NA系列低压智能电力电容器使用说明书
Magnum低压电路断路器的操作说明说明书
Remote latch check switch (LCS) forMagnum low voltage circuit breakersBE PERMITTED TO WORK ON THE EQUIPMENT (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION (3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO THE DISCONNECT POSITION. (4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION AND MECHANISM SPRINGS DISCHARGED.FAILURE TO FOLLOW THESE STEPS FOR ALLPROCEDURES DESCRIBED IN THIS INSTRUCTIONLEAFLET COULD RESULT IN DEATH, BODILY INJURY, OR PROPERTY DAMAGE.PRODUCT LABELS MUST BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES. • DISCONNECTING;• ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED;• VERIFY ISOLATION FROM THE SUPPLY;• EARTHING AND SHORT-CIRCUITING; AND;• COVERING OR PROVIDING BARRIERS TO ADJACENT LIVE PARTS.Section 1: General informationA latch check switch (LCS) indicates when the circuit breaker is “ready to close” (Figure 1). The External version used for remote indication consists of 1 Form C contact wired to the circuit breaker secondary contacts for integration into external control schemes.This product is intended for use in Magnum circuit breakers with PXR or Digitrip trip units.ote: N Wiring the LCS for remote indication directly in series with the SR accessory is not recommended as this will override the “anti-pump” feature.Required tools• 1/4-inch drive ratchet •10 mm socketKit parts identificationRefer to Figure 1 for visual identification of the contents of kit:Figure 1. Contents of kit.ote: N All images show a Magnum circuit breaker with a PXR trip unit unless stated otherwise. Some compo-nents, such as the trip unit, not shown for clarity.LCS (external version shown)2Instructional Leaflet IL2C12701Effective December 2021Remote latch check switch (LCS) for Magnum low voltage circuit breakersEATON Section 2: Installation of external remote LCSTo install the LCS, proceed with the following steps:Step 1: Remove the front cover by unscrewing the hex-head captive bolts (four for three-pole, six for four-pole) that join the cover to the breaker housing using a 10 mm 1/4-inch drive socket. Then hold the charge handle down at about a 45-degree angle to pull off the cover. Step 2: Place the appropriate label on the front cover nameplate space located under “Accessories”.Figure 2. Steps 1 and 2.Step 3: Remove the accessory (if installed) from the indicated position on the accessory tray by lifting its lock up and sliding the accessory toward the front of the breaker. Then lift accessory up and out of tray. Do not disconnect the wiring.Figure 3. Step 3.Step 4: Connect wires from LCS to the secondary connector, refer-ring to T able 1, in keeping with the wire markings. Terminal maps for the secondary connectors are located on top of the secondary connectors. Check that all wire terminals are secure by pulling gently. Then push the LCS into center slot in the accessory tray. Make sure the LCS is fully seated.Figure 4. Step 4 Magnum with Digitrip.Figure 5. Step 4 Magnum with PXR.Step 5: Reinstall any accessory that was removed in Step 2.Step 6: Test the installation.CHARGED. PUSH THE OFF BUTTON FIRST TO ENSURE THAT THE BREAKER IS NOT CLOSED. FAILURE TO FOLLOW THIS ACTION COULD RESULT IN A SERIOUS INJURY.With the breaker OPEN and DISCHARGED, push down on the trip lever platform (to its stop) and release.The LCS should not operate. This is indicated by the absence of an audible “click” from the switch.3Instructional Leaflet IL2C12701Effective December 2021Remote latch check switch (LCS) for Magnum low voltage circuit breakers EATON Now charge the breaker using the manual handle. When the breaker is fully charged, the trip lever will return to the latched (platform level) position. Repeat the above test by pushing the trip lever platform down and releasing it. An audible “click” from the switch should be heard.Figure 6. Step 6.Step 7: Reinstall the front cover. Push the CLOSE and then the OPEN pushbuttons to discharge all energy from the mechanism, leaving it in an OPEN and DISCHARGED status.Eaton1000 Eaton Boulevard Cleveland, OH 44122 United States © 2021 EatonAll Rights ReservedPrinted in USAPublication No. IL2C12701H02/ TBG 001545 December 2021Eaton is a registered trademark.All other trademarks are propertyof their respective owners.Remote latch check switch (LCS) for Magnum low voltage circuit breakersInstructional Leaflet IL2C12701 Effective December 2021Disclaimer of warranties andlimitation of liabilityThe information, recommendations, descriptions, and safety notations in this document are based on Eaton Corporation’s (“Eaton”) experience and judgment, and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted.Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALL Y SETOUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations, and descriptions contained herein.The information contained in this manual is subject to change without notice.。
JKWNA-9低压无功补偿控制器使用说明书(2015总线版、.
