GE Fanuc RX3i PacSystem 919-535-3180输入模块说明说明书
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
Rx3i PacSystem
919-535-3180*******************GE Fanuc IC694MDL646/automation/ge-fanuc/rx3i-pacsystem/IC694MDL646
INPUT MODULE 24 VDC 16 POINT POS/NEG LOGIC 1 MSEC FIL-TER IC694M IC694MD IC694MDL
GFK-2314C Chapter 6 Discrete Input Modules 6-25
Input Module: 24 Volt DC 16 Point Pos/Neg Logic: IC694MDL646 The 24VDC Positive/Negative Logic 16 Point Input module, IC694MDL646, provides 16 input points in one group with a common power input terminal. The on and off response times for this module are typically 1 ms. This input module can be wired for either positive logic or negative logic. Input characteristics are compatible with a wide range of input devices, such as pushbuttons, limit switches, and electronic proximity switches. Current into an input point results in a logic 1 in the input status table (%I). Field devices can be powered from an external supply. Depending on their requirements, some input devices can be powered from the module’s +24V OUT and 0V OUT terminals. Sixteen green LEDs indicate the ON/OFF status of points 1 through 16. The blue bands on the label show that MDL646 is a low-voltage module. This module can be installed in any I/O slot in an RX3i system. Specifications: MDL646
Rated Voltage 24 volts DC Input Voltage Range 0 to +30 volts DC Inputs per Module 16 (one group with a single common) Isolation: Field to Backplane (optical) and to frame ground 250 VAC continuous;
1500 VAC for one minute
Input Current 7mA (typical) at rated voltage
Input Characteristics
On–state Voltage 11.5 to 30 volts DC
Off–state Voltage 0 to +5 volts DC
On–state Current 3.2mA minimum
Off–state Current 1.1mA maximum
On response Time 1ms typical
Off response Time 1ms typical
Power Consumption: 5V 80mA (all inputs on) from 5 volt
bus on backplane
Power Consumption: 24V 125mA from the Isolated 24 volt
backplane bus or from user
supplied power
Refer to Appendix A for product standards and general specifications.
6-26 PACSystems™ RX3i System Manual – October 2005 GFK-2314C
Field Wiring: MDL646
Terminals Connections 1 Inputs 1-16
Common 2 Input 1 3 Input 2 4 Input 3 5 Input 4 6 Input 5 7 Input 6 8 Input 7 9 Input 8 10 Input 9 11 Input 10 12 Input 11 13 Input 12 14 Input 13 15 Input 14 16 Input 15 17 Input 16 18 24VDC for input devices
19 0V for input
devices 20 No connection
Module Circuits Terminals Field Wiring
Note: If the 24V OUT pin is used to connect to input devices in the field, the isolation
specification for this module changes to:
Field to Backplane (optical) and to frame ground : 50 VAC continuous; 500 VAC for 1 minute。