目 次
前言·····································································································································································1范围·······························································································································································2规范性引用文件············································································································································3术语和定义····················································································································································4一般技术要求················································································································································5功能及其技术要求········································································································································6安全要求························································································································································7检验和试验····················································································································································8标志、包装、运输、贮存····························································································································9其他·······························································································································································
I
前 言
电力系统全网及各个可能独立运行的地区网络,都应设置限制频率降低的控制装置,以便在各种可能的扰动下失去部分电源而引起的频率降低,将频率降低限制在短时允许范围内,并保证频率在允许时间内恢复至长时间允许值,低频减负荷控制是自动限制频率降低的主要措施。

为了在系统频率降低时,减弱互联系统的相互影响,以及为了保证发电厂厂用电和其他重要用户的供电安全,可以在系统的适当地点设置低频解列控制。

本标准规范和指导低频减负荷和低频解列装置的研发、生产和检验。

本标准由中国电力企业联合会提出。

本标准由电力行业继电保护标准化技术委员会归口。

本标准主要起草单位:南京南瑞继保电气有限公司、国电南京自动化股份有限公司、北京四方继保自动化股份有限公司、南瑞集团公司稳定技术分公司。

本标准主要起草人:任祖怡、夏尚学、奚汉江、李哲、宣筱青。

本标准在执行过程中的意见或建议反馈至中国电力企业联合会标准化管理中心(北京市白广路二条一号,100761)。

II
电力系统低频减负荷和低频解列装置通用技术条件
1范围
本标准规定了电力系统低频减负荷和低频解列装置(简称装置)的基本技术条件和要求、试验方法及检验规则等。

本标准适用于电力系统低频减负荷和低频解列装置,并作为该类装置设计、制造、检验和运行的依据。

2规范性引用文件
下列文件对于本文件的应用是必不可少的。

凡是注日期的引用文件,仅注日期的版本适用于本文件。

凡是不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。

GB/T 191包装储运图示标志(GB/T 191—2008,ISO 780:1997,MOD)
GB/T 2423.1电工电子产品环境试验 第2部分:试验方法 试验A低温(GB/T 2423.1—2008,IEC 60068−2−1:2007,IDT)
GB/T 2423.2电工电子产品环境试验 第2部分:试验方法 试验B高温(GB/T 2423.2—2008,IEC 60068−2−2:2007,IDT)
GB/T 2423.3电工电子产品环境试验 第2部分:试验方法 试验Cab:恒定湿热试验(GB/T 2423.3—2006,IEC 60068−2−78:2001,IDT)
GB/T 2423.4电工电子产品环境试验 第2部分:试验方法 试验Db:交变湿热(12h+12h循环)(GB/T 2423.4—2008,IEC 60068−2−30:2005,IDT)