JKWNA-9低压无功补偿控制器使用说明书江苏南自通华电力自动化有限公司1产品简介1.1概述JKWNA-9低压无功补偿控制器和NA系列智能集成式电力电容补偿装置配套使用,具备采集并显示电测量数据,监测和显示智能电容器运行工况、投切状态,以及根据无功功率与目标功率因数自动控制投切电容器等功能。
1.2产品特点JKWNA-9低压无功补偿控制器通过通信总线连接NA系列智能集成式电力电容补偿装置;控制器采集电网电测数据,在显示智能电容器组运行情况的同时,可以直接根据当前的电测数据,对电容器组进行智能投切控制,以达到无功补偿的效果。
1.3外观尺寸2技术参数显示分辨率128×64,显示12点阵汉字输入测量RJ45方式接入智能电容器网络电源工作范围AC380V±30%功耗≤2W工作条件-10~55℃,相对湿度≤93%无腐蚀气体场所,海拔≤2000m 隔离耐压电源>2500V绝缘电阻≥2MΩ尺寸面框尺寸:120mm×120mm开孔尺寸:3使用说明JKWNA-9低压无功补偿控制器面板由产品名称及公司信息、液晶显示屏、操作按键组成。
下面对液晶显示屏显示内容和主要功能作简单说明:3.1主菜单液晶屏第1行从左到右依次显示:联网电容器数量、当前投切控制方式(自控/手控和软件版本号;当前所有联网电容器的投切状态以图形的方式直观显示在液晶屏上,同时显示投入到电网中总的补偿容量,显示界面如下:注:表示分补表示共补表示投入表示切除当前电容柜补偿电流界面如下:3.2运行工况显示开关故障、过压保护、过流保护、过温保护、过谐波保护的电容器信息。
使用和切换界面查看各种保护与故障,按键返回主菜单。
3.3设置参数设置参数CT变比(比值:0000目标功率因数:0.99无功算法时间:040设置现场的电流互感器变比,无功控制的目标功率因数和无功算法时间。
和切换参数数字的修改焦点,切换当前焦点的数字大小,进入参数修改“确认/取消”界面,进入参数修改“确认/取消”界面后,和切换“确认/取消”按钮,确定当前的按钮。
TDS_GL滤波式电力电容器技术说明书
低压电力电容器额定电压>产品额定电压>电源额定电压
4.2 产品的额定容量与低压电力电容器的额定容量 TDS(GL)系列滤波式低压电力电容组合电器由于其中电抗器的作用,使产品的额定容量与低压电力电 容器的额定容量不相同,二者的关系如下:
Qd
=
U d2Qc
(1
−
α
)U
2 c
式中: Qd ——产品的额定容量,kvar; U d ——产品的额定电压,V; Qc ——低压电力电容器的额定容量,kvar; U c ——低压电力电容器的额定电压,V; α ——电抗器感抗与电容器容抗的比值。
智能低压无功补偿控制器使用说明书
目录一.产品概述 (1)二.功能特点 (1)三.使用环境 (2)四.技术参数 (2)五.安装与接线 (2)六.操作与运行 (5)七.系统调试 (12)八.常见现象分析 (14)九.售后服务 (15)一.产品概述智能无功补偿控制器(以下简称控制器)是本公司在吸收了国内外多个无功自动补偿控制器技术的基础上研发出来的新一代产品,款式新,功能全,安装使用灵活,全中文液晶菜单,操作方便。
控制器具有RS-485通讯接口,与本公司生产的智能低压电力电容器配套使用,接线简洁,运行可靠。
二.功能特点1.参数设置功能1)过压值、欠压值、欠流值等保护定值的设置;2)延时时间、投入、切除门限等投切限值的设置;3)取样电流互感器变比的设置。
2.测量功能1)取样互感器极性自动判别,接入时无需考虑极性要求;2)配电电压、电流、功率因数、有功功率、无功功率测量。
3.控制功能1)自动、手动控制电容器的投切。
自动控制时,根据受控物理量-无功功率进行投切;2)容量相同的电容器按循坏投切方式工作,容量不同的电容器按无功缺额进行编码投切;3)最多可同时控制32台智能低压电力电容器。
4.保护功能配电系统过电压保护、过电压闭锁、欠电压保护、欠流保护、缺相保护。
5.信号功能1)各台电容器投运、退运状态信号显示,各台电容器容量信号显示,各台电容器温度信号显示;2)配电参数越限信号(过压、欠压等)显示;3)控制器本身或电容器故障显示。
三. 使用环境工作温度: -20℃-60℃ 相对湿度: ≤90%(20℃) 大气压力: 79.5-106.5kpa 海拔高度: ≤3000m无易燃易爆的介质存在,无导电尘埃及腐蚀性气体存在。
四. 技术参数额定电压: 交流50Hz ,380V ±20% 电流取样: ≤5A 额定频率: 50Hz ±5% 净重:约0.8kg五. 安装与接线1.安装在屏柜上开113*113mm 的方孔,将本产品从屏前推入方孔内,把配给的紧固件插入安装槽中,上紧即可固定在屏上。
电力电容器及无功补偿技术手册
1电力电容器及无功补偿技术手册沙舟编著目录前言第一章基本概念 (1)§1-1 交流电的能量转换 (1)§1-2 有功功率与无功功率 (2)§1-3 电容器的串联与并联 (3)§1-4 并联电容器的容量与损耗 (3)§1-5 并联电容器的无功补偿作用 (4)第二章并联电容器无功补偿的技术经济效益 (5)§2-1 无功补偿经济当量 (5)§2-2 最佳功率因数的确定 (7)§2-3 安装并联电容器改善电网电压质量 (8)§2-4 安装并联电容器降低线损 (11)§2-5 安装并联电容器释放发电和供电设备容量 (13)§2-6 安装并联电容器减少电费支出 (15)前言众所周知,供电质量主要决定于电压、频率和波形三个方面。
电网频率稳定决定于电网有功平衡,波形主要决定于网络和负荷的谐波,电压稳定则决定于无功平衡。
当然三者之间也具有一定的内在关系。
无功平衡决定于网络中无功的产生和消耗。
在系统中无功电源有同步发电机、同步调相机、电容器、电缆、输电线路电容、静止无功补偿装置和用户同步电动机,无功负荷则有电力变压器,输电线路电感和用户的感应电动机,各种感应式加热炉、电弧炉等。
为了满足系统中无功电力的需求,单靠发电机、调相机、电缆和输电线路电容是不够的,静补装置中也是采用电容器等。
因此电容器在系统的无功电源中占有相当比重,加之调相机为旋转设备。
建设投资大,运行维护费用高。
近年来世界各国都积极装设电容器,满足系统无功电力要求,维持电压稳定。
但各国主要是装设并联电容器,装串联电容器者较少,因此编者主要介绍并联电容器无功补偿技术,它还广泛应用于谐波滤波装置,动态无功补偿设备和电气化铁道无功补偿装置之中,因与电力系统谐波有关。
限于篇幅,准备在“谐波技术”中详述。
这里主要介绍一些无功补偿技术基础。
限于编者水平,加上时间仓促,不当之处难免,请读者批评指正。
智能电容器使用说明书(改)
0.45-10(7%)
450*130*370
180*2*140
0.45-7.5(7%) 450*130*370
180*2*140
