ACR系列网络多功能电力仪表安装使用说明书

合集下载

ACR系列网络电力仪表 选型手册 0905版

ACR系列网络电力仪表 选型手册 0905版

139
140
ACR
网络电力仪表
Network Power Meters
■ 应用
/
Application
application of this series of meters is very extensive and convenient for system integration, it is widely used in all the place where electric power is supplied, especially suitable for the occasion that need high requirements for power quality, power security and automation. There are much proved successful experience to apply this product in following occasions.
ACR
网络电力仪表
Network Power Meters
2. ACR系列网络电力仪表 ACR Series Network Power Meters
2.1 概 述 General
ACR网络电力仪表,是针对电力系统,工矿企业,公共设施, 智能大厦的电力监控需求而设计的.它能测量所有的常用电力参数, 如三相电流,电压,有功,无功功率,电度,谐波等.由于该电力 仪表还具备完善的通信联网功能,所以我们称之为网络电力仪表. 它非常适合于实时电力监控系统. 该表具有极高的性能价格比,可以直接取代常规电力变送器及 测量仪表.作为一种先进的智能化,数字化的前端采集元件,该系 列网络仪表已广泛应用于各种控制系统,SCADA系统和能源管理系 统中. CR Series Network Power Meters,is a intelligent meter, designed for power monitoring of Power Systems ,industrial and mining establishments,public utility ,intelligent building. It integrate all the power parameters measurement, such as three phase's current,voltage,active power ,reactive power ,electric energy, harmonic etc. So, we call it as network power meter, it is very suitable used in real time power monitoring system. ACR Series Network Power Meters have very high price performance ratio,can directly replace the general power transmitter and measurement meters. As an advanced intelligent, digital Front-end acquisition component,these meters are widely used in various control systems, SCADA system and energy source management system.

爱可信多功能网络电力仪表使用手册

爱可信多功能网络电力仪表使用手册

说明: A. 采用交流电源建议在火线一侧安装 1A 的保险丝. B. 对于临时性力品质较差的地区中, 建议在电源回路中安装浪涌抑制器防止雷击以及快
速脉冲群抑制器. 2)输入信号:ACXE 采用了每个测量通道单独采集的计算方式,保证了使用时完全一致、对称, 其具有多种接线方式,适用于不同的负载形式。 注:具体接线方式见仪表本身所带接线图 方式 1(3 个 CT):三相四线的工作方式,有中心线。
ACXEZ800B1/B2/B3/B4 电能
同上,可另带扩展功能
ACXE700C1/C2/C3/C4 四象限电能 3 排 LED 有分页显示 数字通讯,电能脉冲输出
ACXEZ800C1/C2/C3/C4
同上,可另带扩展功能
二、性能参数
性能
参数
网络
单相、三相三线、三相四线
额定值
AC 100V、220V、380V(订货时请说明)等
附录 1.MODBUS-RTU 通讯地址信息表
ACXE 多功能网络电力仪表 ACXE700A/ACXEZ800A 用户手册
一、概述
ACXE 系列产品是一种具有可编程测量、显示、数字通讯和电能脉冲输出等功能的多功
能智能仪表,能够完成电量测量、电能计量、数据显示、采集及传输,可广泛应用于变电站
自动化、配电自动化、智能建筑、企业内部电能测量、管理、考核。有功测量精度为 0.5
3
方式 2(2 个 CT):三相三线的工作方式
B.电流输入;标准额定输入电流为 5A,大于 5A 的情况应使用外部 CT。如果使用的 CT 上连 有其它仪表,接线应采用串接方式,去除产品的电流输入连线之前,一定要先断开 CT 一次回路或者短接二次回路。建议使用接线排,不要直接接入 CT ,以便于拆装。

多功能电力仪表用户手册

多功能电力仪表用户手册

多功能电力仪表用户手册一、产品简介该系列产品是一种具有可编程测量、显示、数字通讯和电能脉冲变送输出等多功能智能仪表,能够完成电量测量、电能计量、数据显示、采集及传输,可广泛应用变电站自动化、配电自动化、智能建筑、企业内部的电能测量、管理、考核。

测量精度为0.5级,实现LED 现场显示和远程RS-485数字接口通讯,采用MODBUS-RTU通讯协议。

二、技术参数三、安装与接线1.1仪表尺寸96 96X 96 91X 91 96 96 95 8080*80 76*76 80 80 90 7272*7267*677272901.2 安装方法(1)在固定配电柜开开孔尺寸大小的孔; (2)取出仪表,松开螺丝,取下固定支架; (3)仪表由前插入安装孔;(4)插入仪表固定支架,并拧紧螺丝固定仪表。

1.3 端子接线图三相四线接线图三相三线接线图(注1:尺寸不同接线方式都相同)(注2:电流线星号为进线,进出线接反,电能计量到反相电能。

)四、编程操作4. 1进入和退出编程状态进入编程状态:在测量显示状态时按住“SET ”键1秒钟,进入密码认证页面,使用“<”键,“▲”键和“▼”键输 入密码(默认用户密码为1111),再按“SET ”键就进入编程状态页面。

注意:如果输入密码按SET ”键 后,退出到测量显示状态,则表示输入密码不正确。

退出编程状态:在编程状态,一直按住“SET ”键2秒钟,退出编程状态,会提示用户选择是否保存设置值,‘yes ”保存设 置值,“no ”不保存设置值。

按“SET ”键保存,按其它键不保存。

5. 2编程操作中按键的使用功能键SET :确认设置值,进入下一项设置或退出设置。

位选键◄:循环选定要设置的数码管,选定的数码管呈闪烁状态。

增加键▲:改变闪烁位数码管的数值(数码管数值从0到9循环)。

减小键▼:改变闪烁位数码管的数值(数码管数值从9到0循环)。

6. 3设置参数说明序号序号内容说明 显示 范围UAA ----------B ----------C ----------- N ---------- |H | |1 2L NH 柞电黑甲甲甲甲甲甲甲甲甲1004 |rj 05'网UG UN [lA* 31A五、面板说明与测量信息显示2三相电流3有功功率、无功功率、功率因数4频率、第1到第4路开出信息、第1到第4路开入信息5有功电能5000K M O OV ▼ V vV A WHZ49 9 8 V AVarWh5.001 l vAPFvarh3.142 麻1009 v0952 VfHzAVarWhWHZAVarWhA PFVarhK M。

ACR200E多功能电力仪表用户手册

ACR200E多功能电力仪表用户手册

ACR网络电力仪表用户手册一、概述该系列产品是一种具有可编程测量、显示、数字通讯和电能脉冲变送输出等多功能智能仪表,能够完成电量测量、电能计量、数据显示、采集及传输,可广泛应用变电站自动化、配电自动化、智能建筑、企业内部的电能测量、管理、考核。

