《电力建设标准》
合集下载
相关主题
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
二基本原则·············································(1)
三电力负荷分级和供电要求·······························(2)
3.1 负荷分级············································(2)
b) 短时或周期工作制电动机的设备功率统一归算到负载持续率为25%的有功功率。
c) 卤钨灯的功率为灯泡额定功率,气体放电灯的功率为灯泡额定功率加镇流器的功率损耗。
d) 电焊机及电焊装置的变压器设备功率统一归算到负载持续率为100%时的有功功率。
4.1.5具有消防泵用电负荷的10KV变电所计算负荷(Pt),按下述方法分别计算,取其大值。
5.2 一般规定
5.2.1供配电系统建设方案的编制应根据油田总体开发方案,并结合油田所在地区的电力系统现状和发展规划,电源宜从系统电源取得。
5.2.2供配电系统设计,应简化接线,同一电压供电系统的配电级数不宜多于两级。
5.2.3油田配电网线路架设以架空线为主,特殊情况可采用电缆或绝缘导线。
5.7 防雷接地···········································(10)
5.8防火防爆···········································(11)
六变电站(所)·········································(11)
6.4 系统接线···········································(13)
6.5 电气设备选择·······································(14)
6.6 所用电源和操作电源·································(15)
5.1 定义················································(6)
5.2 一般规定············································(7)
5.3 电压、电压偏差和谐波抑制····························(7)
三级
原油接转站
输油泵、掺水泵、热洗泵
二级
加药泵、增压泵
三级
增压集气站、注气站
天然气压缩机、空冷器、空压机
二级
脱水转油站
输油泵、脱水泵、掺水泵、污油泵、空压机、脱水器、加药泵
二级
凝析油轻油
输送泵、空冷器、回流泵、事故油泵及厂房应急照明
一级
外输泵、倒灌泵、电伴热
二级
供水系统
加压泵、水源井、真空泵、水净化装置、水泵、加药泵、搅拌机
3.2.3三级负荷站、场供电要求:采用单回路供电。
3.2.4对于以工业汽轮机、柴油机或燃气轮机拖动为主要动力的站场,其辅助设施可由外部电源供电。无电区宜采用可靠的燃气或柴油发电机组。
3.2.5当油气田所在地区外部系统电网不能满足供电要求时,应设置自备电源。
3.2.6应急电源系统:油气田的应急电源应对各主要用电负荷仔细核算容量后,选择发电机、不间断电源、EPS电源或者蓄电池的形式。
3.2 供电要求············································(4)
四负荷计算和负荷预测···································(5)
五供配电系统···········································(6)
四 负荷计算和负荷预测
4.1 负荷计算
4.1.1站、场内生产装置、机泵等用电设备,应采用轴功率法计算。
4.1.2机械采油、辅助设施等单元的用电设备,宜按需要系数法计算。
4.1.3由变、配电所直馈的电动机计算负荷,宜采用轴功率法计算。
4.1.4用电设备功率的确定方法:
a) 连续工作制电动机的设备功率按铭牌额定功率。
1.3油田电力建设应执行国家标准、行业标准和油田公司的相关规定。
二 基本原则
2.1 油田电力建设以科学发展观为指导,遵守国家有关经济建设的法律、法规,贯彻执行国家合理利用资源、节约能源、节约用地、环境保护等规定。
2.2 油田电力建设的目标是建成网络坚强、结构合理、安全可靠、运行灵活、节能环保、经济高效的油田专用坚强电网,为油田生产、生活提供可靠的电力保障。
b) 由于路径受限且满足一路电源检修、另一路电源正常运行时,铁塔或钢管塔可同杆架设(重冰区除外)。
对于一级负荷中特别重要的负荷,除由两个电源供电外,应设应急电源,并严禁将其他负荷接入应急供电系统。
c) 在一个电源发生故障时,另一个电源应满足生产装置(或单元)一、二级负荷的用电;当工程分期建设时,变配电系统的预留容量应与整个工程相适应。
