夏热冬冷地区某医院建筑空调系统设计毕业设计论文
毕业设计(论文)-毕业设计(论文)-暖通空调专业毕业设计_毕业论文-北京市某综合楼空调系统设计方案
北京市某综合楼空调系统设计方案摘要本设计是北京市某综合楼的空调系统设计。
此建筑是包括超市、会议室、办公室、客房等于一身的多功能型建筑,总建筑面积为11732.3m2,建筑高度为15.3m,建筑共五层,地上四层,地下一层。
制冷机房设在地下一层,冷却塔布置在四层屋面。
一层主要为超市和旅馆大堂,二、三、四层主要是会议室,办公室和旅馆。
此次暖通空调设计内容包括:集中空调系统(含冷、热源方案的选择)、空调冷却水系统、地下室防烟、排烟以及通风系统的设计。
对于层高较高空间较大的房间主要采用全空气系统,对于层高较低空间较小的房间主要采用风机盘管加新风系统。
最后还要对空调系统的设备和管路采取消声、防振和保温等措施。
关键词:综合楼空调系统冷却水系统The comprehensive design plan ofair-conditioning system in BeijingAbstractThe graduation design is the design about the air-conditioning system of a comprehensive building in Beijing. This building is a mal-fuction building, which includes supermarkets, meeting rooms, offices, and guest rooms. Its total area is 11732.2 square meters. The height of the building is 15.3 meters. There are five floors in the building, among them, four floors are on the ground, and one is underground. The generation room of refrigeration system is set up in the basement. The cooling tower is fixed up on the roof of the fourth floor. The supermarkets and the lobby of the hotal are the main room in the first floor. The meeting rooms, offices and the hotal are on the second, third and fourth floors. The content of the heating, ventilation and air-conditioning system design include: central air-conditioning system(include the selection of the cooling and heating source), cooling water of air-conditioning system, prevent and get rid of the smoke in the basement and ventilation system. The complet air system is adopted mainly in the rooms, whose height is more higher and the space is more spacious. And PAU and FCU system is adopted in the other rooms. At last, the measurements of weaken sound, prevent equipment from vibration and insulation are adopted to the equipment of the air-conditioning system and pipeline.Keyword: comprehensive building; air-conditioning system; cooling water system.目录1 绪论................................................ 错误!未定义书签。
简述某医院暖通空调设计论文
简述某医院的暖通空调设计【摘要】结合工程实例,介绍某医院建筑的暖通空调设计,特别介绍了净化空调系统的设计【关键词】洁净空调;icu;设备夹层近几年国家大力支持医疗基本设施的建设,医疗制度的改革,因此很多地区陆续新建、改建和扩建医疗建筑。
由于医疗建筑内部使用性质的不同,所以暖通空调系统形式也就存在差异。
以病房而言,普通病房仅需满足人员的舒适度要求,传染病房则需要预防感染而满足净化要求。
本文结合具体工程实例,详细介绍了医院的暖通空调设计方案。
1 工程概况医院病房楼建筑面积为98281.94㎡,地下2层,地上19层,建筑总高度为87.10 m。
2 室内设计参数表1室内设计参数房间名称夏季冬季夏季最小新风量室内噪声干球温度(℃)相对湿度(%)干球温度(℃)相对湿度(%) m3/h.p (次/h)db(a)病房26 ≤60 20 ≥40 50 ≤45护士站26 ≤60 18 ≥40 30 ≤50诊室26 ≤60 20 ≥40 30 ≤45百级手术室22 50 22 40 60(6)≤50万级手术室22 50 22 40 60(6)≤50洁净走道 24 60 24 45 (3)≤55i c u 24 60 24 45 (3)≤50cc u 24 60 24 45 (3)≤45表2洁净区域指标名称最小静压(pa)换气次数(次/h)手术区手术台工作面高度截面平均风速(m/s)温度(℃)相对湿度(%) 最小新风量m3/h.p(次/h)对相邻级别洁净室百级手术室+8 - 0.25~0.30 22 40 60(6)万级手术室+8 22 - 22 40 60(6)无菌器械 +5 13 - 24 45 3洁净走道 +5 13 - 24 45 3icu +5 13 - 24 45 3ccu +5 13 - 24 45 33 空调、通风及采暖设计3.1 空调冷热源院区内已有的集中冷冻机房,供给全院的空调、采暖冷热水。
夏季冷源采用四台蒸汽溴化锂冷水机组。
浅谈医疗建筑暖通空调设计
浅谈医疗建筑暖通空调设计摘要:当前时期,人们的生活水平持续提升,医疗行业的发展速度也在不断增快,新建医院的数量不断增加,现有医院也开始重视改扩建,这表明医院的规模越来越大。
医疗建筑能耗中,暖通空调能耗为主要能耗,所以需要高度重视医疗建筑暖通空调设计。
关键词:医疗建筑;暖通空调设计;节能前言:随着经济水平的持续提升,人们开始高度重视健康问题,其中医院的医护水平也得到了组合的提升,在医疗建筑中安装暖通空调可以显著提升医疗建筑的舒适程度,给患者提供良好的就诊环境和康复环境。
为了更好地控制医院的运营成本,就需要深入分析建筑暖通空调设计,持续地进行改善,希望可以给相关的人员提供一定的参考。
1医疗建筑暖通空调设计1.1空调冷热源设计1.1.1净化空调系统独立冷热源在医疗建筑工程中,水系统选用舒适的中央空调,净化空调系统的独立冷热源可由风冷热泵冷热水器提供。
冬季和夏季,净化空调系统可以选择舒适性中央空调系统,在过渡季节中,可以选择使用风冷热泵冷热水机组。
不仅如此,可根据工程实际情况和建设单位的实际需要,选择风冷热泵冷热水机组进行制冷供暖。
