LVDT变送器说明书
2003年7月LVDT卡片指南书说明书
Safety GuidelinesWarning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed.Qualified PersonnelThis device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.Warning:This product can only function properly and safely if it is correctly transported, stored, installed, set up, operated, and maintained.Note: Always use product in accordance with specifications.This document is available in bound version and inelectronic version. We encourage users to purchase authorized bound manuals, or to viewelectronic versions as designed and authored bySiemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions.While we have verified the contents ofthis manual for agreement with the instrumentation described, variationsremain possible. Thus we cannotguarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement. Technical data subject to change.MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc. Contact SMPI Technical Publications at the following address:Technical PublicationsSiemens Milltronics Process Instruments Inc.1954 Technology Drive, P.O. Box 4225Peterborough, Ontario, Canada, K9J 7B1Email: techpubs@SpecificationsPower:•±5 V dc (typically from a Milltronics integrator)Ambient Temperature:•-40 to 50 o C (-40 to 122 o F)Input:•0 to 1.0 Vac from LVDT based belt scale or solids flow meter (maximum 3m [(10 ft]separation between LVDT and Conditioner Card).Output:•0 to 50m Vdc to Milltronics BW100 or BW500/SF500(maximum 300 m (1000 ft) separation between Conditioner Card and Integrator).•Accuracy: 0.1% of rangeEnclosure:•General Purpose Type 4/Nema 4Approvals:•CECable:•LVDT Conditioner Card to Integrator: Belden 8404, 4 conductor, shielded 20 AWG orequivalent, 150m (500 ft) max.Belden 9260, 6 conductor, shielded 20 AWG or equivalent, 300 m (1000 ft) max.•LVDT to LVDT Conditioner Card (CT connection not required): Belden 8404, 4 conductor, shielded 20 AWG or equivalent, 300 m (1000 ft) max.7ML19985EF01LVDT Conditioner Card– INSTRUCTION MANUAL Page 1The LVDT Conditioner CardThe LVDT (Linear Variable Differential Transformer) Conditioner Card is an ancillary piece of equipment. The LVDT Conditioner Card provides all the complex circuitry required to allow the Milltronics BW100 or BW500 to interface with a position transducer (LVDT) based scale.It also allows the SF500 to interface with a position transducer (LVDT) based solidsflowmeter.General OperationThe Milltronics BW100 or BW500/SF500 supplies the excitation for the LVDT Conditioner Card, which in turn supplies the excitation for the LVDT.In belt scale operations the LVDT signal is proportional to material loading. The LVDT signal is converted to a 0-50mVdc signal then applied to the Load Cell A input of theMilltronics BW100 or BW 500 and used with the speed signal to produce an integral rate signal.In solids flowmeter applications, the LVDT signal is proportional to the material flow rate.The LVDT signal is converted to a 0-50mV dc signal then applied to Load Cell A input of the Milltronics SF500 and used to produce an integral rate signal. InterconnectionPage 2 LVDT Conditioner Card – INSTRUCTION MANUAL7ML19985EF01Connection to a BW500/SF500* Where separation between the integrator and LVDT conditioner exceeds 150 m (500 ft):•remove the jumpers BW500/SF500 terminal 11/12 and 13/14, or BW100 terminal 17/18 and 19/20•run additional conductors from:BW500/SF500 terminal 12, or Milltronics BW100 terminal 19, to conditioner terminalblock marked Integrator +EXCBW500/SF500 terminal 13, or Milltronics BW100 terminal 18, to conditioner terminalblock marked Integrator -EXCFor further connection information on specific LVDTs, consult Siemens Milltronics. See for a representative near you.!Shields are common, but not grounded to chassis. Run cable shields through SHLD terminals and ground at integrator only.The LVDT Conditioner Card is also available in a smaller configuration for mounting within the solids flowmeter sensing head.7ML19985EF01LVDT Conditioner Card– INSTRUCTION MANUAL Page 3InstallationTop ViewPage 4 LVDT Conditioner Card – INSTRUCTION MANUAL7ML19985EF01。