三 元ቤተ መጻሕፍቲ ባይዱ器件特点
1. 监控单元
采用专用智能控制器及传感元器件,对用电系统及补偿支路和电容器内部的各种数据信息,进行
采集、计算、分析、判断,并发出电容器投、切及各种保护预警、动作等的操作指令。 2. 温度采集单元
0
FKZC 系列—智能电力电容器--使用说明书
诚挚地感谢您选用“沈阳市法克电气有限公司”的智能电容器产品。 请您在安装使用本产品之前详细的阅读本手册,以免造成误操作。 这将为您节约宝贵的时间。
特别声明:由于产品升级、版本更新,本手册所述内容可能无法完全涵盖。如有错误、遗漏等不
当之处,敬请各位用户谅解。
外型尺寸 L*W*H
325*130*420 325*130*390 325*130*390 325*130*390 325*130*390 325*130*390 325*130*390 325*130*390 325*130*390 325*130*340 325*130*340 325*130*340 325*130*340 325*130*340 325*130**330 325*130**330 325*130**330 325*130*390 325*130*390
采用温度传感器件对电容器内部温度进行采集,为监控单元判断电容器的运行状态提供依据。 3. 谐波保护采集单元
采用专用智能控制器取用系统电流互感器对系统的谐波电流及电容器工作电压数据进行采集,为
监控单元进行基波电压电流、谐波电压电流等参数的计算,进行谐波保护提供依据。
(UP-SC380)智能低压电容控制器使用说明书
UP-SC380智能电容控制器使用说明书(2014年1月版)恩联(北京)电气设备有限公司Union Power(Beijing) Electrical Equipment Co., Ltd.目录1. 概述 (3)2. 功能特性 (3)2.1 基本功能 (3)2.2 技术参数 (3)3. 外形结构 (5)4.端子接线 (6)4.1 智能电容控制器端子接线图 (6)4.2 端子接线说明 (6)5. 按键及显示 (7)5.1 面板及按键 (7)5.2 实时数据显示 (7)1. 概述智能电容控制器是一种与智能电容器配合使用的电力监控仪,它可以集中显示多组智能电容的投切状态,进行智能电容器投切测试,并且能够与DTU通信实现自动化功能。
该仪表可广泛应用于工矿企业、民用电力系统的配电装置及各类配电室、箱变、低压综合控制柜中,是配电自动化系统的系列产品之一。
本仪表符合《DL/T597-1996低压无功补偿控制器订货技术条件》等标准要求。
2. 功能特性2.1 基本功能智能电容控制器集配电变压器低压侧三相电气参数测量、记录、控制和通信等功能于一体,其主要功能包括:(1)实时显示电容的投切状态;(2)能够实现投切测试;(3)通信功能,上行与DTU通信,下行与智能电容通信;(4)参数集中设置。
2.2 技术参数(1) 工作电源:(85~265)VAC或(100~300)VDC(2) 通信功能:通信口具有RS-485通信方式。
通信规约:MODBUS通信规约。
波特率:(600~38400)bps 可选。
(3) 机械性能:外形尺寸:宽×高×厚:160mm×160mm×113.59mm。
重量:2.1kg。
(4) 运行环境:工作环境温度:-25℃~+75℃;相对运行湿度:20%~90%。
相对湿度<85%时采取特殊措施可运行在-35℃环境内。
耐受污秽等级IV级。
谐波含量〈20%。
海拔2000米及以下。
ANJKD19低压无功补偿智能控制器使用说明书(V1.1)A5
15s
-3-
武汉安科新能电力科技有限公司 三、操作方法 控制器上电后,默认进入自动运行状态。 自动运行状态 1 ESC 键:短按:回到第一界面;长按(2 秒): 进入状态选择界面 2 ▲键和▼键:向上或向下切换显示界面。 3 Enter 键:无效。 状态选择菜单 ① ESC 键:退出当前状态,回到自动运行状态。 ② ▲ 键和▼键:向上或向下选中不同的工作状态。 ③ Enter 键:系统确认并进入所选中的工作状态。 系统配置状态 在状态选择界面,选中“系统配置” ,Enter 进入参数查看状态。 参数查看状态 ① ESC 键:退出当前状态。 ② ▲键和▼键:选中上一个或者下一个参数。 ③ Enter 键:进入该选中参数的设置状态 在参数查看状态,选中某一个参数,Enter 进入该参数的设置状态。 参数设置状态 ① ESC 键:退出该参数的设置状态,回到查看状态。 ② ▲键:参数被选中的一位的数值加 1。 ③ ▼键:切换并选中设置参数值的下一位。 ④ Enter 键:保存当前参数设置值,回到参数查看状态。 手动投切状态 ① ESC 键:退出当前状态,返回到状态选择界面。 ② ▲键和▼键:选择上一组电容或者下一组电容。 ③ Enter 键:当电容处于切除状态时,短按则该组电容投入; 当电容处于投入状态时,短按则该组电容切除; 出厂设置状态 此状态由厂家设置,请勿随意操作。
测量物理量 电压 电流 功率因数 无功功率 温度
测量准确度 ≤±0.5%(在 80%~120%额定电压范围)
≤±1%(在 10%~110%额定电流范围) ≤±0.5% ≤±1% 0.125℃
5. 用户参数设置
参数名称 CT 变比 投入门限 切除门限
投切延时
分补组数 共补组数 温度保护上限 电压保护上限 电压保护下限 过流保护上限 电压谐波门限 电流谐波门限 电容容量设置
人民电器 RD-ZM型智能低压电容器 产品说明书
052RD-ZM 智能式无功补偿电容器是由智能测控单元、零投切复合开关、智能保护单元、两台(△型)或一台(F 型)低压自愈式电力电容器组成一个独立完整的智能补偿单元。
替代由智能无功控制器、熔丝(或微断)、晶闸管复合开关(或接触器)、热继电器、指示灯、低压电力电容器多种分散器件组装而成的自动无功补偿装置。
产品既可单台使用,也可多台组网构成补偿系统使用;既可三相补偿,也可三相和分相混合补偿。
智能电容器集电子技术、传感技术、网络技术及电器制造等先进技术,将传统无功补偿产品集成化、网络化、智能化。
改变了现有低压无功自动补偿设备的结构模式,大大提高了设备的可靠性及使用寿命,具有结构简洁、生产简易、成本降低、性能提高、维护简便的全面优点。
产品型号格式命名:表示企业代号;表示智能电容器;表示补偿电容器为共补接法,表示补偿电容器为分补接法;电容器电压表示电容器的额定电压。
如./就表示智能低压电容器,补偿电容器是三角形接法共补,额定电压补偿容量为。
R ”F”-R -0420,400V ,20KVar D ZM-G”DZMG -”产品概述选型指南主要技术参数智能电容器为模块化设计,组成模块有:①高品质电容器②智能测控模块③投切开关模块④线路保护模块高品质电容器。