GB/T 2423.10电工电子产品环境试验 第2部分:试验方法 试验Fc:振动(正弦)(GB/T 2423.10—2008,IEC 60068−2−6:1995,IDT)
GB/T 2423.22电工电子产品环境试验 第2部分:试验方法 试验N:温度变化(GB/T 2423.22—2002,IEC 60068−2−14:1984,IDT)
GB/T 2900.1电工术语 基本术语(GB/T 2900.1—2008,IEC 60050−101:1998,NEQ)
GB/T 2900.17—2009电工术语 量度继电器
GB/T 2900.49电工术语 电力系统保护(GB/T 2900.49—2004,IEC 60050−448:1995,IDT)
GB 4208外壳防护等级(IP代码)(GB 4208—2008,IEC 60529:2001,IDT)
GB/T 4798.2电工电子产品应用环境条件 运输(GB/T 4798.2—2008,IEC 60721−3−2:1997,MOD)GB/T 7261—2008继电保护和安全自动装置基本试验方法
GB/T 9361—1988计算站场地安全要求
GB/T 11287电气继电器 第21部分:量度继电器和保护装置的振动、冲击、碰撞和地震 试验 第1篇:振动试验(正弦)(GB/T 11287—2000,IEC 60255−21−1:1988,IDT)
GB/T 13384—2008机电产品包装通用技术条件
GB/T 14285—2006继电保护和安全自动装置技术规程
GB/T 14537继电器和保护装置的冲击与碰撞试验(GB/T 14537—1993,IEC 60255−21−2:1988,IDT)
GB/T 14598.3电气继电器第5 部分:量度继电器和保护装置的绝缘配合要求和试验(GB/T 14598.3—2006,IEC 60255−5:2000,IDT)
GB/T 14598.9电气继电器第22-3部分:量度继电器和保护装置的电气骚扰试验辐射电磁场骚扰
1
试验(GB/T 14598.9—2002,IEC 60255−22−3:2000,IDT)
GB/T 14598.10电气继电器第22-4部分:量度继电器和保护装置的电气骚扰试验电快速瞬变/脉冲群抗扰度试验(GB/T 14598.10—2007,IEC 60255−22−4:2002,IDT)
GB/T 14598.13电气继电器第22-1部分:量度继电器和保护装置的电气骚扰试验 1MHz脉冲群抗扰度试验(GB/T 14598.13—2008,IEC 60255−22−1:2007,MOD)
GB/T 14598.14量度继电器和保护装置的电气干扰试验第2部分:静电放电试验(GB/T 14598.14—1998,IEC 60255−22−2:1996,IDT)
GB/T 14598.16电气继电器 第25部分:量度继电器和保护装置的电磁发射试验(GB/T 14598.16—2002,IEC 60255−25:2000,IDT)
GB/T 14598.17电气继电器第22-6部分:量度继电器和保护装置的电气骚扰试验 射频场感应的传导骚扰的抗扰度(GB/T 14598.17—2005,IEC 60255−22−6:2001,IDT)
GB/T 14598.18电气继电器第22-5部分:量度继电器和保护装置的电气骚扰试验 浪涌抗扰度试验(GB/T 14598.18—2007,IEC 60255−22−5:2002,IDT)
GB/T 14598.19电气继电器第22-7部分:量度继电器和保护装置的电气骚扰试验 工频抗扰度试验(GB/T 14598.19—2007,IEC 60255−22−7:2003,IDT)
GB/T 14598.27量度继电器和保护装置第27部分:产品安全要求(GB/T 14598.27—2008,IEC 60255−27:2005,MOD)
GB/T 17626.8电磁兼容 试验和测量技术 工频磁场抗扰度试验(GB/T 17626.8—2006,IEC 61000−4−8:2001,IDT)
GB/T 17626.11电磁兼容 试验和测量技术 电压暂降、短时中断和电压变化的抗扰度试验(GB/T 17626.11—2008,IEC 61000−4−11:2002,IDT)
GB/T 17626.17电磁兼容 试验和测量技术 直流电源输入端口纹波抗扰度试验(GB/T 17626.17—2005,IEC 61000−4−17:2002,IDT)
GB/T 17626.29电磁兼容 试验和测量技术 直流电源输入端口电压暂降、短时中断和电压变化的抗扰度试验(GB/T 17626.29—2006,IEC 61000−4−29:2000,IDT)
GB/T 19520.12—2009电子设备机械结构 482.6mm(19in)系列机械结构尺寸 第3-101部分:插箱及其插件
GB/T 20840.7互感器 第7部分:电子式电压互感器(GB/T 20840.7—2007,IEC 60044−7:1999,MOD)
GB/T 20840.8互感器 第8部分:电子式电流互感器(GB/T 20840.8—2007,IEC 60044−8:2002,MOD)
GB/T 22386电气继电器 第24部分:电力系统暂态数据交换通用格式(GB/T 22386—2008,IEC 60255−24:2001,IDT)
GB/T XXX—201X电力系统安全稳定控制技术导则
DL/T 478—2010继电保护及安全自动装置通用技术条件
DL/T 667远动设备及系统 第5部分:传输规约 第103篇:继电保护设备信息接口配套标准(DL/T 667—1999,IEC 60870−5−103:1997,IDT)
DL/T 871—2004电力系统继电保护产品动模试验
3术语和定义
GB/T 2900.1、GB/T 2900.17、GB/T 2900.49、GB/T XXX—201X(电力系统安全稳定控制技术导则)、DL/T 478确立的术语和定义适用于本标准。