LVDT变送器说明书
RDP-LVDT 位移传感器说明书一、概述RDP-LVDT 位移传感器分为两个部分,第一部分为前置器部分,它与被测量物相连,根据被测物体位移,产生的频率幅值相应改变;第二部分为变送器单元,它把频率信号转化成两路1-5V 信号和两路4-20mA 信号。
二、功能指标RDP-LVDT 为英国产的五线制位移传感器,所采用的LVDT 行程一般为0-50mm 、0-100mm 和0-150mm 。
其出线图见下图:LVDT 位移传感器的变送器安装在DEH 机柜内,它接受两路24VDC 直流电源,形成冗余配置,一路失电不影响其正常工作,它的接线图和元件布置图见下图:LVDT 位移传感器的变送器大致可以分成三部分,电源部分(24VDC 转化成±15V ,两个绿色发光二极管分别表示±15V 是否工作正常);转换电路部分(提供LVDT 激励信号,把检测到的频率变化信号转化成1-5V 和4-20毫安信号);输入输出端子部分。
LVDT 位移传感器的变送器有四个可调电位器,分别是:调零电位器、调幅电位器、红黄LVDT出线图黑电流I调整电位器和电流II调整电位器。
LVDT调整的顺序为:电压输出的调零调幅最后调整电流的输出(RDP-ACT系列五线位移传感器的红线接输入的1端子、黄线接2端子、蓝线接3端子、绿线接4端子、黑线悬空)。
功能指标●接受两路24VDC 容量0.3安培●RDP-ACT系列五线位移传感器信号●输出1-5V两路●输出4-20mA两路●精度为0.1%三、LVDT零点满度的调整1、把LVDT位移传感器的红、黄、蓝、绿四线接到位移变送器输入端子的1、2、3、4端子上(陡河#3机调试在红黄线圈和蓝绿线圈里分别串接了一个220欧姆电阻,GV变送器中的R12由原来的10K改为17K),把LVDT位移传感器的黑线悬空;LVDT 位移传感器到DEH机柜的接线应是屏蔽电缆,屏蔽线应和LVDT位移传感器出线的屏蔽线短接,并在DEH机柜内接地;GV2、GV4和IV1的屏蔽电缆有现场接地的现象。
700 系列液位变送器 说明书
主要特点◆完全浸入式传感器◆符合RFI / EMC 标准◆抗震结构设计◆直径仅为25mm ,结构紧凑◆安装简便◆EExia IIC T5 本质安全认证◆满量程范围是1-100m wg700系列700系列液位变送器,采用高灵敏度压力膜片和LVDT 测量技术。
专为安装受限制的场合设计,比如深井或地下储存容器。
标准模块完全悬浮于自身电缆上,前端螺纹接口更易于安装。
如需硬性安装,传感器可用支杆支撑安装,也可根据应用需要做成可卸或全焊接构造。
插入的时候仅仅需要一个1英寸的伸缩装置即可完成。
标准的构造原料适用于大多数液体介质,对于一些侵蚀性强的化学介质,可用聚氯乙烯代替不锈钢材质。
远程电路控制功能大大简化了运行和周期检查过程。
第1页技术指标◆量程调节:3:1标准量程◆标准量程:1,2,4,8,16,32,50,100m H2O ◆零点调节:±10%量程◆过载:5倍量程◆传感器材质:316不锈钢,聚氯乙烯可选◆膜片:哈氏合金◆供电电压:12-30V DC◆最大负载电阻:30V时 1000Ω◆输出信号:4-20mA DC,二线制◆精度:优于±0.5%◆传感器电缆:阻燃、屏蔽,带有内部导气管◆最大长度:300m◆运行温度:-25℃- +85℃◆温漂系数:< 0.05% /℃◆环境温度:> -50°C◆电路壳体:IP65(IP67可选),内置RFI屏幕第2页H 哈氏合金C 膜片阻燃屏蔽电缆,带内部导气孔每米聚四氟乙烯保护层**S**变送器以mH 2O 标定量程特殊标度,如提高/校正零点等浸入式传感器-不锈钢材质,3mTPE 电缆和放大器探针式传感器-全焊接不锈钢构造,含1m 支杆 730用不锈钢支杆,每50cm 加价1/2”BSP 内螺纹支杆安装1”插入式传感器,含焊接装置B E F G 不需要选择高温传感器(浸入式可达120℃,外用型可达145℃)温度补偿传感器 (±0.01% / ℃)高精度(0.1%)IP67 放大器防护7007307407701S 2S 4S 8S 16S 32S 50S 100S 1mH 2O2 mH 2O4 mH 2O8 mH 2O16 mH 2O32 mH 2O50 mH 2O100 mH 2O (非哈氏合金)外部电缆超过3m (总长<10m),每米加价外部电缆超过3m (总长<20m),每米加价外部电缆超过3m (总长<50m),每米加价外部电缆超过3m (总长>50m),每米加价NP CF CFS DI CC IS NA 9111316 1/2” NTP 支杆连接(740)1”BSP 软钢安装(730)DN25罐顶安装法兰(730)集成数字指示器(仅限非IS ) 传感器电缆接头(不能适用于浸入式) IS 鉴定 非本安型 带PG9密封管的信号电缆 带PG11密封管的信号电缆 带PG13.5密封管的信号电缆 带PG16密封管的信号电缆P Q 选型表第3页。
T80操作说明书
T80系列控制器简易操作手册目录一、操作画面 (2)二、操作步骤 (3)1.准备启动 (3)2.设置目标转速 (3)3.升降负荷 (4)1>CV阀控 (4)2>功控 (4)3>主汽压控 (5)三、参数设置与功能选择 (6)四、常规伺服阀的调试方法 (9)一、操作画面操作员画面主要分以下四个画面,汽机参数,测点清单,电调试验,电调主控. 其中汽机参数,测点清单,电调试验三个画面的数据须工程师权限才允许操作修改。
如图1-1,2,3,4。
图 1-1.汽机参数图 1-2.测点清单图 1-3.电调试验图 1-4.电调主控二、操作步骤1.启动准备在现场进行挂闸,并且开启主汽门,T80画面相应的状态会改变,外部设备发允许启动信号,使“允许启动”灯亮。
此时点击电调主控画面的运行按钮,转速控制面板亮(转速框图由灰色变为蓝色)。
机组已进入等待冲转状态。
2.设置目标转速机组挂闸进入等待冲转状态后,(注:此时此框图为蓝色)转速控制栏在转速控制栏目标转速输入目标转速(一般设定为3000 r/min)值。
也可以设置为其他任何非临界区的转速值。
首次起机建议先给500转,再1200,然后2500,以此类推。
目标转速设定后,给定转速将以默认的升速率向目标转速靠近;机组开始冲转;司机可根据实际情况在升速率输入框内修改升速率,允许取值范围为0~800最大升速率 r/min/min;(建议慢些100~200)。
随着给定转速的增加,总阀位给定增加,油动机开启,机组转速增加;暖机时间到或点击“停止暖机”按钮后继续升速;当需要保持当前转速时,点击“给定保持”。
3.升降负荷1>CV阀控并网带初负荷后,操作员可通过点按“CV阀控”CV阀控控制栏栏内的增、减按钮(即单箭头与双箭头键,改变总阀位给定值单位为%),从而控制调门开度,来控制负荷。
2>功控功控控制栏功控投入:在电网要求机组维持负荷不变时,可投入功率反馈控制。
LVDT详解
图1-6
图1-5
图1-7
回弹式LVDT 内弹簧式LVDT
弹簧在线圈内运动,要求弹簧无磁,如图1-8所示。 滚珠导轨式LVDT
用于精密测量,与带滚珠导轨的测量头相连接,弹簧为宝塔形态,如图19所示。
图1-21 图1-8
图1-9
高压LVDT 气密封型LVDT
LVDT线圈密封在焊接的外管中,引出线用耐压的插座连接,如图1-10所示。
器分为三级: 商业级:0℃~+70℃ 工业级:-40℃~+85℃ 军 级:-55℃~+125℃ 9. 时间常数小,动态特性好,频带宽一般为200HZ(5ms)最高可500HZ (2ms)。 10.毛利率高:50%。
LVDT的特点
LVDT与光栅,磁栅,同步感应器等高精度测长仪器相比有以下几个优 点:
度20g。 5. 体积小,价格低,性能价格比高。
LVDT分类
按用途分类 交流LVDT 直流LVDT 回弹式LVDT 高压LVDT 航空航天LVDT 特种LVDT
交流LVDT 技术指标
交流LVDT的技术指标:
输入电压: 3Vrms (1~20Vrms)
激励频率: 2.5KHz (1~10KHz)
线性度: 0.5%;0.25%;0.2%;0.1%
LVDT工作原理 直流LVDT,更确切地说应该称为位移变送器。它是在位移传感器
LVDT基础上,外加电路,不论多大行程,都可以使其输出均为0~ ±5V,或0~±10V标准电压信号,或4~20mA标准电流信号的变送 器,其方框图如图1-2:
图1-2
LVDT的特点
1.结构简单,工作可靠,寿命长,线性度好,重复性好,性能价格比高,利税 率高。
(6.36—127毫米)≤0.5% 10.0英寸(254毫米)≤1.0% 输出: 4~20mA,二线制环路 回路供电: 12.75 to 28VDC 最大回路电阻: 600Ω@28VDC\ 输出噪声与纹波:25µA Pk-Pk (最大) 工作温度: -13°F至185°F(-25°至85°C) 灵敏度温度系数:0.04%/°C (最大) 稳定性: 30分钟预热之后为0.10%
LD630系列LVDT 位移变送器
LD630系列LVDT 位移变送器
产品特点
线性度少于0.2%
行程:5 ~ 300 mm
可提供4 ~ 20 mA或20 ~ 4 mA版本
坚固的不锈钢壳体结构
带有可拆卸弹簧的导引芯
IP67环境保护等级
产品描述
LD630系列电流输出位移变送器具有经改进的IP67级密封,可通过刚性载体与聚合物导引装置连接。
这些变送器精准可靠,尤其适用于潮湿和腐蚀性环境。
输出选项为直接作用的4 ~ 20 mA或反向作用的20 ~ 4 mA。
当导引芯完全拉出时,直接作用型号的输出为4 mA,当导引芯完全推入后,输出增加至20 mA。
规格:
线性度:<0.2% FSO
激励电压:10 ~ 30 Vdc
输出: 4 ~ 20 mA
输出波纹:0.02% FSO
带宽:500 Hz (-3 dB)
储存温度:-20 ~ 85°C (-4 ~ 185°F) 工作温度:0 ~ 65°C (32 ~ 149°F) 振动(正弦频率):
10 ~ 50 Hz:1 ~ 10 g rms线性振幅50 Hz ~ 1 kHz:10 g rms振幅
冲击:
掉落测试:从1 m (3')掉落硬表面
倾倒测试:每端倾倒在硬表面上10次
电缆:PFA,2 m (6')长
核心材料:镍-铁。
MDS系列LVDT测微仪用户手册
M D S系列 L V D T测微仪用户手册哈尔滨工业大学博实精密测控有限责任公司目 录目 录 (I)1注意事项 (1)2工作环境 (1)3产品概述 (1)3.2产品命名 (2)3.3产品特征 (2)3.4产品主要技术指标 (3)4基本操作 (4)4.1面板说明 (4)4.2V F D与按键说明 (5)4.3操作指南 (6)4.3.3测量工作状态 (6)4.3.4串行通信 (6)4.3.5零点电压校准 (7)5开箱检验 (7)5.1打开包装注意事项 (7)5.2检查内容 (7)6运输、贮存 (8)在使用本仪器前,请详细阅读本用户手册。
使用过程中请按照本用户手册操作,出现问题时,请与本公司联系,寻求技术支持。
切勿自行对产品进行拆卸改造,否则本公司将不对所产生的任何后果承担责任。
1注意事项请阅读下列注意事项,以避免人身伤害,并防止本产品或与其相连接的任何其他产品受到损坏。
为了避免可能发生的危险,本产品只可在规定的范围内使用。
Ø使用适当的电源线:只可使用本产品附带的专用电源线,使用前应检查电源线,确认没有损坏及不漏电后方可使用。
Ø避免接触裸露电路:产品有电时,请勿触摸裸露的接点和部件。
Ø不要带电拔插输入及输出线Ø保持产品表面清洁及干燥Ø使用完毕后,请关闭电源开关2工作环境Ø电源要求:220V±10%50HZ±10%Ø环境温度:0℃ ~ 45℃Ø相对湿度:<85%3产品概述M D S系列多量程L V D T测微仪是适用于多种测量范围的高精度微位移检测仪,可以实现微米级直至纳米级的高精度微位移检测,广泛应用于国防,生物工程,微电子工业,光纤通信等各种需要动/静态微位移检测的领域,具有性能优越,测量精度高,价格低等优点。
3.1L V D T工作原理L V D T是L i near V ariable Differential Transformer的英文缩写,即线性差动变压器式传感器。
LVDT安装及整定说明
LVDT安装及整定说明1、更换SM3461端子板后首先检查跳线,跳线说明如下:JP1:4~20mA输出信号选择。
1-2短接表示LVDT信号。
JP2:上位机阀位设定值幅度调整选择。
短接将电位器SET-AM断开,不改变阀位设定值。
JP3:阀位设定值选择。
短接表示采用上位机下传的阀位设定值。
JP4:比例功能选择。
短接启用比例功能JP6:用主回路相同的反馈信号作为局部反馈。
断开无此局部反馈功能JP7 JP8 JP9 电位器不需要调整。
JP10 断开,不选择积分功能。
JP13短接,JP11、JP12断开,恒压输出。
JP14短接,启用输出偏置调零功能。
JP15 1-2短接,输出正电压时开油动机。
JP16短接,启用LVDT反馈功能。
JP17 /JP18 /JP19/JP23/JP24无需调整JP20 2-3短接交流1通道输入信号,表示选用的为交流型LVDTJP25 2-3短接交流2通道输入信号,表示选用的为交流型LVDTJP5/JP21/JP22/JP26/JP27/JP28 全断开2、阀门LVDT安装及整定1)LVDT安装后测量主线圈阻值约为240Ω,两个次级线圈阻值约为290Ω。
2)SM3461板卡接线后量交流电压,主线圈约3VAC,两个次级线圈交流电压分别为4.5VAC和1.5VAC。
3)量V0对地直流电压,PID-V0(第3点)与GND(第6点)应为0VDC,如不为0则调整PID-ZERO将电压调为0V.DC4)阀门全关时测量LVDT1(第4点)\LVDT2(第5点)对地直流电压应为0.2~1.5VDC,全开时测量LVDT1(第4点)\LVDT2(第5点)对地直流电压应为3.5~4.8VDC.5)DCS画面中点击阀门自动整定。
6)整定后,投入维修开关,手动输出指令20%,40%,60%,80% ,100%,检查阀门反馈线性误差。
如偏差较大,将指令输出到50%,调节PID-P,将反馈值调至50%左右(48%即可),此时PID-V0(第3点)与GND(第6点)应为0.2~1.5VDC.7)新板卡安装调试时PID-P和PID-D电压调大1V左右。
变送器使用说明书
变送器使⽤说明书⽬录⼀、技术参数 (1)⼆、安装前注意事项 (2)三、安装 (3)四、接线说明 (4)4.1接线端⼦图 (4)4.2仪器接线功能图 (5)4.3接线端⼦说明 (5)4.4电极接线⽰意图 (6)五、按键和界⾯说明 (7)5.1按键说明 (7)5.2界⾯说明 (8)六、操作说明 (11)6.1参数设置操作 (12)6.2校正操作 (13)七、电极保养说明 (16)⼋、操作密码 (17)8.1、参数设置密码 (17)8.2、校正密码 (17)⼀、技术参数⼆、安装前注意事项1、请选择通风良好的位置安装pH计(以下简称仪器),并避免仪器直接受到阳光照射。
2、安装前请阅读本说明书,以免接线不正确导致仪器损坏。
3、在所有接线未完成前,请勿给仪器上电,以免发⽣危险。
4、pH或ORP电极信号传输须采⽤专⽤电极电缆,不能随便⽤⼀般电缆代替,否则将产⽣错误的测量结果。
5、使⽤220VAC的电源时,请避免使⽤三相电源,以免造成电源突波⼲扰。
(若有电源突波⼲扰现象发⽣,可将仪器⽤的电源与动⼒装置电源分开,即仪器采⽤单独电源,或在所有动⼒装置的电源端接突波吸收器来消除突波,如加药机、搅拌机等)。
6、仪器内部的继电器为⼩电流继电器,若要控制较⼤动⼒的附属装置时,请外接电流容量较⼤的继电器,以确保仪器的安全。
7、下图为仪器和动⼒装置的接线⽰意图。
图2-1 仪器和动⼒装置接线⽰意图三、安装1、在配电箱⾯板上开好110+1mm×110+1mm 的仪器安装⽅孔。
2、仪器从配电箱的⾯板直接放⼊,将仪器附带的的固定架卡⼊仪器两侧的固定孔,⽤⼀字型螺丝⼑拧紧固定螺丝。
安装⽰意图如下:主视⽰意图侧视⽰意图(((固定⽰意图开孔尺⼨图3-1 仪器尺⼨和安装⽰意图四、接线说明4.1 接线端⼦图图4-1 仪器接线端⼦图4.2 仪器接线功能图+-RTD图4-2 仪器接线功能图4.4 电极接线⽰意图图4-3电极接线⽰意图五、按键和界⾯说明图5-1 按键⾯板图5.1 按键说明Cal ——校正功能键;Conf ——参数设置功能键;——功能切换/数字循环功能键;——移位功能键;Enter ——确认功能键;5.2 界⾯说明 5.2.1、测量界⾯pH 测量界⾯ ORP 测量界⾯正常⼯作时,若没有进⾏“校正”或“参数设置”操作,仪器显⽰测量界⾯。
LVDT间距显示器 使用操作说明书