采用目前先进的复合边缘加厚金属化膜的自愈式低压并联电容器。
具有重量轻、特性好、使用寿命长、损耗低、发热小、温升低等全面的优点。
□ 实现电压过零导通和电流过零切断,使智能系统在接通和断开的瞬间具有可控硅开关的优点,而在正常接通期间又具有接触器开关无功耗的优点。
其实现方法是:投入时是在电压过零瞬间可控硅先过零触点,稳定后再将磁保持继电器吸合导通;而切出时是先将磁保持继电器断开,可控硅延时过零断开,从而实现电流过零切除。
智能测控模块与线路保护模块采用单片机控制投切并智能监控可控硅、磁保持继电器以及输入电源和负载的运行状况,从而具备完善的保护功能:电压故障缺相保护:系统电压缺相供电时,开关拒绝闭合;接通后若出现缺相,则自动退投。
NA7XXL说明书(V4.0)
自动恢复
保护电路动作断开负载后,可以设定一个自动恢复次数(参数 F21)和间隔时间(参数 F22),例 如 F21=3,F22=5,则 5 分钟后重新接通负载,如果重新接通负载后仍有故障,则每隔 5 分钟再接通 一次,这样重复尝试 3 次,如果再不行则不再尝试,需人工恢复。
2
苏州新亚科技有限公司产品说明书
数码管在正常时显示三相平均电流(单位:A) ,可以按“选择() ”键切换显示 ABC 三相电 流。在告警状态,显示告警代码,代码含义如下表:
代码 OL. LAC OVL PHA 含义 溢出 欠载 过载 缺相 产生原因 电流超过量程(NA704L 的量程为 50A,NA708L 为 100A,NA712L 为 140A) 负载平均电流低于欠载电流 负载平均电流超过整定电流 缺相或三相电流严重不平衡
整定参 数类
F11 F12 F13 F14
自动恢 复类
F21 F22 F00
注意:设置参数操作需要专业人员进行,非专业人员请勿随意改变参数,否则将造成设备损坏 甚至火灾和人身伤害。
基本工作原理 电流检测
通过外接的电流互感器检测负载电流,所以被保护电机的三根相线必须分别穿过电流互感器的 三个小孔。
类别 代码 F10 参数名称 NA704L 欠载电流: NA708L NA712L NA704L 整定电流: NA708L NA712L 过载动作时间 缺相动作时间 欠载动作时间 自动恢复次数 自动恢复间隔时间 退出设置状态 设定范围 1.0 – 40.0 2 – 80 2 – 120 1.0 – 40.0 2 – 80 2 – 120 0.5 – 30.0 0.5 – 30.0 OFF 1 – 30 0 -- 10 1 -- 60 出厂设定 1.0 2 2 20.0 40 60 3.0 2.0 OFF 1 5 单位 A 控制器总会保持 F10<F11 的规则 A 秒 秒 分钟 次 分钟 OFF 表示不使用欠载功能 0 表示没有自动恢复 备注
电容器产品指南说明书
AP470NK500VAC AP1NK500VAC AP100NK500VAC AP2200NK500VAC AP1U5K500VAC AP2U2K500VACICW:Product guide:Radials:RNRT/RNRPFILM CAPACITORS Axials:AC Voltage ratedAX:Polypropylene250Vac ratedAP:Polypropylene500Vac&660Vac ratedPolypropylene axial wrap and end seal style capacitors offeringlow loss characteristics.Ideally suited to applications such asmains filters and where pulse performance is important.ICW:Product guide:Axials:AC Voltage rated:AX/APFILM CAPACITORS Full text descriptionBoth of these capacitors are constructed using the familiar‘wrap and end seal’method-wrapping the wound elements with heavy duty electrical tape which is wider than the elementand sealing the cavities formed at each end with epoxy resin.This style of manufacture resultsin a cost effective and volumetrically efficient component of the highest quality.The AX capacitors are suitable for pulse type circuits where high peak current handlingcapability is essential or at high frequency ac voltages where low loss is of prime consideration.The higher voltage handling capabilities of the AP range makes them ideally suited toapplications such as mains filtering and higher voltage pulse applications.Capacitance range AX:100nF to2µ2FAP:10nF to2µ2FT olerance±10%standard.Others by request Dissipation factor≤0.001@1KHz&20±3°CI nsulation resistance≥104MΩ-µF(C>330nF),≥3x104MΩ(C≤330nF)@250Vac for AX and500Vdcfor AP and20±3°CRated voltage AX:250VacAP:500and660VacPulse performance See table.Ratings assume linear changeto/from rated voltage T emperature range-55to+100°CEnvironmental category55/100/56to EN60068-1(IEC68-1)Proof voltage test 1.5x rated voltage for30s.Not to be