EATON MVS MVS2 WLI 中高压金属封闭加载断路器替代件说明书

合集下载
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

MVS/MVS2/WLI medium-voltage
metal-enclosed load interrupter replacement parts
Contents
i on Page
i pt
Descr
MVS/MSV2 product description . . . . . . . . . . . . . .2
WLI product description . . . . . . . . . . . . . . . . . . . .2
Switch ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Replacement capabilities . . . . . . . . . . . . . . . . . . . .2
Other replacement parts . . . . . . . . . . . . . . . . . . . .7
Renewal parts . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Torque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Further information . . . . . . . . . . . . . . . . . . . . . . . .8
2Renewal Parts MZ022004EN
Effective June 2020
MVS/MVS2/WLI medium-voltage metal-enclosed load interrupter
replacement parts
EATON
MVS/MVS2/WLI load interrupter switchgear
Standard manually operated fused MVS improvements
a Standard hinged barrier
b Larger, lower window (8 .00 x 16 .00-inch) double viewing area
c Rustproof latches
d Removabl
e switch e Nylon finned insulators
f G90 galvanized base
a
b
c
d
e
f
MVS/MSV2 product description
The MVS standard structures for 5 kV and 15 kV switchgear is
33 .00 to 48 .00 inches wide, 90 .38 inches high (indoor), 98 .88 inches high (outdoor), with varying depths . The standard structures for
27 kV and 38 kV switchgear is 48 .00 to 54 .00 inches wide, 101 .50 or 127 .00 inches high (indoor), 110 .00 or 135 .50 inches high (outdoor), with varying depths . Vertical sections are freestanding, close coupled to transformers and bolted together forming lineups .
WLI product description
The WLI (Load Interrupter) switch structure was offered in both 33 .00-inch and 36 .00-inch wide enclosures in the 5 kV and 15 kV ratings . Both designs used vertical sections that were freestanding, close coupled to transformers, and bolted together in lineups . WLI was offered in 5 kV , 15 kV , 25 kV , and 38 kV voltage ratings using 600 A and 1200 A switches .
Switch ratings
MVS
• 5 kV (600 A and 1200 A)• 15 kV (600 A and 1200 A)• 27 kV (600 A)•
38 kV (600 A)
MVS2
• 5 kV (600 A and 1200 A)• 15 kV (600 A and 1200 A)• 27 kV (600 A)•
38 kV (600 A)
WLI
• 5 kV • 15 kV • 25 kV •
38 kV
Replacement capabilities
MVS/MVS2/WLI
Eaton offers an inventory of newly manufactured renewal parts of MVS/MVS2/WLI switchgear . See page 3 through page 7 .
3
Renewal Parts MZ022004EN
Effective June 2020
MVS/MVS2/WLI medium-voltage metal-enclosed load interrupter replacement parts
EATON T able 1. Replacement parts—MVS/MVS2/WLI load break switch
Description and view
Part description
Quantity per switch
Style number
MVS MVS2WLI
Switch three-pole assemblies
Includes main and flicker blades, break jaws, and arc chutes
5/15 kV 60/95 kV BIL 600 A 1 set 7278A27G43—n —5/15 kV 60/95 kV BIL 1200 A 1 set 7278A27G44—n —27/38 kV 125/150 kV BIL 600 A 1 set 7278A27G66—n —27/38 kV 125/150 kV BIL 1200 A continuous, 600 A load break 1 set 7278A27G66—
n —
5/15 kV 60/95 kV BIL 600 A 1 set 7278A27G01n —n 5/15 kV 60/95 kV BIL 1200 A 1 set 7278A27G02n —n 27/38 kV 125/150 kV BIL 600 A 1 set 7278A27G05n

n
Includes main blades only, no arcing contacts 27/38 kV 125/150 kV BIL 1200 A (no load break) 1 set
7278A27G67
—n

