EconoPlus电炉系列100、200和300安装说明书
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
ECONOPLUS ELECTRIC
FURNACE
SERIES 100
Models 115, 118 & 119
SERIES 200
Models 215, 218 & 219
SERIES 300
Model 315, 318, 319 & 323
Rev : June 2009
Econoplus Series 100, 200 and 300 ELECTRIC FURNACES
INSTALLATION INSTRUCTIONS – HOMEOWNER’S MANUAL
1.0Scope and general instructions
1.1Installer and service technician
Use this installation guide for the initial set-up of the furnace and for subsequent service and maintenance. Keep this document near the unit for easy reference.
1.2Homeowner
This guide details the different modes of operation of your unit. Please read this guide after the initial installation by your installer and keep it handy afterward for future reference.
1.3Models covered and description
•Series 100
The 100 series is the basic electric furnace. These furnaces are factory assembled for operation with a single stage or standard thermostat. They also have a cooling relay factory installed to enable high speed operation when coupled with an air conditioning unit at 0.5’’W.C. (Suffix C).
Model Econoplus KW Total
Amps
Volts
(V/Hz/Ph)
Motor
(HP)
Motor
Speed
Static
Pressure (‘’W.C.)
CFM ΔT
(o F)
115 15 64.4 240/60/1 ¼ - 240 Med. 0.2 925 51 115-C 15 64.8 240/60/1 ¼ - 240 High 0.5 1050 45 118 18 76.9 240/60/1 ¼ - 240 Med. 0.2 925 59 118-C 18 77.3 240/60/1 ¼ - 240 High 0.5 1050 52 119 19 78.4 240/60/1 ¼ - 240 Med. 0.2 925 63 119-C 19 78.8 240/60/1 ¼ - 240 High 0.5 1050 65 Table 1 – Series 100 characteristics
•Series 200
The 200 series is the same basic electric furnace with more functional options. These furnaces are factory assembled for operation with a 1, 2 or 3 stages thermostat. When used with a multi-stage thermostat the unit will modulate its power depending on the stage calling for heat. The furnace is factory assembled with a three positions switch to manually choose the level of heat if installed with a one stage thermostat. The intermediate modes of heating are detailed in tables 2 and 3 and explained later in this guide. The Series 200 also comes with a low speed fan switch that enables operation of the lowest speed of the motor for continuous ventilation when needed. The Series 200 also has a cooling relay to permit high speed operation when matched with an air conditioning unit. Suffix C indicates operation at 0.5” W.C. at high speed.
•Series 300
Series 300 has the same functionality of series 200 while being equipped with a 120V motor-blower combination. This series also comes with, as standard equipment, a 120V terminal strip enabling connection
of additional equipment such as electronic air filter and/or humidifier. Finally, this series has insulating wool in the blower compartment. As in series 100 and 200, suffix C indicates operation at 0.5’’ W.C. at high speed. Series 300 features an extended capacity with the addition of a 23 KWatt model. Please note that the 23 KWatt model is ONLY offered on Series 300. Finally, Series 300 is also offered with a 1/2HP ECM motor as optional equipment. This motor is a high efficiency (up to 80%) motor that is fully compatible with the standard control scheme of the furnace. ECM models are identified with the ECM suffix.
Model Econoplus KW Total
Amps
Volts
(V/Hz/Ph)
Motor
(HP)
Motor
Speed
Static
Pressure (“ W.C.)
CFM ΔT
(o F)
215 @ 5KW 5 22.6 240/60/1 ¼ - 240 Lo 0.2 750 21 215 @ 10KW 10 43.5 240/60/1 ¼ - 240 Lo 0.2 750 42 215 15 64.4 240/60/1 ¼ - 240 Med. 0.2 925 51 215-C 15 64.8 240/60/1 ¼ - 240 High 0.5 1050 45 218 @ 9KW 9 39.3 240/60/1 ¼ - 240 Lo 0.2 750 38 218 @ 13KW 13 56 240/60/1 ¼ - 240 Med. 0.2 925 44 218 18 76.9 240/60/1 ¼ - 240 Med. 0.2 925 59 218-C 18 77.3 240/60/1 ¼ - 240 High 0.5 1050 52 219 @ 9KW 9 39.3 240/60/1 ¼ - 240 Lo 0.2 750 38 219 @ 14KW 14 60.1 240/60/1 ¼ - 240 Med. 0.2 925 48 219 19 78.4 240/60/1 ¼ - 240 Med. 0.2 925 63 219-C 19 78.8 240/60/1 ¼ - 240 High 0.5 1050 55 Table 2 – Series 200 characteristics
Model Econoplus KW Total
Amps
Volts
(V/Hz/Ph)
Motor
(HP)
Motor
Speed
Static
Pressure (“ W.C.)