测量精度为0.5级,实现LCD现场显示和远程RS-485数字接口通讯,采用MODBUS-RTU通讯协议。

二、技术参数性能参数输入测电压显示网络三相三线、三相四线电压额定值AC400V过负荷持续:1.2倍瞬时:2倍/10s功耗<1V A(每相)阻抗>300kΩ精度RMS测量,精度等级0.5电流额定值AC5A过负荷持续:1.2倍瞬时:2倍/10s功耗<0.4V A(每相)阻抗<20MΩ精度RMS测量,精度等级0.5 频率40~60Hz,精度0.1Hz功能有功、无功、视在功率,精度0.5级电能四相限计量,有功精度0.5级,无功精度1级显示可编程、切换、循环的LCD显示电源工作范围AC、DC 80~270V 功耗≦5V A输出数字接口RS-485、MODBUS-RTU协议脉冲输出2路电能脉冲输出,光耦隔离环境工作环境-10~55℃储存环境-20~75℃安全耐压输入和电源>2kV,输入和输出>2kV,电源和输出>1kV 绝缘输入、输出、电源对机壳>5MΩ外形尺寸120×120 96×96(长、宽、)重量0.6kg三、安装与接线1. 安装尺寸:2. 安装方法:1)在固定的配电柜上,选择合适的地方开一个开孔尺寸的安装孔。

2)取出DCE仪表,松开定位螺丝,取下固定夹。

3)将仪表安装插入配电柜的仪表孔中。

4)插入仪表的固定夹,固定定位螺丝。

3.端子接线:注:L-N为辅助电源具体接线及仪表参数(脉冲常数等)见仪表所带接线图。

3)辅助电源:DCE系列网络电力仪表具备通用的(AC/DC)开关电源输入接口,若不作特殊声明,提供的是220V(AC/DC)或110V(AC/DC)电源接口的标准产品,仪表极限的工作电源电压为AC/DC:80-270V,请保证所提供的电源适用于该系列产品,以上防止损坏产品。

智能多功能电力仪表 ACR110EL

智能多功能电力仪表 ACR110EL

智能多功能电力仪表ACR110EL安科瑞徐孝峰江苏安科瑞电器制造有限公司江苏江阴2144051概述ACR智能多功能电力仪表是针对电力系统、工矿企业、公共设施、智能大厦的电力监控需求而设计的。

它能测量所有的常用电力参数,如三相电流、电压,有功、无功功率,电度、谐波等。

由于该电力仪表还具备完善的通信联网功能,所以我们称之为智能多功能电力仪表。

它非常适合于实时电力监控系统。

该表具有很高的性能价格比,可以直接取代常规电力变送器及测量仪表。

作为一种先进的智能化、数字化的前端采集元件,该系列网络仪表已广泛应用于各种控制系统、SCADA系统和能源管理系统中。

2产品说明2.1特点ACREL公司集多年电力测量产品设计之经验,采用现代微处理器技术和交流采样技术设计而成了该系列智能多功能电力仪表。

产品的设计充分考虑了成本效能化、智能性和可靠性,有以下特点:●可直接从电流、电压互感器接入信号;●可任意设定PT/CT变比;●仪表显示可滚动设置;●I/O开关量,继电器报警输出,4~20mA模拟量等功能模块化设计;●多块仪表可设置不同地址;●可通讯接入SCADA、PLC系统中;可与业界多种软件通讯(Intouch,Fix,Citec,组态网等);●LED或蓝屏背光LCD显示,可视度高;●方便安装,接线简单,工程量小;●仪表采用专用失电保护电路,在失电情况下,数据保存不丢失,恢复电源后,仪表继续运行;●四象限电能计量,分时计费,最大需量纪录及12个月电能统计。

2.2应用该系列智能多功能电力仪表的应用领域非常广泛而且便于系统集成,凡是有电力供应的地方都有它们的用武之地,特点是在对电力品质、电力安全有较高要求的场合以及有自动化需要的场合。

它适用于如下领域,并且已有众多成功应用经验。

●能源管理系统●变电站自动化●配电网自动化●小区电力监控●工业自动化●智能建筑●智能型配电盘、开关柜2.3功能ACREL公司集多年的专业经验,推出了智能多功能电力仪表。

PZ72L-E4安装使用说明书

PZ72L-E4安装使用说明书

仪表量程 电能清零 密码 保存
注: 1、电能清零操作需在闪动的“ ”下,按动左或右键,使其变为“ 电能清零操作不需另行保存即可生效,且不能恢复,请谨慎操作; 2、百分量是指相对于额定量程计算。
4.3 编程流程 4.3.1 正常显示界面(按动左键或右键,显示界面将按以下顺序进行切换, )
相电压
右键 左键 右键 左键
DO1 控制 (1:闭合继电器;0:分开继电器) DO2 控制 数字闪烁表示可修改,按左键选择需修改项,按右键进行修改,回车确认修改;如果需要同时 控制两路继电器,应先全部修改后,再按回车键确认。
远程读取与控制见通讯应用。 开关量输出为常开继电器;开关量输入为光耦检测,简要原理如下:
4.4.5 液晶背光控制 进入 Prog 菜单,左右键选择 LCd 页面,按回车键进入修改状态;左右键进行液晶背光时间修改 000~250s。 000:表示液晶背光常亮; 250:表示液晶背光在按键 250 秒无操作后,转入微亮状态,以延长背光使用寿命。 4.4.6 编程密码设置 进入 Prog 菜单,左键选择 PASS 页面,按回车键进入修改状态;左右键进行密码修改,密码范 围 0000~9999,回车确认修改。修改后,编程保护密码及开关量输出控制保护密码均为新密码。 默认密码:0000;万能密码:0008 4.4.7 电能的清零 进入 Prog 菜单,左键选择 CLr.E 页面,按回车键进入修改状态;按动左右键,显示将在“no”和 “YES”间切换显示;当显示为“no”按动回车键时,系统将报错显示“Err” ,提示操作未成功;若在显 示为“YES”时按动回车键,系统将进行清零操作。电能清零不需另行保存即可生效,且不能恢复,请谨 慎操作。 5、通讯指南 5.1 通讯协议概述 仪表使用 MODBUS-RTU 通讯协议,MODBUS 协议详细定义了校验码、数据序列等,这些都是特定数 据交换的必要内容。MODBUS 协议在一根通讯线上使用主从应答式连接(半双工) 。当主计算机的信 号寻址到一台唯一的终端设备(从机)后,终端设备发出应答信号传输给主机。 MODBUS 协议只允许在主机(PC,PLC 等)和终端设备之间通讯,而不允许独立的终端设备之间的 数据交换,这样各终端设备不会在它们初始化时占据通讯线路,而仅限于响应到达本机的查询信号。 5.1.1 传输方式 信息传输为异步方式,并以字节为单位,在主机和从机之间传递的通讯信息是 10 位字格式,包含 1 个起始位、8 个数据位(最小的有效位先发送) 、无奇偶校验位、1 个停止位。