Arcing contact three-pole assemblies
Includes flicker blades and arc chutes only 5/15 kV 60/95 kV BIL 600 A 1 set 7278A27G06n n n 5/15 kV 60/95 kV BIL 1200 A 1 set 7278A27G07n n n 27/38 kV 125/150 kV BIL 600 A
1 set 7278A27G08
n
n
n
Drive rod link assemblies
Figure 1
Figure 2
Glass polyester
5/15 kV 60/95 kV BIL (A)—Figure 1 1 set 7278A27G45—n —5/15 kV 60/95 kV BIL (B)—Figure 1 1 set 7278A27G53—n —27/38 kV 125/150 kV BIL—Figure 2 1 set 7278A27G54—
n —
5 kV 60 kV BIL (A)—Figure 1 1 set 7278A27G09n —n 15 kV 95 kV BIL (A)—Figure 1
1 set 7278A27G10n —n 27/38 kV 125/150 kV BIL—Figure 2
1 set
7278A27G12
n

n
Figure 3
Figure 4
Premium
5/15 kV 60/95 kV BIL (A)—Figure 3 1 set 7278A27G63—n —5/15 kV 60/95 kV BIL (B)—Figure 3 1 set 7278A27G62—n —27/38 kV 125/150 kV BIL—Figure 4 1 set 7278A27G57—
n —
5 kV 60 kV BIL (A)—Figure 3
1 set 7278A27G64n —n 15 kV 95 kV BIL (A)—Figure 3
1 set 7278A27G65n —n 27/38 kV 125/150 kV BIL—Figure 4 1 set 7278A27G58
n

n
Fin bus support
Two-phase brace support
Three-phase brace support
8-inch bus centers
Bus support three-phase (glass polyester) 1 each 260C003H51n n —Bus brace three-phase (glass polyester) 1 each 260C005H51n n —Bus brace two-phase (glass polyester) 1 each 260C005H53n n —Bus support three-phase (epoxy) 1 each 260C003H11n n —Bus brace three-phase (epoxy) 1 each 260C005H11n n —Bus brace two-phase (epoxy) 1 each 260C005H13
n
n —
4Renewal Parts MZ022004EN
Effective June 2020
MVS/MVS2/WLI medium-voltage metal-enclosed load interrupter
replacement parts
EATON
T able 1. Replacement parts—MVS/MVS2/WLI load break switch, continued
Description and view Part description
Quantity per switch
Style number
MVS
MVS2
WLI
Insulators
Polyester
Epoxy
5 kV 60 kV BIL glass polyester 3.50-inch tall 1 each 4892A97H01n n n 15 kV 95 kV BIL glass polyester 6.00-inch tall 1 each 4892A97H02n n n 5 kV 60 kV BIL epoxy 3.50-inch tall 1 each 4892A97H07n n n 15 kV 95 kV BIL epoxy 6.00-inch tall
1 each 4892A97H08n n n 27/38 kV 125/150 kV BIL epoxy 10.50-inch tall 1 each 4892A97H18
n
n
n
Removable handle
Switch operator—all ratings 1 each 7274A49H01n n n
Switch spring assemblies
Auxiliary spring
Main spring
5–15 kV / 40 kA fault close 1 set 7278A27G16n n n 5–15 kV / 61 kA fault close 1 set 7278A27G18n
n n
25–38 kV / all kA fault close 1 set 7278A27G75—
n

25 kV / 20 kA fault close 1 set 7278A27G19n —n 25 kV / 40 kA fault close 1 set 7278A27G20n —n 25 kV / 60/64 kA fault close 1 set 7278A27G21n —n 38 kV / 20 kA fault close 1 set 7278A27G22n —n 38 kV / 30/40 kA fault close 1 set 7278A27G23
n

n
Switch barrier assemblies
5 kV 1 set 7278A27G46—n —15 kV 1 set 7278A27G47—n —25–38 kV 1 set 7278A27G77—
n —
5–15 kV 1 set 7278A27G24n —n 25–38 kV 1 set 7278A27G25
n

n
5
Renewal Parts MZ022004EN
Effective June 2020
MVS/MVS2/WLI medium-voltage metal-enclosed load interrupter replacement parts
EATON T able 1. Replacement parts—MVS/MVS2/WLI load break switch, continued
Description and view Part description
Quantity per switch
Style number
MVS MVS2WLI
Fuse barrier assemblies
15 kV (clamp-in knob or quick disconnect) 1 set 6977C71G01n n —15 kV (bolt-in fuses)
1 set 7278A27G61—n —25–38 kV (all fuses) tall height switch 1 set 7278A27G78—n —25–38 kV (all fuses) low height switch 1 set 7278A27G79—n