6.7 变配电装置·········································(15)
6.8 综合自动化·········································(16)
七10KV配电变压器选择··································(16)
6.1 一般规定···········································(11)
6.2变电站站址选择·····································(11)
6.3 变压器的选择·······································(12)
负荷级别
备 注
矿场油库(管输)
仪表电源
一级
输油泵、电动阀、污油泵、污水泵
二级Hale Waihona Puke Baidu
管道首站的输油泵为一级
矿场油库(铁路外运)
仪表电源
一级
装车泵、电动阀、污油泵、污水泵
二级
3.1.6消防负荷的等级划分,执行GB 50183的有关规定。
3.2 供电要求
3.2.1一级负荷站、场供电要求:
a) 一级负荷站、场应采用双电源供电,有条件时,两个电源应引自不同的变电所或发电厂;无条件时,可由当地公共电网同一变电站不同母线段分别引出两个回路供电,但作为上级电源的变电站应具备至少两个电源线和至少两台主变压器、分列运行。
附录A延长油田股份有限公司电力建设应执行的
国家和行业主要技术规范·························(21)
一 总 则
1.1 为适应延长油田股份有限公司(以下简称“油田公司”)建设国内一流标准化大油田的需要,规范和指导公司电力建设工作,提高油田电力建设管理水平,特制定本建设标准。
1.2本建设标准适用于油田公司范围内10KV至110KV新建、扩建、改建电力工程,是编制电力建设方案和实施电力工程项目管理的依据。
3.1.2在一、二、三级负荷中,对供电连续性要求严格的用电负荷如机组控制系统、应急润滑油系统以及各站场的自控、通信用电按照不间断重要负荷考虑。
3.1.3油田油气集输各类站场的电力负荷等级划分如下:
a) 处理能力大于或等于30×104t/年的油气集中处理站、矿场油库(管输)、轻烃储库等用电负荷为一级。
b) 处理能力小于30×104t/年的油气集中处理站、矿场油库(铁路外运)、原油稳定站、接转站、放水站、注水站、污水处理站、配制站、原油脱水站、增压集气站、注气站、机械采油井排等用电负荷为二级。
c) 自喷油井、边远、零散的机械采油井、注入站、配水间、配汽间、分井计量站等为三级负荷。
3.1.4油田油气集输各类站场内用电设备负荷分级应符合表1的规定。
延长油田股份有限公司
电力建设标准
(征求意见稿)
动力装备部
二〇一一年十一月
前 言
按照延长油田股份有限公司加快建设国内一流标准化大油田的要求,公司动力装备部组织编写了延长油田股份公司《电力建设标准》。本标准是油田公司电力建设的指导性文件,适用于油田公司10KV至110KV新建、扩建、改建电力工程。
编制本标准时,参照了国家和行业有关电力建设方面的标准和规范,结合了油田公司多年来在电力建设方面的经验,并多次开会讨论,吸收了采油厂和有关专家的意见。
a) 除消防泵外的最大计算负荷与最大一台消防泵的计算负荷之和。
b) 消防设施的计算负荷与该变电所供电的一级负荷之和。
上述变压器在消防灭火时,其负荷率可达100%。
4.2油田负荷预测。
a) 用电负荷预测是进行油田电力网建设的重要基础工作,要重视和坚持原始用电资料的积累和收集工作,认真做好负荷预测工作。
二级
注水站
注水泵、润滑油泵、冷却水泵、电动阀
二级
对于边远地区0.4KV柱塞式电机的注水站内设备都按三级负荷考虑
聚合物配制站
外输泵、供水泵、分散装置、搅拌器
二级
排污泵
三级
聚合物注入站
注入泵
三级
注汽站
柱塞泵、供油泵(引风机、鼓风机)
二级
移动式注汽站为三级负荷
污水处理站
污油泵、污水泵、加药泵、搅拌机、电动阀
2.3 油田电力建设以油田整体开发方案为基本依据,依托地方区域电力网建设专用电力网,统一规划,资源共享,分期分批实施,避免重复建设。
2.4 积极开展风力、太阳能等可再生能源的推广应用工作和天然气、石油伴生气发电等油田开发副产品的回收利用工作。
三 电力负荷分级和供电要求
3.1 负荷分级
3.1.1原则:油田的电力负荷等级,根据《油气田变配电设计规范》(SY/T 0033-2009)有关规定,结合工程生产特点及中断供电造成的损失和影响程度划分。
表1 油田油气集输各类站场内主要工艺用电设备负荷等级
站场(或装置)名称
用电设备名称
负荷级别
备 注
原油稳定装置
原油稳定泵、轻油泵、压缩机、空压机、仪表控制电源
一级
进料泵、污油泵、污水泵、塔底泵、空冷器
二级
轻油接转
空压机
一级
轻油外输泵、加药泵
二级
轻烃储库
轻烃泵、天然气压缩机、空压机、消防泵