ACR系列网络多功能电力仪表安装使用说明书

ACR系列网络多功能电力仪表安装使用说明书

ACR系列网络多功能电力仪表安装使用说明书目录1 概述2 产品规格3 技术参数4 安装与接线4.1 外形及安装尺寸4.2 安装方法4.3 接线方法4.4 注意事项5 编程与使用5.1 测量项目及面板说明5.2 按键功能说明5.3 操作说明5.4 编程菜单5.4.1 仪表通用编程菜单5.4.2 LCD显示仪表增加的背光控制菜单5.4.3 带开关量仪表增加菜单5.4.4 带复费率仪表增加菜单5.5 编程示例5.5.1 如何修改电流变比5.5.2 如何修改变送设置6 通讯6.1 通讯协议概述6.1.1 传输方式6.1.2信息帧格式6.2 功能码简介6.2.1功能码03H或04H:读寄存器6.2.2功能码10H:写寄存器6.2. 3功能码x8H:读电能数据6.3 通讯应用细节6.3.1开关量输入与输出6.3.2电力参数与电能6.4 通讯地址表1 概述ACR系列网络多功能电力仪表,是针对电力系统,工矿企业,公用设施,智能大厦的电力监控需求而设计的一种智能表,它集成全部电力参数的测量(如单相或者三相的电流、电压、有功功率、无功功率、视在功率、频率、功率因数)以及全面的电能计量和考核管理(如四象限电能计量和分时电能统计、最大需量记录及12月电能统计等)。

同时它具有多种外围接口功能可供用户选择:带有RS485通讯接口,采用MODBUS-RTU协议可满足通讯联网管理的需要;4-20mA的模拟量输出可与任意测量的电参量相对应,满足DCS等接口要求;带开关量输入和继电器输出可实现断路器开关的“遥信”和“遥控”的功能,采用高亮度LED/LCD显示界面,通过面板按键来实现参数设置和控制,非常适合于实时电力监控系统。

ACR系列网络电力仪表具有极高的性能价格比,可以直接取代常规电力变送器及测量仪表。

作为一种先进的智能化、数字化的前端采集元件,该电力仪表已广泛应用于各种控制系统,SCADA 系统和能源管理系统中。

2 产品规格3 技术参数4 安装与接线4.1 外形及安装开孔尺寸(单位:mm)ACR1xx系列ACR2xx系列ACR3xx系列ACR4xx系列4.2 安装方法ACR系列网络电力仪表安装方式为嵌入式,固定方式为挤压式,具体操作如下:1、在配电盘上,选择适合的地方开一个与所安装多功能仪表开孔尺寸相同的安装孔;2、取出网络电力仪表,松开定位螺钉(逆时针),取下安装支架;3、把仪表插入配电盘仪表孔中,插入仪表后装上安装支架、定位螺钉(顺时针)。

ACR谐波表使用说明

ACR谐波表使用说明
1
IH 代代相电电电
Acrel
1
2
2
3
%
3
%
N
N kWh
3 4 DI 5 6 7 8 1
N 代代电电次功
kWh
3 4 DI 5 6 7 8
IMP
1 2
IMP
2
相相2-31次电电电电 1-Ua 2-Ub 3-Uc
相电2-31次电电电电 1-Ia 2-Ib 3-Ic
Ⅲ电网质量参数 仪表显示 ①相电压显示界面, 按 SET 键切换到 ③电压波峰系数界面后按左、 右键可切换显示其它界面: 电 压波峰系数←→电话波形因子←→电流 K 系数←→电压电流不平衡度。
5
Acrel
上海安科瑞电气有限公司
Acrel
Acrel
IMP
1 2 3 4 DI 5 6 7
kWh
8
IMP
1 2 3 4 DI 5 6 7
kWh
8
7.1.3 测量参数 Ⅰ电力参数
A:对三相四线系统,仪表上电后显示
①相电压,按左、右键可如下图切换显示其它界面:相电压←→线
电压←→电流←→总功率(功率因数)←→时间←→有功功率←→无功功率←→视在功率←→功率因数。
kWh
8 1
IMP
2 3 4 DI 5 6 7
kWh
8 1
IMP
2 3 4 DI 5 6 7
kWh
8 1
IMP
2 3 4 DI 5 6 7
kWh
8
注:以上各 SET 循环界面下文中用①,②,③,④,⑤ 表示
7.1.2 仪表开机瞬间显示为仪表版本信息:
仪表开机瞬间显示为仪表版本信息,之后即显示相电压界面

ACR330ELH多功能电力仪表用户手册

ACR330ELH多功能电力仪表用户手册

ACR网络电力仪表用户手册一、概述该系列产品是一种具有可编程测量、显示、数字通讯和电能脉冲变送输出等多功能智能仪表,能够完成电量测量、电能计量、数据显示、采集及传输,可广泛应用变电站自动化、配电自动化、智能建筑、企业内部的电能测量、管理、考核。

测量精度为0.5级,实现LCD现场显示和远程RS-485数字接口通讯,采用MODBUS-RTU通讯协议。

二、技术参数三、安装与接线1. 安装尺寸:2. 安装方法:1)在固定的配电柜上,选择合适的地方开一个开孔尺寸的安装孔。

2)取出DCE仪表,松开定位螺丝,取下固定夹。

3)将仪表安装插入配电柜的仪表孔中。

4)插入仪表的固定夹,固定定位螺丝。

3.端子接线:注:L-N为辅助电源具体接线及仪表参数(脉冲常数等)见仪表所带接线图。

3)辅助电源:DCE系列网络电力仪表具备通用的(AC/DC)开关电源输入接口,若不作特殊声明,提供的是220V(AC/DC)或110V(AC/DC)电源接口的标准产品,仪表极限的工作电源电压为AC/DC:80-270V,请保证所提供的电源适用于该系列产品,以上防止损坏产品。