CFM ΔT
(o F)
315 @ 5KW 5 25.8 240/60/1 1/3 - 120 Lo 0.2 750 21 315 @ 10KW 10 46.7 240/60/1 1/3 - 120 Lo 0.2 750 42 315 15 67.6 240/60/1 1/3 - 120 Med. 0.2 1020 47 315-C 15 68.6 240/60/1 1/3 - 120 High 0.5 1150 41 318 @ 9KW 9 42.5 240/60/1 1/3 - 120 Lo 0.2 750 38 318 @ 13KW 13 59.2 240/60/1 1/3 - 120 Med. 0.2 1020 41 318 18 77.5 240/60/1 1/3 - 120 Med. 0.2 1020 54 318-C 18 78.5 240/60/1 1/3 - 120 High 0.5 1150 48 319 @ 9KW 9 42.5 240/60/1 1/3 - 120 Lo 0.2 750 38 319 @ 14KW 14 63.3 240/60/1 1/3 - 120 Med. 0.2 1020 43 319 19 82.1 240/60/1 1/3 - 120 Med. 0.2 1020 58 319-C 19 83.1 240/60/1 1/3 - 120 High 0.5 1150 51 323 @ 10KW 10 46.7 240/60/1 1/3 - 120 Lo 0.2 750 42 323 @ 18KW 18 77.5 240/60/1 1/3 - 120 Med. 0.2 1020 54 323 23 99.0 240/60/1 1/3 - 120 Med. 0.2 1020 70 323-C 23 100.0 240/60/1 1/3 - 120 High 0.5 1150 62 323ECM @ 10KW 10 46.7 240/60/1 ½ - 120 E Lo 0.2 650 49 323ECM @ 18KW 18 77.5 240/60/1 ½ - 120 E Med. 0.2 1230 47 323ECM 23 96.2 240/60/1 ½ - 120 E Med. 0.2 1230 58 323ECM-C 23 96.9 240/60/1 ½ - 120 E High 0.5 1280 56 Table 3 – Series 300 characteristics
2.0 Important safety information
• WARNING – BASIC SAFETY WARNINGS
The initial electrical connection and subsequent service MUST be done by a qualified electrician in accordance with this manual AND ELECTRICAL CODES HAVING JURISDICTION IN YOUR AREA .
This unit is intended and approved for use with heating ducts. Use without ducts will result in untested operation that could result in property damage, accident or DEATH.
Disconnect power to the unit before doing any service on the unit. The type of voltage and current used in this furnace are enough to cause serious injury and/or DEATH.
This furnace is not approved or intended for use outside. Use outside voids the warranty.
Do not store gasoline, fuel or any flammable substances near the furnace.
Ask the installer to show you the location of the main disconnect breaker of the furnace.
WARNING – BEST PRACTICES FOR OPTIMAL OPERATION
Make sure that the air filter is always clean and in good working condition and not overly obstructed. An obstructed air filter will result in reduced air flow and higher outlet temperature. Continued operation WITH THE FILTER CLOGGED will drastically reduce the life of the heating elements.
The unit must be inspected once a year by a qualified technician.
Make sure that you have enough clearance in the front and the rear of the unit for service and maintenance. Although the unit is approved for zero clearance on these panels, it is definitely NOT a good practice to do it.