2
4一般技术要求
4.1环境条件
4.1.1正常工作大气条件
a)环境温度:−10℃~+55℃。

b)相对湿度:5%~95%(装置内部既无凝露,也不应结冰)。

c)大气压力:80kPa~106kPa。

4.1.2正常试验大气条件
a)环境温度:+15℃~+35℃。

b)相对湿度:45%~75%。

c)大气压力:86kPa~106kPa。

4.1.3基准试验大气条件
a)环境温度:+20℃±2℃。

b)相对湿度:45%~75%。

c)大气压力:86kPa~106kPa。

4.1.4贮存、运输环境温度
a)贮存环境温度为−20℃~+55℃,相对湿度不大于85%。

b)运输环境温度为−40℃~+70℃,相对湿度不大于85%。

4.1.5周围环境
a)应遮阳、挡雨雪,防御雷击、沙尘,通风。

b)不允许有超过4.11规定的电磁干扰存在。

c)场地应符合GB/T 9361中B类安全要求的规定。

d)使用地点不应出现超过GB/T 14537规定的严酷等级为I级的振动。

e)无爆炸危险的介质,周围介质中不应含有能腐蚀金属、破坏绝缘和表面镀覆及涂覆层的介质及导电介质,不允许有明显的水气,不允许有严重的霉菌存在。

4.1.6特殊使用条件
a)当超出4.1.1、4.1.4、4.1.5规定的正常工作条件时,由用户与制造厂商定。

b)安装地点环境温度明显超过4.1.1正常工作环境条件时,优先选用的环境温度范围规定为:1)特别寒冷地区:−25℃~+55℃;
2)特别炎热地区:−10℃~+70℃。