一级
乙二醇水溶液循环泵
d) 根据供电的需要,变、配电所可设置备用电源自动投入装置。
3.2.2二级负荷站、场供电要求:
a) 二级负荷站、场宜采用双回路供电。当采用两回线路供电确有困难,在工艺上设有停电安全措施或有备用电源时,可由一回专用架空线路或专用电缆供电。
b) 二级负荷站、场内的变、配电所在技术经济上合理时,也可采用自动投入装置。
本建设标准系初次编制,在施行过程中,请各单位注意总结经验,积累资料,如发现需要修改和补充之处,请将意见送至延长油田股份有限公司动力装备部,以便今后修订时参考。
本标准的附录A为资料性附录。
本标准由延长油田股份有限公司动力装备部提出、起草并负责解释。
2011年11月
一总则·················································(1)
三级
污水回灌站
回灌泵
二级
污水提升站
污水提升泵
三级
工业锅炉房
上水泵、鼓风机、引风机、盐泵、燃料油泵、火嘴
二级
注:对于油田油气处理能力小于30×104t/年的二级电力负荷站场,表中一级负荷用电设备降为二级负荷
3.1.5矿场油库主要用电设备负荷分级应符合表2的规定。
表2 油库主要用电设备负荷等级
站场名称
用电设备名称
b) 油田不同的开发阶段均应进行负荷预测,作为相应阶段油田电力网建设的基础数据。油田最终用电负荷大小应以油田总体开发方案确定的生产规模作为预测的基础。
c) 目前油田用电负荷预测的主要方法是原油生产综合用电单耗法和用电量增长趋势预测法。
五 供配电系统
5.1 定义
油田供配电系统是指油田供电网和油田配电网组成的电力网络。油田供电网是指由110KV、35KV输变电系统组成的电力网络。油田配电网是指由油田10KV线路、10KV配电变压器和0.4/0.22KV低压线路所组成的电力网络。
八10KV线路············································(17)九 井场配电装置········································(18)
十 节电················································(19)
5.4 系统接线············································(8)
5.5 无功功率补偿·······································(9)
5.6 低压配电系统·······································(10)
三电力负荷分级和供电要求·······························(2)
3.1 负荷分级············································(2)
b) 短时或周期工作制电动机的设备功率统一归算到负载持续率为25%的有功功率。
c) 卤钨灯的功率为灯泡额定功率,气体放电灯的功率为灯泡额定功率加镇流器的功率损耗。
d) 电焊机及电焊装置的变压器设备功率统一归算到负载持续率为100%时的有功功率。
4.1.5具有消防泵用电负荷的10KV变电所计算负荷(Pt),按下述方法分别计算,取其大值。
5.2 一般规定
5.2.1供配电系统建设方案的编制应根据油田总体开发方案,并结合油田所在地区的电力系统现状和发展规划,电源宜从系统电源取得。
5.2.2供配电系统设计,应简化接线,同一电压供电系统的配电级数不宜多于两级。
5.2.3油田配电网线路架设以架空线为主,特殊情况可采用电缆或绝缘导线。
5.7 防雷接地···········································(10)
5.8防火防爆···········································(11)
六变电站(所)·········································(11)
6.4 系统接线···········································(13)
6.5 电气设备选择·······································(14)
6.6 所用电源和操作电源·································(15)
5.1 定义················································(6)
5.2 一般规定············································(7)
5.3 电压、电压偏差和谐波抑制····························(7)
三级
原油接转站
输油泵、掺水泵、热洗泵
二级
加药泵、增压泵
三级
增压集气站、注气站
天然气压缩机、空冷器、空压机
二级
脱水转油站