3.0 Installation of the furnace
The return air/ inlet connection is made on the rear of the unit and the supply plenum is connected in the front of the unit. The flanges supplied with the cabinet are 19” X 19” and can accommodate plenums of that size. The cabinet is also large enough so 20” X 20” supply plenums could be attached directly on the furnace. See Figure 1 for details. The unit is approved for installation with zero clearance on all parts of the cabinet including the floor (combustible floor) and also with zero clearance on the walls of the supply plenum. The unit can be installed directly on the floor, on the adjustable legs (included) or suspended to the ceiling with “plumber” straps. Please see figure 2A, 2B and 2C for the different installation configurations. Make sure to leave sufficient clearance in the front of the unit for the electrical connections and electrical service and in the rear of the unit for blower and motor maintenance and service. Please note that the air filter rack can be installed on the right or left side of the unit in addition to the rear (factory position). To change the filter rack position, refer to fig. 3.
Supply Air Plenum Return Air Plenum
Front of furnace
Floor (Combustible floor approved)
Figure 1 Figure 2A
Also note that the blower in the rear compartment can be removed by loosening the 4 wing nuts (figure 3) that hold it to the blower supports. The wire is long enough so you can remove the blower from the unit without disconnecting it. CAUTION: when removing the blower, DO NOT remove the blower legs. Loosen the 4 wing nuts and slide the blower out. To replace the blower, position the studs in the slots on the blower legs and fully insert the blower. Be sure to RETIGHTEN the wings nuts after reinstalling the blower. Consult figure 4 for details.
4.0 Electrical connection to the furnace
4.1 240VAC – High voltage
You only need to bring a 2 conductors wire + ground to the furnace for the series 100 and 200 and a 3 All other wiring is factory installed/connected. Consult the local electrical codes for the size of the conductors
grounding of the unit. The use of copper wires is
If aluminum wire is used, make sure to
terminal block in the furnace to accommodate a wire coming from the left or right. The factory position is on the right side. Knock-outs are
reconnect the internal wires to the block. To do this, Wing Nuts Installed with the mounting legs supplied as standard equipment. See the mounting procedure at the end of this manual Alternate filter rack position Factory designed 240V connection connection
Alternate 240V
Wiring connection Rotate the connection Block for alternate wiring direction Figure 2B Figure 2C
Figure 3 Figure 4 Figure 5 ( model 115 shown)
consult the electrical diagrams in the following pages. THIS CAN ONLY BE DONE BY A QUALIFIED TECHNICIAN AND/OR ELECTRICIAN. Fig.5 above shows the different possible configurations.
4.2 24VAC – Low voltage (Thermostat and controls) All 24VAC connections are done on the left portion of the upper front panel on the 8 positions magnum style terminal (recessed and accessible by removing the 2 screws on the small access panel). The terminology used is the standard HVAC terminology. Please refer to figure 6. Please note that Rc and Rh (together) and W1, W2 and W3
(together) are jumped at the factory. The unit is factory wired for a
1 stage thermostat. No low voltage connections are needed INSIDE
the electrical panel. Make sure to adjust the thermostat heat
anticipator to its maximum value or ‘’LONGER’’ as often referred.
Please note that the following controls schemes are possible with the ECONOPLUS furnace:
• Fig. 7A: Heating only with a standard 1 stage thermostat;
• Fig. 7B: Heating only with a one stage thermostat AND an outside sensor;
• Fig. 7C: Heating only with a 2 stages thermostat AND an outside sensor;
• Fig. 7D: Heating only with a one stage thermostat AND two outside sensors;
• Fig. 7E: Heating and cooling with a standard heating-cooling thermostat;
• Fig. 7F: Heating and cooling with a heating-cooling thermostat AND one outside sensor;
• Fig. 7G: Heating and cooling with a heating-cooling thermostat AND 2 outside sensors.
Control schemes illustrated on Figures 7C, 7D and 7G are exclusive to the ECONOPLUS furnaces.
4.3 Electrical diagrams
The electrical diagrams are available on the following figures:
• Econoplus 115: Figure 8 - Econoplus 118 and 119: Figure 9
• Econoplus 215: Figure 10 - Econoplus 218 and 219: Figure 11
• Econoplus 315: Figure 12 - Econoplus 318 and 319: Figure 13 - Econoplus 323: Figure 14
4.4 120V terminal strip (Series 300 only)
All series 300 units are equipped, as standard equipment, with a
120V terminal strip as shown on figure 15. Pins 1 and 2 are live
120V connectors and pins 3 and 4 are neutral connectors. The
maximum ampacity of accessories on this terminal strip is 2A.