如果医疗建设项目选择舒适的中央空调作为多联机中央空调系统,独立冷热源的净化空调系统不仅可以选择使用风冷热泵冷热水机组,可选用多联机中央空调系统。
1.1.2独立冷热源1)冷源系统的选择。
制冷剂的选择应综合考虑空调冷水供应总冷负荷的实际温度要求。
通常,应至少安装两台容量分别为1758K和2813KW的离心式冰箱,一小一大。
夜间和手术室的空调需求主要由小型机器满足,而大型机器用于日间和高需求的门诊服务。
之后,还应安装与冰箱流量相对应的变频调速冷却水泵和冷水泵。
并且还应也可设置横流式冷却满足内区和手术室的空调所需,也许应用相应的电伴热防冻举措确保系统运转正常。
2)热源系统的选择。
立足地热和空调总负荷需求情况,应安装两台4.2MW热水锅炉,一用一备,以满足60°C/50°C热水供应的温度要求。
制冷空调系统设计毕业论文
制冷空调系统设计毕业论文目录前言 ------------------------------------------------------------------------ 1 第1章概述------------------------------------------------------------------ 2 1.1工程概况 ---------------------------------------------------------------- 2 第2章负荷计算-------------------------------------------------------------- 3 2.1室外空气的空调设计参数------------------------------------------------ 4 2.2建筑物维护结构----------------------------------------------------------- 5 2.3空调房间的冷负荷--------------------------------------------------------- 6 2.4新风负荷 --------------------------------------------------------------- 12 2.5空调房间的热负荷-------------------------------------------------------- 16 第3章空调方案的确定及技术经济分析 ---------------------------------------- 17 3.1空调方案的技术经济性能分析--------------------------------------------- 17 3.2空调房案的确定---------------------------------------------------------- 22 3.3空气处理过程房间送风量及设备的选择计算---------------------------------- 24 3.4空调系统设计中其它常见问题---------------------------------------------- 26 第4章空调房间的气流组织 --------------------------------------------------- 29 4.1空调房间的气流组织方式和送风口的形式------------------------------------ 29 4. 2散流器选型与计算 ------------------------------------------------------ 29第5章风道的设计与水力计算 ------------------------------------------------- 31 5.1 风道的设计与水力计算--------------------------------------------------- 31 第6章空调水系统的设计与水力计算 ------------------------------------------ 34 6.1冷冻水管路计算方法及理论依据-------------------------------------------- 34 6.2凝结水管的计算---------------------------------------------------------- 36 第7章空调系统的消声与防震 ----------------------------------------------- 41 7.1概述 ------------------------------------------------------------------- 41 7.2消声设备的选型---------------------------------------------------------- 41 7.3空调装置的防震---------------------------------------------------------- 42 第8章空调系统的防火排烟设计 ---------------------------------------------- 43 &1空调系统的防排烟方式----------------------------------------------------- 43 & 2空调系统的防排烟装置---------------------------------------------------- 45 & 3卫生间的排气------------------------------------------------------------ 49 第9章制冷机房------------------------------------------------------------- 50 9.1冷冻设备的选择---------------------------------------------------------- 50 9.2冷却设备的选择---------------------------------------------------------- 51 9. 3补水定压设备的选择 ---------------------------------------------------- 53 9.4水处理设备的选择-------------------------------------------------------- 56 9.5热水系统设备的选择------------------------------------------------------ 57 9.6机房设备布置----------------------------------------------------------- 59 第10章管道的保温设计------------------------------------------------------ 6010.1保温材料的选用 -------------------------------------------------------- 60 10.2保温层厚度确定 -------------------------------------------------------- 60 10.3补偿器的计算---------------------------------------------------------- 61 总结 ---------------------------------------------------------------------- 62 致谢 ---------------------------------------------------------------------- 63 参考文献 ------------------------------------------------------------------ 64 附表1 :冷负荷计算表附表2:热负荷计算表附表3 :四层新风水力计算表附表4 :六层新风水力计算表附表5 :四层水管水力计算表附表6 :六层水管水力计算表附表7 :四层冷凝管水力计算表附表8 :六层冷凝管水力计算表WORD版木.空调制冷技术的诞生是建筑技术的一项重大进步,它标志着人类从被动适应宏观自然气候发展到主动控制建筑微气候,在改造和征服自然的过程的又迈出了坚实的一步。
