C O M P O N E N T S
High-Speed DC Circuit-Breakersfor Industry
Type UR6 and UR15
The UR6and UR15are DC high-speed current-limitingcircuit-breakers with natural cooling, trip free, singlepole, bi-directional, with electromagnetic blow-out,electric control circuits and direct over-current instanta-neous release.The UR6 and UR15 circuit-breakersare of open typeconstruction.
Their simple design and high insulation level combinedwith their compliance to IEC60947 standard for industry,EN50123/ IEC61992 standards for fixed installationsand EN/IEC60077 standard for rolling stock (more
severe for what concerns the mechanical enduranceand the vibrations & shocks, guarantee tothe UR6 andUR15 a very high reliability and an exceptionally long lifetime.
With its proven worldwide experience and acceptance,Sécheron's range of circuit-breakers offers you the keyproduct for such a strategic and critical application thatis to guarantee the highest safety to your equipment aswell as to the people operating it and using it.
Applications
●
Utilisation category A
Main features
●●●●●●●●●●●●●
Rated thermal current 1500 A
Rated operational voltage 900 Vdc and 1800 VdcRated insulation voltage 2300 Vdc
Safe with a high insulation level: over-voltage category OV4Pollution degree PD3
Limited maximum arc voltage
Electro-magnetic closing and reduced holding power
High mechanical and electrical endurance: operational frequency C3Very low maintenance requirementsCompact and light weight
Proven design with worldwide experience and acceptanceInsulation material according to relevant NF standardDesign according to according to IEC60947-2 standard
2
Breaking current parameters
I ss =Short-circuit currentÎ=Peak of Iss
ss I d =Setting of maximum current releaseÎd =Cut off current
di/dt=Initial current rate of riseT =Circuit time constant
U e =Rated operational voltageÛarc =Peak of the arc voltaget m =Opening timet b =Total break time
Opening time
Relationship between opening time tm and the initial rate of rise of current di/dt for direct over-current instantaneousrelease.
Example for an initial rate of rise of current of 2. 106A/s: the openingtime is about 2.8 ms.
t m 8[ms]
76543216di/dt [A/s]
3
Designation code (standard version
●
●●
●●
Be sure to establish the designation code from our latest version of the brochure by downloading it from our website“”.
Be careful to write down 20 digits for the type designation code when placing your order.
The bold part of this designation code defines the device type and the complete designation defines the identificationnumber of the product, as they are displayed on the identification plate attached to the product.The customer shall write down the setting value Ids in its order form.
It can happen that for technical reasons, some configurations of variants and options indicated in the designationcode cannot be combined.
(1Silver contact: Imin = 10 mA
4
Technical data
Symbol
Unit
UR6
UR15
MAIN CIRCUIT
Rated operational voltage
U e
[Vdc]
- Arc chute type 31 and 41900900- Arc chute type 32 and 4218001800Rated insulation voltage
U i [Vdc]23002300Rated impulse withstand voltageU imp [kVdc]1818Rated service current (Tamb =+40°C
I n [A]10001500Conventional free air thermal current (Tamb =+40°CI th /Ithe [A]10001500Service short-circuit breaking capacityI cs /To
[kA]/[ms]30/1530/15Ultimate short-circuit breaking capacityI cu /To [kA]/[ms]
30/1530/15Operational frequencyC3C3Over-voltage category
OV4OV4Direct over-current instantaneous release
[kA]0.45 - 0.9-[kA]0.6 - 1.2-[kA]0.9 - 1.80.9 - 1.8[kA]1.2 - 2.41.2 - 2.4
[kA]1.5 - 3.2
-[kA]
-1.8 - 3.6Maximum arc voltage x Unm line *
Ûarc 0.9 - 2.5
0.9 - 2.5
Power frequency voltage withstand levelU a
- Between opened main contact[kV]8- Between closed main contact and earth & control circuit[kV]10- Between low voltage circuits and earth[kV]2
* Unm line: rated insulation voltage of the line; Ûarc = 1200 Vdc for network 750 Vdc; Ûarc = 2300 Vdc for network 1500 VdcCONTROL CIRCUIT
Nominal voltage (voltage range: from -15% to +10%U n [Vdc]24, 36, 48, 72, 87, 96, 110, 220
Nominal closing power (Tamb =+20°C
P c
[W]/[s]835/1Nominal holding power for electric holding (Tamb
=+20°C[W]2.5Nominal opening power for electric holding (Tamb =+20°C[W]0Nominal holding power for magnetic holding (Tamb =+20°C[W]0Nominal opening power for magnetic holding (Tamb =+20°C[W]/[s]35/1Mechanical opening time* at Un and Tamb =+20°Ct o [ms]5 - 10Mechanical closing time* at Un and Tamb =+20°C
t c
[ms]~ 70
* After the signal has been received by the closing coil
AUXILIARY CONTACTS CIRCUITNumber of contacts
2a(NO+2b(NC or 6a(NO+6b(NC
Rated voltage (potential free contacts[Vdc]24 to 110
Rated current
[A]10
Maximum breaking current
- Ohmic load at 110 Vdc
[A]1- Inductive load τ = 15 ms at 110 Vdc[A]0.3Minimum let-through current at 24 Vdc*[mA]
10
*For a dry and clean environment OPERATING CONDITIONSAmbient temperature
T amb [°C]-25 to +70
Minimum mechanical durabilityN
Operations
360 o/h without current
Altitude [m]
<2000Humidity
Class 5K2Pollution degree
PD3
5
Main dimensions Circuit-breakers weights UR 15-41I [kg] 29 UR 15-42I 39 40 900 V = 165 1800 V = 305 M16 135(2 9 20 180 67.5 14 42.5 20 60(1 65 115 30 130 190 420 30 115 10 40 145 165 10 (1 Space needed for the removal of the arc chute (2 Space needed for the removal of the auxiliary box Insulating distances Minimum insulating distances to: Insulating wall Earth (metal wall A 90 350 B 55 200 C 0 150 C A 420 A 90 B 165 B 6
Options (subject to additional costs Type designation Description Nominal control voltage (1 UR 15 41 I D - Z Z Z Z Z G 2 M B 1 2 Designation Code 87 Vdc 96 Vdc G H N 2 M 1 2 3 4 Varistor on coil Holding type Indirect release Auxiliary contacts (2 No Yes (rectified double vawes Magnetic BIM 1 Silver 6a (NO + 6b (NC Gold 2a (NO + 2b (NC Gold 6a (NO + 6b (NC (1 Only possible with holding type electric E (2 Imin = 10 mA for silver contact; Imin = 4 mA for gold contact. Indirect and manual release - BIM 1 The indirect release enables to shorten the opening time between 2.0~3.5 ms when required by specific application. The indirect release has to be controlled by a control unit type CID-3 (not included in the circuit-breaker - to be ordered separately. This device can also be manually activated. 7
SG104146BEN_A01-07.08 Sécheron SA Rue du Pré-Bouvier 25 1217 Meyrin - Geneva CH-Switzerland Tel: +41 (022 739 41 11 Fax: +41 (022 739 48 11
info@ This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the product, whose characteristics are described in these documents, as required by new technology at any time. It is the purchaser's responsibility to inform himself, no matter what the circumstances, of the product's maintenance conditions and requirements. Sécheron reserves all rights, especially those arising from our "General Delivery Conditions". Copyright© 2008