LVDT間距顯示器LVDT DIMENSION OF DISPLAY使用操作說明書PANEL METERCH ♁ ALM-203目 錄1. 間距控制器安裝使用注意要點 (1)Installation Note of LVDT2.間距控制器校正說明……………………3 CHECK FOR LVDT3.LVDT 本體檢查方式…………………….4 QA process of LVDT4.故障判別…………………………………5 JUDGEMENT5.LVDT 顯示器尺寸圖 (6)6.LVDT + ALM203接線圖 (7)7.LVDT + ALC304接線圖 (8)8.LVDT + 新AMP + 顯示器接線圖 (9)9.LVDT +舊AMP + 顯示器接線圖…….10 (118mm X 100mm)(166mm X 116mm)10. LVDT 尺寸圖 (11)一.間距控制器(LVDT)安裝使用注意要點:Installation Note of LVDT:1.輸入控制器或顯示器的AC 220V電源,請先以隔離型變壓器隔離以避免雜訊輸入。
For Input Power AC220V, Please use isolation transformer to make this input power AC220V.2.使用前請先確認輸入控制器之電源是否為AC220V容許值±10%。
Make sure the Input Power is AC220V ±10%.3.控制器AC220V電源,請單獨使用,不要與設定輸出接點並聯共用。
The Input power of controller AC220V must only be used in power input. It can not use in anotherfunction(such as output).4.設定輸出接點只提供訊號的傳輸使用,馬達運轉控制需求請外接RELAY,以減低接點故障。
北京赛斯维测控技术有限公司MP系列工业型LVDT产品说明说明书
• • • •应用选件产品说明特点MP系列适用恶劣环境法兰安装与所有Schaevitz型号处理设备相兼容• • • 全密闭封装,适用于恶劣的环境法兰安装螺丝接线柱与Schaevitz信号处理设备兼容所有产品均附有校准证• • 适用于恶劣工业环境5 KHz激励频率测试公制螺纹铁芯小直径/轻质铁芯••• MP系列LVDT适用于重工业环境。
它的线圈采用经阳极氧化处理的挤压铝外壳密封,可以抗电磁和静电干扰。
坚固的金属接线板代替了导线。
聚四氟乙烯内衬套是标准配件。
性能参数输入电压频率范围工作温度零点电压耐受冲击振动允限线圈材料外壳材料电气连接3Vrms(标称)400Hz至5KHz-65℉~300℉(-55℃~150℃)<0.5%FS1000g/11毫秒20g/2KHz高密度玻璃填充聚合物经阳极氧化铝处理的铝2.5KHz时的性能和电气规格型号 线性量程 线性度(±%F.R.) mV/V每 欧姆 差型号 英寸 毫米 0.01英寸 毫米 初级 次级 度所有校准均在室温下执行。
50 100 125 150*要求特殊的缩减铁芯。
6针接线端子MP系列标称 灵敏度 阻抗 相位500 MP ±0.500 ±12.70 0.150.25 0.35 0.75 0.7 25.6 460 375 -1 1000 MP ±1.00 ±25.4 0.25 0.25 1.00 1.30* 0.39 14.2 460 320 -3 2000 MP ±2.00 ±50.8 0.25 0.25 0.50* 1.00* 0.23 8.3 330 330 +5 3000 MP ±3.00 ±76.2 0.15 0.25 0.50* 1.00* 0.25 9.1 315 830 +11 4000 MP ±4.00 ±101.6 0.15 0.25 0.60* 1.00* 0.20 7.1 275 550 +1 5000 MP ±5.00 ±127.0 0.15 0.25 1.00* n/v 0.14 5.5 310 400 +3 10000 MP±10.0±2540.150.251.00*n/r0.072.8550750-5布线产品尺寸机械性能型号 主体铁芯A(主体)B(铁芯)MP系列 重量尺寸型号 盎司克 英寸 毫米 盎司克 英寸 毫米 500 MP 12.36 350 0.64 18 6.50 165.1 3.45 87.6 1000 MP 16.59 470 0.74 21 7.64 194.1 4.00 101.6 2000 MP 21.00 595 0.95 27 11.01 279.7 5.30 134.6 3000 MP 26.12 740 0.99 28 13.85 351.8 5.60 142.2 4000 MP 31.77 900 1.27 36 16.68 423.7 7.00 177.8 5000 MP 36.18 1025 1.27 36 18.92 480.6 7.00 177.8 10000 MP60.8917251.524331.90810.38.50215.9The information in this sheet has been carefully reviewed and is believed to be accurate; however, no responsibility is assumed for inaccuracies. Furthermore, this information does not convey to the purchaser of such devices any license under the patent rights to themanufacturer. Measurement Specialties, Inc. reserves the right to make changes without further notice to any product herein. Measurement Specialties, Inc. makes no warranty, representation or guarantee regarding the suitability of its product for any particular purpose, nor does Measurement Specialties, Inc. assume any liability arising out of the application or use of any product or circuit and specifically disclaims any and all liability, including without limitation consequential or incidental damages. Typical parameters can and do vary in different applications. All operating parameters must be validated for each customer application by customer’s technical experts. Measurement Specialties, Inc. does not convey any license under its patent rights nor the rights of others.联系方式Measurement Specialties Inc.1000 Lucas Way Hampton,VA 23666Tel: 1-757-766-1500Fax: 1-757-766-4297Sales: ***************************105 av.Du General EisenhowerBP 23705,31037 Toulouse,Cedex 1,France Tel: +33 561-194-824Fax: +33 561-194-553Sales: *************************中国北美 欧洲 北京赛斯维测控技术有限公司北京市朝阳区望京西路48号金隅国际C座1002电话:+86 010 8477 5646传真:+86 010 5894 9029邮箱:******************MEAS Europe产品选型指定MP型号以及所需选件编号。
变送器使用说明书
目录1技术参数 (2)2安装说明 (3)3接线说明 (5)3.1 变送器(直流供电型)接线端子说明 (6)3.2 变送器(交流供电型)接线端子说明 (7)3.3 仪器接线功能图 (8)3.4 电极接线示意图 (8)4按键和界面说明 (9)4.1 按键及指示灯说明 (9)4.2 界面说明 (10)5操作说明 (13)5.1 参数设置操作 (14)5.2 校正操作 (15)6电极诊断及出错信息 (17)7电极保养说明 (19)8操作密码 (20)8.1 参数设置密码 (20)8.2 校正密码 (20)附1缓冲液 (21)附2技术术语 (23)安全预防措施请认真阅读并遵守下列要求!在仪器上电前,请对照您持有仪表的型号,确认供电电压:变送器需用18V-30VDC直流电源供电变送器需用100V-250V AC交流电源供电打开仪器会有电路部分暴露,因此除了接线仓和仪表透明罩外,不应打开仪器其它部分。