A、采用交流电源建议在火线一侧安装1A的保险丝。

B、对于电力品质较差的地区中,建议在电源回路安装浪涌抑制器防止雷击,以及快速脉冲群抑制器。

4).输入信号:DCE采用了每个测量通道单独采集的计算方式,保证了使用时完全一致、对称,其具有多种接线方式,适用于不同的负载形式。

说明:A、电压输入:输入电压应不高于产品的额定输入电压(100V或400V),否则应考虑使用PT,在电压输入端须安装1A 保险丝。

B、电流输入:标准额定输入电流为5A,大于5A的情况应使用外部CT。

如果使用的CT上连有其它仪表,接线应采用串接方式,去除产品的电流输入连线之前,一定要先断开CT一次回路或者短接二次回路。

建议使用接线排,不要直接接CT,以便于拆装。

C、要确保输入电压、电流相对应,相序一致,方向一致;否则会出现数值和符号错误!!(功率和电能)D、仪表输入网络的配置根据系统的CT个数决定,在2个CT的情况下,选择三相三线两元件方式;在3个CT的情况下,选择三相四线三元件方式。

多功能电力仪表用户手册

多功能电力仪表用户手册

多功能电力仪表用户手册一、产品简介该系列产品是一种具有可编程测量、显示、数字通讯和电能脉冲变送输出等多功能智能仪表,能够完成电量测量、电能计量、数据显示、采集及传输,可广泛应用变电站自动化、配电自动化、智能建筑、企业内部的电能测量、管理、考核。

测量精度为0.5级,实现LED 现场显示和远程RS-485数字接口通讯,采用MODBUS-RTU通讯协议。

二、技术参数三、安装与接线96 96×96 91×91 96 96 9580 80*80 76*76 80 80 9072 72*72 67*67 72 72 903.2 安装方法(1) 在固定配电柜开开孔尺寸大小的孔;(2) 取出仪表,松开螺丝,取下固定支架;(3) 仪表由前插入安装孔;(4) 插入仪表固定支架,并拧紧螺丝固定仪表。

3.3端子接线图三相四线接线图三相三线接线图(注1:尺寸不同接线方式都相同)(注2:电流线星号为进线,进出线接反,电能计量到反相电能。

)四、编程操作4.1 进入和退出编程状态进入编程状态:在测量显示状态时按住“SET”键1秒钟,进入密码认证页面,使用“◄”键,“▲”键和“▼”键输入密码(默认用户密码为1111),再按“SET”键就进入编程状态页面。

注意:如果输入密码按“SET”键后,退出到测量显示状态,则表示输入密码不正确。

退出编程状态:在编程状态,一直按住“SET”键2秒钟,退出编程状态,会提示用户选择是否保存设置值,“yes”保存设置值,“no”不保存设置值。

按“SET”键保存,按其它键不保存。

4.2 编程操作中按键的使用功能键SET:确认设置值,进入下一项设置或退出设置。

位选键◄:循环选定要设置的数码管,选定的数码管呈闪烁状态。

增加键▲:改变闪烁位数码管的数值(数码管数值从0到9循环)。

减小键▼:改变闪烁位数码管的数值(数码管数值从9到0循环)。

序号序号内容说明显示范围进入菜单密码CodE 0~9999说明:输入进入菜单的密码,只有密码正确才能进入菜单,出厂预设值为11111接线方式NEt 3P3L、3P4L 说明:3P3L三相三线接法、3P4L三相四线接法2电压倍率Pt 1~9999说明:本项设定的为线路所用PT的倍率,出厂预设定为1,如线路所用PT类型为:10kV/1 00V,则该项整定值为1003电流倍率Ct 1~9999说明:本项设定的为线路所用CT的倍率,出厂预设定为1,如线路所用CT类型为:600A/ 5A,则该项整定值为1204显示方式diSP 0~99说明:0为固定显示方式,手动切换显示项;1~99设置页面为自动切换,设置的值为显视的间隔时间,单位秒5通信地址Addr 1~247 说明:仪表地址,多机通信时用于识别本机6通信波特率bAUd 2400、4800、9600、19200、38400 说明:用于设定RS485通讯的波特率,出厂预设值为96007通信数据格式dAtA n.8.1、o.8.1、e.8.1、n.8.2说明:n.8.1无校验位8个数据位1个停止位、o.8.1奇校验8个数据位1个停止位、e.8.1偶校验8个数据位1个停止位、n.8.2无校验位8个数据位2个停止位8电能清0 Eclr yes、no 说明:yes电能数据清0,no电能数据不变9保存参数修改值选择SAVE yes、no 说明:yes保存参数修改值,no以前参数值不变10菜单进入密码Code 0~9999 说明:设置进入菜单的密码,密码预设值为1111五、面板说明与测量信息显示页面内容说明1三相电压分别显示电压Ua、Ub、Uc(3相4线)或Uab、Ubc、Uca(3相3线),单位为V,在K指示灯亮的情况下为KV。

ACR测量项目及面板说明

ACR测量项目及面板说明

ACR测量项目及面板说明ACR网络电力仪表面板右侧V123指示灯点亮时三排数码管分别显示三相电压;I123指示灯点亮时三排数码管分别显示三相电流;PQλ指示灯点亮时三排数码管分别显示总有功功率、总无功功率、总功率因数;面板上左边三个灯为功率负号指示灯,当任一负号灯点亮时表明该排显示值为负值;EPQ指示灯点亮表示显示项目为电能, ACR 网络电力仪表可以计量四象限电能数据:EPI--吸收有功电能EPE--释放有功电能EQL--感性无功电能EQC--容性无功电能。

右侧k、M代表所显示项目的单位数量级为千或兆。

例:如下图所示,EPQ指示灯亮,第一排数码管显示EPI,表示当前显示吸收有功电能,k指示灯亮,表示电能单位为kWh,读电能时将第二排数码管和第三排数码管连读,如下图所示电能为123456.78kWh.注:1、通常情况下,用户都是用电状态,此时应读取EPI值(吸收有功电能);发电厂向外发电时读取EPE值(释放有功电能)。

如果用户既有用电情况、又有发电机向外发电情况,则仪表EPI和EPE里都会有电能显示。

2、ACR仪表显示电能值时,LED(数码管)型指示的电能数据为一次侧电能,此值无须再乘以电流、电压变比。

LCD(液晶)型指示的电能数据为二次侧电能值,该值乘以电流、电压变比才是一次侧电能值。

3、当用户发现电能或功率指示明显不正常时,可通过查看三个分相功率的数值和符号确认有无接线错误。

切换到PQλ指示灯亮,三排数码显示总有功功率、总无功功率、三相功率因数时长时按住回车键,此时三排数码分别显示PA、PB、PC三个分相有功功率,若用电状态时存在任一分相功率为负(负号指示灯亮)均属不正常。