15 kV (all fuses) 1 set 7278A27G26—
—n 25–38 kV (all fuses)
1 set 7278A27G27
n

n
Open-closed indicator/interlock cam
G01G02
For lock closed (top) or lock open (bottom)
1 each 260C934G02—
n —
For lock open/closed (top) or lock open (bottom) 1 each 260C934G01
n

n
Auxiliary switch assemblies
5NO and 5NC (on 5–15 kV main switch) 1 each 91C2682G01—n —5NO and 5NC (on 27–38 kV main switch) 1 each 91C2682G02—
n —
5NO and 5NC (on 5–38 kV main switch) 1 each 7278A27G28
n

n
6Renewal Parts MZ022004EN
Effective June 2020
MVS/MVS2/WLI medium-voltage metal-enclosed load interrupter
replacement parts
EATON
T able 1. Replacement parts—MVS/MVS2/WLI load break switch, continued
Description and view Part description
Quantity per switch
Style number
MVS
MVS2
WLI
Fuse live parts kit
Fuse live parts kit clamp-in knob (three-phase, top and bottom)RBA200 5 kV 1 set 98A1125G22
n n —RBA200 15 kV 1 set 98A1125G23n n —RBA400 5 kV 1 set 98A1125G24n n —RBA400 15 kV 1 set 98A1125G25n n —CLE-1 5 kV (single barrel 3-inch diameter) 1 set 98A1125G03n n —CLE-1 15 kV (single barrel 3-inch diameter) 1 set 98A1125G04n n —CLE-2 5 kV (double barrel 3-inch diameter) 1 set 98A1125G05n n —CLE-2 15 kV (double barrel 3-inch diameter) 1 set 98A1125G06n n —CX 5 kV (single barrel) 1 set 98A1125G09n n —CX 15 kV (single barrel) 1 set 98A1125G10n n —CXN 5–15 kV (single barrel 3-inch diameter) 1 set 98A1125G11n n —CXN 5–15 kV (single barrel 4-inch diameter) 1 set 98A1125G12n n —CXN 5–15 kV (double barrel 3-inch diameter) 1 set 98A1125G13n n —CXN 5–15 kV (double barrel 4-inch diameter) 1 set 98A1125G14n
n —RBA200 25 kV 1 set 98A1125G28—n —RBA200 38 kV 1 set 98A1125G29—n —RBA400 25 kV 1 set 98A1125G30—n —RBA400 38 kV 1 set 98A1125G31—n —EJO-1 38 kV (single barrel 3-inch diameter) a 1 set 98A1125G32—n —EJO-1 38 kV (double barrel 3-inch diameter) a 1 set 98A1125G33—n —EJO-1 38 kV (single barrel 3-inch diameter) b 1 set 98A1125G34—n —EJO-1 38 kV (double barrel 3-inch diameter) b 1 set 98A1125G35—n