4.2额定电气参数
4.2.1直流电源
a)额定电压:110V、220V。

b)允许偏差:−20%~+15%。

c)纹波系数:不大于5%。

4.2.2交流回路
a)交流电压:
;100V。

b)额定频率:50Hz。

4.2.3电子式互感器
对于来自电子式互感器的激励量,宜采用数字量输入,其额定值应符合GB/T 20840.7中5.2和GB/T 20840.8中表5的规定。

4.3功率消耗
a)交流电压回路:当额定电压时,每相不大于0.5V A。

3
b)直流电源回路:当正常工作时,不大于50W;当装置动作时,不大于80W。

4.4过载能力
交流电压回路:120V,连续工作;140V,允许10s。

4.5测量元件的准确度和变差
a)电压测量允许误差:在0.2U n~1.2U n范围内,不大于1%U n。

b)频率测量允许误差:在45Hz~55Hz范围内,不大于0.01Hz。

c)d f /d t测量允许误差:在45Hz~55Hz范围内,且在Δt=0.1s时,不大于10%或0.2Hz/s。

d)电压测量温度变差:在工作环境范围内,相对于20℃±2℃时,不超过±0.5%U n。

e)频率测量温度变差:在工作环境范围内,相对于20℃±2℃时,不超过±0.01Hz。

4.6结构和外观
机箱、插件的尺寸应符合GB/T 19520.12—2009的规定。

4.7外壳防护
户内使用装置的外壳防护应符合GB/T 4208中规定的外壳防护等级IP20的要求。

4.8对连接导线、输出继电器和信号继电器的要求
对装置中的连接导线、输出继电器和信号继电器的要求应符合DL/T 478中4.4、4.5.3、4.5.4的规定。

4.9绝缘配合
装置的绝缘配合性能应满足DL/T 478中4.9的规定。

4.10耐湿热性能要求
装置的耐湿热性能应符合DL/T 478中7.3的规定。

4.11电磁兼容要求
装置的抗扰度和电磁发射性能应符合DL/T 478中4.8的规定。

4.12机械性能
装置的机械性能应符合DL/T 478中4.10的规定。

4.13连续通电
装置在完成调试之后,应按DL/T 478中4.11规定进行连续通电试验。

5功能及其技术要求
5.1通用功能及其技术要求
5.1.1装置应满足GB/T 14285—2006中4.1.2~4.1.16的规定。

5.1.2装置应具有独立性、完整性。

5.1.3装置应按GB/T 14285—2006中
6.5.3的要求设置对电磁干扰的减缓措施。

5.1.4装置应配有硬软件监视功能,自动监视硬软件工作状态,对发现的异常、故障,自动采取告警、自复位、闭锁重要控制回路等措施,并记录发现的异常故障信息。

5.1.5装置的实时时钟、主要动作信号、记录保存的信息在失去直流电源的情况下不能丢失,在电源恢复正常后能重新正确显示并输出。

5.1.6装置应具备以下接口:对时接口、通信接口、调试接口和打印机接口。

5.1.7装置的强电开入回路应与装置保护电源隔离;开入回路的启动电压值应不大于0.7倍额定电压值,且不小于0.55倍额定电压值。

5.1.8装置中所有涉及直接跳闸的回路应采用启动电压值不大于0.7倍额定电压值,且不小于0.55倍额定电压值的中间继电器,并要求其启动功率不低于5W。

5.1.9装置的记录功能应满足以下要求:
a)应记录并保存必要的信息(如电压及其变化率等),记录信息内容主要用于判别装置各部分工作是否正常,动作是否正常。

4
b)应能记录装置动作过程的所有信息,并存储8 次以上故障录波波形报告。

c)具有打印记录信息的功能,并可通过通信接口输出,输出格式符合GB/T 22386的要求。

5.1.10应提供中文人机界面。

5.1.11应提供必要的辅助功能软件,如通信及维护软件、定值整定辅助软件、故障记录分析软件、调试辅助软件。

5.2装置功能及其技术要求
5.2.1频率定值整定范围及误差:
a)频率定值整定范围:45Hz~49.5Hz。

b)频率定值整定误差:≤0.01Hz。

5.2.2时间定值整定范围及误差:
a)低频减负荷基本轮:0.1s~1s。

b)低频减负荷特殊轮:5s~99.99s。

c)低频解列:0.1s~5s。

d)时间定值整定误差:≤1%整定值,或60ms。

5.2.3d f /d t定值的整定范围及误差:
a)加速切负荷d f /d t定值的整定范围:0.5Hz/s~3Hz/s。

b)d f /d t闭锁值的整定范围:4Hz/s~20Hz/s,d f /d t闭锁功能可单独退出。

c)d f /d t整定值的误差:≤0.2Hz/s或 10%(在45Hz~55Hz范围内,且在Δt=0.1s时)。

5.2.4装置的返回特性。

返回值和动作值的差值(返回值减动作值):0.05Hz~0.1Hz。

5.2.5应具有电压、频率等参数的监视功能。

5.2.6应有低频启动回路,只有在低频启动回路动作时才允许出口。

5.2.7当用于低频减负荷时,应分轮依次切负荷,并设置长延时的特殊轮。

同一套装置的基本轮设置(3~4)轮、特殊轮设置(1~2)轮。

5.2.8在频率下降较快时,装置应具有加速减负荷功能。

5.2.9当用于低频减负荷时,装置应具有防止过切负荷的措施。

5.2.10在电压互感器断线或电压回路接触不良等电压异常情况下,装置应具有防止误动的措施。

5.2.11应具有抵御谐波或波形畸变影响的能力。

5.2.12应具有防止负荷反馈时装置误动的措施。

5.2.13应有d f /d t闭锁功能。

当装置应用于具有小电源的小系统侧时,d f /d t闭锁定值应根据实际情况适当提高。

5.2.14低频减负荷和低频解列功能与低压减负荷和低压解列功能应完全独立,不能互相闭锁。

5.2.15在系统失步振荡过程中,如果低频减负荷装置动作,应评价为正确动作。

5.2.16若变电站母线在解列后,可能成为两个或多个独立系统的情况下,不宜采用一台装置,宜按母线独立配置。

5.2.17低频减负荷和低频解列装置不宜与保护装置合用。

6安全要求
装置的安全性能应满足DL/T 478中第6章的要求。

7检验和试验
7.1概述
7.1.1除另有规定外,各项试验均应在4.1.2规定的正常试验大气条件下进行。

7.1.2被试装置和测试仪表必须良好接地。

5
6
7.1.3 周围环境应符合4.1.5的规定。

7.1.4 装置的检验一般可分为出厂检验和型式试验两种。

7.2 出厂检验和型式试验 7.2.1 出厂检验
每台装置在出厂前应经制造厂质检部门进行出厂检验,确认检验合格后才能出厂。

检验合格的产品应有证明装置合格的产品合格证书。

出厂检验项目列于表1。

7.2.2 型式试验
a ) 凡遇下列情况之一时,应进行型式试验:
1) 新产品研发或定型前;
2) 产品正式投产后,如遇设计(包括软件)
、工艺材料、元器件等有较大改变,经评估会影响装置性能或安全时。