检查该相电流电压接线,观察是否存在CT进出线反,或电压与电流相序不对应等情况。

若用户采用3相3线接线方式(2CT接法),长时按住回车键时显示两个分相功率,不能使用上述方法判断,建议客户咨询我司技术支持人员。

按键功能说明ACR网络电力仪表四个按键从左至右依次为SET键、左键、右键、回车键。

ACR 系列谐波仪表安装使用说明书

ACR 系列谐波仪表安装使用说明书

085ACR系列谐波仪表ACR Series Harmonic Meters安装使用说明书V1.3Installation and operation instructionV1.3安科瑞电气股份有限公司ACREL CO.,LTD申明DECLARATION版权所有,未经本公司之书面许可,此手册中任何段落、章节内容均不得被摘抄、拷贝或以任何形式复制、传播,否则一切后果由违者自负。

本公司保留一切法律权利。

本公司保留对本手册所描述之产品规格进行修改的权利,恕不另行通知。

订货前,请垂询当地代理商以获悉本产品的最新规格。

No part of this publication may be reproduced,stored in a retrieval system,or transmitted in any form by nay means,electronic,mechanical photocopying,recording,or otherwise without prior permission of Acrel. All rights reserved.This company reserve power of revision of product specification described in this manual,without notice.Before ordering,please consult local anget for the latest specification of product.目录CONTENTS1 概述General......................................................................................................................................................... - 1 -2 产品规格及功能特点Specification and features ............................................................................................. - 1 -2.1系列产品规格 Series Products specification ............................................................................................ - 1 -2.2系列产品辅助功能auxiliary functions of series products .......................................................................... - 3 -3 技术参数 Technical parameter .......................................................................................................................... - 6 -4 安装接线说明Instruction of installing connection ........................................................................................... - 7 -4.1安装尺寸installing size ............................................................................................................................... - 7 -4.2接线方法 Method of connection ................................................................................................................. - 8 -5 包装 Package .................................................................................................................................................... - 10 -6 工程施工注意事项Notice in engineering construction ................................................................................. - 10 -6.1电压输入V oltage input .............................................................................................................................. - 10 -6.2电流输入Current input .............................................................................................................................. - 10 -6.3通讯接线 Communication connection ...................................................................................................... - 11 -7 操作说明Operation description ....................................................................................................................... - 12 -7.1 ACR220ELH /ACR320ELH操作指南Operating guide ........................................................................... - 12 -7.2 ACR230ELH/ACR330ELH操作指南Operation guide ............................................................................ - 26 -8 通讯说明Communication description............................................................................................................. - 40 -8.1简介General ............................................................................................................................................... - 40 -8.2通讯地址表 Communication Address Table ........................................................................................... - 40 -8.3 通讯值与实际值对应关系(约定Val_t为通讯读出值,Val_s为实际值)Communication reading value Vsactual value(Take Val_t as Communication reading value,Val_sas actual value) ............................................. - 55 - 9 DL/T-645通讯指南Communication Guideline............................................................................................... - 58 -9.1 DL/T645-1997协议简述DL/T645-1997 protocol overview ................................................................. - 58 -9.2传输方式 Transmission mode ................................................................................................................... - 59 -9.3协议 Protocol ............................................................................................................................................. - 59 -10 平均值、极值、不平衡度相关说明Explanation of average value、extremum、unbalance................ - 65 -10.1按键操作指南Key operation guide ......................................................................................................... - 65 -10.2 通讯说明Communication description .................................................................................................... - 67 - 11以太网设置Ethernet network settings ................................................................................................................ - 76 -11.1 网络设置Network settings ................................................................................................................ - 76 -11.2 WEB网页配置WEB page configuration......................................................................................... - 77 -11.3 仪表设置Instrument settings ............................................................................................................ - 78 -11.4 ModScan32设置ModScan32 settings ........................................................................................... - 79 -1 概述GeneralACR系列谐波表包括ACR220ELH,ACR230ELH,ACR320ELH,ACR330 ELH 等多款仪表,是本公司按IEC标准设计,与国际先进技术同步的综合电力监控仪表。

acrel-6000G产品中文安装使用说明书

acrel-6000G产品中文安装使用说明书

不注意这些预防措施可能会引起严重伤害。
特别申明:任何组织或个人不得以任何理由对软件进行破译,软件使用的最终解 释权归本公司所有。 本公司保留对本手册所描述之产品信息进行修改的权利,恕不另行通知。 订货前,请垂询当地代理商以获悉本产品的最............................................................................................................................................................ 1 2. 基本功能...............................................................................................................................................................1 2.1. 监控报警功能............................................................................................................................................1 2.2. 控制输出功能............................................................................................................................................1 2.3. 故障报警功能........................................

ACR120EL智能网络仪表

ACR120EL智能网络仪表
ACR120EL 著作权登记号:沪 DGY-2007-1337《安科瑞 ACRXXEL 综合 测控软件 V1.0》
范例 型 号:ACR120EL 辅助电源:AC/DC220V 输入信号:380V 600A/5A 2DI/2DO 电 网:三相四线 通 讯:RS485/Modbus-RTU
深度为 91mm。安装方式为嵌入式,固定方式为挤压式。LCD 显示。
专利及著作权 ACR120EL 专利:可编程智能表 LCD 液晶显示面板(80 型)--外观专利号
200730082423.3 ; 一 种 小 体 积 的 网 络 电 力 仪 表 -- 实 用 新 型 专 利 号 200720071534.9
功能 可直接从电流、电压互感器接入信号; 可任意设定 PT/CT 变比; 仪表显示可滚动设置; I/O 开关量,继电器报警输出,4~20mA 模拟量等功能模块化设计; 多块仪表可设置不同地址; 可通讯接入 SCADA、PLC 系统中;可与业界多种软件通讯(Intouch, Fix,
脉冲输出 输出方式:集电极开路的光耦脉冲,2 路输出 脉冲常数: 10000、40000、160000 imp/kWh
通讯 RS485 接口 MODBUS-RTU 协议
波特率 38400、19200、9600、4800 可设定
外形及安装尺寸(mm) ACR120EL 的面框尺寸为 80mm*80mm,开孔尺寸为 76mm*76mm, 安装
ACR120EL 智能网络仪表
LCD 显示、全电参量测量(U、I、P、Q、PF、F);四象限电能计量、 复费率电能统计、最大需量统计;2DI+2DO;RS485 通讯接口、Modbus 协议, 适用于动力柜中。
适用环境 工作温度:-10℃~+45℃ 储存温度:-25℃~+70℃ 相对湿度:≤95%不结露 海拔高度:≤2500m

ACR120E多功能电力仪表

ACR120E多功能电力仪表

ACR120E多功能电力仪表安科瑞王长幸ACR120E多功能网络仪表是上海ACREL电气股份有限公司自主研发生产的产品,该网络仪表针对电力系统、工矿企业、公共设施、智能大厦的电力监控需求而设计的。

