液阻启动柜说明书
YBQ液体起动器
辅助代号的意义: W多点温度测量及声光报警功能 J配进相机自动转接功能 K配低压电机一次回路 A短接接触用CJ20型 B短接接触用真空接触器 D短接接触器用DW15型 P短接接触触器用两个接触器并联 PC采用可编程序控制器 KJ配低压电机一次回路和二次回路进相机自动转接装置 KC配低压电机一次回路和现场电容功率因素补偿装置 S此型号适用于鼠笼机起动
141
KT2
PT100
KA4
KT1 143
技术说明
控制电源
1、该图为YBQ2-06的控制回路与电阻柜一体。
D
2、KT1设定为40秒,KT2整定5S,KQ设定为60度。
3、KM为定子回路控制柜主开关辅助触点。
合闸/实验
4、KM4为转子回路短路接触器,KM4外接时由173、175
b、将电液粉溶解后分三等份注入三个水箱内,使溶液浓度在3%左右;
c将活动极板升降数次,溶液、搅拌均匀,然后将极板复位测每相两动静极间电阻值
R;
d、若R值在R0范围内,就可试车起动;若R值未在R0范围内则需要调整。R过大的
时应增大电液粉浓度;R过小时应降低电液粉浓度。
3、液体电阻的测量
将液体电阻的活动极板移到起动位置后,给每相两动静极板之间通过5A,50HZ交
3
表3
型号
YBQ5-0.2 YBQ5-0.4 YBQ5-0.6 YBQ5-1 YBQ5-2
YBQ液体电阻起动器使用说明书
A 700 800 1000 1100 1250
MHLS系列高压电动机液态软起动柜使用手册说明书
MHLS系列高压电动机液态软起动柜使用手册产品编号:目录一、概述.......................................................................................1二、型号说明...............................................................................1三、原理框图及工作原理...........................................................1四、主要技术指标.......................................................................4五、使用环境条件.......................................................................4六、产品执行、参照标准...........................................................4七、产品规格及结构说明...........................................................4八、安装调试:..............................................................................6九、定货须知:..............................................................................9十、电气原理图(见附图)........................................................10一、概述MHLS系列高压电动机液态软起动柜是利用液体电阻热容量大,阻值易调等特点,而专为各种大中型高压鼠笼异步电动机及高压同步电动机设计的液体电阻起动器。
液阻柜说明书
QKYZ-3100型液体电阻起动柜使用说明书沈阳凯键电机电气制造厂一、使用范围:QKYZ型液体电阻起动柜主要应用于大中型绕线式异步电动机的起动,既转子回路用液体变阻器作启动设备:通过机械传动装置使导电液体中两平行极板的相对距离逐渐减小直至为零,使串入电机转子回路中的电阻值是无极减小,从而实现绕线式大中型电动机的重载平滑起动。
1.本产品适合在下列条件下工作:⑴海拔高度不超过1000米;⑵户内周围介质温度:不高于+40℃,不低于0℃;⑶在温度为20±5℃时,空气相对湿度不大于85%;⑷没有导电尘埃及足以腐蚀金属和破坏绝缘的气体的场所;⑸没有爆炸危险的场所;⑹没有剧烈的振动和颠簸及垂直倾斜度不超过5°的场所;⑺需三相四线380/220V,20A,50Hz电源。
二、技术数据:1.产品规格:⑴容量至5000千瓦;⑵电源频率50赫兹;⑶转子电流2000安以下。
2.起动性能:⑴起动电流小,电动机重载起动过程定子电流限制在额定电流1.2倍左右;⑵恒转矩起动,消除了电机起动对减速机和机械设备的冲击,从而延长机械设备的使用寿命。
⑶热容量大,从冷态开始,允许连续起动六次。
⑷起动不受电网电压波动的影响,只须电网能保证电机正常运行就能顺利起动。
三、结构特征:控制柜由角钢铁板、焊接而成。
离墙安装,前后检修式结构。
控制柜外形及安装尺寸见图。
四、参数调整:1.电解液的配制:⑴ 起动电阻的确定串入电动机转子回路每相电阻值R0,可按下式确定:112203I I K I U R e M e e •= 式中:U 2e -----转子开路电压;K M -----起动转矩比:1.1~1.3;I 1e ------定子额定电流;I 2e ------转子额定电流;I 1-------定子运行电流;⑵ 液体电阻的配制a.先将活动极板移到起动位置,并将清水冲入水箱到规定水位的3/4左右;b.将电液粉溶解后分三等 份注入三个水箱内,使溶液浓度在3%左右;c.将活动极板升降数次,溶液搅拌均匀,然后将极板复位测量每相两动静极板间电阻值R;d.若R值在R0范围内,就可试车起动;若R值未在R0范围内则需要调整。
瑞丰电子 YBQ液体电阻起动器 说明书
165167
SB2 KM L2
失压保护
A YBQ2-0.6液体电阻起动器原理图
潍坊瑞丰电子有限公司
3
4
地址:临朐东城区东环路中段 电话:0536-3719858 3710339 传真:0536-3710339 HTTP:// E-mail:rfdz@
3
表3
型号
YBQ5-0.2 YBQ5-0.4 YBQ5-0.6 YBQ5-1 YBQ5-2
YBQ液体电阻起动器使用说明书
A 700 800 1000 1100 1250
外形尺寸mm B 650 800 800 900
1100
C 1800 2000 2000 2000 2200
安装尺寸mm
E
F
Φ
660
500 640
电阻柜外形 尺寸mm
A
B
C
800 700 2200
800 700 2200
1000 800 2400
1000 800 2400
1200 1000 2400
电阻柜安装 尺寸mm
E
FΦ
760 540 16
760 540 16
960 600
960 600 18
1150 1000
C
E
F
A
B
图2 YBQ5-系列结构示意图
型号说明 YBQ 大写英文字母表示起动器辅助号 阿拉伯数字表示起动器电流容量(KA) 阿拉伯数字表示起动器设计序号 “起”字汉语拼音第一个大写字母 “变”字汉语拼音第一个大写字母 “液”字汉语拼音第一个大写字母
辅助代号的意义: W多点温度测量及声光报警功能 J配进相机自动转接功能 K配低压电机一次回路 A短接接触用CJ20型 B短接接触用真空接触器 D短接接触器用DW15型 P短接接触触器用两个接触器并联 PC采用可编程序控制器 KJ配低压电机一次回路和二次回路进相机自动转接装置 KC配低压电机一次回路和现场电容功率因素补偿装置 S此型号适用于鼠笼机起动
DYQ3电阻起动柜技术规范书
唐山港陆钢铁有限公司年产240 万吨矿渣粉生产线DYQ3系列电阻起动柜技术规范书2012 年2 月第一部分:液体电阻起动柜1、货物需求1.1 招标文件的货物需求内容详见需求表,卖方在投标中应按液体电阻起动柜(以下称“水阻柜”)招标文件的内容,按照所配电机的型号规格报价。
1.2本技术条件提出的是最低限度的技术要求,并未对一切技术细节作出规定,也未充分引述有关标准和规范的条文。
卖方应提供符合本技术条件和有关国标、行标的优质产品。
如有更新的标准和规范应执行新的标准和规范。
1.3水阻柜参数须满足所配电机参数:电机参数表说明:中标单位投产前应与设计院进一步核实电机数据。