Fuse live parts kit bolt-in (three-phase, top and bottom)RBA200 5–15 kV 1 set 7278A27G29——n RBA400 5–15 kV 1 set 7278A27G30—
—n RBA200 25–38 kV 1 set 7278A27G31n —n RBA400 25–38 kV 1 set 7278A27G32n
—n CLE-1 5–15 kV (single barrel 3-inch diameter) 1 set 7278A27G33——n CLE-2 5–15 kV (double barrel 3-inch diameter) 1 set 7278A27G34——n CX 5–15 kV (single barrel) 1 set 7278A27G36——n CXN 5–15 kV (single barrel 3-inch diameter) 1 set 7278A27G37——n CXN 5–15 kV (single barrel 4-inch diameter) 1 set 7278A27G38——n CXN 5–15 kV (double barrel 3-inch diameter) 1 set 7278A27G39——n CXN 5–15 kV (double barrel 4-inch diameter) 1 set 7278A27G40—
—n NX 23–27 kV 1 set 7278A27G41n —n EJO-1 38 kV 1 set 7278A27G42n —
n
RBA200, 400 or 800, 5 kV 1 set 260C285G51n n —RBA200, 400 or 800, 15 kV 1 set 260C285G52n n —BHLE 5–15 kV 1 set 260C285G50n
n —RBA200, 400 or 800, 25 kV 1 set 98A1125G36—n —RBA200, 400 or 800, 38 kV 1 set
98A1125G37—n —NX 23 kV a
1 set 98A1125G38—n —NX 27 kV a 1 set 98A1125G39—n —NX 23 kV b 1 set 98A1125G40—n —NX 27 kV b 1 set 98A1125G41—
n

NX 23–27 kV 1 set
7278A27G50
n

n
a For low height switch.
b For tall height switch.
7
Renewal Parts MZ022004EN
Effective June 2020
MVS/MVS2/WLI medium-voltage metal-enclosed load interrupter replacement parts
EATON T able 1. Replacement parts—MVS/MVS2/WLI load break switch, continued
Description and view Part description
Quantity per switch
Style number
MVS MVS2WLI
Space heaters
Low watt density 125 V As required 3614A50H11——n 250 V As required 3614A50H12—

n
125 V As required 3614A50H11n n —250 V
As required 3614A50H12
n
n

Shunt trip coil
48 Vdc 1 each 7278A78H01n n n 125 Vdc 1 each 7278A78H02n n n 250 Vdc 1 each 7278A78H03n n n 115 Vac 1 each 7278A78H04n n n 230 Vac 1 each 7278A78H05n n n Cap trip 1 each 7278A78H06
n
n
n
Other replacement parts
Other replacement parts are available but shall be considered on a job-by-job basis .
Include switch nameplate information located behind the switch
operating handle access door with any correspondence . Be sure this includes the ”CN“ or ”SM“ number .
Eaton
1000 Eaton Boulevard Cleveland, OH 44122 United States
Eaton .com
© 2020 Eaton
All Rights Reserved
Printed in USA
Publication No . MZ022004EN / Z24114 June 2020
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
MVS/MVS2/WLI medium-voltage metal-enclosed load interrupter
replacement parts
Renewal Parts MZ022004EN
Effective June 2020
Renewal parts
When ordering parts, specify the part description and mini-MVS switchgear assembly catalog number found on the nameplate . Enter on Suffix Q50 .
T able 2. Replacement parts
Part description Quantity
per assembly
Style
number
Switch pole assembly epoxy (three-pole set,
includes arc chute, switch blade, drive rod
and insulators)
17997A57G03
Non-fused switch and CLE fused switch
barrier assemblies (set of four)
17997A57G06 Switch operator lever assembly17997A57G11 Auxiliary switch assembly17997A57G12 Space heater17997A57G13 Filter (set of two)17997A57G05 Key interlock provision kit a17826C86G01 a Key interlock(s) provided by others.
T able 3. Replacement fuses
Fuse continuous ampere rating Quantity
per assembly
CLE
style number
1035981C29G01 1535981C29G02 2035981C29G03 2535981C29G04 3035981C29G05 4035981C65G01 5035981C65G02 6535981C65G03 8035981C65G04 10035981C65G05 12535981C65G06 15035981C65G07 17535981C65G08 20035981C65G09Torque values
Tighten the hardware per the table below .
T able 4. T orque values
Bolt diameter in inches Nominal torque, ft lb (Nm)
0.25 5 (6.78)
0.3112 (16.27)
0.3825 (33.90)
0.5050 (67.79)
0.6395 (128.82)
Further information
Publication number Description
DB 31-935Descriptive bulletin for WLI load
interrupter metal-enclosed switchgear DB 31-950Descriptive bulletin for unitized
dry-type power centers
IL 31-930-D Instructions for WLI and WVB
metal-enclosed switchgear。

相关文档