W W W R R G Y C
Low Speed Switch 3 Pos. Power Switch Thermostat LED
Thermostat connections Figure 6 Figure 15
120V strip
5.0 Operation modes
5.1Series 100 (models 115, 118 and 119)
On a Series 100 furnace, the operation is as follows:
Heating mode (model 115 as example):
When the thermostat is not calling for heat:
•The elements are not energized and the blower is OFF.
When the thermostat is calling for heat:
•After a delay, the blower will start at the medium speed.
•After a second delay, the first 5KW element will energize.
•After a third delay, the second and third 5KW elements will energize.
When the demand is satisfied:
•The sequence above is reversed until all elements and the blower are OFF.
Cooling mode (model 115 as example):
When the cooling thermostat is not calling for cooling:
•The elements are not energized and the blower is OFF.
When the cooling thermostat is in demand (circuit closed between Rc and G):
•The blower will start on the highest speed.
When the demand is satisfied:
•The blower will stop.
5.2Series 200 and 300 (models 215, 218, 219, 315, 318, 319 and 323)
On a Series 200 or 300 furnace, the operation depends on the position of the switches on the top front panel.
Please refer to figure 6 shown earlier for a schematic of the switches on the front panel. The LED is lighted only when there is a demand for heat (the circuit is closed between Rh and W1 or W2 or W3).
Heating mode (model 215 as example)
Low speed switch at AUTO and power switch at 5KW (lowest position):
When the thermostat is not calling for heat:
•The elements are not energized and the blower is OFF.
When the thermostat is calling for heat:
•After a delay, the blower will start on low speed.
•After a second delay, the first 5KW element will energize.
When the demand is satisfied:
•The sequence above is reversed until all elements and the blower are OFF.
Low speed switch at ON and power switch at 5KW:
When the thermostat is not calling for heat:
•The elements are not energized and the blower is on low speed.
When the thermostat is calling for heat:
•After a first delay, the first 5KW element will energize.
When the demand is satisfied:
•The sequence above is reversed until all elements are OFF. The blower keeps running on low speed.
Low speed switch at AUTO and power switch at 10KW ( highest position):
When the thermostat is not calling for heat:
•The elements are not energized and the blower is OFF.
•After a delay, the blower will start on low speed.
•After a second delay, the first 5KW element will energize.
•After a third delay, the second 5KW element will energize.
When the demand is satisfied:
•The sequence above is reversed until all elements and the blower are OFF.
Low speed switch at ON and power switch at 10KW:
When the thermostat is not calling for heat:
•The elements are not energized and the blower is on low speed.
When the thermostat is calling for heat:
•After a first delay, the first 5KW element will energize.
•After a second delay, the second 5KW element will energize.
When the demand is satisfied:
•The sequence above is reversed until all elements are OFF. The blower keeps running on low speed. Low speed switch at AUTO and power switch at 15KW ( center position):
When the thermostat is not calling for heat:
•The elements are not energized and the blower is OFF.
When the thermostat is calling for heat:
•After a delay, the blower will start at the low speed.
•After a second delay, the first 5KW element will energize.
•After a third delay, the second 5KW element will energize.
•After a fourth delay, the third 5KW element will energize AND the blower will switch to medium speed. When the demand is satisfied:
•The sequence above is reversed until all elements and the blower are OFF.
Low speed switch at ON and power switch at 15KW:
When the thermostat is not calling for heat:
•The elements are not energized and the blower is on low speed.
When the thermostat is calling for heat:
•After a first delay, the first 5KW element will energize.
•After a second delay, the second 5KW element will energize.
•After a third delay, the third 5KW element will energize AND the blower will switch on medium speed. When the demand is satisfied:
•The sequence above is reversed until all elements are OFF. The blower keeps running on low speed.
