巴基斯坦220kV自耦变压器英文招标书
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
SPECIFICATION P-169 : 83
(UDC 621. 314 . 2)
AUTO TRANSFRORMERS
PAKISTAN
WATER AND POWER DEVELOPMENT AUTHORITY DESIGN DEPARTMENT (POWER)
SPECIFICATION P-169 : 83
AUTO TRANSFRORMERS
AMENDMENT NO. 2 DATED 30TH SEPTEMBER, 1986
Sub Clause 6.1.1 Replace the existing clause with the following:-
6.1.1 The 220 & 132 kV Bushings shall be oil filled or of the condenser type
and shall be manufactured and tested in accordance with IEC Publication
137 (1973).
Add the following new sub clause :-
6.1.9 Arcing horns shall not be fitted on the bushings unless specified in the
tender.
SPECIFICATION P-169 : 83
AUTO TRANSFRORMERS
AMENDMENT NO. 1 DATED 10TH MARCH, 1986
1. Table-I, Sr. No. 4, Page - 5
Item 4 line 2 may please be amended to read as follows:
“Cooling with 55 degC Winding”.
2. Table-I, Sr. No. 23, Page - 8
(I) Item (i) (a), (ii) (a) and (iii) (a, b) the existing ratios under column 3 and 4 may
please be replaced with the following :
Column-3Column-4
i) (a) 2 x 600 / 1-1 2 x 1200 / 1-1
ii) (a) 2 x 600 / 1-1 2 x 1200 / 1-1
iii) (a) + (b) 2 x 600 / 1-1 2 x 1200 / 1-1 (II) Item (iv) (a), (b) and (c), the existing ratio under column 3 and 4 may please be replaced with the following :
iv) (a) 1200 / 1-1 2400 / 1-1
(b) 2 2
(c) 3 1
3. Sub-Clause 9.1.2 Page - 29
Third line of this clause may please be amended to read as follows :
“and a pressure of 0.4 kg / sq. cm. additional to that present”.
4. Sub-Clause 11.2 Page - 35
The existing sub clause 11.2 may please be replaced with the following :-
“11.2In the evaluation of tenders for Auto Transformers, the following rates shall be used for the capitalization of transformer losses and auxiliary power in fans.
Capital cost of no-load losses = US$ 1750 per kilowatt
Capital cost of load losses = US$ 900 per kilowatt
Capital cost of auxiliary power = US$ 900 per kilowatt
5. Sub-Clause 11.3, Page - 35
The existing sub clause 11.3 may be replaced with the following :-
6. Sub-Clause 13.2, Page – 41
Pleas e add “Auxiliary Power of fans “after the word “losses”.
7. Sub-Clause 16.4, Sr. No. 43 to 47, Page – 59 & 60
The additions / amendments of items under serial No. 43 to 47 may please be incorporated as given in the attached Sheets 1 to 4.
42) Tertiary Bushing Current Transformers:
a) Number _______________
b) Ratio _______________
c) Accuracy Class _______________
d) Accuracy Limit Factor _______________
e) Rated burden _______________VA
f) Short time thermal current _______________kA
g) Continuous thermal current _______________kA
h) Dynamic current _______________kA
i) Resistance of secondary winding _______________Ohms
j) No. of Cores _______________
k) Limits of temperature rise _______________o C
43) Type of on-load tapchanger (catalogue and data
to be supplied with tender).
a) Manufacturer country of origin _______________
b) Type designation _______________
c) Rated through current _______________Amperes
d) Step voltage _______________Volt
e) Number of steps _______________VA
f) Type of basic connection of tap winding
- Linear _______________
- Reversing switch _______________
- Coarse _______________
g) Catalogue No. _______________
h) Motor drive :
1) Type _______________
2) Supply voltage _______________Volts
3) H. P. _______________
4) Insulation level voltage to earth _______________kV rms
5) Catalogue No. _______________
i) Insulation levels:
1) Voltage to earth _______________kV rms
2) Impulse test voltage _______________kV rms
3) One minute power frequency test
voltage (50 Hz) _______________kV rms