打开的仪器内部能接触到的器件上的电压足以威胁人的生命。
若需检修,需要返回厂家。
只有厂家专业人员才能在带电情况下打开仪器。
当相应的保护失效时,请停止操作。
出现以下情况时,保护可能失效:◇仪器外观有明显破损◇仪器不能正常测量◇长期储存于超过70℃的环境中◇经过剧烈的震动或碰撞后11 技术参数22安装说明①31、请选择合适位置安装pH计(以下简称仪器),避免仪器直接受到阳光照射。
2、安装前请阅读本说明书,以免接线不正确导致仪器损坏。
3、pH或ORP电极信号传输须采用专用电极电缆,请不要用一般电缆代替,否则将产生错误的测量结果。
4、仪器内部的继电器为小电流继电器,若要控制较大动力的图2-1 仪器和动力装置接线示意图43 接线说明接线仓内部图(拆掉压线盖)接线步骤:打开接线仓盖→拆下压线盖→接线→装上压线盖→装上接线仓盖。
5673.3 仪器接线功能图84 按键和界面说明Wash 灯:清洗指示灯,当清洗继电器动作时,此灯亮Alarm灯:报警指示灯,仪表超限报警或自检报警时,此灯亮94.2 界面说明4.2.1 测量界面入码自动清零,请操作人员重新输入。
Sensata技术有限公司LVDT传感器产品说明说明书
Page 1 Copyright © 2018 Sensata Technologies, Inc. | LVDT SENSORSDescriptionFeatures• Single & multiple channel designs (tandem or parallel arrangement)• Linear displacement from .001” to 60”• Stainless steel construction or lightweight aluminum • Operating pressures up to 10,000 psi (15.000 psi burst pressure)• High temperature & vibration environments (per MIL-STD 810 or RTCA DO-160)• High accuracy (± 0.25% full scale)• Infinite resolution • Hermetic designs available • Linearity (± 0.1% full scale)• Fault detection • High reliability (single channel MTBF of 1,000,000 hrs. typical)Applications• Flight control actuators • Valves • Nose wheel steering systems • Cockpit controls • Engine bleed air systems • Fuel controls • Fly-by-wire systems • Brake-by-wire systems • Environmental control systems • Thrust reverser • Engine control actuators • Engine fuel controlKavlico LVDTs operate using a non-contacting induction principle, providing friction free motion and nearly infinite resolution. These sensors have been refined and improved for over 50 years, making Kavlico LVDTs the standard for flight and engine control position measurements. Kavlico is the largest manufacturer of matched multiple channel sensors for redundancy.Multiple channels are provided in a variety of housing designs that can be directly mounted on the airframe control surfaces and cockpit controls, orprovided as an integral part of a servo valve or main ram actuator. Over 1 million Kavlico LVDTs are installed in aircraft worldwide.Page CONTACT US Americas +1 (800) 350 2727 – Option 1****************************Europe, Middle East & Africa +33 (3) 88 20 8080****************************Asia Pacific *************************.com China +86 (21) 2306 1500Japan +81 (45) 277 7117Korea +82 (31) 601 2004India +91 (80) 67920890Rest of Asia +886 (2) 27602006 ext 2808Copyright © 2018 Sensata Technologies, Inc.Sensata Technologies, Inc. (“Sensata”) data sheets are solely intended to assist designers (“Buyers”) who are developing systems that incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible for using its independent analysis, evaluation and judgment in designing Buyer’s systems and products. Sensata data sheets have been created using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that specifically described in the published documentation for a particular data sheet. Sensata may make corrections, enhancements, improvements and other changes to its data sheets or components without notice.Buyers are authorized to use Sensata data sheets with the Sensata component(s) identified in each particular data sheet. HOWEVER, NO OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, AND NO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATA SHEETS ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATA SHEETS OR USE OF THE DATA SHEETS, EXPRESS, IMPLIED OR STATUTORY, INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD TO SENSATA DATA SHEETS OR USE THEREOF.All products are sold subject to Sensata’s terms and conditions of sale supplied at SENSATA ASSUMES NO LIABILITY FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER ACKNOWLEDGES AND AGREES THAT IT IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL, REGULATORY AND SAFETY-RELATED REQUIREMENTS CONCERNING ITS