1.4卖方在投标响应表中详细列出1.2条中配套电机的水阻柜型号等其它参数。
货物需求总表2、技术条件2.1概述2.1.1总则(1)卖方应完全根据水阻柜招标文件的内容(商务条款和技术条款),提供配备电机参数表中规格的水阻柜2套。
(2)卖方应对水阻柜设计、制造、试验、供货运输以及在保证期内的产品质量负总责。
(3)买卖双方在合同执行过程中经双方认可的技术变更作为技术文本的补充,与合同正文具有同等的法律效力。
2.2基本要求2.2.1范围(1)卖方应履行招标文件中规定的水阻柜技术要求,包括有关管理事项、制造、运输、售后服务等过程中卖方的总责任。
除非另有说明,本文所引用的条款均参照技术要求中的相应条款。
(2)卖方应提供满足本技术条款要求及标准高、质量好的水阻柜。
2.2.2质量保证期在用户按照使用说明书规定、正确的使用与存放的情况下,卖方应保证在水阻柜使用一年内能良好的运行。
在上述时间内,水阻柜因制造质量不良而发生损坏或不能正常运行时,卖方应无偿的为用户修理、更换零部件或直至更换水阻柜并赔偿用户由于这些缺陷导致的额外费用和损失。
2.2.3总要求(1)卖方应在合同签订之后,3天之内,将所需审核的技术文件和图纸呈送甲方(以下简称“用户”)审查。
在技术文件、图纸未审核之前,不得进行设备的制造、材料采购、运输,否则出现的一切问题均由卖方承担。
【优选文档】高压液阻软启动柜PPT
传动机构在柜内上部,主要作用是由传动机电机带动极板运动以改变
电阻的大小来实现软起动,应定期(每月)进行检测、维护,以保证 机构运转灵活。 电阻的大小对应有四个特征位置,分别有四个位置开关,分别是初限 位、初限位保护、末限位、末限位保护,其中初、末限位间的间距, 是本液态软起动装置的有效控制行程,在初限位处电阻最大,末限位 处电阻最小(接近为0),初、末限位保护是控制传动机构的最大活 动空间,它们动作时均有报警输出,但只作为警示信号,不要求主要 停车检修。报警信号的消除可通过操作电气室门上的手动试车、手动 复位按钮使机构脱离报警位即可。初限位保护位置开关是初限位位置
液体电阻起动柜主要由以下几个部分组成:水箱、极板(分动极板 及静极板)、传动机构、限位机构(行程开关)及相关电器元件,如 继电器(或PLC)、时间继电器、接触器、按钮、指示灯等状置构成 适用于三相交流50Hz,额定工作电压为380V~10KV,额定功率为 75kW~10000Kw绕线式(鼠笼式及同步电机用WLQ型),适用于交流 电动机的重载平滑软起动,尤其是电网电压不稳或偏低的工矿企业。
是○具二有次起外动接超端机时子、液排失,态压电、气软超室行起的程电、动源超为柜温AC等适3多80重用V,保1于护5A功(额能三。定相四电线)压及为±KM3即~可1。0KV大、中型同步或异步电动机
通过使串入电机定子回路中的电阻值平滑减小,从而实现绕线式大中型电动机的重载平滑起动。
液体电阻起动的柜软主要起由以动下。几个在部分静组态成:工水箱作、条极板件(分下动,极板与及静电极抗板)器、传性动能机构相、限同位;机构在(行动程态开关工)及作相条关电件器元件,
(1)柜体 由角钢和金属薄板焊接而成,柜体内预留有工作接地和接地母线,为 保证柜体接地良好,应妥善与保护接地连接牢固;柜内应保持清洁、 干净,其一次进出线均采用高压电缆连接下进下出。
高低压笼型液阻软启动器使用说明书(英文)
一、High, low-pressure liquid electric resistance soft starter use and characteristicsHigh, low-pressure liquid electric resistance soft starter for the sake of improvement big, weigh starting of type electric motor function but develop success of the new soft start control device. Originally start to control system to is divided into to spread part, liquid Resistance part and control part. It mainly works characteristics is be greatly charged and weigh type electric motor of turn the string in the settling of son(round a line type electrical engineering) or electric motor son(cage type electrical engineering or synchronous electrical engineering) back track into the special liquid electric resistance, and this electric resistance starts in the electric motor automatic devotion combine in the reserved auto inside time, have no class, continuous cut off, make thus electrical engineering at steady under the ideal start electric current and the condition start. The electric motor is even to lift soon, this to protect electrical engineering, use to give or get an electric shock equipments, charged barbed wire net and stanza electricity etc. have already shown Zhao effect. Add it to start, stop, control, order in the system, break down protection, contact, report to the police, show that etc. carries on to with meticulous care design, make thus liquid electric resistance start better than repeatedly quick change Resistance machine, give or get an electric shock an anti- machine and change to press to start old style starters, such as machine and iron casting electric resistance...etc. to compare from the Ou, have to automate degree high, start the electric current is small, the charged barbed wire net electric voltage is low(10 KV electric voltage, the 9.2 KV can start;6 KV electric voltage, the 5.5 KV can start;380 Vs, the 340 Vs can start), biggest lowered the capacity of transformer. It can save users a one-time investment.The this liquid electric resistance soft starter still has function superior credibility, operation convenience, can start to wait an advantage for many times in a row, therefore, this product is extensively applied to a building materials, chemical engineering, metallurgy and mineral mountain, petroleum and machine to process, deckle etc. profession, is be like ball to whet machine and promote heavy burdens, such as machine, crusher, compressor, breeze machine and water pump...etc. to carry currently of most ideal start to control an equipments.