b ) 对系列产品中一个产品进行型式试验时,
宜充分考虑覆盖整个产品系列,且提供风险评估文件,确定哪些型式试验对整个系列产品有效,系列产品中其余产品还需要进行哪些型式试验。

c ) 如果装置已通过型式试验,且设计、元器件、工艺材料或软件无变更,不宜重复型式试验。


有变更应进行风险评估,给出确定哪些型式试验项目仍然有效,须重做哪些型式试验项目的文件。

型式试验项目列于表1。

7.2.3 检验和试验程序
a ) 应确保装置符合其规范,且在试验开始初测阶段,其功能可正确作用,在已规定的检验和试验
各阶段保持装置规定的特性。

检验中检测以及初始和最终检测都应通过直观的性能试验进行。

b ) 在检验和试验程序中,若前一个检验项目最终测量对应紧接着下一个检验项目初始测量,则没
有必要做两次测量。

7.2.4 合格判据
a )进行试验时,如未发现主要缺陷的样品,则判定本批产品或试品为合格。

b )装置的主要缺陷是指性能或功能不符合GB/T 14285—2006、DL/T 478、 GB/T
XXX —201X (电力系统安全稳定控制技术导则)和本标准的要求,需经更换重要元件后才能消除,或一般情况下有不可修复的缺陷(易损元件除外),其余的缺陷作为一般缺陷。

c )各项试验和检验时,一般缺陷数不应超过该项检查数的20%,否则按存在主要缺陷统计。

d )对于安全型式试验,可接受的准则是:零缺陷为合格,一般缺陷为不合格。

表1 检验和试验项目
序号
检验和试验项目
型式试验出厂检验执行标准
本标准中章条 机箱、插件尺寸
√ DL/T 478、GB/T 19520.12
4.6、7.14 表面电镀和涂覆 √ √
4.6、7.14 配线端子 √
DL/T 478 4.8 1
结构尺 寸和外 观检查 标志
√ √ DL/T 478、GB/T 191
6、8.1 功能试验 √ √
a
本标准 5 2
功能 要求
模拟试验或数字仿真 √
DL/T 478、DL/T 871 5 高温运行试验 √ DL/T 478、GB/T 2423.2 4.1.1、7.3 低温运行试验
√ DL/T 478、GB/T 2423.1 4.1.1、7.3 高温贮存试验 √ DL/T 478、GB/T 2423.2 4.1.4、7.3 低温贮存试验 √ DL/T 478、GB/T 2423.1 4.1.4、7.3 温度变化试验 √ DL/T 478、GB/T 2423.22 4.1.1、7.3 恒定湿热试验d √ DL/T 478、GB/T 2423.3 4.1.1、7.3 3
气候环 境要求
交变湿热试验d