PRODUCTS, AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS, NOTWITHSTANDING ANY APPLICATIONS-RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA.Mailing Address: Sensata Technologies, Inc., 529 Pleasant Street, Attleboro, MA 02703, USA.Revised 2/16/18Dimensions in mm [Inch]DIMENSIONS GLOSSARY OF TERMSSensitivity - The slope of a best-fit straight line drawn through the output data. An LVDT is a ratiometric device and the sensitivity should be expressed as the ratio of the volts out (V1-V2 ), per volt in (VE or V1+V2 ), per degree of rotation (V/V/ degree).Accuracy - The maximum allowed deviation from the nominal output, when the output is taken per the above sensitivity definition. Typically specified as a ± percent of full scale.Linearity - The maximum deviation of any calibration point from a specified straight line. The error is usually expressed as a percentage of Full Scale output. The most commonly used line is the “Best Fit Straight Line” (BFSL).Tracking - The uniformity of performance between channels of multiple channel LVDTs. Each channel’s output is compared and the maximum difference between multiple channels is termed “tracking”. Tracking is normally expressed as a percentage of Full Scale.Crosstalk - The term used for multiple channel units to describe the voltage produced in the secondary of one channel by the primary excitation of another channel.Full Scale - The algebraic difference between the nominal outputs at the ends of the electrical stroke. (Ref. Instrument Society of America, ISA - S37.1-1975)Temperature Coefficient - The % change in the LVDT sensitivity over a temperature range. Usually defined as a percentage per 100°F max. Example: 0.25%/100°F.Typical Output (Calibrated Range)Electrical SchematicNominal Individual Output。
LVDT位移传感器介绍
LVDT位移传感器介绍简介: 把LVDT的电测线路采用微电子技术全部封装入LVDT的壳体内。
输入电压±9V~±15V,输出信号±5V或0~5V或0~10V或4~20mA的信号,可与四位半液晶数显表DB-6型多点变位计配合使用,该仪器便于携带和在无交流电源的环境中使用。
DC-LVDT具有较强的抗干扰能力,适宜遥测。
工作原理: LVDT位移传感器由同心分布在线圈骨架上一初级线圈P,二个级线圈S1和S2组成,线圈组件内有一个可自由移动的杆装磁芯(铁芯),当铁芯在线圈内移动时,改变了空间的磁场分布,从而改变了初次级线圈之间的互感量M,当初级线圈供给一定频率的交变电压时,次级线圈就产生了感应电动势,随着铁芯的位置不同,次级产生的感应电动势也不同,这样,就将铁芯的位移量变成了电压信号输出。
为了提高传感器灵敏度改善线性度,实际工作时是将两个次级线圈反串接,故两个次级线圈电压极性相反,于是,传感器的输出是两个次级线圈电压之差,其电压差值与位移量成线性关系。
原理图如下:参数名称测量范围(mm)线性度土(%)灵敏度(mV/mm)直流差动变压器外形尺寸(mm)重量(g)高精度直DA一0.5 ±0.5(0~1)0.05 10000 140×φ15 90 DA一1 ±1(0~2) 0.05 5000 140×φ15 95 DA一2 ±2(0~4) 0.05 2500 140×φ15 95使用注意事项:1、传感器测杆应与被测物垂直接触。
2、请别让活动的铁芯和测杆受大的侧向力而造成变形弯曲,否则会严重影响测杆的活动灵活性。
传感器不可敲打、跌落。
3、避免所有引线在焊接处和电缆的夹固处断线。
4、夹持传感器壳体时应避免松动,但也不可用力太大、太猛。
5、安装传感器时应调节(挪动)传感器的夹持位置,使其位移变化不超出测量范围,既通过观测位移读数,使位移在预定的变化内,信号输出不超出额定范围。
LVDT变送器说明书
RDP-LVDT 位移传感器说明书一、概述RDP-LVDT 位移传感器分为两个部分,第一部分为前置器部分,它与被测量物相连,根据被测物体位移,产生的频率幅值相应改变;第二部分为变送器单元,它把频率信号转化成两路1-5V 信号和两路4-20mA 信号。
二、功能指标RDP-LVDT 为英国产的五线制位移传感器,所采用的LVDT 行程一般为0-50mm 、0-100mm 和0-150mm 。
其出线图见下图:LVDT 位移传感器的变送器安装在DEH 机柜内,它接受两路24VDC 直流电源,形成冗余配置,一路失电不影响其正常工作,它的接线图和元件布置图见下图:LVDT 位移传感器的变送器大致可以分成三部分,电源部分(24VDC 转化成±15V ,两个绿色发光二极管分别表示±15V 是否工作正常);转换电路部分(提供LVDT 激励信号,把检测到的频率变化信号转化成1-5V 和4-20毫安信号);输入输出端子部分。
LVDT 位移传感器的变送器有四个可调电位器,分别是:调零电位器、调幅电位器、电流I 调整电位器和电流II 调整电位器。
LVDT 调整的顺序为:电压输出的调零调幅最后调整电流的输出(RDP-ACT 系列五线位移传感器的红线接输入的1端子、黄线接2端子、蓝线接3端子、绿线接4端子、黑线悬空)。
功能指标● 接受两路24VDC 容量0.3安培 ● RDP-ACT 系列五线位移传感器信号红黄LVDT出线图黑●输出1-5V两路●输出4-20mA两路●精度为0.1%三、LVDT零点满度的调整1、把LVDT位移传感器的红、黄、蓝、绿四线接到位移变送器输入端子的1、2、3、4端子上(陡河#3机调试在红黄线圈和蓝绿线圈里分别串接了一个220欧姆电阻,GV变送器中的R12由原来的10K改为17K),把LVDT位移传感器的黑线悬空;LVDT位移传感器到DEH机柜的接线应是屏蔽电缆,屏蔽线应和LVDT位移传感器出线的屏蔽线短接,并在DEH机柜内接地;GV2、GV4和IV1的屏蔽电缆有现场接地的现象。
Omega LD200系列经济型电源LVDT位移传感器说明书
Electrical Connections: Yellow/Black: Excitation Yellow/Red: Excitation Black: + Signal Red: Signal ground; connect blue and green together
* See for compatible instruments. Comes with complete operator’s manual. Ordering Example: LD200-5, LVDT displacement transducer with a range of ±5 mm (±0.20"), $205.
