220kV变电站电气一次部分毕业设计论文毕业设计(论文)课题名称220kV变电站电气一次部分初步设计学生姓名学号系、专业电气工程系、电气工程及其自动化指导教师职称内容提要本次设计为220kV变电站电气一次部分的初步设计。
根据原始资料,以设计任务书和国家及行业有关电力工程设计的规程规范为设计依据,并结合该地区实际情况设计该变电站,设计的内容符合国家有关经济技术政策,所选设备全部为国家推荐的新型产品,技术先进、运行可靠、经济合理。
本期该变电站设有两台主变压器,远期该变电站设有三台主变压器。
站内主接线分为220kV、110kV和10kV三个电压等级。
设计正文分设计说明书和设计计算书两个部分,设计说明书包括电气主接线设计、变压器选择说明、短路电流计算说明、电气设备选择说明、配电装置设计、电气总平面布置和防雷保护设计;设计计算书包括变压器选择、短路电流计算、电气设备选择及校验等,并附有电气主接线图及其它相关图纸。
关键词:220kV变电站;短路计算;主接线;设备选择。
SummaryThe design of 220 kV substation electrical part of the preliminary design at a time. According to the original data, a design specification and country and industry relevant power engineering design procedure specification for design basis, and combined with the region's actual condition, the design of the substation design in conformity with the relevant economic and technological policies of the state, the contents of the selected equipment for all countries recommend new products, advanced technology, reliable operation, economic and reasonable.. The substation is equipped with two sets of the main transformer, forward the has three main transformer substation. station connection is divided into 220 kV, 110 kV and 10 kV voltage grade three.This text points design specifications and design calculation of two parts, the design specifications, including the main electrical wiring design of transformer selection, the short circuit current calculation, electrical equipment selection, design of power distribution equipment, electrical total plane layout and lightning protection design; Design calculation includes the choice of transformer, the short-circuit current calculation, electrical equipment selection and calibration, etc., with the main electrical wiring diagram and related drawings.Key words: 220 kV substation; Short circuit calculation; The main wiring; Equipment selection.目录内容摘要 (I)Summary (II)第一部分设计说明书1 原始资料 (1)1.1 建站的必要性 (1)1.2 系统接入方式 (1)1.3 变电工程规模 (2)1.4变电站站址选择 (2)1.5系统短路阻抗及本期出线潮流估计 (2)2 变压器选择 (5)2.1 主变压器选择 (5)3 电气主接线设计 (9)3.1 主接线设计的原则和要求 (9)3.2 主接线基本接线方式 (9)3.3 主接线设计步骤 (10)3.4 本站主接线设计方案 (11)4 短路电流计算说明 (18)4.1 短路电流计算概述 (18)4.2 常见短路电流计算 (19)4.3 短路电流计算结果 (21)5 高压电器设备选择 (23)5.1 电气设备选择一般条件 (23)5.2 高压断路器的选择 (24)5.3 隔离开关的选择 (26)5.4 互感器的选择 (27)5.5 母线的选择 (28)6 配电装置设计 (29)6.1配电装置应满足以下基本要求 (29)6.2配电装置设计的基本步骤 (29)6.3配电装置的种类及应用 (29)6.4本变电站配电装置设计 (29)7 防雷保护设计 (31)7.1变电站防雷保护的特点 (31)7.2防雷防护类型 (31)第二部分设计计算书8 短路电流计算 (33)8.1 等值电路计算 (33)8.2 对称短路电流计算 (34)8.2 不对称短路电流计算 (43)9 电气设备选择及校验计算 (51)9.1 高压断路器选择及校验计算 (51)9.2 隔离开关选择及校验计算 (53)9.3 互感器选择及校验计算 (54)9.4 母线选择及校验计算 (55)10 防雷保护计算 (58)总结 (59)参考文献 (60)致谢 (62)第一部分设计说明书1 原始资料1.1 建站的必要性考虑到目前花垣县供电现状及将来的网络发展格局,提高了电源外送和用户供电的可靠性,加强了地区220KV电网,新建花垣220KV变电站主要为地区中间变电站,给花垣县供电并为保靖、水顺、龙山4县水电外送提供接入点。
110kV变电站电气一次系统设计毕业设计(论文)
毕业设计论文110KV变电所电气一次部分初步设计毕业设计(论文)原创性声明和使用授权说明原创性声明本人郑重承诺:所呈交的毕业设计(论文),是我个人在指导教师的指导下进行的研究工作及取得的成果。
尽我所知,除文中特别加以标注和致谢的地方外,不包含其他人或组织已经发表或公布过的研究成果,也不包含我为获得及其它教育机构的学位或学历而使用过的材料。
对本研究提供过帮助和做出过贡献的个人或集体,均已在文中作了明确的说明并表示了谢意。
作者签名:日期:指导教师签名:日期:使用授权说明本人完全了解大学关于收集、保存、使用毕业设计(论文)的规定,即:按照学校要求提交毕业设计(论文)的印刷本和电子版本;学校有权保存毕业设计(论文)的印刷本和电子版,并提供目录检索与阅览服务;学校可以采用影印、缩印、数字化或其它复制手段保存论文;在不以赢利为目的前提下,学校可以公布论文的部分或全部内容。
作者签名:日期:学位论文原创性声明本人郑重声明:所呈交的论文是本人在导师的指导下独立进行研究所取得的研究成果。
除了文中特别加以标注引用的内容外,本论文不包含任何其他个人或集体已经发表或撰写的成果作品。
对本文的研究做出重要贡献的个人和集体,均已在文中以明确方式标明。
本人完全意识到本声明的法律后果由本人承担。
作者签名:日期:年月日学位论文版权使用授权书本学位论文作者完全了解学校有关保留、使用学位论文的规定,同意学校保留并向国家有关部门或机构送交论文的复印件和电子版,允许论文被查阅和借阅。
本人授权大学可以将本学位论文的全部或部分内容编入有关数据库进行检索,可以采用影印、缩印或扫描等复制手段保存和汇编本学位论文。
涉密论文按学校规定处理。
作者签名:日期:年月日导师签名:日期:年月日注意事项1.设计(论文)的内容包括:1)封面(按教务处制定的标准封面格式制作)2)原创性声明3)中文摘要(300字左右)、关键词4)外文摘要、关键词5)目次页(附件不统一编入)6)论文主体部分:引言(或绪论)、正文、结论7)参考文献8)致谢9)附录(对论文支持必要时)2.论文字数要求:理工类设计(论文)正文字数不少于1万字(不包括图纸、程序清单等),文科类论文正文字数不少于1.2万字。
110 35 10KV变电所一次系统设计 毕业论文
成人教育毕业设计(论文) 论文题目:110/35/10KV变电所一次系统设计年级.专业.层次: 10 电力专升本学生姓名:学号 10720120函授站:保定电院指导教师姓名:2012年8月毕业设计任务书一、毕业设计题目:110/35/10kv变电所电气一次系统设计二、毕业设计工作起止时间:2012.6.11—2012.9.02三、毕业设计的内容要求:㈠设计内容要求:1 根据原始资料选择5-7种合理的电气主接线2 进行初步技术,经济比较,选择两种较好的电气主接线3 选择主变压器的容量和型号4 计算两种主接线的短路电流5 根据短路电流计算结果选择电器设备6 通过技术经济比较确定最佳方案7 防雷及接地系统设计8 屋内外配电装置设计和总平面布置9 绘制图纸:电气主接线,电器总平面布置,防雷与接地各一张,配电装置断面图3-4张㈡设计成果:1 收设计说明书一份2 计算书一份(短路电流,设备教研,运行费,防雷校验等计算)3 图纸5-7张(电气主接线图,电气总平面布置图,屋外配电装置断面图,屋内配电装置配置图,防雷校验图等)四、原始数据和参考资料:㈠原始资料:1 变电所类型:110kv降压变电所2 电压等级:110/35/10kv3 负荷情况:35kv侧:最大负荷25MW,最小负荷18MW,Tmax=5300小时,cosφ=0.8510kv侧:最大负荷18MW,最小负荷12MW,Tmax=5300小时,cosφ=0.85负荷性质:工农业生产及城乡生活用电4 出现情况:110kv侧:2回(架空线)LGJ-185/25km35kv侧:4回(架空线)10kv侧:10回(电缆)5 系统情况:系统经双回线给变电所供电系统110kv母线短路电流标幺值为25(Sb=100MV A)6 环境条件最高温度40℃,最低温度-25℃,年平均温度20℃土壤电阻率ρ﹤400欧米当地雷暴日40日/年㈡参考资料:1 发电厂电气部分(第二版)四川联合大学2 发电厂电气部分课程设计参考资料天津大学3 电力工程设计手册(1、3、4分册)东北西北电力设计院4 发电厂变电所电气主接线和布置西北电力设计院5 发电厂变电所电气主接线设计西安交通大学摘要本文首先根据任务书上所给系统与线路及所有负荷的参数,分析负荷发展趋势。