输油泵、脱水泵、掺水泵、污油泵、空压机、脱水器、加药泵
二级
凝析油轻油
输送泵、空冷器、回流泵、事故油泵及厂房应急照明
一级
外输泵、倒灌泵、电伴热
二级
供水系统
加压泵、水源井、真空泵、水净化装置、水泵、加药泵、搅拌机
3.2.3三级负荷站、场供电要求:采用单回路供电。
3.2.4对于以工业汽轮机、柴油机或燃气轮机拖动为主要动力的站场,其辅助设施可由外部电源供电。无电区宜采用可靠的燃气或柴油发电机组。
3.2.5当油气田所在地区外部系统电网不能满足供电要求时,应设置自备电源。
3.2.6应急电源系统:油气田的应急电源应对各主要用电负荷仔细核算容量后,选择发电机、不间断电源、EPS电源或者蓄电池的形式。
3.2 供电要求············································(4)
四负荷计算和负荷预测···································(5)
五供配电系统···········································(6)
四 负荷计算和负荷预测
4.1 负荷计算
4.1.1站、场内生产装置、机泵等用电设备,应采用轴功率法计算。
4.1.2机械采油、辅助设施等单元的用电设备,宜按需要系数法计算。
4.1.3由变、配电所直馈的电动机计算负荷,宜采用轴功率法计算。
4.1.4用电设备功率的确定方法:
a) 连续工作制电动机的设备功率按铭牌额定功率。
1.3油田电力建设应执行国家标准、行业标准和油田公司的相关规定。
二 基本原则
2.1 油田电力建设以科学发展观为指导,遵守国家有关经济建设的法律、法规,贯彻执行国家合理利用资源、节约能源、节约用地、环境保护等规定。
2.2 油田电力建设的目标是建成网络坚强、结构合理、安全可靠、运行灵活、节能环保、经济高效的油田专用坚强电网,为油田生产、生活提供可靠的电力保障。
b) 由于路径受限且满足一路电源检修、另一路电源正常运行时,铁塔或钢管塔可同杆架设(重冰区除外)。
对于一级负荷中特别重要的负荷,除由两个电源供电外,应设应急电源,并严禁将其他负荷接入应急供电系统。
c) 在一个电源发生故障时,另一个电源应满足生产装置(或单元)一、二级负荷的用电;当工程分期建设时,变配电系统的预留容量应与整个工程相适应。
6.7 变配电装置·········································(15)
6.8 综合自动化·········································(16)
七10KV配电变压器选择··································(16)
6.1 一般规定···········································(11)
6.2变电站站址选择·····································(11)
6.3 变压器的选择·······································(12)
负荷级别
备 注
矿场油库(管输)
仪表电源
一级
输油泵、电动阀、污油泵、污水泵
二级Hale Waihona Puke Baidu
管道首站的输油泵为一级
矿场油库(铁路外运)
仪表电源
一级
装车泵、电动阀、污油泵、污水泵
二级
3.1.6消防负荷的等级划分,执行GB 50183的有关规定。
3.2 供电要求
3.2.1一级负荷站、场供电要求:
a) 一级负荷站、场应采用双电源供电,有条件时,两个电源应引自不同的变电所或发电厂;无条件时,可由当地公共电网同一变电站不同母线段分别引出两个回路供电,但作为上级电源的变电站应具备至少两个电源线和至少两台主变压器、分列运行。
附录A延长油田股份有限公司电力建设应执行的
国家和行业主要技术规范·························(21)
一 总 则
1.1 为适应延长油田股份有限公司(以下简称“油田公司”)建设国内一流标准化大油田的需要,规范和指导公司电力建设工作,提高油田电力建设管理水平,特制定本建设标准。
1.2本建设标准适用于油田公司范围内10KV至110KV新建、扩建、改建电力工程,是编制电力建设方案和实施电力工程项目管理的依据。
3.1.2在一、二、三级负荷中,对供电连续性要求严格的用电负荷如机组控制系统、应急润滑油系统以及各站场的自控、通信用电按照不间断重要负荷考虑。
3.1.3油田油气集输各类站场的电力负荷等级划分如下:
a) 处理能力大于或等于30×104t/年的油气集中处理站、矿场油库(管输)、轻烃储库等用电负荷为一级。
b) 处理能力小于30×104t/年的油气集中处理站、矿场油库(铁路外运)、原油稳定站、接转站、放水站、注水站、污水处理站、配制站、原油脱水站、增压集气站、注气站、机械采油井排等用电负荷为二级。
c) 自喷油井、边远、零散的机械采油井、注入站、配水间、配汽间、分井计量站等为三级负荷。