DL/T 478、GB/T 2423.4
4.1.1、7.3
7
表1(续)
序号
检验和试验项目 型式试验出厂检验执行标准
本标准中章条 辐射发射 √ DL/T 478、GB/T 14598.16 4.11、7.4 发射 试验
传导发射 √ DL/T 478、GB/T 14598.16 4.11、7.4 辐射电磁场 √ DL/T 478、GB/T 14598.9 4.11、7.4 静电放电 √ DL/T 478、GB/T 14598.14 4.11、7.4 工频磁场
√ DL/T 478、GB/T 17626.8 4.11、7.4 射频场感应的传导
骚扰 √ DL/T 478、GB/T 14598.17 4.11、7.4 电快速瞬变 √ DL/T 478、GB/T 14598.10 4.11、7.4 1MHz 脉冲群 √ DL/T 478、GB/T 14598.13 4.11、7.4 100kHz 脉冲群
√ DL/T 478、GB/T 14598.13 4.11、7.4 浪涌 √ DL/T 478、GB/T 14598.18 4.11、7.4 4
电磁兼 容要求
抗扰度 试验
工频
√ DL/T 478、GB/T 14598.19 4.11、7.4 电压跌落
√ DL/T 478、GB/T 17626.29
GB/T 17626.11 7.5 短时中断 √ DL/T 478、GB/T 17626.29
GB/T 17626.11 7.5 纹波 √ DL/T 478、GB/T 17626.17
7.5 缓慢关断/启动 √ DL/T 478、 7.5 5
直流电 源电压 跌落短 时中断 瞬变
极性反接
√ DL/T 478、 7.5 6 功率消耗 √ DL/T 478、GB/T 7261 4.3、7.11 7 准确度和变差 √ √e DL/T 478、GB/T 7261 4.5、7.8 8 过载能力 √ DL/T 478、GB/T 7261
4.4、7.10
9 连续通电 √ DL/T 478、 4.13、7.13 10 输出继电器检验
√ DL/T 478、 4.8、7.12 冲击电压 √ DL/T 478、GB/T 14598.3 4.9、7.7 介质强度 √ √ DL/T 478、GB/T 14598.3 4.9、7.7 11
绝缘 试验
绝缘电阻 √ √ DL/T 478、GB/T 14598.3 4.9、7.7 振动响应
√ DL/T 478、GB/T 2423.10、
GB/T 11287 4.12、7.6 振动耐久 √ DL/T 478、GB/T 2423.10、
GB/T 11287 4.12、7.6 冲击响应 √ DL/T 478、GB/T 14537 4.12、7.6 冲击耐受 √ DL/T 478、GB/T 14537 4.12、7.6 12
机械 要求
碰撞
√ DL/T 478、GB/T 14537 4.12、7.6 13 外壳防护 √ DL/T 478、GB 4208
4.7、7.15 14
安全要求c

√b
DL/T 478、
6、7.16
注:符号“√”为该项目必做。

a 仅检验部分特征量准确度、动作时间或设备动作有关的测量精确度;
b 仅检验介质强度和保护接地连续性,见DL/T 478中7.16;
c 产品安全要求包括介质强度试验;
d 选做其中一项;
e 出厂检验时只做准确度试验,不做变差试验。

7.3气候环境试验
按DL/T 478中7.3的规定进行气候环境试验,装置应能承受4.1规定的气候环境及4.10规定的耐湿热性能要求,其性能和功能应符合第5章的规定。

7.4电磁兼容试验
7.4.1装置的端口
装置与外部电磁环境的特定接口称为端口。

它包含电源端口、输入端口、输出端口、通信端口、外壳端口和功能地端口,见图1。

图1保护装置的端口示意图
所有装置应按端口(由制造厂规定的端口)分别进行各项电磁兼容试验。

7.4.2电磁发射试验
按DL/T 478中7. 4的规定和方法,对装置进行电磁发射试验,应满足4.11的要求。

7.4.3抗扰度试验
按DL/T 478中7. 4的规定和方法,对装置进行电磁抗扰度试验,应满足4.11的要求。

7.5直流电源端口电压跌落、短时中断、瞬变和纹波试验
按照DL/T 478中7.5的要求,对辅助电源端口电压跌落、短时中断、瞬变和纹波进行试验和合格判定。

7.6机械试验
7.6.1振动响应和耐久(正弦)
根据4.12的要求,按照DL/T 478中表22规定的试验方法和合格判据,进行振动响应、耐久试验和合格判定。

7.6.2冲击响应、冲击耐久和碰撞
根据4.12的要求,按照DL/T 478中表23规定的试验方法和合格判据,进行冲击响应、冲击耐久、碰撞试验和合格判定。

7.7绝缘试验
根据4.9的要求,按DL/T 478中7.7的规定和方法,对装置进行绝缘试验,应满足4.9的要求。

7.8准确度和变差试验
根据4.5的要求,按GB/T 7261—2008中6.5的规定和方法,进行准确度和变差测量试验,并按DL/T 478中4.3的定义进行计算。