repeated Solderability BS2011:Part2.1T(IEC68-2-20)Solder Globule Method of test T aVibration EN60068-2-6(IEC68-2-6)T est Fc10to500Hz0.75mm or98m/s2 Bump EN60068-2-29(IEC68-2-29)T est Eb390m/s21000±10bumpsT echnical detailsICW:Product guide:Axials:AC Voltage rated:AX/APFILM CAPACITORSCAP(µF) 0.01 0.015 0.022 0.033 0.047 0.0680.1 0.15 0.22 0.33 0.470.681.001.52.2AX:250Vac/400VdcAP:500Vac/1000VdcAP:660Vac/1500VdcSize chart:Axials:AX&APAX Range:T erminations are tinned copper clad steel with a minimum length of30mmICW :Product guide :Axials :AC Voltage rated :AX /APFILM CAPACITORSPulse performanceRated voltage (Vdc)Body length250V 500V 660V (mm)AXAPAP191502910080100465070Maximum rates of change of Voltage dV/dt (V/µSFigures quoted in the chart above assume linear charge/discharge to /from rated voltage.When applied voltage (V A )is less than the rated voltage (V R )the rating may be increased by a factor V R /V A .OutlinedimensionsICW:Product guide:Axials:AC Voltage rated:AX/APFILM CAPACITORSAX100nK250VAX2µ2K250VCap Value µF for C≥IµF nF for C<IµFT oleranceM=±20%K=±10%J=±5%G=±2%†F=±1%†RatedVoltage acAP150nJ 660VAP2µ2K500VCap ValueµF for C≥IµFnF for C<IµFT oleranceM=±20%K=±10%J=±5%G=±2%†F=±1%†Rated Voltage ac†subject to availabilityOrdering detailsContact detailsIndustrial Capacitors(Wrexham)LtdMiners Road Llay Wrexham North Wales LL120PJT elephone44(0)1978853805Facsimile44(0)1978853785 Web Email***************.ukAP470NK500VAC AP1NK500VAC AP100NK500VAC AP2200NK500VAC AP1U5K500VAC AP2U2K500VAC。
智能电容控制器说明书-A
智能电容控制器说明书-A3.运行工况界面运行工况里包含了配电电压、电流、功率因数、功率、电压各次谐波、电流各次谐波等各电参数的数值显示,以及测控仪与智能电容器的通信状况,通过“或”键切换界面查看各电参数以及测控仪与智能电容器的通信状况,按“”键返回到主菜单界面。
以下细分界面依次对各项进行介绍:(1)配电三相功率因数、电压、电流界面在使用过程中若出现过补偿或配电电流接线接反,则在上述界面中功率因数数值前显示‘-’,例如A相功率因数显示‘-0.960’,表示此时A相电容已过补偿或A相配电电流方向接反。
在使用过程中若出现过压或欠压现象,在上述界面中电压反显显示,例如A 相电压显示“”,表示此时A相电压已超过设定过压值。
(2)有功、无功、电容电流界面(3)通信界面测控仪与不同的智能电容器通讯,其显示的通信界面略有不同,如下图所示:图1图2图3图1为测控仪与三相式智能电容器或智能抑谐式电容器(双电容电抗)通信界面;图2为测控仪与三相式智能抑谐式电容器(单电容电抗)的通信界面;图3为测控仪与分相式智能电容器5 6P(KW) :实时的有功功率;Q(Kvar):系统当前过补偿或欠补偿的无功数值;C-I(A) :实时的电容器电流值。
的通信界面;“JH C1 C2”中“JH”表示三相式智能电容器的地址,“C1 C2”分别表示内部两组电容器的容量(如图所示“060 20.20”表示此三相式智能电容器地址为“60”,容量为20 Kvar +20Kvar)。
“JH C”中“JH”表示三相式智能抑谐式电容器(单电容电抗)的地址,“C”表示电容器的容量(如图所示“060 40”表示此三相式智能抑谐式电容器(单电容电抗)地址为“60”,容量为40 Kvar)。
“JH A B C”表示分相式智能电容器的地址及A、B、C三相容量(如图所示“06 6.6 6.6 6.6”表示此分相式智能电容器地址为6,电容器容量为20Kvar)。
智能电容器投入后,状态反显显示。
JKWNA-9低压无功补偿控制器使用说明书(2015总线版、适用智能电容器)V2.2
绝缘电阻 尺寸
≥2MΩ 面框尺寸: 120mm×120mm
开孔尺寸:
3 使用说明 JKWNA-9 低压无功补偿控制器面板由产品名称及公司信
息、液晶显示屏、操作按键组成。下面对液晶显示屏显示内容 和主要功能作简单说明:
3
JKWNA-9 低压无功补偿控制器使用说明书 3.1 主菜单
液晶屏第 1 行从左到右依次显示:联网电容器数量、当前 投切控制方式(自控/手控)和软件版本号;
切换投切方式,
进入方式修改“确认/取消”界
面。如果确认修改,液晶屏第 1 行中间的当前投切控制方式也
会相应改变。
3.5 菜单及菜单内容一览表
主菜单项 1 共 8 台 自控 1、采样数据 2、投切状态 3、运行工况
7
版本
JKWNA-9 低压无功补偿控制器使用说明书
4、设置参数
主菜单项 2
共 8 台 自控
键返回主菜单。 5
JKWNA-9 低压无功补偿控制器使用说明书 3.3 设置参数
设置参数 CT 变比(比值): 0000 目标功率因数: 0.99 无功算法时间: 040
