Intouch 怎样用DASSIDirect with Siemens S7-200 PLC 通讯

合集下载
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

Configure the S7-200 PLC

1.Start Step7-Micro/Win 3

2. Create a new project or load your existing one

(Figure 1 below):

F IGURE 1:S TEP 7-M ICRO/WIN32-P ROJECT1D IALO

G B OX

2.Click on Tools and then select Ethernet Wizard.

3.Step through the wizard:

F IGURE 2:E THERNET W IZARD

4.Click Yes when asked to use symbolic addressing. Otherwise the wizard

cannot continue:

F IGURE 3:C LICK Y ES

5.Enter the module position of the CP243-1.

If you are uncertain about the position, click the button Read Modules.

Otherwise you can enter the number directly:

F IGURE 4:S PECIFY M ODULE P OSITION D IALO

G B OX

6.Enter the IP configuration of your CP243-1.

Especially during the startup phase of the project, I would recommend not to use a BOOTP server.

Let the module detect the connection type (Figure 5 below):

F IGURE 5:M ODULE A DDRESS C ONFIGURATION

7.Enter the numbers of connections you want to configure for the CP243-1.

Default value is 0, which would not allow communication. In this example

I will use 2 connections (Figure 6 below):

F IGURE 6:2C ONNECTIONS

Now you have to configure the connections. Connection 0 (Figure 7

below) will accept all incoming client requests:

F IGURE 7:C ONNECTION C ONFIGURATION

8.Always select This is a Server Connection. I recommend using the

default TSAP's as suggested by Step7-Micro/Win32.

9.Click Next Connection (or Prev. Connection if available) to step

through all the connections to configure them.

Note: If you plan to use such a connection, be sure that only one client tries to connect to the PLC via this connection at the same time. All other connection tries will be rejected.

Connection 1 accepts only requests from the specified client:

F IGURE 8:S PECIFIED C LIENT R EQUESTS

10.If all connections are configured click OK.

During the startup phase of a project I would recommend not to use a CRC protection:

F IGURE 9:N O CRC P ROTECTION

The wizard now needs a range in the V-Memory where to store this

information. Step7-Micro/Win32 will suggest a valid range.

11.Click on Suggest Address if you have planned to use this range for

something else.

In this case Step7-Micro/Win32 will suggest another free range that has the correct size to hold this data:

F IGURE 10:S TORE M EMORY A LLOCATION FOR A DDRESS

12.Click Next.

The program now has enough information:

F IGURE 11:

G ENERATE P ROJECT C OMPONENTS

13.Click Finish to complete the configuration:

相关文档
最新文档