3.1.4油田油气集输各类站场内用电设备负荷分级应符合表1的规定。
延长油田股份有限公司
电力建设标准
(征求意见稿)
动力装备部
二〇一一年十一月
前 言
按照延长油田股份有限公司加快建设国内一流标准化大油田的要求,公司动力装备部组织编写了延长油田股份公司《电力建设标准》。本标准是油田公司电力建设的指导性文件,适用于油田公司10KV至110KV新建、扩建、改建电力工程。
编制本标准时,参照了国家和行业有关电力建设方面的标准和规范,结合了油田公司多年来在电力建设方面的经验,并多次开会讨论,吸收了采油厂和有关专家的意见。
a) 除消防泵外的最大计算负荷与最大一台消防泵的计算负荷之和。
b) 消防设施的计算负荷与该变电所供电的一级负荷之和。
上述变压器在消防灭火时,其负荷率可达100%。
4.2油田负荷预测。
a) 用电负荷预测是进行油田电力网建设的重要基础工作,要重视和坚持原始用电资料的积累和收集工作,认真做好负荷预测工作。
二级
注水站
注水泵、润滑油泵、冷却水泵、电动阀
二级
对于边远地区0.4KV柱塞式电机的注水站内设备都按三级负荷考虑
聚合物配制站
外输泵、供水泵、分散装置、搅拌器
二级
排污泵
三级
聚合物注入站
注入泵
三级
注汽站
柱塞泵、供油泵(引风机、鼓风机)
二级
移动式注汽站为三级负荷
污水处理站
污油泵、污水泵、加药泵、搅拌机、电动阀
2.3 油田电力建设以油田整体开发方案为基本依据,依托地方区域电力网建设专用电力网,统一规划,资源共享,分期分批实施,避免重复建设。
2.4 积极开展风力、太阳能等可再生能源的推广应用工作和天然气、石油伴生气发电等油田开发副产品的回收利用工作。
三 电力负荷分级和供电要求
3.1 负荷分级
3.1.1原则:油田的电力负荷等级,根据《油气田变配电设计规范》(SY/T 0033-2009)有关规定,结合工程生产特点及中断供电造成的损失和影响程度划分。
表1 油田油气集输各类站场内主要工艺用电设备负荷等级
站场(或装置)名称
用电设备名称
负荷级别
备 注
原油稳定装置
原油稳定泵、轻油泵、压缩机、空压机、仪表控制电源
一级
进料泵、污油泵、污水泵、塔底泵、空冷器
二级
轻油接转
空压机
一级
轻油外输泵、加药泵
二级
轻烃储库
轻烃泵、天然气压缩机、空压机、消防泵
一级
乙二醇水溶液循环泵
d) 根据供电的需要,变、配电所可设置备用电源自动投入装置。
3.2.2二级负荷站、场供电要求:
a) 二级负荷站、场宜采用双回路供电。当采用两回线路供电确有困难,在工艺上设有停电安全措施或有备用电源时,可由一回专用架空线路或专用电缆供电。
b) 二级负荷站、场内的变、配电所在技术经济上合理时,也可采用自动投入装置。
本建设标准系初次编制,在施行过程中,请各单位注意总结经验,积累资料,如发现需要修改和补充之处,请将意见送至延长油田股份有限公司动力装备部,以便今后修订时参考。
本标准的附录A为资料性附录。
本标准由延长油田股份有限公司动力装备部提出、起草并负责解释。
2011年11月
一总则·················································(1)
三级
污水回灌站
回灌泵
二级
污水提升站
污水提升泵
三级
工业锅炉房
上水泵、鼓风机、引风机、盐泵、燃料油泵、火嘴
二级
注:对于油田油气处理能力小于30×104t/年的二级电力负荷站场,表中一级负荷用电设备降为二级负荷
3.1.5矿场油库主要用电设备负荷分级应符合表2的规定。
表2 油库主要用电设备负荷等级
站场名称
用电设备名称
b) 油田不同的开发阶段均应进行负荷预测,作为相应阶段油田电力网建设的基础数据。油田最终用电负荷大小应以油田总体开发方案确定的生产规模作为预测的基础。
c) 目前油田用电负荷预测的主要方法是原油生产综合用电单耗法和用电量增长趋势预测法。
五 供配电系统
5.1 定义
油田供配电系统是指油田供电网和油田配电网组成的电力网络。油田供电网是指由110KV、35KV输变电系统组成的电力网络。油田配电网是指由油田10KV线路、10KV配电变压器和0.4/0.22KV低压线路所组成的电力网络。
八10KV线路············································(17)九 井场配电装置········································(18)
十 节电················································(19)
5.4 系统接线············································(8)
5.5 无功功率补偿·······································(9)
5.6 低压配电系统·······································(10)