设置现场的电流互感器变比,无功控制的目标功率因数和 无功算法时间。
和 切换参数数字的修改焦点, 切换当前
焦点的数字大小,
进入参数修改“确认/取消”界面,进
版本
5、投切方式
采样数据
总功率因数、总有功、总无功
三相电压、电流、功率因数
三相有功、无功
三相电压谐波、电流谐1)
电流谐波分次(3-5-7-9-11)
投切状态
所有电容器投切状态总览
运行工况
故障电容器信息…
过压电容器信息…
正泰NA1-2000~6300万能式断路器
行程开关、 微动开关、 脚踏开关
按钮、指示灯 转换开关
交流电机起动器
电动机保护器
电机
电焊机
电动机智能控制装置
正泰“大品质”
为客户提供值得信赖的产品和服务,正泰提出了“大品质”理念,将品质的控制和提升分解成科研体系、质量体系、销售服务体系和物流配 送体系四大板块,又视之为一个整体,并提高至战略层面,提出全面提升产品和服务品质的方法和策略。在坚持行之有效的质量检验制度的 基础上,强调“预防为主、持续改进”的思想。并将这一“大品质”管理流程导入到生产全过程中,精控生产每个环节,实现品质提升的一 体化作业。
N A 1 - 2 0 0 0 ~ 6 3 0 0万 能 式 断 路 器
N A 1 - 2 0 0 0 ~ 6 3 0 0万 能 式 断 路 器
德国 · 法兰克福
植根中国 服务全球
中国 · 杭州
中国 · 上海
中国 · 温州
恒久不变的品牌理念
正泰是中国工业电气领域公认的领先品牌 正泰经营理念是“为顾客创造价值,为员工谋求发展,为社会 承担责任” 正泰恒久不变的品牌精神是“让电尽其所能” 正泰产业涉及新能源、输配电设备、低压电器、仪器仪表、工 业自动化、建筑电器、汽车电器等领域
量≥2kVA,并且控制回路的最高工作电压为AC400V,辅助电路安装类别均为Ⅲ。
断路器应按照制造厂提供的使用说明书的安装要求进行安装,断路器垂直倾斜度不超过5°。 g.防护等级:正面IP20,其余面IP00
P-3
NA1-2000~6300万能式断路器
1.4 产品结构
故障跳闸指示 复位按钮 分闸按钮
2、环境温度超过+40℃时,按P5页2.3条款降容使用,允许最高环境温度为+65℃。
正泰BAGB智能电容器使用说明书
BAGB 智能组合式低电压并联电容器使用说明书一、产品概述BAGB 系列智能式低电压并联电容器(简称智能电容器)是 0.4KV 低压配电网高效节能、降低线损、提高功率因数和电能质量的新一代无功补偿设备。
它由智能测控单元,过零投切开关电路,线路保护单元,低压电力电容器构成。
主要适用于农网建设、小区楼宇建设等谐波含量在国家标准范围内的电力系统。
该产品改变了传统无功补偿装置体积庞大和笨重的结构模式,从而使新一代低压无功补偿设备具有补偿效果更好、体积更小、功耗更低、价格更廉、使用更加灵活、维护更加方便、使用寿命更长、可靠性更高的特点,适应了现代电网对无功补偿的更高要求。
二、功能特点2.1操作简便:只要外部接线正确,选择好从机的地址,通电后就可运行,不需要任何设置。
2.2多台串联简单:不管从机退出或挂接均不影响主机运行。
只要从机挂接,马上会被主机联机进入补偿列内,无需任何条件。
2.3抗干扰能力强:采用弱电与强电分离进线,防止一次线对二次信号线的干扰,极大地提高了整机的抗干扰能力。
2.4防止倒送无功危害:采用永久性故障跳闸保护装置。
一旦智能电容器如发生不可修复故障将自动跳闸,退出电网,防止因故障对电网的倒送无功危害,保证无功补偿系统的正常运行。
2.5投切涌流小:采用先进的过零投切技术,大大减少对电网的冲击。
2.6具有自检功能:可以模拟自动运行投切,电容柜生产厂通过自检功能即可做出厂试验,无需专用设备。
2.7保护功能齐全:除了有永久性故障跳闸保护装置外,还有过压、欠压、欠流、过温保护以及电容器内带防爆压力保护装置。
三、产品型号规格及安装尺寸3.1 型号说明3.2 常规产品型号规格补偿方式型号规格容量(kvar)额定电压(V)A×B×H 备注BAGB450-10(5+5)10 450 235 5+5BAGB450-20(10+10)20 450 300 10+10三相共补BAGB450-30(15+15)30 450 300 15+15 BAGB450-40(20+20)40 450 335 20+20 BAGB450-50(25+25)50 450 335 25+25 BAGB450-60(30+30)60 450 385 30+30 BAGB250-5 5 250 235 5 BAGB250-10 10 250 235 10分相补偿BAGB250-15 15 250 300 15 BAGB250-20 20 250 300 20BAGB250-30 30 250 335 30 3.3 简易型产品型号规格补偿方式型号规格容量(kvar)额定电压(V)高度备注BAGB450-5D 5 450 205BAGB450-10D 10 450 255 三相共补BAGB450-15D 15 450 285BAGB450-20D 20 450 315BAGB450-30D 30 450 360BAGB250-5D 5 250 255分相补偿BAGB250-10D 10 250 285 BAGB250-15D 15 250 315 BAGB250-20D 20 250 3603.4 抗谐波型产品型号规格(带电抗率为 7%和 14%)补偿方式型号规格容量(kvar)额定电压(V)B×A×H(mm)BAGB480-10/7 10 480 160×410×358BAGB480-15/7 15 480 160×410×358 三相共补BAGB480-20/7 20 480 160×410×358BAGB480-30/7 30 480 190×440×458BAGB480-40/7 40 480 190×440×458BAGB280-5/7 5 280 160×410×358BAGB280-10/7 10 280 160×410×358 分相补偿BAGB280-15/7 15 280 160×410×358 BAGB280-20/7 20 280 160×410×458BAGB280-30/7 30 280 190×440×458电抗率为14%的产品另报3.5 产品外形及安装尺寸常规产品的外形尺寸图如下:抗谐波型外形尺寸图如下:四、技术参数4.1输入电压:380V±20%4.2取样电流:≤5A4.3工作温度:-10℃~55℃4.4工作频率:50Hz±5%4.5电压畸变率:≤5%4.6相对湿度:最大95%4.7无有害气体,无导电性或爆炸性尘埃,无剧烈的机械振动五、接线端子排列与定义产品的接线端子分电源端子和测控联机端子,均置于产品的后部,三相补偿电源端子有“UA UB UC”,分相补偿电源端子有“UA UB UC UN”。