二、Main function(一), High, the low pressure round line type electric motor1, be charged electrical engineering power----------50-10000 KW2, be charged electrical engineering to turn sub- electric current --------100-2000 A 3, be charged electrical engineering to turn sub- electric voltage------------200-2200 V4, start time -------20 S, 25 S, 30 S and 50 S are adjustable 5, start number of times in a row ----------3~5 times (the environment temperature is 20 ℃, see work condition)6, start electric current -------------Iq ≤ 1.3 Ie7, the electricity liquid work as usual temperature-----0 ℃ ~60 ℃8, supply voltage Three mutually ----------380 Vs 50HZ9, surroundings environment temperature -----------35 ℃ ~50 ℃10, gearing ground elevation height --------------≤ 4000 ms11, atmosphere relative humidity --------------<85%12, around lie quality should have no explosion and have no corrosion and break insulate air and dust13, the gearing ground should don't show a Zhao impact vibration(二) high and low-pressure rat cage type electric motor1, be charged electrical engineering power -----------------50-10000 KW2, be charged electrical engineering to settle sub- electric current--------20-800 A 3, be charged electrical engineering to settle sub- electric voltage-----------380 V, 3 KV-10 KV 4, start time ----------20 S~ 85 S adjustable 5, start number of times in a row2~5 times (the environment temperature is 20 ℃, see work condition)6, start electric current -------------------- ≤ 3.5Ie7, the electricity liquid work as usual temperature -----------------0 ℃ ~80 ℃8, change Resistance box to insulate to bear to press grade-------------26 KV ±10% 9, surroundings environment temperature ----------------35 ℃ ~50 ℃10, gearing ground elevation height ------------------≤ 4000 m11, atmosphere relative humidity ------------------<85%12, around lie quality should have no explosion and have no corrosion and break insulate air and dust13, the gearing ground should don't show a Zhao impact vibration三、the liquid electric resistance is soft to start an adjusting of machine to try1, estimating of liquid electric resistance value methodA: For round line type electric motor:The machine equipments given to settle, it drags along electrical engineering power, settle son with turn the sum of son settle the electric voltage, electric current also immediately and indeed settle down and start the liquid electric resistance of cabinet also certain. Below introduce two kinds of resistivity to estimate a method:①The first method:R0 ------------ String into each phase of the motor rotor circuit resistance value U2e------------Rotor open circuit voltageI2e-------------Stall current rotor circuit in series with R0I1e-------------Rated current of the statorI1---------------The Stator run currentKm-------------Starting torque ratio, 1.1—1.3②The second method:R0------------- String into each phase of the motor rotor circuit resistance value U2e------------ Rotor opens circuit voltageI2e------------- Rotor rated currentnK------------- Start the current ratio of the rated current series with R0n--------------- Not in series with R0 to start the current and the