(完整版)火电厂电气一次部分毕业设计论文
题目:火电厂电气一次部分毕业设计学院:信息电子技术学院年级:专业:电气工程及其自动化姓名:学号:摘要发电厂是电力系统的重要组成部分,也直接影响整个电力系统的安全与运行。
在发电厂中,一次接线和二次接线都是其电气部分的重要组成部分。
本设计是电气工程及其自动化专业学生毕业前的一次综合设计,它是将本专业所学知识进行的一次系统的回顾和综合的利用。
设计中将主要从理论上在电气主接线设计,短路电流计算,电气设备的选择,配电装置的布局,防雷设计,发电机、变压器和母线的继电保护等方面做详尽的论述,并与三河火力发电厂现行运行情况比较,同时,在保证设计可靠性的前提下,还要兼顾经济性和灵活性,通过计算论证该火电厂实际设计的合理性与经济性。
在计算和论证的过程中,结合新编电气工程手册规范,采用CAD软件绘制了大量电气图,进一步完善了设计。
关键字主接线设计;短路电流;配电装置;电气设备选择;继电保护Power plants is an important part of power system, and also affect the safety of the whole power system with operation. In power plant, a wiring and secondary wiring is the important part of electrical part.This design is the electrical engineering and automation of professional students before graduation design, it is a comprehensive professional knowledge learnt this a systematic review and comprehensive utilization. Design mainly from theory will in the main electrical wiring design, short-circuit current calculation, electrical equipment choice, power distribution equipment layout, lightning protection design, generator, transformer and busbar protection etc, and a detailed discussion with the current operation sanhe coal-fired power plants, meanwhile, in comparison to ensure that the design reliability premise, even give attention to two or morethings economy and flexibility, through calculation demonstrates that the practical rationality of the design of power with economy. In the process of calculation and argumentation, combined with the new electric engineering manuals, using CAD software standard drawing a lot of electrical diagrams, further improve the design.Keywords Lord wiring design; Short-circuit current; Distribution device; Electrical equipment selection; Relay protection摘要........................................................................................................................................................ Abstract...................................................................................................................................................第 1 章绪论....................................................................................................................................1.1课题背景 .......................................................................................................................................1.1.1社会背景.................................................................................................................................1.2课题研究的目的和意义................................................................................................................1.3国内外研究现状 ...........................................................................................................................1.4课题的主要研究工作 ...................................................................................................................第 2 章电气主接线设计..................................................................................................................2.1电气主接线的设计原则及要求....................................................................................................2.1.1明确任务和设计原理.............................................................................................................2.2方案的设计、论证和选择............................................................................................................2.3本章小结 .......................................................................................................................................第 3 章短路电流的计算..................................................................................................................3.1短路的原因、后果及形式............................................................................................................3.2短路的物理过程及计算方法........................................................................................................3.3短路电流的计算数据和计算结果................................................................................................第 4 章电气设备的选择..................................................................................................................4.1主变压器和发电机的选择............................................................................................................4.2高低压电气设备的选择................................................................................................................4.3导体的设计和选择 .......................................................................................................................