XJDBX系列智能集成低压滤波电力电容器说明书V1.2(20160420) -0615--用户手册
一、XJDB系列智能集成电力电容器的概述、分类 1.1 产品概述 1.1.1 产品简介
XJDB系列智能集成电力电容器是 0.4KV 低压配电网高效节能、降低线损、提高功率因数和电能质量的新一 代无功补偿设备。它由智能测控单元,同步开关电路,线路保护单 元,一台(△型,内分两路)或一台(Y型)低压电力电容器构成。替 代常规由智能控制器、熔丝、复合开关或机械式接触器、热继电器 、低压电力电容器、指示灯等散件在柜内和柜面由导线连接而组成 的自动无功补偿装置。改变了传统无功补偿装置体积庞大和笨重的 结构模式,从而使新一代低压无功补偿设备具有补偿效果更好,体 积更小,功耗更低,价格更廉,节约成本更多,使用更加灵活,维 护更加方便,使用寿命更长,可靠性更高的特点,适应了现代电网对 无功补偿的更高要求。
台
300
15
XJDBFX-300/20/14%
台
300
20
XJDBFX-300/25/14%
台
300
25
XJDBFX-300/30/14%
台
300
30
二、XJDB系列智能集成电力电容器的技术性能 2.1 技术性能
技术参数
电源电压
基本参数
电压波形 取样电流 测量频率
指标 AC 220V± 20%(分补电容) AC 380V± 20%(共补电容) 正弦波,总畸变率不大于 5%
自动运行状态共有3屏,操作上行或下行键可循环显示各项电网运行数据。 第一屏:显示实时电压、电流、功率因数、本组投切状态。
第二屏:显示有功功率、无功功率、频率,本组投切状态。
第三屏:显示本组电容电流、温度。
1.2 手动控制
手动功能只作用于补偿电容器的强制投切。 按“返回”键进入主菜单,操作 ▲ ▼键选择“手动控制”,操作“确认”键,进入手动状态。
ZFFJ系列智新新能型低压电力电容器使用说明书
台自愈式电力电容器等组成。 1. 小型断路器:主要起电源开关和短路保护作用 2. 电流电压采样电路:用精密电压电流互感器将电网电压、用电设备的总电流、电容器的 电流变换成一定比率的值提供给 CPU 进行 A/D 转换。 3. CPU 控制:主要作用是测量、无功补偿控制、通信及故障处理。测量电网电压、用电设 备的总电流,经运算得出用电设备的无功功率 Q 和功率因数 COSφ,经比较分析控制过零投 切装置,投入或切除电容器,达到无功自动补偿目的。电容器为等容量时按循环投切,先投 先切,非等容量按一定比列排列容量按编码方式投切。测量和监控电容器的电压、电流、温 度,当电容器电压、电流、温度出现异常时,切除或拒投电容器,发生不可修复故障时,触 发小型断路器跳闸切断智能电容器的总电源。 4. 过零投切装置
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
概述及产品特点1.概述NA系列低压智能电力电容器是以二台(△型)或一台(Y型)低压电力电容器为主体,采用微电子软硬件技术、微型传感技术、微型网络技术和电器制造技术等最新技术成果,将其智能化,实现低压电力无功补偿及使其能够可靠工作、使用方便的零投切、保护、测量、信号、联机等系列功能,是低压电力无功自动补偿技术的重大突破,可灵活使用于低压无功补偿的各种场合,改变了现有低压无功自动补偿设备的结构模式,具有结构简洁、生产简易、成本降低、性能提高、维护简便的多项优点。
2.产品特点1.实现了测控技术与同步开关完美的结合,无可控硅,触点间耐压高,同步投切,开关两端不存在电压叠加现象,控制投切开关的运动速度,提高寿命,对合闸相位进行跟踪修正,开关实现百万次的投切寿命。
与现有同类智能型电力电容器比较,具有高可靠、低故障、自身功耗小、长寿命等诸多优势。
2.合闸无涌流,实现电容器电压同步过零投入、电流同步过零切除,同步投切完全避免开关过电压,无过压击穿,无拉弧和重燃。
3.优化的补偿方式,各项控制保护功能完善,具备高档电能分析仪功能,功能齐全,性能好,还可配置多种外设,以满足不同的客户需求。
4.产品测量保护功能齐全,具备电容器体内温度、电网谐波含量、断相、三相不平衡等特殊保护。
5.产品可多台积木式使用,多台使用时自动产生主机,其余为从机,构成无功自动控制系统,个别故障从机自动退出,不影响其他机器工作。
主机故障自动退出,产生新的主机,组成新的系统工作,智能化程度极高。
6.单体电容器液晶屏显示产品工况及电气线路状况,人机对话简洁直观。
安全使用注意事项在安装、保养和使用我公司低压智能电力电容器时,请仔细阅读这些说明内容并谨慎操作,以便能够充分利用电容器的功能,延长本机的使用寿命。
对因使用不当造成的损失,自动化公司不承担责任。
1.请勿撞击!2.电源线的规格应满足用电负荷的要求30kVar及以上容量的电容器使用16平方的多芯铜导线。
请正确连接A、B、C相并可靠接地。
3.在保养电容器之前,请把电容器开关全部退掉。
4.电容器正常运行期间,如果接线错误,电容器本体可能带电,请勿触摸电容器金属部分,否则有触电可能。
》》安装智能电力电容器1.拆除外包装2.智能电容器概观3.安装要求4.产品安装示意5.电子图纸》》使用电力电容器》》现场检查1.接线正确性检查注意事项2.产品工作正常性检查注意事项》》产品常见错误与异常处理》》产品技术参数4 4 4 5 9 11 1215 15 16 18安装支架网络线冷压件控制器(选配)指示器(选配)说明书出厂检验报告CT(无控制器的情况)JIANGSU NICETOWN ELECTRIC POWER AUTOMATION CO.,LTD.NA 系列低压智能电力电容器请严格执行说明书上相关安装电容器的步骤,这样才能安全的使用本机。
1.拆除外包装将智能电容器的包装打开并检查智能电容器装运时是否损坏,同时检查下图中所有配件是否齐全,如果智能电容器在装运过程中损坏或者配件不全,请立即与我公司或经销商联系。
2.智能电容器概观安装智能电力电容器附件3.安装要求3.1 网络线的长度及分配使用情况3.2 常规安装线的粗细的选择及各种线的制作方法产品的电气接线有电源线、指示灯线(有控制器及状态指示器情况下则不需要)和接地线,以及接插件连接线。
①.电源线应根据产品总容量选择截面积合适的多芯铜导线总容量30Kvar或40Kvar的三相补偿产品应选用标准16mm ²截面积的多芯铜导线,其余规格的产品可选用标准10mm ²截面积的多芯铜导线。
电源线的线头制作如下图所示。
接电源线时必须拧紧螺丝,用劲试拉电源线,不脱出,证明十分牢固方可。
冷压接头一定要压紧,否则容易导致接口发热,影响产品的使用。