rated current than n: 5~7B: For cage type electrical engineeringV------------- Rated motor voltage (V)m-------------Not in series with R0 to start the current and the rated current than, m:4~7Ie------------- Motor rated current (A)n--------------- Start the current ratio of the rated current series with R0, n: 2~3.52, the allocation of liquid electric resistance:①, Infuse the water tank into the clear water (tap water or distilled water) of one fixed amount, water level should at liquid designation restriction of height the following.②, Will inside three slots of the electrolysis powder aqua average infusion water tank of about 8% densities.③, The start ascends and descends electric motor and make activity pole the plank up and down exercise several times with make electrolyte even, then measures pole the electric resistance between the planks be worth, if is bigger than a Ro value, then increase electrolysis powder aqua; Whereas, sample parts of electrolytes, infusion clear water, generally proper first little turn on electricity and solve powder of aqua, increase its density gradually, attain the resistivity needed through the measurement.3, the measurement method of liquid electric resistance:①, Activity pole the plank rise to extreme limit position, at fixedly and very the of plank and activity pole plank exchanges electric current that joins a 10 As, measurement liquid electric resistance up press to decline V.②, Compute according to formula: R=V/I I carry on R and Ro contrast, the adequacy adjusts liquid electric resistance resistivity.四、use and maintenance1,Front operation of operation front-panel in the door and show that the concrete function of function component all is marked clearly with writing, therefore the easy to worker operates and need to notice the following what time:①, Controlling a cabinet to after sending the electricity allow to start a light is bright(move pole plank type), expressing can start; Otherwise forbid a start, at this time, should check whether liquid is normal, gets in touch with a machine and corresponds a route of travel switch whether act, whether rise and fall is good enough. The difference one by one checks, until allowing starting a light is bright, the square can carry on a start.②, this machine has a foreign land and local control conversion switch (depend on electrical engineering capacity the size equip), revolving to converta switch can carry on foreign land, local control.③,This cabinet body has to be firm to connect ground(connect a ground of electric resistance ≤ 4 Ω), at the same time regardless what reason need to be shut down, all want to cut off the power, in order to prevent occurrence the personnel get an electric shock trouble.④, Is a little bit continuous to move number of times to at most disallow while needing to carry on a dynamoelectric control to the electrical engineering (request to add according to customer Conditions) over 8 times.⑤,Have to heat device(round a line type electrical engineering) inside the cabinet for the northern and cold weather, the factory sets to 10 ℃ (the limit in temperature can arbitrarily regulate), when being liquid Resistance the temperature is low here start liquid Resistance heating apparatus, in order to prevent liquid Resistance freeze.2, the maintenance of liquid electric resistance soft starter①,At usually under the circumstance, the liquid electric resistance soft starter meets to break down will automatically shut down, therefore can maintain in time, but specially what to notice BE, periodical(half year) check a route of travel switch of SQ1, SQ2(two work route of travels) whether normal, if discover the SQ3, SQ4(two protection route of travels) has been already acted and explain the SQ1, SQ2 has been bad, have to replace in time and change by assurance to dependable.