A
Leakage current at ground IPE - max
3.5 mA
Mains current distortion
120 %
Mains switch-on frequency
Maximum of one time every 60 seconds
Mains voltage - min
380 V
Mains voltage - max
480 V
Mains voltage tolerance
380 - 480 V (-10 %/+10 %, at 50/60 Hz)
Operating mode
PM and LSPM motors
U/f control
BLDC motors
Synchronous reluctance motors
Sensorless vector control (SLV)
Output frequency - min
0 Hz
Output frequency - max
500 Hz
Overload current
For 60 s every 600 s
At 40 °C
Overload current IL at 150% overload
6.5 A
45 Hz
66 Hz
1.5 kW
480 V AC, 3-phase
400 V AC, 3-phase
0.1 Hz (Frequency resolution, setpoint value)
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
50/60 Hz
8 kHz, 4 - 32 kHz adjustable, fPWM, Power section, Main circuit
AC voltage
Center-point earthed star network (TN-S network)
Phase-earthed AC supply systems are not permitted.2 HP
≤ 0.6 A (max. 6 A for 120 ms), Actuator for external motor brake
≤ 30 % (I/Ie)
Adjustable to 100 % (I/Ie), DC - Main circuit
280/207 V DC -15 % / +10 %, Actuator for external motor brake
10 kA
Type 1 coordination via the power bus' feeder unit, Main circuit
24 V DC (-15 %/+20 %, external via AS-Interface® plug)
180/207 V DC (external brake 50/60 Hz)
Ethernet IP, built in
Plug type: HAN Q4/2
Number of slave addresses: 31 (AS-Interface®)
Max. total power consumption from AS-Interface® power supply unit (30 V): 250 mA
Specification: S-7.4 (AS-Interface®)C1 ≤ 1 m, maximum motor cable length C2 ≤ 5 m, maximum motor cable length C3 ≤ 25 m, maximum motor cable length
Meets the product standard's requirements.
Rated frequency - min
Rated frequency - max
Rated operational power at 380/400 V, 50 Hz, 3-phase Rated operational voltage
Resolution
Starting current - max
Supply frequency
Switching frequency
System configuration type Assigned motor power at 460/480 V, 60 Hz, 3-phase Braking current
Braking torque
Braking voltage
Rated conditional short-circuit current (Iq)
Short-circuit protection (external output circuits) Rated control voltage (Uc)
Communication interface
Connection
Interfaces
Cable length
10.2.2 Corrosion resistance
Meets the product standard's requirements.
Meets the product standard's requirements.
Meets the product standard's requirements.
Meets the product standard's requirements.
Does not apply, since the entire switchgear needs to be evaluated.
Does not apply, since the entire switchgear needs to be evaluated.
Meets the product standard's requirements.
Does not apply, since the entire switchgear needs to be evaluated.
Meets the product standard's requirements.
Does not apply, since the entire switchgear needs to be evaluated.
Does not apply, since the entire switchgear needs to be evaluated.
Is the panel builder's responsibility.
Is the panel builder's responsibility.
Is the panel builder's responsibility.
Is the panel builder's responsibility.
Is the panel builder's responsibility.Anschluss von Frequenzumrichtern an Generatornetze Configuration to Rockwell PLC Rapid Link 5
Configuration to Rockwell PLC for Rapid Link Generationentausch RA-MO zu RAMO4.0 Generationentausch RA-SP zu RASP4.0
Generation change from RA-SP to RASP 4.0
Generation Change RASP4 to RASP5
Generation Change RA-SP to RASP5
Generationenwechsel RA-SP zu RASP5
Generationswechsel RASP4 zu RASP5
Generation change from RA-MO to RAMO 4.0 Elektromagnetische Verträglichkeit (EMV)
Firmware Update RASP 4.0
Generation change RAMO4 to RAMO5
Generationentausch RAMO4 zu RAMO5
MN034004_DE
MN040003_DE
Rapid Link 5 - brochure
DA-SW-drivesConnect - installation help
DA-SW-Driver DX-CBL-PC-3M0
DA-SW-drivesConnect - Installationshilfe
DA-SW-USB Driver DX-COM-STICK3-KIT
DA-SW-USB Driver PC Cable DX-CBL-PC-1M5
DA-SW-drivesConnect
Material handling applications - airports, warehouses and intra-logistics ETN.RASP5-4421EIP-412R000S1.edz
IL034093ZU
DE | Rapid Link 5
Sortimentskatalog Antriebstechnik-DE
10.2.3.1 Verification of thermal stability of enclosures
10.2.3.2 Verification of resistance of insulating materials to normal heat
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
10.2.4 Resistance to ultra-violet (UV) radiation
10.2.5 Lifting
10.2.6 Mechanical impact
10.2.7 Inscriptions
10.3 Degree of protection of assemblies
10.4 Clearances and creepage distances
10.5 Protection against electric shock
10.6 Incorporation of switching devices and components
10.7 Internal electrical circuits and connections
10.8 Connections for external conductors
10.9.2 Power-frequency electric strength
10.9.3 Impulse withstand voltage
10.9.4 Testing of enclosures made of insulating material Anmerkungen zur Anwendung
Benutzerhandbücher
Broschüren
eCAD model Installationsanleitung Installationsvideos
Kataloge
Eaton Konzern plc Eaton-Haus
30 Pembroke-Straße Dublin 4, Irland
© 2023 Eaton. Alle Rechte vorbehalten. Eaton ist eine eingetragene
Marke.
Alle anderen Warenzeichen sind
Eigentum ihrer jeweiligen
Besitzer.
/socialmedia
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.ramo5_v31.dwg
rasp5_v31.stp
eaton-bus-adapter-rapidlink-speed-controller-dimensions-003.eps eaton-bus-adapter-rapidlink-speed-controller-dimensions-004.eps eaton-bus-adapter-rapidlink-speed-controller-dimensions-002.eps eaton-bus-adapter-rapidlink-speed-controller-dimensions-005.eps
10.10 Temperature rise
10.11 Short-circuit rating
10.12 Electromagnetic compatibility 10.13 Mechanical function mCAD model Zeichnungen。