The LD200 Series AC-powered LVDT displacement transducers are ruggedly constructed, delivering high performance at a low cost. Along with a broad measurement range, from 1.25 to 10 mm (0.05 to 0.40"), these transducers have high resolution and repeatability.
*(50$1< ZZZRPHJDGH 'HFNHQSIURQQ *HUPDQ\
%(1(/8; ZZZRPHJDQO
More than 100,000 Products Available!
7HPSHUDWXUH
Calibrators, Connectors, General Test and Measurement Instruments, Handheld Instruments for Temperature Measurement, Ice Point References, Indicating Labels, Crayons, Cements and Lacquers, Infrared Temperature Measurement Instruments, Recorders, Relative Humidity Measurement Instruments, PT100 Probes, PT100 Elements, Temperature & Process Meters, Timers and Counters, Temperature and Process Controllers and Power Switching Devices, Thermistor Elements, Probes and Assemblies, Thermocouples, Thermowells and Head and Well Assemblies, Transmitters, Thermocouple Wire, RTD Probes
LVDT直线位移传感器资料
LVDT位移传感器编辑词条分享深圳市信为科技发展有限公司LVDT(Linear Variable Differential Transformer)是线性可变差动变压器缩写,属于直线位移传感器。
工作原理简单地说是铁芯可动变压器。
它由一个初级线圈,两个次级线圈,铁芯,线圈骨架,外壳等部件组成。
LVDT工作过程中,铁心的运动不能超出线圈的线性范围,否则将产生非线性值,因此所有的LVDT 均有一个线性范围。
初级线圈、次级线圈分布在线圈骨架上,线圈内部有一个可自由移动的杆状铁芯。
当铁芯处于中间位置时,两个次级线圈产生的感应电动势相等,这样输出电压为零;当铁芯在线圈内部移动并偏离中心位置时,两个线圈产生的感应电动势不等,有电压输出,其电压大小取决于位移量的大小。
为了提高传感器的灵敏度,改善传感器的线性度、增大传感器的线性范围,设计时将两个线圈反串相接、两个次级线圈的电压极性相反,LVDT输出的电压是两个次级线圈的电压之差,这个输出的电压值与铁芯的位移量成线性关系。
LVDT的工作电路称为调节电路或信号调节器。
一个典型的调节电路应包括稳压电路、正弦波发生器、解调器和一个放大器。
正弦波发生器应具有恒定的幅度和频率,且不受时间和温度的影响。
正弦可用文氏电桥产生,或用方波、阶梯波经滤波产生,或用其它合适的方法产生。
解调器可以是一个简单的二极管结构,当LVDT次级线圈的交流输出大于1VF.S时,使用简单二极管解调器;如果信号幅度低于此值,由于两个二极管正向电压的差异,会存在温度敏感问题,但对较大的信号电压,二极管误差的影响并不明显。
也可以用同步解调器,在同步解调器中,两个场效应管交替地开关,其定时与为初级供电的正弦波同步。
在初级与解调器开关间所需相移量取决于LVDT指标和LVDT与信号调节器间的导线长度。
正弦波发生器、解调器和放大电路已组合成商品化IC,使用这些器件将极大地简化LVDT信号调节器的设计。
最常用的有Philips出品的NE5521和ADI公司的AD598/698。
变送器调试说明书
智能压力变送器调试使用说明书1.按键功能概述1.1. 按键模式说明压力变送器表头上都有三个按键,分别为“M”、“S”、“Z”。
Z键用于进入提示数据设置界面和移位;S键用于进入数据设置界面、增加数字和数据保存;M键用于数据保存。
注:任何时候都可以按下“M“键,保存当前的设置数据。
2.按键功能2.1. 输入操作码2.1.1.操作码及对应功能现场使用按键组态时,LCD左下角“88”字符用于表示当前设置变量类型,也就是当前按键所执注:通过输入各个功能对应的操作码,可以快速进入对应功能。
例如输入“5”,直接进入设置阻尼功能。
例如输入“8”,直接进入设置输出特性。
2.1.2.操作码输入方法图例说明:1.均以当前采集值1 kPa,量程为0~100kPa为例2.2. 设置单位2.3. 设置量程下限假设原来的量程下限为0,新输入的量程下限为-40kPa。
2.4. 设置量程上限2.5. 设置阻尼2.6. 主变量调零(清零)功能2.7.设置输出特性2.8.零点迁移与量程迁移[调零和调满]2.9.显示变量设置液晶显示屏能显示“电流”、“百分比”、“主变量”三种变量的一种或交替显示其中的两种(间隔时间4秒)。
在实时正常显示状态,使用S键能更改两个显示变量,当两个显示变量设定为相同的参数,屏幕上固定显示一种变量;当两个显示变量设定为不同的参数时,屏幕上交替显示两种变量。
方法如下:按下“S”键,当前显示变量(如:电流)发生变化,循环显示“电流、百分比、主变量”,当所需要的显示变量(如:主变量)出现在屏幕上时,松开“S”键,即实现了将显示变量“电流”改为“主变量”。