浅谈医疗建筑暖通空调设计
浅谈医疗建筑暖通空调设计【摘要】介绍我院近几年承接的医疗建筑暖通空调设计的特点,主要就空调冷热源、水系统、空气品质保证措施、特殊科室的空调设计等方面展开讨论。
希望对今后该类型建筑的暖通空调设计起到借鉴作用。
【关键词】医疗建筑;冷热源;水系统;空气品质;病理科;检验科0引言近些年随着国家医疗体制改革,我国医院建筑建设进入了一个黄金期,大量医疗建筑开始设计并投入使用。
新建医院建筑由于体量大、楼层高、功能科室多,对其空调的人性化设计要求也越来越高,重视对医疗建筑工程的研究和设计有着重要的意义。
1空调负荷与冷热源1.1空调负荷医院建筑的空调冷热负荷整体较办公和商业建筑要低,单位面积冷负荷一般在90~110W/m2,单位面积热负荷一般在70~90W/m2。
1.2空调冷热源根据建筑所在区域的能源特点及医院自身运行的特点,不同类型不同规模医院的空调冷热源形式也有所差异。
目前医院建筑的空调冷热源主要采用的是压缩式制冷机+燃气锅炉的形式。
由于医院中的用电可靠性高,均采用双路供电,是首先保证的供电用户,因此在医院建筑中使用能效比高的压缩式制冷机是一种安全节能的制冷方式。
在采用溴化锂吸收式制冷方式时,应考察热源的可靠性,不宜采用自备锅炉。
利用直燃型溴化锂机组,可以同时解决供冷和供热问题,减少空调冷热源占用的空间,但是必须做好机房的泄爆,空调水循环泵建议与机组分开设置,增加系统运行的安全性。
如果土壤换热器性能测试及埋管面积满足要求,也可设计地源热泵系统,该系统可以兼顾卫生热水,可采用带热回收地源热泵机组+普通地源热泵机组的组合方式,由于空调及卫生热水使用中的不定因素,设计时建议预留冷却塔。
空调热源采用燃气锅炉的,建议采用真空热水机组,首先由于其负压运行,减少了机组爆炸的危险,同时由于采用间接加热方式,空调循环水不经过炉体,电热管不易结构,提高了机组的使用寿命。
如果建筑外部有蒸汽源的,也可利用蒸汽对空调水进行加热,同时也可利用蒸汽进行消毒。
浅谈医院空调系统设计
浅谈医院空调系统设计摘要:本文介绍了医院空调的设计,通过对冷源选择,设备布置,医院空调末端系统设计,水系统设计等方面,阐述了医院空调设计过程中的一些特点。
关键词:医院空调系统冷源新风+风机盘管系统同程系统COP系数引言近10年来,国内的医院建设发展很快,建筑设备在现代化医院建筑中的比重也越来越大,所起的作用也越来越重要。
暖通空调系统,尤其是净化空调系统的要求越来越高,应用面也越来越广。
一、医院建筑特点:现代化医院组成一般包括住院部、医技部、门诊部等,医院建筑中三大部门各自分工明确,又互相密切联系。
通常是分幢建筑,有通廊联接,人流、物流分明、合理。
二、医院空调特点:医院空调要为病人的诊断、治疗和康复提供良好环境,并有利于医护人员的医疗效果,保障医护人员的健康,维持诊疗设备的性能。
由此目的出发,医院空调应具有下列特点:1确保满足医疗要求的室内空气环境医院最主要的服务对象是病人,最适宜的空气温、湿度能使病人的代谢降到最低,有利于集中能量于患部,促使早日恢复健康。
2.确保满足医疗要求的感染控制对策医院中人是最大的发尘、发菌源,要求空调系统对微生物的污染及其引起的交叉感染做出系统性对策。
3.确保满足医疗要求的空气净化能力对医院中的空气进行有效级别的过滤,使之达到一定的洁净度,满足医院部门洁净要求。
4确保满足医疗要求的系统安全性和可靠性空调系统服务对象是病人,不允许出差错,选择系统要考虑系统的安全性及可靠性,这是医院空调系统的必然要求三、空调末端系统选用及原则1.合理的空调分区由于医院各部门的使用时间,房间的温湿度要求。
洁净度要求的不同,同时各功能科室的布置情况,医院工艺要求不同,那么医院空调末端分区就要求细分,划分的原则:(1)根据医院部门、科室的使用时间来划分使用时间是由医院的运行来决定的;要求24小时运行的房间:如住院楼的病房每日定时运行的:如门诊科室,医技科室要求随时运行的:如手术室、急救室,分娩室等要求独立运行的:如医技部的CT、MR,解剖实验、分娩室等主要是要区分这些运行时间,把相同运行时间划分到同一系统,这主要指水系统、及新风、排风系统的划分。
某医院门诊综合楼空调系统设计
0 引言节能建筑、低碳建筑和生态建筑是当下绿色建筑的所提倡的主基调。
中国建筑节能协会[1]报告披露2020年我国建筑运行阶段能耗占全国能源总量的比重为的21.3%,空调系统作为建筑能耗大户,已经从舒适层面逐步向健康节能的层面发展。
暖通空调系统是医院建筑中的重要组成部分,既要满足人们对环境温湿度、洁净度的需求,也要满足大型医疗设备对温湿度的要求。
在能源规划方面,我国已经进入到第四阶段气候变化时期,既要通过提高资源利用率和变频控制的方式对接节能减排指标,由此可见,邹惠芬等[2]的研究认为在空调设计及改造过程中,针对智能控制和变频控制系统的设计工作相当重要。
本文在此基础上,提出了合理的空调系统划分及气流组织、新风全热回收以及节能空调设备的采用,能从源头降低空调能耗,助力我国提出的“在2030年碳排放达到峰值,2060年实现碳中和”的承诺[3]。
多联式空调机组简称多联机,即变制冷剂流量空调系统,其空调系统具有方便灵活、舒适节能等特点,随着变频技术及数码涡旋技术的运用、室内机形式的多元化、设备的高可靠性、简捷的系统设计及智能化技术等的发展,使多联机日趋完善,在办公楼、商业建筑、医院等建筑中得到广泛的运用。
本文介绍了多联式空调在某医院门诊综合楼的运用,对发热门诊、信息中心、放射科等区域空调系统设计进行分析。
1 工程概况1.1 建筑概况本项目为泉州市某医院扩建项目,按二级甲等精神专科医院标准设计,主要建设内容为门诊医技楼及住院楼,其中门诊综合楼建筑面积 33 327.8m 2,空调房间面积为23 530m 2。
建筑高度为39m。
地下一层为地下停车及设备用房;一层:门诊大厅、药房、综合门诊入口、心理咨询门诊、急诊室与发热门诊等;二层:小综合门诊、治疗室及检验科等;三层:病房、餐厅、会议室及信息中心等。
四~八层:病房、办公室、治疗室、餐厅等;九层:食堂、职工餐厅及活动生活区。
1.2 设计参数室内空调设计计算参数如表1所示。
医院空调系统设计论文
医院空调系统设计论文摘要:空调系统冷热源方案的确定需分步进行:一要明确工程需求;二要结合工程能源供应状况,确定大体方案;三要对方案进行细分,对差异方案进行细分,通过定性定量分析,并进行经济性比对分析,找出最优方案。
引言根据《民用建筑热工设计规范》中全国建筑热工设计分区图可知,夏热冬暖地区主要包含广东、广西大部分地区,香港、澳门,以及福建南部地区,这些地区都有气候状况类似;能源供应状况也类似,冷源方案的确定具有相通性,通过本工程方案的比对确定,可以用于类似工程参考。
1 工程概况本工程地下一层,地上25层,建筑总面积约为49067m2(地上45405m2,地下3662m2),地下一层为车库以及设备用房,1层为入口门厅和架空、2层为消毒供应中心,3层、4层为手术室,5层为手术ICU,6层为架空设备层,7~24为病房及医生办公,25层为病案及阅览,建筑总高度96.95m,属一类高层建筑。