第 5 章配电装置..............................................................................................................................5.1屋外配电装置 ...............................................................................................................................5.2屋内配电装置 ...............................................................................................................................第 6 章继电保护..............................................................................................................................6.1发电机的保护 ...............................................................................................................................6.2变压器的保护 ...............................................................................................................................6.3母线保护 .......................................................................................................................................6.4防直击雷保护 ...............................................................................................................................第7 章总结和展望..........................................................................................................................致谢........................................................................................................................................................参考文献..................................................................................................................................................附录A......................................................................................................................................................第 1 章绪论1.1 课题背景1.1.1 社会背景电力工业是国民经济的重要部门之一,是一种将煤,石油,天然气,水能,核能,风能等一次能源转换成电能这个二次能源的工业,作为国民经济的其他各部门的快速,稳定发展提供足够的动力,其发展水平是反映国家经济发达程度的重要标志,又和广大人民群众的日常生活有着密切的关系。
(完整版)水电站电气一次·某水电学院毕业设计论文
前言毕业是教学过程中的一个重要环节,通过设计可以巩固本专业理论知识,掌握供配电设计的基本方法,通过解决各种实际问题,培养独立分析和解决实际工程技术问题的能力,同时对电力工业的有关政策、方针、技术规程有一定的了解,在计算、绘图、设计说明书等方面得到训练,为今后的工作奠定基础。
本设计根据设计任务书可分为二大部分,第一部分为设计计算书,包括负荷计算、无功功率及补偿计算、短路电流的计算、设备选择及校验计算、配电变压器保护定值计算;第二部分为设计说明书,包括变电所位置和形式选择、变电所主接线设计、变电所主变压器台数和容量、变电所一次设备的选择与校验、变电所高、低压线路设计、变电所二次回路设计及继电保护的整定、防雷和接地装置设计;本设计基于本人掌握的供电知识基础,尚有正确和不完善的地方,敬请老师、同学指正!第一章毕业设计任务书1.1设计题目10KV降压变电所电气设计1.2设计目的毕业设计是完成本专业教学计划的最后一个重要的教学环节,是对各门课程的综合运用和提高。
通过毕业设计,巩固和加深学生所学专业理论知识,锻炼学生分析和解决实际工程问题能力。
培养和提高学生综合使用技术规范、技术资料,进行有关计算、设计、绘图和编写技术文件的初步技能,为今后参加水电站和变电所电气设计、安装、运行、检修、试验打下基础。
通过本毕业设计,初步掌握一个小型水电站工程设计的思想、内容、方法和步骤。
1.3有关的原始资料黄坪电站为低水头径流式水电站,座落于茶陵县虎踞镇黄坪村,距茶陵县城25km,装机容量5×1600 kw,年利用小水电网络规划和业主意向,电站出线等级为35kv,共三回路,一回路送到9km平水变并入茶陵县新组建小水电网,一回路送到近区新建的虎踞镇工业区,一回路备用。
其输电导线型号为LGJ-120。
1.4 设计的总体要求集中布置,明确要求,提倡讨论,独立完成,严禁抄袭,严禁拷贝现象。
第二章电气一次部分设计2.1 电气主接线方案的拟定分析设计原始资料,全面考虑所设计电站在系统中所处地位、所供负荷性质、地理位置以及电站本身的总容量和机组台数,拟出二至三个可行的方案,进行一般的技术经济比较,通过论证,确定一个合理的主接线方案。
110KV变电所电气一次部分设计论文
. . ..毕业论文系(部):水利水电工程系专业班级:10秋姓名:小龙学号:54目录毕业设计计算书2第一篇 110KV变电所电气一次部分设计2第一章负荷资料21.1、工程概况:21.2、气候条件2第二章变电站主变压器的选择32.1设计原则32.2主变容量与台数选择32.2.1 选择计算32.2.2.相数选择4绕组数量和连接方式的选择42.2.4 主变阻抗和调压方式选择42.2.5 容量比52.2.6 冷却方式52.2.7 电压级选择5全绝缘,半绝缘问题5. 资第三章电气主接线设计53.1电气主接线5电气主接线设计的基本要求5各电压级主接线型式选择63.2所用电设计7所用变电源数量及容量的确定73.2.2 所用电源引接方式83.3变压器中性点接地方式和中性点设计[4]83.4无功补偿设计8无功补偿的意义8无功补偿装置的容量确定8并联电容器装置的分组与接线9单台电容器容量与台数的确定9计算9第四章线路及变压器回路电流IFma*第五章短路电流计算95.1短路计算目的95.2短路电流计算的一般规定95.3短路电流的计算方法10第六章电气设备的选择与校验116.1本次设计中电器选择的主要任务11导体和绝缘子11电器设备116.2选择导体和电器的一般原则116.3 开关电器选择116.3.1 断路器型式选择116.3.2 隔离开关的选择原则126.3.3 电压互感器的选择原则12电流互感器选择原则126.4电气设备的选择12第二篇**巴楚县110kV变电所二次设计部分设计21第七章概述217.1 继电保护装置的作用[9]217.2电力系统对继电保护的基本要求[10]217.3 保护整定时应考虑的问题22选择保护配置及构成方案时的基本原则227.3.2 系统运行方式的确定227.3.3 短路点的确定22第八章**巴楚县110kV变电所保护配置方案设计238.1主变压器保护配置方案的设计23第九章变压器差动保护整定与计算239.1差动保护保护围239.2 变压器保护的整定计算[11]239.2.1确定保护的动作电流239.2.2 确定保护的二动作电流和差动线圈匝数249.2.3非基本侧工作线圈和平衡线圈匝数选择24 总结24参考文献25致25毕业设计计算书第一篇 110KV变电所电气一次部分设计第一章负荷资料1.1、工程概况:随着改革开放政策的深放,城市化发展,各工商业用电也在不断的增长。
毕业论文110kv降压变电所电气一次系统设计
毕业设计(论文) `题目110kV降压变电所电气一次系统设计:110/35/10kV,进出线数2/7/9院系电力工程系专业班级农电08k2班学生姓名周笑天指导教师赵飞二○一二年六月110kV降压变电所电气一次系统设计(110/35/10kV,进出线数2/7/9)摘要变电所是电力系统的重要组成部分,其作用在于变换电压、汇集和分配电能,因此,变电所安全可靠运行与国民经济的发展密切相关。
随着电力系统装机容量和供电地域的不断扩大,同时电能质量、供电可靠性、运行经济性的要求也越来越高。
随着现代文明的发展与进步,社会生产和生活对电能供应的质量和管理提出了越来越高的要求。
供电系统的核心部分是变电所。
因此,设计和建造一个安全、经济的变电所,是极为重要的。
本次设计建设一座110kV降压变电所,首先,根据主接线的经济可靠、运行灵活的要求选择各个电压等级的接线方式,在技术方面和经济方面进行比较,选取灵活的最优接线方式。
其次进行短路电流计算,根据各短路点计算出各点短路稳态电流和短路冲击电流,从三相短路计算中得到当短路发生在各电压等级的工作母线时,其短路稳态电流和冲击电流的值。
然后,根据各电压等级的额定电压和最大持续工作电流进行设备选择和校验。