它能测量所有的常用电力参数,如三相电流、电压,有功、无功功率,电度、谐波等。

由于该电力仪表还具备完善的通信联网功能,所以我们称之为网络电力仪表。

它非常适合于实时电力监控系统。

技术支持:安科瑞王长幸Q28802633230510-86179961该表具有很高的性能价格比,可以直接取代常规电力变送器及测量仪表。

作为一种先进的智能化、数字化的前端采集元件,该系列网络仪表已广泛应用于各种控制系统、SCADA 系统和能源管理系统中。

多功能网络电力仪表国外知名品牌有溯高美DIRIS A20,国内知名品牌有上海ACREL 的ACR120E、ACR120EL、ACR220E、ACR220EL、ACR320E、ACR320EL,江苏斯菲尔PD194-E4,珠海派诺PMAC503,深圳中电电力PMC-530A,美国电气控制QP650,华通测控PDM-803HE等。

下面以上海ACREL的ACR120E产品为例,介绍ACR120E多功能网络仪表的功能及技术参数。

功能:LED显示、全电参量测量(U、I、P、Q、PF、F);四象限电能计量;2DI+2DO;RS485通讯接口、Modbus协议。

适用环境l工作温度:-10℃~+45℃l储存温度:-25℃~+70℃l相对湿度:≤95%不结露l海拔高度:≤2500m电磁兼容l静电抗干扰实验Ⅲ级(IEC61000-4-2)l辐射抗干扰试验Ⅲ级(IEC61000-4-3)l电快速瞬变脉冲群干扰试验Ⅳ级(IEC61000-4-4)l浪涌抗干扰试验Ⅳ级(IEC61000-4-5)l射频传导干扰试验Ⅲ级(IEC61000-4-6)l电磁场抗干扰试验Ⅲ级(IEC61000-4-8)功能l可直接从电流、电压互感器接入信号;l可任意设定PT/CT变比;l仪表显示可滚动设置;l I/O开关量,继电器报警输出,4~20mA模拟量等功能模块化设计;l多块仪表可设置不同地址;l可通讯接入SCADA、PLC系统中;可与业界多种软件通讯(Intouch,Fix,Citec,组态网等);l LED或蓝屏背光LCD显示,可视度高;l方便安装,接线简单,工程量小;l仪表采用专用失电保护电路,在失电情况下,数据保存不丢失,恢复电源后,仪表继续运行;l四象限电能计量,分时计费,最大需量纪录及12个月电能统计。

多功能电力仪表使用说明书

多功能电力仪表使用说明书

多功能电力仪表使用手册使用手册USER MANUAL目录一、多功能电力仪表使用手册 (2)1、概述 (2)2、技术参数 (2)3、编程和使用 (3)测量显示 (3)编程操作 (5)4、通迅 (10)通迅报文举例 (11)MODBUS地址信息表 (11)5、功能输出 (13)二、多功能三相电压、三相电流、有功电度、无功电度表使用手册 (14)1、概述 (14)2、使用 (14)三、多功能有功电度、无功电度使用手册 (16)4、概述 (16)5、使用 (16)四、多功能三相电流、有功电度表使用手册 (18)1、概述 (18)2、使用 (18)五、接线图 (19)120*120接线图 (20)96*96接线图 (21)80*80接线图 (22)72*72接线图 (23)六、常见问题及解决方法: (24)1多功能电力仪表--使用手册一、概述多功能电力仪表是一种具有可编程测量、显示、数字通讯和电能脉冲输出等功能的多功能电力仪表,能够完成电量测量、电能计量、数据显示、采集及传输,可广泛应用变电站自动化,配电自动化、智能建筑、企业内部的电能测量、管理、考核。

测量精度为0.5级、实现LED 现场显示和远程RS-485数字接口通讯,采用MODBUS-RTU通讯协议。

1)辅助电源:多功能电力仪表具备通用的(AC/DC)电源输入接口,若不作特殊声明,提供的是AC/DC85~270V电源接口的标准产品,保证所提供的电源适用于该系列的产品,以防止损坏产品。

注:采用交流供电时,建议在火线一侧安装1A保险丝电力品质较差时,建议在电源回路安装浪涌抑制器防止雷击,以及快速脉冲群抑制器。

2)输入信号:多功能电力仪表采用了每个测量通道单独采集的计算方式,保证了使用时完全一致对称,其具有多种接线方式。

适用于不同的负载形式。

注:具体接线及仪表参数(脉冲常数等)见仪表所带接线图。

说明:A、电压输入:输入电压应不高于产品的额定输入电压(100V或400V),若无注明,出厂为AC0~500V、高于500V应考虑使用PT,在电压输入端须安装1A保险丝。

多功能电力仪表使用说明书

多功能电力仪表使用说明书

多功能电力仪表使用手册使用手册USER MANUAL目录一、多功能电力仪表使用手册 (2)1、概述 (2)2、技术参数 (2)3、编程和使用 (3)测量显示 (3)编程操作 (5)4、通迅 (10)通迅报文举例 (11)MODBUS地址信息表 (11)5、功能输出 (13)二、多功能三相电压、三相电流、有功电度、无功电度表使用手册 (14)1、概述 (14)2、使用 (14)三、多功能有功电度、无功电度使用手册 (16)4、概述 (16)5、使用 (16)四、多功能三相电流、有功电度表使用手册 (18)1、概述 (18)2、使用 (18)五、接线图 (19)120*120接线图 (20)96*96接线图 (21)80*80接线图 (22)72*72接线图 (23)六、常见问题及解决方法: (24)1多功能电力仪表--使用手册一、概述多功能电力仪表是一种具有可编程测量、显示、数字通讯和电能脉冲输出等功能的多功能电力仪表,能够完成电量测量、电能计量、数据显示、采集及传输,可广泛应用变电站自动化,配电自动化、智能建筑、企业部的电能测量、管理、考核。

测量精度为0.5级、实现LED 现场显示和远程RS-485数字接口通讯,采用MODBUS-RTU通讯协议。

21)辅助电源:多功能电力仪表具备通用的(AC/DC)电源输入接口,若不作特殊声明,提供的是AC/DC85~270V电源接口的标准产品,保证所提供的电源适用于该系列的产品,以防止损坏产品。

注:采用交流供电时,建议在火线一侧安装1A保险丝电力品质较差时,建议在电源回路安装浪涌抑制器防止雷击,以及快速脉冲群抑制器。

2)输入信号:多功能电力仪表采用了每个测量通道单独采集的计算方式,保证了使用时完全一致对称,其具有多种接线方式。

适用于不同的负载形式。

注:具体接线及仪表参数(脉冲常数等)见仪表所带接线图。

说明:A、电压输入:输入电压应不高于产品的额定输入电压(100V或400V),若无注明,出厂为AC0~500V、高于500V应考虑使用PT,在电压输入端须安装1A保险丝。