②, That is periodical (half year) to check to start a cabinet liquid whether normal, if the liquid is too low meeting the bell report to the police, and fill with electrolysis aqua or water in time under the situation that cut the power, fill with electrolysis aqua or water attention keep liquid bead from splashing, so as not to break insulate.③,Periodically(4-5 years) replace to conduct electricity a liquid, at the same time clean pole plank and insulate a box of body, can first throw away with the sparse hydrochloric acid pole the oxide on the plank, and then use clear water blunt clean, the box body is several times washed and brushed to dry in the air with the clear water, and then use the PVC antisepsis eclipse gum Smear surface, the general box of body doesn't easily dismantle to unload to clean, even if take out or put a fashion from the cabinet, avoid vibration and bump shot as far as possible, so as not to box the body is broken.④,Such as detection lord electrical engineering circulate the electric current is small, then want to check to link a switch to touch whether the point burns bad, should repair in time, such as start electric current lead big, then the liquid electric resistance value diminishes, should increase clear water.五、Mourn luck and gearing1,This series product has no such as the customer special request, all press the company the factory unify a packing, the upper part has already packed to unload a ring, easy to pack to unload and install. In the process of mourning to carry in not of inclination, transport under guard medium the Cape maximizing carbon is no bigger than 15 °.2, Ensure while installing cabinet body and horizontal plane are perpendicular, and start a cabinet should have electric cable ditch under.3,The electric motor turns a son(or settle son) cable to lead into liquid Resistance first short connect a switch up, then wear tube to lead into start cabinet fixedly and very plank up.六、After-sales service1, any lately old customer provides an easy Sun spare part in time;2, the free instruction gearing adjusts to try, free is customer training operation personnel with maintain a personnel;3, the product protects to fix for a year, lifelong service;4, Opinion and problem half an hour of all customers inside give to reply, if need company technical personnel's support (in addition to minority of sides far area), 48 hours, the wife member arrives upon the scene.。
高压10KV液阻启动柜电阻液配比
高压水电阻软起动柜专用电液粉高压水电阻软起动柜(液阻柜)专用电液粉,纯净的电液粉外观为白色粉末或细粒结晶,味涩。
易溶于水。
用电解沉积法制得的粉末。
相对密度(25℃)2.532。
熔点851℃。
比热容1.042J/(g·℃)(20℃)。
易溶于水,在35.4℃其溶解度最大,每100g水中可溶解49.7g碳酸钠(0℃时为7.0g,100℃为45.5g)。
微溶于无水乙醇,不溶于丙醇。
其水溶液水解呈碱性,有一定的腐蚀性,能与酸进行中和反应,生成相应的盐并放出二氧化碳。
高温下可分解,生成氧化钠和二氧化碳。
电液粉易溶于水,呈强碱性,都能提供Na+离子。
电液粉是平面分子,其中心原子N原子为sp2杂化。
由于羟基上的氢原子与另外一个氧原子形成了氢键,分子才呈平面结构,而且N的三根键长都不相同。
N原子垂直于分子平面的一个p轨道是满的,它与未连接H的两个氧原子上的p轨道共轭,形成大π键。
分子内氢键也是硝酸沸点较低的原因。
电液粉去掉一个氢原子的结构是硝酸根,一般带一个负电荷(硝酸根离子)。
电液根具有对称的平面等边三角形结构,4个原子形成大π键,多出来的1个电子在离域π键里。
电液粉去掉一个羟基的结构是硝基-NO2。
硝基的正离子叫硝酰正离子。
用途高、低压液阻柜(水阻柜)配制液体电阻。
液体电阻启动器专用电解粉(电液粉)又称高压水电阻软起动柜电解粉。
液体电阻起动器又称“液体变阻器”(俗称“水电阻”)是为改善大中型绕线式交流异步电动机或高压鼠笼型电机的起动性能而研制的新型起动器。
液体电阻起动器的基本原理是通过机械传动装置使导电液体中两平行极板的距离逐渐减小直至为零,使串入电机转子回路中的电阻值平滑减小,从而实现绕线式大中型电动机的重载平滑起动。
它克服了频敏电阻起动器冲击电流大、难起动和操作不便等问题。
适用于大型设备的电动机重载起动,是频敏电阻起动器和金属电阻起动器的替代产品。