最后进行配电装置设计和总平面布置,防雷保护的设计。
关键词:变电所;电气主接线;电气设备;防雷接地;配电装置A DESIGN OF ELETRIC MAIN SYSTEMFOR 110kV STEP-DOWN SUBSTATION(110/35/10kV, the number of inlet and outlet 2/7/9)AbstractSubstation is an important part of the power system, its role is to transform voltage, collection and distribution of electric energy, therefore, safe and reliable operation of substation and national economic development are closely related.With the regional power system and electricity installed capacity continues to expand at the same time power quality, supply reliability, operational economy demands increasingly high. Along with the electric power system installed capacity and power supply area continues to expand, at the same time, power quality, power supply reliability, economic operation requirements are also getting higher and higher .The core of the city power supply system is the substation. Therefore, the design and construction of a safe, economical substation, it is extremely important. The design and construction of a 110kV substation step-down, first of all, according to the main terminal of the economic and reliable operation and flexible asked to select various voltage levels of wiring, technical and economic aspects in the comparison, select the optimal flexible wiring. Second, the short-circuit current calculation, according to the short circuit short-circuit steady-state were calculated for each point of the impact of current and short circuit current, calculated from the three-phase short circuit obtained when the voltage level in the work of the bus, its steady-state current and the impact of short-circuit current value. Then, we according to the voltage level of the rated voltage and maximum continuous operating current of equipment selection and validation. Finally, electrical installations and the general layout, lightning protection design.Keywords: Transformer substation; Main connection; Electric equipment; Lightning proof protection and earth system; Distribution equipment目录摘要 (I)Abstract (II)1 前言 (1)2 变压器的选择 (2)2.1 变电站主变压器选择的规定 (2)2.2 主变压器选择的一般原则与步骤 (2)2.2.1 主变压器台数的确定原则 (2)2.2.2 主变压器形式的选择原则 (2)2.2.3 主变压器容量的确定原则 (2)2.3 主变压器的计算与选择 (3)2.3.1 容量计算 (3)2.3.2 变压器型号的选择 (3)3 电气主接线的设计 (4)3.1 概述 (4)3.2 主接线方式的简介 (4)3.3主接线设计的基本要求 (6)3.3.1 主接线可靠性的要求 (6)3.3.2 主接线灵活性的要求 (6)3.3.3 主接线经济性的要求 (6)3.4 电气主接线的选择和比较 (7)3.4.1 主接线方案的拟订 (7)3.4.2 主接线各方案的讨论比较 (9)3.4.3 主接线方案的最终选择 (10)4 短路电流的计算 (11)4.1 概述 (11)4.2 短路电流计算的目的及原则 (11)4.3 计算步骤 (11)4.4 压器及电抗器的参数计算 (12)4.4.1 主变压器参数计算 (12)4.4.2 线路等值电抗 (12)4.5 变电站网络化简 (12)4.5.1 短路点d1的短路计算(主变110kV侧) (13)4.5.2 短路点d2的短路计算(35kV母线) (13)4.5.3 短路点d3的短路计算(10kV母线) (13)5 导体和电气设备的选择和设计 (14)5.1 断路器的选择 (15)5.1.1 断路器选择原则与技术条件 (15)5.1.2 断路器型号的选择及校验 (16)5.2 隔离开关的选择 (18)5.2.1 隔离开关的选择原则及技术条件 (18)5.2.2 隔离开关型号的选择及校验 (19)5.3 电流互感器的选择 (20)5.3.1 110kV侧电流互感器的选择 (21)5.3.2 35kV电压等级电流互感器的选择 (21)5.3.3 10kV电压等级电流互感器的选择 (21)5.4 电压互感器的选择 (23)5.4.1 110kV侧母线上电压互感器 (23)5.4.2 35kV侧母线上电压互感器 (23)5.4.3 10kV侧母线上电压互感器 (23)5.5 高压熔断器的选择 (23)5.6 导线的选择 (24)5.6.1 110kV侧母线桥的选择 (24)5.6.2 35kV侧母线的选择 (25)5.6.3 35kV侧出线的选择 (25)5.6.4 35kV侧变压器回路的选择 (25)5.6.5 10kV侧母线的选择 (26)5.6.6 10kV侧出线的选择 (26)5.6.7 10kV侧变压器回路的选择 (27)5.7 站用变压器的选择 (27)5.8 绝缘子的选择 (27)6 屋内外配电装置设计和总平面布置 (28)6.1 概述 (28)6.2 配电装置形式的设计 (29)6.2.1 屋内配电装置 (29)6.2.2 屋外配电装置 (29)7 防雷保护设计 (31)7.1 概述 (31)7.2 避雷装置的配置原则 (32)7.2.1 避雷器的配置原则 (32)7.2.2 避雷针的配置原则 (32)7.3 避雷器的选择 (32)7.3.1 110kV侧避雷器的选择和校验 (32)7.3.2 35kV侧避雷器的选择和校验 (33)7.3.3 10kV侧避雷器的选择和校验 (33)7.4 避雷针的设计 (34)7.4.1 避雷针的作用 (34)7.4.2 避雷针的保护范围及计算 (34)8 接地系统的设计 (35)8.1 设计说明 (35)8.2 接地体的设计 (36)8.3 接地网间距的设计及选择 (36)结论 (37)参考文献 (38)致谢 (39)1 前言变电所是联系电网的纽带,是电力系统中变换电压、接受和分配电能、控制电力的流向和调整电压的电力设施,主要是通过变压器将各级电压的电网联系起来,起着变换和分配电能的作用,其运行的可靠和安全与否直接关系到整个电网的安全运行。
毕业论文110KV变电所电气一次部分设计说明
华北电力大学成人教育学院毕业设计(论文)论文题目:110kV变电站电气一次系统设计专业: 电力系统及其自动化专业姓名: 猛学号:09201761函授站: 电力高等专科学校日期: 2011年08月30日110kV变电站电气一次系统设计摘要变电所是电力系统的重要组成部分,它直接影响整个电力系统的安全与经济运行,是联系发电厂和用户的中的间环节,起着变换和分配电能的作用。
电气主接线是发电厂变电所的主要环节,电气主接线拟定直接关系着全所电气设备的选择、配电装置的布置、继电保护和自动装置的确定,是变电站电气部分投资大小的决定性因素。
本次设计建设一座110kV降压变电站,首先,根据主接线的经济可靠、运行灵活的要求选择各个电压等级的接线方式,在技术方面和经济方面进行比较,选取灵活的最优接线方式。
其次,进行短路电流计算,根据各短路点计算出各点短路稳态电流和短路冲击电流。
最后,根据各电压等级的额定电压和最大持续工作电流进行设备选择,然后进行校验。