2 设计内容本建筑的通风防排烟换气系统;冬夏两季舒适性空调系统,本文只介绍空调系统部分。
3 设计参数(1)室外气象参数,见表1(参照GB50736-2012中玉林地区参数)。
(2)夏季室内参数,见表2。
4 空调系统(1)根据业主设计要求,贵港市人民医院外科综合楼设计冷暖两用空调系统;二至五层设置洁净空调系统(洁净空调系统由业主另行委托专业公司设计,由于洁净度要求及运行时间上的差别,二至五层设置独立的空调系统),其他部分设计中央空调系统;中央空调系统的夏季冷负荷约为3810kW,冬季热负荷约为2128kW。
(2)医院院方无现有锅炉,且不打算设置锅炉,当地的燃气价格也较贵,故本工程设置三台空气源热泵机组作为冬季空调热源,空气源热泵夏季运行,承担一部分冷负荷,另设计两台冷水螺杆式制冷机组作为夏季空调冷源的补充,冷冻水供回水温度为7/12℃。
(3)冬季:设置空气源热泵机组作为冬季空调热源,根据计算负荷,设置3台机组,每台制热量为696kW同时设4台空调用热水水泵(三用一备),每台流量为132m3/h,热水供回水温为45/40℃。
某医院空调系统设计方案的探讨
中央空调市场年月(上)1前言近年来,随着人民生活水平日益提高,人们对就医条件也有了更高的要求,因而国内的医院建设发展很快,很多大、小医院均在扩建、改建。
与其他建筑相比,医疗建筑使用功能复杂,特别是综合性医院,人流量大,疾病种类多,且医院的功能更趋复杂化。
因此,医疗建筑对暖通空调系统,尤其是净化空调系统的要求越来越高,空调系统在医疗建筑中的应用越来越广。
同时,考虑到节约能源,环境友好的要求,对该类建筑的暖通空调系统的设计值得大家广泛探讨。
笔者不久前参与了中部某医院的工程招标,结合该医院空调系统的设计方案,本文仅浅谈笔者对该类空调系统设计的看法。
2工程概述该医院为一县级人民医院,目前在建的项目为该医院新的综合大楼,划分为门诊部、诊疗部及住院部,是该医院的扩建项目,有着明晰的功能分区,各功能做到按污染、半污染、清洁分区。
该综合楼共12层,建筑面积约30000m 2。
其中1~5层为门诊部及诊疗部,手术室、急诊室设在1层,6层以上为住院部。
该综合楼空调系统采用的冷、热源为制冷量960kW 风冷螺杆式冷水(热泵)机组4台。
空调系统采用风机盘管加新风系统,以保证各个房间可以分别控制。
该综合楼手术部较集中,集中设置了净化空调系统,在空调系统新风口、系统正压段及末端的天花板送风装置附近分别设置不同级别的空气过滤器,气流组织形式为手术台上方垂直送风,双侧下回风。
为了满足该综合楼住院部全年生活热水供应的要求,另外单独配置了住院部热水供热源设备,采用了制热量15.6kW 空气源热泵机组2台,并配有热水箱、辅助电热水器及水处理仪,以满足60t/天的供水要求,供水温度为60℃,回水温度为55℃。
3系统分析该空调系统为医疗建筑综合楼空调系统,系统舒适性要求高,要求室内温度的波动不宜太大;医院各部门空调使用时间不一致,门诊部以及诊疗部为白天供空调,夜间则停止供应;门诊部中的急诊室及住院部需要24小时空调供应。
过渡季节会出现某些部门如住院部需要供暖,而某些部门如手术部需要供冷的情况。
南京某医院空调系统设计_secret
绪论随着我国综合国力的日益增加和人民生活水平的不断提高,人们对医院就医环境的要求越来越高。
人们在医疗保健、看病、住院等方面除对医院的诊断、服务态度提出更高的要求外,对医院的设施、环境、空气质量方面的要求也日渐提高。
同时,医院作为一个特殊的服务性机构,由于激烈的市场竞争,促进医院更加注重增加室内建筑环境投资[1]。
近年来,医院建设发展快速,就湖北武汉地区而言,同济、协和、省人民医院、省中医院等许多大中型医院先后兴建了高层门诊部、住院部。
这些建筑全部设有中央空调系统,一些旧的医疗建筑也增设了空调系统。
甚至有些县级医院也兴建了近千平方米的洁净手术室,少数手术室还可进行脏器移植手术。
手术室是直接关系到病人生命的场所,也是医院最重要的、标志性的部门和形象窗口。
医院洁净手术室空调系统控制室内温度、相对湿度、尘、菌及有害气体浓度,并提供室内人员所需的新风量,维持室内外合理的气流分布。
而最重要的是控制室内细菌浓度,以防止手术过程中手术伤口受感染,从而提高手术的成功率。
为达此目的,在洁净手术室空调设计中需要采用洁净技术,强调净化级别,通过空气洁净技术来控制细菌浓度,既防止微生物、灰尘对手术用房的污染,减少伤口感染风险,又能防止对手术室外部环境的污染[2]。
按《医院洁净手术部建筑技术规范》规定医院洁净手术室分为4 级。
医院洁净手术部一般由多级别手术室组成。
空调设计应既能使该洁净手术部可整体控制,又能方便各洁净手术室的灵活使用。
手术室建筑及设备的基本条件是:1)手术最大限度地保持接近无菌的清洁环境,减少创伤感染;2)要为医护人员创造出最有利于工作的舒适环境,满足手术过程中对空气的温度、湿度、风速、洁净度、噪声等的严格要求[3]。
净化空调在防止感染和保证手术成功方面起到了不可替代的作用,是手术室中不可缺少的配套技术。
高水平手术室要求高质量的净化空调,而高质量的净化空调才能保证手术室的高水平。
考虑到净化空调工程是一个完整的系统,保证室内的洁净也就不能仅仅靠高效过滤器,而净化手术室的测试指标也达9项之多。
医疗建筑空调设计
医疗建筑空调设计医疗建筑作为保障人们健康的重要场所,其内部环境的舒适度和空气质量对于患者的康复以及医护人员的工作效率都有着至关重要的影响。
而空调系统在其中扮演着关键角色,它不仅要调节温度和湿度,还要保证空气的清洁和流通,以满足医疗环境的特殊要求。
一、医疗建筑空调系统的特点医疗建筑的空调系统相较于其他类型的建筑,具有一些显著的特点。
首先,由于医疗建筑内存在各种不同的功能区域,如病房、手术室、诊疗室、候诊区等,每个区域对于温度、湿度、洁净度和通风的要求都有所不同。
例如,手术室需要保持恒温恒湿、无菌的环境,而病房则更注重舒适性和通风效果。
其次,医疗建筑内人员密集,且患者的免疫力相对较弱,这就要求空调系统能够有效地过滤空气中的细菌、病毒和灰尘等污染物,提供高质量的空气。
此外,医疗设备的运行也会产生大量的热量,需要空调系统具备较强的制冷和散热能力。
二、医疗建筑空调系统的设计要求1、温度和湿度控制不同的医疗区域对温度和湿度的要求各异。
一般来说,病房的温度应保持在 22-26℃,相对湿度在 40%-60%之间。
手术室的温度则通常控制在 20-24℃,相对湿度在 50%-60%。
对于一些特殊的诊疗区域,如新生儿病房、重症监护室等,温度和湿度的控制要求更加严格。
2、空气洁净度为了减少交叉感染的风险,医疗建筑的空调系统需要具备良好的空气过滤和净化功能。
通常采用高效过滤器来去除空气中的微小颗粒和微生物,确保室内空气的洁净度达到相关标准。
3、通风和换气充足的新鲜空气供应对于医疗建筑至关重要。
合理的通风系统设计可以有效地排除室内的污浊空气,引入新鲜空气,改善室内空气质量。
通风量应根据不同区域的人员密度和使用功能进行计算和设计。
4、噪声控制医疗建筑内需要保持安静的环境,以利于患者的休息和治疗。
因此,空调系统的运行噪声应控制在较低水平,避免对患者和医护人员造成干扰。
5、可靠性和稳定性医疗建筑的空调系统必须具备高度的可靠性和稳定性,以确保在任何时候都能正常运行。
空调系统设计毕业论文.
南京东湖酒店空调系统设计摘要本次设计的内容是南京东湖酒店空调系统设计,其目的是在保证空调系统安全、经济、环保的前提下,为顾客提供一个舒适的居住环境。
保护顾客的权益并营造自身良好的形象。
本次设计内容包括:空调冷负荷的计算;空调系统的划分与系统方案的确定;冷源的选择;空调末端处理设备的选型;风系统的设计与计算;室内送风方式与气流组织形式的选定;水系统的设计、布置与水力计算;最后,根据设计的过程及计算结果运用CAD绘制标准层空调系统平面图,水系统图、空调机房平面图以及冷冻机房平面图。
