艾顿Moeller系列MSC-D DOL启动器102950产品说明说明书
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
Eaton 102950
Eaton Moeller® series MSC-D DOL starter, 380 V 400 V 415 V:
0.25 kW, Ir= 0.63 - 1 A, 230 V 50 Hz, 240 V 60 Hz, AC voltage
MSC-D-1-M7(230V50HZ)/BBA
General specifications
Eaton Moeller® series MSC-D DOL
starter
102950
4015081025893
154 mm200 mm
45 mm0.875 kg
CE
IEC/EN 60947-4-1
CSA File No.: 012528
CSA-C22.2 No. 14-10
UL Category Control No.: NKJH CSA Class No.: 3211-04
CSA-C22.2 No. 14 (on request) UL60947-4-1A
UL 508 (on request)
CSA
UL
UL File No.: E123500MSC-D-1-M7(230V50HZ)/BBA
Product Name Catalog Number
EAN
Product Length/Depth Product Height Product Width Product Weight Certifications Model Code
Short-circuit release
Temperature compensated overload protection CLASS 10 A
Screw terminals
No
2
IP20
NEMA Other
Direct starter
Mounting on Busbar 60 mm
0.63 A
1 A
III
3
6000 V AC
Also motors with efficiency class IE3 Starter with Bi-Metal release
AC
Fitted with: Functions Class
Connection
Connection to SmartWire-DT
Coordination type
Degree of protection
Model
Mounting method
Number of auxiliary contacts (normally closed contacts) Overload release current setting - min
Overload release current setting - max
Overvoltage category
Pollution degree
Rated impulse withstand voltage (Uimp)
Suitable for
Type
Voltage type
Max. 2000 m -25 °C
55 °C 0.8 A
1 A
0.12 kW
0.25 kW
230 - 415 V AC
15 A, 600 V AC, (UL/CSA)
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA) A600, AC operated (UL/CSA)
50000 A 15.5 A 1.2 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz 230 V
230 V
0 V
0 V
0 V
0 V
Altitude
Ambient operating temperature - min Ambient operating temperature - max Rated operational current (Ie)
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V Rated operational power at AC-3, 220/230 V, 50 Hz
Rated operational power at AC-3, 380/400 V, 50 Hz
Rated operational voltage
Switching capacity (auxiliary contacts, general use) Switching capacity (auxiliary contacts, pilot duty)
Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V
Short-circuit release (Irm) - max Power consumption, sealing, 50 Hz
Rated control supply voltage (Us) at AC, 50 Hz - min Rated control supply voltage (Us) at AC, 50 Hz - max Rated control supply voltage (Us) at AC, 60 Hz - min Rated control supply voltage (Us) at AC, 60 Hz - max Rated control supply voltage (Us) at DC - min
Rated control supply voltage (Us) at DC - max
5.7 W
0 W
1.9 W
1 A
1.4 W
Meets the product standard's requirements.
Meets the product standard's requirements.
Meets the product standard's requirements.
Meets the product standard's requirements.
Meets the product standard's requirements.
Does not apply, since the entire switchgear needs to be evaluated.
Does not apply, since the entire switchgear needs to be evaluated.
Meets the product standard's requirements.
Does not apply, since the entire switchgear needs to be evaluated.
Meets the product standard's requirements.
Does not apply, since the entire switchgear needs to be evaluated.Simple, flexible and safe! Distribution system for motor-starter combinations
eaton-manual-motor-starters-adapter-msc-d-dol-starter-dimensions.eps
DA-CE-ETN.MSC-D-1-M7(230V50HZ)_BBA
IL03402015Z
IL034038ZU
IL034014ZU
DA-CD-msc_d_bba_bg1
DA-CS-msc_d_bba_bg1
DA-DC-00004243.pdf
DA-DC-00004107.pdf
eaton-manual-motor-starters-device-msc-d-dol-starter-wiring-diagram.eps
Equipment heat dissipation, current-dependent Pvid
Heat dissipation capacity Pdiss
Heat dissipation per pole, current-dependent Pvid
Rated operational current for specified heat dissipation (In) Static heat dissipation, non-current-dependent Pvs
10.2.2 Corrosion resistance
10.2.3.1 Verification of thermal stability of enclosures
10.2.3.2 Verification of resistance of insulating materials to normal heat
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
10.2.4 Resistance to ultra-violet (UV) radiation
10.2.5 Lifting
10.2.6 Mechanical impact
10.2.7 Inscriptions
10.3 Degree of protection of assemblies
10.4 Clearances and creepage distances
10.5 Protection against electric shock
10.6 Incorporation of switching devices and components Brochure
Disegni
eCAD model
Istruzioni di installazione mCAD model
Report di certificazione Schemi di cablaggio
Eaton Corporation plc Eaton House
30 Pembroke Road Dublin 4, Ireland
© 2023 Eaton. Tutti i diritti riservati. Eaton is a registered trademark.
All other trademarks are
property of their respective
owners.
/socialmedia
Does not apply, since the entire switchgear needs to be evaluated.
Is the panel builder's responsibility.Is the panel builder's responsibility.Is the panel builder's responsibility.Is the panel builder's responsibility.
Is the panel builder's responsibility.The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Is the panel builder's responsibility. The specifications for the switchgear must be observed.Is the panel builder's responsibility. The specifications for the switchgear must be observed.The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.7 Internal electrical circuits and connections 10.8 Connections for external conductors 10.9.2 Power-frequency electric strength 10.9.3 Impulse withstand voltage 10.9.4 Testing of enclosures made of insulating material 10.10 Temperature rise
10.11 Short-circuit rating
10.12 Electromagnetic compatibility
10.13 Mechanical function。