2-channel 安卓隔离开关放大器 IM1-22EX-R 230VAC Edition说明书

合集下载
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

E d i t i o n • 2015-10-24T 21:58:49+02:00
The 2-channel isolating switching amplifier IM1-22EX-R/230VAC is equipped with intrinsi-cally safe input circuits.
Sensors according to EN 60947-5-6 (NAMUR)or potential-free contact makers can be con-nected to the device.
The output circuits feature 2 relays, each with 1 NO contact.
Six front panel switches are available to set the output mode separately for each channel (NO/NC mode), as well as to enable/disable wire-break (WB) and short-circuit (SC) moni-toring separately.
When using mechanical contacts, wire-break and short-circuit monitoring must be switched off or the contacts must be wired to resistors (II) (see circuit diagram).
The Pwr LED lights green to indicate opera-tional readiness. The 2-color LEDs 1 and 2below light yellow to indicate the switching status of the corresponding output. The same LEDs turn red in the event of an input circuit error, provided the input circuit monitoring function is switched on. Thereupon the asso-ciated output relay drops out.
■ATEX, TR CU ■Installation in zone 2
■Adjustable output mode (NO/NC)■Input circuits monitored for wire-break/short-circuit (ON/OFF switchable)■Complete galvanic isolation
E d i t i o n • 2015-10-24T 21:58:49+02:00
Type code IM1-22EX-R/230VAC Ident no.
7541211Nominal voltage 230 VAC
Operating voltage 196…253 VAC Frequency
48…62 Hz Power consumption ð 2 VA
NAMUR input NAMUR
EN 60947-5-6Input circuit monitoring on/off switchable No-load voltage 8 VDC Short-circuit current 8 mA Input resistance 1 k òCable resistance ð 50 òSwitch-on threshold 1.75 mA Switch-off threshold
1.55 mA Wire breakage threshold ð 0.06 mA Short-circuit threshold ï 6.4 mA
Output circuits (digital) 2 x relays (NO)Relay switching voltage ð 250 VAC/30 VDC Switching current per output ð 2 A
Switching capacity per output ð 500 VA/60 W Switching frequency ð 10 Hz Contact quality AgNi, 3µ Au
Important note
For safety applications the values specified in the safety manual or the relevant Ex certificates (ATEX,IECEx, UL, etc.) apply.Ex approval acc. to conformity certificate PTB 00 ATEX 2033Application area
II (1) G, II (1) D
ignition protection category [Ex ia Ga] IIC; [Ex ia Da] IIIC Max. values:
Terminal connection: 1…6Max. output voltage U ð 9.6 V Max. output current I ð 10.7 mA Max. output power P ð 26 mW Characteristic
linear
Internal inductance/capacitance L /C C negligibly small, L negligibly small External inductance/capacitance L /C Ex ia
IIC IIIC Lo [mH]
1
515Co [µF](2 termi-nals)
1.10.84
6.2
4.4
Co [µF](3 termi-nals or more
1.10.8 6.2 4.3
State/ Fault
2 x yellow / red
Mechanical Data IP Rating
IP20Flammability class acc. to UL 94V-0
Ambient temperature -25 …+60 °C Storage temperature -40…+80°C Relative humidity ð 95 %
Dimensions 104 x 18 x 110 mm Weight
148 g
Mounting instruction for DIN rail / panel Housing material polycarbonate/ABS
Electrical connection 4 x 3-pin removable terminal blocks, reverse polarity protected, screw connection Terminal cross-section 1 x 2.5 mm / 2 x 1.5 mm Tightening torque
0.5 Nm
Output relay – Load curve
Output relay – Electrical lifetime
E d i t i o n • 2015-10-24T 21:58:49+02:00
Accessories
Type code Ident no.Description
Design
IM-CC-3X2BU/2BK
6900475
Cage clamp terminals for IM modules (Ex-devices with 18mm overall width); includes: 2 pcs. 3-pin blue terminals and 2pcs. 3-pin black terminals.
WM1 WIDER-STANDSMODUL
0912101The resistor module WM1 meets the requirements for line monitoring between a mechanical contact and a TURCK signal processor. The input circuit of the signal processor is designed for sensors acc. to EN60947-5-6 (NAMUR) and equipped with a wire-break and short-circuit monitoring func-tion.。