本设计依据有关规范考虑节能和舒适性要求,设计的空调系统首层采用全空气通风系统,标准层采用风机盘管—新风系统。
关键词中央空调;全空气;风机盘管;新风Design of central air-conditioning system ofNanjing East Lake HotelAbstractThe design of the Nanjing East Lake Hotel air conditioning system design, its purpose is to provide customers with a comfortable living environment under the premise of ensuring the air conditioning system security, economic, environmental, protect the interests of the customer and create their own good image.The design elements include: the cooling load calculation; air-conditioning systems division and program; cold source selection; air conditioning terminal equipment selection; air system design and calculation; indoor air with air form of organization selected; water system design, layout and hydraulic calculations; Finally, according to the design process and calculation results, the use of CAD drawing standard layer of air-conditioning system plan, water system, air-conditioned computer room floor plan, and chiller plant plan.This design in accordance with the relevant specifications to consider energy efficiency and comfort requirements of the first floor of the design of air-conditioning system with full air ventilation system, the standard floor fan coil units - a new wind system.Keywords centtral air conditioning; all air system; fan coil units (FCUs);fresh air system目录摘要 (I)Abstract (II)第1章绪论 (5)1.1 课题背景 (5)1.2 宾馆空调设计的重要性 (5)1.2.1 空调设计必须满足宾馆建筑热舒适指标和卫生要求 (5)1.2.2 节能空调设计是宾馆建筑节能的重要环节 (5)1.2.3 防火排烟与安全卫生是宾馆空调设计的重要任务 (6)1.3 设计任务与意义 (6)第2章冷负荷计算 (7)2.1 原始资料 (7)2.1.1 室外气象条件 (7)2.1.2 土建条件 (7)2.1.3 其他条件 (7)2.2 冷负荷计算 (8)2.2.1 夏季建筑围护结构的冷负荷 (8)2.2.2 人体散热形成的冷负荷 (9)2.2.3 灯光照明散热形成的冷负荷 (10)2.3 空调房间内的散湿量计算 (10)2.3.1 人体散湿量 (10)2.4 建筑物制冷系统总冷负荷 (10)2.5 冷负荷计算举例 (11)2.6 冷负荷计算 (11)2.7 各分项逐时冷负荷汇总 (12)2.8 湿负荷计算举例 (12)2.9 本章小结 (12)第3章空调方案的选择集风量计算 (14)3.1 空调方案的选择 (14)3.1.1 空调系统选择的一般原则 (14)3.1.2 本次设计中空调系统的选择 (14)3.2 客房风量计算 (15)3.3 本章小结 (17)第4章新风机组以及风口的选择 (18)4.1 新风机组的选择 (18)4.2 其他系统的新风机组选择及校核 (18)4.3 送风口的选择 (18)4.4 标准层风口的选择计算举例 (18)4.5 一层风口的选择计算举例 (19)4.6 本章小结 (20)第5章风系统管道设计 (21)5.1 风系统管道的设计方法 (21)5.2 新风管道水力计算 (22)5.2.1管道摩擦阻力计算 (22)5.2.2管道局部阻力计算 (23)5.2.3新风管道水力计算 (23)5.2.3.1标准层通风管道水力计算 (23)5.2.3.2标准层右侧环路水力计算 (25)5.3 本章小结 (27)第6章空调冷冻水系统管道设计 (28)6.1 冷冻水系统水力计算过程 (29)6.1.1 沿程阻力和局部阻力 (29)6.2 计算举例 (30)6.3 本章小结 (32)结论 (34)致谢 (35)参考文献 (36)附录A (37)附录B (46)附表1 冷负荷计算 (51)附表2 风机盘管选型表 (64)附表3 排风系统设备选型 (65)附表4 新风系统水力计算(A) (66)附表4 新风系统水力计算(B) (68)附表5 冷冻水系统阻力计算 (70)第1章绪论1.1课题背景空调系统最早应用于工厂,随着近代工业和人民生活水平的提高,空调系统也被广泛的应用到了居住和商业建筑中,特别是改革开放以后商业性空调得到了进一步完善和发展,蓄冷空调,低温送风,洁净系统以及末端装置都得到了应用和提高,新的产品和技术更是层出不穷。
某医院病房、手术室洁净空调系统设计毕业设计
郑州轻工业学院本科毕业设计(论文)题目沧州某医院病房、手术室洁净空调系统设计学生姓名刘庆功专业班级建筑环境与设备工程11-01学号541102040120院(系)建筑环境工程学院指导老师(职称)张文慧(讲师)完成时间2015年6月8日郑州轻工业学院建筑环境工程学院本科毕业设计任务书题目沧州某医院病房、手术室洁净空调系统设计专业建筑环境与设备工程学号541102040120姓名刘庆功一、原始资料及技术条件1. 建筑地点:沧州2. 建筑功能:病房、手术室3. 洁净室温度:夏季24-26℃,冬季20-22℃4. 洁净室相对湿度:夏季50-70%,冬季30-50%二、主要内容1. 设计计算:空调热湿负荷计算、管道阻力校核。
2. 设备选型:空调器选择、过滤器选择、其他零部件选择。
3. 设计图样:空调及通风平面图、空调系统流程图、风系统图、机房布置图。
三、基本要求1. 认真进行实习(调研)、完成实习(调研)报告。
2. 阅读文献写出文献综述。
3. 按统一格式完成开题报告。
4. 阅读英文文献,并译成中文(不少于5000汉字)。
5. 规范绘制图样,绘图不少于五张零号图。
6. 英中文对照摘要,中文不少于400 字。
7. 按统一格式编制设计说明书,不少于30000字。
8. 有全部设计的纸介质文档和电子文档。