关键词: 变电所;变压器;电力负荷;电气主接线;短路电流;电气设备The Primary Design of 110 KV Transformer SubstationAbstractThe know-why the learns , real circumstances of this engineering of combination are used , the analysis conscientiously careful by way of to the primary sources , as well as short circuit calculation to decides on the scheme . The selection of the electric owner grasping the transformer substation wiring scheme , the mould selecting of major electric installation , the selection of main transformer platform number , capacity and model , as well as the various protections are surely calmly . Define finally this110 kV transformer substation electric owner's wiring diagram , and accomplishes the preliminary design to the 110KV transformer substation . Designing by way of this , I have had a more overall understanding to the design of transformer substation , and makes me learn , not only the reliability will fully be thought over in the engineering designation and the flexibility , and still more will give consideration to many things economy , long-range nature and technical .Key words :transformer substation ;transformer ;power load ;the electricity mainwiring ;the short-circuit current ;electricity equipment目录第一章设计任务书 (7)1.1设计资料 (7)1.1.1建所目的 (7)1.1.2环境条件: (7)1.1.3负荷资料 (7)1.2 设计要求 (8)1.2.1编写技术说明书 (8)1.2.2编写计算书 (8)1.2.3绘制图纸 (8)第二章设计说明书 (9)2.1、电气主接线设计 (9)2.1.1 电气主接线设计的原则 (9)2.1.2 电气主接线的设计程序 (9)2.1.3 主接线形式的选择 (11)2.2 主变压器的选择 (12)2.3 短路电流的计算及负荷计算 (13)2.3.1 短路电流计算的目的和条件 (13)2.3.2 短路时间的计算 (14)2.3.3 等效电路阻抗及短路电流的计算 (14)2.4、设备的选择与校验 (15)2.4.1 导体和电气设备选择的一般条件 (15)2.4.2设备选择 (16)2.5、防雷保护的确定及接地网的设计 (21)2.5.1避雷针的作用 (21)2.5.2防雷接地 (21)2.5.3防雷保护方案 (22)2.5.4地网的设计 (24)第三章计算书 (27)3.1 电力负荷的计算 (27)3.2、等效电路电抗的计算 (28)3.3、等效电路短路电流的计算 (28)3.4、设备的选择及校验 (32)3.4.1高压断路器 (32)3.4.2隔离开关 (34)3.4.3电流互感器 (36)3.4.4电压互感器 (38)3.4.5 导线 (38)结束语 (40)致语 (41)参考文献 (42)前言电能是现代工业生产的主要能源和核心动力。
发电厂电气一次系统设计-毕业论文
毕业设计(论文) 题目发电厂电气一次系统设计系别电力工程系专业班级电气07K1班学生姓名×××指导教师梁海平××××年六月发电厂电气一次系统设计摘要发电厂是电力系统中生产电能、控制电力的流向和调整电压的电力设施。
它通过其变压器将各级电压的电网联系起来,将电能输送出去。
本设计是对一高压侧110kV,2回出线;中压侧35kV,4回出线;低压侧10kV,12回出线的发电厂一次系统进行的初步设计。
该发电厂属于小型发电厂,它除承担向系统供应电能的任务外,还提供地区负荷。
本设计首先进行了原始资料的分析。
通过分析,了解该发电厂的类型、负荷情况等;然后,再依据发电厂的电压等级、出线数目及其负荷大小,拟定出多种接线方案,再通过初步技术和经济比较,确定一个最优方案;再根据选择主变的原理和所给的该发电厂各电压等级的最大负荷量,确定了主变容量、台数及型号;然后,选择各个短路点,进行短路电流计算,为下面的电气设备选择打下基础;再次,便是根据上述设计成果确定各电气设备,确定配电设备。
最后根据这地区的雷雨情况配置避雷与接地装置及配电装置,完成电气主接线、电气平面布置、防雷与接地图。
关键字:发电厂设计;短路计算;设备选择;防雷保护A DESIGN OF ELECTRIC MAIN SYSTEMFORPOWER STATIONAbstractPower Stations are producing electricity in the power system, controlling the power flow and adjusting the voltage. It will link all levels of voltage power grid through its transformer and will supply power to the transmission system.The tentative design is to the first system of the power station which has high-tension side 110kV, four output connections; middle-tension side 35kV, four output connections, low-tension side 10kV, twelve output connections. The power station belongs to one middle-size station. In addition to assume the supply of power to the power system also to content the region loads.The design has firstly been carried on the analysis of primary source. Passing through the analysis, we can understand the type of this power station, load condition and so on. Secondly, based on the voltage level of power station, load size and the number of outline, we can obtain a wide range of wiring, and then through the preliminary technical comparison, the two options identified. In the light of the principle of choosing main transformer,we can choose the main transformer’s number, capacity and type .Next, selecting each short circuit point and carrying on the calculation of short circuit current, it is the foundation that has been conquered in the selection of the electric installation of next. Then, based on the above results of designed we can determine the electrical equipment, through the economically optimal choosing the best plan and determining the distributed equipments of the power base on the design achievement mentioned above.According to the situation in this region of the thunderstorm, lightning protection and grounding device are configured. The final completion of the main electrical wiring, the electrical layout, lightning protection and access map are draw.Keywords: Power station design; Short current calculation; Equipment selection; Lightning Resistant protection; Distribution devic目录摘要 (I)Abstract (II)1 电气主接线选择 (1)1.1概述 (1)1.2主接线设计原则 (1)1.3主接线的接线方式选择 (1)1.3.1单母线接线 (1)1.3.2单母分段 (1)1.3.3双母接线 (2)1.3.4双母线分段接线 (2)1.3.5桥形接线 (2)1.3.6一个半断路器(3/2)接线 (2)1.4主接线线方案的比较选择 (3)1.4.1主接线方案 (3)1.4.2主接线方案选择 (7)2主变压器容量、台数及形式的选择 (8)2.1概述 (8)2.2主变压器的选择原则 (8)2.3主变压器容量和台数的确定原则 (8)2.4主变压器型式的选择 (8)2.5绕组数的选择 (9)2.6主变压器容量的选择 (9)3短路电流计算 (11)3.1 概述 (11)3.2短路计算的目的及假设 (11)3.2.1短路电流计算的目的 (11)3.2.2短路电流计算的一般规定 (11)3.2.3短路计算基本假设 (12)3.2.4基准值 (12)3.3 短路电流计算步骤 (12)3.4短路电流的计算 (13)3.4.1 各电气设备参数 (13)3.4.2短路电流的计算 (14)4电气设备的选择 (20)4.1概述 (20)4.1.1一般原则 (20)4.1.2技术条件 (20)4.2断路器的选择 (21)4.2.1按开断电流选择 (21)4.2.2短路关合电流的选择 (21)4.3隔离开关的选择 (22)4.4各电压等级的断路器、隔离开关的选择和校验 (22)4.4.1 110kV侧断路器、隔离开关的选择 (22)4.4.2 35kV侧断路器、隔离开关的选择 (23)4.4.3 10KV侧高压开关柜的选择 (24)5 经济技术比较 (26)5.1方案一的经济投资计算 (26)5.1.1 开关设备投资 (26)5.1.2 变压器投资 (26)5.1.3 配电装置综合投资 (26)5.1.4 10kV母线分段电抗器、出线电抗器投资: (26)5.1.5 综合投资及年运行费用计算 (26)5.2方案二的经济投资计算 (27)5.2.1 开关设备投资 (27)5.2.2 变压器投资 (28)5.2.3 配电装置综合投资 (28)5.2.4 10kV母线分段电抗器、出线电抗器投资: (28)5.2.5 综合投资及年运行费用计算 (28)5.3 两方案经济比较 (29)6 其它电气设备的选择 (30)6.1互感器的选择 (30)6.2电流互感器的选择 (30)6.2.1 110KV侧电流互感器的选择 (31)6.2.2 35KV侧电流互感器的选择 (32)6.3电压互感器的选择 (34)6.3.1 110KV电压互感器的选择 (34)6.3.2 35KV电压互感器的选择 (35)6.4导体的选择 (36)6.4.1裸导体的选择条件选择和校验 (36)6.4.2各电压等级的母线的选择 (36)6.4.2.1 35kV侧母线的选择 (36)6.4.2.2 10kv侧母线的选择 (38)6.4.3各电压等级出线的选择 (39)6.4.3.1 110kV侧出线的选择 (39)6.4.3.2 35kV侧出线的选择 (39)6.4.3.3 10kV侧电缆的选择 (40)6.5高压熔断器的选择 (41)6.6避雷器的选择 (42)6.6.1 110kV避雷器的选择及校验: (42)6.6.2 35kV避雷器的选择及校验: (43)6.6.3 10kV避雷器的选择及校验 (44)7电气总平面布置及配电装置的选择 (46)7.1概述 (46)7.2高压配电装置的选择 (46)8厂用电的接线设计 (50)8.1对厂用的设计的要求 (50)8.2厂用电电压 (50)8.3厂用母线接线方式 (50)8.4厂用工作电源 (50)8.5厂用备用或起动电源 (50)8.6交流事故保安电源 (50)8.7 厂用电接线.......................................... 错误!未定义书签。
变电站电气一次部分设计毕业设计论文
教师批阅第一章原始资料分析1.1 目的与意义变电站电气一次部分直接关系到变电站投资的大小、运行的灵活性、经济性及供电的可靠性,变电站电气一次部分设计是变电站设计最主要的设计工作之一。
同时,变电站电气一次部分设计综合了电气工程专业众多的专业课基础课。
因此,变电站电气一次部分设计可以锻炼学生综合运用所学知识提出问题、解决问题的能力。
变电站电气一次部分设计的目的在于使学生通过此次毕业设计,在如下几个方面得到充分训练。
(1) 结合毕业设计任务,加深对所学知识内在联系的理解,并能灵活地加以综合运用。
(2 )根据所学知识及毕业设计任务,学会提出问题、解决问题,最终将所学知识转化为能力。
(3) 通过毕业设计实践,熟悉工程设计的全过程,掌握工程设计的思想、方法、手段,树立必要的工程概念,培养一丝不苟的求实态度。
(4) 掌握资料收集、工程计算、工程技术图纸的绘制标准及绘制方法、设计报告的撰写1.2 原始资料教师批阅1.2.1 拟建变电所联网情况如下图1所示L1220kV S1Xc1S2Xc2L2L3110kV 10kV(预留)拟建变电所系统与线路参数表系统1 系统2 线路参数 S 1(MVA)x c1 S 2(MVA ) x c2 L 1(kM ) L 2(kM ) L 3(kM)第1组 2250.38 1800 .40 60 57 66第2组 2150.36 1850 .42 50 62 75第3组 2100.43 1780 .41 55 65 68第4组2300.421960 .39 65 68 501.2.2 地区环境条件年最高气温:40℃;年最低气温:-5℃;年平均气温:18℃ 出线方向:220kv 向北 110kv 向西 10kv 向东南1.2.3 负荷资料教师批阅(1)220kV线路3回,预留1回备用,架空线路型号选用LGJQ-300。
(2)110kV线路8回,其中2回留做备用,架空。
(3)10kv线路12回,另有2回备用,架空。
110KV变电站电气一次系统设计毕业论文.doc
110KV变电站电气一次系统设计毕业论文目录1主变压器的确定 (1)1.1主变压器台数的确定 (1)1.2调压方式的确定 (1)1.3主变压器容量的确定 (1)2电气主接线的确定 (3)2.1接线选择的主要原则 (3)2.2电气主接线的一般要求 (4)2.3拟定主接线方案 (4)2.4主接线方案的可靠性比较 (8)2.5主接线方案的灵活性比较 (9)2.6主接线方案的经济性比较 (9)2.7主接线方案的确定 (10)3短路电流计算 (11)3.1短路电流计算的目的 (11)3.2短路电流计算的一般规定 (12)3.3短路电流计算 (12)4设备的选择与校验 (18)4.1设备选择的原则和规定 (18)4.2导线的选择和校验 (20)4.3断路器的选择和校验 (26)4.4隔离开关的选择和校验 (29)4.5互感器的选择及校验 (31)4.6避雷器的选择及校验 (35)5屋内配电装置设计 (36)5.1配电装置的设计要求 (36)5.2配电装置的选型、布置 (38)6防雷及接地系统设计 (39)6.1防雷系统 (39)6.2变电所接地装置 (41)7变电所总体布置 (41)7.1总体规划 (41)7.2总平面布置 (42)8结论 (43)参考文献 (44)附录 (45)毕业设计(论文)正文1主变压器的确定1.1主变压器台数的确定为了保证供电的可靠性,变电所一般装设两台主变压器。
1.2调压方式的确定据设计任务书中:系统110KV母线电压满足常调压要求,且为了保证供电质量,电压必须维持在允许范围内,保持电压的稳定,所以应选择有载调压变压器。
1.3主变压器容量的确定主变压器容量一般按变电所建成后5~10年的规划负荷选择,亦要根据变电所所带负荷的性质和电网结构来确定主变压器的容量。
对装设两台主变压器的变电所,每台变压器容量应按下式选择:Sn=0.6P M。
因对一般性变电所,当一台主变压器停运时,其余变压器容量应能保证70~80%负荷的供电,考虑变压器的事故过负荷能力40%。
毕业论文 220kv变电站电气一次部分初步设计
毕业论文 220kv变电站电气一次部分初步设计编号毕业设计报告设计题目:220KV变电站电气一次部分初步设计姓名专业名称班级指导老师姓名:(姓名)(单位)报告提交日期:答辩日期:答辩委员会主席:评阅人:(日期)二0一0年四月毕业设计(论文)摘要电力工业是国民经济发展中最重要的基础能源产业,是国民经济的第一基础产业,是关系国计民生的基础产业,是世界各国经济发展战略中的优先发展重点。
作为一种先进的生产力和基础产业,电力行业对促进国民经济的发展和社会进步起到了重要作用。
与社会经济和社会发展有着十分密切的关系,它不仅是关系国家经济安全的战略大问题,而且与人们的日常生活、社会稳定密切相关。
本设计讨论的是220KV变电站电气部分的设计。
首先对原始资料进行分析,选择主变压器,在此基础上进行主接线设计,再进行短路计算,选择设备,然后进行防雷接地以及保护、配电装置设计。
关键字:变电站;短路计算;设备选择。
目录1 引言 (3)2 原始资料的分析……………………………………………………………42.1原始资料 (4)2..2原始资料分析………………………………………………………………53 变电站电气主接线的确定………………………………………………63.1电气主接线的概述 (6)3.2计算220kV侧的短路 (10)3.3变压器的选择……………………………………………………………………1 4 4所用电设计 (17)4.1所用变选择 (17)4.2所用电接线图 (17)5 短路电流计算…………………………………………………………19 5.1 作出系统的简化等值电路图 (19)5.2 系统的参数计算………………………………………………………………19 5.3 短路点的选择 (20)5.4 计算短路电流 (20)6 电气设备的选择……………………………………………………………3 1 6.1 变压器变压器的选择……………………………………………………………3 1 6.2 电抗器的选择 (31)6.3 主要电气设备的选择……………………………………………………………3 1 7 继电保护与自动装置………………………………………………………48 8 防雷保护与接地……………………………………………………………51 8.1防雷保护……………………………………………………………………51 8.2 避雷针防雷保护计算……………………………………………………………528.3 接地装置 (57)致谢………………………………………………………………………………58参考文献…………………………………………………………………………59心得………………………………………………………………………………60第1章引言电力事业的日益发展紧系着国计民生。
220kv变电站电气一次系统设计大学毕设论文
220kV变电站电气一次系统设计摘要变电站是电力系统的一个重要组成部分,由电器设备及配电网络按一定的接线方式所构成,他从电力系统取得电能,通过其变换、分配、输送与保护等功能,然后将电能安全、可靠、经济的输送到每一个用电设备的专设场所。
作为电能传输与控制的枢纽,变电站必须改变传统的设计和控制模式,才能适应现代电力系统、现代化工业生产和社会生活的发展趋势。
随着计算机技术、现代通讯和网络技术的发展,为目前变电站的监视、控制、保护和计量装置及系统分隔的状态提供了优化组合和系统集成的技术基础。