多功能电力仪表使用说明书

多功能电力仪表使用说明书

创作编号:BG7531400019813488897SX创作者:别如克*多功能电力仪表使用手册使用手册USER MANUAL目录一、多功能电力仪表使用手册 (2)1、概述 (2)2、技术参数 (2)3、编程和使用 (3)测量显示 (3)编程操作 (5)4、通迅 (10)通迅报文举例 (11)MODBUS地址信息表 (11)5、功能输出 (13)二、多功能三相电压、三相电流、有功电度、无功电度表使用手册 (14)1、概述 (14)2、使用 (14)三、多功能有功电度、无功电度使用手册………………………………………4、概述 (16)5、使用 (16)四、多功能三相电流、有功电度表使用手册……………………………………181、概述 (18)2、使用 (18)五、接线图 (19)120*120接线图 (20)96*96接线图 (21)80*80接线图 (22)72*72接线图 (23)六、常见问题及解决方法:………………………………………………………24创作编号:BG7531400019813488897SX创作者:别如克*1多功能电力仪表--使用手册一、概述多功能电力仪表是一种具有可编程测量、显示、数字通讯和电能脉冲输出等功能的多功能电力仪表,能够完成电量测量、电能计量、数据显示、采集及传输,可广泛应用变电站自动化,配电自动化、智能建筑、企业内部的电能测量、管理、考核。

测量精度为0.5级、实现LED 现场显示和远程RS-485数字接口通讯,采用MODBUS-RTU通讯协议。

21)辅助电源:多功能电力仪表具备通用的(AC/DC)电源输入接口,若不作特殊声明,提供的是AC/DC85~270V电源接口的标准产品,保证所提供的电源适用于该系列的产品,以防止损坏产品。

注:采用交流供电时,建议在火线一侧安装1A保险丝电力品质较差时,建议在电源回路安装浪涌抑制器防止雷击,以及快速脉冲群抑制器。

2)输入信号:多功能电力仪表采用了每个测量通道单独采集的计算方式,保证了使一致对称,其具有多种接线方式。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

ACR系列网络多功能电力仪表安装使用说明书目录1 概述2 产品规格3 技术参数4 安装与接线外形及安装尺寸安装方法接线方法注意事项5 编程与使用测量项目及面板说明按键功能说明操作说明编程菜单5.4.1 仪表通用编程菜单5.4.2 LCD显示仪表增加的背光控制菜单5.4.3 带开关量仪表增加菜单5.4.4 带复费率仪表增加菜单编程示例5.5.1 如何修改电流变比5.5.2 如何修改变送设置6 通讯通讯协议概述6.1.1 传输方式6.1.2信息帧格式功能码简介.1功能码03H或04H:读寄存器.2功能码10H:写寄存器. 3功能码x8H:读电能数据通讯应用细节.1开关量输入与输出.2电力参数与电能通讯地址表1 概述ACR系列网络多功能电力仪表,是针对电力系统,工矿企业,公用设施,智能大厦的电力监控需求而设计的一种智能表,它集成全部电力参数的测量(如单相或者三相的电流、电压、有功功率、无功功率、视在功率、频率、功率因数)以及全面的电能计量和考核管理(如四象限电能计量和分时电能统计、最大需量记录及12月电能统计等)。

同时它具有多种外围接口功能可供用户选择:带有RS485通讯接口,采用MODBUS-RTU协议可满足通讯联网管理的需要; 4-20mA的模拟量输出可与任意测量的电参量相对应,满足DCS 等接口要求;带开关量输入和继电器输出可实现断路器开关的“遥信”和“遥控”的功能,采用高亮度LED/LCD显示界面,通过面板按键来实现参数设置和控制,非常适合于实时电力监控系统。

ACR系列网络电力仪表具有极高的性能价格比,可以直接取代常规电力变送器及测量仪表。

作为一种先进的智能化、数字化的前端采集元件,该电力仪表已广泛应用于各种控制系统,SCADA 系统和能源管理系统中。

2 产品规格3 技术参数4 安装与接线外形及安装开孔尺寸(单位:mm)ACR1xx系列ACR2xx系列ACR3xx系列ACR4xx系列安装方法ACR系列网络电力仪表安装方式为嵌入式,固定方式为挤压式,具体操作如下:1、在配电盘上,选择适合的地方开一个与所安装多功能仪表开孔尺寸相同的安装孔;2、取出网络电力仪表,松开定位螺钉(逆时针),取下安装支架;3、把仪表插入配电盘仪表孔中,插入仪表后装上安装支架、定位螺钉(顺时针)。

接线方法(注:如与仪表壳体上接线图不一致,以仪表壳体上接线图为准)电压电流信号端子开关量输入输出电源、 RS485、脉冲输出模拟量变送输出注意事项电压输入输入电压应不高于产品的额定输入电压(100V或400V)的120%,否则应考虑使用PT;在电压输入端须安装1A保险丝;电流输入标准额定输入电流为5A或1A,大于5A的情况应使用外部CT;接线时确保输入电流与电压相序一致,即1号接线端接A相电压则5、6号接线端一定要接A相电流,否则会出现显示数值和符号错误;同时确保电流进出线连接正确(打*号端子接进线)。

如果使用的CT上连有其它仪表,接线应采用串接方式;安装接线时建议使用接线排,不要直接接CT,以便于拆装;去除产品电流输入连线前,必须先切断CT一次回路或者短接二次回路!通讯接线该仪表提供异步半双工RS485通讯接口,采用MODBUS-RTU协议,各种数据信息均可在通讯线路上传送。

理论上在一条线路上可以同时连接多达128个仪表,每个仪表均可设定其通讯地址(Addr),通讯速率(buad)也可通过设置选择。

通讯连接建议使用三芯屏蔽线,线径不小于0.5mm,2分别接A、B、COM,屏蔽层接大地,布线时应使通讯线远离强电电缆或其他强电场环境。

建议最末端仪表的A、B之间加匹配电阻,阻值范围为120Ω~10kΩ。

5 编程与使用测量项目及面板说明ACR网络电力仪表面板右侧V123指示灯点亮时三排数码管分别显示三相电压;I123指示灯点亮时三排数码管分别显示三相电流;PQλ指示灯点亮时三排数码管分别显示总有功功率、总无功功率、总功率因数;面板上左边三个灯为功率负号指示灯,当任一负号灯点亮时表明该排显示值为负值;EPQ指示灯点亮表示显示项目为电能, ACR网络电力仪表可以计量四象限电能数据:EPI--吸收有功电能EPE--释放有功电能EQL--感性无功电能EQC--容性无功电能。