采用水电阻取代频敏电阻起动器和金属电阻起动器,近些年来的技改项目中也普遍使用。
CYDT系列自动电液变阻起动调速控制柜
CYDT系列自动电液变阻起动调速控制柜应用范围适用于冶金、供热、化工、建材、.水利水电、轻工、采矿、机械等工业领域的三相交流50HZ、额定电压为380v、440V 、660V、额定功率为75KW以上大中型绕线型交流异步电动机所拖动的诸如风机、水泵、空压机等设备的.软起动与调速节能运行。
亦适用于配合变负载特别是冲击性负载情况下电动机瞬间的过流保护。
本装置电压与绕线型交流异步电动机的电压没有直接的联系,所以适用于各种不同电压等级及各种不同容量的电动机。
工作原理及特点对于风机、泵类负载通过改变串在电动机转子上的液态电阻阻值来改变电动机的转速,电阻越小,电动机转速越高,电阻为零时,电动机恢复到全速,从而达到调速的目的。
本装置由起动系统、热交换器和电控系统三部分组成。
为克服在调速过程中液体因电阻产生热量而使温度升的过高,由循环系统自动将液体进行冷却。
设备起动平稳,运行安全可靠,维护方便,对电网要求不高。
主要技术参数●起动起始电流倍数Iq≤1.3Ie●起动时间10~60,预整定,现场可调●调速比(T型)风机、泵类负载2 :1;推荐范围60%-90%●抑制冲击特性(B型)轧机可根据实际工况而定,转差率S≤0.12●运行节电率风机、泵类负载可达30%以上●电液正常工作温度0~70●外壳防护等级IP20, IP30执行标准●低压成套开关设备和控制设备GB/T14084. 1----1993GB 7251. 1----1993●自动电液变阻起动、调速补偿控制装置Q/FCYI---2008使用环境条件●环境温度;最高温度+40℃,最低温度-40℃,[带加热装置---10℃]●空气相对湿度不超过90%;●海拔高度不超过2000m;●地面倾斜度不大于5°;●安装地点无火灾、爆炸危险,无化学腐蚀及剧烈震动。
●注;若有特殊环境使用条件,请在定货时与我公司申明和协商。
型号说明CYDT □- □- □被控电动机额定电流被控电动机额定功率设计序号产品名称代号产品规格型号规格电机功率(KW)外形参考尺寸(mm)安装参考尺寸(mm)宽(W)深(D)高(H)w d ΦCYDT400-/□-□≤400 1400 900 2200 1240 850 14 CYDT500-/□-□≤500 1400 900 2200 1340 850 14 CYDT800-/□-□≤800 1500 1000 2300 1340 950 14 CYDT1200-/□-□≤1200 1600 1000 2300 1440 950 14 CYDT1400-/□-□≤1400 1200 1000 2300 1040 950 14 CYDT1400-/□-□≤1400 1200 1000 2000 1040 1150 14 CYDT1600-/□-□≤1600 1200 1000 2300 1040 950 14CYDT1600-/□-□≤1600 1100 800 2000 1040 1150 14 一次方案图③可配套使用我公司的高低压开关柜;②可配套使用我公司的CP静止式进相器;行提出;注: ①此方案为我公司常规方案图。
高压液阻启动柜液阻配比
高压液阻启动柜液阻配比(原创实用版)目录1.高压液阻启动柜的概念与用途2.液阻配比的意义和作用3.液阻配比的计算方法4.液阻启动柜的优点及应用范围5.结语正文一、高压液阻启动柜的概念与用途高压液阻启动柜,又称为水阻柜、进相器、高压固态软起动柜等,是一种用于控制和调节电动机启动、停止和运行的设备。
其主要作用是降低电动机启动时的电流冲击,减少电动机启动对电网的影响,提高电动机的运行效率和保护电动机。
广泛应用于建材、化工、冶金、石油、机械、电力、矿山等各个行业。
二、液阻配比的意义和作用液阻配比是指高压液阻启动柜中液体电阻与电极材料之间的比例。
它的设定对高压液阻启动柜的性能和效果起着至关重要的作用。
合适的液阻配比可以保证启动柜具有良好的起动性能和稳定的运行性能,同时还能提高设备的使用寿命和维护方便性。
三、液阻配比的计算方法液阻配比的计算方法通常根据电动机的功率、电压、频率等参数以及启动柜的规格进行。
计算公式如下:液阻配比 = 电流冲击峰值 / (电动机额定电流×电极材料电阻率)其中,电流冲击峰值通常根据电动机的启动方式和负载情况来确定;电动机额定电流是指电动机在额定电压下的电流值;电极材料电阻率则由电极材料的性质决定。
四、液阻启动柜的优点及应用范围液阻启动柜具有以下优点:1.降低电动机启动时的电流冲击,减轻电网负担;2.提高电动机的起动性能和运行效率;3.保护电动机,延长设备使用寿命;4.结构简单,操作方便,维护容易。
因此,液阻启动柜广泛应用于各种高低压电动机、风机、水泵等设备的启动、停止和调速控制。
五、结语高压液阻启动柜作为一种先进的电动机启动控制设备,其优良的性能和广泛的应用范围使其在工业生产中具有重要的地位。
而液阻配比的合理设置,更是保证高压液阻启动柜正常运行和发挥最大效能的关键。
第1页共1页。
高压液阻启动柜液阻配比
高压液阻启动柜液阻配比【最新版】目录1.高压液阻启动柜的概念与用途2.液阻配比的意义和作用3.液阻配比的计算方法和参数4.液阻配比的实际应用案例5.湖北尊科电气有限公司的相关介绍正文一、高压液阻启动柜的概念与用途高压液阻启动柜,又称为水阻柜、进相器、高压固态软起动柜等,是一种用于控制和调节电动机启动、停止和运行的设备。
通过调整液阻配比,可以实现电动机的平稳启动和停止,降低电动机启动过程中的电压冲击,保护电动机和电网。
广泛应用于建材、化工、冶金、石油、机械、电力、矿山等各个行业。
二、液阻配比的意义和作用液阻配比是指高压液阻启动柜中液体电阻与电极材料之间的比例。
液阻配比的大小直接影响到电动机启动过程中的电流和电压,是高压液阻启动柜正常运行的关键参数。
合适的液阻配比可以使电动机在启动过程中受到较小的电压冲击,降低电动机的启动电流,延长电动机的使用寿命。
三、液阻配比的计算方法和参数液阻配比的计算方法通常采用经验公式或试验法。
经验公式是根据大量实验数据总结出来的,但只适用于特定类型的高压液阻启动柜。
试验法是通过实际操作和测量,根据电动机的启动特性和电网参数来调整液阻配比。
液阻配比的参数通常包括电阻值、电极材料、液体电阻的浓度等。
四、液阻配比的实际应用案例某大型矿山企业,其电动机启动过程中经常出现电压冲击,导致电动机和电网的损坏。
该企业采用了高压液阻启动柜,并通过调整液阻配比,成功实现了电动机的平稳启动和停止,降低了电动机启动过程中的电压冲击,保护了电动机和电网,提高了生产的稳定性和效率。
五、湖北尊科电气有限公司的相关介绍湖北尊科电气有限公司是一家集科研、生产、销售为一体的实业型高新技术企业,拥有数十项国内同行领先地位的专利成果。
公司专注于高低压成套设备、新型电气节能设备、工业控制设备、电机起动、调速、补偿设备及自动化控制系统的研发、生产制造及推广应用。
YBQL1
为了您检修方便, 请务必保存好本说明书,如果您在检修时有什么困 难,请及时与我们联系,我们随时为您提供技术支持。
1
一、概述 YBQL-6系列高压笼型液体电阻起动器适用于额定电压3-10KV,额定功
YBQL-6 高压笼型液阻柜
使 用 说 明 书
潍坊瑞丰电子有限公司
电话:0536-3719858 3710039 地址:山东临朐东环路98号
目录
一、 概 述 二、 工作原理 三、 型号说明 四、 使用条件 五、 技术参数 六、 性能特点 七、 系统组成 八、外形结构及安装尺寸 九、 安装调试 十、 操作说明 十一、 使用维护 十二、订货须知
5
保护功能。 注:高压起动控制柜和液变阻柜在电机功率较小时也可合并在一个
柜体内。 八、外形结构及安装尺寸
1、外型尺寸
6
3、规格尺寸
型号
电机 功率
YBQL6-500
≤500
YBQL6-1000 ≤1000
YBQL6-1500 ≤1500
YBQL6-2000 ≤2000
YBQL6-3000 YBQL6-4000
Ue:电机额定电压 Ie:电机额定电流
8
m:直接起动时起动电流以与额定电流比(一般取 4~7)
n:串入液体电阻后起动电流与额定电流比(一般取 2~2.5)
5、液体电阻的配制
(1)、先将活动极板升到允许起动位置;