四、主要参考资料1 洁净度等级的国家标准和国际标准ISO 146442 洁净厂房设计规范GB50073-20013 制药工业洁净厂房设计规范4 实验动物环境及设施GB14925-20015 采暖通风与空气调节设计规范GB50019-20036 微生物和生物医学实验室生物安全通用准则WS233-20027 张吉光主编.净化空调[M].北京:国防工业出版社,20038 赵荣义等编.简明空调设计手册[M].北京:中国建筑工业出版社,19989 陆耀庆著;实用供热空调设计手册[M].北京:中国建筑工业出版社,200010 赵荣义,范存养,薛殿华等.空气调节[M] .第三版.北京,中国建筑工业出版社,1996.11:4-10完成期限:2 015.03~2015.06指导教师签章:专业负责人签章:2015年 3 月 2 日沧州某医院病房、手术室洁净空调系统设计摘要本设计为河北省沧州市某医院病房、手术室洁净空调系统设计。
医疗建筑空调设计
医疗建筑空调设计医疗建筑作为保障人们健康和生命安全的重要场所,其内部环境的舒适性和空气质量对于患者的康复、医护人员的工作效率以及医疗设备的正常运行都有着至关重要的影响。
而空调系统作为调节室内环境的关键设施,在医疗建筑的设计中更是需要精心规划和考量。
医疗建筑的功能区域繁多,包括门诊区、病房区、手术室、检验科、影像科等,每个区域对于温度、湿度、空气洁净度和通风量的要求都有所不同。
例如,手术室需要保持严格的恒温恒湿环境,温度通常控制在 22-25℃,相对湿度在 40%-60%之间,同时要求空气中的细菌和尘埃粒子数量极低,以防止手术感染。
而病房区则更注重舒适性和通风效果,温度可在 20-26℃之间调节,相对湿度在 50%-60%左右。
在进行医疗建筑空调设计时,首先要考虑的是空调系统的类型选择。
常见的空调系统有集中式空调系统、半集中式空调系统和分散式空调系统。
集中式空调系统适用于大型医疗建筑,能够实现对多个区域的统一控制和管理,但初投资较大,运行维护成本较高。
半集中式空调系统则结合了集中式和分散式的优点,通过风机盘管和新风系统的组合,可以灵活调节各个房间的温度和湿度,适用于中型医疗建筑。
分散式空调系统则多用于小型医疗建筑或个别特殊区域,如独立的诊室或设备间,其安装和维护较为方便,但控制精度相对较低。
空调系统的负荷计算也是设计中的关键环节。
医疗建筑的空调负荷不仅包括人员、设备、照明等常规负荷,还需要考虑医疗设备的散热量、新风负荷以及特殊区域的净化负荷等。
例如,影像科的 X 光机、CT 机等设备在工作时会产生大量的热量,需要在负荷计算中予以充分考虑。
同时,由于医疗建筑的人员流动性较大,不同时间段的人员密度也会有所变化,因此在计算人员负荷时需要采用合理的人员密度指标和使用时间系数。
新风系统在医疗建筑空调设计中起着至关重要的作用。
充足的新鲜空气可以有效改善室内空气质量,降低交叉感染的风险。
根据相关规范和标准,医疗建筑的新风量要求较高,一般病房区每人每小时的新风量不应少于40m³,手术室等特殊区域则更高。
夏热冬冷地区某医院建筑空调系统设计
2014“金牛杯”暖通空调设计大赛夏热冬冷地区某医院建筑空调系统设计浙江海洋学院参赛人员:杜泽杭毛海勇颜伟曹卓朝指导老师:刘春花摘要降低建筑能耗是现今建筑行业发展的趋向。
医院建筑的能耗使用在行业中是一类重要代表,其具有功能繁多,要求不一、小空间多的特点。
在本次设计过程中,通过对多家三甲医院调研,了解众多医院设计方案;以及参考成功案例,寻求出团队设计特色。
利用鸿业软件获得房间负荷,在DeST平台得出全年负荷变化,找出最优系统设计方案,运用eQUEST能耗模拟软件对逐月及全年能耗分析,从而寻求降低建筑能耗方案。
本设计旨在满足节能环保要求,改善综合医院建筑室内空气品质,为患者和医务人员等提供健康、适用、安全和高效的使用空间。
在此前提下,考虑建筑的功能性、系统性、先进性、文化性、经济性及“四节一保”,从而设计最为适用的空调系统方案。
目录摘要 (II)第一章建筑概况及设计简介 (1)1.1 建筑信息 (1)1.2 土建资料 (2)1.3 设计规范 (2)1.4 本设计要点及创新 (3)第二章建筑负荷计算 (6)2.1 负荷计算依据 (6)2.1.1 室外参数 (6)2.1.2 围护结构参数 (7)2.1.3 室内参数 (7)2.1.4人员设备参数 (7)2.1.5人员设备作息 (7)2.1.6 DeST模型 (8)2.2 全年负荷计算结果 (8)2.2.1 全年冷热负荷 (8)2.3 典型房间负荷计算结果 (10)2.3.1空调房间冷负荷计算 (10)2.3.2 空调房间热负荷计算 (14)2.3.3手算冷负荷举例 (15)第三章平面分区规划 (19)3.1 分区原则 (19)3.2 各层分区结果 (19)3.3 分区负荷统计 (23)3.4 DeST分区全年满意度分析 (35)第四章焓湿图确定与风量分析 (37)4.1 风量确定的依据 (37)4.1.1新风量的确定 (37)4.1.2送风量的确定 (37)4.2 典型房间的风量确定 (37)4.2.1 风机盘管加新风空调系统 (37)4.2.2 全空气空调系统-输液大厅 (39)第五章气流组织设计与校核 (42)5.1 房间气流分布形式 (42)5.2气流组织举例计算 (42)5.2.1散流器送风计算 (42)5.2.2侧送风计算 (43)第六章水力计算 (44)6.1 风管水力计算 (45)6.1.1 风管水力计算方法 (45)6.1.2 典型系统风管水力计算 (45)6.2 水管水力计算 (45)6.2.1冷凝水管估算依据 (45)6.2.2 典型系统水管水力计算 (46)第七章冷热源方案 (49)7.1 空调季划分 (49)7.2 冷热源选型原则 (49)7.3 冷源选取 (49)7.3.1 冷源简介 (49)7.3.2 电制冷机选型 (50)7.4 热源选取 (51)7.4.1 热源简介 (51)7.4.2 方案选取 (51)7.4.3 热源设备选型 (51)7.5 全楼方案的确定 (51)7.5.1 供冷季供暖季方案 (51)7.5.2 过渡季方案 (52)第八章设备选型 (54)8.1冷热源选型 (54)8.1.1冷水机组选型 (54)8.1.2换热器的选择 (54)8.1.3冷却塔的选型 (54)8.1.4冷热水泵的选择 (55)8.1.5冷却水循环水泵的选择 (57)8.1.6分水器和集水器的选择 (58)8.1.7膨胀水箱的选取 (58)8.2风机盘管选型 (58)8.3全空气机组选型 (59)8.4VRV机组选型 (59)8.5分体空调选型 (59)8.6 恒温恒湿空调选型 (59)8.7全热交换器选型: (59)第九章 eQUEST软件介绍及模拟 (60)9.1 eQUEST简介 (60)9.2 建筑模型 (60)9.2.1 建筑体型及围护结构参数 (60)9.2.2空调房间参数设计 (61)9.2.3空调系统方案 (61)第十章冷热源和空调末端全年运行自动控制策略 (64)10.1 概述 (64)10.2 自控系统主要监控内容 (64)10.2.1冷冻站主要监控内容 (64)10.3 水系统全年运行策略 (64)10.3.1 冷水机组群控调节 (64)10.3.2冷冻泵的控制 (65)10.3.3冷却泵的控制 (65)10.3.4冷却塔控制 (65)10.3.5 空调热水系统控制 (65)10.3.6 过渡季空调水系统控制 (65)10.4 空气处理机组控制策略 (65)10.4.1内区空气处理机组控制 (65)10.4.2新风机组控制策略 (67)10.4.3 风机盘管的控制 (67)第十一章建筑节能与经济性分析 (69)11.1 本建筑节能方案............................................................................. 错误!未定义书签。
[暖通毕业设计] 某医院门诊楼空调系统设计
空调设计方案不仅关系到建筑的室内环境参数能否满足使用要求而且直接关系到建筑的工程投资运行能耗和费用系统安全性调节性能操作方便性维护费用环境影响人员舒适性机房面积建筑美观性等诸多指标参数