右侧k、M代表所显示项目的单位数量级为千或兆。

例:如下图所示,EPQ指示灯亮,第一排数码管显示EPI,表示当前显示吸收有功电能,k指示灯亮,表示电能单位为kWh,读电能时将第二排数码管和第三排数码管连读,如下图所示电能为.注:1、通常情况下,用户都是用电状态,此时应读取EPI值(吸收有功电能);发电厂向外发电时读取EPE 值(释放有功电能)。

如果用户既有用电情况、又有发电机向外发电情况,则仪表EPI和EPE里都会有电能显示。

2、ACR仪表显示电能值时,LED(数码管)型指示的电能数据为一次侧电能,此值无须再乘以电流、电压变比。

LCD(液晶)型指示的电能数据为二次侧电能值,该值乘以电流、电压变比才是一次侧电能值。

3、当用户发现电能或功率指示明显不正常时,可通过查看三个分相功率的数值和符号确认有无接线错误。

切换到PQλ指示灯亮,三排数码显示总有功功率、总无功功率、三相功率因数时长时按住回车键,此时三排数码分别显示PA、PB、PC三个分相有功功率,若用电状态时存在任一分相功率为负(负号指示灯亮)均属不正常。

检查该相电流电压接线,观察是否存在CT进出线反,或电压与电流相序不对应等情况。

若用户采用3相3线接线方式(2CT接法),长时按住回车键时显示两个分相功率,不能使用上述方法判断,建议客户咨询我司技术支持人员。

按键功能说明ACR网络电力仪表四个按键从左至右依次为SET键、左键、右键、回车键。

SET键测量模式下,按该键进入编程模式,仪表提示输入密码CODE 输入正确密码后,可对仪表进行编程设置;编程模式下,用于返回上一级菜单左键测量模式下,用于切换显示项目;编程模式下,用于切换同级菜单或个位数的减小。

右键测量模式下,用于切换显示项目;编程模式下,用于切换同级菜单或个位数的增加。

回车键测量模式下,显示电能数据时按该键可查看分时复费率电能(有该功能时);编程模式下,用于菜单项目的选择确认和参数的修改确认。

左键+回车键编程模式下,该组合键用于百位数的减小。

右键+回车键编程模式下,该组合键用于百位数的增加。

、操作说明(第1、2、3排数码管分别用LEDA、LEDB、LEDC表示)5.3.1 查看ACR100E、200E、300E、400E吸收有功电能(用电)、释放有功电能(发电)、感性无功电能、容性无功电能:在测量状态下,单击左键或右键可以依次切换查看:吸收有功电能EpI←→释放有功电能EPE←→感性无功电能EqL←→容性无功电能EqC。

显示一次侧有功电能EpI/EpE时, Wh灯和k指示灯会点亮,此时低位的电能数据显示在LEDC上,高位数据显示在LEDB上,有功电能的单位为kWh,当电能值达到预定数值时, k灯熄灭, M灯亮,单位转换为MWh。

显示一次侧无功电能EqL/EqC时,varh灯和k灯会点亮,此时低位的电能数据显示在LEDC上,高位数据显示在LEDB上,无功电能的单位为kvarh,当电能值达到预定数值时, k灯熄灭, M灯亮,单位转换为Mvarh。

显示电能时,最高精确到两位小数。

5.3.2 查看ACR110E、210E、310E、410E三相电流和吸收有功电能在测量状态下,单击左键或右键可以依次切换查看:电流I←→一次侧有功电能EpI。

显示电流I时, I灯会点亮。

电流显示的单位通常为A,当一次侧电流达到预定数值时, k灯点亮,显示单位转换为kA。

显示一次侧有功电能EpI时, Ep灯和k灯会点亮,此时低位的电能数据显示在LEDC上,高位数据显示在LEDB上,有功电能的单位为kWh,当电能值达到预定数值时, k灯熄灭, M灯亮,单位转换为MWh。

5.3.3 查看ACR120E、220E、320E、420E电流、电压、功率、电能和频率在测量状态下,单击左键或右键可以依次切换查看:电压V←→电流I←→功率及功率因数 PQλ←→吸收有功电能EpI←→释放有功电能EPE←→感性无功电能EqL←→容性无功电能EqC←→频率F 显示电压V时,V123灯点亮,在三相四线时,按回车键可切换显示相电压←→线电压。

电压单位通常为V,当一次侧电压达到预定数值时, k灯点亮,显示单位转换为kV。

电流显示的单位通常为A,当一次侧电流达到预定数值时,k灯点亮,显示单位转换为kA。

有功功率显示单位为W,无功功率显示单位为var,当功率值达到预定数值时,k灯点亮,显示单位转换为kW或者kvar;当功率值达到预定数值时, k灯熄灭、M灯点亮,显示单位转换为MW或者Mvar。

有功功率显示在LEDA上,无功功率显示在LEDB上,功率因素显示在LEDC上。

显示一次侧有功电能EpI/EpE时, Wh灯和k指示灯点亮,此时低位的电能数据显示在LEDC上,高位数据显示在LEDB上,有功电能显示的单位为kWh,当电能值达到预定数值时, k灯熄灭, M 灯亮,单位转换为MWh。

显示一次侧无功电能EqL/EqC时, varh灯和k灯点亮,此时低位的电能数据显示在LEDC上,高位数据显示在LEDB上,无功电能显示的单位固定为kvarh,当电能值达到预定数值时, k灯熄灭、M灯亮,单位转换为Mvarh。

显示频率F时,“F”显示在LEDA上,频率值显示LEDB上,频率单位“Hz”显示在LEDC上。

面板上左边三个灯为功率负号指示灯,当任一负号灯点亮时表明该排显示值为负值;否则为正。

5.3.4 查看ACR120EL、ACR220EL、ACR320EL电流、电压、功率、电能和频率ACR120EL、ACR220EL、ACR320EL显示二次侧电能时,电能的低位数据显示在LEDC上,高位数据显示在LEDB上,有功电能单位kWh,无功电能单位kvarh。

查看流程见下图:5.3.5 ACR120EFL、ACR220EFL、ACR320EFL查看流程图ACR120EL、ACR220EL、ACR320EL显示二次侧电能时,电能的低位数据显示在LEDC上,高位数据显示在LEDB上有功电能单位kWh,无功电能单位kvarh。

编程菜单仪表通用编程菜单LCD显示仪表的背光控制菜单开关量输出增加的菜单ACR仪表开关量输出采用继电器输出,有两种控制方式:1、电平方式(继电器触点常开或常闭);2、脉冲方式(继电器触点闭合一段时间后断开,闭合时间由控制)。

复费率仪表增加的菜单复费率电能一天最多可分成8个时段、4种费率来完成电能的分时计量。

编程示例编程示例以流程图的形式介绍改变编程菜单中的某些选项,如电流倍数、变送设置等。