(2)、将电液溶解后分三等份注入三个水箱内;
(3)、将动极板升降数次,溶液搅拌均匀,然后将极板复位,测每相两
2
YBQL □ - □ / □
水阻操作规程
操作注意事项1、控制柜送电步骤●检查控制柜内部是否有接地或短路。
●液体电阻启动柜液体液面符合要求。
●合上AC380V控制电源开关。
●合上DC220V控制电源保险。
●合上液体电阻启动柜QF1开关●合上控制柜UPS开关。
●检查液体电阻启动柜指示是否正常●合上液体电阻启动柜QF2开关●合上液体电阻启动柜QF3开关●检查AC380及DC220V电源指示灯指示正常。
●合上控制柜AC380V电源开关。
●合上液体电阻启动柜QF4开关。
●合上控制柜DC220V电源开关。
●检查直流220V及直流24V电源指示灯指示正常。
●检查LCD显示正常。
●检查液体电阻启动柜联机设置是否在投入位置。
●按试车“按钮”液体电阻启动柜电极极板向下运动随后返回待启动状态。
2、高频斩波串级调速系统启动●检查高压开关柜是否在工作位置。
●检查液体电阻启动柜联机设置是否在投入位置。
●检查风机符合启动条件。
●检查出口挡板已关闭。
●检查调速控制柜及液体电阻启动柜无报警。
●液体电阻启动柜电极在待启动状态(最上面)。
●检查控制柜刀闸QS1在分开位置、QS2、QS3在合闸位置。
●检查调速控制柜工作状态为工作和远方。
●按启动按钮,高压开关合闸,电机开始转动,高频斩波串级调速系统启动程序启动,液体电阻电极极板向下运动,LCD显示系统处于启动状态,启动指示灯亮。
电机转速逐渐上升,延时一段时间,液体电阻电极极板向下运动至最小,KM2闭合KM1打开,液体变阻器启动回路切除,电机转速达到额定转速,启动过程完成进入全速状态。
LCD显示系统处于全速状态,全速指示灯亮。
●缓慢打开风机风门,注意观察电机定子电流。
(也可以在进入调速状态,电机转速调低后再开风门)。
3、全速转调速●检查调速控制系统在全速状态。
●检查电机定子电流已稳定。
●检查液体电阻电极极板在带启动位置(启动过程结束后1分钟电极极板返回到待启动位置)。
●按调速按钮,调速系统进入有全速转调速程序,LCD显示系统处于调速状态,调速指示灯亮。
高压液阻软启动柜
高压水阻柜
板数次,注意不要将电液溅出箱体外,以免损坏箱体绝缘。再将动定 极板置于初始位置,在动定极板间加6.3v交流电压,测量所配液阻回 路电阻,由:R=U/I,可计算出所配制的液阻箱内纯电阻的电阻值R,测 量电路如图:
高压液阻软启动柜
2021/5/9
1
高压水阻柜
液体电阻起动器又称“液体变阻器”(俗称“水电阻”)。是为改善 大中型绕线式交流异步电动机的起动性能而研制的新型起动器。液体 电阻起动器的基本原理是在电动机定子回路中串入起分压和限流作用 的特种液体电阻,起动过程中,通过机械传动装置使导电液体中两平 行极板的距离逐渐减小,液态电阻阻值在预定的时间内自动实现由大 到小无级变化,直到接近为零时,液阻自动切除,电动机投入运行。 通过使串入电机定子回路中的电阻值平滑减小,从而实现绕线式大中 型电动机的重载平滑起动。它克服了起动冲击电流大、难起动和操作 不便等问题。 。
2021/5/9
8
高压水阻柜
开关的后备,作用是控制传动机构上升(复位)时的准确停车,同样 ,末限位保护位置开关是末限位位置开关的后备,作用是控制传动机 构下降时的准备停车。 在脱机运行时,传动机构应自动复位到初限位处,主机起动前,根据 起动需要的阻值,传动机构使动极板移动到合适位置或初限位处允许 起动,起动过程中,传动机构按预定的程序下移(减小阻值),起动 完成液阻切除后,极板自动复位到初限位处为下次起动作好准备。传 动机构中的拖动电机过载一般只作为警示信号。 (3)液阻的配制: ☆ 首先将软起动装置活动极板调至允许起动状态; ☆ 打开电液箱盖板,向箱内注入清洁的自来水至液位线以下线约
(2)电气室
电气室内安装有各种用于在主机起动过程中参与控制保护的低压电气
YDQ5液体水阻柜产品说明书(DLSYDQ2010-5-20)
YDQ5系列液体电阻起动器产品说明书目录封面概述 2标准及规范 2正常工作条件 2型号说明 2产品特点 3结构简介 4安装 5设备调试 5使用与维护 8包装、运输、贮存、开箱及检查 8订货须知 9附表一 9封底 101 概述YDQ5系列液体电阻起动器(以下简称起动器)是为改善大中型绕线式交流异步电动机的起动性能而研制的新型起动器,克服了频敏电阻起动器冲击电流大、难起动和操作不便等问题,适用于建材、冶金、化工、矿山等工业部门的球磨机、空压机、破碎机、大型风机、大型水泵等电动机的重载起动,是频敏起动器和金属电阻起动器的理想替代产品。
2 标准及规范GB4720-1984 电控设备第一部分低压电器电控设备GB4942.2-1993 低压电器外壳防护等级GB/T5226.1-1996 工业机械电气设备第一部分通用技术条件GB/T13384-2008 机电产品包装通用技术条件GB14048.4-2003 低压开关设备和控制设备低压机电式接触器和电动机起动器3 正常工作条件环境温度上限不超过50℃,下限不低于-5℃;相对湿度不超过85%;海拨高度不超过2000M;应放置室内无剧烈振动及冲击且垂直倾斜度不超过5°,没有火灾及爆炸危险的场合;不允许有导电尘埃及腐蚀性气体;电源采用三相四线 380/220V 20A,且电压波动必须保证在额定电压的±15%范围内。
注:1)环境温度长期低于0℃时需加装加热器,用户订货时应予说明。
2)电源电压等级特殊时需重新设计,用户订货时应予说明。
4 型号说明YDQ 5辅助代号适配电机功率kW设计序号液体电阻起动器4.1 辅助代号的意义:K 配低压电机一次回路B 短接接触器用真空接触器PC 采用可编程序控制器辅助代号可以组合使用。
仅0.2-0.4系列可以配低压电机一次回路。
环境温度长期低于0℃时需配电加热功能。
PLC可以根据需要选用。
5 产品特点 5.1 基本原理本起动器通过机械传动装置使导电液体中两平行极板的距离逐渐减小直至为零,使串入电机转子回路中的电阻值由最大逐渐平滑减小为零,使电动机转速逐渐平滑达到额定转速。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
LXMGD系列高压鼠笼式电机液阻软起动柜使用手册目录一概述 (2)二工作原理 (2)三型号说明 (3)四主要技术参数及使用环境条件 (3)五典型一次方案 (4)六符合标准 (4)七产品规格及安装基础图 (4)八功能说明 (6)九装置的安装、调试 (7)十使用与维护 (9)十一运输与储存 (11)十二开箱须知 (11)十三订货须知 (11)一、概述LXMGD系列高压鼠笼式电机液阻软起动柜(“简称高压液阻柜”)适用于额定电压为3~10KV大、中型同步或异步鼠笼式电机的软起动。
在静态工作条件下,与电抗器性能相同;在动态工作条件下,可实现无级的连续起动。
由于其利用液体电阻的负温度特性,使电机的端电压逐步上升,起动转矩也逐步增加,因而电机起动比较平稳。
特别是该系统结构简单、可靠性强,不仅经济实用,而且安装和操作简单、维护方便。
它广泛应用于冶金、建材、矿山、石化、供水、电力行业等的泵类、风机、压缩机、破碎机、皮带传输机等各大、中容量高压电机的重载起动,是传统的电抗器降压起动、直接起动的理想的替代产品。
LXMGD系列高压交流电动机液态软起动柜主要性能特点如下:1 标准型☆采用具有国内领先水平的计算机仿真软件对电动机的起动全过程进行模拟仿真,使电动机起动的全过程可预测、可调整、可控制。
☆起动电流小而平滑、无冲击,显著降低电网压降,保证电网的可靠运行,有效保护电动机及传动机械。
☆具备完善的报警提示功能和电动机保护功能。
☆采用PIC控制,可靠性高。
2 增强型☆在标准型的基础上,增加电流闭环自动控制功能。
即在电动机起动过程中自动检测电动机电流,同时根据电流大小自动调节控制装置,使电动机起动最佳化。
☆采用先进的控制技术,使电动机起动过程的控制响应更快,精度更高。
☆电动机起动电流可预置,满足不同工况、负载的起动要求。
3 智能型☆采用计算机控制系统、动态软件,对软起动装置进行智能化监控。
☆友好的人机界面,观察、操作、记录非常方便。
☆可输出实时电流曲线、实时电压曲线(显示、打印)。
☆数据库全面,可随时调用各类数据以便系统分析。
☆电动机起动完成后,实施有效动态监控。