Cooling mode (model 215 as example):
Low speed switch at AUTO
When the cooling thermostat is not calling for cooling:
•The elements are not energized and the blower is OFF.
When the cooling thermostat is in demand (circuit is closed between Rc and G):
•The blower will start on the highest speed.
When the cooling demand is satisfied:
•The blower will stop.
Low speed switch at ON
When the cooling thermostat is not calling for cooling:
•The elements are not energized and the blower is on low speed.
•The blower will start at the highest speed.
When the cooling demand is satisfied:
The blower will keep running on low speed.
NOTES:
The power switch has no effect on cooling mode when there is a cooling demand from the thermostat.
If a two stage thermostat is used, remove the jumpers between W1 & W2. If a three stage thermostat is used remove the jumpers between W1 & W2 and between W2 & W3. In this mode the thermostat will automatically control the sequence between the different elements and the motor speeds. In such a case, it is imperative that the power switch be at its maximum position (center position), i.e. 15KW for model 215, 18KW for model 218 and 19KW for model 219.
In the above examples, the operation is similar for models 218, 219, 318 and 319. The three settings are, respectively, 9KW with low speed, 13KW with medium speed and 18KW with medium speed for model 218 and 319 and 9KW with low speed, 14KW with medium speed and 19KW with medium speed for model 219 and 319, 10 KW with low speed, 18 KW with medium speed and 23 KW with medium speed for model 323.
REMEMBER TO VERIFY THE POWER SWITCH POSITION WHEN TROUBLESHOOTING PROBLEMS THAT RELATE TO THE FURNACE NOT SUPPLYING ENOUGH HEAT OR WHEN MEASURING A CURRENT LOWER THAN EXPECTED.
6.0Air flow verification
After the installation, it is CRITICAL that proper air flow be verified. This is done by taking the difference of temperatures (delta T) between the inlet plenum and the supply (warm air) plenum. Take 4 or 5 measurements in the duct and calculate the average for the warm air duct. This temperature differential must be in accordance with the table in section 1.3. If the temperature difference is much higher than table 1, 2 or 3 of section 1.3 for the specified power setting, it is an indication that restriction in the heating system is much larger than normal. This might be caused by an obstruction or a clogged air filter. It is also possible that your house has an abnormally high pressure restriction. In that case it is possible to use the high speed of the blower. To do this, internal connections to the motor must be transferred from the medium speed tap to the high speed tap on the motor. Refer to the electrical diagram. It is strongly recommended that this modification be done by a qualified technician or electrician. Note the Delta T’s in the table below. This information will be very valuable when doing annual maintenance. Please note that the factory settings for the blower are:
•Series 100
o15KW, 18KW and 19KW without cooling coil (0.20” W.C.): medium speed.
o15KW, 18KW and 19KW with cooling coil (0.50” W.C.): high speed.
•Series 200 and 300
o 5 KW and 10KW power setting on Econoplus-215 and 315: low speed.
o9 KW power setting on Econoplus-218, 219, 318 and 319: low speed.
o13 KW power setting on Econoplus-218 and 318: medium speed.
o14 KW power setting on Econoplus-219 and 319: medium speed.
o15 KW power setting on Econoplus-215 and 315: medium speed.
o18 KW power setting on Econoplus-218, 318 and 323: medium speed.
o19 KW power setting on Econoplus-219 and 319: medium speed.
o23 KW power setting on Econoplus-223: medium speed.
o All models with cooling coil (0.5” W.C.): high speed.
Model Power setting Blower speed Delta T
7.0Annual maintenance
This electric furnace requires very little maintenance. Nonetheless the following points should be checked annually:
REPLACE the air filter. The model used is a standard 20” X 20” X 1” thick paper air filter found at any hardware store.
Verify the operation of the unit by having the thermostat call for heat. Re-verify the temperature differential (Delta T) between the inlet and outlet plenums. A difference from the initial installation results can be a clue to obstruction problems in the duct system if the delta T is higher but could also be a clue that one or more heating elements are faulty if the delta T is lower.
The blower motor DOES NOT require lubrication.
8.0Contact information
For information on the furnace, technical questions, sales and replacement parts information, please visit
.。