JIANGSU NICETOWN ELECTRIC POWER AUTOMATION CO.,LTD.NA 系列低压智能电力电容器②.指示灯线采用截面积为0.75mm²的多芯铜导线和冷压接头,按下图所示制作成连接线,然后接到产品上对应的绿色凤凰端子上(三相式产品是“HL1”、“HL2”,分相式产品是“HL1”、“HL2”、“HL3”),如下图所示。
外接指示灯根据需要,可不接。
冷压件接线位置(三相式为例)指示灯线的线头制作指示灯接线位置(三相式)JIANGSU NICETOWN ELECTRIC POWER AUTOMATION CO.,LTD.NA 系列低压智能电力电容器指示灯接线位置(分相式)注:产品使用中,三相式的HL1、HL2端子不可短接,分相式的HL1、HL2、HL3端子不能短接。
③.接地端子在产品后部(有标志),接地线应采用截面积不小于2.5mm²的单股铜导线,接地线连接应十分可靠,并且真正与外部接地端相连。
④.插件连接方式使用如上表1所示的插件线缆,使用插件线缆进行插件连接见下图所示。
JIANGSU NICETOWN ELECTRIC POWER AUTOMATION CO.,LTD.NA 系列低压智能电力电容器第一台产品直接连接二次CT 或用C 型线缆连接控制器,相邻两台电容器用A 型线缆连接,不同层的电容器用B 型线缆连接。
⑤.正确的电气连接接口方式注意:A 、B 、C 不可反接或者接错,同时三相线之间不能用扎线带捆扎⑥.电气距离及安装尺寸电容器之间距离,最小不能低于50mm⑦.如果通信不能完全,或插件线缆漏发,请联系本公司索取,不要自配网络线以免通信不能正常进行,影响产品的正常使用。
⑧.产品安装通电之前,请把拨动开关拨动到“调试”位;通电之后将拨动开关拨动到“工作”位(以三相式为例)。
JIANGSU NICETOWN ELECTRIC POWER AUTOMATION CO.,LTD.NA系列低压智能电力电容器4.产品安装示意4.1实物配置方式及实物连接方式举例(含控制器+状态指示器)组柜完成图样式JIANGSU NICETOWN ELECTRIC POWER AUTOMATION CO.,LTD.NA 系列低压智能电力电容器步骤三.电容器的安装4.2 GGD 柜体安装例(以含控制器+状态指示器为例)步骤一.柜体准备步骤二.母排、防雷装置及刀开关安装JIANGSU NICETOWN ELECTRIC POWER AUTOMATION CO.,LTD.NA系列低压智能电力电容器步骤四.控制器及状态指示器的安装步骤五.冷压件压好后,连接线的安装步骤六.完成安装5.电子图纸5.1 含控制器+状态指示器5.2 无控制器有指示灯的接法JIANGSU NICETOWN ELECTRIC POWER AUTOMATION CO.,LTD.NA 系列低压智能电力电容器NA系列低压智能电力电容器JIANGSU NICETOWN ELECTRIC POWER AUTOMATION CO.,LTD.使用电力电容器1.首次使用,检查接线有控制器及指示器接线结束并经校核接线,A、B、C电源线(分相A、B、C、N)方向正确,无反接或错接现象,控制器上A、B、C电流采样无误及U A、U B、U C、U N接线无误。
控制器上L与指示器上的L相连;控制器A与电容器第一台A之间接线无误;用万用表检查三相电源线各相之间及各相与外壳间是否短路,将面板上拨键拨向“调试”。
无控制器外接指示灯接线结束并经校核接线,A、B、C电源线(分相A、B、C、N)方向正确,无反接或错接现象。
分相补偿HL1、HL2、HL3的指示灯为220V,另一端接U N;三相补偿HL1、HL2的指示灯为380V,公共端接U B;此两处接线不能接错,请务必仔细检查。
2.上电前注意事项上电前面板上的键拨向“调试”端,所有微断都处于断开状态。
3.上电后参数及正确与否的判断及设定将面板上拨键拨向“调试”并合上微断开关,面板上右边二指示灯显示绿色,左边指示灯显示红色,并长闪,按键检查显示器,应如下:U AC(三相)或U A、U B、U C(分相)数值与实际配电电压一致;I B(三相)或I A、I B、I C与配电电流一致;COSΦ数值与实际配电功率因数一致;TC数值与实际电容器外壳温度相近(实际为电容器体内温度);I A、I B、I C为电容器工作电流,均为零。
多台产品使用时,插件线缆连接后,应自动联机形成队列。
如果某台产品未进入网络参与组网,“SL”界面会显示“SL-1”并且组网灯常亮为红色,其自成主机。
如果一个柜体内总共有10台机器,那么“SL”应显示“SL-10”,如显示数据不正确,请检查联机线和找到不参与组网的部分机器。
NA系列低压智能电力电容器JIANGSU NICETOWN ELECTRIC POWER AUTOMATION CO.,LTD.多台产品使用时,各台产品所显示的配电电压、电流、功率因数、无功功率等应基本相同。
4.调试电容器(参数设置)如想调试电容器并设置参数,把电容器拨动开关拨到“工作”档,长按电容器左键“确定”键,会显示出“ID 0XX”,如需其他界面,则按左键“确定”或右键“执行”键上下翻屏,找到需要编辑的界面,长按左键“确定”键进入编辑界面,按右键“执行”键并输入数据并用左键切换焦点,后长按左键“确定”退出编辑界面,然后长按右键“执行”完成设置并回到初始界面。
5.强投电容器用钳型电流表监视产品的三相进线电流。
电容器通电后,等待一分钟,把拨动开关拨向“调试”档,屏幕会显示“dby yes”界面,在三秒钟内按“执行”健,电容器执行强投命令。
面板上状态指示应顺次显示红色,同时按键检查显示器:IA、IB、IC显示电容器三相工作总电流,应与钳形电流表显示值一致。
如果三秒内不按,则电容器进入自动调试界面。
强投测试完成后,请把电容器拨动开关拨回到“工作”档,强投退出以便于电容器的自动控制。
6.自动控制试验进行自动控制试验时,应将面板上的拨键拨向“工作”档。
有外接控制器时,产品执行外接控制器的控制命令。
操作外接控制器使其发出控制电容器的投、退命令,产品应准确执行。
上图中L 是容量25Kvar 左右的三相电抗器,TA1是普通变比为100/5的电流互感器,TA2是产品配件穿心式二次电流互感器,QK是小型断路器,当QK合闸时,产品显示的功率因数在0.5左右,产品中的电容器即自动顺次投运,而当QK分闸时,产品中投运的电容器即顺次退运,由此确定产品自动控制功能正常与否。
注意:在进行检查和试验时,要考虑试验电源及其配电装置的容量,应大于投运被试产品的容量,否则会损坏试验电源及其配电装置。
无外接控制器时,产品将根据无功缺额进行完全的自动控制,投、退电容器使无功(功率因数)得到最佳补偿。
在具备调试设备的情况下,可以操作调试设备改变无功参数,产品应向补偿无功(减少无功)方向自动控制电容器的投、退。