☆电动机运行的历史曲线使电动机运行过程一目了然。
☆完善的报警提示功能。
☆通信功能、网络功能。
二工作原理该装置是在电机定子回路中串可变液体电阻的一种降压起动方式,即随着主电动机的起动,装置自动改变液体电阻动、定极板之间的间距,使电阻线性均匀减小,电机端电压均匀提高的一种起动方式。
主机起动结束后,软起动装置从主回路中完全脱离或处于零电位,活动极板自动复位,为下次起动作好准备。
三型号说明LXM GD△:定子绕组Y接法(星点不能打开)或△接法Y:定子绕组Y接法(星点可以打开)被控电机额定工作电压(KV)被控电机额定功率(kW)设计序号 1:标准型(可省略)2:增强型3:智能型高压鼠笼式电机企业代号四主要技术参数注:起动电流在负载系统阻力矩允许的情况下可控制到最小。
使用环境条件:1)环境温度:最高气温﹢40℃,最低气温0℃;2)空气相对湿度不超过90%;3)海拔高度不大于1000M;4)地面倾斜度不大于5°;5)安装地点无火灾、爆炸危险、化学腐蚀及剧烈震动;注:若有特殊使用条件,请在订货时注明五典型一次方案一次方案图(可实现与GG1A、XGN、KYN、JYN、GZS等多种柜型配套)说明:图表中虚线框内元件为液阻起动设备.六符合标准高压开关设备和控制设备标准共用技术要求 GB/T11022-1999 3-35KV交流金属封闭开关设备 GB3906-1991 高压交流电动机液态软起动装置 Q/FZR2-2000七产品规格及安装基础图根据主电机容量及接法不同,主要有如下产品规格:注:随着产品不断更新换代,外形及安装尺寸会有所变化,请以实际的产品为准。
其柜体安装基础图如下:单面柜安装基础图观察窗观察窗进线沟图一三面柜安装基础图图二四面柜安装尺寸则为(2650×1000×1200)×3+2650×800×1200八功能说明本装置主要由柜体、电气室、电液箱和传动机构四部份组成,下面分别介绍各部分的功能:(1)柜体由角钢和金属薄板焊接而成,柜体内预留有工作接地和接地母线,为保证柜体接地良好,应妥善与保护接地连接牢固;柜内应保持清洁、干净,其一次进出线均采用高压电缆连接下进下出。
(2)电气室电气室内安装有各种用于在主机起动过程中参与控制保护的低压电气元件、PIC等,门是安装有操作开关、信号灯等,室的下部安装的是二次外接端子排,电气室的电源为AC380V,15A(三相四线)及±KM即可。
(3)电液箱电液箱在柜内下部,箱内安装有液体电阻的动、定极板,在主机起动过程中正是通过控制改变他们之间的间距来实现软起动的,在停机断电的情况下经常观察液位高低,液面过低请注入清水(自来水)。
电液箱是本装置的核心之一,只有在箱体完好、状态(包括液温、液位)输出正常、动定极板位置适宜,本柜才能输出允许起动信号,主机才能完成起动合闸,关于允许起动信号所包含的全部条件将在使用及维护中进行介绍。
(4)传动机构传动机构在柜内上部,主要作用是由传动机电机带动极板运动以改变电阻的大小来实现软起动,应定期(每月)进行检测、维护,以保证机构运转灵活。
电阻的大小对应有四个特征位置,分别有四个位置开关,分别是初限位、初限位保护、末限位、末限位保护,其中初、末限位间的间距,是本液态软起动装置的有效控制行程,在初限位处电阻最大,末限位处电阻最小(接近为0),初、末限位保护是控制传动机构的最大活动空间,它们动作时均有报警输出,但只作为警示信号,不要求主要停车检修。
报警信号的消除可通过操作电气室门上的手动试车、手动复位按钮使机构脱离报警位即可。
初限位保护位置开关是初限位位置开关的后备,作用是控制传动机构上升(复位)时的准确停车,同样,末限位保护位置开关是末限位位置开关的后备,作用是控制传动机构下降时的准备停车。
在脱机运行时,传动机构应自动复位到初限位处,主机起动前,根据起动需要的阻值,传动机构使动极板移动到一合适位置或初限位处允许起动,起动过程中,传动机构按预定的程序下移(减小阻值),起动完成液阻切除后,极板自动复位到初限位处为下次起动作好准备。
传动机构中的拖动电机过载一般只作为警示信号,如用户另有要求,也可作为分闸信号使主机停车。
九装置的安装、调试(1) 安装就位☆软起动装置安装前,首先应确保安装基础符合《建筑电气安装工程质量检查评定标准》GBJ303-88的要求,并参加柜体安装基础图图一、图二完成基础施工。
☆软起动装置拆箱后,应首先保管好随机文件资料,并根据装箱单检查随柜备件、附件是否齐全,并作好相应记录,然后检查有没有明显的损坏。
如没有问题,可采取垂直吊装的方式实施就位。
☆ 三面组合柜的安装务必仔细检查,确保从柜体正面从左至右布置的相序为A 、B 、C 次序。
(2) 电气检查及安装☆ 通电前应仔细对软起动装置上主回路元件进行检查。
具体的方法请参阅相关的技术文件。
☆ 柜内工作接地和保护接地应连接牢固、导通良好,接地母线在适当的地方与建筑预设的接地网相连接,确保人身设备安全。
☆ 电气接线及部件组装请依据随机文件资料中提供的有关图纸认真进行。
☆ 所有单机调试必须保证在高压断电的情况下进行!正式通电前,必须确认传动机构的运行方向正确,确认(调整传动电机运转方向)的方法如下:☆ 接通控制电源,脱机运行时传动机构应自动复位(上升),可通过操作电气室门上的按钮使机构升降,确保手动试车时极板下降,手动复位时极板上升。
☆ 根据原理图,检查软起动装置内各部分电器控制性能是否正常,动作是否可靠,并依据下面的动作流程检查软起动装置动作至正常:☆ 允许起动→主机合闸→主机联机起动→极板下降(LXMGD2、3型起动电流过大 起动完成时时有上升现象)→主机运行(LXMGD-Y 型:星期三点短接;LXMGD-△型:运行柜投入)→软起动装置切除→极板复位至初限位处(为下次起动作好准备)(3) 液阻的配制:☆ 首先将软起动装置活动极板调至允许起动状态;☆ 打开电液箱盖板,向箱内注入清洁的自来水至液位线以下约20mm 处,将电液粉用温水溶解后,正确连接电阻至电气室内预留的AC6.3V 或AC24V 测量电源,由图三所示测量回路中Rs =U/I 计算出实际配制的液体电阻值,在边测量边搅拌的情况下将溶解的电液适量注入电液箱中; ☆ 所需Rs(Ω)值由下式确定2-1nIe3mIe Ue Rs=mIe式中:m-未串R 前起动电流与额定电流之比,一般取4~7n-串入R 后起动电流与额定电流之比,取2.5~3 Ie-电机额定工作电流(A ) Ue-电机额定工作电压(V )(4) 测量回路:VATCRs图 三液阻配制完成后应确保电液箱的电液至口部液位线处,且液位状态正常;(5) 联机通电前的检查☆ 联机通电前应用干布将电液箱四周擦净,再用2500V 光欧表检测确保三相对地及相间绝缘电阻在10M Ω以上(注:此处的绝缘电阻值指断开外接线路时,在本说明书第4项所述使用环境条件下),必要时需进行工频耐压试验;☆ 联机通电前需手动模拟试机2~3次,电气动作、信号指示均正常时,再与开关柜联调空动作,反复试验正常后,方可联机通电。
十 使用和维护本装置具有较大的热容量,允许一定的连续起动,但多次连续起动会出现液温过高(一般设定为65~70℃)。
在主机起动前一旦液温过高时,就有报警输出,同时产生电气联锁禁止起动,以防止电机起动造成液体飞溅等不安全因素,这时需经过一定时间的冷却,待液温过高报警消除即可。
需要强调的是液位过低、液温过高等保护开关,在主机起动前有报警输出时即禁止起动,但在起动过程中或起动结束后有报警输出时在能确保没有液体沸腾造成飞溅情况下,报警输出只作为警示信号,不要求主机停车检修,可将报警声响回路关闭,待停机断电后或下降起动前排除即可。
软起动装置在起动及运行中,除应遵守有关规程外,还应注意以下问题;(1)操作程序虽然软起动装置设计有保证开关柜各部分操作程序正确联锁,但是操作人员对软起动装置各部分的投入仍应严格按开关柜操作规格和相关技术文件的要求进行,不得随意操作。
否则,容易造成设备损坏,甚至引起事故。
1)软起动装置的检修应按有关高压断电检修的规格要求进行,确保人身设备安全。
建议用户特别注意以下几点:☆定期(每月)检查液位是否正常,若液位太低,应及时添加清水;在加清水时应避免水珠飞溅,并用干燥、洁净的棉纱将电液箱体表面擦干,确保绝缘强度。
☆定期(每季)进行传动机构检测、维护、检修或更换上、下限位开关。
☆定期(4~5年)更换电液,同时清洗极板和箱体;先用稀盐酸,清洗极板上的氧化物,而后再用清水洗净,箱体在取出和置入时避免撞击以免损坏箱体。