某大学毕业设计
XX 某医院门诊楼空调系统设计 摘要
本设计为 XX 某医院门诊楼空调系统设计,拟为之设计合理的中央空调 系统,为室内人员提供舒适的工作环境。
II
某大学毕业设计
KEY WORDS: air-conditioning systems, the entire air system, fan coil and a new air system, performance comparison.IIIຫໍສະໝຸດ 某大学毕业设计目录
某市第二人民医院病房楼空调设计
某市第二人民医院病房楼空调设计介绍了山东省某市第二人民医院的冷热源设置、空调方式等设计情况,并介绍了二次回风空调系统在手术室等净化空调系统的运用标签:冷热源;空调方式;净化空调系统1、引言近些年来,大型综合医院在各地不断出现。
由于建设用地相对紧张,大型综合医院大多将门诊、急诊、医技、病房等功能区组合在一个大型建筑中。
综合性的的功能布置给空调通风系统设计带来了较多困难和挑战。
空调系统是医院日常运行的耗能大户,空调系统节能设计对节能减排意义重大。
2、工程概况本工程为某市第二人民医院病房楼,地下1层,地上11层,总建筑面积为41114.2m2,建筑高度47.80m,属一类高层民用建筑。
本建筑地下一层为药物库房、变配电室、空调制冷机房,消防水泵房等用房;一层为出、入院办理手续大厅、消毒供应中心、中心摆药、财务、餐厅厨房等;二层为ICU、病房,三层为手术部、液科、病理科;四层为产房、病房,五层为透析科、病房;六~九层为病房;十一层为病房、会议室等。
3、空调冷热源及系统分区3.1冷热源(1)依据规划与建筑方案、运营特点,同时根据建设方的要求,本子项设置三台水冷离心式冷水机组(制冷量为2286kW(650RT)/台)和一台水冷螺杆式冷水机组(制冷量为455kW(130RT)/台)作为空调系统的冷源(其中一台水冷离心式冷水机组作为医院二个副楼空调冷源预留),机组设置于地下二层的冷冻机房内,制冷剂采用符合环保要求的冷媒,夏季供应供、回水温度为7/12℃的空调冷水。
(2)本工程热源来自城市热力管网,一次热水经过换热站交换成60/50℃低温热水供冬季空调使用。
(3)空调设计冷负荷为4243.8kW,空调面积冷指标90.0W/ m2;空调设计热负荷为4181.4kW,空调面积热指标88.7W/ m2。
3.2 空调水系统分区门诊、急诊、医技、病房等功能区温湿度要求、空调运行时间均有所不同,同时建筑体形大,存在大面积的内区。
医院建筑中的空调设计
医院建筑中的空调设计摘要:随着我国经济的发展、医疗技术的进步和人民生活水平的改善,人们对医院建筑的要求日益提高,全国各地新建、改扩建了许多医疗设施。
医院筑房间功能众多,使用时段不一,医疗设备也经常在增加与更新,导致空调系统配置复杂。
此外,医院的空调系统设计除需满足舒适性、空气感染控制等要求外,还需重视系统优化配置,降低空调能耗。
关键词:医院建筑;空调设计;方法前言随着社会经济建设和发展脚步的加快,人们对社会医疗服务的需求和要求也越来越高,尤其是近些年医院改扩建进程的加快,使得医院建筑业进入到一个快速发展的新阶段。
暖通空调系统作为现代建筑中的不可或缺组成部分,在医院建筑中显得更为重要,医院暖通系统的好坏,直接关系到医护人员的工作环境和患者的就医住院感受。
下面笔者就以本医院空调系统为实例,将在运行中所遇到的问题进行研究和分析,并提出相关的应对措施。
希望通过本文内容的阐述,能为今后医院的空调系统运行提供相应有益的参考资料。
1设计施工中常见的问题及对策分析1.1药房、检验科、血液透析室、新生儿病房等区域过渡季节制冷采暖问题。
医院建筑不同于一般的民用建筑,不同的功能分区导致空调系统的运行时间及冷热负荷也有所不同,像手术室、分娩室、重症监护室等洁净区域,其功能明显不同于普通病房,这些区域设计人员在进行暖通系统设计时会对其进行单独的冷热源设计,如不进行单独设计,会在后期运行中造成很大的麻烦,严重时可能导致手术暂停,威胁到病人的生命健康。
手术室、分娩室、重症监护室属于封闭空间,一般情况下四个季节都需要进行制冷,而普通病房则是冬季需要采暖夏季需要制冷,所以冷热源必须分开设计,独立按需使用。
在医院暖通设计中,手术室等洁净区域的冷热源独立设计,一般设计人员很容易考虑到。
但在实际运行中发现,药房、检验科、血液透析室等区域,药品需要低温储藏、大量医疗设备也需要低温环境,所以其在过渡季节如4月份、10月份是需要制冷的,但由于其空调系统和住院病房的制冷主机是一个系统,而住院病房的制冷系统每年5月下旬才开始运行,这就导致药房、检验科、超声科、血液透析室等区域在过渡季节室内温度偏高,影响了科室医疗工作的正常开展;新生儿病房正好相反,考虑到刚出生的需住院治疗生孩子的特殊性,在过渡季节就需要提供温暖的环境,但这个时候市政热源尚未开始运行,导致病房温度较低,不利于新生儿的康复治疗。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
2014“金牛杯”暖通空调设计大赛夏热冬冷地区某医院建筑空调系统设计摘要降低建筑能耗是现今建筑行业发展的趋向。
医院建筑的能耗使用在行业中是一类重要代表,其具有功能繁多,要求不一、小空间多的特点。
在本次设计过程中,通过对多家三甲医院调研,了解众多医院设计方案;以及参考成功案例,寻求出团队设计特色。
利用鸿业软件获得房间负荷,在DeST平台得出全年负荷变化,找出最优系统设计方案,运用eQUEST能耗模拟软件对逐月及全年能耗分析,从而寻求降低建筑能耗方案。
本设计旨在满足节能环保要求,改善综合医院建筑室内空气品质,为患者和医务人员等提供健康、适用、安全和高效的使用空间。
在此前提下,考虑建筑的功能性、系统性、先进性、文化性、经济性及“四节一保”,从而设计最为适用的空调系统方案。
目录摘要 (I)第一章建筑概况及设计简介 (1)1.1 建筑信息 (1)1.2 土建资料 (2)1.3 设计规范 (2)1.4 本设计要点及创新 (3)第二章建筑负荷计算 (6)2.1 负荷计算依据 (6)2.1.1 室外参数 (6)2.1.2 围护结构参数 (7)2.1.3 室内参数 (7)2.1.4人员设备参数 (7)2.1.5人员设备作息 (7)2.1.6 DeST模型 (8)2.2 全年负荷计算结果 (8)2.2.1 全年冷热负荷 (8)2.3 典型房间负荷计算结果 (10)2.3.1空调房间冷负荷计算 (10)2.3.2 空调房间热负荷计算 (14)2.3.3手算冷负荷举例 (15)第三章平面分区规划 (19)3.1 分区原则 (19)3.2 各层分区结果 (19)3.3 分区负荷统计 (23)3.4 DeST分区全年满意度分析 (35)第四章焓湿图确定与风量分析 (37)4.1 风量确定的依据 (37)4.1.1新风量的确定 (37)4.1.2送风量的确定 (37)4.2 典型房间的风量确定 (37)4.2.1 风机盘管加新风空调系统 (37)4.2.2 全空气空调系统-输液大厅 (39)第五章气流组织设计与校核 (42)5.1 房间气流分布形式 (42)5.2气流组织举例计算 (42)5.2.1散流器送风计算 (42)5.2.2侧送风计算 (43)第六章水力计算 (45)6.1 风管水力计算 (45)6.1.1 风管水力计算方法 (45)6.1.2 典型系统风管水力计算 (45)6.2 水管水力计算 (45)6.2.1冷凝水管估算依据 (45)6.2.2 典型系统水管水力计算 (46)第七章冷热源方案 (49)7.1 空调季划分 (49)7.2 冷热源选型原则 (49)7.3 冷源选取 (49)7.3.1 冷源简介 (49)7.3.2 电制冷机选型 (50)7.4 热源选取 (51)7.4.1 热源简介 (51)7.4.2 方案选取 (51)7.4.3 热源设备选型 (51)7.5 全楼方案的确定 (51)7.5.1 供冷季供暖季方案 (51)7.5.2 过渡季方案 (52)第八章设备选型 (54)8.1冷热源选型 (54)8.1.1冷水机组选型 (54)8.1.2换热器的选择 (54)8.1.3冷却塔的选型 (54)8.1.4冷热水泵的选择 (55)8.1.5冷却水循环水泵的选择 (57)8.1.6分水器和集水器的选择 (58)8.1.7膨胀水箱的选取 (58)8.2风机盘管选型 (58)8.3全空气机组选型 (59)8.4VRV机组选型 (59)8.5分体空调选型 (59)8.6 恒温恒湿空调选型 (59)8.7全热交换器选型: (59)第九章 eQUEST软件介绍及模拟 (60)9.1 eQUEST简介 (60)9.2 建筑模型 (60)9.2.1 建筑体型及围护结构参数 (60)9.2.2空调房间参数设计 (61)9.2.3空调系统方案 (61)第十章冷热源和空调末端全年运行自动控制策略 (64)10.1 概述 (64)10.2 自控系统主要监控内容 (64)10.2.1冷冻站主要监控内容 (64)10.3 水系统全年运行策略 (64)10.3.1 冷水机组群控调节 (64)10.3.2冷冻泵的控制 (65)10.3.3冷却泵的控制 (65)10.3.4冷却塔控制 (65)10.3.5 空调热水系统控制 (65)10.3.6 过渡季空调水系统控制 (65)10.4 空气处理机组控制策略 (65)10.4.1内区空气处理机组控制 (65)10.4.2新风机组控制策略 (67)10.4.3 风机盘管的控制 (67)第十一章建筑节能与经济性分析 (69)11.1 本建筑节能方案........................................................................... 错误!未定义书签。
第一章建筑概况及设计简介1.1 建筑信息本设计目标建筑系医院建筑,位于江西九江地区,地上15层,地下2层,空调面积约29308.78㎡,建筑楼高63m。
各楼信息见下表1.1:表 1.1 医院各层层高及功能裙房楼层层高(m)附属功能-2F 4.8 车库、设备用房、配电房、冷热源机房等-1F 4.8 停车库、体检中心、放射科等1F 4.8 门诊大厅等2F 4.5 内科、妇产科、功能科、儿科、手术室、诊室等3F 4.5 预防保健、皮肤、五官、口腔等科室科;住院部分4F 4.5 行政办公、社区医院等;放置冷却塔塔楼层高(m)附属功能5~13F 3.9 住院病房14F 3.9 ICU中心15F 3.9 手术中心本建筑各方向的视图如图1.1~1.3所示:图1.1 建筑主视图图1.2 建筑后视图图1.3 建筑侧视图1.2 土建资料本医院建筑为三级甲等医院,整体结构体系为框架结构。
根据本建筑设计要求以及查询《民用建筑供暖通风与空气调节设计规范GB50736-2012》、《公共建筑节能设计标准》,最后确定本建筑的建筑围护结构信息详见下表1.2~表1.4,其它围护结构在设计说明中未给出明确要求,我们根据相关的规范自行设定。
表 1.2 建筑物围护结构基本信息 围护结构 材料 围护结构夏季传热系数(W/(㎡·K))围护结构延迟(h)围护结构衰减系数外墙 墙体构造表第3号类型 0.56 9.10.34 外窗 蓝灰色铝合金中空玻璃窗 3.2 0.4 1 屋面屋面构造表第3号类型0.7310.50.16表 1.3 外窗(含凸窗)热工性能朝向 东 南 西 北 注:外窗气密性全为6级玻璃透明幕墙气密性均为4级传热系数 (W/(㎡*K )) 3.20 3.30 3.28 3.27 综合遮阳系数Sw 0.27 0.27 0.27 0.27 可见光透射比 0.28 0.28 0.28 0.28 可开启面积比0.500.500.520.511.3 设计规范为更好贯彻节能设计理念,在设计过程中,我们严格按照各类国家与地方节能设计规范进行;同时,我们也参考了一些其他规范的意见,相关的标准规范如下表1.5所示:表 1.5 规范设计标准序号标准名称标准号1 暖通空调制图标准GB/T 50114-20102 民用建筑供暖通风与空气调节设计规范GB 50736-20123 通风与空调工程施工质量验收规范GB50243-20024 公共建筑节能设计标准GB50189-20055 绿色医院建筑评价标准CSCU/GBC 2-20116 建筑设计防火规范GB50016-20067 锅炉房设计规范GB50041-20088 城镇燃气设计规范GB50028-20069 全国民用建筑工程设计技术措施200910 实用供热空调设计手册第二版11 综合医院建筑设计规范2004发布12 综合医院建设标准08年修改版13 夏热冬冷地区居住建筑建筑节能设计标准JGJ 134- 200114 夏热冬冷地区采暖期/空调期划分对居住建筑能耗限值的影响分析1002- 8528( 2007)08-0027- 051.4 本设计要点及创新本设计遵循“节能、降耗、减排及提高能源的综合利用效率”的设计理念,具体针对目标建筑的地理位置及功能需求,结合已有的工程实践成果和建筑节能研究成果,在传统方法的基础上进行空调系统的方案设计。
具体说来,本设计主要有以下设计特点:1)运用软件科学设计运用DeST软件进行建筑全年8760小时逐时负荷计算,分析建筑全年负荷特征,使用鸿业负荷计算软件进行负荷计算与统计,在此基础上进行空调设计;运用DeST软件进行建筑全年能耗分析以及系统方案满意度分析,再由eQUEST软件进行建筑详细的能耗分析,并针对各类影响因素进行调整对比,从而确保系统方案是符合可行性、经济性、节能性原则的。
2)空调分区以及方案选择首先,依据负荷特性我们进行了内外分区。
建筑临近外墙的区域在冬季需要供暖,而进深3-5m的区域由于存在人员设备的产热需要供冷,如果进行此类区域的空调方案设计时没有考虑内区的存在冬季空调时统一送风,可能会出现外冷内热的室内环境,极大地影响舒适性。
本设计中,我们考虑到内外区冬季的负荷特性差异,将一楼输液大厅、二楼东侧妇科等作为典型的内区区域,经过分析比较最终选用了全空气系统。
其次,参考负荷及建筑结构特点我们进行了空调系统分区。
在对本建筑进行分区设计时,按照控制标准(如温湿度、洁净度、噪声要求)、使用时间、负荷特点(如冷/热性质、峰谷值出现时间、显热/潜热得热比例)一致的原则进行分区,如诊室、治疗室和办公室等。
而其他一些房间,如心电室和碎石室,尽管功能不相同,但是如果负荷特性差异不大,作息时间基本相同,则可以划入同一分区。
在设计方案确定时,对于门诊大厅、输液大厅及周边功能区域采用全空气系统,而在病房、诊室等多数功能房间采用风机盘管加新风的系统。
详见“第三章平面分区规划”。
对于过渡季节,根据DeST模拟过渡季逐时冷热负荷以及冷机的运行效率分析,如果全部采用冷机承担负荷这是非常不经济、不节能的,而九江市过渡季室外温度较适宜,大部分时间室内冷热负荷较小,所以我们最终决定采用“新风+冷机”承担过渡季负荷的方案。
详见“第 7.5.2节过渡季方案”。
3)空调冷热源设计及主要设备选型按照经济性、节能性和可行性的原则,我们在电制冷冷机选型时,通过DeST计算出的供冷季逐时冷负荷作出累计频率分布图进行合理分析详见“第七章冷热源方案、第八章冷热源设备选型”。
4)全年控制策略全年控制在不同负荷下冷机运行模式的确定上,从经济性和节能性出发,考虑冷机的高效冷负荷工作区段,基于不同台数冷机的配合,作出理论上可能实现的所有不同冷机台数组合运行模式下对应的理论高效冷负荷区段,根据理论优化后确定实际的冷机运行模式,并采用自控系统根据实际负荷的变化对冷热源进行全年调控,大大减少能耗。