更改显示变量过程中,左下角功能码显示“30”。
例子:假设当前显示变量为“电流”,需要设置为:交替显示“主变量”和“百分比”。
步骤:修改第一个显示变量:按下“S”键,液晶循环显示“电流、百分比、主变量”,当显示“主变量”时,松开“S”键,即可。
此时,液晶交替显示“主变量”和“电流”。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
RDP-LVDT 位移传感器说明书
一、概述
RDP-LVDT 位移传感器分为两个部分,第一部分为前置器部分,它与被测量物相连,根据被测物体位移,产生的频率幅值相应改变;第二部分为变送器单元,它把频率信号转化成两路1-5V 信号和两路4-20mA 信号。
二、功能指标
RDP-LVDT 为英国产的五线制位移传感器,所采用的LVDT 行程一般为0-50mm 、0-100mm 和0-150mm 。
其出线图见下图:
LVDT 位移传感器的变送器安装在DEH 机柜内,它接受两路24VDC 直流电源,形成冗余配置,一路失电不影响其正常工作,它的接线图和元件布置图见下图:
LVDT 位移传感器的变送器大致可以分成三部分,电源部分(24VDC 转化成±15V ,两个绿色发光二极管分别表示±15V 是否工作正常);转换电路部分(提供LVDT 激励信号,把检测到的频率变化信号转化成1-5V 和4-20毫安信号);输入输出端子部分。
LVDT 位移传感器的变送器有四个可调电位器,分别是:调零电位器、调幅电位器、电流I 调整电位器和电流II 调整电位器。
LVDT 调整的顺序为:电压输出的调零调幅最后调整电流的输出(RDP-ACT 系列五线位移传感器的红线接输入的1端子、黄线接2端子、蓝线接3端子、绿线接4端子、黑线悬空)。
功能指标
● 接受两路24VDC 容量0.3安培 ● RDP-ACT 系列五线位移传感器信号
红
黄
LVDT出线图
黑
●输出1-5V两路
●输出4-20mA两路
●精度为0.1%
三、LVDT零点满度的调整
1、把LVDT位移传感器的红、黄、蓝、绿四线接到位移变送器输入端子的1、
2、
3、4
端子上(陡河#3机调试在红黄线圈和蓝绿线圈里分别串接了一个220欧姆电阻,GV 变送器中的R12由原来的10K改为17K),把LVDT位移传感器的黑线悬空;LVDT 位移传感器到DEH机柜的接线应是屏蔽电缆,屏蔽线应和LVDT位移传感器出线的屏蔽线短接,并在DEH机柜内接地;GV2、GV4和IV1的屏蔽电缆有现场接地的现象。
2、把攻放板拔掉,在DEH机柜内用一号电池给每个MOG阀加电,在位移变送器的输
出端子上用四位半万用表电压档观察阀门由关到开的过程中,电压是否是增大的过程,如不是对调位移变送器输入端子的蓝绿接线;LVDT的调零:MOG阀不加电,调整W1电位器使OUT1输出为1.0XXV,MOG阀加电,该调门全开,调整W2电位器使OUT1输出为5V;再使MOG阀失电,调门全关,调整W1电位器使OUT1输出为1.0XXV,重新使MOG阀加电,该调门全开,调整W2电位器使OUT1输出为5V,反复几次这样调整使LVDT的零点为1.0XXV,满度为5V。
三线制LVDT 位移传感器说明书
一、概述
LVDT 位移传感器分为两个部分,第一部分为前置器部分,它与被测量物体相连,根据被测物体位移,产生的频率幅值相应改变;第二部分为变送器单元,它把频率信号转化成两路1-5V 信号和两路4-20mA 信号。
二、功能指标
三线制LVDT 位移传感器,所采用的LVDT 行程一般为0-50mm 、0-100mm 、0-150mm 和0-250mm 其出线图见下图:
LVDT 位移传感器的变送器安装在DEH 机柜内,它接受两路24VDC 直流电源,形成冗余配置,一路失电不影响其正常工作,它的接线图和元件布置图见下图:
LVDT 位移传感器的变送器大致可以分成三部分,电源部分(24VDC 转化成±15V ,两个绿色发光二极管分别表示±15V 是否工作正常);转换电路部分(提供LVDT 激励信号,把检测到的频率变化信号转化成1-5V 和4-20毫安信号);输入输出端子部分。
LVDT 位移传感器的变送器有四个可调电位器,分别是:调零电位器、调幅电位器、电流I 调整电位器和电流II 调整电位器。
LVDT 调整的顺序为:电压输出的调零调幅最后调整电流的输出(三线位移传感器的1线接输入的1端子、2线接2端子、3线接3端子)。
功能指标
● 接受两路24VDC 容量0.3安培 ● RDP-ACTII 系列三线位移传感器信号 ● 输出1-5V 两路
LVDT出线图
3
12
●输出4-20mA两路
●精度为0.1%
三、LVDT零点满度的调整
3、把LVDT位移传感器的1、2、3三线接到位移变送器输入端子的1、2、3端子上,
LVDT位移传感器到DEH机柜的接线应是屏蔽电缆,屏蔽线应和LVDT位移传感器出线的屏蔽线短接,并在DEH机柜内接地。
4、把攻放板拔掉,在DEH机柜内用一号电池给每个MOG阀加电,在位移变送器的输
出端子上用四位半万用表电压档观察阀门由关到开的过程中,电压是否是增大的过程,如不是对调位移变送器输入端子的1、3接线;LVDT的调零:MOG阀不加电,调整W1电位器使OUT1输出为1.0XXV,MOG阀加电,该调门全开,调整W2电
位器使OUT1输出为5V;再使MOG阀失电,调门全关,调整W1电位器使OUT1输出为1.0XXV,重新使MOG阀加电,该调门全开,调整W2电位器使OUT1输出
为5V,反复几次这样调整使LVDT的零点为1.0XXV,满度为5V,必须注意的是,LVDT零点要大于1伏,为1.0XX伏最好。
注意调整LVDT的零点满度时,现场一定有人监视阀门的实际行程,以便确认阀门全开全关的真实性。