220kV变电站属于高压网络,该地区变电所所涉及方面多,考虑问题多,分析变电所担负的任务及用户负荷等情况,选择所址,利用用户数据进行负荷计算,确定用户无功功率补偿装置。
同时进行各种变压器的选择,从而确定变电站的接线方式,再进行短路电流计算,选择送配电网络及导线,进行短路电流计算。
选择变电站高低压电气设备,为变电站平面及剖面图提供依据。
本变电所的初步设计包括了:(1)总体方案的确定;(2)短路电流的计算;(3)高低压配电系统设计与系统接线方案选择;(4)防雷保护等内容。
关键词:变电站;输电系统;配电系统;高压网A DESIGN OF ELETRIC SYSTEM FOR220KV STEP-DOWN TRANSFORMERSUBSTATIONABSTRACTThe substation is an importance part of the electric power system, it is consisted of the electric appliances equipments and the Transmission and the Distribution. It obtains the electric power from the electric power system, through its function of transformation and assign, transport and safety. Then transport the power to every place with safe, dependable, and economical. As an important part of power’s transport and control, the transformer substation must change the mode of the traditional design and control, then can adapt to the modern electric power system, the development of modern industry and the of trend of the society life.The region of 220-voltage effect many fields and should consider many problems. Analyse change to give or get an electric shock a mission for carrying and customers carries etc. circumstance, choose the address, make good use of customer data proceed then carry calculation, ascertain the correct equipment of the customer. At the same time following the choice of every kind of transformer, then make sure the line method of the transformer substation, then calculate the short-circuit electric current, choosing to send together with the electric wire method and the style of the wire, then proceeding the calculation of short-circuit electric current. This first step of design included:(1) ascertain the total project (2) the calculation of the short-circuit electric current . (3) the design of an electric shock the system design to connect with system and the choice of line project .(4) the contents to defend the thunder and so on.Key words:substation; transmission system; distribution; high voltage network.前言目前,我国城市电力网和农村电力网进行大规模的改造,与此相应,城乡变电所也正不断的更新换代。
(完整版)牵引变电所一次系统电气设备的选择毕业论文
毕业设计(论文)题目:110KV牵引变电所一次系统电气设备的设计学科专业:电气化铁道技术班级:电气化3122姓名:党王胜指导老师:吕岚起止日期:目录1 引言 (2)2 牵引供电系统 (4)2.1牵引供电系统简介 (4)2.2 牵引变电所 (4)2.3接触网 (4)2.4牵引变电所设计步骤 (5)2.5影响牵引变电所设计的因素 (5)3 牵引变压器及其接线 (6)4 短路计算 (7)4.1三相对称短路电流的分析计算 (7)4.2短路的原因 (8)4.3短路的危害及防范措施 (8)4.4短路计算的目的及假设条件 (8)5 短路电流的危害及措施 (12)6 高压电气设备选择及校验 (14)6.1 母线的选择和校验 (14)6.2 高压电气设备选择的原则 (17)6.3 高压断路器的选择和校验 (19)6.4 隔离开关的选择和校验 (20)6.5 高压熔断器的选择和校验 (22)6.6 支柱绝缘子及穿墙套管的选择和校验 (22)6.7电流互感器的校验 (25)6.8 电压互感器的校验 (26)结论 (28)致谢 (29)参考文献 (30)1 引言采用电力机车为主要牵引动力的铁路称为电气化铁路,1879年5月31日在德国柏林举办的世界贸易博览会上,由西门子和哈尔斯克公司展出了第一条电气化铁路迄今已有120多年的历史。
低能耗、高效率、高速度的电力牵引已成为世界各国铁路发展趋势,是铁路现代化的额标志。
20世纪60年代,世界第一条高速电气化铁路------东京到大阪的新干线在日本建成,拉开了高速电气化铁道建设的新篇章。
随着电气化铁路的迅猛发展,我国在1961年8月15日第一条电气化铁路宝成线,即宝鸡------凤州段正式通车,从此揭开了中国电气化铁路建设的序幕。
从第一条电气化铁路运营到现在的40多年里,特别是改革开放以来,中国的电气化铁道得到了迅猛的发展。
到2006年7月1日既有京沪线化改造完成为止,电气化铁路已突破2.1万Km,居亚洲第一,世界第二。
110kV变电站电气一次部分设计毕业论文
110kV变电站电气一次部分设计毕业论文
设计毕业论文的题目可以为"110kV变电站电气一次部分设计",该论文可以包括下列内容:
1. 引言:介绍110kV变电站的作用和重要性,以及电气一次
部分设计的背景和目的。
2. 变电站布置图:绘制变电站的布置图,包括主变、断路器、组合电器柜、电流互感器等设备的布置和连接方式。
3. 变电站主要设备选型:根据变电站的负载情况、运行要求和安全标准,对主要设备进行选型,包括主变压器、断路器、电容器等。
4. 主变压器设计:根据负载需求计算主变压器的容量,选择适当的交流电压等级,并设计主变压器的绕组、冷却系统、绝缘等。
5. 断路器设计:根据负载需求和故障电流的大小,选择合适的断路器额定电流,并设计断路器的开关特性、运行机构和保护装置等。
6. 组合电器柜设计:根据变电站的布置和设备需求,设计组合电器柜的结构和连接方式,并设计合适的开关柜、控制柜和仪表柜等。
7. 电流互感器设计:根据主变压器的容量和负载要求,选择适
当的电流互感器额定电流,并设计电流互感器的绕组和保护装置等。
8. 变电站电力系统设计:根据变电站的负载要求和电力系统的稳定性要求,设计电力系统的配电方案、保护方案和接地方案等。
9. 结论:总结论文的主要内容和设计成果,提出对未来变电站电气一次部分设计的展望和改进建议。
10. 参考文献:列举参考文献,包括相关标准、技术手册和专
业论文等。
以上是110kV变电站电气一次部分设计的毕业论文内容提纲,具体的内容可以根据实际情况进行调整和完善。
电气论文六篇
电气论文六篇电气论文范文1老师自身的专业水平理论联系实际,在实践工作中检验理论、提升理论,是企业对毕业生的要求。
理论指导实践,在实践工作中运用科学的理论指导实践,是企业对工程技术人员的要求。
曾在电力系统就职,体会比较深刻。
对于变电站而言变压器检修常常要做空载和短路试验,工程上变压器空载试验方法采纳调压器在低压侧加压,空载容量应小于调压器容量的50%,试验电流为额定电流的1‰~1%,以测量变压器的铁损。
一般电力变压器在额定电压时,空载损耗约为额定容量的0.1%~1%。
变压器短路试验用自耦变压器调整原边电压,原边电流达到额定值时,测量变压器铜损。
通常电力变压器在额定电流下的短路损耗约为额定容量的0.4%~4%。
通过亲自动手做压器空载、短路试验及观看试验现象,联系《电路》、《电机学》中关于变压器的相关学问,加深了对变压器的学习与理解。
发电厂自动化掌握是电力系统的进展趋势与要求,已投产和在建的大型发电厂的自动化掌握水平特别高,已达到“无人值守,少人值班”管理模式。
发电机组的自动开停机、自动同期并网技术验证了《自动掌握理论》、《继电爱护》等相关理论学问。
在电力系统工作的4年中,笔者的理论学问在工作实践中不断得到深化和提升。
二电力系统工作经受对电气工程本科教学起到的乐观作用1教材选用目的更加明确教材是高校实施培育方案的重要介质直接影响着教学质量和人才。
高质量、合理化的教材是提高教学质量与水平、完成人才培育方案与目标的保证。
在施教时参照自身的工作阅历,选用更具有方向性与实践性的教材,提高毕业生与企业之间的契合度。
智能电网、数字化电站是电力系统的进展趋势,其要求电网信息化、自动化程度更高。
由于这一目的,可编程掌握器(ProgrammableLogicController,PLC)被广泛应用到电力系统中,目前国内应用的PLC有西门子(SIEMENS)公司生产的S7系列、施耐德公司生产的Quantum等系列、三菱公司生产的FX3G系列等。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