7.9装置功能试验
7.9.1用继电保护试验设备对装置功能进行试验,必要时进行电力系统动态模拟试验,装置的功能应符合第5章的规定,试验结果应符合DL/T 478中7.9.3的规定。

7.9.2基本功能试验
a)低频减负荷和低频解列功能的动作频率定值。

b)低频减负荷和低频解列功能的动作延时定值。

c)加速减负荷功能的d f /d t定值。

d)d f /d t闭锁定值。

e)低频减负荷和低频解列功能的动作特性。

f)装置及其逻辑回路动作的正确性。

8
DL / T 315 — 2010
9
7.9.3 其他功能试验
a ) 硬件系统自检。

b ) 硬件系统时钟功能。

c ) 通信及信息显示、输出功能。

d ) 开关量输出和输入回路检查。

e ) 数据采集系统的准确度和线性度。

7.10 过载能力试验
按照GB/T 7261—2008中第14章的规定和方法,对装置进行过载能力试验。

装置经受过载能力试验后应无绝缘损坏,其性能应符合4.4的规定。

7.11 功率消耗试验
按照GB/T 7261—2008中第7章的规定和方法,对装置进行功率消耗试验,其结果应符合4.3的规定。

7.12 输出继电器检验
按照4.8的要求,用继电保护试验设备对装置输出继电器的性能进行检验,其结果应符合DL/T 478中4.5.3的规定。

7.13 连续通电试验
按照DL/T 478中7.13的要求进行连续通电试验,试验期间性能应满足4.13的要求。

7.14 结构和外观检查
按照GB/T 7261—2008中第5章的要求逐项进行检查,其结果应符合DL/T 478中4.10.1的规定。

7.15 外壳防护
按照DL/T 478中4.10.2的要求,参照该标准中表2的要求进行检查。

7.16 安全要求试验
应按照DL/T 478中7.16的要求,进行安全要求试验。

7.17 检验或试验报告
装置在检验或试验之后,应给出包括检验或试验过程以及检验或试验结果的报告。

报告需要提供的信息,可参照DL/T 478中7.17的规定。

8 标志、包装、运输、贮存
8.1 标志 8.1.1 每台装置必须在机箱的显著位置设置持久明晰的标志或铭牌,标志下列内容:
a ) 装置型号及名称。

b ) 制造厂名全称及商标。

c ) 主要参数。

d ) 对外端子及接口标识。

e ) 出厂日期及编号。

8.1.2 包装箱上应以不易洗刷或脱落的涂料作如下标记
a ) 发货厂名、产品型号、名称。

b ) 收货单位名称、地址、到站。

c ) 包装箱外形尺寸(长×宽×高)及毛重。

d ) 包装箱外面书写“防潮”
、“向上”、“小心轻放”等字样。

e ) 包装箱外面应规定叠放层数。

f ) 应有符合规定的安全警示标志。

DL / T 315 — 2010
10 8.2 包装 8.2.1 产品包装前的检查
a ) 产品合格证书和装箱清单中各项内容应齐全。

b ) 产品外观无损伤。

c ) 产品表面无灰尘。

8.2.2 包装的一般要求
产品应有内包装和外包装,插件插箱的可动部分应锁紧扎牢,包装应有防尘、防雨、防水、防潮、防震等措施。

包装应符合GB/T 13384—2008的规定。

8.3 运输
产品应适用于陆运、空运、水运(海运),在4.1.4规定的条件下运输。

运输装卸按包装箱上的标志进行操作,并应符合GB/T 4798.2的规定。

8.4 贮存
长期不用的装置应保留原包装,在4.1.4规定的条件下贮存。

贮存场所应无酸、碱、盐及腐蚀性、爆炸性气体和灰尘以及雨、雪的侵害。

9 其他
9.1 随同装置提供
a ) 装箱清单(包括技术资料和技术文件)。

b ) 必要的装置电气原理图或接线图。

c ) 产品出厂合格证书。

d ) 按合同规定提供的备品、备件、安装附件、专用工具等。

9.2 质量保证期限
在用户遵守本标准和产品说明书所规定的运输、贮存规则条件下,装置自出厂之日起至安装不超过两年或安装运行后一年(按先到期),如装置或配件发生非人为损坏,制造厂应负责免费维修或更换。