INTRODUCTION
The 8726C (round plate) and 8726W (rectangular plate) Address-able Remote Lamps, shown in Figure 1, operate as an additional LED indicator for a device in the fire alarm control system’s addres-sable device circuit. The 8726C/8726W can be used when a device already has an accessory. The 8726C/8726W can be installed at any location of an addressable device circuit, and it remotely indicates the status of the device(s) in that same circuit.
Mode of Operation
The 8726C/8726W has one mode of operation: Direct Addressing Mode. The two-position jumper P1 must be positioned to set the mode to Direct Addressing.
When set and programmed to Direct Addressing Mode, system logic and programming determine when the ILED-H will blink.
Controls and Indicators
In Direct Addressing mode, the LED on the 8726C/8726W is controlled by logic functions programmed using the CIS-4 Tool. In Direct Addressing mode, the 8726C/8726W blink color (red only) cannot be changed.
PROGRAMMING
Refer to Figure 2 for the location of the programming holes and jumper P1.
Direct Addressing Mode
To set the 8726C/8726W to Direct Addressing Mode follow the steps listed below:
1.Determine a unique address for the 8726C/8726W.
2.Set jumper P1 to position 2 and
3.
3.
Connect the 8726C/8726W to the 8720 Programmer/Tester by
inserting the plug from the cable provided with the 8720 Programmer/Tester into the programming holes on the 8726C/8726W board.
4.
Follow the instructions in the 8720 Programmer/Tester Manual, P/N 315-033260FA, to program the 8726C/
8726W to the desired address. Record the device address on the label located on the 8726C/8726W front panel.
INSTALLATION INSTRUCTIONS AND WIRING FOR
INTELLIGENT REMOTE LAMPS
P/N 8726C AND 8726W
Figure 1
8726C And 8726W Remote Lamps
Siemens Industry, Inc.
Building Technologies Division • Florham Park, NJ Tel: (973) 593-2600 • Fax: (973) 593-6670
Web:
Figure 2
8726 Printed Circuit Board
5.
In the CIS-4 Programming Tool, assign the 8726C/8726W to an output zone. When an Input Group that is assigned to that Output Zone reports an off-normal event, the 8726C/8726W will blink red if the reported event type matches the output type selected for its zone. Refer to the CIS-4 Manual for further information.6.
The 8726C/8726W can now be installed and wired to the system.
WIRING
WARNING: Disconnect BATTERY and AC prior to working on equipment.Refer to the wiring diagram in Figure 3 below to wire the 8726C/8726W.
NOTE: The 8726C/8726W is polarity insensitive. Switching Line1 and Line2 has no effect on performance.
Recommended wire size:18 AWG minimum, 14 AWG maximum
Wire larger than 14 AWG can damage the connector.
LINE2
LINE1TO ADDRESSABLE DEVICE CIRCUIT
Figure 3
Wiring The 8726C/8726W
INSTALLATION
NOTE: Be sure to program the 8726C/8726W before installing the unit.
The 8726C/8726W may be placed at any location on the address-able device circuit. Use a single-gang switch box (user supplied) for mounting the 8726W. Use a 4-inch octagonal conduit box (user supplied) for mounting the 8726C. Refer to Figure 4 for typical 8726C/8726W installation.
The number of 8726C/8726W modules on the addressable device circuit must be included in the total count of intelligent field devices.For the restriction of the total number of devices in the FDLC loop,refer to the FDLC Installation Instructions, P/N 315-447360FA.
ELECTRICAL RATINGS
DO NOT USE REAR CONDUIT ENTRY
Figure 4
Mounting The 8726W
t
n e r r u C t u p n I A
m 1。