1电气系统总论1.1 电气主接线1.1.1 发电厂电气主接线的基本要求发电厂的电气主接线是电力系统接线的主要部分,它表明了发电机、变压器、线路和断路器等电气设备的数量,并且指出了发电机、变压器、线路的连接方式,从而完成发电、变电、输电、配电的任务。
主接线的质量对电力系统的安全、稳定、灵活、经济运行,以及对发电厂电气设备的选择、配电装置布置、继电保护和控制方式的拟定等都有密切的关系。
由于发电、变电、输电、配电和用电是同时完成的,所以主接线设计、施工、运行的质量不仅影响电力系统本身,同时也影响到工农业生产和人民生活。
发电厂的主接线应根据发电厂在电力系统中的地位、回路数、设备特点及负荷性质等条件确定,并且应满足运行可靠、简单灵活、操作方便和节约投资的要求。
a ) 可靠性根据系统和用户的要求,保证必要的供电可靠性是对电气主接线最基本的要求。
停电不仅对发电厂造成损失,给国民经济各部门带来的损失更严重,往往比因停电而少发电能的价值大许多倍。
可靠性的客观衡量标准是运行实践,可靠性还是主接线各组成元件,包括一次部分和二次部分在运行中可靠性的综合,不仅要考虑母线、断路器、隔离开关、互感器等一次设备的故障率及其对供电的影响,还要考虑继电保护等二次设备的故障率及其对供电的影响。
衡量主接线可靠性的标志是:断路器检修时不影响供电;线路、断路器或母线故障时以及检修母线时,停运回路数少,停运时间短,能保证对重要用户的供电;发电厂全部停运的可能性小。
b )灵活性电气主接线的布局应能适应各种运行方式。
不但在正常时能方便地投入或切换某些设备,而且在其中一部分电路检修时,能尽量保证未检修的设备继续供电和检修工作的安全进行。
同时,主接线的布局要求在各种切换操作时操作步骤最少。
c)经济性主接线应简单清晰,以便节省断路器、隔离开关、电流和电压互感器、避雷器等一次设备的投资;要能使控制保护不过于复杂,以节约二次设备和控制电缆投资;要能限制短路电流,以便选择价格合理的电气设备或轻型电器。
1.1.2 32接线32 接线是指在两组母线间,装有三台断路器,但可引接两个回路。
32 接线是现代国内外大型发电厂和变电站 3 30 ~ 7 5 0 k V 超高压配电装置应用最广泛的一种典型接线。
32接线一次回路的突出优点为运行调度灵活,操作检修方便,有高度的可靠性。
正常运行时,两组母线和全部断路器都投入工作,形成多环形供电,运行调度灵活。
当一组母线停电检修时,回路不需要切换。
任一台断路器检修时,各回路仍按原接线方式运行,也不切换。
隔离开关仅在检修时作隔离电器使用。
一组母线故障时,只断开与该母线相连的所有断路器,全部线路仍可通过另一组母线继续供电。
在两组母线同时故障或一组检修另一组故障的极端情况下部分线路仍能继续输送功率。
32接线在一次接线方面具有较突出的优点,但是由于每个回路连接着两台断路器,一台中间联络断路器连接着两个回路,给继电保护及二次线带来了复杂性。
这些问题已逐步得到妥善解决,如每回线路设两套主保护,同时出口继电器、断路器跳闸线圈和直流回路均为双套,比较灵活可靠。
1.1.3 发电机-变压器单元接线大容量发电机出口断路器由于制造困难、技术尚欠成熟、造价很高,一般均不装设。
制造大机组出口断路器需要解决的主要问题是大电流发热问题及开断短路时的过渡现象问题。
对较小容量发电机因电感与电阻的比值小,时间常数小,直流分量衰减很快。
短路一般经数十毫秒即通过零点,灭弧较容易。
对大机组因电感与电阻的比值大,时间常数大,直流分量衰减慢,短路电流有时经数百毫秒也不通过零点,断路器动作切断短路故障时会产生异常过电压,灭弧不易。
我国在九十年代 300 兆瓦机组是电力系统的主力,担负着基本负荷,起停次数并不频繁,大多数采用发电机—变压器单元接线,一般不考虑装设发电机出口断路器或负荷开关。
在发电机与主变压器以及厂用变压器之间采用全连式分相封闭母线连接,中间不设任何操作电器。
这一方面是由于主变压器采用双绕组式而无断开的必要,另一方面也使大电流回路尽量简化,保持可靠的连接。
发电机做耐压试验时,连同主变低压绕组及厂用变压器高压绕组一并进行。
至于厂用电回路则由于电流小,连接和拆卸方便,有的电厂采用可拆连接,进行简单作业即可断开和安装。
发电机出口双绕组变压器之间采用分相封闭母线。
采用分相封闭母线的原因为:目前世界上投入运行的最大单机容量已达 1500M W,在我国600M W 容量的机组也相继投入运行。
单机容量的增大,使联接发电机与变压器之间母线的电流随之增大,其相间故障短路电流亦增大。
首先,母线额定电流增大,不仅使母线本身的损耗和发热增大,而且由于母线通过电流时,在母线周围伴随着强大的交变磁场,使母线周围钢结构的感应损耗和发热十分严重,影响母线的安全经济运行,其次是大型发电机出口相间短路电流很大,相应的短路电动力也很大.致使发电机出口回路的设备制造和选择发生困难。
一旦发生故障,会造成大面积停电,甚至引起电力系统瓦解和重大设备损坏。
采用分相封闭母线就可以提高发、供电的可靠性,它的主要优点是:a ) 减少接地故障,避免相间短路。
只有不同相的两点同时发生接地故障时,才能成为相间短路,这种机率是很少的。
封闭母线因有外壳保护,可基本消除外界潮气,灰尘以及外物引起的接地故障。
b ) 封闭母线采用外壳屏蔽可从根本上解决钢结构感应发热问题。
当很大的短路电流流过母线时,由于外壳的屏蔽作用,使相导体所受的短路电动力大为降低。
c)母线封闭后,采用微正压运行方式,防止绝缘子结露,并为母线采用通风冷却方式创造了条件。
d ) 封闭母线由工厂成套生产,质量较有保证,运行维护工作量小,施工安装方便,不需设置网拦,简化了结构,也简化了对土建的要求。
分相封闭母线主要由母线导体、支持绝缘子、防护屏蔽外壳三部分组成。
导体和外壳均采用铝管结构。
分相封闭母线按外壳电气连接方式可分为分段绝缘式和全连式。
分段绝缘式封闭母线的特点是:沿母线长度方向的外壳各段之间彼此绝缘,相与相之间和外壳对地之间也彼此绝缘,且规定每段外壳只在一点接地,以避免产生环流。
分段绝缘式分相封闭母线的主要优点是:可使现场焊接工作量减到最小,能实现快速安装。
缺点是外壳上的短路电动力很大。
全连式封闭母线的特点是沿母线长度方向上的外壳,在同一相内从头到尾全部连通。
在封闭母线的各个终端通过短路板,将各相的外壳连接成完整的电气通路。
全连式分相封闭母线以母线导体为一次侧,母线外壳为二次侧,恰似一台变比为1:1 的空气芯变压器。
当导体通电时,外壳上产生一个方向相反而其数值几乎与母线导体上流过的电流相等的感应电流,使壳外剩余磁场大为降低,周围钢结构或混凝土钢筋中几乎不存在热损耗或温升。
由于母线相间短路电动力很小,从而可采用较轻型的支持结构。
外壳基本处于等电位,使接地方式大为简化。
全连式分相封闭母线导体一般用三个绝缘子组成一组,在外壳上支持,在空间以彼此相差 120°的位置安装。
1.1.4 电气主接线运行方式及倒闸操作1.1.4.1 运行方式的编制原则电气主接线的运行方式是电气运行人员在电气主接线正常运行、操作及事故状态下分析和处理各种事故的基本依据,电气运行人员必须熟悉和掌握电气主接线的各种运行方式。
由于电力系统负荷和潮流分布的变化,系统的频率和电压需要调整,发电厂的主辅设备的停电检修和重新投入运行,发生电气事故,这些都需要改变运行方式。
在改变运行方式时,应最大限度地满足安全可靠的要求,遵守以下几个原则:1.1.4. 1.1 保证厂用电的可靠性及经济性厂用电是发电厂最重要的负荷,为了保证供电的可靠件和连续性.使发电厂能安全满发,故应考虑发电厂在正常、事故及检修状态时厂用电的运行方式,以及机炉起动及停止过程中的供电要求,此外,还应考虑切换操作的简便。
厂用工作电源的每一分段,均有备用电源,当工作电源发生故障时,备用电源应能自动投入。
发电厂起动初期或全厂停电时,可从系统取得厂用电。
适当地将最重要辅机安排在有厂用柴油发电机的系统上,当遇到电网发生故障或频率、电压突变时,柴油发电机可与电网解列运行,以保证主设备的安全。
1.1.4.1.2 保证对用户供电的可靠性。
大型电厂对枢纽变电站应采用双回路供电。
1.1.4.1.3 潮流分布要均匀,避免设备过负荷而限制出力。
1.1.4.1.4 便于事故处理,尽量缩小故障范围并保证厂用电安全。
1.1.4.1.5 满足防雷保护和继电保护的要求。
在各种运行方式下避免继电保护误动作,避免在故障时继电保护拒动。
1.1.4.1.6 在满足安全运行的同时,应考虑到运行的经济性,减少线路损耗。
1.1.4.1.7 满足系统静态稳定和动态稳定的要求。
在正常运行方式下,联络线的最大输送功率不得超过允许值,发电机强行励磁及自动电压调整器等自动装置应投入运行。
这样,在负荷变化,发电机经受微小干扰后,能恢复到原来的稳定运行状态,满足静态稳定要求。
在系统发生短路等故障时,断路器切除故障的时间要短,线路的自动重合闸装置的动作要正确,使系统内发电机保持同步运行,达到动态稳定。
1.1.4.1.8 电气设备的遮断容量应大于最大运行方式时的短路容量,否则在短路状态下,电气设备不能完全切断短路电流,以致发生爆炸,扩大事故。
1.1.4. 2 倒闸操作发电厂中运行的电气设备,常常遇到检修、试验及处理事故等情况,这就需要改变电气设备的运行状态或改变系统的运行方式、当电气设备由一种状态转换到另一种状态或改变系统的运行方式时,需要进行一系列倒闸操作。
倒闸操作主要指拉开或合上某些断路器和隔离开关;拉开或合上某些直流操作回路;切除或投入某些继电保护等自动装置或改变其定值;拆除或装设临时接地线及检查设备的绝缘等。
倒闸操作是一件既重要又复杂的工作,若发生误操作事故,可能会导致设备的损坏,危及人身安全及造成大面积停电,对国民经济带来巨大损失。
因此,必须采取有效的措施加以防止,这些措施包括组织和技术两个方面。
1.1.4.2.1 倒闸操作的原则应使用断路器拉、合闸,绝对禁止使用隔离开关切断或接通负荷电流。
(电路未设置断路器的特殊情况,按有关规定执行。
)送电线路若需停电时,必须先拉开断路器,然后拉开线路侧隔离开关,最后拉开母线侧隔离开关。
送电时的操作顺序与此相反。
双绕组升压变压器停电时,应先拉开变压器高压侧断路器,再拉开变压器低压侧断路器,最后拉开变压器两侧隔离开关;送电操作顺序与此相反。
双绕组降压变压器停电时,应先拉开变压器低压侧断路器,再拉开变压器高压侧断路器,最后拉开变压器两侧隔离开关;送电操作顺序与此相反。
三绕组升压变压器停电时,应按顺序拉开变压器高、中、低三侧断路器,再拉开变压器三侧隔离开关;送电时的操作顺序与此相反。
三绕组降压变压器停送电时的操作顺序与三绕组升压变压器相反。